MASTERYS MC

from 100 to 120 kVA


UPS for critical IT equipment power supply
> Data centre
> Telecommunications
> Service sector

2
Three phase
UPS system
MASTERYS MC
from 100 to 120 kVA
UPS for critical IT equipment power supply
3
Total Cost of Ownership
> Maximum energy efficiency
Energy saving with efficiency of up to 96%
> Optimisation of electrical system
Power factor >0.99 and input current harmonic distortion< 3%
> Extended battery life and performance
Intelligent battery charge algorithm (EBS)
> Optimised space for servers
UPS footprint and front access only
Integratability and communication
> UPS monitoring and server shutdown
Thanks to the wide range of communication protocols, modes and integrated LAN
> Suitable for more sophisticated server rooms
Installation on technical floor
> User-friendly interface
Graphical user interface with graphic display and multilingual web browser
Availability
> Uptime maximisation
Redundant parallel
> Fault tolerance and protection selectivity
High overload capacity in all operating conditions
> Power supply stability with minimal battery use
Wide input voltage and frequency tolerance
> Wall installation, next to other cabinets, easy maintenance
Pull-up ventilation (front and below air intake - outlet at top)
Technology
> Suitable for high power factor loads
Designed to work with latest-generation servers
> Precise, interference-free load supply
Online double conversion with DSP digital control
> High-efficiency solution
Innovative inverter technology
Three phase
UPS system
MASTERYS MC
from 100 to 120 kVA
Save thousands of euros
4
The high efficiency reduces energy loss and reduces the requirement of air
conditioning systems. MASTERYS
TM
MC 100-120 kVA gives the highest efficiency
performance on the market: up to 96% over a wide range of use. The graphs below
show the annual savings with 96% efficiency as against 94% and 93%, referred to
the average kWh cost within the European Community under typical load
conditions, including the lower conditioning costs.
Built to cope with more unstable power supply networks
The excellent power factor and harmonic content avoid over rating of the supply
system: i.e. of switches, generator sets and protective devices.
The battery is a very important part of the investment, its life depends not only on the
frequency of use but is also influenced by the charging and trickle-charge.
MASTERYS
TM
MC 100-120 kVA combines an intelligent system that manages the
charging method on the basis of battery room temperature, thus lengthening the life of
the batteries.
The MASTERYS
TM
MC 100-120 kVA , with its high power density availability, occupies a
foot print of 700x800 mm, leaving the server room to the servers.
The pull-up ventilation system (front and below air intake - outlet at top) means that it
can be installed against a wall and between other cabinets.
Three phase
UPS system
MASTERYS MC
from 100 to 120 kVA
16000
14000
12000
10000
8000
6000
4000
2000
one year two years three years four years five years
0
Saving with 96% efficiency as against...
93%
94%
Load (%)
Efficiency (%)
0
0
25 50 75 100
100
96
+
+
+
.
.
.
backup time up to 20
backup time up to 60
and over
The wide input tolerance of the MASTERYS
TM
MC 100-120 kVA , withstanding volt-
ages of -40% of the rated voltage, and the flexible backup times guarantee a high-
quality, uninterrupted power supply to your servers.
The high availability of the individual UPSs can be further increased with parallel
redundant configuration.
5
Peace of mind
T.SERVICE offers round-the-clock, 7 days-a-week control of the UPS from the
SOCOMEC operational centre. The MASTERYS
TM
MC 100-120 kVA sends periodical
statistical reports on the network operating quality and significant events
automatically, via GSM modem or the Internet. If an anomaly occurs, the sending of
the information in real time allows the cause to be diagnosed immediately, with the
immediate call-out of specialist engineers, if necessary.
The MASTERYS
TM
MC 100-120 kVA communication solutions mean that the UPS
can be integrated with the infrastructure for monitoring and control in the same way
as the IT peripherals.
The environmental monitor device (EMD) allows the constant monitoring of the
environment as well, checking the humidity and temperature and alerting via mail if
pre set alarm thresholds are exceeded.
The MASTERYS
TM
MC 100-120 kVA can notify via mail or text message and can
integrate two physically independent Ethernet interfaces. The shutdown of the
servers can be controlled, with the simultaneous remote monitoring of the UPS
systems, keeping the network and sensitive data entirely safe.
For latest-generation servers
The MASTERYS
TM
MC 100-120 kVA is designed to supply latest-generation servers
without over rating the UPS power. The 0.9 rated output leading to lagging power
factor responds perfectly to computer system high power factor load requirements.
Three phase
UPS system
MASTERYS MC
from 100 to 120 kVA
12% more active power
120
100
80
60
40
20
0
kW
UPS with a PF of 0.8
100 kVA 120 kVA
MASTERYS
TM
MC 100-120 kVA
The MASTERYS
TM
MC 100-120kVA is designed for easy installation in existing
environments: it is suitable for installation on technical flooring and its smart design
makes it ideal for all server rooms.
The MASTERYS
TM
MC 100-120 kVA communicates via the most varied protocols
(HTTP, HTTPS, SNMP, SMTP, JBUS/MODBUS and PROFIBUS) and through the
commonest communication ports (RS 232, RS 485, RJ45-Ethernet, voltage-free
signalling contacts).
The Global Supply System (GSS) allows UPS-generator set coordination for
optimisation during emergency operation.
6
F
A
C
I
L
I
T
Y
M
A
N
A
G
E
R
24/7/365
worldwide
Coordination and
monitoring of
generator via GSS
APRIL
M
AY
JUNE
APRIL
M
AY
JUNE
APRIL
M
AY
JUNE
Remote control
with Web browser
Remote shutdown
Workstation/server with JNC
Mail server
Remote monitoring
via SNMP
Windows

workstation/server
(shutdown and display)
Linux workstation/server
(shutdown and display)
Sun Solaris, IBM AIX, HP-UX, ...
workstation/server
(shutdown and display)
Management
solutions
Communication and monitoring
L
O
G
IC
_
0
1
3
_
A
_
G
B
7
Three phase
UPS system
MASTERYS MC
from 100 to 120 kVA
F
A
C
I
L
I
T
Y
M
A
N
A
G
E
R
24/7/365
worldwide
Coordination and
monitoring of
generator via GSS
APRIL
M
AY
JUNE
APRIL
M
AY
JUNE
APRIL
M
AY
JUNE
Remote control
with Web browser
Remote shutdown
Workstation/server with JNC
Mail server
Remote monitoring
via SNMP
Windows

workstation/server
(shutdown and display)
Linux workstation/server
(shutdown and display)
Sun Solaris, IBM AIX, HP-UX, ...
workstation/server
(shutdown and display)
Technical data
Sn [kVA] 100 120
Pn [kW] 90 108
INPUT
Rated voltage 400V 3ph+N
Voltage tolerances 20% without declassing, -40% with 50% of Pn
Input frequency 50/60 Hz 10%
Power factor / THDI >0.99 / < 3%
OUTPUT
Voltage 400V 3ph+N 1% (380/415 configurable)
Voltage tolerance Static load 1%
Dynamic load in accordance with VFI-SS-111
Frequency 50/60 Hz 2% (configurable with generator from 1% to 8% )
Automatic bypass Rated voltage output 15%
(configurable with generator from 10% to 20%)
Total harmonic voltage distortion <1% with linear load / <3% with nonlinear load
Overload @ p.f. 0.9 125% for 5 minutes / 150% for 30 seconds
Crest factor 3:1 (in accordance with (EN) IEC 62040-3)
EFFICIENCY
Online mode up to 96%
Mode 98%
ENVIRONMENT
Operating environment temperature 0 C to + 40 C (from 15 C to 25 C for maximum battery life)
Relative humidity 0% - 95 % without condensation
Maximum altitude 1000 m without declassing (max. 3000 m)
Noise level (ISO 3746) <65 dB(A)
Weight 380 kg
UPS CABINET
Dimensions (L x D x H) [mm] 700x800x1930
Protection grade IP 20 (IP 30 optional)
Colour RAL 7012, Silver grey frontal door
STANDARDS
Safety EN62040-1-1, EN60950-1-1
Performance EN62040-3 (VFI-SS-111)
Electromagnetic compatibility (EMC) EN62040-2
Product declaration CE
IP grade IEC 60529
Standard communication kit
RS 232 / 485 serial port
RS 232 serial port for modem
Integrated LAN interface
3 auxiliary interface slots.
Standard electrical kit
Integrated maintenance bypass
Double input network
External backfeed control.
Remote maintenance
T.SERVICE program for continuous monitoring of
MASTERYS with the SOCOMEC UPS maintenance service.
Communication options
Remote panel
ADC interface (configurable voltage-free contacts)
GSS interface (generator management)
UNI VISION PROremote control and shutdown software
NETVISIONWEB/SNMP manager interface for connecting
the UPS system to the LAN/WAN network.
Electrical options
External maintenance bypass
Extended autonomy
Additional battery chargers
Isolation transformer
ACS synchronisation system
Integrated backfeed protection.
R

f
.

D
O
C

7
6
0
1
3
I

-

0
9
/
0
7

-

P
h
o
t
o

:

M
a
r
t
in

B
e
r
n
h
a
r
t

-

R

a
lis
a
t
io
n

:

S
O
C
O
M
E
C

S
e
r
v
ic
e

C
o
m
m
u
n
ic
a
t
io
n

-

I
m
p
r
im
e
u
r
This document is not a specification. SOCOMEC UPS reserves the right to make any changes to data without prior notice.
ISO 9001: 2000
FM 28237
VALID FOR FRANCE VALID FOR ITALY
H E A D O F F I C E
SOCOMEC GROUP
S.A. SOCOMEC capital 11 014 300 - R.C.S. Strasbourg B 548 500 149
B.P. 60010 - 1, rue de Westhouse - F-67235 Benfeld Cedex
SOCOMEC UPS Strasbourg
11, route de Strasbourg - B.P. 10050 - F-67235 Huttenheim Cedex- FRANCE
Tel. +33 (0)3 88 57 45 45 - Fax +33 (0)3 88 74 07 90
ups.benfeld.admin@socomec.com
SOCOMEC UPS Isola Vicentina
Via Sila, 1/3 - I - 36033 Isola Vicentina (VI) - ITALY
Tel. +39 0444 598611 - Fax +39 0444 598622
info.it.ups@socomec.com
S A L E S , MA R K E T I N G A N D
S E R V I C E MA N A G E ME N T
SOCOMEC UPS PARIS
95, rue Pierre Grange
F-94132 Fontenay-sous-Bois Cedex - FRANCE
Tel. +33 (0)1 45 14 63 90 - Fax +33 (0)1 48 77 31 12
ups.paris.dcm@socomec.com
Socomec UPS
worldwide
I N E U R O P E
BELGIUM
Schaatsstraat, 30 rue du Patinage
B - 1190 Bruxelles
Tel. +32 (0)2 340 02 34
Fax +32 (0)2 346 16 69
be.ups.sales@socomec.com
FRANCE
95, rue Pierre Grange
F - 94132 Fontenay-sous-Bois Cedex
Tel. +33 (0)1 45 14 63 90
Fax +33 (0)1 48 77 31 12
ups.paris.dcm@socomec.com
GERMANY
Heppenheimerstrae 57
D - 68309 Mannheim
Tel. +49 (0) 621 71 68 40
Fax +49 (0) 621 71 68 44 4
de.ups.all@socomec.com
ITALY
Via Leone Tolstoi, 73 - Zivido
20098 San Giuliano Milanese (MI)
Tel. +39 02 98 242 942
Fax +39 02 98 240 723
siconmi@socomec.com
NETHERLANDS
Bergveste 2F
NL - 3992DE Houten
Tel. +31 (0)30 63 71 504
Fax +31 (0)30 63 72 166
info@socomec.nl
POLAND
Nowowiejska St 21/25
00-665 Warszawa
Tel. +48 (0)22 2345 223
Fax +48 (0)22 2345 223
ups.poland@socomec.com
PORTUGAL
Rua Moinho do Cuco
Bloco A
Lj. Dta. - Paz
2640-566 MAFRA
Tel. +351 261 812 599
Fax +351 261 812 570
portugal@socomec.com
RUSSIA
Kutuzovsky pr. 13, 44-45
121248 - Moscow
Tel. +7 495 775 19 85
Fax +7 495 775 19 85
ups.russia@socomec.com
SLOVENIA
Savlje 89
SI - 1000 Ljubljana
Tel. +386 1 5807 860
Fax +386 1 5611 173
info@socomec.si
SPAIN
C/Nord, 22 Pol. Ind. Buvisa
E - 08329 Tei (Barcelona)
Tel. +34 935 407 575
Fax +34 935 407 576
info@socomec-aron.com
UNITED KINGDOM
Units 7-9 Lakeside Business Park
Broadway Lane
South Cerney
Cirencester
GL7 5XL
Tel. +44 (0)1285 863300
Fax +44 (0)1285 862304
uk.ups.sales@socomec.com
I N A S I A
CHINA
No.1 Yuanda Road Haidian District, Beijing, 100097
Golden Resource Times Shopping Mall
No. 1001 section B the 2nd issue of business building
Tel. +86 10 8889 2202
Fax +86 10 8889 2150
socomec@socomec-sicon-ups.com.cn
INDIA
SOCOMEC NUMERIC
No 5 Sir P.S. Sivasamy Salai
Mylapore
Chennai 600 004
Tel. +91 44 2499 3266
Fax +91 41 2499 8210
in.ups.sales@socomec.com
MALAYSIA
31 Jalan SS 25/41- Mayang Industrial Park
47301 Petaling Jaya.- Selangor, Malaysia
Tel. +603 7804 1153
Fax +603 7803 8901
sales@cspm.com.my
SINGAPORE
31 Ubi Road 1, Aztech Building
# 01-00 (Annex) - SG - Singapore 408694
Tel. +65 6745 7555
Fax +65 6458 7377
sg.ups.sales@socomec.com
THAILAND
17/178 Prachachuen Road
TungSong Hong, Laksi
TH - 10210 Bangkok
Tel. +66 2 503 92 43
Fax +66 2 503 99 23
inquiry@socomec-unitrio.co.th
www.socomec.com

Вам также может понравиться