/// 3G Side indoor TP48400B AND TP48200B SITE

SET ALMPORT: CN=0, SRN=0, SN=18, PN=0, SW=ON, AID=65033, PT=BOOL, AVOL=HIGH; In
truder Alarm
SET ALMPORT: CN=0, SRN=0, SN=18, PN=1, SW=ON, AID=65035, PT=BOOL, AVOL=HIGH; Ai
r Condition Alarm
SET ALMPORT: CN=0, SRN=0, SN=18, PN=2, SW=ON, AID=65037, PT=BOOL, AVOL=HIGH; hi
gh Temperature Alarm
SET ALMPORT: CN=0, SRN=0, SN=18, PN=3, SW=ON, AID=65039, PT=BOOL, AVOL=HIGH; Fi
re Alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=6, SW=ON, AID=65041, PT=BOOL, AVOL=HIGH; Ma
ins Failue Alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=7, SW=ON, AID=65057, PT=BOOL, AVOL=HIGH; Av
iation Light Failure
SET ALMPORT: CN=0, SRN=0, SN=19, PN=0, SW=ON, AID=65043, PT=BOOL, AVOL=LOW; AC
power failures alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=1, SW=ON, AID=65045, PT=BOOL, AVOL=LOW; DC
overvoltage and undervoltage alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=2, SW=ON, AID=65047, PT=BOOL, AVOL=LOW; Re
ctifier failures alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=3, SW=ON, AID=65049, PT=BOOL, AVOL=LOW; SP
D failure alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=4, SW=ON, AID=65051, PT=BOOL, AVOL=LOW; Fu
se burn-out alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=5, SW=ON, AID=65053, PT=BOOL, AVOL=LOW; Ba
ttery temperature alarm
/// 3G Side indoor TP48300A SITE
SET ALMPORT: CN=0, SRN=0, SN=18, PN=0, SW=ON, AID=65033, PT=BOOL, AVOL=HIGH; In
truder Alarm
SET ALMPORT: CN=0, SRN=0, SN=18, PN=1, SW=ON, AID=65035, PT=BOOL, AVOL=HIGH; Ai
r Condition Alarm
SET ALMPORT: CN=0, SRN=0, SN=18, PN=2, SW=ON, AID=65037, PT=BOOL, AVOL=HIGH; hi
gh Temperature Alarm
SET ALMPORT: CN=0, SRN=0, SN=18, PN=3, SW=ON, AID=65039, PT=BOOL, AVOL=HIGH; Fi
re Alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=6, SW=ON, AID=65041, PT=BOOL, AVOL=HIGH; Ma
ins Failue Alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=7, SW=ON, AID=65057, PT=BOOL, AVOL=HIGH; Av
iation Light Failure
SET ALMPORT: CN=0, SRN=0, SN=19, PN=0, SW=ON, AID=65043, PT=BOOL, AVOL=LOW; AC
power failures alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=1, SW=ON, AID=65045, PT=BOOL, AVOL=LOW; DC
overvoltage and undervoltage alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=2, SW=ON, AID=65047, PT=BOOL, AVOL=LOW; Re
ctifier failures alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=3, SW=ON, AID=65049, PT=BOOL, AVOL=LOW; SP
D failure alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=4, SW=ON, AID=65051, PT=BOOL, AVOL=LOW; Fu
se burn-out alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=5, SW=ON, AID=65055, PT=BOOL, AVOL=LOW; Ba
ttery protection alarm
/// 3G Side outdoor
/// 3G Side Old Delta SITE
SET ALMPORT: CN=0, SRN=0, SN=19, PN=0, SW=ON, AID=65075, PT=BOOL, AVOL=HIGH; M
ain Power Failure
SET ALMPORT: CN=0, SRN=0, SN=19, PN=1, SW=ON, AID=65057, PT=BOOL, AVOL=HIGH; A
viation Light Failure
SET ALMPORT: CN=0, SRN=0, SN=19, PN=2, SW=ON, AID=65077, PT=BOOL, AVOL=HIGH; R
ectifier Failure
SET ALMPORT: CN=0, SRN=0, SN=19, PN=3, SW=ON, AID=65091, PT=BOOL, AVOL=HIGH; C
ooling Alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=4, SW=ON, AID=65079, PT=BOOL, AVOL=HIGH; H
igh Temperature Alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=5, SW=ON, AID=65093, PT=BOOL, AVOL=HIGH; S
moke Alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=6, SW=ON, AID=65087, PT=BOOL, AVOL=HIGH; D
oor Open
SET ALMPORT: CN=0, SRN=0, SN=19, PN=7, SW=ON, AID=65095, PT=BOOL, AVOL=HIGH; o
ther alarm
/// 3G Side NEW Delta SITE
SET ALMPORT: CN=0, SRN=0, SN=19, PN=0, SW=ON, AID=65075, PT=BOOL, AVOL=HIGH; Ma
in Power Failure
SET ALMPORT: CN=0, SRN=0, SN=19, PN=1, SW=ON, AID=65077, PT=BOOL, AVOL=HIGH; Re
ctifier Module Failure
SET ALMPORT: CN=0, SRN=0, SN=19, PN=2, SW=ON, AID=65079, PT=BOOL, AVOL=HIGH; Hi
gh Temperature Alarm
SET ALMPORT: CN=0, SRN=0, SN=19, PN=3, SW=ON, AID=65081, PT=BOOL, AVOL=HIGH; PL
VD Disconnect
SET ALMPORT: CN=0, SRN=0, SN=19, PN=4, SW=ON, AID=65083, PT=BOOL, AVOL=HIGH; Su
rge Arrester Failure
SET ALMPORT: CN=0, SRN=0, SN=19, PN=5, SW=ON, AID=65085, PT=BOOL, AVOL=HIGH; Lo
ad Breaker Trip
SET ALMPORT: CN=0, SRN=0, SN=19, PN=6, SW=ON, AID=65087, PT=BOOL, AVOL=HIGH; Do
or Open
SET ALMPORT: CN=0, SRN=0, SN=19, PN=7, SW=ON, AID=65057, PT=BOOL, AVOL=HIGH; Av
iation Light Failure
SET ENVALMPARA:ALMID=65033,ANM="Intruder Alarm",ALVL=CRITICAL,ASS=ENV;

SET ENVALMPARA:ALMID=65035,ANM="Air Condition Alarm",ALVL=MAJOR,ASS=ENV;

SET ENVALMPARA:ALMID=65037,ANM="high Temperature Alarm",ALVL=MAJOR,ASS=ENV;

SET ENVALMPARA:ALMID=65039,ANM="Fire Alarm",ALVL=CRITICAL,ASS=ENV;

SET ENVALMPARA:ALMID=65041,ANM="Mains Failue Alarm",ALVL=CRITICAL,ASS=POWER;

SET ENVALMPARA:ALMID=65057,ANM="Aviation Light Failure",ALVL=MAJOR,ASS=ENV;

SET ENVALMPARA:ALMID=65043,ANM="AC power failures alarm",ALVL=CRITICAL,ASS=POWER
;
SET ENVALMPARA:ALMID=65045,ANM="DC overvoltage and undervoltage alarm",ALVL=MAJO
R,ASS=POWER;
SET ENVALMPARA:ALMID=65047,ANM="Rectifier failures alarm",ALVL=CRITICAL,ASS=POWE
R;
SET ENVALMPARA:ALMID=65049,ANM="SPD failure alarm",ALVL=MAJOR,ASS=POWER;



SET ENVALMPARA:ALMID=65051,ANM="Fuse burn-out alarm",ALVL=CRITICAL,ASS=POWER;

SET ENVALMPARA:ALMID=65053,ANM="Battery temperature alarm",ALVL=MAJOR,ASS=POWER;

SET ENVALMPARA:ALMID=65055,ANM="Battery protection alarm",ALVL=MAJOR,ASS=POWER;

SET ENVALMPARA:ALMID=65075,ANM="Main Power Failure",ALVL=CRITICAL,ASS=POWER;

SET ENVALMPARA:ALMID=65077,ANM="Rectifier Module Failure",ALVL=CRITICAL,ASS=POWE
R;
SET ENVALMPARA:ALMID=65079,ANM="High Temperature Alarm",ALVL=CRITICAL,ASS=ENV;

SET ENVALMPARA:ALMID=65081,ANM="PLVD Disconnect",ALVL=CRITICAL,ASS=POWER;

SET ENVALMPARA:ALMID=65083,ANM="Surge Arrester Failure",ALVL=CRITICAL,ASS=POWER;

SET ENVALMPARA:ALMID=65085,ANM="Load Breaker Trip",ALVL=CRITICAL,ASS=POWER;

SET ENVALMPARA:ALMID=65087,ANM="Door Open",ALVL=CRITICAL,ASS=ENV;

SET ENVALMPARA:ALMID=65057,ANM="Aviation Light Failure",ALVL=MAJOR,ASS=ENV;
SET ENVALMPARA: ALMID=65093, ANM="Somke Alarm", ALVL=MINOR, ASS=ENV;
SET ENVALMPARA: ALMID=65095, ANM="Other Alarm", ALVL=MINOR, ASS=ENV;
SET ENVALMPARA: ALMID=65091, ANM="Cooling Alarm", ALVL=MINOR, ASS=ENV;
SET ALMPORT:CN=0,SRN=0,SN=19,PN=7,SW=OFF;
--------------------------------------------------------------------------------
--------------------------------------------
///(65053650552G side indoor TP48400B AND TP48200B SITE in 2G end
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=356,CN=0,SRN=0,SN=18,PN=0,SW=OPEN,AID=65033,
PT=BOOL,AVOL=HIGH; Intruder Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=356,CN=0,SRN=0,SN=18,PN=1,SW=OPEN,AID=65035,
PT=BOOL,AVOL=HIGH; Air Condition Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=356,CN=0,SRN=0,SN=18,PN=2,SW=OPEN,AID=65037,
PT=BOOL,AVOL=HIGH; high Temperature Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=356,CN=0,SRN=0,SN=18,PN=3,SW=OPEN,AID=65039,
PT=BOOL,AVOL=HIGH; Fire Alarm

SET BTSENVALMPORT:IDTYPE=BYID,BTSID=356,CN=0,SRN=0,SN=19,PN=0,SW=OPEN,AID=65043,
PT=BOOL,AVOL=LOW; AC power failures alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=356,CN=0,SRN=0,SN=19,PN=1,SW=OPEN,AID=65045,
PT=BOOL,AVOL=LOW; DC overvoltage and undervoltage alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=356,CN=0,SRN=0,SN=19,PN=2,SW=OPEN,AID=65047,
PT=BOOL,AVOL=LOW; Rectifier failures alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=356,CN=0,SRN=0,SN=19,PN=3,SW=OPEN,AID=65049,
PT=BOOL,AVOL=LOW; SPD failure alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=356,CN=0,SRN=0,SN=19,PN=4,SW=OPEN,AID=65051,
PT=BOOL,AVOL=LOW; Fuse burn-out alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=356,CN=0,SRN=0,SN=19,PN=5,SW=OPEN,AID=65053,
PT=BOOL,AVOL=LOW; Battery temperature alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=356,CN=0,SRN=0,SN=19,PN=6,SW=OPEN,AID=65041,
PT=BOOL,AVOL=HIGH; Mains Failue Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=436,CN=0,SRN=0,SN=19,PN=7,SW=OPEN,AID=65057,
PT=BOOL,AVOL=HIGH; Aviation Light Failure
/// 65055650532G Side indoor TP48300A SITE



SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=18, PN=0, SW=OPEN, AID=6
5033, PT=BOOL, AVOL=HIGH; Intruder Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=18, PN=1, SW=OPEN, AID=6
5035, PT=BOOL, AVOL=HIGH; Air Condition Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=18, PN=2, SW=OPEN, AID=6
5037, PT=BOOL, AVOL=HIGH; high Temperature Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=18, PN=3, SW=OPEN, AID=6
5039, PT=BOOL, AVOL=HIGH; Fire Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=0, SW=OPEN, AID=6
5043, PT=BOOL, AVOL=LOW; AC power failures alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=1, SW=OPEN, AID=6
5045, PT=BOOL, AVOL=LOW; DC overvoltage and undervoltage alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=2, SW=OPEN, AID=6
5047, PT=BOOL, AVOL=LOW; Rectifier failures alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=3, SW=OPEN, AID=6
5049, PT=BOOL, AVOL=LOW; SPD failure alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=4, SW=OPEN, AID=6
5051, PT=BOOL, AVOL=LOW; Fuse burn-out alarm

SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=5, SW=OPEN, AID=6
5055, PT=BOOL, AVOL=LOW; Battery protection alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=6, SW=OPEN, AID=6
5041, PT=BOOL, AVOL=HIGH; Mains Failue Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=7, SW=OPEN, AID=6
5057, PT=BOOL, AVOL=HIGH; Aviation Light Failure
/// 2G Side outdoor
/// 2G Side Old Delta SITE
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=759,CN=0, SRN=0, SN=19, PN=0, SW=OPEN, AID=6
5075, PT=BOOL, AVOL=HIGH; Main Power Failure
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=759,CN=0, SRN=0, SN=19, PN=1, SW=OPEN, AID=6
5057, PT=BOOL, AVOL=HIGH; Aviation Light Failure
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=759,CN=0, SRN=0, SN=19, PN=2, SW=OPEN, AID=6
5077, PT=BOOL, AVOL=HIGH; Rectifier Failure
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=759,CN=0, SRN=0, SN=19, PN=3, SW=OPEN, AID=6
5091, PT=BOOL, AVOL=HIGH; Cooling Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=759,CN=0, SRN=0, SN=19, PN=4, SW=OPEN, AID=6
5079, PT=BOOL, AVOL=HIGH; High Temperature Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=759,CN=0, SRN=0, SN=19, PN=5, SW=OPEN, AID=6
5093, PT=BOOL, AVOL=HIGH; Smoke Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=759,CN=0, SRN=0, SN=19, PN=6, SW=OPEN, AID=6
5087, PT=BOOL, AVOL=HIGH; Door Open
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=759,CN=0, SRN=0, SN=19, PN=7, SW=OPEN, AID=6
5095, PT=BOOL, AVOL=HIGH; other alarm


/// 2G Side NEW Delta SITE

SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=0, SW=OPEN, AID=6
5075, PT=BOOL, AVOL=HIGH; Main Power Failure
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=1, SW=OPEN, AID=6
5077, PT=BOOL, AVOL=HIGH; Rectifier Module Failure
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=2, SW=OPEN, AID=6
5079, PT=BOOL, AVOL=HIGH; High Temperature Alarm
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=3, SW=OPEN, AID=6
5081, PT=BOOL, AVOL=HIGH; PLVD Disconnect
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=4, SW=OPEN, AID=6
5083, PT=BOOL, AVOL=HIGH; Surge Arrester Failure
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=5, SW=OPEN, AID=6
5085, PT=BOOL, AVOL=HIGH; Load Breaker Trip
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=6, SW=OPEN, AID=6
5087, PT=BOOL, AVOL=HIGH; Door Open
SET BTSENVALMPORT:IDTYPE=BYID,BTSID=101,CN=0, SRN=0, SN=19, PN=7, SW=OPEN, AID=6
5057, PT=BOOL, AVOL=HIGH; Aviation Light Failure
SET ENVALMPARA:AID=65033,ANM="Intruder Alarm",ALVL=CRITICAL,ASS=ENV;
SET ENVALMPARA:AID=65035,ANM="Air Condition Alarm",ALVL=MAJOR,ASS=ENV;
SET ENVALMPARA:AID=65037,ANM="high Temperature Alarm",ALVL=MAJOR,ASS=ENV;
SET ENVALMPARA:AID=65039,ANM="Fire Alarm",ALVL=CRITICAL,ASS=ENV;
SET ENVALMPARA:AID=65041,ANM="Mains Failue Alarm",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:AID=65057,ANM="Aviation Light Failure",ALVL=MAJOR,ASS=ENV;
SET ENVALMPARA:AID=65043,ANM="AC power failures alarm",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:AID=65045,ANM="DC overvoltage and undervoltage alarm",ALVL=MAJOR,
ASS=POWER;
SET ENVALMPARA:AID=65047,ANM="Rectifier failures alarm",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:AID=65049,ANM="SPD failure alarm",ALVL=MAJOR,ASS=POWER;
SET ENVALMPARA:AID=65051,ANM="Fuse burn-out alarm",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:AID=65053,ANM="Battery temperature alarm",ALVL=MAJOR,ASS=POWER;
SET ENVALMPARA:AID=65055,ANM="Battery protection alarm",ALVL=MAJOR,ASS=POWER;
SET ENVALMPARA:AID=65075,ANM="Main Power Failure",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:AID=65077,ANM="Rectifier Module Failure",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:AID=65079,ANM="High Temperature Alarm",ALVL=CRITICAL,ASS=ENV;
SET ENVALMPARA:AID=65081,ANM="PLVD Disconnect",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:AID=65083,ANM="Surge Arrester Failure",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:AID=65085,ANM="Load Breaker Trip",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:AID=65087,ANM="Door Open",ALVL=CRITICAL,ASS=ENV;
SET ENVALMPARA:AID=65057,ANM="Aviation Light Failure",ALVL=MAJOR,ASS=ENV;