Вы находитесь на странице: 1из 42

Chapman BDSP Plantroom & Riser Schedule

Heating Plantroom 5700 mm wide x 5300 mm deep x 3000 mm high (overall)



Chapman BDSP Plantroom & Riser Schedule

Plantroom
Reference Area Location Notes
Heating Plantroom 30 m Ground Floor -
Equipment
Reference Duty Selection
Sidestream Filter 1 No. sidestream filter(s) Sidestream filter, 600 mm wide x 600 mm deep x 2000 mm high,
100 kg, 100 kg
Enwamatic, TBC
www.enwamatic.com
Calorifiers 2 No. calorifiers @ 1340 litres/hr to meet 2000 litres/hr total capacity
Venting: unvented
Arrangement: vertical
Generic semi storage vertical, 440 litres/hr, 735 mm wide x 1060
mm deep x 2050 mm high, 850 kg
IMI Rycroft semi storage vertical, model MX440V, 1760 litres/hr
http://www.rycroft.com/
HRS semi storage vertical, model Aquasave AS515, 2500 litres/hr
http://www.hrs.co.uk/
Calorifiers heating pumps 1 No. duty / 1 No. standby @ 6.52 l/s, 100 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 196 mm wide x 381 mm deep x 519
mm high, 56 kg
Armstrong in-line vertical pump, model Starline50-150
www.armstrongpumps.com
Hot water circulating pump 1 No. duty @ 10.8 l/s, 100 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 255 mm wide x 635 mm deep x 753
mm high, 120 kg
Armstrong in-line vertical pump, model Starline100-200
www.armstrongpumps.com
Calorifiers expansion vessels 2 No. expansion vessels
3350 litres system volume
3.00 bar g feed pressure
3.55 bar g final pressure
75C maximum system temperature
0% glycol
370 litres expansion volume
Generic expansion vessel, 500 litres, 581 kg
Rycroft expansion vessel, model EXP500V, 500 litres
http://www.rycroft.com/
Smedegaard expansion vessel, model Type 2 500, 500 litres
http://www.smedegaard.com/
Ground energy Storage Pump 1 No. duty / 1 No. standby @ 0 l/s, 180 kPa
Pump type: in-line vertical
Pump arrangement: single
Pump fluid: water
Generic in-line vertical pump, 131 mm wide x 285 mm deep x 446
mm high, 21 kg
Armstrong in-line vertical pump, model Starline32-120
www.armstrongpumps.com
Micro CHP 5 kW 1 No. micro chp(s) Micro chp, 600 mm wide x 600 mm deep x 900 mm high, 100 kg,
100 kg
Chapman BDSP Plantroom & Riser Schedule

Micro CHP 5 kW 1 No. micro chp(s) Micro chp, 600 mm wide x 600 mm deep x 900 mm high, 100 kg,
100 kg
MCC 200 Amp incomer, 5 starters
415 V, TP&N, 50 Hz
Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm high
ABB MCC, model MNS
http://www.abb.co.uk/
Eaton Moeller MCC, model Modan
http://www.moeller.net/en/index.jsp
Electrical board 100 Amp incomer, 12 ways
Type: MCB
415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
wide x 150 mm deep x 885 mm high, 28 kg
Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomer
http://www.moeller.co.uk/
MEM mcb electrical board, model EBM121, 12 way, 125 Amp
incomer
http://www.eaton.com/uk
Heating pressurisation
unit(upper floors)
1 No. pressurisation unit
9000 litres system volume
8.0 bar g maximum working pressure
1.6 bar g maximum system pressure
60C maximum system temperature
0% glycol
Pressurisation unit types: standard, compressor
Generic standard pressurisation unit, 1170 mm wide x 800 mm deep
x 1660 mm high, 802 kg
Hoval standard pressurisation unit, model PressVal Micron SM600,
600 litres
http://www.hoval.co.uk/
Boilers vents Vent type: Natural high level, natural low level
High level vents to provide 0 m/s ventilation air exhaust
Low level vents to provide 0 m/s combustion and ventilation air
intake
(Based on BS6644, BS5410-2 and manufacturer recommendations)
1 No. generic vent at high level, 200 mm wide x 100 mm high, 50 %
free area
1 No. generic vent at low level, 200 mm wide x 100 mm high, 50 %
free area

Chapman BDSP Plantroom & Riser Schedule

Auditorium AHU 8800 mm wide x 3500 mm deep x 2900 mm high

Chapman BDSP Plantroom & Riser Schedule

Plantroom
Reference Area Location Notes
Auditorium AHU 30 m Ground Floor -
Equipment
Reference Duty Selection
Basement AHU Air flow 3 m/s
Configuration: stacked, intake bottom
Maximum velocity 2.2 m/s
Supply components:
- Louvre
- Attenuator (600 mm)
- Bag filter (long)
- Access (short)
- Thermal wheel
- Thermal wheel
- Access (short)
- Fan (backward curved)
- Access (short)
- Humidifier (steam)
- Attenuator (600 mm)
- Connection
Extract components:
- Louvre
- Attenuator (600 mm)
- Access (short)
- Thermal wheel
- Heating coil (2 row)
- Access (short)
- Thermal wheel
- Access (short)
- Humidifier (steam)
- Fan (backward curved)
- Panel filter
- Access (short)
- Attenuator (600 mm)
- Connection
Generic modular AHU, SFP 1.9 W/l/s (estimated), 7600 mm wide x
1404 mm deep x 2748 mm high, 3040 kg
Flakt Woods modular AHU, model EU40
http://www.flaktwoods.com/products/air-handling-units/
Chapman BDSP Plantroom & Riser Schedule

Main (option!) AHU 11300 mm wide x 8500 mm deep x 5400 mm high

Chapman BDSP Plantroom & Riser Schedule

Plantroom
Reference Area Location Notes
Main AHU 96 m Ground Floor -
Equipment
Reference Duty Selection
Basement AHU Air flow 8.5 m/s
Configuration: stacked, intake bottom
Maximum velocity 2.2 m/s
Supply components:
- Louvre
- Attenuator (600 mm)
- Bag filter (long)
- Access (short)
- Thermal wheel
- Thermal wheel
- Access (short)
- Fan (backward curved)
- Access (short)
- Humidifier (steam)
- Attenuator (600 mm)
- Connection
Extract components:
- Louvre
- Attenuator (600 mm)
- Access (short)
- Thermal wheel
- Heating coil (2 row)
- Access (short)
- Thermal wheel
- Access (short)
- Humidifier (steam)
- Access (short)
- Fan (backward curved)
- Panel filter
- Attenuator (600 mm)
- Connection
Generic modular AHU, SFP 1.8 W/l/s (estimated), 10050 mm wide x
2650 mm deep x 4100 mm high, 9630 kg
Flakt Woods modular AHU, model EU62
http://www.flaktwoods.com/products/air-handling-units/
Chapman BDSP Plantroom & Riser Schedule

Basement AHU Air flow 8.5 m/s
Configuration: stacked, intake bottom
Maximum velocity 2.2 m/s
Supply components:
- Louvre
- Attenuator (600 mm)
- Bag filter (long)
- Access (short)
- Thermal wheel
- Thermal wheel
- Access (short)
- Fan (backward curved)
- Access (short)
- Humidifier (steam)
- Attenuator (600 mm)
- Connection
Extract components:
- Louvre
- Attenuator (600 mm)
- Access (short)
- Thermal wheel
- Heating coil (2 row)
- Access (short)
- Thermal wheel
- Access (short)
- Humidifier (steam)
- Access (short)
- Fan (backward curved)
- Panel filter
- Attenuator (600 mm)
- Connection
Generic modular AHU, SFP 1.8 W/l/s (estimated), 10050 mm wide x
2650 mm deep x 4100 mm high, 9630 kg
Flakt Woods modular AHU, model EU62
http://www.flaktwoods.com/products/air-handling-units/

Chapman BDSP Plantroom & Riser Schedule

HV Plantroom 7100 mm wide x 4900 mm deep x 3400 mm high (overall)

Chapman BDSP Plantroom & Riser Schedule

Plantroom
Reference Area Location Notes
HV Plantroom 35 m Ground Floor -
Equipment
Reference Duty Selection
RMU Rating 200 Amps
12000 V, TP&N, 50 Hz
Generic RMU, 771 mm wide x 765 mm deep x 1510 mm high, 300
kg
ABB RMU, model SafeRing
http://www.abb.com/
Schneider RMU, model Ringmaster RN2
http://www.schneider-electric.co.uk/
Minimum connection space above: 600 mm
HV switchpanel 12000 V, TP&N, 50 Hz
Module type: withdrawable
Modules:
- Incomer
- Bus section
- Feeder
Future expansion 25%
Note: For some manufacturers VTs are integral to other components
Generic HV switchpanel, 2600 mm wide x 1550 mm deep x 2300
mm high
ABB HV switchpanel, model Unigear ZS1
http://www.abb.com/
Schneider HV switchpanel, model MCSet
http://www.schneider-electric.co.uk/
Minimum connection space above: 600 mm
Chapman BDSP Plantroom & Riser Schedule

LV Plantroom 6000 mm wide x 3500 mm deep x 3000 mm high (overall)
Plantroom
Reference Area Location Notes
LV Plantroom 21 m Ground Floor -
Equipment
Reference Duty Selection
LV Board 1 No. lv board(s) Lv board, 4000 mm wide x 1200 mm deep x 600 mm high, 100 kg,
100 kg

Chapman BDSP Plantroom & Riser Schedule

Life Safety LV Plantroom 6000 mm wide x 3500 mm deep x 3000 mm high (overall)
Plantroom
Reference Area Location Notes
Life Safety LV Plantroom 21 m Ground Floor -
Equipment
Reference Duty Selection
LV Board 1 No. lv board(s) Lv board, 4000 mm wide x 1200 mm deep x 600 mm high, 100 kg,
100 kg

Chapman BDSP Plantroom & Riser Schedule

Generators Plantroom 9100 mm wide x 4200 mm deep x 4200 mm high (overall)

Chapman BDSP Plantroom & Riser Schedule

Plantroom
Reference Area Location Notes
Generators Plantroom 38 m Ground floor -
Equipment
Reference Duty Selection
LV generators board 1 No. incomer
1 No. feeder
415 V, TP&N, 50 Hz
Access: front
Generic generators LV switchboard, 2650 mm wide x 655 mm deep
x 2429 mm high
GE Power Controls generators LV switchboard, model System 4
http://www.ge.com/
Eaton generators LV switchboard, model Bill Classic Form 4
http://www.eaton.com/
Minimum connection space above: 600 mm
Generators 1 No. generators @ 400 kVA
415 V, TP&N, 50 Hz
Generic diesel generator, 400 kVA, 3500 mm wide x 1150 mm
deep x 2158 mm high, 3700 kg
Broadcrown diesel generator, model BCC 440-50 E2, 440 kVA,
Emissions compliance EU Stage 2
http://www.broadcrown.com/
FG Wilson diesel generator, model P350P4, 400 kVA, Emissions
compliance EU Stage 2
http://www.fgwilson.com/
Day tanks 1 No. day tanks @ 8 hours storage
Generator fuel tank capacity : 650 litres
Day tank capacity (nett): 38 litres
Generic day tank , 1364 litres, 1750 mm wide x 1170 mm deep x
1250 mm high
Joseph Ash day tank, model D01, 1364 litres
http://www.jaenvirotanks.com/
Blake day tank, model TEBU FO 1000, 1000 litres
http://www.blakegroup.co.uk/

Chapman BDSP Plantroom & Riser Schedule

Gas Meter Plantroom 1200 mm wide x 2000 mm deep x 2500 mm high (overall)

Plantroom
Reference Area Location Notes
Gas Meter Plantroom 3 m Ground Floor -
Equipment
Reference Duty Selection
Gas Meter 1 No. gas meter(s) Gas meter, 800 mm wide x 480 mm deep x 600 mm high, 100 kg,
100 kg

Chapman BDSP Plantroom & Riser Schedule

Telecoms Plantroom 4000 mm wide x 2000 mm deep x 2500 mm high (overall)
Plantroom
Reference Area Location Notes
Telecoms Plantroom 8 m Ground Floor -
Equipment
Reference Duty Selection
Copper Rack 1 No. rack(s) Rack, 2000 mm wide x 500 mm deep x 1600 mm high, 100 kg, 100
kg

Chapman BDSP Plantroom & Riser Schedule

Transformers Plantroom 5200 mm wide x 4300 mm deep x 3500 mm high (overall)

Chapman BDSP Plantroom & Riser Schedule

Plantroom
Reference Area Location Notes
Transformers Plantroom 22 m Ground Floor -
Equipment
Reference Duty Selection
Transformers supply duct 0.82 m/s @ 10.0 m/s maximum, 1.0 Pa/m maximum
Maximum aspect ratio: 4.0
Insulation: none
(Air flow requirement based on transformers losses)
500 mm wide x 300 mm deep
No insulation
Transformers 1 No. @ 800 kVA
HV 12000 V, LV 415 V, TP&N, 50 Hz
Transformer type: dry
Derating factor: 1.25
Generic dry transformer, 1000 kVA, 2000 mm wide x 1210 mm deep
x 2400 mm high, 2870 kg
ABB dry transformer, model Cast resin 1000, 1000 kVA
http://www.abb.com/
Schneider dry transformer, model Cast Resin 1000, 1000 kVA
http://www.schneider-electric.co.uk/
Minimum connection space above: 600 mm
Transformers extract duct 0.82 m/s @ 10.0 m/s maximum, 1.0 Pa/m maximum
Maximum aspect ratio: 4.0
Insulation: none
(Air flow requirement based on transformers losses)
500 mm wide x 300 mm deep
No insulation

Chapman BDSP Plantroom & Riser Schedule

Fire Fighting Riser 2 2275 mm wide x 650 mm deep x 4000 mm high (overall)
Riser
Reference Area Location Notes
Fire Fighting Riser 2 1.5 m Fire Fighting Core2 Sprinkler valves and wet riser valves may be provided in one of the
two riser only.
Equipment
Reference Duty Selection
Dry riser 1 No. dry riser @ 100 mm diameter 100 mm diameter riser pipe
Cabinet 510 mm wide x 325 mm deep x 720 mm high

Chapman BDSP Plantroom & Riser Schedule

Mechanical Riser 1 3125 mm wide x 450 mm deep x 4000 mm high

Riser
Reference Area Location Notes
Mechanical Riser 1 1.4 m Core 1 To serve the floors of the tower and the roof condensers
Equipment
Reference Duty Selection
LPHW F&R 400 kW @ 3.0 m/s maximum, 240 Pa/m maximum
Pipe configuration: flow and return
Insulation: mineral wool (e=0.05), heating water 75C, internal
100 mm diameter
60 mm mineral wool (e=0.05) insulation
CHW F&R 600 kW @ 3.0 m/s maximum, 240 Pa/m maximum
Pipe configuration: flow and return
Insulation: mineral wool (e=0.05), chilled water 5C, internal
125 mm diameter
60 mm mineral wool (e=0.05) insulation
Condensate 54 mm diameter
Pipe configuration: single
Insulation: none
54 mm diameter
No insulation
VP (SVP) 54 mm diameter
Pipe configuration: single
Insulation: none
54 mm diameter
No insulation
RWP 150 mm diameter
Pipe configuration: single
Insulation: none
150 mm diameter
No insulation
Condenser Water 150 mm diameter
Pipe configuration: flow and return
Insulation: mineral wool (e=0.05), chilled water 5C, internal
150 mm diameter
60 mm mineral wool (e=0.05) insulation
24/7 cooling 150 kW @ 3.0 m/s maximum, 240 Pa/m maximum 80 mm diameter
Chapman BDSP Plantroom & Riser Schedule

Pipe configuration: flow and return
Insulation: mineral wool (e=0.05), chilled water 5C, internal
50 mm mineral wool (e=0.05) insulation

Chapman BDSP Plantroom & Riser Schedule

Public Health Risers 1 2475 mm wide x 525 mm deep x 4000 mm high
Riser
Reference Area Location Notes
Public Health Risers 1 1.3 m WC Riser core 1 To serve WC's
Prefab (100 mm frame included in dimensions)
Equipment
Reference Duty Selection
MWS 54 mm diameter
Pipe configuration: single
Insulation: none
54 mm diameter
No insulation
BCWS 54 mm diameter
Pipe configuration: single
Insulation: none
54 mm diameter
No insulation
HWS F 54 mm diameter
Pipe configuration: single
Insulation: mineral wool (e=0.05), hot water 60C, internal
54 mm diameter
50 mm mineral wool (e=0.05) insulation
HWS R 28 mm diameter
Pipe configuration: single
Insulation: mineral wool (e=0.05), hot water 60C, internal
28 mm diameter
40 mm mineral wool (e=0.05) insulation
RWP 150 mm diameter
Pipe configuration: single
Insulation: none
150 mm diameter
No insulation
SVP 100 mm diameter 100 mm diameter
Chapman BDSP Plantroom & Riser Schedule

Pipe configuration: single
Insulation: none
No insulation
VP (SVP) 110 mm diameter
Pipe configuration: single
Insulation: none
110 mm diameter
No insulation
VP (interceptor) 100 mm diameter
Pipe configuration: single
Insulation: none
100 mm diameter
No insulation

Chapman BDSP Plantroom & Riser Schedule

WC Extract 800 mm wide x 825 mm deep x 4000 mm high
Riser
Reference Area Location Notes
WC Extract 0.7 m WC Riser -
Equipment
Reference Duty Selection
Extract duct 1.80 m/s @ 7.5 m/s maximum, 1.0 Pa/m maximum
Maximum aspect ratio: 3.0
Insulation: none
600 mm wide x 500 mm deep
No insulation
Chapman BDSP Plantroom & Riser Schedule

MER Room 5900 mm wide x 4200 mm deep x 3400 mm high (overall)

Chapman BDSP Plantroom & Riser Schedule

Plantroom
Reference Area Location Notes
MER Room 25 m Ground Floor -
Equipment
Reference Duty Selection
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack, Rack
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack, Rack
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack
Battery Unit 1 No. battery unit(s) Battery unit, 800 mm wide x 1000 mm deep x 2200 mm high, 100
kg, 100 kg
AC Unit 1 No. ac unit(s) Ac unit, 1200 mm wide x 800 mm deep x 2000 mm high, 500 kg,
500 kg
AC Unit 1 No. ac unit(s) Ac unit, 1200 mm wide x 800 mm deep x 2000 mm high, 500 kg,
500 kg
Electrical board 160 Amp incomer, 12 ways
Type: MCCB
415 V, TP&N, 50 Hz
Generic mccb electrical board, 12 way, 400 Amp incomer, 900 mm
wide x 230 mm deep x 1605 mm high, 168 kg
Moeller mccb electrical board, model PB12-400, 12 way, 400 Amp
incomer
http://www.moeller.co.uk/
MEM mccb electrical board, model PBJG1240M, 12 way, 400 Amp
incomer
http://www.eaton.com/uk
UPS 1 No. ups(s) Ups, 800 mm wide x 1000 mm deep x 2200 mm high, 100 kg, 100
kg
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
rack
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
rack
Chapman BDSP Plantroom & Riser Schedule

IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
rack

Chapman BDSP Plantroom & Riser Schedule

Security Room 5600 mm wide x 3600 mm deep x 3700 mm high (overall)

Chapman BDSP Plantroom & Riser Schedule

Plantroom
Reference Area Location Notes
Security Room 20 m Ground Floor
Equipment
Reference Duty Selection
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack, Rack
IT Rack Copy 1 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack, Rack
IT Rack Copy 2 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack
Desk 1 No. desk(s) Desk, 1800 mm wide x 850 mm deep x 850 mm high, 100 kg, 100
kg
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 1200 mm wide x 250 mm deep x 400 mm high, 30
kg, 30 kg
Desk 1 No. desk(s) Desk, 1800 mm wide x 850 mm deep x 850 mm high, 100 kg, 100
kg
Electrical board 100 Amp incomer, 12 ways
Type: MCB
415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
wide x 150 mm deep x 885 mm high, 28 kg
Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomer
http://www.moeller.co.uk/
MEM mcb electrical board, model EBM121, 12 way, 125 Amp
incomer
http://www.eaton.com/uk
Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,
100 kg
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 1200 mm wide x 250 mm deep x 400 mm high, 30
kg, 30 kg

Chapman BDSP Plantroom & Riser Schedule

AV Room 2900 mm wide x 2300 mm deep x 3700 mm high (overall)

Chapman BDSP Plantroom & Riser Schedule

Plantroom
Reference Area Location Notes
AV Room 7 m Ground Floor
Equipment
Reference Duty Selection
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100
kg
Rack, Rack
Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,
100 kg
Desk 1 No. desk(s) Desk, 1200 mm wide x 750 mm deep x 850 mm high, 100 kg, 100
kg
Electrical board 100 Amp incomer, 12 ways
Type: MCB
415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
wide x 150 mm deep x 885 mm high, 28 kg
Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomer
http://www.moeller.co.uk/
MEM mcb electrical board, model EBM121, 12 way, 125 Amp
incomer
http://www.eaton.com/uk
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg,
30 kg
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg,
30 kg

Chapman BDSP Plantroom & Riser Schedule

BEMS and Maintenance Room 3600 mm wide x 2300 mm deep x 3700 mm high (overall)

Chapman BDSP Plantroom & Riser Schedule

Plantroom
Reference Area Location Notes
BEMS and Maintenance Room 9 m Ground Floor
Equipment
Reference Duty Selection
Desk 1 No. desk(s) Desk, 1800 mm wide x 750 mm deep x 850 mm high, 100 kg, 100
kg
Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,
100 kg
AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg,
30 kg
Electrical board 100 Amp incomer, 12 ways
Type: MCB
415 V, TP&N, 50 Hz
Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm
wide x 150 mm deep x 885 mm high, 28 kg
Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp
incomer
http://www.moeller.co.uk/
MEM mcb electrical board, model EBM121, 12 way, 125 Amp
incomer
http://www.eaton.com/uk
Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,
100 kg
Locker2 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,
100 kg

Chapman BDSP Plantroom & Riser Schedule

Ventilation distributed fans 9100 mm wide x 8300 mm deep x 1000 mm high (overall)

Chapman BDSP Plantroom & Riser Schedule

Plantroom
Reference Area Location Notes
Ventilation distributed fans 76 m Every floor -
Equipment
Reference Duty Selection
Floor void unit (approx 4No per
floor)
1 No. floor void unit (s) Floor void unit , 1900 mm wide x 1600 mm deep x 600 mm high,
100 kg, 100 kg
Nuaire , Xbober XB55
www.nuaire.co.uk
Floor void unit (approx 4No per
floor) Copy 1
1 No. floor void unit (s) Floor void unit , 1900 mm wide x 1600 mm deep x 600 mm high,
100 kg, 100 kg
Nuaire , Xbober XB55
www.nuaire.co.uk
Floor void unit (approx 4No per
floor) Copy 2
1 No. floor void unit (s) Floor void unit , 1900 mm wide x 1600 mm deep x 600 mm high,
100 kg, 100 kg
Nuaire , Xbober XB55
www.nuaire.co.uk
Floor void unit (approx 4No per
floor) Copy 3
1 No. floor void unit (s) Floor void unit , 1900 mm wide x 1600 mm deep x 600 mm high,
100 kg, 100 kg
Nuaire , Xbober XB55
www.nuaire.co.uk

Chapman BDSP Plantroom & Riser Schedule

Satellite 4000 mm wide x 2200 mm deep x 1800 mm high (overall)

Plantroom
Reference Area Location Notes
Satellite 9 m Roof -
Equipment
Reference Duty Selection
SATELLITE DISH 1 No. satellite dish(s) Satellite dish, 1200 mm wide x 1200 mm deep x 1200 mm high, 100
kg, 100 kg
SATELLITE DISH 1 1 No. satellite dish(s) Satellite dish, 1200 mm wide x 1200 mm deep x 1200 mm high, 100
kg, 100 kg

Chapman BDSP Plantroom & Riser Schedule

Computer AC Units 4100 mm wide x 2200 mm deep x 1200 mm high
Plantroom
Reference Area Location Notes
Computer AC Units 9 m Roof -
Equipment
Reference Duty Selection
Computer Room AC units 2 No. condensers @ 10 kW
Condenser type: vertical air flow
Mean condensing temperature: 50C
Ambient temperature: 35C
Noise: 70 dBA @ 10 m
Generic vertical air flow condenser, 14 kW, 907 mm wide x 972 mm
deep x 1076 mm high, 62 kg
Airedale vertical condenser, model CR12, 14 kW
http://www.airedale.com/

Chapman BDSP Plantroom & Riser Schedule

Air Cooled Chillers Heat pump 11300 mm wide x 6000 mm deep x 2400 mm high
Plantroom
Reference Area Location Notes
Air Cooled Chillers Heat pump 67 m Roof Air Cooled Chillers Heat pump to operate with ground storage
complete with hydronic kit
Equipment
Reference Duty Selection
Air cooled chillers 2 No. chillers @ 200 kW to meet 400 kW total load
Minimum EER (or CoP):
- 2.50 kW/kW <750 kW
- 2.60 kW/kW =>750 kW
Chiller types: scroll, screw
Chilled water: 12C on / 7C off
Ambient temperature: 35C
Noise: 70 dBA @ 10 m
Generic air cooled chiller, 220 kW, 3400 mm wide x 2300 mm deep
x 2297 mm high, 2245 kg
Trane scroll air cooled chiller, model CGAN800, 220 kW
http://www.trane.com/
Carrier scroll air cooled chiller, model 30RB232, 227 kW
http://www.carrieraircon.co.uk/

Chapman BDSP Plantroom & Riser Schedule

Solar Collector Plantroom 3700 mm wide x 2100 mm deep x 1000 mm high

Chapman BDSP Plantroom & Riser Schedule

Plantroom
Reference Area Location Notes
Solar Collector Plantroom 8 m Roof Composed of multiple solar panels: numbers to be confirmed (by
ICAX at www.icax.co.uk) for collecting heat from the sun an storing
it to minipiles or piles or horizontal slinkies.
Equipment
Reference Duty Selection
Solar Panels (number TBC) 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Black tarmac'd roof surface as
solar collector
1 No. ancillary item(s) Ancillary item, 600 mm wide x 600 mm deep x 600 mm high, 100 kg,
100 kg
Solar Panels (number TBC)
Copy 1
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 2
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 3
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 4
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 5
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 6
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 7
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 8
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 9
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 10
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 11
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 12
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Chapman BDSP Plantroom & Riser Schedule

Solar Panels (number TBC)
Copy 13
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 14
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 15
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 16
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 17
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 18
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 19
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Solar Panels (number TBC)
Copy 20
1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600
mm high, 100 kg, 100 kg
Chapman BDSP Plantroom & Riser Schedule

Landlord Electrical Riser 1875 mm wide x 475 mm deep x 4000 mm high
Riser
Reference Area Location Notes
Landlord Electrical Riser 0.9 m Core -
Equipment
Reference Duty Selection
Main tray - Generic tray, 450 mm wide
Dist bd 1 100 Amp incomer, 24 ways
Type: MCB
415 V, TP&N, 50 Hz
Generic mcb electrical board, 24 way, 100 Amp incomer, 460 mm
wide x 150 mm deep x 1180 mm high, 44 kg
Moeller mcb electrical board, model FG-B-24, 24 way, 100 Amp
incomer
http://www.moeller.co.uk/
MEM mcb electrical board, model EBM242, 24 way, 125 Amp
incomer
http://www.eaton.com/uk
Lighting panel 1 No. lighting panel(s) Lighting panel, 450 mm wide x 150 mm deep x 450 mm high, 100
kg, 100 kg