single/dual duct terminal units

M
www.titus-hvac.com | www.titus-energysolutions.com

www.titus-hvac.com | www.titus-energysolutions.com

Table of Contents

SINGLE/DUAL DUCT TERMINALS

M2

Single/Dual Duct Terminals

single/dual duct terminal products


Single/Dual Duct Terminal Products..............................................................................................................................................M3

single duct terminals


ESV Single Duct.............................................................................................................................................................................M4
Design Features.....................................................................................................................................................................M4
Control Strategies..................................................................................................................................................................M6
ESV - Basic Unit with Controls..............................................................................................................................................M8
Accessories............................................................................................................................................................................M9
Performance Data................................................................................................................................................................M12
Electric Coils........................................................................................................................................................................M19
Suggested Specifications.....................................................................................................................................................M21
Model Number Specification...............................................................................................................................................M23
AHRI Certification................................................................................................................................................................M24

dual duct terminals


EDV/MDV Dual Duct....................................................................................................................................................................M25
Design Features...................................................................................................................................................................M25
Control Strategies................................................................................................................................................................M26
EDV - Dual Duct without Attenuator....................................................................................................................................M27
Performance Data................................................................................................................................................................M28
EDV/EDC - Dual Duct with Attenuator.................................................................................................................................M30
Performance Data................................................................................................................................................................M31
MDV/MDC - Dual Duct High Performance Blending...........................................................................................................M33
Performance Data................................................................................................................................................................M34
Suggested Specifications.....................................................................................................................................................M36
Model Number Specification...............................................................................................................................................M37
AHRI Certification................................................................................................................................................................M38

Single/Dual Duct Terminals

Single/Dual Duct Terminal Products

ESV
AVAILABLE CONFIGURATIONS

CONTROL OPTIONS

UNIT ACCESSORIES

With integral attenuator.


With water coils.
With integral electric coil section.

Pneumatic.
Electric.
TA1 electronic.
OEM controls program.
Factory mounting of controls by others.
OEM controls (Titus Alpha BACnet).

Fibre Free lining.


Steri-Loc lining.
UltraLoc lining.
Multi-outlet section.
Round outlet adapter.
EcoShield.
Removable flow sensor.

www.titus-hvac.com | www.titus-energysolutions.com

SINGLE DUCT TERMINALS

pages: M4-M24

DUAL DUCT TERMINALS

pages: M25-M38

AVAILABLE CONFIGURATIONS

CONTROL OPTIONS

UNIT ACCESSORIES

For non-mixing.
With integral attenuator/mixing section.
Special high performance blending.

Pneumatic.
OEM controls program.
Factory mounting of controls by others.
OEM controls (Titus Alpha BACnet).

Fibre Free lining.


Steri-Loc lining.
EcoShield.
Removable flow sensor.

For detailed controls information, please refer to the Terminal Unit Accessories section.

SINGLE/DUAL DUCT TERMINALS

EDV

M3

Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com

Single Duct Design Features

LEADING THE INDUSTRY: THE TITUS ESV SINGLE DUCT VAV TERMINAL
Single duct terminals are the fundamental building blocks
for a variable air volume (VAV) system. Their primary
function is to regulate airflow to a zone, in response to
zone temperature requirements. The Titus ESV is unique
as it incorporates many design features that increase
performance, decrease installation and service cost and
offers increased value, over and above this basic function.
All VAV terminals are not equal! By specifying the Titus ESV,
you are assured of accurate, AHRI Certified performance
ratings. All units are tested, and data shown, in accordance
with AHRI Standards. A wide selection of unit configurations,
accessories and control types provide considerable scope for
problem solving and cost-effective innovation.
The ESVs compact size and easy access for service saves
time and expense in installation. The ESV fits easily

ESV Casing Leakage, cfm


INLET
SIZE
4, 5, 6
7, 8
9, 10
12
14
16

0.5
2
4
4
5
6
7

PS, IN WG
1.0
2.0
3
4
5
7
6
8
7
10
9
13
10
14

3.0
5
9
10
12
16
17

in cramped mechanical spaces, either in new building


construction or retrofit.
Building owners will benefit from the energy efficient low
leakage design, reducing utility expenses. Control accuracy,
especially at minimum flow rates, is easier to achieve with a
Titus multi-point inlet velocity sensor. Control accuracy
is critical in maintaining good air quality reducing energy
waste.
The ESVs standard insulation is a dual density liner. The
skin resists abrasion and erosion from air movement. The
body maximizes thermal and acoustical performance. The
Titus single blade damper design helps reduce noise levels
too, for a quieter work environment.

Damper Leakage, cfm


INLET
SIZE
4, 5, 6
7, 8
9, 10
12
14
16

1.0
3
3
3
3
3
4

PS, IN WG
2.0
4.0
4
6
4
6
4
6
4
6
5
7
5
7

6.0
7
7
7
7
8
9

DESIGN FEATURES

MORE REASONS TO SPECIFY AND SELECT THE TITUS ESV:

M4

Titus innovation carries through the widest array of standard


single duct terminal configurations. ETL listed electric coils,
manufactured by Titus, are installed, wired and functionally
tested as an integral unit before shipment for quicker,
trouble-free job-site installation. Multiple outlets with
standard locking balancing dampers and integral attenuators
are also available.

reinforced surfaces that can be wiped down.

Titus continues to offer the most innovative and popular


lining alternatives for special applications including FibreFree; the industry benchmark Steri-Loc; and the premium
double wall liner, UltraLoc and EcoShield which is the only
natural fiber insulation on the market.

EcoShield is a sustainable liner comprised of recycled denim


making it environmentally friendly and contains no harmful
irritants or chemicals.

Fibre-Free eliminates the requirement for foil linings and


solid inner liners since there is no fiberglass in the airstream.
Additionally, Fibre-Free minimizes mold growth since it holds
no moisture, is acoustically preferable to foil or solid metal
linings and maintains acceptable thermal protection. All
of these benefits are available at a competitive price and
significantly less than solid metal liners.

With a detailed understanding developed through years of


selling and supporting the powerful TD1 digital controller,
and now the Titus BACnet OEM controls, Titus has industry
leading experience in the application of Direct Digital Control
(DDC) to terminals. This same expertise is made available
when your project requires quality engineering, coordination
and manufacturing for factory mounting when controls are
supplied by others.

SteriLoc provides a smooth, nonporous skin to guard


against mold and bacteria growth. Erosion is eliminated,
as there is no glass fiber exposure to the airstream. It has

SteriLoc adds the feature of a very high density, rigid


insulation and special Z-Strip construction for an extremely
rigid terminal. Sound levels are generally superior to dual
wall construction, while offering virtually identical levels of
protection.

Titus - experts in DDC zone control!

Count on Titus - the industry leader in VAV!

Single/Dual Duct Terminals

Design Features (continued)

Unique integral fold fabrication method increases lining and


casing integrity and minimizes leakage.

Beaded inlet for consistent roundness and low leakage


construction, sized to fit standard round duct.

Standard insulation is -inch dual density fiberglass, to resist


erosion at surface velocities up to 5,000 fpm. Meets requirements
of NFPA 90A and UL181.
Delrin damper bearings provide smoother damper operation.

AeroCrossTM multi-point, center averaging sensor amplifies flow


signal for best control of low flow rates. Center averaging feature
provides signal accuracy regardless of inlet duct configuration.

Flow measurement taps included when velocity sensor is


provided, for easy balancing connections.

Damper design provides smoother airflow for reduced sound


levels and lower leakage.
DESV

NEMA 1 control enclosure available for protection of electronic


controls. Double backplane construction for strength and easier
control installation, with no exposed screw tips for safe handling.

Optional Fibre-Free and reinforced sealed skin of Steri-Loc and


metal lined UltraLoc lining guard against environments favoring
bacteria and mold growth. Meets UL 181 and NFPA 225 (25/50).

Fibre-Free & EcoShield are ideal IAQ insulation providing


acoustical and thermal characteristics of fiberglass insulation
without the concern of fiberglass in the airstream.

UL Class II transformers and disconnect switches available installed


for use with any electroniccontrol configuration.

Multiple knockouts in sizes from 7/16-inch to 11/8-inch to


accommodate almost any field connection requirement.

www.titus-hvac.com | www.titus-energysolutions.com

Removable flow sensor (optional).

DESV

DESIGN FEATURES
M5

Single/Dual Duct Terminals

Variable Air Volume - VAV Cooling


As the room temperature increases over setpoint, the unit modulates the cold
airflow from the minimum (which may be zero flow) to the maximum setting.

Analog: See pg. O11 Digital: See pg. O5

ow

Fl

Analog: See pg. O11 Digital: See pg. O5

Max.

er

Pneumatic: See pg. O18

Room Temperature Increase

at

VAV Cooling, Hot Water Reheat


As the room temperature increases, the unit modulates the hot water coil valve
toward the closed position. On a further increase in room temperature, the unit
modulates the cold airflow from the minimum (which must be greater than zero) to
the maximum setting.

cfm Increase

Pneumatic: See pg. O18

Min.

cfm Increase

For detailed information on specific control types, refer to the following pages in
Section S:

Max.

tW
Ho

www.titus-hvac.com | www.titus-energysolutions.com

SINGLE DUCT CONTROL STRATEGIES

Min.

Room Temperature Increase

VAV Cooling, Dual Minimum Flows with Hot Water Reheat


In the cooling mode, as the room temperature increases, the unit thermostat
modulates the cold airflow from the lower minimum to the maximum setting.

Ho

Max.

VAV Cooling and VAV Heating, Local Heat Flows


In the heating mode, as the room temperature increases, the unit modulates the
airflow from maximum to minimum and modulates the hot water coil valve toward
the closed position.
cfm Increase

Max.
Max.

cfm Increase

CONTROL STRATEGIES

low

rF
ate

Analog: See pg. O11 Digital: See pg. O5

tW

VAV Cooling and VAV Heating, Central Heat Flows


In the heating mode, as the room temperature increases, the unit modulates the
airflow from maximum to minimum and modulates the hot water coil valve toward
the closed position.

Pneumatic: See pg. O18

M6

Room Temperature Increase

Analog: See pg. O11 Digital: See pg. O5

A further increase in room temperature changes the operation to the cooling


mode, and the unit modulates the cold airflow from minimum to maximum, which
is different from the heating maximum (usually higher). Both the heating and the
cooling maximum airflows are adjustable.

Max.

Max.

Ho

Pneumatic: See pg. O18

Min.
Room Temperature Increase

Analog: See pg. O11 Digital: See pg. O5

A further increase in room temperature changes the operation to the cooling mode,
and the unit modulates the cold airflow from minimum to maximum, which is the
same as the heating maximum.

ow

Pneumatic: See pg. O18

Alt. Min.

Fl

In the heating mode, the unit references the alternate (higher) minimum airflow. As
the room temperature decreases, the unit modulates the airflow from the maximum
to the higher minimum, then modulates the hot water coil valve toward the open
position. The valve operates only in the heating mode.

cfm Increase

er

at

tW

Room Temperature Increase

Single/Dual Duct Terminals

low

rF
Room Temperature Increase

Pneumatic: See pg. O18

Analog: See pg. O11 Digital: See pg. O5

Step 2

Max.
Step 1

cfm Increase

VAV Cooling, Electric Reheat


As the room temperature increases, the unit de-energizes the electric heating coil
one step at a time. On a further increase in room temperature, the unit modulates
the cold airflow from the minimum (which must be greater than zero) to the
maximum setting.

Min.

www.titus-hvac.com | www.titus-energysolutions.com

a te

Analog: See pg. O11 Digital: See pg. O5

tW

Pneumatic: See pg. O18

Ho

Constant Volume, Hot Water Reheat


The cold airflow remains constant regardless of changes in duct pressure or room
temperature. As the room temperature increases, the unit modulates the hot water
coil valve toward the closed position.

cfm Increase

Control Strategies (continued)

Room Temperature Increase

Pneumatic: See pg. O18

Analog: See pg. O11 Digital: See pg. O5

Step 2
Alt. Min.

cfm Increase

VAV Cooling, Dual Minimum Flows with Electric Reheat


In the cooling mode, as the room temperature increases, the room thermostat
modulates the cold airflow from the lower minimum to the maximum setting.
In the heating mode, as the room temperature decreases, the unit modulates the
airflow from the lower minimum to the higher minimum, then energizes the electric
heating coil stages.

Max.

Step 1

Min.

Room Temperature Increase

VAV Cooling with Morning Warmup


When provided the appropriate signal, the damper in the terminal modulates to
maximum or fully open position. Heated air from the central system moves through
the duct (the flow may be pressure dependent with some control types).

Analog: See pg. O11

Digital:

See pg. O5

Min.

Room Temperature Increase

CONTROL STRATEGIES

Pneumatic: See pg. O18

cfm Increase

When the signal is removed, the unit resumes normal control of airflow. With the
central system now supplying cold air, as room temperature increases, the unit
modulates the cold airflow from minimum to the maximum setting.

Max.

M7

Single/Dual Duct Terminals

ESV
Available Models:

PESV

EESV

AESV


DESV

Standard dual density insulation.

Pneumatic
Electric
Analog
Electronic
Digital
Electronic

Standard 22-gauge casing with slip


and drive discharge connection.
Controls supplied by Titus are
factory calibrated for a quicker
start-up.

Standard AeroCrossTM multi-point


center averaging velocity sensor
(except EESV).
PESV

Pneumatic
Actuator

Multi-Point
Center Averaging
Velocity Sensor

DESV
AESV
EESV

Thermostat &
20 psi Main Air
Connections for
Dia. Tubing

Slip and Drive


Cleat Connection

M
F

12

Control
Enclosure

(Optional for cooling only)

ESV

Control
Cover
(optional)

M8

ESV

www.titus-hvac.com | www.titus-energysolutions.com

Basic Unit with Controls

Slip & Drive


Cleat
Connection

18

INLET
SIZE

CFM
RANGE

4
5
6
7
8
9
10
12
14
16
24X16

0-225
0-350
0-500
0-650
0-900
0-1050
0-1400
0-2000
0-3000
0-4000
0-8000

3
4
5
6
7
8
9
11
13
15
23 - 15

PESV
1
1
1

AESV
DESV
EESV
2
2
2
1
1
1

7
7
7
7
7
5
5
5
3
3
5

8
8
8
10
10
12
12
15
17
18
18

15
15
15
15
15
15
15
15
15
15
15

5
5
3
3
3
3
3
3
3
3
3

12
12
12
12
12
14
14
16
20
24
38

All dimensions are in inches.

Single/Dual Duct Terminals

ACCESSORIES
Titus unique integral design minimizes
casing leakage and disturbance to
airflow with no casing or insulation
seams.

39

18

12

INTEGRAL ELECTRIC COIL

With a rigid one piece assembly,


Titus locates the heating elements for
optimal heat transfer and insets them
for protection during shipment
and installation.

Primary automatic reset thermal


cutout (one per coil).
Secondary manual reset
thermal cutout.
Airflow switch
(differential pressure).
Derated nickel chrome
heating elements.
Magnetic or safety contactors
(as required).
Line terminal block.
Control terminal block.
ETL listed.
80/20 nickel chrome element wire.

Class ll, 24 volt control transformer.


Mercury contactors.
Door interlock disconnect switch.
Main supply fuses.
Dust tight construction.
Removable flow sensor.

365/8

Side View

End View

39

L
W

HOT WATER REHEAT COILS

Details on water coil features are


shown on performance pages M18-22.
Side View
INLET
SIZE

4, 5
6
7, 8
9, 10
12
14
16
24X16

8
8
10
12
15
17
18
18

5
3
3
3
3
3
3
3

12
12
12
14
16
20
24
38

WATER COIL
L (1-2 ROW) L (3-4 ROW)
5
7
5
7
5
7
5
7
5
7
7
9
7
9
5
7

Note: The total length of the ESV basic unit and


accessories (attenuators and coils) is the summation of
basic unit length and the accessories length.
All dimensions are in inches.

End View

ACCESSORIES

INTEGRAL SOUND ATTENUATOR


WITH OPTIONAL HOT WATER
REHEAT COIL

12

OPTIONAL FEATURES:





39

STANDARD FEATURES:

www.titus-hvac.com | www.titus-energysolutions.com

INTEGRAL SOUND ATTENUATOR

M9

Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com

ACCESSORIES
MULTI-OUTLET PLENUMS FOR SINGLE DUCT TERMINALS
2 Outlets

3 Outlets

36

2 Outlets

4 Outlets

ESV Unit
Sizes

Outlet Size D

4, 5, 6
7, 8
8
9, 10
9, 10
12
12
14
14
16
16

5
7
7
9
7
11
9
11
9
11
9

36

33/8 TYP.

5 Outlets

D TYP.

D TYP.

33/8 TYP.

D TYP.

D TYP.

5 Outlets

36

33/8 TYP.

3 Outlets

D TYP.

4 Outlets

36

33/8 TYP.

D TYP.

D TYP.

2 Outlets
G
M
4
5
5
6
6
6
-

3 Outlets
G
M
4
5
5
5
6
6
6
6
6
6
-

4 Outlets
G
M
5
12
5
14
5
12
6
14
6
14
6
14

5 Outlets
G
M
5
12
6
14
6
14
6
14

8
10
10
12
12
15
15
17
17
18
18

12
12
12
14
14
16
16
20
20
24
24

ROUND OUTLETS

ACCESSORIES

33/8

M10

All dimensions are in inches.

D TYP.

Unit Size
4
5
6
7
8
9
10
12
14
16

D
3
4
5
6
7
8
9
11
13
15

H
8
8
8
10
10
12
12
15
17
18

W
12
12
12
12
12
14
14
16
20
24

Single/Dual Duct Terminals

ACCESSORIES

www.titus-hvac.com | www.titus-energysolutions.com

REMOVABLE FLOW SENSOR

Removable Sensor
Installed

#8 Sheet metal screw


6 places

Sensor
Removed

Removable flow
sensor assembly

ESV WITH ACCESS DOOR OPTION


ESV Terminal Unit

Gasket (Access door is sealed with


foam gasket material)
Insulation type specified per order

Access Door (Insulated)

6.00

6.00

2.25

2.25

9.00

9.00

39.50

0.50

0.50

ACCESSORIES

15.50

Right Hand Unit Shown

Basic Unit w/Attenuator


(Bottom View)

Basic Unit
(Bottom View)

All dimensions are in inches.

M11

Single/Dual Duct Terminals

RECOMMENDED PRIMARY AIR CFM RANGES / ALL TERMINALS


Control Types:

PESV

AESV

DESV

Pneumatic
Analog Electronic
Digital Electronic
AESV

www.titus-hvac.com | www.titus-energysolutions.com

PERFORMANCE DATA

QUICK SELECTION PROCEDURE

1. Select unit inlet size based


upon acoustic parameters and/
or maximum pressure drop
requirements, using pages M13.
2. Check inlet size selection against
cfm control limits based on control
type shown on this page.
3. Select accessories (multi-outlets,
attenuators) as required.

4. Select reheat coil, if required.


Make your selection using the
actual heating flow rate, not
cooling.

PERFORMANCE DATA

cfm Ranges of Minimum and Maximum Settings

M12

Inlet Size

Total cfm
Range

4
5
6
7
8
9
10
12
14
16
24X16

0-225
0-350
0-500
0-650
0-900
0-1050
0-1400
0-2000
0-3000
0-4000
0-8000

PESV - Pneumatic

PESV - Pneumatic

AESV - Analog Electronic

DESV - Digital

Titus II Controller

Titus I Controller

TA1 Controller

Typical Controller

Minimum
45*-170
65*-270
80*-330
105*-425
145*-590
175*-700
230*-925
325*-1330
450*-1800
580*-2350
1400*-5200

Maximum
80-225
120-350
150-500
190-650
265-900
315-1050
415-1400
600-2000
810-3000
1100-4000
2600-8000

Minimum
55*-170
85*-270
105*-330
135*-425
190*-590
225*-700
300*-925
425*-1330
575*-1800
750*-2350
1800*-5200

Maximum
80-225
120-350
150-500
190-650
265-900
315-1050
415-1400
600-2000
810-3000
1100-4000
2600-8000

MINIMUM
45*-225
65*-350
80*-500
105*-650
145*-900
175*-1050
230*-1400
325*-2000
450*-3000
580*-4000
1400*-7500

MAXIMUM
45-225
65-350
80-500
105-650
145-900
175-1050
230-1400
325-2000
450-3000
580-4000
1400-7500

MINIMUM
45*-225
65*-350
80*-500
105*-650
145*-900
175*-1050
230*-1400
325*-2000
450*-3000
580*-4000
1400*-7500

MAXIMUM
45-225
65-350
80-500
105-650
145-900
175-1050
230-1400
325-2000
450-3000
580-4000
1400-7500

*Factory cfm settings (except zero) will not be made below this range because control accuracy is reduced. On pressure
dependent units, minimum cfm is always zero and there is no maximum.
Note: On controls mounted by Titus but supplied by others (FMA or Factory Mounting Authorization), these values are
guidelines only. Controls mounted on an FMA basis are calibrated in the field.

Single/Dual Duct Terminals

PERFORMANCE DATA

Min
Ps

100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600
3900
4600
5300
6000
6700

0.02
0.03
0.04
0.06
0.08
0.01
0.02
0.03
0.04
0.06
0.07
0.10
0.13
0.16
0.20
0.07
0.09
0.10
0.12
0.15
0.02
0.02
0.02
0.02
0.03
0.04
0.04
0.05
0.06
0.06
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.02
0.02
0.03
0.04
0.05
0.03
0.04
0.06
0.07
0.09

10

12

14

16

40

2
49
52
55
58
60
49
53
55
58
60
55
57
58
59
59
59
60
60
61
62
59
60
60
61
62
58
58
59
59
60
60
60
61
62
63
58
60
61
61
62
56
58
59
60
62
55
57
59
61
62
70
73
75
77
79

3
45
49
52
55
57
44
48
52
54
56
49
52
53
55
56
48
50
51
53
54
50
51
52
53
54
47
48
49
50
50
50
51
52
53
54
50
52
53
55
56
51
53
54
55
56
48
51
53
55
56
65
68
71
73
75

0.5 Ps
4 5 6
36 33 31
39 36 32
41 37 34
42 39 35
44 40 36
36 32 31
39 35 34
41 37 35
43 39 37
45 40 38
40 35 32
42 37 34
44 39 35
45 40 36
47 42 37
42 38 33
43 39 34
44 40 35
45 42 35
46 43 36
44 40 38
44 41 39
45 42 40
46 43 40
47 43 41
43 36 34
43 37 34
44 37 35
44 37 35
44 38 36
47 45 42
48 46 43
48 47 44
48 47 45
49 48 45
47 41 37
48 42 38
50 43 40
51 44 41
52 45 43
45 43 40
46 44 41
47 45 42
48 46 43
49 47 44
43 41 39
45 43 41
46 44 42
48 46 44
49 47 45
63 59 57
66 62 59
68 64 61
71 66 63
72 67 64

7
26
27
28
29
30
25
27
29
30
31
28
29
30
31
32
24
24
25
25
26
32
32
33
34
34
30
31
31
31
31
29
30
32
32
33
30
32
34
35
36
36
36
37
38
38
31
33
34
36
37
54
55
56
57
58

NC
11
16
20
23
25
10
15
20
22
24
16
20
21
23
24
20
22
22
23
24
20
22
22
23
24
19
19
20
20
22
22
22
23
24
25
20
22
24
25
26
18
21
22
23
24
36
18
21
23
24
38
41
43
47
48

2
52
55
58
61
63
53
56
59
62
63
59
60
61
62
63
61
62
63
63
64
62
63
63
64
65
61
61
62
62
63
63
64
65
65
66
62
63
64
65
66
60
62
63
64
66
59
61
63
65
66
72
75
78
80
82

3
48
52
55
58
60
49
53
56
59
61
54
57
58
60
61
54
55
57
58
59
55
56
57
58
59
53
54
55
56
56
57
58
58
59
60
56
57
59
60
61
56
58
59
60
61
53
56
58
60
61
68
71
73
75
77

Octave
1.0 Ps
4 5 6
39 36 35
42 38 36
44 40 38
46 42 39
47 43 40
41 36 35
44 38 37
46 40 39
48 42 41
49 43 42
45 39 37
47 41 38
49 42 39
50 44 40
51 45 41
48 42 38
49 43 39
50 45 40
51 46 41
52 47 41
49 43 43
50 44 44
50 45 44
51 46 45
52 47 46
49 42 40
49 43 41
50 43 41
50 43 42
50 44 42
53 50 48
54 51 49
54 52 50
54 53 51
55 53 52
52 47 43
54 48 45
55 49 46
56 50 48
57 51 49
50 48 45
51 49 46
52 50 47
53 51 48
54 52 49
47 45 44
49 47 46
51 48 47
52 50 49
54 51 50
66 62 61
68 64 63
71 66 65
73 68 66
75 70 68

Radiated sound is the noise transmitted


through the unit casing.
Min Ps is the static pressure drop from the unit inlet
to the unit outlet with primary damper full open.
Sound power levels are in dB, ref 10-12 watts.
Sound performance based on units lined with
standard dual density fiberglass lining.

Band Sound Power, Lw


1.5 Ps
7 NC 2 3 4 5 6
31 15 53 50 41 37 37
32 20 57 54 44 40 39
34 23 60 57 46 41 40
34 27 63 59 48 43 41
35 29 65 62 49 44 42
30 16 55 51 43 38 37
32 21 59 55 46 40 40
34 24 62 59 49 42 41
35 28 64 61 50 44 43
36 30 66 63 52 45 44
33 22 61 57 48 41 39
34 25 62 59 50 43 40
35 27 63 61 52 44 42
36 29 64 63 53 46 43
37 30 65 64 54 47 44
30 23 62 57 51 45 41
30 24 63 58 52 46 42
31 25 64 59 53 47 43
31 27 65 61 54 48 44
32 28 65 62 55 49 44
39 24 64 58 52 46 45
40 25 65 59 53 47 46
41 25 65 60 53 47 47
41 27 66 61 54 48 48
42 28 66 62 55 49 48
35 23 62 57 52 46 44
35 23 63 58 53 46 45
35 24 64 58 53 47 45
36 24 64 59 54 47 45
36 25 65 60 54 47 46
37 27 65 60 57 53 52
38 28 66 61 57 54 53
39 28 67 62 57 55 54
40 28 67 63 58 56 55
41 29 68 63 58 56 55
37 26 64 59 56 50 46
39 28 65 60 57 52 48
40 29 66 62 59 53 50
41 30 67 63 60 54 51
43 31 68 64 61 55 52
41 24 62 59 53 51 48
42 27 64 60 54 52 49
43 28 66 62 55 53 50
43 29 67 63 56 54 51
44 30 68 64 57 55 52
38 21 61 56 50 47 47
39 24 64 59 52 49 49
41 27 66 61 54 50 50
42 29 67 62 55 52 52
44 30 69 64 56 53 53
58 41 74 69 67 63 63
60 43 77 72 70 66 65
61 47 79 74 72 68 67
62 49 81 76 74 70 68
63 51 83 78 76 71 70

7
34
36
37
38
38
33
35
37
38
39
36
37
38
39
40
33
34
34
35
35
44
45
45
46
47
38
38
38
38
39
41
42
43
44
45
41
42
44
45
47
45
45
46
47
47
41
43
45
46
48
61
63
64
65
66

NC
17
22
25
28
31
18
23
28
30
33
25
28
30
33
34
25
27
28
30
31
27
28
29
30
31
26
27
27
28
29
31
31
31
33
33
30
31
34
35
36
28
29
31
33
34
24
28
30
31
34
42
46
48
50
52

2
55
58
61
64
66
57
60
63
65
67
63
64
65
66
67
63
64
66
66
66
65
66
67
67
68
63
64
65
65
66
67
67
68
69
69
66
67
68
69
69
64
66
67
69
70
63
65
67
69
71
75
78
80
82
84

3
51
55
58
61
63
53
57
61
63
65
59
62
63
65
67
59
60
62
63
64
60
61
62
63
64
59
60
61
62
62
63
64
64
65
66
61
63
64
65
67
61
63
64
65
66
58
61
63
64
66
70
73
75
77
79

2.0 Ps
4 5 6
43 38 39
45 41 40
47 42 42
49 44 43
51 45 44
45 39 39
48 42 41
51 44 43
52 45 44
54 47 45
50 42 41
52 44 42
54 46 43
55 47 45
56 49 46
53 46 43
54 48 44
55 49 45
56 50 46
57 51 46
54 47 47
55 48 48
56 49 49
56 50 50
57 51 50
55 48 47
55 49 47
56 49 48
56 49 48
57 50 48
59 56 54
59 56 55
60 57 56
60 58 57
61 58 58
58 53 49
60 54 51
61 55 52
62 56 54
63 57 55
55 53 50
56 54 51
58 55 52
58 56 53
59 57 54
52 49 49
54 51 51
55 52 52
57 53 54
58 55 55
68 64 65
71 67 67
73 69 68
75 71 70
77 72 71

7
36
38
39
40
41
35
37
39
40
41
38
39
40
41
42
35
36
37
37
38
47
48
48
49
50
40
40
40
40
40
44
45
46
47
48
43
45
47
48
49
47
48
49
49
50
44
46
48
49
50
63
64
66
67
68

NC
18
23
27
30
33
21
25
30
33
35
28
31
33
35
37
28
29
31
33
34
29
30
31
33
34
29
29
30
31
31
34
34
35
35
36
32
35
36
37
38
30
33
34
35
36
27
30
33
34
36
43
47
49
51
53

All performance based on tests conducted in


accordance with ASHRAE 130-2008 and AHRI 880-2008.
All NC levels determined using AHRI 885-2008
Appendix E. See Terminal Unit Engineering Guidelines.
Dash (-) in space denotes NC value less than NC10.
Only highlighted data points are AHRI certified. See
page M24 for AHRI Certified Performance Listings.

PERFORMANCE DATA

Size CFM

www.titus-hvac.com | www.titus-energysolutions.com

PESV, AESV, DESV / RADIATED SOUND PERFORMANCE

M13

Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com

PERFORMANCE DATA
PESV, AESV, DESV / DISCHARGE SOUND PERFORMANCE
Size CFM

Min
Ps

100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600
3900
4600
5300
6000
6700

0.02
0.03
0.04
0.06
0.08
0.01
0.02
0.03
0.04
0.06
0.07
0.10
0.13
0.16
0.20
0.07
0.09
0.1
0.12
0.15
0.02
0.02
0.02
0.02
0.03
0.04
0.04
0.05
0.06
0.06
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.02
0.02
0.03
0.04
0.05
0.03
0.04
0.06
0.07
0.09

10

12

14

PERFORMANCE DATA

16

M14

40

2
62
64
65
67
68
60
63
65
66
68
60
61
63
64
65
64
64
65
65
65
66
67
67
68
68
67
68
68
69
69
69
70
70
71
72
68
69
70
71
71
65
66
67
68
68
65
67
68
70
71
74
75
77
78
79

3
53
57
60
62
64
50
54
57
59
61
57
59
60
62
63
58
59
61
62
63
60
61
62
63
64
59
60
61
61
62
60
61
61
62
63
62
63
64
66
67
56
58
59
60
61
58
61
63
64
66
69
70
72
73
74

0.5 Ps
4 5 6
46 42 40
49 44 42
51 47 44
53 48 45
55 50 46
46 43 41
49 46 43
52 49 45
54 51 47
56 52 48
53 50 45
54 52 47
56 54 48
57 55 49
59 56 50
53 51 47
54 52 48
55 54 49
56 55 49
57 56 50
55 52 48
56 53 48
56 54 49
57 54 49
57 55 50
56 53 49
56 53 49
57 54 50
57 54 50
58 55 50
57 55 50
58 56 50
58 57 51
59 57 52
60 58 52
59 55 53
61 56 54
62 57 55
63 58 55
64 59 56
56 53 50
58 53 50
59 54 51
60 54 51
61 54 51
57 54 52
59 55 53
61 57 55
63 58 56
65 59 57
66 62 61
67 63 63
69 65 64
70 66 65
71 67 67

7
33
35
36
37
38
34
36
38
39
40
39
40
41
42
43
40
40
41
42
43
40
41
41
42
42
43
43
43
44
44
44
44
45
45
46
46
47
48
49
50
44
44
44
44
45
45
46
48
49
50
56
58
60
61
62

NC
17
19
20
23
24
14
18
20
18
20
14
16
17
20
21
15
16
18
20
21
18
19
20
20
21
17
18
18
19
19
19
20
20
22
23
18
20
21
23
24
14
15
17
18
18
14
17
20
21
23
27
28
30
31
33

2
63
65
67
68
69
62
65
67
69
70
64
66
67
68
69
67
67
68
68
68
69
70
70
70
71
70
70
71
72
72
71
72
73
73
74
71
72
73
74
74
68
69
70
71
72
68
70
72
73
74
79
80
82
83
84

3
56
60
62
65
67
55
58
62
64
66
62
64
66
67
69
63
65
66
67
69
66
67
68
69
70
64
65
66
66
67
65
66
67
68
68
67
69
70
71
72
62
64
65
66
67
62
65
67
68
70
74
76
77
78
79

Octave
1.0 Ps
4 5 6
50 46 47
53 49 49
56 51 50
58 53 51
60 55 53
51 47 47
55 51 49
57 53 51
59 55 53
61 57 54
58 54 51
60 56 52
61 58 53
63 59 54
64 61 55
58 54 51
59 56 52
60 57 53
61 58 54
62 59 55
59 55 52
60 56 53
60 56 53
61 57 54
62 58 54
60 57 54
60 57 54
61 57 55
61 58 55
61 58 55
61 59 55
62 60 56
63 61 56
63 61 57
64 62 58
63 59 57
65 61 59
66 62 59
67 63 60
68 64 61
61 59 57
62 59 58
64 60 58
65 60 59
66 61 59
60 58 56
63 60 58
65 61 59
66 62 60
68 63 61
71 67 67
73 68 68
74 69 70
75 71 71
76 72 72

Discharge sound is the noise emitted from the


unit discharge into the downstream ductwork.
Min Ps is the static pressure drop from the unit inlet
to the unit outlet with primary damper full open.
Sound power levels are in dB, ref 10-12 watts.
Sound performance based on units lined with
standard dual density fiberglass lining.

Band Sound Power, Lw


1.5 Ps
7 NC 2 3 4 5 6
41 18 64 58 53 49 50
43 20 66 61 56 52 52
44 23 68 64 59 54 54
45 24 69 66 61 56 55
46 27 70 69 62 58 56
42 17 64 57 54 50 51
44 20 67 61 58 53 53
45 23 69 64 60 56 55
46 22 70 67 62 58 56
47 24 72 69 64 60 57
46 20 67 65 61 57 54
47 22 68 67 63 59 55
48 24 70 69 64 60 57
49 25 71 70 66 62 58
50 28 72 72 67 63 59
46 21 68 67 60 56 54
47 23 69 68 62 58 55
48 24 69 70 63 59 56
48 25 70 71 63 60 57
49 28 70 72 64 61 58
47 24 71 69 61 56 55
47 25 71 70 62 57 55
48 27 72 71 63 58 56
48 27 72 72 63 58 56
49 28 72 73 64 59 57
49 21 71 67 62 59 57
50 22 72 68 62 59 57
50 23 73 68 63 59 57
50 23 73 69 63 60 58
50 24 74 70 64 60 58
50 22 72 68 64 61 58
51 23 73 69 65 62 59
51 24 74 70 65 63 60
52 25 75 71 66 64 60
53 25 75 72 67 65 61
52 24 73 70 65 62 60
53 27 74 72 67 63 61
55 28 75 73 68 64 62
56 29 75 74 70 65 63
56 30 76 75 71 66 64
53 18 70 66 63 62 62
53 21 71 67 65 63 62
54 22 72 68 66 63 63
54 23 73 69 68 64 63
54 24 74 70 69 64 63
51 18 70 65 62 61 59
52 22 72 67 64 62 61
54 24 74 69 66 64 62
55 25 75 71 68 65 63
56 28 76 72 70 66 64
62 33 82 77 74 69 70
64 35 83 79 76 71 71
65 36 85 80 77 72 73
67 37 86 81 78 73 74
68 38 87 82 79 74 75

7
46
47
49
50
51
46
48
50
51
52
50
51
52
53
54
49
50
51
52
53
51
51
52
52
53
53
54
54
54
54
54
55
55
56
56
56
57
58
59
60
59
59
59
59
60
54
56
57
59
60
66
67
69
70
71

NC
19
22
24
25
29
19
23
25
25
28
23
25
28
29
31
25
27
29
30
31
28
29
30
30
31
24
25
25
27
28
25
27
28
29
30
28
30
31
33
34
23
24
25
27
28
22
24
27
29
30
36
38
40
41
42

2
65
67
68
70
71
65
68
70
71
73
69
70
71
73
74
70
70
71
71
72
72
72
73
73
74
72
73
74
74
75
73
74
75
76
76
74
75
76
76
77
72
73
74
74
75
71
73
75
76
78
84
86
87
88
89

3
59
62
65
68
70
59
63
66
69
71
67
69
71
73
74
69
71
72
73
74
72
73
74
75
75
69
70
70
71
72
71
72
72
73
74
72
74
75
76
77
68
70
71
72
73
67
69
71
72
74
79
81
82
83
84

2.0 Ps
4 5 6
55 51 53
58 54 55
60 56 57
63 58 58
64 60 59
57 52 53
60 55 55
62 58 57
65 60 59
66 61 60
63 58 56
65 60 58
66 62 59
68 63 60
69 65 61
62 58 56
63 59 57
64 60 58
65 61 59
66 62 59
63 57 57
64 58 57
64 59 58
65 60 58
66 60 59
64 60 59
64 61 59
65 61 59
65 61 60
65 62 60
66 63 61
67 64 61
67 65 62
68 66 63
68 66 63
67 64 62
69 65 63
70 66 64
71 67 65
72 68 66
65 65 65
67 65 65
68 66 66
69 66 66
70 67 66
63 63 61
66 64 62
68 66 64
70 67 65
71 68 66
76 71 72
78 73 74
79 74 75
80 75 76
81 76 77

7
49
51
52
53
54
49
51
53
54
55
53
54
55
56
57
52
53
54
55
55
54
54
55
55
56
56
56
57
57
57
57
57
58
59
59
59
60
61
62
63
62
63
63
63
63
57
58
60
61
62
68
70
71
73
74

NC
20
23
24
28
30
20
24
27
28
30
25
28
30
33
34
28
30
31
33
34
31
33
34
34
34
27
28
28
29
30
29
30
30
31
33
30
33
34
35
36
25
28
29
30
31
24
27
29
30
33
34
41
42
43
45

All performance based on tests conducted in


accordance with ASHRAE 130-2008 and AHRI 880-2008.
All NC levels determined using AHRI 885-2008
Appendix E. See Terminal Unit Engineering Guidelines.
Dash (-) in space denotes NC value less than NC10.
Only highlighted data points are AHRI certified. See
page M24 for AHRI Certified Performance Listings.

Single/Dual Duct Terminals

PERFORMANCE DATA

Sizes 4-5-6

Rows/
Circuits
One-Row
Single
Circuit

Two-Row
MultiCircuit

Sizes 7-8

Rows/
Circuits
One-Row
Single
Circuit

Two-Row
MultiCircuit

Sizes 9-10

Rows/
Circuits
One-Row
MultiCircuit

Two-Row
MultiCircuit

One-Row
MultiCircuit

Two-Row
MultiCircuit

50
4.2
4.4
4.4
4.5
0.01
5.3
5.5
5.6
5.6
0.01

100
5.9
6.3
6.5
6.5
0.01
8.6
9.4
9.6
9.7
0.02

150
7.0
7.5
7.8
7.8
0.02
11.0
12.5
12.8
13.0
0.04

200
7.7
8.3
8.7
8.8
0.03
12.9
15.0
15.5
15.8
0.07

Head
gpm
Loss
1.0
0.69
2.0
2.34
3.0
4.77
4.0
7.96
Airside Ps
1.0
0.33
3.0
2.32
5.0
5.66
7.0
10.28
Airside Ps

100
6.9
7.2
7.4
7.4
0.01
9.4
10.1
10.3
10.3
0.01

200
9.2
9.9
10.2
10.3
0.02
14.3
16.5
17.0
17.2
0.04

300
10.7
11.7
12.1
12.3
0.04
17.6
21.2
22.2
22.6
0.08

400
12.2
13.6
14.1
14.4
0.07
20.1
25.0
26.3
27.0
0.13

gpm
2.0
3.0
5.0
6.0
Airside
2.0
4.0
6.0
8.0
Airside

Head
Loss
0.68
1.40
3.41
4.72
Ps
0.65
2.19
4.43
7.35
Ps

200
11.7
12.1
12.5
12.6
0.01
17.4
18.5
18.8
19.0
0.02

300
13.8
14.4
15.0
15.1
0.02
22.4
24.3
25.0
25.4
0.04

400
15.3
16.0
16.7
16.9
0.04
26.3
29.0
30.1
30.7
0.07

500
17.0
18.0
18.9
19.1
0.05
29.5
33.0
34.5
35.3
0.10

gpm
2.0
3.0
5.0
6.0
Airside
2.0
4.0
6.0
8.0
Airside

Head
Loss
0.88
1.81
4.40
6.08
Ps
0.84
2.79
5.63
9.33
Ps

300
14.7
16.4
17.5
17.9
0.01
21.7
26.0
27.1
27.6
0.02

500
17.3
19.9
21.6
22.3
0.03
27.5
35.7
37.9
39.0
0.06

700
19.6
23.0
25.4
26.3
0.06
31.1
42.8
46.3
47.9
0.11

900
21.4
25.7
28.7
29.9
0.09
33.7
48.5
53.0
55.3
0.16

Airflow, cfm
250
300
8.6
9.4
9.4
10.3
9.8
10.9
9.9
11.0
0.05
0.07
14.4
15.6
17.1
19.0
17.9
19.9
18.2
20.4
0.10
0.13
Airflow, cfm
500
600
13.4
14.5
15.1
16.4
15.8
17.2
16.1
17.7
0.10
0.14
21.9
23.4
28.1
30.8
29.9
32.9
30.7
34.0
0.20
0.27
Airflow, cfm
600
700
18.5
19.8
19.7
21.2
20.8
22.4
21.1
22.8
0.07
0.10
32.1
34.4
36.5
39.6
38.3
41.7
39.3
42.9
0.14
0.18
Airflow, cfm
1100
1300
22.9
24.1
28.0
29.9
31.6
34.0
33.0
35.8
0.12
0.17
35.6
37.1
53.0
56.9
58.7
63.6
61.6
67.0
0.23
0.32

For performance notes, see the next page.

350
10.1
11.1
11.8
11.9
0.09
16.7
20.7
21.8
22.3
0.18

400
10.6
11.8
12.6
12.8
0.12
17.6
22.2
23.5
24.1
0.22

450
11.2
12.5
13.4
13.6
0.14
18.4
23.5
25.0
25.7
0.27

700
15.3
17.6
18.5
19.0
0.19
24.7
33.1
35.6
36.9
0.36

800
16.1
18.6
19.6
20.2
0.24
25.7
35.1
38.0
39.5
0.46

900
16.8
19.5
20.7
21.3
0.30
26.6
37.0
40.2
41.8
0.56

800
21.0
22.5
23.9
24.3
0.12
36.3
42.3
44.8
46.2
0.23

900
22.0
23.7
25.3
25.8
0.15
38.1
44.7
47.6
49.2
0.29

1000
23.0
24.8
26.6
27.1
0.18
39.6
46.9
50.1
51.9
0.35

1500
25.2
31.5
36.2
38.2
0.21
38.3
60.2
67.8
71.8
0.41

1700
26.0
32.9
38.1
40.3
0.27
39.3
63.1
71.6
76.1
0.51

1900
26.8
34.2
39.9
42.3
0.33
40.2
65.6
75.0
79.9
0.62

PERFORMANCE DATA

Size 12

Rows/
Circuits

Head
gpm
Loss
1.0
0.50
2.0
1.69
4.0
5.77
5.0
8.59
Airside Ps
1.0
0.24
3.0
1.66
5.0
4.06
7.0
7.39
Airside Ps

www.titus-hvac.com | www.titus-energysolutions.com

PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 1- AND 2-ROW

M15

Single/Dual Duct Terminals

PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 1- AND 2-ROW

Size 14

Rows/
Circuits
One-Row
MultiCircuit

Two-Row
MultiCircuit
Rows/
Circuits

Size 16

www.titus-hvac.com | www.titus-energysolutions.com

PERFORMANCE DATA

One-Row
MultiCircuit

Two-Row
MultiCircuit

Size 24 x 16

Rows/
Circuits
One-Row
MultiCircuit

PERFORMANCE DATA

Two-Row
MultiCircuit

M16

gpm
2.0
3.0
5.0
6.0
Airside
2.0
4.0
6.0
8.0
Airside

Head
Loss
0.45
0.95
2.31
3.17
Ps
0.56
1.94
3.89
6.40
Ps

400
21.9
23.2
24.3
24.6
0.01
32.5
35.6
36.8
37.4
0.02

700
26.8
28.8
30.6
31.1
0.03
43.9
50.5
53.2
54.6
0.05

1000
30.7
33.4
36.0
36.7
0.05
51.4
61.3
65.5
67.8
0.10

gpm
3.0
5.0
7.0
9.0
Airside
3.0
5.0
7.0
9.0
Airside

Head
Loss
0.98
2.44
4.38
6.83
Ps
0.50
1.26
2.25
3.46
Ps

600
30.1
31.9
32.7
33.2
0.02
45.4
49.1
50.8
51.8
0.03

1000
36.2
38.9
40.3
41.1
0.04
59.2
66.1
69.6
71.7
0.07

1400
42.1
46.0
47.9
49.1
0.07
68.5
78.4
83.6
86.8
0.13

gpm
3.0
5.0
7.0
9.0
Airside
3.0
5.0
7.0
9.0
Airside

Head
Loss
1.15
2.90
5.20
8.08
Ps
0.56
1.41
2.51
3.86
Ps

600
38.0
40.3
41.3
41.9
0.01
52.2
55.9
57.6
58.6
0.01

1200
49.5
53.8
55.9
57.1
0.02
76.1
85.8
90.6
93.5
0.04

1800
57.4
63.4
66.5
68.3
0.05
90.4
105.6
113.5
118.4
0.09

All coil performance in accordance with AHRI 410-2001.


Heating capacities are in MBH.
Data based on 180F entering water
and 55F entering air.
For temperature differentials other than 125,
multiply MBH by correction factors below.
Head loss is in feet of water.
Always supply water to lowest connection
pipe to prevent air entrapment.
Air temperature rise = 927 x MBH/cfm.

1300
34.2
37.5
40.9
41.8
0.08
56.8
69.7
75.3
78.5
0.16

Airflow, cfm
1600
1900
36.9
39.2
40.9
43.8
45.0
48.5
46.1
49.8
0.12
0.17
60.9
64.2
76.4
82.0
83.4
90.3
87.4
95.1
0.23
0.31

Airflow, cfm
2200
2600
50.6
53.8
56.4
60.4
59.4
63.9
61.2
66.0
0.16
0.21
80.7
85.0
95.5
101.9
103.7 111.4
108.9 117.5
0.30
0.40
Airflow, cfm
2400
3000
3600
64.5
70.1
74.7
72.4
79.8
85.9
76.5
84.8
91.8
79.0
87.8
95.4
0.08
0.12
0.17
100.1 107.2 112.7
120.0 131.2 140.1
130.8 144.6 155.9
137.6 153.2 166.1
0.15
0.23
0.31
1800
46.8
51.7
54.1
55.6
0.11
75.3
87.9
94.6
98.9
0.21

2200
41.1
46.3
51.6
53.1
0.21
66.8
86.8
96.3
101.8
0.41

2500
42.8
48.4
54.3
56.0
0.27
69.1
90.9
101.5
107.8
0.51

2800
44.3
50.3
56.7
58.6
0.33
71.0
94.5
106.1
113.1
0.63

3000
56.5
63.9
67.9
70.3
0.27
88.5
107.2
118.0
125.0
0.51

3400
58.9
67.1
71.4
74.1
0.34
91.5
111.9
123.7
131.5
0.64

3800
61.0
69.8
74.6
77.5
0.41
94.1
115.9
128.8
137.3
0.78

4200
78.5
91.1
97.8
102.0
0.22
117.0
147.5
165.4
177.2
0.41

4800
81.8
95.7
103.2
107.9
0.27
120.6
153.7
173.5
186.7
0.52

5400
84.7
99.7
107.9
113.1
0.34
123.6
159.0
180.6
195.1
0.64

Water temperature drop = 2.04 x MBH/gpm.


Connection size is -in OD male solder for 1-row coil
sizes 04-08. All other coils have -in OD male solder.
Coils are not intended for steam applications and are
labeled for a maximum water temperature of 200F.
Coils are tested for leakage at test pressure of 500 psi.
Water volumes less than those shown may result
in laminar flow and reduced heating capacity.
If possible reduce the number of coil rows to
increase water velocity into turbulent range.

Correction Factors for Other Entering Conditions


T

50

60

70

80

90

100

110

125

140

150

Factor

0.40

0.48

0.56

0.64

0.72

0.80

0.88

1.00

1.12

1.20

Note: Airside DPs reflects the air pressure drop of the hot water coil.

Single/Dual Duct Terminals

PERFORMANCE DATA

Sizes 4-5-6
Sizes 7-8
Sizes 9-10

FourRow
MultiCircuit
Rows/
Circuits
ThreeRow
MultiCircuit
FourRow
MultiCircuit
Rows/
Circuits
ThreeRow
MultiCircuit
FourRow
MultiCircuit
Rows/
Circuits
ThreeRow
MultiCircuit
FourRow
MultiCircuit

Head
Loss
1.31
2.63
6.43
8.88
Ps
1.59
2.61
5.28
8.77
Ps

50
6.2
6.2
6.3
6.3
0.01
6.5
6.5
6.5
6.5
0.01

100
11.0
11.2
11.4
11.4
0.03
12.1
12.2
12.3
12.4
0.04

150
14.9
15.3
15.7
15.8
0.06
16.9
17.2
17.4
17.5
0.08

200
18.1
18.8
19.4
19.6
0.10
21.1
21.5
21.9
22.2
0.13

Head
gpm
Loss
2.0
0.79
4.0
2.63
6.0
5.31
8.0
8.80
Airside Ps
4.0
2.04
6.0
4.12
8.0
6.79
10.0 10.04
Airside Ps

100
11.5
11.8
11.9
11.9
0.02
12.6
12.7
12.7
12.7
0.02

200
19.2
20.3
20.8
21.0
0.06
22.6
23.0
23.2
23.4
0.08

300
24.8
27.0
27.9
28.3
0.12
30.6
31.5
32.0
32.3
0.16

400
29.2
32.5
33.7
34.4
0.20
37.2
38.7
39.5
40.0
0.26

gpm
3.0
5.0
7.0
9.0
Airside
4.0
5.0
8.0
10.0
Airside

Head
Loss
1.18
2.85
5.11
7.92
Ps
1.72
2.53
5.71
8.41
Ps

200
21.5
22.1
22.4
22.6
0.03
23.9
24.1
24.4
24.6
0.04

300
28.8
30.1
30.7
31.1
0.06
33.0
33.5
34.3
34.6
0.08

400
34.7
36.8
37.8
38.3
0.10
40.7
41.6
43.0
43.5
0.13

500
39.7
42.5
43.9
44.7
0.15
47.3
48.6
50.6
51.4
0.20

gpm
3.0
4.0
6.0
8.0
Airside
4.5
5.0
7.0
9.0
Airside

Head
Loss
1.50
2.46
4.94
8.14
Ps
2.67
3.20
5.71
8.81
Ps

300
29.7
31.9
32.6
33.0
0.03
35.2
35.4
36.1
36.3
0.05

500
40.6
45.6
47.5
48.5
0.09
52.0
52.6
54.5
55.1
0.11

700
48.3
56.2
59.3
61.0
0.16
65.3
66.2
69.7
70.9
0.21

900
53.9
64.6
69.0
71.4
0.24
76.0
77.4
82.5
84.3
0.32

gpm
2.0
3.0
5.0
6.0
Airside
3.0
4.0
6.0
8.0
Airside

Airflow, cfm
250
300
20.9
23.3
21.9
24.5
22.7
25.6
22.9
25.9
0.14
0.20
24.7
27.9
25.3
28.7
26.0
29.6
26.3
30.1
0.19
0.26
Airflow, cfm
500
600
32.7
35.6
37.0
41.0
38.8
43.2
39.7
44.4
0.29
0.40
42.7
47.5
44.9
50.3
46.0
51.8
46.8
52.8
0.39
0.53
Airflow, cfm
600
700
43.9
47.5
47.6
52.0
49.4
54.3
50.4
55.6
0.21
0.27
53.0
58.0
54.7
60.2
57.5
63.7
58.5
65.0
0.27
0.36
Airflow, cfm
1100
1300
58.4
61.9
71.6
77.4
77.2
84.3
80.4
88.2
0.35
0.47
84.9
92.4
86.7
94.7
93.5
103.2
96.0
106.3
0.46
0.61

For Performance Notes, see the next page.

350
25.4
26.9
28.3
28.7
0.26
30.7
31.8
33.0
33.6
0.34

400
27.3
29.1
30.7
31.2
0.33
33.3
34.6
36.0
36.8
0.43

450
28.9
31.0
32.9
33.5
0.40
35.6
37.2
38.8
39.8
0.53

700
38.1
44.4
47.0
48.5
0.53
51.7
55.0
56.9
58.1
0.70

800
40.2
47.4
50.5
52.2
0.67
55.3
59.3
61.6
63.0
0.89

900
42.0
50.1
53.6
55.6
0.83
58.6
63.2
65.8
67.5
1.10

800
50.8
56.0
58.7
60.3
0.34
62.5
65.1
69.4
70.9
0.46

900
53.6
59.6
62.7
64.5
0.42
66.5
69.5
74.5
76.4
0.56

1000
56.2
62.9
66.4
68.5
0.51
70.1
73.5
79.3
81.5
0.68

1500
64.8
82.5
90.5
95.0
0.60
98.8
101.5
111.7
115.5
0.79

1700
67.3
86.8
95.9
101.2
0.75
104.4
107.5
119.3
123.7
0.99

1900
69.4
90.7
100.8
106.7
0.91
109.4
112.8
126.1
131.2
1.20

PERFORMANCE DATA

Size 12

Rows/
Circuits
ThreeRow
MultiCircuit

www.titus-hvac.com | www.titus-energysolutions.com

PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 3- AND 4-ROW

M17

Single/Dual Duct Terminals

Size 14

Rows/
Circuits
ThreeRow
MultiCircuit
FourRow
MultiCircuit
Rows/
Circuits
ThreeRow
MultiCircuit
FourRow
MultiCircuit
Rows/
Circuits
ThreeRow
MultiCircuit

PERFORMANCE DATA

Size 24 x 16

PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 3- AND 4-ROW

Size 16

www.titus-hvac.com | www.titus-energysolutions.com

PERFORMANCE DATA

M18

FourRow
MultiCircuit

gpm
4.0
5.0
6.0
8.0
Airside
6.0
6.0
8.0
10.0
Airside

Head
Loss
1.95
2.87
3.93
6.44
Ps
2.77
2.77
4.55
6.67
Ps

400
42.5
43.2
43.7
44.4
0.03
47.6
47.6
48.2
48.6
0.04

700
62.2
64.2
65.6
67.3
0.08
73.2
73.2
75.2
76.4
0.10

1000
76.5
79.9
82.2
85.3
0.15
93.0
93.0
96.7
99.0
0.20

gpm
6.0
8.0
10.0
12.0
Airside
9.0
10.0
11.0
12.0
Airside

Head
Loss
1.54
2.54
3.73
5.10
Ps
2.79
3.34
3.94
4.57
Ps

600
60.4
61.9
62.9
63.5
0.04
68.9
69.3
69.7
69.9
0.06

1000
84.3
87.8
90.0
91.6
0.11
100.8
101.9
102.9
103.6
0.14

1400
101.8
107.4
111.1
113.7
0.20
125.6
127.5
129.2
130.5
0.26

gpm
6.0
8.0
10.0
12.0
Airside
9.0
10.0
11.0
12.0
Airside

Head
Loss
1.69
2.78
4.08
5.57
Ps
3.01
3.61
4.25
4.93
Ps

600
66.6
67.9
68.7
69.3
0.02
73.7
74.0
74.3
74.5
0.03

1200
107.8
112.5
115.4
117.4
0.07
127.6
129.0
130.2
131.1
0.09

1800
135.8
144.3
149.8
153.6
0.14
167.4
170.3
172.7
174.7
0.18

All coil performance in accordance with AHRI 410-2001.


Heating capacities are in MBH.
Data based on 180F entering water
and 55F entering air.
For temperature differentials other than 125,
multiply MBH by correction factors below.
Head loss is in feet of water.
Always supply water to lowest connection
pipe to prevent air entrapment.
Air temperature rise = 927 x MBH/cfm.

Airflow, cfm
1600
1900
96.3
103.5
102.2 110.5
106.4 115.6
112.2 122.7
0.34
0.46
121.8 132.6
121.8 132.6
129.1 141.7
133.9 147.7
0.45
0.61
Airflow, cfm
1800
2200
2600
115.5 126.4 135.5
123.0 135.9 146.7
128.1 142.2 154.3
131.7 146.8 159.8
0.31
0.44
0.59
145.5 161.9 175.8
148.3 165.6 180.2
150.7 168.6 184.0
152.7 171.3 187.2
0.40
0.58
0.78
Airflow, cfm
2400
3000
3600
156.2 171.9 184.4
168.4 187.5 203.0
176.4 197.9 215.7
182.1 205.4 225.0
0.23
0.33
0.46
198.0 222.2 242.0
202.4 228.2 249.4
206.1 233.2 255.7
209.3 237.6 261.2
0.30
0.44
0.61

1300
87.5
92.2
95.5
99.9
0.24
108.8
108.8
114.3
117.9
0.31

2200
109.5
117.6
123.5
131.8
0.60
141.8
141.8
152.6
159.7
0.79

2500
114.7
123.7
130.4
139.9
0.75
149.7
149.7
162.1
170.4
1.00

2800
119.1
129.0
136.5
147.0
0.92
156.7
156.7
170.5
180.0
1.22

3000
143.1
155.9
164.7
171.1
0.76
187.7
192.8
197.3
201.1
1.00

3400
149.7
164.0
173.8
181.1
0.94
198.0
203.9
208.9
213.3
1.25

3800
155.5
171.0
182.0
190.0
1.15
207.0
213.6
219.2
224.2
1.52

4200
194.6
216.0
230.8
241.7
0.61
258.4
267.2
274.7
281.2
0.80

4800
203.2
227.0
243.8
256.2
0.77
272.3
282.4
291.0
298.5
1.02

5400
210.4
236.6
255.1
269.0
0.95
284.3
295.5
305.1
313.6
1.25

Water temperature drop = 2.04 x MBH/gpm.


Connection size is -in OD male solder for 1-row coil
sizes 04-08. All other coils have -in OD male solder.
Coils are not intended for steam applications and are
labeled for a maximum water temperature of 200F.
Coils are tested for leakage at test pressure of 500 psi.
Water volumes less than those shown may result
in laminar flow and reduced heating capacity.
If possible reduce the number of coil rows to
increase water velocity into turbulent range.

Correction Factors for Other Entering Conditions


T

50

60

70

80

90

100

110

125

140

150

Factor

0.40

0.48

0.56

0.64

0.72

0.80

0.88

1.00

1.12

1.20

Note: Airside DPs reflects the air pressure drop of the hot water coil.

Single/Dual Duct Terminals

ELECTRIC COILS
Recommended Coil Selection Data
The table at the right describes the maximum recommended
kW capacities and number of stages available for
Titus single duct terminals.
To make a coil selection:
1. Check the desired kW is available in desired unit size
and number of stages. (Required to prevent excessive
watt density and current draw, while taking into account
unit size limitations.)
2. Check the desired minimum airflow limit is within
recommended operating range. (Ensures velocity
pressure will be sufficient to close airflow sensing
switch.)
3. Multiply desired minimum airflow limit by a factor of
0.0142 and check the result is equal to or greater than
desired kW. (Limits temperature rise across the coil
to 45F.)

kW cfm x 0.0142

Titus electric heating coils are specifically designed for use


with VAV terminal units. They include an extended plenum
section and diffuser plate to minimize stratification. The
heating elements are designed to minimize hot spots and
nuisance tripping of the thermal cutouts.
These requirements established to prevent excessive
temperature rise caused by low airflow and/or oversized
coils. Minimum airflow limits must be within recommended
ranges to ensure proper operation and long service life.
For optimum diffuser performance and maximum thermal
comfort, coil discharge temperatures should not be more
than 15F above desired room temperatures. For proper
coil operation it is recommended that coil discharge
temperatures do not to exceed 100F.

PESV, AESV, DESV / APPLICATION DATA (STAGED HEAT)


Inlet
Size

Heating
cfm Range

55-225

85-350

105-500

135-650

190-900

225-1050

10

300-1400

12

425-2000

14

575-3000

16

750-4000

24x16 1800-8000

Min

1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3

0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
1.0
2.0
3.0
1.0
2.0
3.0
1.0
2.0
3.0

Max
3.0
5.0
7.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5

240V
1 Phase
kW Range
Min
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
2.0
3.0
1.0
2.0
3.0
1.0
2.0
3.0

Max
3.0
5.0
7.5
9.5
11.0
11.0
11.0
11.0
11.0
11.0
11.0

277V
1 Phase
kW Range
Min
1.0
1.5
2.5
1.0
1.5
2.5
1.0
1.5
2.5
1.0
1.5
2.5
1.0
1.5
2.5
1.0
1.5
2.5
1.0
1.5
2.5
1.0
1.5
2.5
1.5
2.0
3.0
1.5
2.0
3.0
1.5
3.0
4.5

208V
3 Phase
kW Range

480V
3 Phase
kW Range

Max

Min

Max

Min

Max

3.0

1.5

3.0

2.5

3.0

5.0

1.5

5.0

2.5

5.0

7.5

1.5

7.5

2.5

7.5

9.5

1.5

9.5

2.5

9.5

13.0

1.5

13.0

2.5

13.0

13.0

1.5

16.0

2.5

16.0

13.0

1.5

16.0

2.5

21.0

13.0

1.5

16.0

2.5

30.0

16.0

3.0

36.0

16.0

3.0

36.0

16.0

4.0

36.0

13.0
13.0
13.0

1.5
2.0
3.0
1.5
2.0
3.0
1.5
2.0
3.0

Note: The Titus 480V, 3-phase


electric heat configuration
is 4-wire wye. Contact your
Titus representative for other
configuration options.

ELECTRIC COILS

208V
1 Phase
kW Range

Number
of
Steps
Available

www.titus-hvac.com | www.titus-energysolutions.com

SELECTION AND CAPACITIES

Useful formulas:
kW=

cfm x T

3160
Where T = air temperature rise.

or

T=

kW x 3160
cfm

or

cfm =

kW x 3160
T

M19

Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com

ELECTRIC COILS

ELECTRIC COILS

M20

SELECTION AND CAPACITIES

Recommended Coil Selection Data


The table at the right describes the maximum recommended
kW capacities and number of stages available for
Titus single duct terminals.
To make a coil selection:
1. Check the desired kW is available in desired unit size
and number of stages. (Required to prevent excessive
watt density and current draw, while taking into account
unit size limitations.)
2. Check the desired minimum airflow limit is within
recommended operating range. (Ensures velocity
pressure will be sufficient to close airflow sensing
switch.)
3. Multiply desired minimum airflow limit by a factor of
0.0142 and check the result is equal to or greater than
desired kW. (Limits temperature rise across the coil
to 45F.)

kW cfm x 0.0142

These requirements established to prevent excessive


temperature rise caused by low airflow and/or oversized
coils. Minimum airflow limits must be within recommended
ranges to ensure proper operation and long service life.
For optimum diffuser performance and maximum thermal
comfort, coil discharge temperatures should not be more
than 15F above desired room temperatures. For proper
coil operation it is recommended that coil discharge
temperatures do not to exceed 100F.

PESV, AESV, DESV / APPLICATION DATA (LYNERGY HEAT)


Inlet
Size

Heating cfm
Range

208V
1 Phase
kW Range

240V
1 Phase
kW Range

277V
1 Phase
kW Range

208V
3 Phase
kW Range

480V
3 Phase
kW Range

Min

Max

Min

Max

Min

Max

Min

Max

Min

Max

55-225

0.5

3.0

1.0

3.0

1.0

3.0

1.5

3.0

2.5

3.0

85-350

0.5

5.0

1.0

5.0

1.0

5.0

1.5

5.0

2.5

5.0

105-500

0.5

7.5

1.0

7.5

1.0

7.5

1.5

7.5

2.5

7.5

135-650

0.5

9.5

1.0

9.5

1.0

9.5

1.5

9.5

2.5

9.5

190-900

0.5

9.5

1.0

11.0

1.0

13.0

1.5

10.5

2.5

13.0

225-1050

0.5

9.5

1.0

11.0

1.0

13.0

1.5

10.5

2.5

16.0

10

300-1400

0.5

9.5

1.0

11.0

1.0

13.0

1.5

10.5

2.5

21.0

12

425-2000

0.5

9.5

1.0

11.0

1.0

13.0

1.5

10.5

2.5

25.0

14

575-3000

1.0

9.5

1.0

11.0

1.5

13.0

1.5

10.5

3.0

25.0

16

750-4000

1.0

9.5

1.0

11.0

1.5

13.0

1.5

10.5

3.0

25.0

24x16

1800-8000

1.0

9.5

1.0

11.0

1.5

13.0

1.5

10.5

4.0

25.0

Note: The Titus 480V, 3-phase electric heat configuration is 4-wire wye. Contact your
Titus representative for other configuration options.
Useful formulas:
kW=

cfm x T

or

T=

3160
Where T = air temperature rise.

kW x 3160
cfm

or

cfm =

kW x 3160
T

SUGGESTED SPECIFICATIONS
See Section O for control specifications.
1. Furnish and install Titus Model (P)(A)(D) ESV single
duct, variable air volume terminals of the sizes and
capacities shown in the plans.
2. Terminals shall be certified under the AHRI Standard
880 Certification Program and carry the AHRI Seal.
Noncertified terminals may be submitted after testing
at an independent testing laboratory under conditions
selected by the engineering consultant in full compliance
with AHRI Standard 880. These tests must be witnessed
by the engineering consultant with all costs to be borne
by the terminal manufacturer. Testing does not ensure
acceptance.
3. The terminal casing shall be minimum 22-gauge
galvanized steel, internally lined with -inch dual
density insulation which complies with UL 181 and NFPA
90A. All exposed insulation edges shall be coated with
NFPA 90A approved sealant to prevent entrainment
of fibers in the airstream. The discharge connection
shall be slip and drive construction for attachment to
metal ductwork. The casing shall be constructed to hold
leakage to the maximum values shown in the Casing
Leakage table.
4. The damper shall be heavy gauge steel with shaft
rotating in Delrin self-lubricating bearings. Nylon
bearings are not acceptable. Shaft shall be clearly
marked on the end to indicate damper position. Stickers
or other removable markings are not acceptable. The
damper shall incorporate a mechanical stop to prevent
overstroking and a synthetic seal to limit close-off
leakage to the maximum values shown in the Damper
Leakage table.
5. Actuators shall be capable of supplying at least 35-inch
lbs. of torque to the damper shaft and shall be mounted
externally for service access. Terminals with internal
actuator mounting or linkage connection must include
gasketed access panel, removable without disturbing
ductwork. Casing with access panel shall be constructed
to hold leakage to the maximum values shown in the
Casing Leakage table.
6. At an inlet velocity of 2000 fpm, the minumum static
pressure required to operate any terminal size shall not
exceed 0.13-inch wg for the basic terminal.
7. Sound ratings for the terminal shall not exceed ____
NC at ____ static pressure. Sound performance shall be
AHRI certified.

1. Hot water reheat coils shall be enclosed in a minimum


20-gauge galvanized steel casing with slip and drive
construction for attachment to metal ductwork. Coils
shall be factory installed on the terminal discharge. Fins
shall be rippled and corrugated heavy gauge aluminum,
mechanically bonded to tubes. Tubes shall be copper
with minimum wall thickness of 0.016-inch with male
solder header connections. Coils shall be leak tested
to 300 psi with minimum burst pressure of 1800 psi at
ambient temperature. Number of coil rows and circuits
shall be selected to provide performance as required per
the plans. Coil performance data shall be based on tests
run in accordance with AHRI Standard 410.

(Available on pressure independent terminals only)


1. Electric coils shall be supplied and installed on the
terminal by the terminal manufacturer. Coils shall be
ETL listed. Coils shall be housed in an attenuator section
integral with the terminal with element grid recessed
from unit discharge a minimum of 5 inches to prevent
damage to elements during shipping and installation.
Elements shall be 80/20 nickel chrome, supported
by ceramic isolators a maximum of 3.5 inches apart,
staggered for maximum thermal transfer and element
life and balanced to ensure equal output per step.
The integral control panel shall be housed in a NEMA
1 enclosure with hinged access door for access to all
controls and safety devices.
2. Electric coils shall contain a primary automatic reset
thermal cutout, a secondary manual reset thermal
cutout, differential pressure airflow switch for proof
of flow, and line terminal block. Unit shall include an
optional integral door interlock type disconnect switch
that will not allow the access door to be opened while
power is on. Non-interlocking type disconnects are not
acceptable. All individual components shall be UL listed
or recognized.
3. (Optional) Electric coils shall include line fusing, mercury
contactors mounted and wired within the control
enclosure.

OPTIONAL LYNERGY ELECTRIC HEAT

1. Proportional electric coils shall be supplied and installed


on the terminal by the terminal manufacturer. Coils shall
be ETL listed. Coils shall be housed in an attenuator
section integral with the terminal with element grid
recessed from unit discharge a minimum of 5 inches
to prevent damage to elements during shipping and
installation. Elements shall be 80/20 nickel chrome,
supported by ceramic isolators a maximum of 3
inches apart, staggered for maximum thermal transfer
and element life, and balanced to ensure equal output
per step. The integral control panel shall be housed in a
NEMA 1 enclosure with hinged access door for access to
all controls and safety devices.
2. Electric coils shall contain a primary automatic reset
thermal cutout, a secondary replaceable heat limiter per
element, differential pressure airflow switch for proof
of flow, and line terminal block. Coil shall include an
integral door interlock type disconnect switch, which
will not allow the access door to be opened while
power is on. Non-interlocking type disconnects are not
acceptable. All individual components shall be UL listed
or recognized.
3. Heaters shall be equipped with a Lynergy Comfort
Controller to control heater coil firing. The control panel
shall include an interface to control heater coil firing
in proportion to the ATC signal. The ATC signal shall
connect to low voltage universal signal interface circuitry
supplied and installed by the terminal manufacturer.
The universal interface shall allow at least the following
seven interface options without additional interface
circuitry.

SPECIFICATIONS

ACCESSORIES
HOT WATER REHEAT COILS

ELECTRIC REHEAT COILS

www.titus-hvac.com | www.titus-energysolutions.com

ESV BASIC UNIT

Single/Dual Duct Terminals

M21

Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com

SUGGESTED SPECIFICATIONS

SPECIFICATIONS

3. ATC equipment providers with 0-20mA or 4-20mA


signals shall supply and install a suitable dropping
resistor to convert the current signal to a 0-10VDC
signal or 2-10VDC signals:
PWM heat
2 stage heat
0-10V / 0-20mA
2-10V /4-20mA
Incremental T-stat
Binary
3 point floating
4. A downstream air temperature limit and control shall
be automatically invoked by adding a downstream air
temperature sensor. When invoked, the downstream
air from the heater shall not exceed an adjustable
maximum temperature set point. When the ATCs call
for heat is less than 100%, the heater shall control the
downstream air temperature to a point in proportion
to the span between the heaters probable entering
air temperature and the maximum air temperature set
point.

OPTIONAL STANDARD SCR ELECTRIC HEAT

1. Proportional, modulating electric coils shall be


supplied and installed on the terminal by the terminal
manufacturer. Coils shall be ETL listed. Coils shall
be housed in an attenuator section integral with the
terminal with element grid recessed from unit discharge
a minimum of 5 inches to prevent damage to elements
during shipping and installation. Elements shall be
80/20 nickel chrome, supported by ceramic isolators a
maximum of 3.5 inches apart, staggered for maximum
thermal transfer and element life, and balanced to
ensure equal output per step. The integral control panel
shall be housed in a NEMA 1 enclosure with hinged
access door for access to all controls and safety devices.
2. Electric coils shall contain a primary automatic reset
thermal cutout, a secondary manual reset thermal
cutout, proportional electronic airflow sensor for proof
of flow, and line terminal block. The proportional
electronic airflow sensor shall be totally independent
of the duct static pressure and shall adjust the heater
capacity according to the available airflow. The
heaters shall deliver maximum heating when needed
with normal minimum airflow, reduce heating with
lower than minimum airflow and stop heating with no
airflow. Unit shall include an integral door interlock
type disconnect switch which will not allow the access
door to be opened while power is on. Non-interlocking
type disconnects are not acceptable. All individual
components shall be UL listed or recognized.
3. Heaters shall be equipped with a proportional SCR
controller to modulate the heater load according to the
temperature control signal. The electronic controller
shall be compatible with the following input signals:
Variable voltage signal 0-10 VDC
Pulse width modulation AC or DC

M22

FIBRE-FREE LINER

(Substitute the following paragraph 3 for paragraph 3 in the


ESV Basic Unit Specification.)
3. The terminal casing shall be minimum 22-gauge
galvanized steel, internally lined with engineered
polymer foam insulation which complies to UL181 and
NFPA 90A. Insulation shall be 1 pound density, closed
cell foam. Exposed fiberglass is not acceptable. The
insulation shall be mechanically fastened to the unit
casing. The casing shall be constructed to hold leakage
to the maximum values shown in the Casing Leakage
table.

ESV Casing Leakage, cfm


INLET
SIZE
4, 5, 6
7, 8
9, 10
12
14
16

0.5
2
4
4
5
6
7

PS, IN WG
1.0
2.0
3
4
5
7
6
8
7
10
9
13
10
14

3.0
5
9
10
12
16
17

Damper Leakage, cfm


INLET
SIZE
4, 5, 6
7, 8
9, 10
12
14
16

1.0
3
3
3
3
3
4

PS, IN WG
2.0
4.0
4
6
4
6
4
6
4
6
5
7
5
7

6.0
7
7
7
7
8
9

ECOSHIELD

(Substitute the following paragraph 3 for paragraph 3 in the


ESV Basic Unit Specification.)
3. The terminal casing shall be minimum 22 gauge
galvanized steel (20 gauge for fan powered terminals),
internally lined with in. or 1 matte or foil faced
natural fiber insulation which complies with ASTM C 739
and NFPA 90A. The liner shall comply with ASTM G21
and G22 for fungi and bacterial resistance. All exposed
edges shall be coated with NFPA approved sealant to
prevent entrainment of fibers in the airstream.

STERI-LOC LINER

(Substitute the following paragraph 3 for paragraph 3 in the


ESV Basic Unit Specification.)
3. The terminal casing shall be minimum 22-gauge
galvanized steel, internally lined with a non-porous,
sealed liner which complies with UL 181 and NFPA 90A.
Insulation shall be 4 lb. density. All cut edges must be
sealed from the airstream using mechanically bonded
metal barrier strips. Liners made of Mylar, Tedlar, Silane
or woven fiberglass cloth are not acceptable. Insulation
shall be equivalent to Titus Steri-Loc or double wall
lining is acceptable. The casing shall be constructed
to hold leakage to the maximum values shown in the
Casing Leakage table.

Single/Dual Duct Terminals

SUGGESTED SPECIFICATIONS

www.titus-hvac.com | www.titus-energysolutions.com

ULTRALOC LINER

(Substitute the following paragraph 3 for paragraph 3 in the


ESV Basic Unit Specification.)
3. The terminal casing shall be minimum 22-gauge
galvanized steel. The units shall be lined with 1-inch
thick matte faced insulation, meeting UL 181 and
NFPA 90A, enclosed between the unit casing and a
non-perforated internal 22-gauge sheet metal cover
extending over the fiberglass insulation, as well as
covering the liner cut edges. The discharge connection
shall be slip and drive construction for attachment to
metal ductwork. The casing shall be constructed to hold
leakage to the maximum values shown in the Casing
Leakage table.

MODEL NUMBER SPECIFICATION


Model
Single Duct
Variable
Volume

X
P
E
A
D

ESV
Pneumatic
Electric
Analog Electric
Digital Electric

0
1

Base Unit

with Electric Coil


Attenuator Section

with Integral
Attenuator

1
3

No Inlet Sensor
AeroCrossTM
Sensor

Example: AESV 3120R 16

Analog electronically controlled single duct


variable volume terminal, with multi-point sensor,
integral attenuator, Steri-Loc lining, right hand
controls, 16 inlet size.

Casing
Configuration
Right Hand
0R
Left Hand
0L
XX

Standard
0
1
1
Steri-LocTM
2
UltraLoc
4
No Liner
6
Fibre-Free
9
EcoShield
J
EcoShield 1
K
EcoShield Foil
L
EcoShield Foil 1
M
Lining Type

XXX

Inlet
Size
(specify)

SPECIFICATIONS
M23

www.titus-hvac.com | www.titus-energysolutions.com

SUGGESTED SPECIFICATIONS

AHRI Directory Of Certified Performance


Titus is a charter member company and current participant
in the AHRI Directory of Certified Performance. This voluntary certification program was developed by participating
manufacturers in conjunction with the former Air-Conditioning and Refrigeration Institute (ARI) in the 1990s. It is
currently administrated by the Air-Conditioning, Heating,
and Refrigeration Institute (AHRI). The purpose of this
program is to provide for the independent verification of
manufacturers published performance data. Only participating products are authorized to bear the AHRI VAV Certification Mark. Certified data may be viewed and downloaded at
www.ahrinet.org .
In order to participate in this program, member companies
pay annual dues based on sales volume, submit published
performance data for all applicable model types, and agree
to provide a number of randomly selected product samples
for annual rounds of independent testing at the manufacturers expense. All verification testing is conducted in accordance with ASHRAE Standard 130 Methods of Testing Air
Terminal Units. These tests are conducted to verify that a
manufacturers published certified ratings are within the test
tolerances outlined in AHRI Standard 880 Performance Rating of Air Terminals. Any failure to demonstrate the certified
performance is punished by additional testing requirements,
mandatory performance re-rating, monetary penalties and
possible expulsion from the Certified Directory.
Product samples provided for certification testing are
standard production units with standard in dual density
fiberglass lining (unless otherwise specified) and no optional
appurtenances such as add-on attenuators or heating/cooling coils. The certified ratings are measured at the standard
operating points under the following test conditions:

SPECIFICATIONS

PESV, EESV, AESV, DESV

M24

Single/Dual Duct Terminals

Rated airflow (cfm) Based on an


inlet velocity of 2000 fpm.
Rated Min Ps (in wg) Minimum static
pressure drop from the unit inlet to discharge
at rated airflow with damper full open.
Rated Ps (in wg) A static pressure drop of
1.5 in wg from unit inlet to discharge.
Rated sound power by octave band (dB, re 10-12 watts)
Radiated and discharge sound performance conducted
in a reverberation room that meets both the broadband
and pure tone qualifications of AHRI Standard 220.

PESV, AESV, DESV


Min
Ps

Radiated Sound
Power

Discharge Sound
Power

Inlet
Size

Rated
CFM

04

150

0.04 60 57 46 41 40 37 68 64 59 54 54 49

05

250

0.03 62 59 49 42 41 37 69 64 60 56 55 50

06

400

0.13 63 61 52 44 42 38 70 69 64 60 57 52

07

550

0.10 64 59 53 47 43 34 69 70 63 59 56 51

08

700

0.02 65 60 53 47 47 45 72 71 63 58 56 52

09

900

0.05 64 58 53 47 45 38 73 68 63 59 57 54

10

1100

0.01 67 62 57 55 54 43 74 70 65 63 60 55

12

1600

0.01 66 62 59 53 50 44 75 73 68 64 62 58

14

2100

0.04 66 62 55 53 50 46 72 68 66 63 63 59

16

2800

0.03 66 61 54 50 50 45 74 69 66 64 62 57

40

5300

0.06 79 74 72 68 67 64 85 80 77 72 73 69

Single/Dual Duct Terminals

Dual Duct Design Features


The concern for IAQ has led to renewed interest in the
benefits of dual duct systems. Dual duct systems are
an ideal vehicle for alternative ventilation strategies and
humidity control. Additionally, total filtration of all air
delivered to the zone is possible. Titus dual duct terminals
provide high performance and value, making them the
preferred selection for these applications.
Titus dual duct terminals vary the airflow individually
between hot and cold inlets for highly accurate temperature
control.
As the ratio of hot and cold air is critical in most
applications, pressure independent controls are used with a
separate velocity control loop to each inlet.

Titus dual duct terminals are available in three styles. In


those instances where no blending of airstreams is required,
the EDV without the integral attenuator assembly can be an
effective choice.
When blending of hot and cold supply air is needed
for accurate temperature control with minimum flow
requirements, the EDV or EDC with integral attenuator
should be used.
The attenuator reduces discharge sound levels and provides
some mixing benefit. An optional mixing baffle is available
for use with the attenuator to provide maximum blending
of hot and cold airstreams. Less than 1F temperature
variation is provided at the discharge with a 10F inlet
temperature differential!

www.titus-hvac.com | www.titus-energysolutions.com

TITUS DUAL DUCT TERMINAL - LEADERSHIP IN A RE-EMERGING TECHNOLOGY!

M
EDV NON MIXING

DEDV WITH OPTIONAL


MIXING BAFFLE

MDV WITH INTEGRAL MIXING


ATTENUATOR, DMDV SHOWN

All Titus dual duct terminals are available with Fibre-Free and other lining options.
20F inlet temperature differential. Additional ductwork is
not required downstream to achieve proper mixing, allowing
for immediate take-off to diffusers. This is also beneficial for
installations with space limitations.

Like the EDV/EDC, the MDV/MDC terminals use separate


pressure independent velocity control loops for each inlet,
rather than a single velocity controller for discharge volume
control only. This provides superior temperature control
during blending, as each inlet can compensate for duct
pressure changes without affecting the other.

The tightly sealed casing typically allows less than 1 percent


leakage of conditioned air to the space at 1.5 inches wg.
differential static pressure, making this one of the most
energy efficient dual duct terminals. The dampers are the
improved Titus low leakage design.

The unique internal mixing baffle design provides


for exceptional mixing characteristics. Less than 1F
temperature variation is provided at the discharge with a

All Titus dual duct terminals are also available with


EcoShield, Fibre-Free and Steri-Loc lining options. Specify
the MDV/MDC and you will be providing the best performing
dual duct terminal available.

DESIGN FEATURES

The Titus MDV/MDC Dual Duct Terminals have been


specially designed for those applications where comfort
levels are critical, as in hospitals, research facilities, and
other institutional applications.

M25

VAV, Zero Minimum - non-blending


In cooling mode, as temperature approaches setpoint, cold airflow modulates from
maximum to zero flow. As room temperature drops below setpoint, hot airflow
modulates from zero to maximum. Heating and cooling maximum flow rates can be
different. A deadband may be utilized.

Max HTG

cfm Increase

As this is a non-blending application, a mixer/attenuator section is not required.


For detailed information on specific control types, refer to the following pages in
Section S:

Max CLG*

Room Temperature Increase

Pneumatic: O20

Digital: O6 Model: EDV

VAV, Minimum Mix Equal to Maximum HTG - blending


In cooling mode, as temperature approaches setpoint, cold air modulates from
maximum to a minimum mix flow rate. As temperature continues to drop, hot
airflow modulates open as cold airflow closes, maintaining a minimum total flow
rate. Lower heating flow rates require unequal inlet sizes to maintain control. A
mixer/attenuator section is required.
Pneumatic: O20

Digital: O6 Model: EDV or MDV

Max CLG

cfm Increase

Single/Dual Duct Terminals

Max HTG

Room Temperature Increase

VAV, Minimum Mix, Unequal Maximum Flows - blending


Similar in cooling mode to the sequence above, when entering the heating mode a
flow rate higher than the minimum mix is employed. Maximum flow rates may be
close enough that equal inlet sizes may be used. A mixer/attenuator section
is required.
Pneumatic: O20

Digital: O6 Model: EDV or MDV

Max HTG

Max CLG

cfm Increase

www.titus-hvac.com | www.titus-energysolutions.com

DUAL DUCT CONTROL STRATEGIES

Room Temperature Increase

Pneumatic: O20

Digital: O6 Model: EDC or MDC

Max HTG

Room Temperature Increase

Optional Censor Location Configuration


For blending applications with integral mixer/attenuator. Multi-point velocity sensors
are available in four different configurations to match any application and control
requirement. Configurations 3B and 3C are to match hot or cold inlet
control requirements.
Pneumatic: O20

Digital: O6

3A

3B

Discharge

Hot

Hot Cold

3C
Hot

M26

Max CLG

cfm Increase

CONTROL STRATEGIES

Constant Volume Discharge - blending


In this sequence cooling and heating maximum flow rates are the same and
minimum mix flow rates are the same as maximums. The result is a constant
airflow over the entire cooling and heating range. A mixer/attenuator section is
required.

Cold

3D

Cold

Inlet

Hot Cold

= Sensor Location

Single/Dual Duct Terminals

Dual Duct without Attentuator


Available Models:

PEDV

DEDV

Pneumatic
Digital
Electronic

Standard matte faced insulation


for maximum thermal and
acoustic performance.
EDV

Standard 22 gauge casing with slip


and drive discharge connection.

FOR NON-BLENDING APPLICATIONS


ONLY

Controls supplied by Titus are


factory calibrated for quicker
start-up.

Standard AeroCrossTM multi-point


center averaging velocity sensors
in each inlet for accurate flow
control.
PEDV - Basic Unit with Controls
W

www.titus-hvac.com | www.titus-energysolutions.com

EDV

Pneumatic
Actuator

Discharge

A
Control Cover
(optional)

DEDV - Basic Unit with Controls


L

12

H
Discharge

A
F

cfm
Range

4
5
6
7
8
9
10
12
14
16

0-225
0-350
0-500
0-650
0-900
0-1050
0-1400
0-2000
0-3000
0-4000

12
12
12
12
12
14
14
16
20
24

3
4
5
6
7
8
9
11
13
15

6
F
PEDV
1
1
1

DEDV
2
2
2
1
1
-

Slip & Drive


Cleat Connection

7
7
7
7
7
5
5
5
3
3

8
8
8
10
10
12
12
15
17
18

15
15
15
15
15
15
15
15
15
15

5
5
3
3
3
3
3
3
3
3

24
24
24
24
24
28
28
32
40
48

All dimensions are in inches.

EDV

Inlet
Size

18

Control
Enclosure

M27

Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com

PERFORMANCE DATA

PEDV, DEDV WITHOUT ATTENUATOR - RADIATED SOUND PERFORMANCE


Size

10

12

M28

16

Min
Ps

100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600

0.02
0.03
0.04
0.06
0.08
0.01
0.02
0.03
0.04
0.06
0.07
0.10
0.13
0.16
0.20
0.07
0.09
0.10
0.12
0.15
0.02
0.02
0.02
0.02
0.03
0.04
0.04
0.05
0.06
0.06
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.02
0.02
0.03
0.04
0.05

2
52
55
58
61
63
53
56
59
62
63
59
60
61
62
63
61
62
63
63
64
62
63
63
64
65
61
61
62
62
63
63
64
65
65
66
62
63
64
65
66
60
62
63
64
66
59
61
63
65
66

3
48
52
55
58
60
49
53
56
59
61
54
57
58
60
61
54
55
57
58
59
55
56
57
58
59
53
54
55
56
56
57
58
58
59
60
56
57
59
60
61
56
58
59
60
61
53
56
58
60
61

1.0 Ps
4
5
6
39 36 35
42 38 36
44 40 38
46 42 39
47 43 40
41 36 35
44 38 37
46 40 39
48 42 41
49 43 42
45 39 37
47 41 38
49 42 39
50 44 40
51 45 41
48 42 38
49 43 39
50 45 40
51 46 41
52 47 41
49 43 43
50 44 44
50 45 44
51 46 45
52 47 46
49 42 40
49 43 41
50 43 41
50 43 42
50 44 42
53 50 48
54 51 49
54 52 50
54 53 51
55 53 52
52 47 43
54 48 45
55 49 46
56 50 48
57 51 49
50 48 45
51 49 46
52 50 47
53 51 48
54 52 49
47 45 44
49 47 46
51 48 47
52 50 49
54 51 50

7
31
32
34
34
35
30
32
34
35
36
33
34
35
36
37
30
30
31
31
32
39
40
41
41
42
35
35
35
36
36
37
38
39
40
41
37
39
40
41
43
41
42
43
43
44
38
39
41
42
44

NC
15
20
23
27
29
16
21
24
28
30
22
25
27
29
30
23
24
25
27
28
24
25
25
27
28
23
23
24
24
25
27
28
28
28
29
26
28
29
30
31
24
27
28
29
30
21
24
27
29
30

Octave Band Sound Power, Lw


1.5 Ps
2
3
4
5
6
7 NC
53 50 41 37 37 34 17
57 54 44 40 39 36 22
60 57 46 41 40 37 25
63 59 48 43 41 38 28
65 62 49 44 42 38 31
55 51 43 38 37 33 18
59 55 46 40 40 35 23
62 59 49 42 41 37 28
64 61 50 44 43 38 30
66 63 52 45 44 39 33
61 57 48 41 39 36 25
62 59 50 43 40 37 28
63 61 52 44 42 38 30
64 63 53 46 43 39 33
65 64 54 47 44 40 34
62 57 51 45 41 33 25
63 58 52 46 42 34 27
64 59 53 47 43 34 28
65 61 54 48 44 35 30
65 62 55 49 44 35 31
64 58 52 46 45 44 27
65 59 53 47 46 45 28
65 60 53 47 47 45 29
66 61 54 48 48 46 30
66 62 55 49 48 47 31
62 57 52 46 44 38 26
63 58 53 46 45 38 27
64 58 53 47 45 38 27
64 59 54 47 45 38 28
65 60 54 47 46 39 29
65 60 57 53 52 41 31
66 61 57 54 53 42 31
67 62 57 55 54 43 31
67 63 58 56 55 44 33
68 63 58 56 55 45 33
64 59 56 50 46 41 30
65 60 57 52 48 42 31
66 62 59 53 50 44 34
67 63 60 54 51 45 35
68 64 61 55 52 47 36
62 59 53 51 48 45 28
64 60 54 52 49 45 29
66 62 55 53 50 46 31
67 63 56 54 51 47 33
68 64 57 55 52 47 34
61 56 50 47 47 41 24
64 59 52 49 49 43 28
66 61 54 50 50 45 30
67 62 55 52 52 46 31
69 64 56 53 53 48 34

Radiated sound is the noise transmitted


through the unit casing.
Min Ps is the static pressure drop from the unit inlet
to the unit outlet with the cold damper full open.
Sound power levels are in dB, ref 10-12 watts.
Sound performance based on units lined with
standard dual density fiberglass lining.

2
55
58
61
64
66
57
60
63
65
67
63
64
65
66
67
63
64
66
66
66
65
66
67
67
68
63
64
65
65
66
67
67
68
69
69
66
67
68
69
69
64
66
67
69
70
63
65
67
69
71

3
51
55
58
61
63
53
57
61
63
65
59
62
63
65
67
59
60
62
63
64
60
61
62
63
64
59
60
61
62
62
63
64
64
65
66
61
63
64
65
67
61
63
64
65
66
58
61
63
64
66

2.0 Ps
4
5
6
43 38 39
45 41 40
47 42 42
49 44 43
51 45 44
45 39 39
48 42 41
51 44 43
52 45 44
54 47 45
50 42 41
52 44 42
54 46 43
55 47 45
56 49 46
53 46 43
54 48 44
55 49 45
56 50 46
57 51 46
54 47 47
55 48 48
56 49 49
56 50 50
57 51 50
55 48 47
55 49 47
56 49 48
56 49 48
57 50 48
59 56 54
59 56 55
60 57 56
60 58 57
61 58 58
58 53 49
60 54 51
61 55 52
62 56 54
63 57 55
55 53 50
56 54 51
58 55 52
58 56 53
59 57 54
52 49 49
54 51 51
55 52 52
57 53 54
58 55 55

7
36
38
39
40
41
35
37
39
40
41
38
39
40
41
42
35
36
37
37
38
47
48
48
49
50
40
40
40
40
40
44
45
46
47
48
43
45
47
48
49
47
48
49
49
50
44
46
48
49
50

NC
18
23
27
30
33
21
25
30
33
35
28
31
33
35
37
28
29
31
33
34
29
30
31
33
34
29
29
30
31
31
34
34
35
35
36
32
35
36
37
38
30
33
34
35
36
27
30
33
34
36

All performance based on tests conducted in


accordance with ASHRAE 130-2008 and AHRI 880-2008.
All NC levels determined using AHRI 885-2008
Appendix E. See Terminal Unit Engineering Guidelines.
Dash (-) in space denotes NC value less than NC10.
Only highlighted data points are AHRI certified. See
page M38 for AHRI Certified Performance Listings.

PERFORMANCE DATA

PERFORMANCE DATA

14

CFM

Single/Dual Duct Terminals

PERFORMANCE DATA

Size

10

12

16

Min
Ps

100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600

0.02
0.03
0.04
0.06
0.08
0.01
0.02
0.03
0.04
0.06
0.07
0.10
0.13
0.16
0.20
0.07
0.09
0.1
0.12
0.15
0.02
0.02
0.02
0.02
0.03
0.04
0.04
0.05
0.06
0.06
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.02
0.02
0.03
0.04
0.05

2
63
65
67
68
69
62
65
67
69
70
64
66
67
68
69
67
67
68
68
68
69
70
70
70
71
70
70
71
72
72
71
72
73
73
74
71
72
73
74
74
68
69
70
71
72
68
70
72
73
74

3
56
60
62
65
67
55
58
62
64
66
62
64
66
67
69
63
65
66
67
69
66
67
68
69
70
64
65
66
66
67
65
66
67
68
68
67
69
70
71
72
62
64
65
66
67
62
65
67
68
70

1.0 Ps
4
5
6
50 46 47
53 49 49
56 51 50
58 53 51
60 55 53
51 47 47
55 51 49
57 53 51
59 55 53
61 57 54
58 54 51
60 56 52
61 58 53
63 59 54
64 61 55
58 54 51
59 56 52
60 57 53
61 58 54
62 59 55
59 55 52
60 56 53
60 56 53
61 57 54
62 58 54
60 57 54
60 57 54
61 57 55
61 58 55
61 58 55
61 59 55
62 60 56
63 61 56
63 61 57
64 62 58
63 59 57
65 61 59
66 62 59
67 63 60
68 64 61
61 59 57
62 59 58
64 60 58
65 60 59
66 61 59
60 58 56
63 60 58
65 61 59
66 62 60
68 63 61

7
41
43
44
45
46
42
44
45
46
47
46
47
48
49
50
46
47
48
48
49
47
47
48
48
49
49
50
50
50
50
50
51
51
52
53
52
53
55
56
56
53
53
54
54
54
51
52
54
55
56

NC
18
20
23
24
27
17
20
23
22
24
20
22
24
25
28
21
23
24
25
28
24
25
27
27
28
21
22
23
23
24
22
23
24
25
25
24
27
28
29
30
18
21
22
23
24
18
22
24
25
28

Octave Band Sound Power, Lw


1.5 Ps
2
3
4
5
6
7 NC
64 58 53 49 50 46 19
66 61 56 52 52 47 22
68 64 59 54 54 49 24
69 66 61 56 55 50 25
70 69 62 58 56 51 29
64 57 54 50 51 46 19
67 61 58 53 53 48 23
69 64 60 56 55 50 25
70 67 62 58 56 51 25
72 69 64 60 57 52 28
67 65 61 57 54 50 23
68 67 63 59 55 51 25
70 69 64 60 57 52 28
71 70 66 62 58 53 29
72 72 67 63 59 54 31
68 67 60 56 54 49 25
69 68 62 58 55 50 27
69 70 63 59 56 51 29
70 71 63 60 57 52 30
70 72 64 61 58 53 31
71 69 61 56 55 51 28
71 70 62 57 55 51 29
72 71 63 58 56 52 30
72 72 63 58 56 52 30
72 73 64 59 57 53 31
71 67 62 59 57 53 24
72 68 62 59 57 54 25
73 68 63 59 57 54 25
73 69 63 60 58 54 27
74 70 64 60 58 54 28
72 68 64 61 58 54 25
73 69 65 62 59 55 27
74 70 65 63 60 55 28
75 71 66 64 60 56 29
75 72 67 65 61 56 30
73 70 65 62 60 56 28
74 72 67 63 61 57 30
75 73 68 64 62 58 31
75 74 70 65 63 59 33
76 75 71 66 64 60 34
70 66 63 62 62 59 23
71 67 65 63 62 59 24
72 68 66 63 63 59 25
73 69 68 64 63 59 27
74 70 69 64 63 60 28
70 65 62 61 59 54 22
72 67 64 62 61 56 24
74 69 66 64 62 57 27
75 71 68 65 63 59 29
76 72 70 66 64 60 30

Discharge sound is the noise emitted from the


unit discharge into the downstream ductwork.
Min Ps is the static pressure drop from the unit inlet
to the unit outlet with the cold damper full open.
Sound power levels are in dB, ref 10-12 watts.
Sound performance based on units lined with
standard dual density fiberglass lining.

2
65
67
68
70
71
65
68
70
71
73
69
70
71
73
74
70
70
71
71
72
72
72
73
73
74
72
73
74
74
75
73
74
75
76
76
74
75
76
76
77
72
73
74
74
75
71
73
75
76
78

3
59
62
65
68
70
59
63
66
69
71
67
69
71
73
74
69
71
72
73
74
72
73
74
75
75
69
70
70
71
72
71
72
72
73
74
72
74
75
76
77
68
70
71
72
73
67
69
71
72
74

2.0 Ps
4
5
6
55 51 53
58 54 55
60 56 57
63 58 58
64 60 59
57 52 53
60 55 55
62 58 57
65 60 59
66 61 60
63 58 56
65 60 58
66 62 59
68 63 60
69 65 61
62 58 56
63 59 57
64 60 58
65 61 59
66 62 59
63 57 57
64 58 57
64 59 58
65 60 58
66 60 59
64 60 59
64 61 59
65 61 59
65 61 60
65 62 60
66 63 61
67 64 61
67 65 62
68 66 63
68 66 63
67 64 62
69 65 63
70 66 64
71 67 65
72 68 66
65 65 65
67 65 65
68 66 66
69 66 66
70 67 66
63 63 61
66 64 62
68 66 64
70 67 65
71 68 66

7
49
51
52
53
54
49
51
53
54
55
53
54
55
56
57
52
53
54
55
55
54
54
55
55
56
56
56
57
57
57
57
57
58
59
59
59
60
61
62
63
62
63
63
63
63
57
58
60
61
62

NC
20
23
24
28
30
20
24
27
28
30
25
28
30
33
34
28
30
31
33
34
31
33
34
34
34
27
28
28
29
30
29
30
30
31
33
30
33
34
35
36
25
28
29
30
31
24
27
29
30
33

All performance based on tests conducted in


accordance with ASHRAE 130-2008 and AHRI 880-2008.
All NC levels determined using AHRI 885-2008
Appendix E. See Terminal Unit Engineering Guidelines.
Dash (-) in space denotes NC value less than NC10.
Only highlighted data points are AHRI certified. See
page M38 for AHRI Certified Performance Listings.

PERFORMANCE DATA

PERFORMANCE DATA

14

CFM

www.titus-hvac.com | www.titus-energysolutions.com

PEDV, DEDV WITHOUT ATTENUATOR - DISCHARGE SOUND PERFORMANCE

M29

Single/Dual Duct Terminals

EDV/EDC
Available Models:

PEDV/PEDC

DEDV

Pneumatic
Digital
Electronic

Standard matte faced insulation


for maximum thermal and
acoustic performance.
EDV

www.titus-hvac.com | www.titus-energysolutions.com

Dual Duct with Attentuator

Standard 22-gauge casing with slip


and drive discharge connection.

FOR BLENDING OR NON-BLENDING


APPLICATIONS

Controls supplied by Titus are


factory calibrated for quicker
start-up.

Standard AeroCrossTM multi-point


center averaging velocity sensors
in four location combinations to
match any control requirement.
PEDV - Basic Unit with Controls
L

D
A

Discharge
D

Slip & Drive


Cleat Connection
Controller
4
Pneumatic Actuator

DEDV - Basic Unit with Controls


G

4"

D
W

Discharge

A
D

Slip and Drive


Duct Connection
6"
18"

EDV, EDC

12"

M30

Inlet
Size
4
5
6
7
8
9
10
12
14
16

cfm
Range
0-225
0-350
0-500
0-650
0-900
0-1050
0-1400
0-2000
0-3000
0-4000

8
8
8
10
10
12
12
14
16
18

3
4
5
6
7
8
9
11
13
15

513/16
513/16
513/16
71/16
71/16
101/16
101/16
111/16
129/16
151/16

513/16
513/16
513/16
81/16
81/16
111/16
111/16
131/16
161/16
161/16

5
5
3
6
3
6
3
3
3
3

8
8
8
10
10
12
12
15
18
18

19
19
19
23
23
27
27
31
35
38

19
19
19
23
23
27
27
31
35
38

All dimensions are in inches.

PEDV
J
1
1
1

DEDV
K
2
2
2
1
1
-

Single/Dual Duct Terminals

PERFORMANCE DATA

Size

10

12

14

Min
Ps

100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600

0.18
0.29
0.41
0.56
0.73
0.17
0.30
0.47
0.67
0.92
0.51
0.70
0.91
1.15
1.42
0.35
0.44
0.53
0.63
0.74
0.40
0.47
0.55
0.63
0.71
0.18
0.21
0.23
0.26
0.29
0.25
0.31
0.38
0.45
0.53
0.25
0.33
0.44
0.55
0.68
0.18
0.25
0.34
0.45
0.57
0.21
0.30
0.40
0.53
0.67

2
46
48
50
52
53
48
51
53
55
57
51
52
52
NA
NA
59
60
61
62
62
58
58
59
59
60
62
63
63
64
65
60
60
61
61
61
64
65
65
66
66
62
63
64
65
65
65
66
66
67
68

3
46
49
51
52
54
45
48
51
53
54
51
53
54
NA
NA
52
53
54
55
56
52
53
54
55
56
53
53
54
54
55
52
52
53
54
55
56
57
58
59
60
54
56
57
58
60
55
57
58
59
60

1.0 Ps
4
5
6
37 31 29
40 33 31
42 35 33
44 37 34
45 38 36
38 32 32
42 35 35
44 37 37
47 39 38
48 40 40
43 38 36
44 39 37
46 41 38
NA NA NA
NA NA NA
46 41 40
47 42 41
48 43 41
49 43 42
49 44 43
45 39 37
46 39 38
46 40 38
47 41 39
47 41 39
45 41 42
45 42 42
46 42 42
46 42 43
46 43 43
44 40 38
45 41 39
46 41 40
47 42 40
47 42 40
52 50 53
54 51 53
55 52 54
56 52 54
57 53 54
47 42 43
49 43 44
51 45 45
52 46 46
53 47 47
50 45 47
52 46 48
54 47 48
56 48 49
57 49 49

7 NC
23 12
25 16
26 18
28 20
29 22
25 11
28 15
31 18
33 21
35 22
30 18
31 21
32 22
NA NA
NA NA
35 20
36 22
37 23
37 24
38 24
35 20
36 21
36 22
37 23
38 24
40 24
40 25
40 25
40 27
41 28
37 22
37 22
38 23
39 23
39 23
52 27
52 28
52 29
52 30
52 31
43 24
44 25
45 27
46 28
47 29
47 28
47 29
47 29
47 31
47 32

Octave Band Sound Power, Lw


1.5 Ps
2
3
4
5
6
7 NC
49 49 39 33 33 28 16
52 52 42 36 35 29 20
54 53 44 38 36 31 21
55 55 46 39 38 32 23
57 57 48 41 39 33 25
51 48 41 35 35 29 15
54 51 44 37 37 32 18
56 54 47 40 39 35 22
58 56 49 41 41 37 24
60 58 51 43 43 39 27
54 54 46 40 39 34 22
55 56 47 42 40 35 24
55 57 49 43 41 37 25
55 58 50 45 42 38 27
55 60 51 46 43 39 29
61 56 49 43 43 40 24
62 57 50 44 44 41 25
63 57 51 45 45 41 25
64 58 52 46 45 42 27
65 59 52 47 46 43 28
60 57 49 42 40 39 25
61 58 49 42 41 40 27
61 59 50 43 41 40 28
62 60 51 44 41 41 29
62 60 51 44 42 42 29
64 56 49 44 45 45 27
65 57 49 45 46 45 28
66 57 50 45 46 45 29
66 58 50 46 46 45 29
67 58 50 46 46 45 31
63 55 47 42 41 39 25
63 56 48 43 41 40 25
64 57 49 43 42 41 27
64 58 49 44 42 42 27
65 59 50 45 43 42 28
68 59 55 54 57 57 32
68 61 57 55 58 57 32
68 62 58 55 58 57 32
69 63 59 56 58 57 34
69 64 60 56 58 58 35
66 57 50 44 46 47 29
67 59 52 46 47 48 31
67 60 53 47 48 49 31
68 62 55 48 49 49 32
69 63 56 49 49 50 33
68 59 52 47 50 51 32
69 60 54 48 50 51 33
70 61 56 50 51 51 34
70 62 58 51 51 51 34
71 63 59 51 52 51 36

Radiated sound is the noise transmitted


through the unit casing.
Min Ps is the static pressure drop from the unit inlet
to the unit outlet with the cold damper full open.
Sound power levels are in dB, ref 10-12 watts.
Sound performance based on units lined with
standard dual density fiberglass lining.

2
52
54
56
58
59
53
56
58
60
62
57
57
57
57
58
63
64
65
65
66
62
63
63
64
64
66
66
67
68
68
65
66
66
66
67
70
70
71
71
72
68
69
70
70
71
70
71
72
73
73

3
51
53
55
57
59
50
54
56
58
60
57
58
60
61
62
58
59
60
61
61
60
61
62
63
64
59
59
60
61
61
58
59
60
61
61
62
63
64
65
66
60
61
63
64
65
61
62
64
65
66

2.0 Ps
4
5
6
41 35 35
44 38 37
46 40 39
48 41 40
49 43 41
43 36 36
46 39 39
49 41 41
51 43 43
53 45 44
48 42 41
50 44 42
51 45 44
52 47 45
53 48 45
51 45 45
52 46 46
53 47 47
54 48 48
55 48 48
51 44 42
52 44 43
53 45 43
53 46 43
54 46 44
52 47 48
52 47 48
52 47 48
53 48 49
53 48 49
49 44 42
50 44 43
51 45 44
51 46 44
52 46 44
58 57 60
59 58 61
60 58 61
61 59 61
62 59 62
52 46 47
54 47 49
55 49 49
57 50 50
58 51 51
53 49 51
56 50 52
58 51 53
59 52 53
61 53 54

7
31
33
34
36
37
32
35
38
40
42
37
39
40
41
42
43
44
45
45
46
42
43
43
44
44
48
48
48
49
49
41
42
43
44
44
61
61
61
61
61
49
50
51
52
53
53
53
53
53
53

NC
18
21
23
25
28
17
22
24
27
29
25
27
29
30
31
27
28
29
30
30
29
30
31
33
34
29
29
31
32
32
28
29
29
30
31
34
34
36
36
37
32
33
34
34
36
34
36
37
38
38

All performance based on tests conducted in


accordance with ASHRAE 130-2008 and AHRI 880-2008.
All NC levels determined using AHRI 885-2008
Appendix E. See Terminal Unit Engineering Guidelines.
Dash (-) in space denotes NC value less than NC10.
Only highlighted data points are AHRI certified. See
page M38 for AHRI Certified Performance Listings.

PERFORMANCE DATA

16

CFM

www.titus-hvac.com | www.titus-energysolutions.com

PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR AND MIXING BAFFLES / RADIATED SOUND PERFORMANCE

M31

Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com

PERFORMANCE DATA

PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR AND MIXING BAFFLES / DISCHARGE SOUND PERFORMANCE
Size

10

12

PERFORMANCE DATA

14

M32

16

CFM Min Ps
100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600

0.18
0.29
0.41
0.56
0.73
0.17
0.30
0.47
0.67
0.92
0.51
0.70
0.91
1.15
1.42
0.35
0.44
0.53
0.63
0.74
0.40
0.47
0.55
0.63
0.71
0.18
0.21
0.23
0.26
0.29
0.25
0.31
0.38
0.45
0.53
0.25
0.33
0.44
0.55
0.68
0.18
0.25
0.34
0.45
0.57
0.21
0.30
0.40
0.53
0.67

2
55
58
60
62
64
53
57
60
62
64
56
57
58
NA
NA
60
62
63
64
65
61
62
62
63
63
67
68
68
69
70
67
68
69
69
70
67
68
70
71
71
66
68
70
71
72
68
69
70
71
72

3
52
55
58
60
62
51
55
58
61
63
56
57
58
NA
NA
60
61
62
63
64
61
62
63
63
64
61
61
62
62
63
60
61
62
63
64
61
62
64
65
66
60
62
63
64
65
60
62
64
65
66

1.0 Ps
4
5
6
47 44 44
50 47 47
53 49 49
55 51 51
57 53 53
46 43 45
50 47 48
53 49 50
56 51 52
58 53 54
51 49 50
53 50 52
55 52 53
NA NA NA
NA NA NA
53 49 51
55 50 52
56 51 53
57 52 54
58 53 55
55 51 53
55 52 54
56 53 54
57 53 55
57 54 55
54 52 54
54 52 55
55 52 55
55 53 55
56 53 56
54 52 56
55 53 56
56 53 57
56 54 57
57 54 57
55 53 56
57 54 57
58 55 58
60 56 59
61 57 60
54 53 56
56 54 57
58 55 58
59 56 59
60 57 60
55 53 58
57 55 59
59 56 60
61 58 61
62 59 61

7
36
40
43
46
48
40
44
47
50
52
48
49
51
NA
NA
48
49
50
52
53
51
52
52
53
54
52
52
53
54
54
55
56
57
58
59
55
57
58
59
60
56
58
59
61
62
58
60
61
62
63

Octave Band Sound Power, Lw


1.5 Ps
NC 2
3
4
5
6
7 NC
- 56 53 48 45 45 38 10
12 59 56 51 48 48 41 14
16 62 59 54 50 50 45 17
18 64 61 56 52 52 47 20
21 66 63 58 54 54 50 22
- 55 53 49 45 48 43 10
12 59 57 53 49 50 47 15
16 62 61 56 51 53 50 20
18 64 63 58 53 54 53 21
21 66 65 60 55 56 55 23
12 59 59 54 51 53 51 16
14 60 60 56 52 54 53 17
15 61 61 57 54 55 54 18
NA 62 62 59 55 56 55 20
NA 63 63 60 56 57 56 21
17 62 62 56 52 54 51 20
18 64 63 57 53 55 53 21
20 65 64 58 53 56 54 22
21 66 66 59 54 56 55 24
22 67 67 60 55 57 56 25
18 63 64 57 53 55 54 22
20 64 65 58 54 56 55 23
21 64 66 59 55 57 56 24
20 65 67 60 55 57 57 24
21 65 67 60 56 58 57 24
17 70 64 57 55 57 56 21
18 70 65 58 55 57 56 22
18 71 65 58 55 58 57 22
19 72 66 59 56 58 57 23
20 72 66 59 56 58 58 23
17 70 64 58 55 58 59 21
18 71 65 59 56 59 60 22
19 72 66 60 57 59 61 23
20 73 67 60 57 60 62 24
21 73 68 61 57 60 62 25
17 70 65 58 56 58 58 22
18 72 66 60 57 59 60 23
21 73 67 61 58 60 61 24
22 74 68 63 59 61 62 25
23 75 69 64 60 62 63 27
16 70 64 58 56 58 59 21
18 71 66 60 57 60 61 23
20 73 67 61 58 61 62 24
22 74 68 62 59 62 64 25
23 75 69 64 60 62 65 27
18 71 64 58 56 60 61 22
19 73 66 60 58 61 63 24
21 74 67 62 59 62 64 25
22 75 69 64 60 63 66 27
23 76 70 65 61 64 67 28

Discharge sound is the noise emitted from the


unit discharge into the downstream ductwork.
Min Ps is the static pressure drop from the unit inlet
to the unit outlet with the cold damper full open.
Sound power levels are in dB, ref 10-12 watts.
Sound performance based on units lined with
standard dual density fiberglass lining.

2
57
60
63
65
67
56
60
63
65
67
61
63
64
64
65
64
65
66
67
68
65
65
66
67
67
72
72
73
74
74
72
73
74
75
76
73
74
75
76
77
72
74
75
77
78
74
75
77
78
79

3
54
57
60
62
64
55
59
62
65
67
61
62
64
65
66
64
65
66
67
68
67
67
68
69
70
67
67
68
68
69
67
68
69
70
70
67
69
70
71
72
67
68
70
71
72
67
69
70
71
73

2.0 Ps
4
5
6
49 46 46
52 49 49
55 51 52
57 53 54
59 55 55
50 47 49
54 50 52
57 53 54
60 55 56
62 56 58
56 52 55
58 54 56
60 55 57
61 56 58
62 57 59
58 53 56
59 54 57
60 55 57
61 56 58
62 57 59
59 55 57
60 56 58
61 56 58
62 57 59
62 58 59
60 57 59
61 57 59
61 57 59
61 58 60
62 58 60
61 58 60
62 58 60
62 59 61
63 59 61
63 60 62
61 58 60
62 59 61
64 60 62
65 61 63
66 62 63
60 58 60
62 59 61
64 60 62
65 61 63
66 62 64
60 58 62
63 60 63
64 61 64
66 62 65
67 63 65

7
39
43
46
49
51
45
49
52
55
57
54
55
56
58
59
54
55
56
58
59
57
57
58
59
60
58
59
60
60
61
61
62
63
64
65
61
62
64
65
66
62
63
65
66
67
64
65
67
68
69

NC
11
15
18
21
23
12
17
21
23
25
18
20
22
23
24
22
23
24
25
27
25
25
27
27
28
24
24
25
25
27
24
25
27
28
28
24
27
28
29
30
24
25
28
29
31
25
27
29
31
32

All performance based on tests conducted in


accordance with ASHRAE 130-2008 and AHRI 880-2008.
All NC levels determined using AHRI 885-2008
Appendix E. See Terminal Unit Engineering Guidelines.
Dash (-) in space denotes NC value less than NC10.
Only highlighted data points are AHRI certified. See
page M38 for AHRI Certified Performance Listings.

Single/Dual Duct Terminals

Dual Duct High Performance Blending

Standard matte faced insulation


for maximum thermal and
acoustic performance.

Available Models:

PMDV/PMDC Pneumatic

DMDV
Digital

Electronic
Standard AeroCrossTM multi-point
center averaging velocity sensors
available in multiple location
combinations to match any
control requirement.

MDV

Standard 22-gauge casing with slip


and drive discharge connection.
Controls supplied by Titus are
factory calibrated for quicker
start-up.

PMDV/PMDC - Basic Unit with Controls


G

4"

D
A

Discharge
D

Slip and Drive


Duct Connection

www.titus-hvac.com | www.titus-energysolutions.com

MDV/MDC

Controllers

4"

Pneumatic Actuator

DMDV - Basic Unit with Controls


8"
Max
G

4"

H
6"
F

D
W

Discharge

A
D

Slip and Drive


Duct Connection
6"
18"

K
12"

cfm
Range
0-225
0-350
0-500
0-650
0-900
0-1050
0-1400
0-2000
0-3000
0-4000

8
8
8
10
10
12
12
14
16
18

3
4
5
6
7
8
9
11
13
15

5
5
5
7
7
10
10
11
12
15

5
5
5
8
8
11
11
13
16
16

5
5
3
6
3
6
3
3
3
3

8
8
8
10
10
12
12
15
18
18

34
34
34
42
42
50
50
58
66
72

19
19
19
23
23
27
27
31
35
38

All dimensions are in inches.

PMDV DMDV
J
K
1
2
1
2
1
2

1
-

MDV, MDC

Inlet
Size
4
5
6
7
8
9
10
12
14
16

M33

Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com

PERFORMANCE DATA
PMDV, PMDC, DMDV / RADIATED SOUND PERFORMANCE
Size

10

12

PERFORMANCE DATA

14

M34

16

CFM

Min
Ps

100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600

0.18
0.29
0.41
0.56
0.74
0.15
0.27
0.42
0.60
0.82
0.43
0.58
0.76
0.96
0.39
0.32
0.39
0.47
0.56
0.66
0.37
0.43
0.50
0.57
0.65
0.20
0.22
0.25
0.28
0.31
0.21
0.26
0.31
0.37
0.44
0.29
0.39
0.51
0.64
0.80
0.16
0.23
0.31
0.41
0.52
0.20
0.28
0.39
0.50
0.64

2
55
56
57
58
59
55
58
60
62
63
58
59
60
60
63
62
63
64
64
65
62
63
63
64
64
67
67
68
68
68
63
64
65
65
66
68
69
70
70
71
66
67
68
69
70
70
71
72
73
74

3
50
52
53
55
56
51
54
55
57
58
54
54
55
56
57
56
57
58
58
59
56
57
57
58
58
57
58
58
58
59
58
59
59
60
61
60
61
62
63
64
58
60
61
62
63
60
61
62
63
64

1.0 Ps
4
5
6
42 36 35
43 38 36
44 39 37
45 39 38
46 40 38
43 34 29
45 37 34
46 39 37
48 41 40
49 43 42
46 41 41
47 42 42
48 44 43
48 45 44
48 43 41
48 42 40
48 43 41
49 43 41
49 44 42
50 45 42
48 42 40
49 43 41
50 44 41
50 45 42
50 45 43
47 40 38
48 41 39
48 42 40
49 42 40
49 43 41
51 47 47
52 48 48
53 48 49
53 49 49
54 49 49
54 53 54
55 54 55
57 54 56
58 55 57
58 56 57
49 41 38
52 43 41
54 45 43
56 47 45
57 49 47
53 45 42
55 47 44
57 50 47
59 51 49
61 53 51

7
31
32
33
34
34
21
27
32
36
40
37
38
38
39
36
36
36
37
37
37
38
39
39
40
40
29
30
30
31
31
47
47
48
48
48
52
52
53
54
54
31
34
36
38
40
37
40
42
44
45

NC
17
20
21
23
24
18
22
23
25
27
22
22
23
24
25
24
25
27
27
28
24
25
25
27
27
31
31
32
32
32
27
28
28
29
30
32
33
34
34
36
29
31
32
33
34
34
36
37
38
40

Octave Band Sound Power, Lw


1.5 Ps
2
3
4
5
6
7 NC
57 53 45 38 37 34 21
58 55 46 40 38 35 23
59 56 47 41 39 36 24
60 58 48 42 40 36 27
61 59 49 42 41 37 28
58 55 47 37 32 24 23
60 57 49 40 36 30 25
63 59 50 43 40 35 28
64 60 52 45 42 40 29
66 62 53 46 45 43 31
61 58 50 44 45 41 27
66 62 53 46 45 43 31
63 59 51 47 47 43 28
64 60 52 48 48 43 29
64 60 53 49 49 44 29
64 60 51 45 44 41 29
65 61 52 46 45 42 30
66 61 53 46 45 42 30
67 62 53 47 46 42 31
68 62 54 48 46 43 32
65 61 52 45 44 43 30
66 61 53 46 45 43 30
67 61 53 47 45 44 31
67 62 54 48 46 44 31
68 62 54 48 47 45 32
70 61 51 43 41 34 34
70 62 52 44 42 34 34
71 62 52 45 42 35 36
71 62 52 46 43 35 36
71 63 53 46 44 36 36
68 63 54 50 51 51 33
69 63 55 51 52 51 33
69 64 56 51 52 52 34
70 65 56 52 53 52 35
70 65 57 52 53 53 35
71 63 58 57 58 57 36
72 65 59 58 59 58 37
73 66 60 58 60 58 38
74 67 61 59 61 59 40
75 67 62 60 62 59 41
70 62 52 43 40 35 34
71 64 54 46 43 37 36
72 65 56 48 46 40 37
73 66 58 50 48 42 38
74 67 60 51 50 44 40
74 64 56 48 44 41 40
75 65 58 50 47 43 41
76 66 60 52 49 45 42
77 68 62 54 51 47 43
78 68 64 56 53 49 45

Radiated sound is the noise transmitted


through the unit casing.
Min Ps is the static pressure drop from the unit inlet
to the unit outlet with the cold damper full open.
Sound power levels are in dB, ref 10-12 watts.
Sound performance based on units lined with
standard dual density fiberglass lining.

2
58
60
61
62
62
59
62
64
66
67
64
67
65
66
67
66
67
68
69
70
68
68
69
69
70
72
72
73
73
73
71
72
73
73
74
74
75
76
77
78
73
74
75
76
77
77
78
79
80
80

3
55
57
58
60
61
57
59
61
63
64
61
64
62
63
63
62
63
64
64
65
63
64
64
65
65
64
65
65
65
66
66
66
67
68
68
66
67
68
69
70
65
66
68
69
69
67
68
69
70
71

2.0 Ps
4
5
6
47 40 39
49 41 40
50 42 41
50 43 41
51 44 42
50 39 34
52 42 38
53 45 41
55 47 44
56 48 47
52 47 47
56 48 47
54 49 50
55 50 51
56 51 52
54 47 47
56 51 52
55 48 48
56 49 49
56 50 49
55 47 47
56 48 47
56 49 48
57 50 49
57 50 49
54 46 43
54 46 44
55 47 45
55 48 45
56 49 46
57 52 54
57 53 54
58 53 55
59 54 55
59 54 56
60 60 61
61 61 62
62 61 63
63 62 64
64 63 65
54 45 42
56 48 45
58 50 47
60 52 50
62 53 51
58 50 46
60 52 49
62 54 51
64 56 53
66 58 55

7
36
37
38
39
39
26
33
38
42
45
44
45
46
46
47
45
47
46
46
46
46
47
47
48
48
37
38
38
39
39
54
54
55
55
55
60
61
62
62
63
37
40
42
44
46
43
46
48
50
51

NC
23
25
27
29
30
25
28
30
33
34
30
34
31
33
33
31
33
34
34
35
33
34
34
35
35
37
37
38
38
38
36
37
38
38
40
40
41
42
43
45
38
40
41
42
43
43
45
46
47
47

All performance based on tests conducted in


accordance with ASHRAE 130-2008 and AHRI 880-2008.
All NC levels determined using AHRI 885-2008
Appendix E. See Terminal Unit Engineering Guidelines.
Dash (-) in space denotes NC value less than NC10.
Only highlighted data points are AHRI certified. See
page M38 for AHRI Certified Performance Listings.

Single/Dual Duct Terminals

PERFORMANCE DATA

Size

10

12

14

Min
Ps

100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600

0.18
0.29
0.41
0.56
0.74
0.15
0.27
0.42
0.60
0.82
0.43
0.58
0.76
0.96
0.39
0.32
0.39
0.47
0.56
0.66
0.37
0.43
0.50
0.57
0.65
0.20
0.22
0.25
0.28
0.31
0.21
0.26
0.31
0.37
0.44
0.29
0.39
0.51
0.64
0.80
0.16
0.23
0.31
0.41
0.52
0.20
0.28
0.39
0.50
0.64

2
53
56
59
61
63
56
60
63
65
67
62
64
65
66
67
65
67
68
69
70
66
67
67
68
69
68
69
69
70
71
69
70
71
72
73
72
74
75
76
77
71
73
75
77
78
74
76
77
79
80

3
51
54
57
59
61
53
57
61
63
66
59
61
62
63
64
62
64
65
66
67
63
64
64
65
66
62
62
63
63
63
63
64
65
66
67
64
66
68
69
71
62
65
67
69
71
65
68
70
71
73

1.0 Ps
4
5
6
47 44 38
49 46 42
52 48 45
53 50 48
55 52 50
49 45 38
52 48 44
55 51 48
57 53 51
59 55 54
53 50 46
54 52 49
55 53 51
56 54 53
57 52 52
56 51 50
57 52 52
58 53 53
59 54 55
60 55 56
57 52 51
58 53 52
59 53 53
60 54 54
60 55 55
57 50 48
58 51 49
58 52 50
58 52 51
59 53 52
58 54 52
59 55 53
60 56 55
61 57 56
62 58 58
60 54 53
62 56 56
63 58 59
65 60 61
66 61 63
58 51 51
60 54 54
62 56 57
64 59 59
66 60 61
61 55 54
63 58 58
66 61 60
67 63 63
69 65 65

7
28
34
38
42
46
31
39
45
50
54
39
43
45
48
48
45
48
50
52
54
46
48
50
51
53
44
45
47
48
49
46
48
50
52
53
49
52
55
57
59
45
48
51
54
56
49
52
56
58
61

NC
11
15
17
20
10
15
20
21
24
16
18
20
21
22
20
22
23
24
25
21
22
22
22
23
18
19
20
20
22
20
21
22
23
24
29
32
33
34
36
28
31
33
36
37
32
34
36
38
40

Octave Band Sound Power, Lw


1.5 Ps
2
3
4
5
6
7 NC
55 53 49 46 40 30 10
58 56 52 49 44 36 14
61 59 54 51 47 40 17
63 61 56 53 50 44 20
65 63 57 54 52 47 22
57 55 51 47 40 33 12
61 59 55 51 46 40 17
64 63 58 54 50 46 22
67 65 60 56 53 51 23
69 68 62 58 56 55 27
65 62 56 53 48 42 20
69 68 62 58 56 55 27
68 65 59 56 53 48 23
69 67 60 57 55 50 25
69 68 61 58 56 53 27
67 65 59 53 51 47 23
69 66 60 55 53 50 24
70 67 61 55 55 52 25
71 69 62 56 57 54 28
72 70 63 57 58 56 29
69 66 61 55 52 48 24
69 67 62 56 54 50 25
70 67 62 56 55 52 25
71 68 63 57 56 53 25
71 69 64 58 57 55 27
71 65 61 53 51 47 22
72 66 61 54 52 48 23
72 66 62 54 53 49 23
73 67 62 55 54 50 24
73 67 62 56 54 51 24
73 67 62 56 54 49 24
74 68 63 58 55 51 25
75 69 64 59 57 52 27
75 69 64 60 58 54 27
76 70 65 60 60 56 28
75 67 63 56 55 51 33
76 69 65 58 58 54 34
78 71 67 60 61 57 37
79 72 68 62 63 59 38
80 74 69 64 65 61 40
74 66 61 53 53 47 32
76 68 63 56 56 51 34
78 70 65 59 59 54 37
79 72 67 61 61 56 38
81 74 69 63 63 58 41
77 68 64 57 56 51 36
79 71 66 60 60 55 38
80 73 68 63 63 58 40
82 75 70 65 65 60 42
83 76 72 67 67 63 43

Discharge sound is the noise emitted from the


unit discharge into the downstream ductwork.
Min Ps is the static pressure drop from the unit inlet
to the unit outlet with the cold damper full open.
Sound power levels are in dB, ref 10-12 watts.
Sound performance based on units lined with
standard dual density fiberglass lining.

2
56
59
62
64
66
59
63
66
68
70
67
70
69
70
71
69
71
71
72
73
71
71
72
73
73
73
74
74
75
75
75
76
77
78
79
77
78
80
81
82
76
78
80
81
83
79
81
83
84
85

3
54
57
60
62
64
56
61
64
67
69
64
69
68
69
70
66
70
69
70
71
68
69
70
70
71
68
68
69
69
70
69
70
71
72
73
69
71
73
75
76
68
71
73
75
76
71
73
75
77
78

2.0 Ps
4
5
6
51 48 42
54 51 45
56 53 49
58 55 51
59 56 54
53 49 42
57 53 47
59 56 51
62 58 55
64 60 57
59 55 50
64 60 57
61 58 54
63 59 56
63 60 58
61 55 52
63 60 58
63 57 56
64 58 58
65 59 59
63 57 54
64 58 55
65 59 56
65 59 57
66 60 58
63 55 52
64 56 53
64 57 54
65 57 55
65 58 56
64 58 55
65 60 57
66 61 58
67 62 60
68 62 61
65 58 57
67 60 60
69 62 62
70 64 64
72 65 66
63 55 54
65 58 57
67 60 60
69 62 63
71 64 65
65 59 58
68 62 61
70 65 64
72 67 66
74 69 69

7
32
37
42
46
49
34
41
47
52
56
43
56
49
52
54
48
54
53
55
57
50
51
53
55
56
48
50
51
52
53
50
52
54
56
57
53
56
58
61
63
49
53
55
58
60
53
56
59
62
64

NC
11
15
18
21
23
14
20
23
25
28
22
28
27
28
29
24
29
28
29
30
27
28
29
28
29
25
25
27
27
28
27
28
29
31
32
36
37
40
41
42
34
37
40
41
43
38
41
43
45
46

All performance based on tests conducted in


accordance with ASHRAE 130-2008 and AHRI 880-2008.
All NC levels determined using AHRI 885-2008
Appendix E. See Terminal Unit Engineering Guidelines.
Dash (-) in space denotes NC value less than NC10.
Only highlighted data points are AHRI certified. See
page M38 for AHRI Certified Performance Listings.

PERFORMANCE DATA

16

CFM

www.titus-hvac.com | www.titus-energysolutions.com

PMDV, PMDC, DMDV / DISCHARGE SOUND PERFORMANCE

M35

www.titus-hvac.com | www.titus-energysolutions.com

SUGGESTED SPECIFICATIONS

EDV BASIC UNIT WITHOUT ATTENUATOR


EDV/EDC BASIC UNIT WITH MIXER-ATTENUATOR
MDV/MDC BASIC UNIT WITH MIXER-ATTENUATOR
See Section O for control specifications.

1. Furnish and install Titus Model (P)(D)(EDV)(EDC)


(MDV)(MDC) dual duct, (variable)(constant) air volume
terminals of the sizes and capacities shown in the plans.
2. Terminals should be certified under the AHRI Standard
880 Certification Program and carry the AHRI Seal.
Noncertified terminals may be submitted after testing
at an independent testing laboratory under conditions
selected by the engineering consultant in full compliance
with AHRI Standard 880. These tests must be witnessed
by the engineering consultant with all costs to be borne
by the terminal manufacturer. Testing does not ensure
acceptance.
3. The terminal casing shall be minimum 22-gauge
galvanized steel, internally lined with dual density
insulation which complies with UL 181 and NFPA 90A.
All exposed insulation edges shall be coated with NFPA
90A approved sealant to prevent entrainment of fibers
in the airstream. The casing shall be constructed to hold
leakage to the maximum values shown in the Casing
Leakage table.

EDV without Mixer Casing Leakage, cfm


Inlet
Size
4, 5, 6
7, 8
9, 10
12
14
16

0.5
4
7
8
10
13
14

Ps, in wg
1.0
2.0
6
8
10
14
12
17
14
20
18
25
20
28

3.0
10
17
21
24
31
35

EDV/EDC with Mixer and MDV/MDC


Casing Leakage, cfm

SPECIFICATIONS

Inlet
Size
4, 5, 6
7, 8
9, 10
12
14
16

M36

0.5
3
5
5
7
9
12

Ps, in wg
1.0
2.0
5
7
7
9
7
10
9
13
13
18
17
24

3.0
8
11
13
16
23
30

4. (Delete this paragraph for EDV without mixer-attenuator)


Each terminal shall include a mixer-attenuator section as
an integral part of the terminal to minimize downstream
stratification. The terminal shall provide less than 2F,
EDV/EDC (or 1F, MDV/MDC) discharge temperature
variation with a 20 differential in inlet temperature.
5. Cooling and heating inlets shall have separate damper
assemblies for complete pressure independent control
of each airstream for variable or constant volume total
discharge applications. Terminals with inlet dampers
mechanically interconnected are not acceptable. The
dampers shall be heavy gauge steel with solid shaft
rotating in Delrin self-lubricating bearings. Nylon
bearings are not acceptable. Shaft shall be clearly
marked on the end to indicate damper position. Stickers
or other removable markings are not acceptable. The
damper shall incorporate a mechanical stop to prevent
overstroking and a synthetic seal to limit close-off

Single/Dual Duct Terminals


leakage to the maximum values shown in the Damper
Leakage table.

Damper Leakage, cfm


Inlet
Size
4, 5, 6
7, 8
9, 10
12
14
16

1.0
3
3
3
3
3
4

Ps, in wg
2.0
4.0
4
6
4
6
4
6
4
6
5
7
5
7

6.0
7
7
7
7
8
9

6. Actuators shall be capable of supplying at least 35


inches per pound of torque to the damper shaft
and shall be mounted externally for service access.
Terminals with internal actuator mounting or linkage
connection must include gasketed access panel,
removable without disturbing ductwork. Casing with
access panel shall be constructed to hold leakage to the
maximum values shown in the Casing Leakage table.
7. Sound ratings for the terminal shall not exceed ____
NC at ____ static pressure. Sound performance shall be
AHRI certified.

ACCESSORIES
STERI-LOC LINER

(Substitute paragraph 3 below for paragraph 3 in the Basic


Unit specification).
3. The terminal casing shall be minimum 22-gauge
galvanized steel, internally lined with a non-porous,
sealed liner which complies with UL 181 and NFPA 90A.
Insulation shall be 4-pound density. All cut edges must
be sealed from the airstream using mechanically bonded
metal barrier strips. Liners made of Mylar, Tedlar, Silane
or woven fiberglass cloth are not acceptable. Insulation
shall be equivalent to Titus Steri-Loc or double wall
lining is acceptable. The casing shall be constructed
to hold leakage to the maximum values shown in the
Casing Leakage table.

FIBRE-FREE LINER

(Substitute paragraph 3 below for paragraph 3 in the Basic


Unit specification).
3. The terminal casing shall be minimum 22-gauge
galvanized steel, internally lined with engineered
polymer foam insulation which complies to UL181 and
NFPA 90A. Insulation shall be 1 pound density, closed
cell foam. Exposed fiberglass is not acceptable. The
insulation shall be mechanically fastened to the unit
casing. The casing shall be constructed to hold leakage
to the maximum values shown in the Casing Leakage
table.

ECOSHIELD

(Substitute the following paragraph 3 for paragraph 3 in the


ESV Basic Unit Specification.)
3. The terminal casing shall be minimum 22 gauge
galvanized steel (20 gauge for fan powered terminals),
internally lined with in. or 1 matte or foil faced
natural fiber insulation which complies with ASTM C 739
and NFPA 90A. The liner shall comply with ASTM G21

Single/Dual Duct Terminals

SUGGESTED SPECIFICATIONS

MODEL NUMBER SPECIFICATION


0
1
P
D
X

Model
Dual Duct

C
V

E
M

Standard

Pneumatic
Digital Electric

2
Constant Volume
Variable Volume

XX
3A

High
Performance
Mixing

3B

EXAMPLE: PEDV 3B100R 66


Pneumatically controlled, dual duct variable
volume terminal, with multi-point sensor in hot
inlet and total discharge locations, integral mixer/
attenuator, standard liner, right hand cold inlet
location, 6 cold and 6 hot inlet sizes.

3C

3D

Base Unit
with Integral Mixer/
Attenuator (EDC/EDV
only)
with Integral Mixer/
Attenuator and Mixing
Baffle (EDC/EDV only)

Casing
Configuration
0R Right Hand
0L Left Hand
XX

AeroCross Multipoint Sensor


(hot and cold
duct inlets)

0
1
2

Standard
Steri-LocTM

Cold
Inlet
Size

AeroCross Multipoint Sensor


(hot inlet and
total discharge
ducts)

Fibre-Free

(specify)

EcoShield

EcoShield 1

EcoShield Foil

EcoShield Foil 1

AeroCross Multipoint Sensor


(cold inlet and
total discharge
ducts)

Hot
Inlet
Size
(specify)

www.titus-hvac.com | www.titus-energysolutions.com

and G22 for fungi and bacterial resistance. All exposed


edges shall be coated with NFPA approved sealant to
prevent entrainment of fibers in the airstream.

Lining Type

AeroCross Multipoint Sensor


(total discharge
only)

SPECIFICATIONS
M37

Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com

SUGGESTED SPECIFICATIONS

AHRI Directory of Certified Performance


Titus is a charter member company and current participant
in the AHRI Directory of Certified Performance. This voluntary certification program was developed by participating
manufacturers in conjunction with the former Air-Conditioning and Refrigeration Institute (ARI) in the 1990s. It is
currently administrated by the Air-Conditioning, Heating,
and Refrigeration Institute (AHRI). The purpose of this
program is to provide for the independent verification of
manufacturers published performance data. Only participating products are authorized to bear the AHRI VAV Certification Mark. Certified data may be viewed and downloaded at
www.ahrinet.org .
In order to participate in this program, member companies
pay annual dues based on sales volume, submit published
performance data for all applicable model types, and agree
to provide a number of randomly selected product samples
for annual rounds of independent testing at the manufacturers expense. All verification testing is conducted in accordance with ASHRAE Standard 130 Methods of Testing Air
Terminal Units. These tests are conducted to verify that a
manufacturers published certified ratings are within the test
tolerances outlined in AHRI Standard 880 Performance Rating of Air Terminals. Any failure to demonstrate the certified
performance is punished by additional testing requirements,
mandatory performance re-rating, monetary penalties and
possible expulsion from the Certified Directory.
Product samples provided for certification testing are
standard production units with standard in dual density
fiberglass lining (unless otherwise specified) and no optional
appurtenances such as add-on attenuators or heating/cooling coils. The certified ratings are measured at the standard
operating points under the following test conditions:

SPECIFICATIONS

PEDV, PEDC, PMDV, PMDC, DEDV, DMDV

M38

PMDV, PMDC, DMDV


Min
Ps

Radiated Sound
Power

Discharge Sound
Power

Inlet
Size

Rated
CFM

04

150

0.41 59 56 47 41 39 36 61 59 54 51 47 40

05

250

0.42 63 59 50 43 40 35 64 63 58 54 50 46

06

400

0.76 63 59 51 47 47 43 68 65 59 56 53 48

07

550

0.47 66 61 53 46 45 42 70 67 61 55 55 52

08

700

0.50 67 61 53 47 45 44 70 67 62 56 55 52

09

900

0.25 71 62 52 45 42 35 72 66 62 54 53 49

10

1100

0.31 69 64 56 51 52 52 75 69 64 59 57 52

12

1600

0.51 73 66 60 58 60 58 78 71 67 60 61 57

14

2100

0.31 72 65 56 48 46 40 78 70 65 59 59 54

16

2800

0.39 76 66 60 52 49 45 80 73 68 63 63 58

PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR AND


MIXING BAFFLE
Min
Ps

Radiated Sound
Power

Discharge Sound
Power

Inlet
Size

Rated
CFM

04

150

0.41 54 53 44 38 36 31 62 59 54 50 50 45

05

250

0.47 56 54 47 40 39 35 62 61 56 51 53 50

06

400

0.91 55 57 49 43 41 37 61 61 57 54 55 54

07

550

0.53 63 57 51 45 45 41 65 64 58 53 56 54

08

700

0.55 61 59 50 43 41 40 64 66 59 55 57 56

09

900

0.23 66 57 50 45 46 45 71 65 58 55 58 57

10

1100

0.38 64 57 49 43 42 41 72 66 60 57 59 61

12

1600

0.44 68 62 58 55 58 57 73 67 61 58 60 61

Rated airflow (cfm) Based on an


14
2100 0.34 67 60 53 47 48 49
inlet velocity of 2000 fpm.
16
2800 0.40 70 61 56 50 51 51
Rated Min Ps (in wg) Minimum static
pressure drop from the cold inlet to discharge
at rated airflow with damper full open.
PEDV, DEDV WITHOUT ATTENUATOR
Rated Ps (in wg) A static pressure drop
Radiated Sound
of 1.5 in wg from cold inlet to discharge
Inlet Rated Min
Power
with the hot damper fully closed.
Size
CFM
Ps
2 3 4 5 6 7
Rated sound power by octave band (dB, re 10-12 watts)
Radiated and discharge sound performance conducted
0.04 60 57 46 41 40 37
04
150
in a reverberation room that meets both the broadband
05
250
0.03 62 59 49 42 41 37
and pure tone qualifications of AHRI Standard 220.

73 67 61 58 61 62
74 67 62 59 62 64

Discharge Sound
Power
2

68 64 59 54 54 49
69 64 60 56 55 50

06

400

0.13 63 61 52 44 42 38 70 69 64 60 57 52

07

550

0.10 64 59 53 47 43 34 69 70 63 59 56 51

08

700

0.02 65 60 53 47 47 45 72 71 63 58 56 52

09

900

0.05 64 58 53 47 45 38 73 68 63 59 57 54

10

1100

0.01 67 62 57 55 54 43 74 70 65 63 60 55

12

1600

0.01 66 62 59 53 50 44 75 73 68 64 62 58

14

2100

0.04 66 62 55 53 50 46 72 68 66 63 63 59

16

2800

0.03 66 61 54 50 50 45 74 69 66 64 62 57