ETA ENGlhlEERIMG PRIVATE LIMITED

503-504, Prakash Deep Building, 7, Tolstoy Marg, New Delhi - 110001


Ph. : 01 1-26451115/6/7/8,43743800,41520840/43
Fax : 01 1-43743866,41520844
Email : etametro@vsnl.net
Ref: ETA/ICMLl9MWlBClSClKW078
Date: August 11, 201 1
DGM-BUSINESS DEVELOPMENT (POWER)
MI S CESC LIMITED
CESC House
Chowringhee Square
Kolkata - 700001
West Bengal
KIND ATTN: MR ADRlT PALCHOUDHURY
SUB: ICML, 9MWp SOLAR POWER PROJECT AT PRATAPGARH, DIST.
KUTCH, GUJARAT - SUBMISSION OF BASIC DESIGN FOR FIRE
PROTECTION SYSTEM.
Dear Sir,
This is in reference to the subject project. We are pleased to attach herewith
documents of Basic Design for Fire Protection System.
We hope the above is in line with your requirements and would request you to
kindly let us have your kind approval for the same to enable us to proceed
further in the interest of the project.
Thanking you and assuring you of our best services at all times.
Yours faithfully,
for ETA ENGINEERING PVT LTD.
,WAURABH CHAUHAN
GENERAL MANAGER
Encl: as above
Regd. Office : 5, Moores Road, Chennai - 600 006 Tamil Nadu, India
Branches (Tel.) - Bangalore : 41802300, Chennai : 28297626, Hyderabad : 27763529130, Mumbai : 67742700, Pune : 26051310, Kolkata : 24864329
SUBMISSION
TRANSMITTAL FORM
m e -
1 n w. t c r w~ c - , I C?r*a~ ICI vr sl r l y-
~A.,..*u <.'I
Prepared By
Gaurav
Details
Approved By
PROJECT : 9MWp GRID INTERACTIVE SOLAR PV
POWER PROJECT
CUSTOMER : INTEGRATED COAL MINING LIMITED -
GUJARAT
CONTRACTOR : ETA ENGINEERING PVT LTD
Submission Phase:
I DRAWINGS I DOCUMENT
VENDOR & TECHNICAL SUBMITTAL
CONSTRUCTION DOCUMENTS
REPORTS
RECORDS
Submission Number: I First Second Third Fourth
Submission Contents.
Checked By
Saurabh Tripathi
Name
Sr.No.
1.
Reviewed By
Kapil
For Information W For Approval As Built
ETA:
ICML:
j
DOCUMENT TRAIVSMZTTAL. REF. DOC
ETA-SOLAR-TRANS-46
..
System Description
FIRE PROTECTION
SYSTEM
Description of the Document
BASIC DESIGN- SYSTEM 6 FIRE
PROTECTION SYSTEM
Approved By
f S a u r q h Chauhan
u
Designation
Rev No
00
Sign
FIRE PROTECTION SYSTEM
PURPOSE:
An automatic fire alarm system is designed to detect the unwanted presence offire by
monitoring environmental changes associated with combustion. In general, a fire alarm system is
classified as either automatically actuated, manually actuated, or both. Automatic fire alarm
systems are intended to notify the building occupants to evacuate in the event of a fire or other
emergency, report the event to an off-premises location in order to summon emergency services,
and to prepare the structure and associated systems to control the spread of fire and smoke.
DESTGN:
After the fire protection goals are established - usually by referencing the minimum levels of
protection mandated by the appropriate model building code, insurance agencies, and other
authorities - the fire alarm designer undertakes to detail specific components, arrangements, and
interfaces necessary to accomplish these goals. Equipment specifically manufactured for tl~ese
purposes are selected and standardized installation methods are anticipated during the design
Fundamental Configuration
a) Initiating Devices
Manually actuated devices; Break glass stations, Buttons and manual fire alarm
activation are constructed to be readily located (near the exits), identified, and operated.
Automatically actuated devices can take many forms intended to respond to any number
of detectable physical changes associated with fire: convicted thermal energy; heat
detector, products of combustion; smoke detector, radiant energy; flame detector,
combustion gasses; carbon monoxide detector and release of extinguishing agents; water-
flow detector. The newest innovations can use cameras and computer algorithms to
analyze the visible effects of fire and movement in applications inappropriate for or
hostile to other detection methods.
b) Notification Appliances
Audible, visible, tactile, textual or even olfactory stimuli (odorizer) to alert the occupants
Evacuation signals may consist of audible or visible appliances with a distinct audible
tone or speakers to deliver live or pre-recorded instructions to the occupants.
FIRE PROTECTION SYSTEM FOR 9 MWp GRID INTERACTIVE SOLAR PV PLANT
a) In each of the nine PCU rooms there is one number of optical smoke detector to detect
the presence of any fire condition and flasher are installed outside the PCU room which
will indicates the fire condition in their respective PCU rooms. As PLC's are located in
each of the PCU room so a smoke detector acts as digital input to that PLC and flasher
outside the PCU room acts as a digital output to that PLC. In case of any fire condition
i.e. smoke a digital input is received by plc which switches on the flasher outside the
PCU room to indicate the emergency condition. Plc is mounted with acknowledgement
button to acknowledge the fire condition.
b) Any fire condition inside the main control room is communicated through main PLC
panel located in PCU room number five through seven detectors placed inside the Main
Control Room.
c) Manual call points are installed outside each PCU room, three numbers in main control
room at the exit and entrance, and one number inside the guard room to activate the alarm
condition in case required.
d) Guard room is equipped with one PLC looped with main plc through a fiber optic cable
and connected to an alarm annunciator panel inside the guard room to visualize the alarm
condition in any of the PCU rooms and main control room.
e) Hooters are installed inside the guard room and are activated in case of any fire condition
in any of the rooms.
f ) Any of the fire condition in the plant installed with detectors will be indicated in the
SCADA.
g) The PLC's used for Fire Protection System and SCADA are same.
NOTE: Please refer to the system architecture of Fire Protection System.