Вы находитесь на странице: 1из 2

ALPU-BSA

10701 Airport Drive, Hayden ID 83835


208.772.8515 800.882.9110
1 . I M P O R T A N T S A F E T Y A N D I N S T R U C T I O N S ! T h i s d e v i c e
s h o u l d o n l y b e i n s t a l l e d b y q u a l i f i e d p e r s o n n e l .
2 . R e a d a n d u n d e r s t a n d a l l i n s t r u c t i o n s b e f o r e i n s t a l l i n g
t h i s p r o d u c t . S a v e t h e s e i n s t r u c t i o n s f o r f u t u r e r e f e r e n c e .
3 . ! S A V E T H E S E I N S T R U C T I O N S !
1200-151-1 REV. B
T h a n k y o u f o r p u r c h a s i n g a s u r g e s u p p r e s s i o n p r o d u c t f r o m
T r a n s t e c t o r , t h e i n d u s t r y l e a d e r .
F o r q u e s t i o n s o r c o m m e n t s , p l e a s e c o n t a c t u s a t
8 0 0 . 8 8 2 . 9 1 1 0 o r v i s i t o u r w e b s i t e a t w w w . t r a n s t e c t o r . c o m .
ALPU-BSA
1. This product is intended for use only on data circuits with operating
voltages not to exceed 12VDC and DC power circuits with operating
voltages not to exceed 48VDC and operating currents not to exceed 10A.
2. Mounting the ALPU-BSA (See Diagram): Mount the device as close to
the equipment to be protected as possible using the provided hardware
and the concealed mounting holes. Mount the unit in the orientation
shown.
3. Wiring the ALPU-BSA
3.1 The ALPU-BSA surge suppressor is bidirectional and may be
wired in either orientation.
3.2 Removing the Cover: Remove the 4 cover screws using a Phillips
screwdriver and lift off the cover.
3.3 Wiring the CAT-5 Data Section: Thread a multiconductor cable
from the data source through one of the strain reliefs on the side of
the unit. Strip back the cable jacket as needed, crimp on RJ J acks
and plugs into J ack on circuit board. (Do not ove torque!!). Repeat
this procedure for the outgoing multiconductor cable running to the
equipment to be protected.
3.4 Wiring the Coax 36VDC Section Thread a coax cable from the
power source through one of the strain reliefs on the bottom of the
unit. Strip back the cable jacket and insulator as needed and
terminate the cable with a male F connector. Install the terminated
cable into the corresponding female F connector. Tighten the strain
relief onto the cable. Repeat this procedure for the outgoing coax
cable running to the equipment to be protected.
3.5 Reinstall the cover.
3.6 Grounding: Connect the external ground lug on the enclosure to a
solid Earth ground. The unit must be grounded for the suppressor to
operate properly!
800.882.9110 or 208.772.8515
Note: It is recommended that weatherproof tape be installed
around each cable entrance and around the seam between
the enclosure and the cover for added protection against
violent rainstorms.
C
O
N
C
E
A
L
E
D

M
O
U
N
T
I
N
G
H
O
L
E
S
STRAIN RELIEF ACCEPT
CABLE DIAM. RANGE
0.250" THRU 0.375"
EXTERNAL GND LUG
ACCEPTS 4-14 AWG