Doc. n.

2GJA708478
Rev. 0 06/2010 [WF]
Type of document
Manual

Title
Composition and housing

1/10

ABB S.p.A. PPD U.O. ADDA

COMPOSITION AND GAS COMPARTMENTS

OF THE METAL-CLAD STATION

BLF/PASS 145-170

SINGAPORE POWER - AYER RAJAH 66kV































Doc. n. 2GJA708478
Rev. 0 06/2010 [WF]
Type of document
Manual

Title
Composition and housing

2/10

ABB S.p.A. PPD U.O. ADDA

CONTENTS


1. COMPOSITION OF THE STATION......................................................................................... 3
2. DESCRIPTION........................................................................................................................ 4
2.1 Each Feeder bay includes:................................................................................................ 4
2.2 Each 230/66kV transformer bay includes:......................................................................... 4
2.3 Each 66/22kV transformer bay includes:........................................................................... 5
2.4 Each bus coupler bay includes:......................................................................................... 6
2.5 Each bus section bay includes:......................................................................................... 6
2.6 Double Bus Bar System:................................................................................................... 6
3. GAS COMPARTMENTS AND ACCESSORIES....................................................................... 7
3.1 Standards for container of molecular sieves...................................................................... 7
4. WARNINGS AND ALARMS..................................................................................................... 8
4.1 Type and quantity of alarms and block.............................................................................. 8
4.2 Warning............................................................................................................................ 8
5. FILLING PRESSURE AND CONTROL DEVICE...................................................................... 8
5.1 General............................................................................................................................. 8
5.2 Rated filling values............................................................................................................ 8
Reproduction prohibited................................................................................................................ 10
Address ........................................................................................................................................ 10
Notes............................................................................................................................................ 10


Doc. n. 2GJA708478
Rev. 0 06/2010 [WF]
Type of document
Manual

Title
Composition and housing

3/10

ABB S.p.A. PPD U.O. ADDA

1. COMPOSITION OF THE STATION

The station includes three separate phases, basically identical, but different in the length of certain
connection elements.

The station, represented in the single-line diagram and housing 2GJA101826 and in the drawing
2GJA101827 includes:

- Twenty-one feeder bays double bus bar, with connection to the bar system and cable
outlet;

- Four 230/66kV transformer bays double bus bar, with connection to the bar system and
double cable outlet;

- Two 66/22kV transformer bays double bus bar, with connection to the bar system and cable
outlet;

- Two bus coupler bays, with connection to the bar system;

- Two bus section bays, with connection to the bar system;

- A double bus bar system, four zones, connecting the thirty-one bays;

- Local Control Cabinets are located in proximity the metal enclosed GIS;

Doc. n. 2GJA708478
Rev. 0 06/2010 [WF]
Type of document
Manual

Title
Composition and housing

4/10

ABB S.p.A. PPD U.O. ADDA

2. DESCRIPTION
2.1 Each Feeder bay includes:
- One (1) three-pole disconnector switch combined with one (1) slow earthing switch three-pole
operated by means the common motor driver.
- One (1) three-pole disconnector switch three-pole operated by means the motor driver.
- Three (3) ring type single-pole current transformers with the followings characteristics:
Core #1: 1000-800/5 A; Vk>500-400V Imag.<500-600mA Rct<0.5-0.4;
Core #2: 1000-800/5 A; Vk>500-400V Imag.<500-600mA Rct<0.5-0.4;
- One (1) three-pole circuit breaker operated by means the three-pole operating mechanism BLK
222, spring type.
Nominal current: 2000A;
Short circuit current: 40kA;
- Three (3) ring type single-pole current transformers with the followings characteristics:
Core #3: 3000/1 A; Vk>650V Imag.<100mA Rct<6.7;
- One (1) three-pole disconnector switch combined with one (1) slow earthing switch three-pole
operated by means the common motor driver.
- One (1) three-pole fast earthing switch three-pole operated by means the motor/spring driver.
- Three (3) high voltage cable terminals, (cable boxes)
- Supporting structure with rail matching via solid metal wheels
- Low voltage cables from pole BLF/PASS equipment to local control cubicle
- Local Control Cubicle is located nearby correspondent bay
2.2 Each 230/66kV transformer bay includes:
- One (1) three-pole disconnector switch combined with one (1) slow earthing switch three-pole
operated by means the common motor driver.
- One (1) three-pole disconnector switch three-pole operated by means the motor driver.
- Three (3) ring type single-pole current transformers with the followings characteristics:
Core #1: 2000/1A; Vk>375V Imag.<60mA Rct<3.6;
Core #2: 2000/5; Vk>375V Imag.<310mA Rct<0.87;
- One (1) three-pole circuit breaker operated by means the three-pole operating mechanism BLK
222, spring type.
Nominal current: 2000A;
Short circuit current: 40kA;
- Three (3) ring type single-pole current transformers with the followings characteristics:
Core #3: 3000/1 A; Vk>650V Imag.<100mA Rct<6.7;

Doc. n. 2GJA708478
Rev. 0 06/2010 [WF]
Type of document
Manual

Title
Composition and housing

5/10

ABB S.p.A. PPD U.O. ADDA
- One (1) three-pole disconnector switch combined with one (1) slow earthing switch three-pole
operated by means the common motor driver.
- One (1) three-pole fast earthing switch three-pole operated by means the motor/spring driver.
- Three (3) single-pole voltage transformers
- Six (6) high voltage cable terminals, (cable boxes).
- Supporting structure with rail matching via solid metal wheels
- Low voltage cables from pole BLF/PASS equipment to local control cubicle
- Local Control Cubicle is located nearby correspondent bay
2.3 Each 66/22kV transformer bay includes:
- One (1) three-pole disconnector switch combined with one (1) slow earthing switch three-pole
operated by means the common motor driver.
- One (1) three-pole disconnector switch three-pole operated by means the motor driver.
- Three (3) ring type single-pole current transformers with the followings characteristics:
Core #1: 800/5A; Vk>355V Imag.<125mA Rct<0.4;
Core #2: 800/5A; Vk>355V Imag.<125mA Rct<0.4;
- One (1) three-pole circuit breaker operated by means the three-pole operating mechanism BLK
222, spring type.
Nominal current: 2000A;
Short circuit current: 40kA;
- Three (3) ring type single-pole current transformers with the followings characteristics:
Core #3: 3000/1 A; Vk>650V Imag.<100mA Rct<6.7;
- One (1) three-pole fast earthing switch three-pole operated by means the motor/spring driver.
- Three (3) high voltage cable terminals, (cable boxes)
- Supporting structure with rail matching via solid metal wheels
- Low voltage cables from pole BLF/PASS equipment to local control cubicle
- Local Control Cubicle is located nearby correspondent bay

Doc. n. 2GJA708478
Rev. 0 06/2010 [WF]
Type of document
Manual

Title
Composition and housing

6/10

ABB S.p.A. PPD U.O. ADDA
2.4 Each bus coupler bay includes:
- One (1) three-pole disconnector switch three-pole operated by means the motor driver.
- Three (3) ring type single-pole current transformers with the followings characteristics:
Core #1: 3000/1A; Vk>650V Imag.<100mA Rct<6.7;
Core #2: 3000-1600/5; 30/1 5P20;
- One (1) three-pole circuit breaker operated by means the three-pole operating mechanism BLK
222, spring type.
Nominal current: 3150A;
Short circuit current: 40kA;
- Three (3) ring type single-pole current transformers with the followings characteristics:
Core #3: 3000/1 A; Vk>650V Imag.<100mA Rct<6.7;
- One (1) three-pole disconnector switch three-pole operated by means the motor driver.
- Supporting structure with rail matching via solid metal wheels
- Low voltage cables from pole BLF/PASS equipment to local control cubicle
- Local Control Cubicle is located nearby correspondent bay
2.5 Each bus section bay includes:
- One (1) three-pole disconnector switch three-pole operated by means the motor driver.
- Three (3) ring type single-pole current transformers with the followings characteristics:
Core #1: 3000/1A; Vk>650V Imag.<100mA Rct<6.7;
Core #2: 3000-1600/5; 30/1 5P20;
- One (1) three-pole circuit breaker operated by means the three-pole operating mechanism BLK
222, spring type.
Nominal current: 3150A;
Short circuit current: 40kA;
- Three (3) ring type single-pole current transformers with the followings characteristics:
Core #3: 3000/1 A; Vk>650V Imag.<100mA Rct<6.7;
- One (1) three-pole disconnector switch three-pole operated by means the motor driver.
- Supporting structure with rail matching via solid metal wheels
- Low voltage cables from pole BLF/PASS equipment to local control cubicle
- Local Control Cubicle is located nearby correspondent bay
2.6 Double Bus Bar System:
- Four (4) three-pole fast earthing switch three-pole operated by means the motor/spring driver.
- Twelve (12) single-pole voltage transformers
- Double Bus Bar System connected to 31 bays, total of 4 zones.


Doc. n. 2GJA708478
Rev. 0 06/2010 [WF]
Type of document
Manual

Title
Composition and housing

7/10

ABB S.p.A. PPD U.O. ADDA
3. GAS COMPARTMENTS AND ACCESSORIES

All the information concerning the housing of gas SF
6
, the number of SF
6
compartments and their
division are indicated in the single-line drawing where also the symbols, they type and the location
of the accessories of each compartment are indicated. More specifically:

- gas density gauge and fill ing valve;
- pre-set rupture disc;
- inspection window for posi tion of mobile contacts of line di sconnecting switch;
3.1 Standards for container of molecular sieves

Molecular sieves have the capacity to absorb, hence trap, the humidity contained in gas SF
6
. It is
necessary to leave this material in contact with the environment as less as possible.
(Fig.1) shows the absorption capacity of the dehydration material in normal environmental
conditions (20C and H. 65%). The figure also shows that, by leaving the molecular sieves for 5
hours at normal temperature and humidity, they consume over 50% of their absorption power.

Doc. n. 2GJA708478
Rev. 0 06/2010 [WF]
Type of document
Manual

Title
Composition and housing

8/10

ABB S.p.A. PPD U.O. ADDA
4. WARNINGS AND ALARMS

Warning and alarm circuits, relating gas SF
6
, depend on the main cabinet as defined in the relating
module wiring diagrams.
4.1 Type and quantity of alarms and block

Three types of signals are foreseen for each compartment SF
6
coming from the pressure control
device, balanced in temperature, and they are:

- Minimum pressure 1
st
alarm: in case of tripping, just top up the gas without shutting down
the compartment;

- Minimum block pressure, in case of tripping shut down compartment.
4.2 Warni ng

An alarm and block situation produces electric signals necessary for the creation of the interlock
logics as defined in the specific wiring diagrams.
5. FILLING PRESSURE AND CONTROL DEVICE
5.1 General

The definitions "filling pressure" and "pressure control" are not appropriate, because the value we
need to refer to and that we need to control is the density of gas SF
6
.
Since the density varies as the temperature varies, when we refer to filling pressure it is necessary
to specify the corresponding temperature value, (if the pressure is the relative pressure it is
necessary to specify the value of the atmospheric pressure); furthermore, the pressure control
device must be of the type balanced in temperature. More specifically it only indicates the
pressure variations caused by actual density variations and not temperature variations.
General information on SF
6
and the filling pressure of the equipment are contained in the specific
booklet.

5.2 Rated filling values

Each compartment must be filled with SF
6
as indicated in the single-line diagram.

- at a temperature of 20C
- at a local atmospheric pressure of 760 mm/Hg (1.013 bar).

Doc. n. 2GJA708478
Rev. 0 06/2010 [WF]
Type of document
Manual

Title
Composition and housing

9/10

ABB S.p.A. PPD U.O. ADDA



For temperature values different from 20C and atmospheric pressures different from 760 mm/Hg,
the value of the relative filling pressure must be appropriately corrected to keep the rated filling
density constant.
For example:
- every 10C more or less, increase or decrease by 0.155 kg/cm
2
.




% Absorbtion Capacity
Time (hours)

Doc. n. 2GJA708478
Rev. 0 06/2010 [WF]
Type of document
Manual

Title
Composition and housing

10/10

ABB S.p.A. PPD U.O. ADDA

NOTES
If you have some comments we kindly ask You to write that here below and send us this page back.
Thank You for your collaboration.















Copyright

We reserve all rights concerning this document and the components described therein. It must not be
reproduced or disclosed to third
parties and the contents must not be made use of neither in part or in whole without our prior written
permission.
ABB Italy S.p.A., Division High Voltage Product
The information in this document is subject to alteration without prior notice and should not be regarded as
an undertaking from ABB S.p.A. - Power Products Division U.O. Adda-HV
ABB S.p.A. - Power Products Division U.O. Adda-HV takes no responsibility for errors that can occur in
the documentation.
ABB S.p.A. - Power Products Division U.O. Adda-HV is not responsible for damage incurred due to the
misuse of this document.
Reproduction prohibited
By law, we remain the owners of this document. Under no circumstances may it be reproduced, handed over
or disclosed to competitor companies or to third parties without our written authorisation.
ABB S.p.A. - Power Products Division U.O. Adda-HV
Address
ABB S.p.A. -PPD U.O. Adda
Via dei Ceramisti
26900 Lodi Italy
tel. +39.0371 452.1
fax +39.0371 452.222
internet : http:/www.abb.com/it
Notes
These instructions describe high voltage technology products and are intended specifically for making known
the use of such products.
These instructions are not intended to replace valid regulations, with regard to high voltage systems and
equipment, and are intended for the use of specialists in the electrical field.