Вы находитесь на странице: 1из 8

Sr.

No
DATE
Equipment Tag
No with
Description
START TIME
STOP
TIME
Total Time kw
1 23-Mar 01:15Pm 01:30Pm 15Mins 22
2 29-Apr 7:40Pm 7:45Pm 5Mins 22
3 15-Mar 1:00Pm 1:15Pm 15Mins 22
4 16-Mar 4:30AM 4:40AM 10 mins 22
5 18-Mar 4pm 4 10 pm 10 mins 22
6 3-Apr 4:30PM 6:30PM 2 Hours 22
7 3-Feb 8:30Pm 8:40Pm 10Mins 22
8 18-Feb 2:30AM 2:35AM 5 mins 22
9 25-Feb 6pm 6:10pm 10 mins 22
10 9-Mar 5:35PM 5:45PM 10Mins 22
11 13-Apr 4:00PM 4:05PM 5 mins 22
12 4-Feb 11:30AM 11:40AM 10Mins 22
13 4-Feb 03:30Pm 03:50Pm 20Mins 22
14 4-Feb 11:30AM 11:40AM 10Mins 22
15 9-Feb 4:30PM 4:45PM 15 mins 22
16 18-Feb
10:00AM
11:30AM
1:00PM
10:05AM
11:35AM
1:05PM
5 MINS 22
17 19-Feb 11:35PM 11:40PM 5 MINS 22
18 20-Feb 12:30PM 12:35PM 5mins 22
CELL MOTOR TRIPPING DETAILS
5AG-03F
5AG-03G
5AG-05E
5AG-05I
19 14-Apr 10:40PM 11:00PM 20Mins 22
20 25-Feb 5:30AM 5:35AM 5 mins 22
21 28-Feb
2:30PM
9:30PM
2:35PM
9:35PM
5 mins 22
22 24-Apr 1:20AM 1:30AM 10 MIns 22
23 24-Apr 2:20AM 2:25AM 5Mins 22
24 27-Feb 6AG-03B 6:50PM 6:53PM 3 mins 22
25 24-Feb
2:00AM
3:00AM
2:15AM
3:15AM
15mins 22
26 25-Feb 11:30PM 11:40PM 10 MINS 22
27 25-Feb 3:00AM 3:05AM 5 mins 22
28 26-Feb 6:35AM 6:40AM 5 mins 22
29 27-Feb 5:35AM 5:40AM 5 mins 22
30 27-Feb 10:50PM 11:53PM 10 mins 22
31 28-Feb
10:30PM 10:35PM
6 mins 22
32 26-Mar 4:00Am 8:30Am 4.30Hrs 22
33 16-Apr 3:30AM 3:35AM 5Mins 22
34 25-Apr 0.375 9 10 am 10 mins 22
35 24-May 11PM 11:05PM 5 mins 22
36 26-May 2:10am 2:15AM 5 mins 22
6Ag-06A
5AG-05I
6AG-03A
6Ag-03C
tripping
current
38
38
38
38
38
38
38
38
38
38
38
37
38
38
40
38
38
38
CELL MOTOR TRIPPING DETAILS
38
38
38
40
40
38
38
38
38
38
38
38
38
38
40
44
40
40
Type of Tripping with reason and rectification
Motor was tripped due to thermal overload. It was reset and started again and taking 38A
Motor was tripped due to thermal O/L. It was reset and started again. Now running fine and taking 35A
Motor was tripped due to thermal O/L. It was reset and started again. Now running fine and taking 34A
Motor was tripped due to thermal overload. It was reset and started again. Now running fine and taking
34A
motor tripped on overload. It was reset and started. And on motor side vibrations are noticed. So better
motor bearings should be replaced on tomorrow.
Motor tripped on Earth fault. So previous 5AG-03G motor was fixed in that. Running fine now. Taking 30-
31A on load.
Motor Was tripped due to thermal overload. It was reset and started again. Now running fine & taking
37.5A
Process water line got jammed, So slurry becomes viscous. Due to this motors are tripped. Reset &
Started. Taking 38A-40A
Motor tripped on overload. Loose connection found on Y-ph connecting 42x contactor. It was tightened
and started. Motor taking 36-38A on load.
tripped due to thermal overload. No problem found .Feeder was reset & Started. Now taking 36A.
Tripped due overload. Process dept was asked to maintain proper supply of air and water into the cell.
Feeder was reset and started , taking 40A now.
Motor Was tripped due to thermal overload. It was reset and started again. Now running fine & taking
26A
Motor Was tripped due to thermal overload. After adjusting of air pressure, motor was reset and
started again. Now running fine & taking 37.4A
Motor Was tripped due to thermal overload. It was reset and started again. Now running fine & taking
26A
motor tripped on thermal overload fault. It was reset and turned on. Now drawing 40-42A. Process dept
was told to increase the air+water supply.
Motor tripped thrice due to thermal overload. I/C cables to cantactor are req to be replaced soon. Now
motor drawing 36-37A.
tripped due to thermal overload. From process side air pressure was increased.Feeder was reset &
Started. Now taking 36A.
tripped due to thermal overload. From process side air pressure was increased.Feeder was reset &
Started. Now taking 35A.
CELL MOTOR TRIPPING DETAILS
Motor was trip due to thermal overload. Reset & Started. Took 55A while starting, After sometime ( Air
was increased & Water added in the cell ) it is taking 28-32A.
Motor tripped on overload. It was reset and started. Motor taking 36-38A on load.
Motor tripped on overload. It was reset and started. Motor taking 40A on load.
Motor tripped on overload, Reset and started. And it was taking 42A. Informed to process to adjust the
flow then it was taking 36A. Running fine now.
Motor tripped on overload, Reset and started. And it was taking 43A. Informed to process to adjust the
flow then it was taking 33A. Running fine now.
Motor tripped on overload. It was reset and started. Motor taking 36A on load.
42x contactor R-phase outgoing cable was found burnt. Feeder was replaced. New feeder MPCB is
require to be replaced. (28-40A) motor rated current-38A
Motor tripped on overload. It was reset and started. Motor taking 36-38A on load.
Motor tripped on overload. It was reset and started. Motor taking 36-38A on load.
Motor tripped on overload. It was reset and started. Motor taking 36-38A on load.
Motor tripped on overload. It was reset and started. Motor taking 36-38A on load.
Motor tripped on overload. It was reset and started. Motor taking 36A on load.
Motor tripped on overload. It was reset and started. Motor taking 40A on load.
Motor tripped on overload. While checking motor side terminal box, One & two winding found broken
& motor cable was found burnt. Motor was replaced with new one. After motor connection trial was
taken and it is running fine & taking 32A
Motor tripped on overload, Reset and started. While runnig its taking 34A ( Air pressure adjusted)
tripped on overload. And feeder MPCB got damaged and so feeder replaced with spare feeder(Emg
MCC - 8F7) and started. On spare feeder MPCB needs to be changed
Motor was tripped due to thermal O/L. It was reset and started again. Now running fine and drawing 39
A.
Motor was tripped due to thermal O/L. It was reset and started again. Now running fine and taking 37
A..
Effect of
Production or
Not from
Electrical side
Name of Shift
Engineer
no Pitamber
no Pitamber
no Pitamber
no avinash
no vinoth
Yes Linges
no Pitamber
Yes Linges
no vinoth
no Linges
no avinash
no Linges
no Pitamber
no Pitamber
no avinash
no avinash
no Linges
no avinash
CELL MOTOR TRIPPING DETAILS
no Linges
no avinash
no avinash
no Linges
no Linges
no Linges
no avinash
no avinash
no avinash
no Deepna
no vinoth
no vinoth
no vinoth
no
Linges,
Pitamber
no Linges
no vinoth
Yes Linges