The compressor's discharge temperature is often an overlooked temperature when

troubleshooting a refrigeration or air conditioning system. However, it is very important


because it's an indication of the amount of heat absorbed in the evaporator and suction line,
and any heat of compression generated by the compression process.
Because the compressor's discharge temperature is superheated, a pressure-temperature
relationship does not exist and it must be read directly on the discharge line by some sort of
temperature-measuring device.
The compressor's discharge temperature should be measured about 1 to 2 inches away from
the compressor on the discharge line. This discharge temperature should never exceed 225F.
Carbonization and oil breakdown can occur if compressor discharge temperatures exceed
225.
The three causes for high discharge temperatures are:
High condensing temperature.
Low evaporator pressures and temperatures.
High compression ratios.
HIGH CONDENSING TEMPERATURE
There are many potential causes of high compressor discharge temperatures. A high
condensing temperature is one of them.
When the condensing temperature is high, the compressor must compress the refrigerant from
the low-side (evaporating) pressure to an elevated high-side (condensing) pressure. This
added work done by the compressor would raise the heat of compression. Thus, the
compressor's discharge temperature will be higher.
Remember, condensing temperature is the temperature the refrigerant is as it changes from a
vapor to a liquid in the condenser. There is a pressure-temperature relationship with the
condensing temperature because of the phase change. A gauge reading on the high side of the
system is all that is needed to find the condensing temperature. Convert this pressure to a
temperature using a pressure-temperature chart. This is the condensing temperature.
However, there are many causes for high condensing temperatures, which will also cause
high discharge temperatures; high condensing temperatures cause high compressor discharge
temperatures. Listed below are causes for high condensing temperatures:
Dirty condenser.
High ambient temperature.
Noncondensable (air) in the system.
Condenser fan out.
Restricted airflow over condenser.
Refrigerant overcharge.
Wrong refrigerant.
High heat load on evaporator.
LOW EVAPORATOR PRESSURES AND TEMPS
Low evaporator pressures also may cause a high compressor discharge temperature. When
evaporator pressures are low, the compressor must compress refrigerant from this lower
evaporator pressure to the condensing temperature. This added work of compression would
make the heat of compression higher. Thus, the compressor's discharge temperature will be
higher.
Remember, evaporator temperatures are the temperature of the refrigerant as it changes from
a liquid to a vapor in the evaporator. There is a pressure-temperature relationship with the
evaporating temperature because of the phase change.
A gauge reading on the low side of the refrigeration system is all that is needed to find the
evaporating temperature. Convert this pressure to a temperature using a pressure-temperature
chart. This will be the evaporating temperature.
However, there are many causes for low evaporating pressures and temperatures, which will
also cause high compressor discharge temperatures, since low evaporating pressures cause
high compressor discharge temperatures. Listed below are causes of low evaporator
pressures:
Dirty evaporator coil.
Iced up evaporator coil.
Evaporator fan motor out.
Shortage of airflow over the evaporator.
Frosted evaporator coil from high humidity.
Frosted evaporator coil from a bad defrost heater or other defrost component malfunction.
Low heat load on the evaporator coil.
Defrost intervals set too far apart on the time clock.
Undercharge of refrigerant.
End of the running cycle.
Partially plugged filter-drier.
Compressor inlet screen partially plugged.
Restricted liquid line.
Wrong refrigerant.
Metering device starving.
HIGH COMPRESSION RATIOS
High compression ratios are a result of high condensing pressures or low evaporator
pressures, or both. So, any time there are high condensing pressures or low evaporator
pressures, or both, there will be high compression ratios. And, anytime there is a high
compression ratio either from high condensing or low evaporator pressures, or both, there
will be more work added to the compression stroke of the compressor. This will cause the
heat of compression to increase and the compressor will have a higher discharge temperature.
Compression ratio is defined as the absolute discharge pressure divided by the absolute
suction pressure. Discharge pressure and condensing pressure are one in the same and will be
used interchangeably throughout this article. The same holds true for suction pressure and
evaporating pressure.
Compression ratio = Absolute discharge pressure Absolute suction pressure
A compression ratio of 8 to 1 (expressed as 8:1) simply means that the discharge pressure is 8
times the magnitude of the suction pressure.
Again, a compression ratio of 12.3:1 simply indicates to the technician that the "absolute" or
true discharge pressure is 12.3 times as great as the absolute suction pressure.
VOLUMETRIC EFFICIENCY
The volumetric efficiency is expressed as a percentage from 0 percent to 100 percent.
Volumetric efficiency is defined as the ratio of the actual volume of the refrigerant gas
pumped by the compressor to the volume displaced by the compressor pistons. A high
volumetric efficiency means that more of the piston's cylinder volume is being filled with
new refrigerant from the suction line and not re-expanded clearance volume gases. The
higher the volumetric efficiency, the greater the amount of new refrigerant that will be
introduced into the cylinder with each down stroke of the piston, and thus more refrigerant
will be circulated with each revolution of the crankshaft.

The system will now have better capacity and a higher efficiency. So, the lower the discharge
pressure, the less re-expansion of discharge gases to suction pressure. Also, the higher the
suction pressure, the less re-expansion of discharge gases, because of the discharge gases
experiencing less re-expansion to the higher suction pressure and the suction valve will open
sooner.
The compressor's volumetric efficiency depends mainly on system pressures. In fact, the
farther apart the discharge pressure's magnitude is from the suction pressure's magnitude, the
lower the volumetric efficiency is because of more re-expansion of discharge gases to the
suction pressure before the suction valve opens. Compression ratio is the ratio that measures
how many times greater the discharge pressure is than the suction pressure; in other words,
their relative magnitudes. Remember, a compression ratio of 10:1 indicates that the discharge
pressure is 10 times as great as the suction pressure, and a certain amount of re-expansion of
vapors will occur in the cylinder before new suction gases will enter.
This is why lower compression ratios will cause higher volumetric efficiencies and lower
discharge temperatures. So, keep those compression ratios as low as possible by keeping
condensing pressures low and evaporator pressures high.