Академический Документы
Профессиональный Документы
Культура Документы
Thus, in this experiment it is required to determine the COP of the vapor compression
refrigeration cycle.
MM321 Refrigeration and Air Conditioning
Lab 2: Vapor Compression System Page 2
EXPERIMENTAL SET-UP
Figure 2: Schematic Diagram for the refrigeration circuit
RESULTS AND DISCUSSION
Following results were obtained from the refrigeration unit:
Pressure Condenser = 5 Bar
Pressure Evaporator = 1 Bar
Mass flow rate of the refrigerant = 0.04kg/s
Power input compressor = 1.5kW
Corresponding to these temperatures and with reference to Pressure-Enthalpy Diagram
[Arcton 12], the enthalpy values were noted and tabulated as in table 1.
Table 1: Results for Temperature and its corresponding Enthalpy
Point Temperature [K] Enthalpy [kJ/kg]
1` 293 267
2` 352 303
3 311 116
4 271 116
Superheated
MM321 Refrigeration and Air Conditioning
Lab 2: Vapor Compression System Page 3
Figure 2: Pressure-Enthalpy diagram to obtain enthalpy values with respective temperature
Calculations:
Compressor Power:
)
( )
Heat Absorbed by the evaporator (
):
)
( )
Coefficient of Performance (COP):
MM321 Refrigeration and Air Conditioning
Lab 2: Vapor Compression System Page 4
DISCUSSION
From the results it was noted that the refrigeration cycle obtained a COP of 4.19. COP
indicates the ratio of the heat transferred from the refrigerated space to the work supplied to
the cycle (by the compressor). Thus, the greater the COP the better and more efficient the
system is, and since the COP for this system was found to be 4.19, indicated that the system is
quite effective and efficient. The compressor used in this system had a power capacity of
1.5kW, and from the analysis it was found that to successfully remove heat, the system
requires power input of 1.44kW, therefore, this indicated that the result and analysis was
quite proficient and acceptable.
CONCLUSION
From this experiment, the practical aspect of the refrigeration cycle was observed and using
the theory of vapor compression refrigeration cycle the coefficient of performance (COP) of
this refrigeration cycle was calculated. Comparing the calculated data with the experimental
data showed fairly good results. It was also observed that the greater the COP is the efficient
the system becomes as the heat transfer from the refrigerated space increases to the work
input to the system.
REFERENCE
[1] Ahmed, D. M. (2013). Vapor Compression refrigeration Cycle. In MM321 Refrigeration and
Air Conditioning.
[2] HubPages.Inc. (2010, January 16). What is Vapor Compression Refrigeration System.
Retrieved August 17, 2013, from Hub Pages:
http://ninjacraze.hubpages.com/hub/What-is-Vapour-Compression-Refrigeration-
System
.