Compressor Seems Excessively

Noisy At Start-up (High Pitch) Unloading Valve


Energize coil to
Suction Service Valve
Max temp 65F, 6” from
Motor Temperature
(5K thermistor connection
Suction load compressor the service valve on terminal plate)
 Insure oil feed lines are open (oil solenoid). Access Port
Min Pressure
 Check oil pressure at compressor manifold 10” vacuum Economizer/
Subcooler Port
with a gauge. Discharge
Service Valve
Max Temp 230F,
6” from the service
(not shown)
Rotalock valve,
7/8” sweat
connection
Screw Compressor
Compressor Makes a Loud Grinding
Noise at Start-up
valve (5K thermistor
strapped to
discharge line)
must have
15F - 20F
superheat
Troubleshooting
 Oil solenoid is leaking oil into the
Oil Port Access Port
Guide
compressor while off. Repair or replace Discharge Access Port (1/4” Schrader, not shown)
oil solenoid. Max Press Differential
Liquid
Injection Port
For field gauge connections

 Compressor filling with refrigerant while (discharge - suction) 350psid


(3/8” Flare,
Oil Press Transducer
Max Press Differential
used if necessary)
off. Determine refrigerant source and VI (Volume Index)
Valve energize coil at
(discharge - oil) 50psi
Oil Inlet Min Differential Pressure
eliminate during compressor off cycle. pressure ratios > 5:1 (3/8” Flare) (Oil - Suction) 45psi

 Check evaporator superheat.

Compressor Periodically Makes Caution: Never Run the


Loud Noise or Becomes Very Quiet Compressor in Reverse!
for a Short Time
 Check for excessive liquid/oil return 06T Model
to compressor.

Support/Contact
 Call Application Engineering for further
assistance at 800.532.5036. Carlyle Compressor Division
P. O. Box 4808
Syracuse, NY 13221
Phone: 800.532.5036
Fax: 315.432.3274
05T Model
0604 Lit. No. 574-081 Rev. A
Reverse Rotation Trips Thermal Protection
(High Motor Temperature) Trips
At initial start-up:
 Compressor is running in reverse,  Check economizer rotalock valve to insure  Insure liquid feed is available to the valve(s).
check phase sequence and bump it is open.  Add refrigerant charge if necessary.
compressor to insure proper rotation  Check superheat from economizer expansion  Check economizer rotalock valve to insure
valve. it is open.
(check pressure at outlet port).
 Check motor cooling valve for operation to  Check superheat from economizer expansion
insure liquid is feeding. valve.
 Insure LonCEM module and discharge  Verify motor cooling valve is downstream of  Check for high system discharge pressure.
pressure transducer are wired and check valve.  If desuperheating valve is not installed,
functioning correctly.  Verify motor thermistor wiring from module to check application to insure it is not required.
compressor terminal plate.
When compressor cycles off: Low Oil Level Switch Cutout
Circuit Breaker Trips
 Pressure switch set too high, reset as  Check for adequate oil charge (fill to top
low as necessary (older systems with  Check contactor. Replace if damaged. separator sightglass).
reverse rotation switch).  Compressor full of oil due to oil solenoid  Check discharge superheat (less than 20°F
manually open or stuck open. Repair or will cause high carryover past separator).
Oil Pressure Differential Trips replace solenoid.  Check for high pressure system transients
 Tighten and recheck all power and control (rapid pressure changes in the discharge).
 Insure all manual oil line valves are open. circuit wiring connections.
 Check pressure drop through oil system,  Short cycling of compressor. Adjust controls Low Compressor Capacity
oil filters may have to be changed. to limit compressor cycles.
 Check operation of economizer (is liquid
 Insure oil line solenoid is functioning properly.  Check circuit breaker. If incorrect, install
temperature at evaporator txv as expected).
 Insure LonCEM module and pressure trans- correct breaker.
 Verify unloader is energized. Check wiring
ducers are wired and functioning properly.  High discharge pressure. Check condenser
and power source.
control and operation.
 Check unloader coil and replace if bad.
 Check voltage. If low, verify power supply.
 Check unloader valve. Replace unloader
Thermal Protection assembly (Part # 06NA660001).
 Remove clogged suction filter, clean and
(High Discharge Temperature) Trips reinstall.
 Check internal pressure relief valve.
 Check motor cooling valve for operation. If blown, replace compressor.
 Verify size of motor cooling valve and desuper-
heating valve (where applicable).