APPENDIX B COMMAND CROSS-REFERENCE

INTRODUCTION
This appendix lists all ASCII commands, command syntax, brief command descriptions, and any
corresponding HMI screens. Commands are organized by function in the following groups and tables.
&
&
&
&
&
&

Miscellaneous (Table B-1)


Metering (Table B-2)
Control (Table B-3)
Report (Table B-4)
Setting (Table B-5)
Alarm Setting (Table B-6)

&
&
&
&
&
&

General Setting (Table B-7)


Breaker Monitoring and Setting (Table B-8)
Programmable Logic Setting (Table B-9)
User Programmable Name Setting (Table B-10)
Protection Setting (Table B-11)
Global (Table B-12)

An entry of x in the HMI Screen column represents multiple entry possibilities such as 0, 1, 2, or 3 for setting
groups or 43, 143, 243, or 343 for virtual switches.

Table B-1. Miscellaneous Commands


ASCII Command

Function

HMI Screen

ACCESS[=<password>]

Read/Set access level in order to change


settings.

N/A

EXIT

Exit programming mode.

N/A

HELP <cmd> or H <cmd>

Obtain help with command operation.

N/A

Table B-2. Metering Commands


ASCII Command

Function

HMI Screen

Read all metered values.

N/A

M-FREQ

Read metered frequency.

3.9

M-SYNC

Read metered sync angle between GEN


and BUS inputs.

M-I[<phase>]

Read metered current in primary unit.

M-PF

Read metered three-phase power factor.

3.8

M-S

Read metered three-phase VA in primary


units.

3.8

M-V[<phase>]

Read metered voltage in primary units.

M-VAR or M-Q

Read metered three-phase vars in


primary units.

3.7

M-3V0

Read calculated neutral voltage.

3.3

M-WATT or M-W or M-P

Read metered three-phase watts in


primary units.

3.7

3.4, 3.5, 3.6

3.1, 3.2, 3.3

Table B-3. Control Commands


ASCII Command

Function

HMI Screen

CO-<control>[=<mode>]

Control operation.

N/A

CS-<control>[=<mode>]

Control selection.

N/A

BE1-GPS100

Appendix

B-1

ASCII Command

Function

HMI Screen

CS/CO-43

Control virtual switches

2.1.x

CS/CO-101

Control breaker control switch

2.2.1

CS/CO-GROUP

Control group

2.3.1

CS/CO-OUTn

Control output n

2.4.1

Table B-4. Report Commands


ASCII Command

Function

HMI Screen

RA[=0]

Report/Reset alarm information.

1.3

RA-LGC[=0]

Report/Reset logic alarm information.

N/A

RA-MAJ[=0]

Report/Reset major alarm information.

N/A

RA-MIN[=0]

Report/Reset minor alarm information.

N/A

RA-REL[=0]

Report/Reset relay alarm information.

N/A

RB

Read breaker status.

1.5.6

RB-DUTY[<phase>[=%duty>]]

Read/Set breaker contact duty log.

4.3.2

RB-OPCNTR[=<#operations>]

Read/Set breaker operation counter.

4.3.1

RD

Report all demand data.

N/A

RD-PI[<p>[=0]]

Read/Reset peak demand current.

RD-PVAR[=0]

Read/Reset peak demand vars.

4.4.3.8 (+)
4.4.3.9 ()

RD-PWATT[=0]

Read/Reset peak demand watts.

4.4.3.6 (+)
4.4.3.7 ()

RD-TI[<p>]

Report todays demand current.

4.4.1.14.4.1.5

RD-TVAR

Report todays demand vars.

4.4.1.8 (+)
4.4.1.9 ()

RD-TWATT

Report todays demand watts.

4.4.1.6 (+)
4.4.1.7 ()

RD-YI[<p>]

Report yesterdays demand current.

RD-YVAR

Report yesterdays demand vars.

4.4.2.8 (+)
4.4.2.9 ()

RD-YWATT

Report yesterdays demand watts.

4.4.2.6 (+)
4.4.2.7 ()

RE

Report all energy data.

RE-KVARH[=0]

Read/Reset three-phase varhours.

4.5.3 (+)
4.5.4 ()

RE-KWH[=0]

Read/Reset three-phase watthour.

4.5.1 (+)
4.5.2 ()

RF[-n/NEW][=0/TRIG]

Read/Reset fault report data.

N/A

RG

Report general information.

N/A

RG-DATE[=<M/D/Y>] or RG-DATE[=<D-M-Y>]

Read/Set date.

4.6

RG-STAT

Report relay status.

N/A

B-2

Appendix

4.4.3.14.4.3.5

4.4.2.14.4.2.5

N/A

BE1-GPS100

ASCII Command

Function

HMI Screen

RG-TARG[=0]

Report/Reset target status.

1.2

RG-TIME[=hr:mn:sc] or RG-TIME[=hr:mn<f>sc]]

Report/Set time.

4.6

RG-VER

Read program version, model number,


style number, and serial number.

4.7

RO-nA/B[#].CFG/DAT

Read oscillographic fault report.

N/A

RS[-n/Fn/ALM/IO/LGC/NEW][=0]

Read oscillographic
COMTRADE.DAT/.CFG fault report.

N/A

Table B-5. Setting Command


ASCII Command

Function

Read all relay setting parameters.

HMI Screen
N/A

Table B-6. Alarm Setting Commands


ASCII Command

Function

HMI Screen

SA

Read all major and minor alarm settings.

N/A

SA-BKR[n][=<mode>,<alarm limit>]

Read/Set breaker alarm settings.

N/A

SA-DI[p][=<alarm level>]

Read/Set demand alarm settings.

N/A

SA-DVAR[=<alm lvl>,<alm lvl>]

Read/Set var demand alarm setting.

N/A

SA-DWATT[=<alm lvl>,<alm lvl>]

Read/Set watt demand alarm setting.

N/A

SA-LGC[=<alarm num 1>[/<alarm num 2>] . . .


[<alarm num n>]]

Read/Set logic alarm setting mask.

N/A

SA-MIN[=<alarm num 1>[/<alarm num 2>] . . .


[<alarm num n>]]

Read/Set minor alarm setting mask.

N/A

SA-MAJ[=<alarm num 1>[/<alarm num 2>] . . .


[<alarm num n>]]

Read/Set major alarm setting mask.

N/A

SA-RESET[=<rst alm logic>]

Read/Set programmable alarms reset


logic.

N/A

Table B-7. General Setting Commands


ASCII Command

Function

HMI Screen

SG

Read all general settings.

N/A

SG-CLK[=<date format(M/D)>,<timeformat(12/24)>]

Read/Program time and date format .

N/A

SG-COM[#[=<baud>,A<addr>,P<pglen>,
R<reply ack>,X<XON ena>]]

Read/Set serial communication protocol.

6.1.1-6.1.3

SG-CT[t][=<CTratio>]

Read/Set Phase/Neutral CT ratio.

6.3.1, 6.3.2

SG-DI[p][=<interval>]

Read/Set P(IA/IB/IC/var/watt), N and Q


demand interval.

N/A

SG-DSP[P/N]

Read analog signal dsp filter type.

N/A

SG-FREQ[=<freq(Hz)>]

Read/Enter power system frequency.

6.3.6

SG-HOLD[n][=<1/0 hold ena>]

Read/Program output hold operation.

N/A

SG-ID[=<relayID>,<StationID>]

Read/Set relay ID and station ID used in


reports.

N/A

BE1-GPS100

Appendix

B-3

ASCII Command

Function

HMI Screen

SG-IN[#[=<r(ms)>,<db(ms)>]]

Read/Set input recognition/denounce.

N/A

SG-PHROT[=<phase rotation>]

Read/Set phase rotation setting.

6.3.7

SG-SCREEN[n][=<default screen number>]

Read/Set default screen(s).

N/A

SG-SGCON[=<time>]

Read/Set SGC output on time.

N/A

SG-TARG[=<x/x/...x>,<rst TARG logic>]

Report/Enable Target List and Reset


Target Logic.

N/A

SG-TRIGGER[n][=<TRIPtrigger>,<PUtrigger>,
<LOGIC trigger>]

Read/Set trigger logic.

N/A

SG-VTP[=<VT ratio>,<connection>,
<27/59mode>,<51/27Rmode>]

Read/Set VT ratio, connection, and 27/59


pickup mode.

6.3.4

SG-VTX[=<VT_ratio>,<connection>]

Read/Set Aux. VT ratio and connection.

6.3.5, 6.3.6

Table B-8. Breaker Monitoring and Setting Commands


ASCII Command

Function

HMI Screen

SB

Read all breaker settings.

N/A

SB-DUTY[=<mode>,<DMAX>]

Read/Set breaker contact duty.

N/A

SB-LOGIC[=<breaker close logic>]

Read/Set breaker contact logic.

N/A

Table B-9. Programmable Logic Setting Commands


ASCII Command

Function

HMI Screen

SL[:<name>]

Obtain setting logic information.

N/A

SL-24[=<mode>,<BLK logic>]

Read/Set logic for 24 function modules.

N/A

SL-25[=<mode>,<BLK logic>]

Read/Set logic for 25 function modules

N/A

SL-<f>27[<p>[=<mode>,<BLK logic>]]

Read/Set logic for 27 function modules.

N/A

SL-46[=<mode>,<BLK logic>]

Read/Set logic for 46 function modules.

N/A

SL-47[=<mode>,<BLK logic>]

Read/Set logic for 47 function modules.

N/A

SL-x50T[<p>[=<mode>,<BLK logic>]]

Read/Set logic for x50 function modules.

N/A

SL-x51[<p>[=<mode>,<BLK logic>]]

Read/Set logic for 51 function modules.

N/A

SL-<f>59[<p>[=<mode>,<BLK logic>]]

Read/Set logic for 59 function modules.

N/A

SL-<f>62[=<mode>,<INI logic>,<BLK logic>]

Read/Set logic for 62 function modules.

N/A

SL-<f>81[=<mode>,<BLK logic>]

Read/Set logic for 81 function modules.

N/A

SL-BF[<p>[=<mode>,<INI logic>,<BLK logic>]]

Read/Set logic for breaker failure function


modules.

N/A

SL-GROUP[=<mode>,<D0 logic>,<D1 logic>]

Read/Set logic for setting group module.

N/A

SL-N[=<name>]

Read, set, or copy the name of the


custom logic.

N/A

SL-VO[#[=<Boolean equation>]]

Read/Set output logic.

N/A

Table B-10. User Programmable Name Setting Command


ASCII Command

B-4

Function

Appendix

HMI Screen

BE1-GPS100

SN[-<var>[=<name>,<TRUE label>,<FALSE label>]]

Read/Set user programmable names.

N/A

Table B-11. Protection Setting Commands


ASCII Command

Function

HMI Screen

S<g>

Read all protection settings.

N/A

S<g>-24[=<pu(V/Hz)>,<td>,<rst>]

Read/Set 24 pickup level, time delay and


reset delay

S<g>-25[=<volts>,<ang>,<slip>,<mode>]

Read/Set 25 delta volts, phase angle, slip


frequency and mode

S<g>-<f>27[<p>[=<pu(V)>,<td(m)>]

Read/Set 27 pickup level, time delay, and


mode.

5.x.1.1

S<g>-<f>27R[=<pu(V)>,<mode(m)>]

Read/Set (51)/27R control level and


operating mode.

5.x.4.5

S<g>-46[=<pu(A),<td(m)]

Read/Set 46 pickup level, time delay, and


curve

S<g>-47[=<pu(V)>,<td(m)>]

Read/Set 47 pickup level and time delay.

5.x.2.1

S<g>-50TP[=<pu(A)>,<td(m)>]

Read/Set 50TP pickup level and time


delay.

5.x.3.1

S<g>-50TN[=<pu(A)>,<td(m)>]

Read/Set 50TN pickup level and time


delay.

5.x.3.2

S<g>-51P[=<pu(A)>,<td(m)>,<crv>]

Read/Set 51 pickup level, time delay, and


curve.

5.x.4.1

S<g>-<f>51N[=<pu(A)>,<td(m)>,<crv>]

Read/Set 51N pickup level, time delay,


and curve.

5.x.4.2

S<g>-<f>59[<p>][=<pu(V)>,<td(m)>]

Read/Set 59 pickup level, time delay, and


mode.

5.x.5.1
5.x.5.2

S<g>-<f>62[=<t1>,<t2>]

Read/Set 62 time delay.

5.x.6.1

S<g>-81[=<pu(Hz)>,<td(m)>,<mode>]

Read/Set 81 pickup level, time delay, and


mode.

5.x.8.1

S<g>-81INH[=<pu(V)>]

Read/Set 81 undervoltage inhibit level.

5.x.8.7

SP-60FL[=<I_Blk>,<V_Blk>]

Read/Set loss of potential pickup setting.

5.5.2.1
5.5.2.2

SP-BF[=<time>[m/s/c]]

Read/Set the breaker failure timer setting

5.5.1.1

SP-CURVE[=<A>,<B>,<C>,<N>,<R>]

Read/Set the user programmable 51


curve parameters.

N/A

Table B-12. Global Command


ASCII Command
GS-PW<t>[=<password>,<com ports(0/1/2)>]]

BE1-GPS100

Function
Read or change a password.

Appendix

HMI Screen

N/A

B-5