Heating Plantroom 5700 mm wide x 5300 mm deep x 3000 mm high (overall)
Chapman BDSP Plantroom & Riser Schedule
Plantroom Reference Area Location Notes Heating Plantroom 30 m Ground Floor - Equipment Reference Duty Selection Sidestream Filter 1 No. sidestream filter(s) Sidestream filter, 600 mm wide x 600 mm deep x 2000 mm high, 100 kg, 100 kg Enwamatic, TBC www.enwamatic.com Calorifiers 2 No. calorifiers @ 1340 litres/hr to meet 2000 litres/hr total capacity Venting: unvented Arrangement: vertical Generic semi storage vertical, 440 litres/hr, 735 mm wide x 1060 mm deep x 2050 mm high, 850 kg IMI Rycroft semi storage vertical, model MX440V, 1760 litres/hr http://www.rycroft.com/ HRS semi storage vertical, model Aquasave AS515, 2500 litres/hr http://www.hrs.co.uk/ Calorifiers heating pumps 1 No. duty / 1 No. standby @ 6.52 l/s, 100 kPa Pump type: in-line vertical Pump arrangement: single Pump fluid: water Generic in-line vertical pump, 196 mm wide x 381 mm deep x 519 mm high, 56 kg Armstrong in-line vertical pump, model Starline50-150 www.armstrongpumps.com Hot water circulating pump 1 No. duty @ 10.8 l/s, 100 kPa Pump type: in-line vertical Pump arrangement: single Pump fluid: water Generic in-line vertical pump, 255 mm wide x 635 mm deep x 753 mm high, 120 kg Armstrong in-line vertical pump, model Starline100-200 www.armstrongpumps.com Calorifiers expansion vessels 2 No. expansion vessels 3350 litres system volume 3.00 bar g feed pressure 3.55 bar g final pressure 75C maximum system temperature 0% glycol 370 litres expansion volume Generic expansion vessel, 500 litres, 581 kg Rycroft expansion vessel, model EXP500V, 500 litres http://www.rycroft.com/ Smedegaard expansion vessel, model Type 2 500, 500 litres http://www.smedegaard.com/ Ground energy Storage Pump 1 No. duty / 1 No. standby @ 0 l/s, 180 kPa Pump type: in-line vertical Pump arrangement: single Pump fluid: water Generic in-line vertical pump, 131 mm wide x 285 mm deep x 446 mm high, 21 kg Armstrong in-line vertical pump, model Starline32-120 www.armstrongpumps.com Micro CHP 5 kW 1 No. micro chp(s) Micro chp, 600 mm wide x 600 mm deep x 900 mm high, 100 kg, 100 kg Chapman BDSP Plantroom & Riser Schedule
Micro CHP 5 kW 1 No. micro chp(s) Micro chp, 600 mm wide x 600 mm deep x 900 mm high, 100 kg, 100 kg MCC 200 Amp incomer, 5 starters 415 V, TP&N, 50 Hz Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm high ABB MCC, model MNS http://www.abb.co.uk/ Eaton Moeller MCC, model Modan http://www.moeller.net/en/index.jsp Electrical board 100 Amp incomer, 12 ways Type: MCB 415 V, TP&N, 50 Hz Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm wide x 150 mm deep x 885 mm high, 28 kg Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp incomer http://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Amp incomer http://www.eaton.com/uk Heating pressurisation unit(upper floors) 1 No. pressurisation unit 9000 litres system volume 8.0 bar g maximum working pressure 1.6 bar g maximum system pressure 60C maximum system temperature 0% glycol Pressurisation unit types: standard, compressor Generic standard pressurisation unit, 1170 mm wide x 800 mm deep x 1660 mm high, 802 kg Hoval standard pressurisation unit, model PressVal Micron SM600, 600 litres http://www.hoval.co.uk/ Boilers vents Vent type: Natural high level, natural low level High level vents to provide 0 m/s ventilation air exhaust Low level vents to provide 0 m/s combustion and ventilation air intake (Based on BS6644, BS5410-2 and manufacturer recommendations) 1 No. generic vent at high level, 200 mm wide x 100 mm high, 50 % free area 1 No. generic vent at low level, 200 mm wide x 100 mm high, 50 % free area
Chapman BDSP Plantroom & Riser Schedule
Auditorium AHU 8800 mm wide x 3500 mm deep x 2900 mm high
Chapman BDSP Plantroom & Riser Schedule
Plantroom Reference Area Location Notes Auditorium AHU 30 m Ground Floor - Equipment Reference Duty Selection Basement AHU Air flow 3 m/s Configuration: stacked, intake bottom Maximum velocity 2.2 m/s Supply components: - Louvre - Attenuator (600 mm) - Bag filter (long) - Access (short) - Thermal wheel - Thermal wheel - Access (short) - Fan (backward curved) - Access (short) - Humidifier (steam) - Attenuator (600 mm) - Connection Extract components: - Louvre - Attenuator (600 mm) - Access (short) - Thermal wheel - Heating coil (2 row) - Access (short) - Thermal wheel - Access (short) - Humidifier (steam) - Fan (backward curved) - Panel filter - Access (short) - Attenuator (600 mm) - Connection Generic modular AHU, SFP 1.9 W/l/s (estimated), 7600 mm wide x 1404 mm deep x 2748 mm high, 3040 kg Flakt Woods modular AHU, model EU40 http://www.flaktwoods.com/products/air-handling-units/ Chapman BDSP Plantroom & Riser Schedule
Main (option!) AHU 11300 mm wide x 8500 mm deep x 5400 mm high
Chapman BDSP Plantroom & Riser Schedule
Plantroom Reference Area Location Notes Main AHU 96 m Ground Floor - Equipment Reference Duty Selection Basement AHU Air flow 8.5 m/s Configuration: stacked, intake bottom Maximum velocity 2.2 m/s Supply components: - Louvre - Attenuator (600 mm) - Bag filter (long) - Access (short) - Thermal wheel - Thermal wheel - Access (short) - Fan (backward curved) - Access (short) - Humidifier (steam) - Attenuator (600 mm) - Connection Extract components: - Louvre - Attenuator (600 mm) - Access (short) - Thermal wheel - Heating coil (2 row) - Access (short) - Thermal wheel - Access (short) - Humidifier (steam) - Access (short) - Fan (backward curved) - Panel filter - Attenuator (600 mm) - Connection Generic modular AHU, SFP 1.8 W/l/s (estimated), 10050 mm wide x 2650 mm deep x 4100 mm high, 9630 kg Flakt Woods modular AHU, model EU62 http://www.flaktwoods.com/products/air-handling-units/ Chapman BDSP Plantroom & Riser Schedule
Basement AHU Air flow 8.5 m/s Configuration: stacked, intake bottom Maximum velocity 2.2 m/s Supply components: - Louvre - Attenuator (600 mm) - Bag filter (long) - Access (short) - Thermal wheel - Thermal wheel - Access (short) - Fan (backward curved) - Access (short) - Humidifier (steam) - Attenuator (600 mm) - Connection Extract components: - Louvre - Attenuator (600 mm) - Access (short) - Thermal wheel - Heating coil (2 row) - Access (short) - Thermal wheel - Access (short) - Humidifier (steam) - Access (short) - Fan (backward curved) - Panel filter - Attenuator (600 mm) - Connection Generic modular AHU, SFP 1.8 W/l/s (estimated), 10050 mm wide x 2650 mm deep x 4100 mm high, 9630 kg Flakt Woods modular AHU, model EU62 http://www.flaktwoods.com/products/air-handling-units/
Chapman BDSP Plantroom & Riser Schedule
HV Plantroom 7100 mm wide x 4900 mm deep x 3400 mm high (overall)
Chapman BDSP Plantroom & Riser Schedule
Plantroom Reference Area Location Notes HV Plantroom 35 m Ground Floor - Equipment Reference Duty Selection RMU Rating 200 Amps 12000 V, TP&N, 50 Hz Generic RMU, 771 mm wide x 765 mm deep x 1510 mm high, 300 kg ABB RMU, model SafeRing http://www.abb.com/ Schneider RMU, model Ringmaster RN2 http://www.schneider-electric.co.uk/ Minimum connection space above: 600 mm HV switchpanel 12000 V, TP&N, 50 Hz Module type: withdrawable Modules: - Incomer - Bus section - Feeder Future expansion 25% Note: For some manufacturers VTs are integral to other components Generic HV switchpanel, 2600 mm wide x 1550 mm deep x 2300 mm high ABB HV switchpanel, model Unigear ZS1 http://www.abb.com/ Schneider HV switchpanel, model MCSet http://www.schneider-electric.co.uk/ Minimum connection space above: 600 mm Chapman BDSP Plantroom & Riser Schedule
LV Plantroom 6000 mm wide x 3500 mm deep x 3000 mm high (overall) Plantroom Reference Area Location Notes LV Plantroom 21 m Ground Floor - Equipment Reference Duty Selection LV Board 1 No. lv board(s) Lv board, 4000 mm wide x 1200 mm deep x 600 mm high, 100 kg, 100 kg
Chapman BDSP Plantroom & Riser Schedule
Life Safety LV Plantroom 6000 mm wide x 3500 mm deep x 3000 mm high (overall) Plantroom Reference Area Location Notes Life Safety LV Plantroom 21 m Ground Floor - Equipment Reference Duty Selection LV Board 1 No. lv board(s) Lv board, 4000 mm wide x 1200 mm deep x 600 mm high, 100 kg, 100 kg
Chapman BDSP Plantroom & Riser Schedule
Generators Plantroom 9100 mm wide x 4200 mm deep x 4200 mm high (overall)
Chapman BDSP Plantroom & Riser Schedule
Plantroom Reference Area Location Notes Generators Plantroom 38 m Ground floor - Equipment Reference Duty Selection LV generators board 1 No. incomer 1 No. feeder 415 V, TP&N, 50 Hz Access: front Generic generators LV switchboard, 2650 mm wide x 655 mm deep x 2429 mm high GE Power Controls generators LV switchboard, model System 4 http://www.ge.com/ Eaton generators LV switchboard, model Bill Classic Form 4 http://www.eaton.com/ Minimum connection space above: 600 mm Generators 1 No. generators @ 400 kVA 415 V, TP&N, 50 Hz Generic diesel generator, 400 kVA, 3500 mm wide x 1150 mm deep x 2158 mm high, 3700 kg Broadcrown diesel generator, model BCC 440-50 E2, 440 kVA, Emissions compliance EU Stage 2 http://www.broadcrown.com/ FG Wilson diesel generator, model P350P4, 400 kVA, Emissions compliance EU Stage 2 http://www.fgwilson.com/ Day tanks 1 No. day tanks @ 8 hours storage Generator fuel tank capacity : 650 litres Day tank capacity (nett): 38 litres Generic day tank , 1364 litres, 1750 mm wide x 1170 mm deep x 1250 mm high Joseph Ash day tank, model D01, 1364 litres http://www.jaenvirotanks.com/ Blake day tank, model TEBU FO 1000, 1000 litres http://www.blakegroup.co.uk/
Chapman BDSP Plantroom & Riser Schedule
Gas Meter Plantroom 1200 mm wide x 2000 mm deep x 2500 mm high (overall)
Plantroom Reference Area Location Notes Gas Meter Plantroom 3 m Ground Floor - Equipment Reference Duty Selection Gas Meter 1 No. gas meter(s) Gas meter, 800 mm wide x 480 mm deep x 600 mm high, 100 kg, 100 kg
Chapman BDSP Plantroom & Riser Schedule
Telecoms Plantroom 4000 mm wide x 2000 mm deep x 2500 mm high (overall) Plantroom Reference Area Location Notes Telecoms Plantroom 8 m Ground Floor - Equipment Reference Duty Selection Copper Rack 1 No. rack(s) Rack, 2000 mm wide x 500 mm deep x 1600 mm high, 100 kg, 100 kg
Chapman BDSP Plantroom & Riser Schedule
Transformers Plantroom 5200 mm wide x 4300 mm deep x 3500 mm high (overall)
Chapman BDSP Plantroom & Riser Schedule
Plantroom Reference Area Location Notes Transformers Plantroom 22 m Ground Floor - Equipment Reference Duty Selection Transformers supply duct 0.82 m/s @ 10.0 m/s maximum, 1.0 Pa/m maximum Maximum aspect ratio: 4.0 Insulation: none (Air flow requirement based on transformers losses) 500 mm wide x 300 mm deep No insulation Transformers 1 No. @ 800 kVA HV 12000 V, LV 415 V, TP&N, 50 Hz Transformer type: dry Derating factor: 1.25 Generic dry transformer, 1000 kVA, 2000 mm wide x 1210 mm deep x 2400 mm high, 2870 kg ABB dry transformer, model Cast resin 1000, 1000 kVA http://www.abb.com/ Schneider dry transformer, model Cast Resin 1000, 1000 kVA http://www.schneider-electric.co.uk/ Minimum connection space above: 600 mm Transformers extract duct 0.82 m/s @ 10.0 m/s maximum, 1.0 Pa/m maximum Maximum aspect ratio: 4.0 Insulation: none (Air flow requirement based on transformers losses) 500 mm wide x 300 mm deep No insulation
Chapman BDSP Plantroom & Riser Schedule
Fire Fighting Riser 2 2275 mm wide x 650 mm deep x 4000 mm high (overall) Riser Reference Area Location Notes Fire Fighting Riser 2 1.5 m Fire Fighting Core2 Sprinkler valves and wet riser valves may be provided in one of the two riser only. Equipment Reference Duty Selection Dry riser 1 No. dry riser @ 100 mm diameter 100 mm diameter riser pipe Cabinet 510 mm wide x 325 mm deep x 720 mm high
Chapman BDSP Plantroom & Riser Schedule
Mechanical Riser 1 3125 mm wide x 450 mm deep x 4000 mm high
Riser Reference Area Location Notes Mechanical Riser 1 1.4 m Core 1 To serve the floors of the tower and the roof condensers Equipment Reference Duty Selection LPHW F&R 400 kW @ 3.0 m/s maximum, 240 Pa/m maximum Pipe configuration: flow and return Insulation: mineral wool (e=0.05), heating water 75C, internal 100 mm diameter 60 mm mineral wool (e=0.05) insulation CHW F&R 600 kW @ 3.0 m/s maximum, 240 Pa/m maximum Pipe configuration: flow and return Insulation: mineral wool (e=0.05), chilled water 5C, internal 125 mm diameter 60 mm mineral wool (e=0.05) insulation Condensate 54 mm diameter Pipe configuration: single Insulation: none 54 mm diameter No insulation VP (SVP) 54 mm diameter Pipe configuration: single Insulation: none 54 mm diameter No insulation RWP 150 mm diameter Pipe configuration: single Insulation: none 150 mm diameter No insulation Condenser Water 150 mm diameter Pipe configuration: flow and return Insulation: mineral wool (e=0.05), chilled water 5C, internal 150 mm diameter 60 mm mineral wool (e=0.05) insulation 24/7 cooling 150 kW @ 3.0 m/s maximum, 240 Pa/m maximum 80 mm diameter Chapman BDSP Plantroom & Riser Schedule
Pipe configuration: flow and return Insulation: mineral wool (e=0.05), chilled water 5C, internal 50 mm mineral wool (e=0.05) insulation
Chapman BDSP Plantroom & Riser Schedule
Public Health Risers 1 2475 mm wide x 525 mm deep x 4000 mm high Riser Reference Area Location Notes Public Health Risers 1 1.3 m WC Riser core 1 To serve WC's Prefab (100 mm frame included in dimensions) Equipment Reference Duty Selection MWS 54 mm diameter Pipe configuration: single Insulation: none 54 mm diameter No insulation BCWS 54 mm diameter Pipe configuration: single Insulation: none 54 mm diameter No insulation HWS F 54 mm diameter Pipe configuration: single Insulation: mineral wool (e=0.05), hot water 60C, internal 54 mm diameter 50 mm mineral wool (e=0.05) insulation HWS R 28 mm diameter Pipe configuration: single Insulation: mineral wool (e=0.05), hot water 60C, internal 28 mm diameter 40 mm mineral wool (e=0.05) insulation RWP 150 mm diameter Pipe configuration: single Insulation: none 150 mm diameter No insulation SVP 100 mm diameter 100 mm diameter Chapman BDSP Plantroom & Riser Schedule
Pipe configuration: single Insulation: none No insulation VP (SVP) 110 mm diameter Pipe configuration: single Insulation: none 110 mm diameter No insulation VP (interceptor) 100 mm diameter Pipe configuration: single Insulation: none 100 mm diameter No insulation
Chapman BDSP Plantroom & Riser Schedule
WC Extract 800 mm wide x 825 mm deep x 4000 mm high Riser Reference Area Location Notes WC Extract 0.7 m WC Riser - Equipment Reference Duty Selection Extract duct 1.80 m/s @ 7.5 m/s maximum, 1.0 Pa/m maximum Maximum aspect ratio: 3.0 Insulation: none 600 mm wide x 500 mm deep No insulation Chapman BDSP Plantroom & Riser Schedule
MER Room 5900 mm wide x 4200 mm deep x 3400 mm high (overall)
Chapman BDSP Plantroom & Riser Schedule
Plantroom Reference Area Location Notes MER Room 25 m Ground Floor - Equipment Reference Duty Selection IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kg Rack, Rack IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kg Rack, Rack IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kg Rack Battery Unit 1 No. battery unit(s) Battery unit, 800 mm wide x 1000 mm deep x 2200 mm high, 100 kg, 100 kg AC Unit 1 No. ac unit(s) Ac unit, 1200 mm wide x 800 mm deep x 2000 mm high, 500 kg, 500 kg AC Unit 1 No. ac unit(s) Ac unit, 1200 mm wide x 800 mm deep x 2000 mm high, 500 kg, 500 kg Electrical board 160 Amp incomer, 12 ways Type: MCCB 415 V, TP&N, 50 Hz Generic mccb electrical board, 12 way, 400 Amp incomer, 900 mm wide x 230 mm deep x 1605 mm high, 168 kg Moeller mccb electrical board, model PB12-400, 12 way, 400 Amp incomer http://www.moeller.co.uk/ MEM mccb electrical board, model PBJG1240M, 12 way, 400 Amp incomer http://www.eaton.com/uk UPS 1 No. ups(s) Ups, 800 mm wide x 1000 mm deep x 2200 mm high, 100 kg, 100 kg IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kg rack IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kg rack Chapman BDSP Plantroom & Riser Schedule
IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kg rack
Chapman BDSP Plantroom & Riser Schedule
Security Room 5600 mm wide x 3600 mm deep x 3700 mm high (overall)
Chapman BDSP Plantroom & Riser Schedule
Plantroom Reference Area Location Notes Security Room 20 m Ground Floor Equipment Reference Duty Selection IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kg Rack, Rack IT Rack Copy 1 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kg Rack, Rack IT Rack Copy 2 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kg Rack Desk 1 No. desk(s) Desk, 1800 mm wide x 850 mm deep x 850 mm high, 100 kg, 100 kg AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 1200 mm wide x 250 mm deep x 400 mm high, 30 kg, 30 kg Desk 1 No. desk(s) Desk, 1800 mm wide x 850 mm deep x 850 mm high, 100 kg, 100 kg Electrical board 100 Amp incomer, 12 ways Type: MCB 415 V, TP&N, 50 Hz Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm wide x 150 mm deep x 885 mm high, 28 kg Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp incomer http://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Amp incomer http://www.eaton.com/uk Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg, 100 kg AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 1200 mm wide x 250 mm deep x 400 mm high, 30 kg, 30 kg
Chapman BDSP Plantroom & Riser Schedule
AV Room 2900 mm wide x 2300 mm deep x 3700 mm high (overall)
Chapman BDSP Plantroom & Riser Schedule
Plantroom Reference Area Location Notes AV Room 7 m Ground Floor Equipment Reference Duty Selection IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100 kg Rack, Rack Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg, 100 kg Desk 1 No. desk(s) Desk, 1200 mm wide x 750 mm deep x 850 mm high, 100 kg, 100 kg Electrical board 100 Amp incomer, 12 ways Type: MCB 415 V, TP&N, 50 Hz Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm wide x 150 mm deep x 885 mm high, 28 kg Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp incomer http://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Amp incomer http://www.eaton.com/uk AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg, 30 kg AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg, 30 kg
Chapman BDSP Plantroom & Riser Schedule
BEMS and Maintenance Room 3600 mm wide x 2300 mm deep x 3700 mm high (overall)
Chapman BDSP Plantroom & Riser Schedule
Plantroom Reference Area Location Notes BEMS and Maintenance Room 9 m Ground Floor Equipment Reference Duty Selection Desk 1 No. desk(s) Desk, 1800 mm wide x 750 mm deep x 850 mm high, 100 kg, 100 kg Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg, 100 kg AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg, 30 kg Electrical board 100 Amp incomer, 12 ways Type: MCB 415 V, TP&N, 50 Hz Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm wide x 150 mm deep x 885 mm high, 28 kg Moeller mcb electrical board, model FG-B-12, 12 way, 100 Amp incomer http://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Amp incomer http://www.eaton.com/uk Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg, 100 kg Locker2 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg, 100 kg
Chapman BDSP Plantroom & Riser Schedule
Ventilation distributed fans 9100 mm wide x 8300 mm deep x 1000 mm high (overall)
Chapman BDSP Plantroom & Riser Schedule
Plantroom Reference Area Location Notes Ventilation distributed fans 76 m Every floor - Equipment Reference Duty Selection Floor void unit (approx 4No per floor) 1 No. floor void unit (s) Floor void unit , 1900 mm wide x 1600 mm deep x 600 mm high, 100 kg, 100 kg Nuaire , Xbober XB55 www.nuaire.co.uk Floor void unit (approx 4No per floor) Copy 1 1 No. floor void unit (s) Floor void unit , 1900 mm wide x 1600 mm deep x 600 mm high, 100 kg, 100 kg Nuaire , Xbober XB55 www.nuaire.co.uk Floor void unit (approx 4No per floor) Copy 2 1 No. floor void unit (s) Floor void unit , 1900 mm wide x 1600 mm deep x 600 mm high, 100 kg, 100 kg Nuaire , Xbober XB55 www.nuaire.co.uk Floor void unit (approx 4No per floor) Copy 3 1 No. floor void unit (s) Floor void unit , 1900 mm wide x 1600 mm deep x 600 mm high, 100 kg, 100 kg Nuaire , Xbober XB55 www.nuaire.co.uk
Chapman BDSP Plantroom & Riser Schedule
Satellite 4000 mm wide x 2200 mm deep x 1800 mm high (overall)
Plantroom Reference Area Location Notes Satellite 9 m Roof - Equipment Reference Duty Selection SATELLITE DISH 1 No. satellite dish(s) Satellite dish, 1200 mm wide x 1200 mm deep x 1200 mm high, 100 kg, 100 kg SATELLITE DISH 1 1 No. satellite dish(s) Satellite dish, 1200 mm wide x 1200 mm deep x 1200 mm high, 100 kg, 100 kg
Chapman BDSP Plantroom & Riser Schedule
Computer AC Units 4100 mm wide x 2200 mm deep x 1200 mm high Plantroom Reference Area Location Notes Computer AC Units 9 m Roof - Equipment Reference Duty Selection Computer Room AC units 2 No. condensers @ 10 kW Condenser type: vertical air flow Mean condensing temperature: 50C Ambient temperature: 35C Noise: 70 dBA @ 10 m Generic vertical air flow condenser, 14 kW, 907 mm wide x 972 mm deep x 1076 mm high, 62 kg Airedale vertical condenser, model CR12, 14 kW http://www.airedale.com/
Chapman BDSP Plantroom & Riser Schedule
Air Cooled Chillers Heat pump 11300 mm wide x 6000 mm deep x 2400 mm high Plantroom Reference Area Location Notes Air Cooled Chillers Heat pump 67 m Roof Air Cooled Chillers Heat pump to operate with ground storage complete with hydronic kit Equipment Reference Duty Selection Air cooled chillers 2 No. chillers @ 200 kW to meet 400 kW total load Minimum EER (or CoP): - 2.50 kW/kW <750 kW - 2.60 kW/kW =>750 kW Chiller types: scroll, screw Chilled water: 12C on / 7C off Ambient temperature: 35C Noise: 70 dBA @ 10 m Generic air cooled chiller, 220 kW, 3400 mm wide x 2300 mm deep x 2297 mm high, 2245 kg Trane scroll air cooled chiller, model CGAN800, 220 kW http://www.trane.com/ Carrier scroll air cooled chiller, model 30RB232, 227 kW http://www.carrieraircon.co.uk/
Chapman BDSP Plantroom & Riser Schedule
Solar Collector Plantroom 3700 mm wide x 2100 mm deep x 1000 mm high
Chapman BDSP Plantroom & Riser Schedule
Plantroom Reference Area Location Notes Solar Collector Plantroom 8 m Roof Composed of multiple solar panels: numbers to be confirmed (by ICAX at www.icax.co.uk) for collecting heat from the sun an storing it to minipiles or piles or horizontal slinkies. Equipment Reference Duty Selection Solar Panels (number TBC) 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Black tarmac'd roof surface as solar collector 1 No. ancillary item(s) Ancillary item, 600 mm wide x 600 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 1 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 2 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 3 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 4 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 5 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 6 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 7 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 8 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 9 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 10 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 11 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 12 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Chapman BDSP Plantroom & Riser Schedule
Solar Panels (number TBC) Copy 13 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 14 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 15 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 16 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 17 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 18 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 19 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Solar Panels (number TBC) Copy 20 1 No. solar panels (number tbc)(s) Solar panels (number tbc), 2200 mm wide x 1500 mm deep x 600 mm high, 100 kg, 100 kg Chapman BDSP Plantroom & Riser Schedule
Landlord Electrical Riser 1875 mm wide x 475 mm deep x 4000 mm high Riser Reference Area Location Notes Landlord Electrical Riser 0.9 m Core - Equipment Reference Duty Selection Main tray - Generic tray, 450 mm wide Dist bd 1 100 Amp incomer, 24 ways Type: MCB 415 V, TP&N, 50 Hz Generic mcb electrical board, 24 way, 100 Amp incomer, 460 mm wide x 150 mm deep x 1180 mm high, 44 kg Moeller mcb electrical board, model FG-B-24, 24 way, 100 Amp incomer http://www.moeller.co.uk/ MEM mcb electrical board, model EBM242, 24 way, 125 Amp incomer http://www.eaton.com/uk Lighting panel 1 No. lighting panel(s) Lighting panel, 450 mm wide x 150 mm deep x 450 mm high, 100 kg, 100 kg