h=
13
VIVIENDA
zona medianamente sismico
b= 0.25
h= 0.48
bo= 0.40 CUMPLE
ho = 0.38 CUMPLE usaremos: 0.40 x 0.40 m2
Para predimensionar el VOLADIZO de la viga V-102
Lv = 2.25
DATOS:
B = 4.9
Lv = 2.25
FACTOR = 13
b h
0.25 0.48
CUMPLE CUMPLE
usaremos: 0.25 x 0.50 m2
= 1.4
= 1.4*(
) = 1.4*(
2
)
=
20
2. Dimensionamiento de la viga V-104(b*h)
DATOS:
ancho = 0.25 m
largo = 2.1 m
FACTOR = 1.8 t/m albaileria maciza MURO=0.25 0.125
P. aliger. = 300 Kg/m2
P. acab. = 100 Kg/m2 4.5
P. tab. = 50 Kg/m2
S/C = 200 Kg/m2
L n = 6.2 m
FACT. VIVI. = 13
P = 0.95 t/m
P = 950 Kg/m2
W = 650 Kg/m2
Bad = 1.46 m
long. Afect. = 4.5 m
ancho muro= 0.25 m
B = 2.38 m
3.84 m
CALCULO DE LA BASE
HALLANDO
PESO DEL MURO DE FACHADA
PESOS EXTERIORES
CALCULO DE :
CALCULO DE :
=
/20
= B +
h=
13
VIVIENDA
= de albaileria maciza
W = . . + . . +. . +/
B =
..
2
+
2
= B +
=
=
/20
B = 0.19 m NO CUMPLE BASE MINIMA 0.25
CALCULO DE LA ALTURA
H = 0.48 m CUMPLE
RESPUESTA
usaremos: 0.25 x 0.50 m2
b= 0.19
h= 0.48
bo= 0.25 CUMPLE usaremos: 0.25 x 0.45 m2
ho = 0.44 CUMPLE
3. Dimensionamiento de la viga V-108(b*h)
se considerara el criterio de dimensionamiento de la viga de luz libre menor que corresponde a una losa aligerada reforzada en dos direcciones
DATOS:
A = 4.8
FACTOR = 13
4.8
b h
0.24 0.37
NO CUMPLE CUMPLE
BASE MINIMA 0.25
usaremos: 0.25 x 0.4 m2
alto riesgo sismico:
=
/20
h=
13
VIVIENDA
=
20
h=
13
VIVIENDA
Ejemplo N 2:
4.00
consideramos: 250
B= 5.00
S/C= m
ln= kg/m2
m
B
Solucion: 20
Ln b= 0.20 m
0.58 1.4(2*Ln/12)
h=
m 0.60 m
utilizando igualdad de rigideces:
0.25
bo= 0.56
m
ho= usar: 0.25*0.60 m2
m
Ejemplo N 3:
1. Dimensionamiento de la viga de un tramo con apoyos monoliticos m
kg/m2
B= 4.00 m
S/C= 250
Ln= 4.75
Solucion:
b=
h=
=
B
20 b= 0.20 m
Ln
m 1.25(Ln/12)
h= 0.49
0.90 m
usando el criterio de igualdad de cuantias:
0.25
bo= 0.44
m
ho= usar: 0.25*0.49 m2
m
b=
h=
=
se tiene un edificio aporticado de 10 pisos cuya planta tipica se muestra en la figura adjunta; el uso es de oficinas, considere los techos aligerados
de 0.25m, tabiqueria de 120kg/m2, acabados de 100kg/m2, fc=420kg/cm2, fy=4200kg/cm2. se pide dimensionar las columnas sealadas.
N pisos 10
uso oficinas
Aligerado 350 kg/m2
tabiqueria 120 kg/m2
Acabados 100 kg/m2
P.P. Vigas 100 kg/m2
P.P. Columnas 60 kg/m2
s/c 250 kg/m2
f'c 420 kg/cm2
Fy 4200 kg/cm2
WD = 730 kg/m2
WL = 250 kg/m2
PG = 980 kg/m2 CARGA POR PISO
8 m
8 m
8 m
6.85 6.75 6.75
PLANTA TIPICA DEL 1 er AL 10mo PISO
datos
COLUMNA C-2: EXTERIOR P = 1.1 PG
n = 0.3
A = 8 m P = 1.1 PG
B = 3.425 m n = 0.25
PG = 980 kg/m2 P = 1.25 PG
n = 0.25 n = 0.25
P= 1.25 PG P = 1.5 PG
f'c = 420 kg/cm2 n = 0.2
PISOS =
AREA TRIBUTARIA PG NUEVO b*D b = D = t (cm)
27.4 26852 3197 56.5
usaremos: 0.60 x 0.60 m2
8 m
8 m
8 m
6.85 6.75 6.75
10
TIPO C1 (para los
primeros pisos)
columna interior
N>4pisos
TIPO C1 (para los 4
ultimos pisos)
columna interior
N<3pisos
TIPO C2, C3
columnas extremas
de porticos interiores
TIPO C4
columnas de
esquina
A
B
=
COLUMNA C-1: INTERIOR
P = 1.1 PG
A = 8 m n = 0.3
B = 6.8 m P = 1.1 PG
PG = 980 kg/m2 n = 0.25
n = 0.3 P = 1.25 PG
P= 1.1 PG n = 0.25
f'c = 420 kg/cm2 P = 1.5 PG
PISOS = n = 0.2
AREA TRIBUTARIA PG NUEVO b*D b = D = t (cm)
54.4 53312 4654 68.2
usaremos: 0.70 x 0.70 m2
8 m
8 m
8 m
6.85 6.75 6.75
TIPO C1 (para los 4
ultimos pisos)
columna interior
N<3pisos
TIPO C2, C3
columnas extremas
de porticos interiores
TIPO C4
columnas de
esquina 10
TIPO C1 (para los
primeros pisos)
columna interior
N>4pisos
A
B
=
losa aligerada
h=0.17
h=0.20
h=0.25
h=0.30
L = 4.93
losas aligeradas h=L/25 h = 0.1972 0.25 por norma
USO DEPOSITO VIVIENDA
S/C 1000 kg/m2 200 kg/m2
PERALTE h L/8 L/13
PERALTE: h=L/13
Lp = 4.555
Ls = 4.305
b x h
viga principal h= 0.35038462 b = 0.17519231 VP 0.25 x 0.35
viga secundaria h= 0.33115385 b = 0.35 VS 0.25 x 0.3
h = L/13 b = B/20
TIENDAS GARAJES
250 kg/m2 500 kg/m2
L/11 ; L/12 L/10
LUZ PRINCIPAL Y SECUNDARIO
PREDIMENSIONAMIENTO DE COLUMNA
utilizando el valor mayor
PREDIMENSIONAMIENTO DE VIGAS
DEPART U OFICINA
CAPITULO VI
DIMENSIONAMIENTO DE VIGAS- COLUMNA PROBLEMA
luces conprendidos entre 4 y 5.5m . 300 kg/m2
luces conprendidos entre 5.5 y 6.5 . 350 kg/m2
luces conprendidos entre 6.5 y 7.5 . 400 kg/m2 TOMAMOS :
PREDIMENSIONAMIENTO DE LOSA
h=l/25 en una sola direccion 4.93 = a la luz mayor de dicho plano
luces menores a 4m . 270 kg/m2
CONSIDERACIONES
Fallaran de manera fragil por fuerza cortante
columna extremadamente corta
no se admiten en zonas de alto riesgo.
Falla fragil o falla ductil.
Falla ductil.
Se recomienda que:
Las columnas se predimensionan con:
PREDIMENSIONAMIENTO DE COLUMNA
METRADO DE CARGAS
P. aligerado 350 kg/m2
tabiqueria 120 kg/m2
acabado 100 kg/m2
P. viga 100 kg/m2
P. columnas 60 kg/m2
S/C 200 kg/m2
fc 210 kg/m2
Carga muerta 730 kg/m2
Carga viva 200 kg/m2
PG = 930 kg/m2
3
COLUMNAS INTERIORES
nota: Las columnas centrales son las que deben tener mayor dimensin SI : b*D = t
ya que en estas se concentran la mayor parte del peso de la estructura.
COLUMNA At t
C - 7 20.28 1347.171429
max t = 1347.17143 m2
DIMENSIONES 37 X 37
DIMENSIONES 40 X 40
COLUMNAS EXTERNAS DE PORTICOS INTERIOES
NUMERO DE PISOS
METRADO DE CARGAS DE LA ESTRUCTURA
PG = P. muerta + P. viva
COLUMNA At t SI : b*D = t
C - 2 10.14 673.5857143
C - 3 9.24 613.8
C - 4 10.92 725.4
C - 6 6.3 418.5
C - 8 13.02 864.9
C - 9 16.38 1088.1
C - 10 10.92 725.4
C - 11 7.0165 466.0960714
C - 12 6.6384 440.9794286
C - 13 6.6816 443.8491429
max t = 1088.1 m2
DIMENSIONES 33 X 33
DIMENSIONES 30 X 30
COLUMNAS DE ESQUINA
COLUMNA At t SI : b*D = t
C - 1 6.3 627.75
C - 5 5.46 544.05
C - 14 3.78 376.65
C - 15 5.46 544.05
C - 16 5.46 544.05
max t = 627.75 m2
DIMENSIONES 25 X 25
0.35