0 оценок0% нашли этот документ полезным (0 голосов)
39 просмотров34 страницы
A cable which is submitted to a 10%overload current will have a reduced lifetime up to 50% Sizing Overloads Permissive current conductors are always sized from the value of the permissive current.
A cable which is submitted to a 10%overload current will have a reduced lifetime up to 50% Sizing Overloads Permissive current conductors are always sized from the value of the permissive current.
A cable which is submitted to a 10%overload current will have a reduced lifetime up to 50% Sizing Overloads Permissive current conductors are always sized from the value of the permissive current.
Of each machines in cable: In Lathe = 3 kW -> In = 6 A In Milling machine = 11 kW -> In = 20 A Of a several machines in Canalis: In = 3 x 11 + 3 x 3 = 42 kW -> In = 80 A Take into account the Simultaneity factor (Ks) Canalis: In = 80 x 0.7 = 56 A N b o f K s Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 12 Rq: for a machine which works continuously / for lighting K=1. Take into account the expansion factor: generally, in the case of an industrial installations, it needs at least a factor of 1.2 (= leave a margin of 20%) Canalis: In = 56 x 1.2 = 68 A Power sum N b o f m a c h i n e s K s 2 e t 3 0 , 9 4 e t 5 0 , 8 6 9 0 , 7 1 0 3 9 0 , 6 4 0 a n d m o r e 0 , 5 Choice of the electrical distribution architecture Choice of materials according to external influences Power sum Sizing of wires Chronology of a design Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 13 Overloads Permissive current Conductors are always sized from the value of the permissive current It corresponds to the maximal current which can go through the conductor Beyond this value, the insulation qualities are jeopardised premature ageing Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 14 A cable which is submitted to a 10%overload current will have a reduced lifetime up to 50% Sizing Overloads Permissive current The permissive current of a cable is: Iz = (K x Ib) / (f1 x f2 x f3 x f4 x f5 x n x fs) The nominal rated current is: Inc = (K x Ib) / (f1 x f3) With: Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 15 In: Nominal current of the circuit K: Type of protection (fuse / circuit breaker) f1: Ambient temperature f2: Number of conductors loaded in a circuit f3: Reference method and fixing mode n: Number of parallel cables fs: Symmetrical factor f4: Number of layers f5: Several circuit grouping (joined cables) Sizing Constant parameters whenever Factors depending on the evolutions Iz = (K x In) / (f1 x f2 x f3 x f4 x f5 x fs x n) Protection by circuit breaker K = 1 Ambient temperature = 30C f1 = 1 Neutral not loaded f2 = 1 T R R Example 1: 5 machines - P = 9 kW/ machine (Cos = 0.87 / Ib = 15 A) Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 16 Cable with 3 conductors (Mthode E) + cable fixed on cable tray on a horizontal way (Mode 13) f3 = 1 1 layer f4 = 1 5 non joined circuits f5 = 0,1 No parallel cables n et fs = 1 I z = (1 x 15) / (1x1x1x1x1x1x1) = 15 A R R R S theoric = 1.08 mm S chosen = 1.5 mm Example 2: 9 machines - P = 9 kW / machine (Cos = 0.87 then Ib = 15 A) Iz = (K x In) / (f1 x f2 x f3 x f4 x f5 x fs x n) Protection by circuit breaker K = 1 Ambient temperature de 30C f1 = 1 Neutral not loaded f2 = 1 Cable with 3 conductors (Mthode E) + cable fixed on cable tray on a horizontal way (Mode 13) f3 = 1 R R R TD R R R R R R Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 17 way (Mode 13) f3 = 1 1 layer f4 = 1 9 non joined circuits f5 = 0.72 No parallel cables n et fs = 1 I z = (1 x 15) / (1x1x1x0,8x0,72x1x1) = 21 A S theoric = 1.83 mm S chosen = 2.5 mm R R R R 4 machines more: 9 joined circuits f5 = 0.72 S z1 = 2.5 mm Setting up 5 machines in t 0 : 5 non joined circuits f5 = 1 S z0 = 1.5 mm Evolution from 5 to 9 machines Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 18 Results: the 5 circuits installed in t 0 are overloaded : no conformity to installation standards Consequences : the circuits installed in t 0 have to be replaced by 2.5 mm material and labour extra-costs and a long production stopping, . if the installation remains the same, the cable lifetime will considerably be reduced Fire risks . Overloads Application: Canalis 3 lathes + 3 milling machines Inc = (K x Ib) / (f1 x f3) Choice of the range of Canalis: Ib = 68 A IP < 55 KN is chosen Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 19 KN is chosen Choice of the rating of the Canalis: Protection by circuit breaker K = 1 Ambient temperature = 30C f1 = 1 Edgewise mounting = Standard f3 = 1 Inc = (1 x 68) / (1 x 1) = 68 A KN 100 A is chosen Sizing Overloads Application: cable supplying Canalis Iz = (K x In) / (f1 x f2 x f3 x f4 x f5 x fs x n) Protection by circuit breaker K = 1 Ambient temperature = 30C f1 = 1 Neutral not loaded f2 = 1 Cable with 3 conductors (Method E) + cable fixed on cable tray Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 20 Cable with 3 conductors (Method E) + cable fixed on cable tray on a horizontal way (Mode 13) f3 = 1 1 layer f4 = 1 2 joined circuits f5 = 1 No parallel cables n et fs = 1 Iz = (1 x 100) / (1 x 1 x 1 x 1 x 1 x 1 x 1) = 100 A S chosen = 16 mm Sizing Ligthing Other use Installation power directly supplied by a low voltage public distribution network 3% 5% Voltage drops The voltage drop between the origin and any point of use mustnt exceed the values below: Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 21 Sizing Setting of the voltage drop In cable (it needs a calculation): u = b (L/S x Ib x cos ) u: voltage drop in V b: 1 in single phase and 2 in 3 phases : resistivity of phase conductor in ?.mm/m L: length of the cable S: section of the phase conductor in mm Ib: rated current in A cos : power factor (use 0.8 when there is no indication) Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 22 Sizing In Canalis (catalogue data): u = Val catalogue * Ib * L / 100 Example : Page "Charactristics KN from 40 until 100 A" KN 40 A KN 63 A KN 100 A With Cos = 0,8 V/100m/A 0.389 0.163 0.075 With Cos = 0,9 V/100m/A 0.433 0.180 0.080 With Cos = 1 V/100m/A 0.473 0.191 0.080 Checking of the voltage drop Application: cable of the lathe u = b (L/S x Ib x cos ) 3 phases machines b = 2 Copper cable copper = 22.5 x 10-3 .mm/m Rq: aluminium = 36 x 10-3 .mm/m L Lathe (The worst case) = 40 m Section of a phase conductor 1.5 mm Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 23 Sizing Rated current 8 A cos = 0.8 (No specification) u = 2 (22.5 x 10-3 x 40 / 1.5 x 8 x 0.8) = 7.68 V U = u x 100 / U u = 7.68 V U = 400 V U = 0.768 x 100 / 400 = 1.92 % Checking of the voltage drop Application: Canalis Supplying cable of the busway: u = 2 (22.5 x 10-3 x 18 / 16 x 100 x 0.8) = 4.05 V Canalis: Canalis KN 100 A, Cos = 0.8 Val cat 0.075 V / 100 m/A Ib = 100 A (the worst case - its not the actual rated current) L = 20 m Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 24 L = 20 m u = 0.075 x 100 x 20 /100 = 1.5 V Supplying cable of the lathe: u = 2 (22.5 x 10-3 x 6 /1.5 x 8 x 0.8) = 1.15 V Ucable + canalis = u x 100 / U u = 4.05 + 1.5 + 1.15 = 6.7 V U = 400 V U = 6.7 x 100 / 400 = 1.68 % Sizing Short circuits currents (Isc) Generally, Canalis is over sized and can support the short circuits. Particular cases (building > 5000 m): Transformers in parallel Canalis of low power near a transformer of high power Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 25 Sizing Practice Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 26 Power distribution 60 m 45 m L: Lathe 4 kW M: Milling machine 4 kW B: Buffing wheel 0,75 kW C: Circular saw4 kW DT: Drilling/Tapper machine2.2 kW Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 27 45 m Exercise D: Drilling machine 1.5 kW DT: Drilling/Tapper machine2.2 kW DM: Drilling/milling machine 3 kW RD: Radial drilling machine7.5 kW V: Vice filer 2.2 kW Fluo Tubes 2 x 58 W 45 m 60 m Ligthing distribution Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 28 Structure: 1 beam every 2.50 m Exercise Practice Power Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 29 Power - Choice of the materials Calculation of the current needed by each machine: I = P / 3 x U x cos L: Lathe = 4 kW I = 7.2 A M: Milling machine = 4 kW I = 7.2 A B: Buffing wheel = 0.75 kW 1.4 C: Circular saw= 4 kW I = 7.2 A DT: Drilling / Tapper machine = 2,2 kW I = 4 A Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 30 DT: Drilling / Tapper machine = 2,2 kW I = 4 A DM: Drilling / Milling machine = 3 kW I = 5.4 A RD: Radial drilling machine = 7.5 kW I = 13.5 A V: Vice filer = 2.2 kW I = 4 A D: Drilling machine = 1.5 kW I = 2.7 A Exercise L1 L2 L3 L4 L0 20 m Power - Tracking of the runs Solution 1 Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 31 L5 L6 L7 L8 L0 25 m Exercise Power - Power sum Solution 1 I L1 = (3 I EL + 3 I F ) x Ks x 1.2 = (3x4 + 3x7.2)x0.7x1.2 = 28 A I L2 = I L1 = 28 A I L3 = (3 I T + 3 I F ) x Ks x 1.2 = (3x7.2 + 3x7.2)x0.7x1.2 = 36 A I L4 = I L3 = 36 A I L5 = (6 I F + 2 I M ) x Ks x 1.2 = (6x7.2 + 2x1.4)x0.7x1.2 = 39 A I L6 = I L5 = 39 A Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 32 L6 L5 I L7 = (3 I P + 3 I F ) x Ks x 1.2 = (3x2.7 + 3x7.2)x0.7x1.2 = 25 A I L8 = (2 I tr + I PT + I PF + I PR ) x Ks x 1.2 = (2x7.2 + 4 + 5.4 + 13.5)x0.8x1.2 = 36 A I L0 = (I L1 + I L2 + I L3 + I L4 + I L5 + I L6 + I L7 + I L8 )x Ks x 1.2 = (2x28 + 2x36 + 2x39 + 25 + 36 )x0.7x1.2 = 225 A Exercise Power - Choice of the busways Solution 1 Workshop: IP busway > 20 Inc = (K x Ib) / (f1 x f3) Protection of runs by circuit breaker K = 1 Ambient temperature = 30C f1 = 1 Edgewise mounting = standard f3 = 1 Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 33 Exercise Edgewise mounting = standard f3 = 1 Inc L1/L2 = 28 A KNA 40 A Inc L3/L4 = 36 A KNA 40 A Inc L5/L6 = 39 A KNA 40 A Inc L7 = 25 A KNA 40 A Inc L8 = 36 A KNA 40 A Inc L0 = 225 A KSA 250 A Power - Choice of Canalis elements (1/2) Solution 1 Runs L1 to L8: Canalis KNA 40 A, 3L+N+PE - length 20 m: 1 End feed box 63 A 7 straight elements 40 A - 3m - 1 tap-off outlet / m 8 universal brackets Connectors KNA 3L+N+PE,for fuses: Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 34 Exercise Connectors KNA 3L+N+PE,for fuses: Runs L1/L2: 6 connectors 25 A Runs L3/L4: 6 connectors 25 A Runs L5/L6: 8 connectors 25 A Run L7: 6 connectors 25 A Run L8: 5 connectors 25 A Power - Choice of Canalis Elements (2/2) Solution 1 Run L0 : Canalis KSA 250 A, 3L+N+PE - length 55 m: 1 end feed box 250 A + 1 end cover 11 straight elements 250 A - 5m - 2 tap-off outlets / m 20 universal brackets Connectors KSA 3L+N+PE, for circuit-breakers: Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 35 Exercise Connectors KSA 3L+N+PE, for circuit-breakers: 8 connectors 50 A L0 Power - Tracking of the runs Solution 2 Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 36 L1 L2 L3 L4 45 m Exercise Power - Power sum Solution 2 I L1 = (3 I EL + 9 I F + 2 I M )x Ks x 1.2 = (3x4 + 9x7.2 + 2x1.4)x0.6x1,2 = 57 A I L2 = I L1 = 57 A I L3 = (3 I T + 6 I F + 3 I P ) x Ks x 1.2 = (3x7.2 + 6x7.2 + 3x2.7)x0.6x1.2 = 52 A Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 37 Exercise I L4 = (3 I F + 3 I T + 2 I tr + I PT + I PF + I PR )x Ks x 1.2 = (3x7.2 + 6x7.2 + 2x7.2 + 4 + 5.4 + 13.5)x0.6x1.2 = 74 A I L0 = (I L1 + I L2 + I L3 + I L4 )x Ks x 1.2 = (57x2 + 52 + 74)x0.8 x1,2 = 230 A Power - Choice of the busways Solution 2 Work-shop: IP busway > 20 Inc = (K x Ib) / (f1 x f3) Protection of runs by circuit-breaker K = 1 Ambient temperature = 30C f1 = 1 Edgewise mounting = Standard f3 = 1 Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 38 Edgewise mounting = Standard f3 = 1 Inc L1 = 57 A KNA 63 A Inc L1/L2 = 57 A KNA 63 A Inc L3 = 52 A KNA 63 A Inc L4 = 74 A KNA 100 A Inc L0 = 230 A KSA 250 A Exercise Power - Choice of Canalis elements (1/2) Solution 2 Runs L1, L2 and L3: Canalis KNA 63 A, 3L+N+PE - Length 41 m: 1 end feed box 63 A 13 straight elements 63 A - 3 m - 1 tap-off outlet / m 14 universal brackets Connectors KNA 3L+N+PE, for fuses: Run L1: 14 connectors 25 A Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 39 Run L1: 14 connectors 25 A Run L2: 14 connectors 25 A Run L3: 12 connectors 25 A Run L4: Canalis KNA 100 A, 3L+N+PE length 41 m: 1 end feed box 100 A 13 straight elements 100 A de 3 m - 1 tap-off outlet / m 14 universal outlets Connectors KNA 3L+N+PE, for fuses: Run L1: 11 connectors 25 A Exercise Power - Choice of Canalis elements (2/2) Solution 2 Run L0: Canalis KSA 250 A, 3L+N+PE length 55 m: 1 end feed box 250 A 11 straight elements 250 A - 5m - 2 tap-off outlets / m 20 universal brackets Connectors KSA 3L+N+PE, for circuit-breakers: Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 40 Connectors KSA 3L+N+PE, for circuit-breakers: 4 connectors 100 A Exercise Practice Power Lighting Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 41 Lighting - Tracking of the runs Solution 1 Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 42 Exercise Lighting - Power sum Solution 1 I luminaire = (P luminaire +P ballast ) / (U 0 xcos ) = (2*58+5)/(230*0.86) I luminaire = 0.65 I clairage = 12 I Luminaire x Ks x 1.2 = (12x0.65)x1x1.2 = 9,36 A I = 14 I x Ks x 1.2= (14x9,36)x1x1.2 = 157 A Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 43 I feeder = 14 I clairage x Ks x 1.2= (14x9,36)x1x1.2 = 157 A Exercise Lighting - Choice of the busways Solution 1 Work-shop: IP busways > 20 Inc = (K x Ib) / (f1 x f3) Protection of runs by circuit-breakers K = 1 Ambient temperature = 30C f1 = 1 Edgewise mounting = standard f3 = 1 Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 44 Edgewise mounting = standard f3 = 1 Inc L lighting = 9,36 A KBA 25 A - 1L+N+PE Inc L feeder = 157 A KSA 160 A Exercise Lighting - Choice of the tracking Solution 2 Schneider Electric / E&S Bernard Genoulaz 14/12/2005 - FR 45 Exercise