Вы находитесь на странице: 1из 3

Type test report no.

MA D 005e
Protective housing
Test department
Buml/Wagner
23.11.2007

Type test for protective


housing type:

size S and size L for ED 100 and ED 200

Test specification:

IEC 60214-1:2003

Test samples:
Protective housing:

size L for ED 100 and ED 200

Type of transmission gear:

size 100 and size 200

Manufacturer:

Maschinenfabrik Reinhausen GmbH, Regensburg, Germany

Date of test

October 2007 to November 2007

Places of test

RST Rail System Testing GmbH, Henningsdorf, Germany


Maschinenfabrik Reinhausen GmbH, Regensburg, Germany

Tests performed:
Degree of protection of
motor-drive cubicle:
Test results:

The motor drive protective housing was tested according to the protection
requirements of IP 66 according to IEC 60529, sub-clause 13.4 and
sub-clause 14.2.6.
The test for the first characteristic numeral 6 and the test for the second
characteristic numeral 6 were successfully completed, thus the
protection requirements of IP 66 according to IEC 60529 are fulfilled for
the motor drive protective housing types L and S.
The requirements of IEC 60214-1:2003 were met.

This report contains 3 sheets.

i. A. Thomas Strof
[valid

without signature]

MASCHINENFABRIK REINHAUSEN GMBH


- TEST DEPARTMENT F01106:00

Page 2 of 3 / MA D 005e
1.
Test specification
The type test was performed in accordance with IEC 60214-1:2003 Tap-changers - Part 1: Performance
requirements and test methods,
- sub-clause 6 Requirements for motor drive mechanisms for on-load tap-changers, sub-clause 6.2
Type tests, sub-clause 6.2.3 Degree of protection of motor-drive cubicle,
- sub-clause 8 Requirements for motor drive mechanisms for off-circuit tap-changers, sub-clause 8.2
Type tests , sub-clause 8.2.3 Degree of protection of motor-drive cubicle.

2.

Data of test sample

Type:
Serial no.:
Year of manufacture:

3.

Motor drive protective housing size L


1011857
2005, modified in 2007

Scope of application

The type test was carried out on a motor drive protective housing size L. This variant is longer than size
S. All other characteristics are identical to size S, e.g. the same profile of the cover gasket, the same
outline of the cover, the same number of screwed joints, the same transmission gear unit and the same
ventilation.
Due to the cover of the motor drive protective housing of size L has a larger faying surface than size S
and resulting into a longer distance between the hinges and locking levers, testing of size L is more
critical then testing of size S.
Therefore this type test report is valid for the motor drive protective housing size L and size S.

4.

Test arrangement

4.1 Test for first characteristic numeral 6 (protection against access to hazardous parts)
Place of test
Protection against access
Test means:

RST Rail System Testing GmbH, Henningsdorf, Germany.

Test force:
Acceptance conditions:

Access probe (rigid steel wire 1.0 mm diameter, 100 mm length,


edged rounded off).
1 N 10%
The access probe must not be able to penetrate.

Protection against foreign objects


Test means:
Underpressure in the enclosure:
Extraction rate:
Sucked air volume
Test duration
Test dust
Acceptance conditions

Dust chamber
20 mbar
60 enclosure volumes / hour
80 enclosure volumes
8 hours
Talcum powder
No penetration of dust

Page 3 of 3 / MA D 005e
4.2 Test for second characteristic numeral 6 (protection against water)
Place of test
Test conditions
Internal diameter of the nozzle:
Water delivery rate:
Water pressure:
Core of the substantial stream:
Test duration:
Distance from nozzle to
enclosure surface:
Realization:
Acceptance conditions

5.

Maschinenfabrik Reinhausen GmbH, Regensburg, Germany.

12.5 mm
100 l/min 5%
to be adjusted to achieve the specified delivery rate
circle of approx. 120 mm diameter at 2.5 m distance from nozzle.
3 min
2.5 3 m
The test is made by spraying the enclosure from all practicable
directions with a stream of water from a standard test nozzle.
No penetration of water.

Tests performed

5.1 Test for first characteristic numeral 6 (protection against access to hazardous parts)
The test was carried out in a dust chamber with underpressure using talcum powder according to
IEC 60529, sub-clause 13.4, category 1 enclosures:
Underpressure inside the
protective housing:
Extraction rate:
Test duration:

19 mbar
0.25 enclosure volumes / hour
8h

Results:
No talcum dust penetrated into the enclosure of the test specimen. The access to the hazardous parts
with an access probe was not possible.
5.2 Test for second characteristic numeral 6 (protection against water)
This test was carried out with spray water according to IEC 60529, sub-clause 14.2.6:
Water delivery rate:
Internal diameter of the nozzle:
Test duration:

100 l/min
12.5 mm
3 min

Results:
No water penetrated into the enclosure of the test specimen.

6.

Test result

The test for the first characteristic numeral 6 and the test for the second characteristic numeral 6 were
successfully completed, thus the protection requirements of IP 66 according to IEC 60529 are fulfilled for
the motor drive protective housing types L and S. The requirements of IEC 60214-1:2003 were met.