Вы находитесь на странице: 1из 32

ARMY TM 5-814-2

AIR FORCE AFM 88-11, Vol. 2

SANITARY AND INDUSTRIAL


WASTEWATER COLLECTION--
PUMPING STATIONS AND FORCE MAINS

D E P A R T M E N T S O F T H E A R M Y A N D T H E A I R F O R C E
MARCH 1985
TM 5-814-2/AFM 88-11, Vol. 2

REPRODUCTION AUTHORIZATION/RESTRICTIONS

This manual has been prepared by or for the government and, except to the extent indicated below, is
public property and not subject to copyright.

Copyrighted material included in the manual has been used with the knowledge and permission of the
proprietors and is acknowledged as such at point of use. Anyone wishing to make further use of any
copyrighted material, by itself and apart from this text, should seek necessary permission directly from
the proprietors.

Reprints or republications of this manual should include a credit substantially as follows: "Joint
Departments of the Army and Air Force, USA, Technical Manual TM 5-814-1/AFM 88-11, Volume 2,
Sanitary and Industrial Wastewater Collection--Pumping Stations and Force Mains."

If the reprint or republication includes copyrighted material, the credit should also state: "Anyone wishing
to make further use of copyrighted material, by itself and apart from this text, should seek necessary
permission directly from the proprietors."
*TM 5-814-2
AFM 88-11, Vol. 2

Technical Manual DEPARTMENTS OF THE ARMY


No. 5-814-2
Air Force Manual
AFM 88-11, Volume 2 } AND THE AIR FORCE

Washington, DC, 15 March 1985

SANITARY AND INDUSTRIAL WASTEWATER COLLECTION-


PUMPING STATIONS AND FORCE MAINS
Paragraph Page
Chapter 1. GENERAL
Purpose and scope.................................................................................. 1-1 1-1
Special wastes ........................................................................................ 1-2 1-1
Pump Station alternatives ....................................................................... 1-3 1-1

Chapter 2. LOCATION OF PUMPING STATIONS


Service area............................................................................................ 2-1 2-1
Site selection .......................................................................................... 2-2 2-1
Building and site requirements ................................................................ 2-3 2-1

Chapter 3. TYPE AND CAPACITY OF PUMPING STATIONS


Required pumping capacity ..................................................................... 3-1 3-1
Type of construction................................................................................ 3-2 3-1

Chapter 4. WASTEWATER PUMPING EQUIPMENT


Wastewater pumps ................................................................................. 4-1 4-1
Pump drives............................................................................................ 4-2 4-2
Drive mechanisms .................................................................................. 4-3 4-3
Pump speed controls............................................................................... 4-4 4-3

Chapter 5. PUMPING SYSTEM DESIGN


Force main hydraulics ............................................................................. 5-1 5-1
Pump analysis and selection ................................................................... 5-2 5-3
Wet well design....................................................................................... 5-3 5-5
Pump controls and instrumentation ......................................................... 5-4 5-6
Surge phenomena................................................................................... 5-5 5-7
Screening and comminuting devices ....................................................... 5-6 5-9

Chapter 6. PIPING, VALVES AND APPURTENANCES


Pipe materials, fittings, joints................................................................... 6-1 6-1
Valves and appurtenances ...................................................................... 6-2 6-2
Installation............................................................................................... 6-3 6-2

Chapter 7. PUMP STATION COMPONENTS


Construction requirements ...................................................................... 7-1 7-1
Heating and ventilation............................................................................ 7-2 7-1
Electrical equipment and lighting............................................................. 7-3 7-2
Standby power ........................................................................................ 7-4 7-2
Water supply........................................................................................... 7-5 7-2
Flow measurement.................................................................................. 7-6 7-2
Paints and protective coatings................................................................. 7-7 7-3

Appendix A. References...........................................................................................................................................A-1
Bibliography .........................................................................................................................................................BIBLIO-1

*This manual supersedes TM 5-814-2 dated 1 September 1958.

i
TM 5-814-2/AFM 88-11, Vol. 2

LIST OF FIGURES

Figure Page
5-1. Chart for Hazen-Williams formula ....................................................................................... 5-2
5-2. Typical pump-system curves............................................................................................... 5-5
5-3. Pump suction connections to wet well ................................................................................. 5-7

LIST OF TABLES
Table Page
3-1. Classification of pumping stations ....................................................................................... 3-1
5-1. Minimum pump cycle times................................................................................................. 5-6
5-2. Required submergence depth to prevent vortexing ............................................................. 5-6
5-3. Water hammer wave velocities . ......................................................................................... 5-8

ii
TM 5-814-2/AFM 88-11, Vol. 2

CHAPTER 1
GENERAL

1-1. Purpose and scope. This manual provides expense of deep trench excavation, jacking, boring,
guidance, instructions and criteria for the design of tunneling, or construction of long sewer runs to avoid
sanitary and industrial wastewater pumping facilities at high terrain. In those cases, both wastewater pumping
fixed Army and Air Force installations, and any and gravity flow sewers will be technically feasible and
applicable special projects. Facilities covered in this capable of meeting service requirements. However,
manual include pump and ejector stations required for they may not be equivalent in economic terms. When it
(1) removal of sanitary and industrial wastes from is not readily apparent which solution would be more
remote or low lying areas of the installation which economical, the decision to use one or the other will be
cannot be served hydraulically by gravity sewers, (2) based on a life cycle cost analysis. Initial capital and
controlled introduction and lifting of raw wastewater into construction costs for pumps, ejectors, structures, force
the waste treatment plant, (3) transfer of recycled and mains, etc., plus operation and maintenance costs, will
bypassed flows throughout the plant, and (4) discharge be compared with the costs of deep trench excavation,
of treated effluent. Pumping systems for the handling of or other special construction methods required for a
sludge, grit and scum are presented in TM 5-814-3/AFM gravity system. Generally, a gravity sewer system will
88-11, Vol. 3. The design of a wastewater pumping be justified until its cost exceeds the cost of a pumped
station will typically include site improvements, system by 10 percent. TM 5-814-8 contains criteria for
structures, screening and flow monitoring devices, economic evaluation of wastewater pumping. TM 5814-
pumping units, pump drives, system controls and 1/AFM 88-11, Vol. 1 provides criteria for engineering
instrumentation, mechanical and electrical components, and design of sanitary and industrial wastewater
interior piping, underground force mains, valves and collection systems.
appurtenances. b. Grinder pumps and vacuum systems. There
may be areas so limited by high groundwater,
1-2. Special wastes. Pumping systems for subsurface rock, unstable soil or steep topography, that
hazardous and explosive wastes, corrosive acids or neither gravity sewers nor centralized pumping stations
alkalies, high temperature or other industrial type will be feasible. In these cases, the use of grinder
wastes, will generally require the selection of highly pumps or vacuum systems will be investigated. See
resistant pumps, valves and piping materials. Design of paragraph 1-4b of TM 5-814-1/AFM 88-11, Vol. 1.
these systems will be in accordance with special criteria Design criteria for grinder pumps are contained in this
developed for the particular situation. Selection of manual.
materials for pumps, piping, valves and controls, etc.,
will be based on manufacturers' recommendations,
product specifications, and any other appropriate design
manuals or applicable criteria.

1-3. Pump stations alternatives


a. Gravity sewer system. Pumping stations and
pneumatic ejectors will normally be required to remove
wastes from areas which cannot be served hydraulically
by gravity sewers. In certain situations however, a
gravity sewer system can be utilized, but only at the

1-1
TM 5-814-2/AFM 88-11, Vol. 2

CHAPTER 2
LOCATION OF PUMPING STATIONS

2-1. Service area. The requirement that an area be required utilities such as electric power, potable water,
served by a wastewater pumping facility will in most fire protection, gas, steam and telephone service.
cases be determined by topography. Building and grade
elevations in the area generally will be too low for proper 2-3. Building and site requirements
gravity drainage to an existing or proposed sewer a. Floor and building elevations. The invert
system, or waste treatment facility. Thus, collection and elevations of incoming sewers will determine the depths
pumping of wastes from these low lying areas will be of underground portions (substructure) of the pumping
necessary. In addition to topographic considerations, station. It is common practice to set the maximum
natural boundaries like waterways, rivers, streams, etc., liquid level in the wet well equal to the 80-90 percent
and property lines of Federal, state and local flow depth of the lowest incoming sewer. Subsurface
jurisdictions, also play a role in determining the size and and soil conditions at the site will dictate the structural
limits of service areas. design, excavation depths, and top of footing elevations
required for the foundation. Surface conditions such as
2-2. Site selection. The location of pumping adjacent buildings and site grading will determine the
facilities within a service area will be based primarily on elevations of floors above ground (superstructure),
topographic considerations and the need to provide for except that the elevation of the ground floor will be set
future development. Pump stations will be located so above the maximum expected flood level.
that all points within the intended service area can be b. Architectural and landscaping. For pumping
drained adequately by gravity sewers. Any planned stations located in built-up areas, the architectural
development within the service area, such as exterior of the buildings should be made similar to, or
construction of new buildings or modifications to existing compatible with, surrounding buildings. When the
ones, or any projected shifts in population and/or station is located in a remote area, building appearance
workforce will be considered. This type of information is is not important, but the possibility of future
generally obtained from the installation master plans, or development in the vicinity will be considered. Pump
from personnel staffing requirements. It is a relatively stations and facilities will be provided with fencing where
simple matter to design a pumping station with capacity necessary to prevent vandalism, and to protect people
for future development by providing room for additional from hazardous contact with electrical transformers and
or larger pumps, motors, impellers, etc. However, the switching equipment. Landscaping should be
physical location of the station is more critical since it considered in built-up areas, and will be required in
cannot be moved to accommodate new buildings or residential communities. Where stations must be
population increases. The following general guidelines constructed in close proximity to residences or other
for site selection and location of pumping stations will be quarters, buffer zones of planted shrubbery should be
used: provided for noise reduction.
-Pumping facilities will not be constructed c. Access. All pump stations will be readily
beneath buildings, streets, roadways, railroads, aircraft accessible from an improved road. For stations that are
aprons or runways, or other major surface structures, to not enclosed, access will be provided for direct
the maximum extent practical. maintenance from a truck equipped with hoist
-Pump stations will not be located closer than attachments. For enclosed stations, provisions will be
500 feet to buildings, or other facilities to be occupied by included in the structure to facilitate access for repair,
humans, unless adequate measures are provided for and to provide a means for removal and loading of
odor and gas control. equipment onto a truck.
-Pumping stations at wastewater treatment
facilities will normally be located adjacent to, or in
connection with, other plant elements as required for
proper functioning of the treatment systems.
-The location of pumping stations will be made
with proper consideration given to the availability of

2-1
TM 5-814-2/AFM 88-11, Vol. 2

CHAPTER 3
TYPE AND CAPACITY OF PUMPING STATIONS

3-1. Required pumping capacity. Proper selection mode of operation will normally require two or more
of the number and capacity of pumping units is wastewater pumps of the constant or variable speed
dependent upon the quantity and variation of type, operating in single or multiple pump combinations,
wastewater flows to be handled. Except as indicated as required to match the incoming flowrates.
below for small stations, pumping units will be selected
to handle the normal daily range of wastewater flows 3-2. Type of construction. A classification of
generated in the service area. The number and pumping stations by capacity and the method of
capacity of pumps provided will be sufficient to construction normally utilized for that capacity is
discharge the minimum, average, peak daily and provided in Table 3-1. Factory assembled pumping
extreme peak flowrates as calculated in TM 5-814- stations, commonly referred to as package type stations,
1/AFM 88-11, Vol. 1. Pumping capacity will be are manufactured in standard sizes and are shipped
adequate to discharge the peak flowrates with the from the factory in modules with all equipment and
largest pump out of service. Pumps utilized for components mounted, installed, and ready for
treatment plant processes, recycling and bypassing of connection. These type stations will be suitable for low
flows, etc., will be based on criteria developed in TM 5- flows, and where the need to protect pumps from
8143/AFM 88-11, Vol. 3. Consideration will be given to clogging is minimal. Conventional field erected
future conditions which may occur during the life of the pumping stations are designed for a particular location
station. Normally, where future development and and to meet specific requirements. Field constructed
population increases are projected for the area, pumps stations will be used where the quantity of flow or its
will be designed for initial conditions only, and the variation, or both, exceeds the capacity of available
station will be provided adequate room for expansion of factory assembled stations, or where site conditions
pumping capacity at a later date. Expansion of pumping require the use of special designs or construction
capacity can be accomplished with the installation of methods.
additional pumping units, larger pumps, impellers, drive
units, adjustable or variable speed drives. However, Table 3-1. Classification of pumping stations.
some situations may warrant provision of capacity for
future increases initially, for economic or other reasons. Recommended
Each case will be analyzed individually. Capacity
a. Small stations. Pumping stations required for Range Class/Type Gallons Per Minute
small remote areas which generate extreme peak Factory Assembled (Package
flowrates of less than 700 gpm, and where the possibility Type)
of future expansion is unlikely, and grinder pump Pneumatic Ejectors 30-200
installations serving three or more buildings, will be Wet Pit Submersible 100-500
provided with two identical pumping units. Each Pumps
pumping unit will be of the constant speed type, and will Dry Pit Pumps 100-2,000
be capable of discharging the extreme peak wastewater Conventional Field Erected
flowrate. The station will be designed to alternate Small 300-1,500
between zero discharge and peak discharge. This Intermediate 1,500-10,000
arrangement will provide 100 percent standby capacity Large over 10,000
to allow for necessary maintenance and repairs. Note: Package type, dry pit pump stations in the
Pneumatic ejector stations will be provided with duplex capacities shown are generally available off-the-
ejectors each sized for the extreme peak flowrate. shelf. However, station capacities up to 5,000
b. Large stations. Pumping stations serving large gallons per minute can be obtained by special
areas of the installation, and especially stations where order.
the entire wastewater flow or major portions thereof
must be pumped to the treatment facility, will be
designed so far as practicable to operate on a
continuous basis. The rate of pumpage must change in
increments as the inflow to the station varies. This

3-1
TM 5-814-2/AFM 88-11, Vol. 2

CHAPTER 4
WASTEWATER PUMPING EQUIPMENT

4-1. WASTEWATER PUMPS furnished with vertical shaft having a bottom suction,
a Centrifugal pumps. The centrifugal pump is the with the propeller mounted near the bottom of the shaft
predominate type of wastewater pump used. These and enclosed in a bowl. The propeller is totally
pumps are available in three variations, radial flow, submerged and can be clogged by large solids, rags or
mixed flow, and axial flow. Centrifugal pumps will not trash. Therefore, this pump will only be used for clear
be used in capacities of less than 100 gallons per well applications. Axial flow centrifugal pumps are
minute. available in 8-inch through 72-inch discharge sizes. The
(1) Radial flow pumps. The radial flow recommended capacity range for these pumps is 500 to
centrifugal pump is the major type used for pumping raw 100,000 gpm. Pumps are available to operate from 1 to
wastes. In a radial flow pump, the fluid enters the 40 feet TDH.
impeller axially and is discharged at right angles to the (4) Pump construction. Centrifugal
shaft. Two types of radial flow pumps are available, wastewater pumps will normally be constructed of cast
single suction and double suction. In a single-end iron with bronze or stainless steel trim, and with either
suction pump, fluid enters the impeller from one side. cast iron or bronze impellers. When operating' ill
The shaft does not extend into the suction passage, and wastewater containing substantial quantities of grit,
because of this, rags and trash do not clog the pump. impellers made of bronze, cast steel or stainless steel
The single-end suction pump will be suitable for will be required. Enclosed impellers will be specified for
handling untreated wastewater. For a double suction wastewater pumps required to pass solids. Pump
pump, fluid enters the impeller from both sides, however casings of the volute type will be used for pumping raw
the shaft extends into the suction passage, thereby untreated wastes and wastewaters containing solids.
limiting its use to handling only clear water. Radial flow Diffusion of turbine type casings may be utilized for
centrifugal pumps are available in discharge sizes of 2 effluent or clear water service at waste treatment
to 20 inches. However, pumps with a capacity to pass facilities. Pump shafts will be high grade forged steel,
3-inch minimum solids will be required. The and will be protected by renewable bronze or stainless
recommended capacity range for these pumps is 100 to steel sleeves where the shaft passes through the
20,000 gpm. Pumps are available in discharge heads of stuffing box. Stuffing boxes will utilize either packing
25 to 200 feet total dynamic head (TDH). Peak design glands or mechanical type seals.
efficiency ranges from 60 percent for smaller pumps to (5) Stuffing box seals. The stuffing box will
85 percent for larger pumps. Radial flow pumps are be lubricated and sealed against leakage of wastewater
suitable for either wet well or dry well applications. They (into the box) by grease, potable water, or another clear
can be installed with horizontal or vertical shafting, fluid. The lubricating and sealing sealing medium will
however, vertical shaft pumps require considerably less be supplied to the stuffing box at a pressure of 5 to 10
space. psi greater than the pump shutoff head. Grease seals
(2) Mixed flow pumps. The mixed flow are usually provided by cartridges which are either
centrifugal pump is an intermediate design between the spring loaded or pressurized by connections off the
radial flow type and the axial flow type, and has pump discharge. These arrangements generally do not
operating characteristics of both. The mixed flow pump maintain sufficient seal pressure on the stuffing box.
is designed with wide unobstructed passages, and is However, they will be acceptable for low head pumps
therefore suitable for handling wastewater or clear and where the wastewater contains little grit, as when
water. Mixed flow centrifugal pumps are available in 8- pumping treated effluent. When pumping raw untreated
inch through 84-inch discharge sizes. The wastes containing the usual quantities of grit, a potable
recommended capacity range for these pumps is 1,000 water seal system with seal pump will be required if a
to 80,000 gpm. Pumps are available to operate at 10 to potable water line is assessable within a reasonable
60 feet TDH. Peak design efficiency depends on the distance. The Later seal system will be capable of
size and characteristics of the individual pump, but supplying 3 gpm per pump minimum. The principal
generally ranges from 80 to 90 percent. The mixed flow advantage of a water seal over a grease seal is the
centrifugal pump is normally used only in dry well positive pressure maintained on the stuffing box by the
applications, with either horizontal or vertical shafting seal pump, and small amount of water which flows from
configuration. the stuffing box into the pump casing. Grit and other
(3) Axial flow pumps. Axial flow centrifugal abrasive materials that may be in the wastewater are
pumps will not be used to pump raw untreated
wastewater. This pump is designed primarily for clear
water service and for wet well installations. The pump is
4-1
TM 5-814-2/AFM 88-11, Vol. 2

thereby prevented from entering the stuffing box, thus pumped under low head through pressure sewers as
reducing wear on the shaft and packing. The advantage small as 1¼ inches in diameter. Grinder pumps are for
of less frequent repairs to the shaft and less frequent submersible installation, with a recommended operating
repacking should be considered in relationship to the range of 10 to 100 gpm. These pumps are available in
cost of providing the water line and other necessary discharge heads of 10 to 150 feet TDH. The peak
facilities for the water seal. Where freezing of seal design efficiency is generally very low. Grinder pumps
water is likely to occur, protective measures will be will be used only to handle domestic type wastes from
taken. There must not be, under any circumstances, a one or more individual buildings, and only in remote
direct connection between wastewater pumps and the areas or areas where gravity sewers and centralized
potable water system, nor any possibility of backflow of pumping facilities are not feasible (see paragraph 1-3b).
wastes into the potable water system. Air Force
facilities will comply with AFM 85-21. 4-2. Pump drives
b. Screw pumps. The screw pump is classified as a Electric motors. As a general rule, electric
a positive displacement pump, and as such, maintains motors will be provided as the primary drive unit in
two distinct advantages over centrifugal pumps. It can sanitary and industrial wastewater pumping stations.
pass large solids without clogging, and can operate over Small pump stations serving remote areas where
a wide range of flows with relatively good efficiencies. electric power is not available, will usually require
Screw pumps are normally available in capacities engine drives. The three types of electric motors most
ranging from 150 to 50,000 gpm with a maximum lift of commonly used in wastewater pumping are (1) squirrel-
30 feet. Because of its nonclog capabilities and wide cage induction, (2) wound-rotor induction, and (3)
pumping range, the screw pump is best suited for lifting synchronous. Squirrel-cage induction motors will
raw untreated wastewater into the treatment facility, and normally be selected for constant speed pump
for the pumping of treated effluent. Its use in sludge applications because of their simplicity, reliability and
pumping is discussed in TM 5-814-3/AFM 88-11, Vol. 3. economy. They can also be used for variable speed
Also, when treatment plants are upgraded, screw pumps operation when provided with the proper speed control.
may be installed to overcome the additional head losses Synchronous motors may be more economical for large
created by new treatment units, so that existing capacity, low rpm, constant speed pumps. Wound-rotor
discharge facilities can be retained. Screw pumps are induction motors are most commonly used for pumps
usually driven by a constant speed motor with gear requiring variable speed operation. For a 60 cycle,
reducer, and are inclined at angles of 30 to 38 degrees alternating current power supply, the maximum
from the horizontal. In most instances, screw pumps will synchronous motor speed allowed for wastewater pumps
be installed outdoors with only the drive unit enclosed. will be 1800 rpm (approximately 1770 rpm induction
c. Pneumatic ejectors. Pneumatic ejector stations speed). The normal range of speeds is from 600 to
will generally be used only in remote areas where 1200 rpm, with speeds below 450 rpm unusual at
quantities of wastes are small, and where future military installations. Lower speed pumps and motors
increases in waste flows are projected to be minimal. A are larger and more expensive, but generally are more
pneumatic ejector consists of a receiving tank, inlet and reliable. The selection of electric motors will depend
outlet check valves, air supply, and liquid level sensors. upon the type, size and location of the pumps, type of
When the wastewater reaches a preset level in the speed control used, and the power available at the site.
receiver, air is forced in ejecting the wastewater. When Pump location will determine the type of motor
the discharge cycle is complete, the air is shut off and enclosure. For dry pit pump installations, motor
wastewater flows through the inlet into the receiver. enclosures will normally be the open, drip proof type.
Generally, duplex ejectors operate on a 1-minute cycle, Pumps installed outdoors, or in dirty or corrosive
filling for 30 seconds and discharging for 30 seconds. environments, will require totally enclosed motors.
Thus, each receiver tank will be equal in volume to 30 Submersible pumps will have motor enclosures which
seconds of the extreme peak flowrate. Pneumatic are watertight. Motors installed outdoors will have
ejector stations are available in capacities ranging from temperature ratings adjusted to suit ambient operating
30 to 200 gpm with recommended operating heads up to conditions. For pumps designed to operate on an
60 feet TDH. A typical ejector installation will include intermittent basis, space heaters will be provided in
duplex units with two compressors, receivers, level motor housings to prevent condensation. Motors
sensors, etc. installed in wet wells will be explosion proof. Motor
d Grinder pumps. Grinder pumps shred solids starting equipment will be selected in accordance with
normally found in domestic wastewater, including rags, paragraph 7-3, and will be suitable for the type of motor
paper and plastic, into a slurry. The slurry can be

4-2
TM 5-814-2/AFM 88-11, Vol. 2

required voltage. Motor starters will be designed for engine mounted adjacent to the pump. A vertical motor
limiting the inrush current where shocks or disruptions to mounted above, and at a distance from a vertical pump,
the electrical supply are likely to occur as a result of will be connected to the pump with one or more lengths
pump start-up. Where low starting inrush current is of flexible shafting. Direct drive offers the most efficient
required for constant speed pumps, such as when using operation because no power is lost between the drive
engine driven generator sets, wound-rotor motors will be unit and the pump.
considered as an alternative to squirrel-cage motors. b Belt drive. Belt drives may be utilized if the
The voltage required for operation of motors and other pump speed is different from those available with
equipment will be determined in accordance with standard drive units, or if speed adjustment is required.
paragraph 7-3. Speed adjustment is accomplished by changing pulley
b Internal combustion engines. Internal or sheave ratios. Belt drives used with horizontal pumps
combustion (I.C.) engines will be used primarily at large require more floor space than a direct drive unit. There
pumping stations where electric motors are the primary is power loss through the belt, which results in lower
drive units, and where emergency standby facilities are efficiency, and belt wear increases maintenance
required. Conditions which dictate the use of fixed, requirements. Belt drives will be used only when it is
standby power at wastewater pumping stations are not possible to choose single speed equipment to cover
outlined in paragraph 7-4. I.C. engines will be required service conditions, or where pump speed adjustments
for small pump stations in remote locations where no may be required, but variable speed operation is not.
electric power source exists. At large wastewater c Right angle drive. Right angle drives will be
treatment plants where abundant digester gas is used on vertical pumps being driven by horizontal
produced, it will generally be more feasible to use I.C. engines. If the engine serves as emergency standby, a
engines which are fueled by the waste gas. I.C. combination gear box will be installed on the angle drive
engines may be arranged to drive horizontal pumps by to allow operation of the pump by the primary drive unit,
direct or belt connections, or they may drive vertical which is normally an electric motor. A clutch or
pumps through a right angle gear drive with an electric disconnect coupling disengages the right angle gear
motor as the primary drive unit (dual drive). It is more when the motor drives the pump. When the engine
common however, and will be the general rule at large drives the pump, the clutch is engaged and the motor
pump stations, to provide fixed emergency generator rotates freely. In case of a power failure the engine is
sets powered by I.C. engines. Generators produce automatically started, and after reaching partial
electric power not only for pumps, but also for auxiliary operating speed is engaged to drive the pump.
equipment such as heaters, lights, alarms, etc., and for
critical pump control systems. The types of internal 4-4. Pump speed controls
combustion engines normally used include (1) diesel, (2) a Mode of operation. Wastewater pumps will be
gasoline, (3) natural gas, primarily digester gas, and (4) designed to operate in one of the following modes: (1)
dual-fuel diesel. The use of gasoline engines for constant speed, (2) adjustable speed, or (3) variable
anything except small, remotely located pumping speed. The type of speed control system will be
stations is not recommended due to the hazards selected accordingly. As indicated in paragraph 4-2a,
associated with fuel handling and storage. Dual-fuel the type of speed control required will influence the type
diesel engines fire a mixture of diesel oil and natural of electric motor to be used.
gas, with a minimum of 10 percent diesel fuel required (1) Constant speed. Constant speed drive is
to ignite the mixture. Propane is usually provided as a the simplest, most reliable, and most economical mode
backup fuel for gas and dual-fuel diesel units. The of operation, and will be suitable for the majority of
selection of I.C. engines will be coordinated with the wastewater pumping applications at military
installation's Facility Engineer to insure that adequate installations. However, where there is a need to match
operation and maintenance can be made available. pumping rates with the incoming wastewater flowrates, a
variable speed drive will usually be more appropriate.
4-3. Drive mechanisms (2) Adjustable speed. By changing pulley or
a Direct drive. Direct drive, with the shaft of the sprocket ratios on a belt driven pump, the speeds can
drive unit directly connected to the pump shaft, is the be adjusted to accommodate several constant speed
most common configuration. This connection can be pumping rates. This type of system will be used mainly
either close-coupled or flexible-coupled. When using a in sludge pumping, but can be a good alternative
close-coupled connection, the pump is mounted directly
on the drive shaft. This is the normal arrangement for a
vertical pump driven by an electric motor. A horizontal
pump will usually have a flexible connection, with the

4-3
TM 5-814-2/AFM 88-11, Vol. 2

to variable speed control in wastewater pumping when (b) Bubbler tube. One of the most
speed adjustment is not required too often. Where commonly used systems employs a bubbler tube which
automatic operation is needed pulleys or sheaves can is suspended in the wet well and is fed by compressed
be positioned through the use of pneumatic, hydraulic or air. The backpressure on the open end of the tube is
electric devices. sensed by pressure switches, and then transduced to a
(3) Variable speed. Variable speed operation voltage or current signal. These signals are transmitted
will usually be required at large pumping stations where to a controller which operates the pumps. This system
the entire wastewater flow, or major portions thereof, has no moving parts in contact with the wastewater, and
must be pumped to the treatment facility, and where it is requires very little maintenance. The constant flow of
desired to match the incoming flowrates in order to compressed air keeps the tube free of solids
maintain a smooth, continuous flow into the plant. accumulations.
Pumping stations will normally require more pumps (c) Electrodes. A series of electrodes
under a constant speed system than one utilizing are mounted at different elevations so that when the
variable speeds. Also, the size of the wet well can be liquid level rises and contacts an electrode, an electric
reduced greatly when pumps operate on a continuous circuit is energized. Electrodes are used primarily in
basis. Variable speed operation is less efficient than pneumatic ejectors where the compressed air serves to
constant speed when pumping at reduced rates, keep the electrodes clean. They will not normally be
however friction losses and thus power costs are used in wet wells due to frequent fouling by grease and
generally less for the smaller flows. waste debris.
b Speed control systems. The selection and (d) Sonic meters. A sonic meter
design of the speed control system will be coordinated measures the distance from the liquid level to the meter.
closely with the selection of the pump and drive units. They are difficult to install free of obstructions, and must
The simplest system which allows pumps to accomplish be isolated from stray electrical or acoustic signals.
the required hydraulic effects will be chosen for design. (e) Capacitances tubes and pressure
Factors to be considered in selecting a system include diaphram sensors. These types of controls will not
cost, efficiency, reliability, structural requirements, ease normally be used due to fouling by the wastes.
of operation and degree of maintenance necessary. (2) Variable speed. A bubbler system will in
The last two items are critical at military installations most cases be employed to control the operation of
where adequate personnel cannot always be provided. automatic variable speed pumps. In these systems, the
Pumping stations will normally be designed for backpressure from the bubbler tube is transduced to a
automatic on/off operation of the pumping units, with pneumatic or electronic signal for use in on/off and
manual override by pushbutton or selector switch. variable speed control of the pumps. On/ off controls
(1) Constant and adjustable speed. Most are usually provided by pressure or electronic switches.
automatic constant speed and adjustable speed systems Variable speed control devices consist of (1) magnetic
will operate from level signals. Pumps are turned on as (eddy current) clutches, (2) liquid clutches, (3) variable
the liquid level in the wet well rises, and are turned off voltage controls, (4) variable frequency controls, and (5)
when it falls. Pumping systems utilized in treatment wound-rotor motor controls. Magnetic and liquid
plant processes are sometimes controlled by flow or clutches have been available for many years as
pressure sensors. Level detection systems in standard controllers for variable speed pumps. These older
use include the following: methods are inefficient in that the slip losses which
(a) Float switches. The simplest type developed are lost as heat. The recent development of
of switch consists of a float attached to a rod or tape, solid state electronics has led to the introduction of
and suspended in the wet well. The float rod opens or newer methods of variable speed control suitable for
closes a switch, depending on the rise or fall of the float both squirrel-cage and wound-rotor induction motors.
riding on the liquid level. The float may also be The variable voltage and variable frequency controls are
suspended in a tube or cage. These units usually suitable for use with squirrel-cage motors. Variable
require frequent maintenance as grease, scum and frequency drives are possible in efficiencies up to 95
debris in the wastewater build up on the equipment. percent, and are available in sizes up to 250 hp.
Another type of float control incorporates a mercury However, variable voltage units are inefficient and are
switch encapsulated in a corrosion resistant ball, and not recommended. Wound-rotor motor controls come in
suspended by cable in the wet well. This unit is not five categories, (1) fixed step resistors, (2) liquid
dependent upon the smooth, vertical movement of a rheostats, (3) reactance/resistance controllers, (4)
rod, and thus is not subject to the maintenance electronic rheostats, and (5) regenerative secondary
problems described above. controls. Of these, the regenerative secondary

4-4
TM 5-814-2/AFM 88-11, Vol. 2

control offers the best efficiency, while the other units a higher degree of maintenance than constant speed
are considerably less efficient and require more controls.
maintenance. In general, variable speed control
devices are more expensive, less efficient, and require

4-5
TM 5-814-2/AFM 88-11, Vol. 2

CHAPTER 5
PUMPING SYSTEM DESIGN

5-1. Force main hydraulics


a. General. The pipeline which receives 0.63 0.54
V = 1.32 C R S
wastewater from a pumping station, and conveys it to
the point of discharge, is called a force main. Force
where
mains will be designed as pressure pipe, and must be
V = velocity in feet per second
adequate in strength to withstand an internal operating
C = coefficient of pipe roughness
pressure equal to the pump discharge head, plus an
R = hydraulic radius in feet, and
allowance for transient pressures caused by water
S = slope of energy grade line in feet per foot
hammer. The internal operating pressure is maximum
at the pumping station, and is reduced by friction to
(1) Roughness coefficient. Values of C to be
atmospheric, or near atmospheric, at the point of force
used in the formula range from 100 for older force
main discharge. The primary consideration in the
mains which have been in service a number of years
hydraulic design of force mains is to select a pipe size
(usually over 10), to 140 for force mains which are
which will provide the required minimum velocities
newly constructed. Some manufacturers of plastic and
without creating excessive energy losses due to pipe
asbestos-cement pipe report C values as high as 150.
friction. The most economical size of force main should
However, due to uncertainties in design and
be determined on the basis of power costs required for
construction, plus a desire to provide a margin of safety,
pumping, and capital investment costs of piping and
C values greater than 140 will not normally be
equipment. In practice however, the size is usually
permitted. At some installations, force mains may be
governed by the need to maintain minimum velocities at
very old (40 to 50 years) and in extremely bad condition,
low flows to prevent deposition of solids, and to develop
with offset joints broken pipe, or materials encrusted on
sufficient velocity at least once a day to resuspend any
pipe walls. For these cases, lower C values may be
solids which may have settled in the line. However,
justified. However, values lower than 80 will not be
regardless of pipe sizes required for minimum velocities,
allowed unless verified by flow and pressure tests. A
the minimum diameters to be used are 1Y4-inch for
solution to the Hazen-Williams formula is given in figure
pressure sewers at grinder pump installations, 4-inch for
5-1.
force mains serving small pump stations and pneumatic
ejectors, and 6-inch for all other force mains.
b Design formula and chart. Force mains will be
designed hydraulically with the use of the Hazen-
Williams formula as follows:

5-1
TM 5-814-2/AFM 88-11, Vol. 2

Source: Design and Construction of Sanitary and Storm Sewers WPCF Manual of Practice No. 9
by Water Pollution Control Federation, 1970, p. 83.

Figure 5-1. Chart for Hazen-Williams formula.

(2) Velocity. Velocity criteria for force mains to warrant a minimum velocity of 3.5 fps with one pump
are based on the fact that suspended organic solids do operating, the design may call for both pumps to be
not settle out at a velocity of 2.0 foot per second or operated manually once a week for a sufficient period of
greater. Solids will settle at velocities less than 1.0 fps time to flush out the line. Larger stations having three
and when wastewater pumps are idle. However, a or more pumping units, which operate a major portion of
velocity of 2.5 to 3.5 fps is generally adequate to the time, will require minimum force main velocities
resuspend and flush the solids from the line. Force ranging from 2.0 fps with one pump operating, to 5.0 fps
mains serving small pump stations, which are designed with several pumps operating. In these cases, it is only
to operate on an intermittant basis, will be sized to required
provide a minimum velocity of 3.5 fps at the peak
discharge rate. For small stations having flows too low

5-2
TM 5-814-2/AFM 88-11, Vol. 2

that a minimum velocity of 2.5 to 3.5 fps be provided b. System head-capacity curve. To determine the
once or twice daily. Large pumping stations which serve head required of a pump, or group of pumps, that would
the entire installation or major portions thereof, and discharge at various flowrates into a force main system,
which are designed to pump continuously, will usually a head-capacity curve must be prepared. This curve is
have a greater number of pumps operating over a wider a graphic representation of the total dynamic head, and
range of flowrates. Since the pumping range may vary will be constructed by plotting the TDH over a range of
from 7 or 8 to 1, it will generally be sufficient to design flowrates from zero to the maximum expected value.
for velocities of 0.5 up to 7.0 or 8.0 fps. Maximum Friction losses can be expected to increase with time,
velocity is set at 10.0 fps. thus affecting the capacity of the pumping units and
(3) Slope. The value of S in the formula is their operation. Therefore, system curves well reflect
equivalent to the kinetic energy loss due to pipe friction the maximum and minimum friction losses to be
divided by the length of conduit, or S = Hf/L. Minor expected during the lifetime of the pumping units, as
energy losses from fittings and valves will be converted well as high and low wet well levels. The typical set of
to equivalent lengths of conduit for use in the formula. system curves will generally consist of two curves using
Conversion tables for fittings and valves can be found in a Hazen-Williams coefficient of C = 100 (one for
standard hydraulics textbooks. The total kinetic energy maximum and one for minimum static head), and two
loss in a force main will be computed by multiplying the curves using a Hazen-Williams co-efficient of C = 140
slope of the energy grade line by the total length of (for maximum and minimum static head). These
conduit including equivalent lengths, or Hf = S x L. coefficients represent the extremes normally found in
wastewater applications.
5-2. Pump analysis and selection c. Pump head-capacity curve. The head that a
a. Total dynamic head. The head in feet against particular pump can produce at various flowrates is
which a pump must work when wastewater is being established in pump tests conducted by the pump
discharged is termed the total dynamic head (TDH). manufacturer. The results of these tests are plotted on
The two primary components of TDH in wastewater a graph to form the pump characteristic curve. Along
applications are the static discharge head and the with the discharge head developed, the pumps
kinetic losses due to pipe friction. Velocity and pressure operating efficiency, required power input, and net
heads are also present, but are usually insignificant. positive suction head are generally included on the
The TDH will be calculated with the use of the Bernoulli same diagram.
energy equation which can be written as follows: (1) Efficiency and power input. Pump efficiency is the
ratio of the useful power output to the input, or brake
2 horsepower, and is given by:
TDH = (Pd/W + V d/2g + Zd) -(P8/W +
2
V 8/2g + Z8) + Hf E = wQ TDH
(bhp)(550)
where
where
E = pump efficiency (100 E =
Pd, P8 =gage pressures in pounds per
percent)
square foot w = specific weight of fluid in pounds
Vd, V8 =velocities in feet per second per cubic foot
Q = pump capacity in cubic feet per
Zd, Z8 =static elevations in feet
second
Hf = kinetic energy loss from pipe TDH = Total dynamic head, and
friction, fittings, and valves, as bhp = brake horsepower
calculated in paragraph 5-1b (3).
w = specific weight of fluid in pounds Pump efficiencies usually range from 60 to 85 percent.
per cubic foot, and Most characteristic curves will indicate a best efficiency
g = acceleration due to gravity 32.2 point (BEP) at which pump operation is most efficient.
2 Where possible, pumps will be selected to operate
ft/sec )
within a range of 60 to 120 percent of the BEP.
(2) Net positive suction head. When pumps
All head terms are in feet. Subscripts d and 8 represent operate at high speeds and at capacities greater than
force main discharge and pump suction, respectively. In the BEP, the potential exists for pump cavitation.
order to determine hydraulic conditions at the pump Cavitation can reduce pumping capacity and may in
suction, it will be necessary to write an energy equation time damage the pump impeller. Cavitation occurs
from the liquid level in the wet well to the pump suction when
nozzle.
5-3
TM 5-814-2/AFM 88-11, Vol. 2

the absolute pressure at the pump inlet drops below the variable speed pump operation in the absence of
vapor pressure of the fluid being pumped. To determine manufacturer's characteristic curves, or where
if cavitation will be a problem, the net positive sunction characteristic curves do not show performance at the
head (NPSH) available will be computed, and compared desired speeds.
with the NPSH required by the pump. The NPSH is not d Pump selection. System analysis for a pumping
normally a problem when discharge heads are less than station will be conducted to select the most suitable
60 feet. However, when heads are greater than 60 feet, pumping units which will meet service requirements,
or when the pump operates under a suction lift, or far and to determine their operating points, efficiencies, and
out on its curve, the NPSH will be checked. The NPSH required horsepower.
available at the eye of the impeller in feet will be (1) Single pump operation. A system head-
calculated with the following formula: capacity curve will be prepared showing all conditions
under which the pump is required to operate. The
NPSHA = H8 + Pa/w - Pa/w system curve will then be superimposed onto a pump
where head-capacity curve, or characteristic curve, to define
H8 = total energy head at pump suction the pump operating point. The point where the two
nozzle curves intersect represents the head and capacity at
= P8/w + V2 /2g + Z, which the pump will operate in the given piping system.
Pa = atmospheric pressure in pounds (2) Multiple pump operation. Where two or
per square foot absolute, and more pumps discharge into a common header, the head
Pv = vapor pressure of fluid being losses in individual suction and discharge lines will be
pumped in pounds per square foot omitted from the system head-capacity curve. This is
absolute because the pumping capacity of each unit will vary
depending upon which units are in operation. In order to
All head terms are in feet. obtain a true picture of the output from a multiple pump
(3) Affinity laws. A set of relationships installation, the individual suction and discharge losses
derived from flow, head and power coefficients for are deducted from the pump characteristic curves. This
centrifugal pumps, can be used to determine the effect provides a modified curve which represents pump
of speed changes on a particular pump. These performance at the point of connection to the discharge
relationships are known as affinity laws and are as header. Multiple pump performance will be determined
follows: by adding the capacity for points of equal head from the
modified curve. The intersection of the modified
Q1/Q2 = N1/N2 individual and combined pump curves with the system
H1/H2 = N21/N22 curves shows total discharge capacity for each of the
P1/P2 = N31/N32 several possible combinations. Pumps will be selected
where so that the total required capacity of the pump
N1, N2 = pump speeds in revolutions per minute installation can be delivered with the minimum level in
(rpm) the wet well and maximum friction in the discharge line.
Pump efficiency will be a maximum at average
Q, H and P terms represent pump capacity, discharge operating conditions. A typical set of system curves
head, and power output respectively, at speeds N1 and with pump characteristic curves is shown in figure 5-2.
N2. These relationships will be used in analyzing

5-4
TM 5-814-2/AFM 88-11, Vol. 2

Figure 5-2. Typical pump-system curves.

5-3. Wet well design For pumps driven by varible speed drives, the storage
a General. Wet wells will be constructed at volume may be small provided pumping rates closely
pumping stations for the purpose of storing wastewater match the incoming flowrates. The volume required for
flows prior to pump operation. The storage volume the wet well will be computed with the following formula:
required depends upon the method of pump operation,
i.e., whether pumps are constant, adjustable or variable V = tq/4
speed. In addition to providing adequate storage where
volume, wet wells will be designed to (1) allow for proper V = required volume in gallons
pump and level controls, (2) maintain sufficient between start and stop elevations
submergence of the pump suction inlet, (3) prevent for a single pump, or a single
excessive deposition of solids, and (4) provide speed step increase for adjustable
ventilation of incoming sewer gases. In smaller stations, or variable speed operation
bar racks or comminuting devices may be installed
within the wet well in order to reduce costs. Overflows
from wet wells are prohibited in all cases.
b Storage volume. If pumps are of constant or
adjustable speed type, the wet well volume must be
large enough to prevent short cycling of pump motors.

5-5
TM 5-814-2/AFM 88-11, Vol. 2

t = minimum time in minutes of one pumping Table 5-2. Required submergence depth to prevent
cycle (time between successive pump vortexing.
starts), or time required for a speed or Velocity at diameter D, fps S, feet
capacity change, and 2 1.0
q = pumping capacity, or increment in capacity 4 2.6
where one or more pumps are operating 5 3.4
and an additional pump is started, or where 6 4.5
pump speed is increased, in gallons per 7 5.7
minute 8 7.1
Constant or adjustable speed pumps driven by squirrel- Larger, conventional type pump stations will normally be
cage induction motors will be designed for minimum constructed with wet wells divided into two or more
cycle times as shown in the following table. sections, or compartments, so that a portion of the
Table 5-1. Minimum pump cycle times. station can be taken out of service for inspection or
More size, bhp t, minutes maintenance. Each compartment will have individual
Less than 20 10 to 15 suction pipes, and will be interconnected with slide or
20 to 100 15 to 20 sluice gates. The floor of the wet well will be level from
100 to 250 20 to 30 the wall to a point 12 to 18 inches beyond the outer
Over 250 as recommended by edge of the suction bell, and then will be sloped upward
manufacturer at a minimum 1:1 slope.
The storage volume calculated for small stations
(capacities less than 700 gpm) which utilize two identical 5-4. Pump controls and instrumentation
constant speed pumps, may be reduced one half by a. General. Instrumentation at a pumping station
providing a control circuit to automatically alternate the includes automatic and manual controls used to
pumps. The storage volume required for variable speed sequence the operation of pumps, and alarms for
pumps will be based on providing sufficient time for a indicating malfunctions in the pumping system.
change in capacity when a pump is started or stopped. Automatic control of pumps will usually be based on the
When a pump is started, the motor must be ramped to liquid level in the wet well. Paragraph 4-4 contains a
the desired speed, and the pumps already in operation discussion of the various modes of pump operation,
must be reduced in speed. The time required for this is pump control systems, and a description of level
usually less than 1 minute. A considerable amount of detection devices. Manual control of pumps is always
storage is normally available in large sewers which required in order to operate the pumps during
serve stations utilizing variable speed pumps. This emergencies, for maintenance purposes, or when
volume may be considered in design by calculating automatic systems fail. Manual override will be set to
backwater curves for the various operating levels. The bypass the low level cut-off, but not the low level alarm.
maximum retention time in the wet well will not exceed b. Selection of control points. A control range of at
30 minutes to prevent septicity. least 3.0 feet is required between maximum and
c. Suction pipe connections. Pump suction piping minimum liquid levels in the wet well. A minimum of 6
will be selected to provide a velocity of 4 to 6 feet per inches will be required between pump control points
second. Pipe should be one or two sizes larger than the used to start and stop successive pumps, or to change
pump suction nozzle. Vertical pumps installed in a dry pump speeds. For small stations, the control range may
well which is adjacent to the wet well, will be fitted with a be less, however control points will not be set closer
90 degree suction elbow, followed by an eccentric than 3 inches.
reducer and a gate valve. The suction line will be (1) Constant or adjustable speed pumps
extended through the wall into the wet well, and require simple on-off switches to start or stop pumps, or
terminated with either a 90 or 45 degree flared elbow, or to change from one speed step to the next.
an elbow with a flared fitting. The most commonly used (2) Variable speed pumps require a more
piping arrangements are illustrated in figure 5-3, where D complex control arrangement. The two basic types of
is the diameter of the flared inlet, and S is the level control for variable speed operation are (a)
submergence depth. variable level, and (b) constant level. For variable level
Adequate submergence of the suction inlet is critical to control, a narrow band of control points is established in
prevent air from being drawn in by vortexing. Minimum the wet well. Pump speed is then adjusted in steps by
required submergence depths are given in table 5-2 as a the level detection system (usually a bubbler tube) as
function of velocity. The net positive suction head the level varies. Pumps operate at maximum
(NPSH) will also be considered when determining S.
See paragraph 5-2c (2).
5-6
TM 5-814-2/AFM 88-11, Vol. 2

Figure 5-3. Pump suction connections to wet well.

speeds near the HWL, and at minimum speeds near the


LWL. However, pumps are started and stopped by level 5-5. Surge phenomena
switches. Constant level control is seldom used, but a. Water hammer. Sudden changes in flow and
may be required where a very narrow band of operation velocity in force mains can occur as a result of pump
is necessary. In a constant level system, one level is startup, pump shutdown, power failure, or rapid closing
set as the control point, and pump speed is adjusted in a of a valve. These velocity changes can produce large
stepless fashion as the liquid level rises above, or falls pressure increases or surge phenomena known as water
below this point. hammer. The most severe water hammer conditions
c. Alarms. Alarms will be provided to signal high are usually caused by a pump shutdown or power
and low liquid levels in the wet well, pump failure, or a failure. An analysis of water hammer will include
malfunctioning speed control system. The high level calculating the critical time, determining the maximum
alarm will be set above the start point of the last pump pressure increase, and selecting a method of control.
in the operational sequence, but below the start point of b. Critical time. When flow is suddenly changed in
the standby pump, if used. The low level alarm will be a force main, a pressure wave is generated which
set below the shutoff point of the lead pump. An rapidly travels the entire length of conduit, and back
emergency, low level pump cutoff will be set below the
low level alarm.
5-7
TM 5-814-2/AFM 88-11, Vol. 2

to the point of change. The time required for this to control and limit these surge phenomena, the
roundtrip is given by: following practices will be followed.
Tc = 2L/a (1) Gravity check valves. For simple cases
where involving small to medium sized pump stations with
Tc = critical time in seconds gradually rising force mains (no intermediate high
L = length of force main between points) of less than 1000 feet in length, and with static
point of flow change and point of discharge heads of less than 50 feet, a gravity operated
discharge in feet, and check valve will usually be sufficient. Gravity type
a = velocity of pressure wave in feet check valves may be either swing checks utilizing
per second outside lever and weight (or spring) set to assist closure,
When flow is completely stopped (Q = O) in a time or then may be ball checks. Swing check valves are
interval greater than Tc, the maximum theoretical usually installed horizontally, while ball check valves
pressure increase is not fully developed. However, may be either vertical or horizontal. For additional
when flow is stopped in a time interval less than or equal protection, a pressure relief valve may be installed in
to Tc, the change is said to be instantaneous, and the conjunction with check valves to allow reversing flow to
maximum pressure increase is developed as given reenter the wet wall. Pressure relief valves must be
below. specially designed for sewage applications. As an
c. Maximum pressure increase. The maximum alternative to relief valves, a hydro-pneumatic tank may
theoretical pressure increase or surge caused by water be utilized.
hammer is calculated from the following: (2) Automatic control valves. In situations
hw = aV/g where long force mains are required, pipe profiles must
where conform to existing ground elevations for economic
hw = pressure increase in feet reasons. This normally will result in high points in the
V = velocity of fluid in the pipeline force main, with the possibility of water column
prior to flow change in feet per separation at the high points in the force main, with the
second possibility of water column separation at the high points
g = acceleration due to gravity, or during pump shutdown or power failure. The pressures
32.2 ft/sec2 at sea level, and generated when these separated columns come to rest
a = velocity of pressure wave in feet against closed valves or against stagnant columns may
per second be large, and are again determined by paragraph c
Some typical values of a are given in table 5-3 below. above. In general, where force mains are greater than
Table 5-3. Water hammer wave velocities. 1000 feet in length or contain intermediate high points,
Pipe Material a, ft/sec and where pumping stations are large in capacity, or
Asbestos-cement 2700--400 static discharge heads are greater than 50 feet, control
Ductile iron 3100--4200 valves will be automatically operated (1) cone, (2) plug,
Steel 2700--3900 (3) ball, or (4) butterfly valves. Normal operation of
Concrete 3300--3800 these valves upon pump shutdown, is to slowly close the
Plastic 1100--1500 valve while the pump continues to run. When the valve
Fiberglass 1200--1600 is closed, a limit switch then stops the pump motor. On
d. Methods of control. Whenever a pump is shut power failure, an emergency hydraulic or other type
down, or power to the station fails, the pump motor is operator closes the valve slowly. The time of valve
suddenly cut off. Pump speed along with flow and closure is of utmost importance. Valves should be half
velocity in the force main are quickly decelerated by closed when the velocity in the force main has dropped
pressure waves, which travel up the pipeline and back in to zero. The time required to reach zero velocity can be
accordance with Newton's second law of motion. When calculated with the following formula:
the velocity is reduced to zero, reverse flow through the t = LV/g Hav
pump would occur if a gravity operated check valve or where
an automatic control valve were not installed on the t = time in seconds
pump discharge line, and did not close properly. L = length of force main in feet
Reverse flow fully accelerated through the pump could V = velocity of fluid in pipeline in feet
cause transient flows and pressures well above per second, and
maximum design conditions. A swing check valve Hav = average decelerating head
which stuck open temporarily, and then slammed shut including pipe friction in feet
under these conditions, would re5-8 suit in a large
pressure surge as given by paragraph c above. In order

5-8
TM 5-814-2/AFM 88-11, Vol. 2

The types of valve operators most often utilized are available for water hammer analysis, and are
hydraulic, electric and pneumatic. Valves and operators recommended for use in those instances.
specified for use will be fully adjustable for closure times
ranging from t to 4t minimum. In some large pumping 5-6. Screening and comminuting devices.
stations, the use of automatically controlled valves Centrifugal pumps are susceptible to clogging by rags,
alone will not be sufficient. Extremely long force mains trash, and other debris normally found in wastewater.
(over 1 mile) may require very long valve closing times, To protect pumps from clogging, equipment will be
and thus result in excessive backflow to the wet well and installed to screen or cut up these materials prior to
reverse rotation of the pump and motor. To solve these pumping. Small pump stations with capacities of less
problems, a pump bypass with surge relief valve will than 200 gpm, including grinder pumps and pneumatic
generally be required. Valves used for surge relief will ejectors, are exempt from this requirement. The types
be automatically controlled cone or butterfly valves, of equipment to be used include bar racks, screens, and
similar to the pump discharge valves. Normal operation comminutors which are installed in the wet well, or in a
upon pump shutdown now will require the pump separate influent channel. The design of these facilities
discharge valve to be fully closed when the velocity has is covered in TM 5-814-3/AFM 88-11, Vol. 3. At most
dropped to zero. The surge relief valve will be fully medium to large sized pump stations, the use of
open allowing backflow to enter the wet well at a mechanically cleaned bar screens or comminutors will
reduced rate. As before, the relief valve must close be required. However, at smaller stations in remote
slowly to avoid water hammer. Most cases involving areas, manually cleaned racks may be more feasible.
large pump stations with long force mains, which contain The smallest clear opening between bars is normally 1
several intermediate high points, will be too complex to inch, and spacings of less than 3/4 inch will not be
solve by hand using conventional methods such as permitted. All electrically operated equipment in wet
graphical solutions, arithmetic integration, or water wells will have explosion proof motors.
hammer charts. Many computer programs are now

5-9
TM 5-814-2/AFM 88-11, Vol. 2

CHAPTER 6
PIPING, VALVES AND APPURTENANCES

6-1. Pipe materials, fittings and joints The Handbook of Ductile Iron Pipe, Cast Iron Pipe
a. General. Factors to be considered in the published by the Cast Iron Pipe Research Association
selection of pipe materials and piping systems for force (CIPRA) will be used for guidance in designing ductile
mains are: -Flow characteristics or friction coefficient. iron force mains.
-Life expectancy and history of use. c. Steel. Steel pipe may be used for force mains
-Resistance to scour and abrasion. when lined with cement mortar or bituminous materials
-Resistance to acids, alkalis, high temperature to provide internal protection. A bituminous coating
or corrosive wastes, and corrosive soils. must be applied for external protection also. Lined and
-Ease of handling and installation. coated steel pipe is available in diameters 6-inch
-Physical strength and pressure ratings. through 144-inch. Galvanized steel pipe will be used for
-Joint watertightness and ease of installation. small diameter force mains and pressure sewers from
-Availability of pipe in required sizes, strengths, 1/4-inch to 4-inch in size. Joints for steel pipe less than
etc. 6-inch will be threaded. Pipe 6-inch in diameter and
-Availability of fittings, connections and larger will have mechanical, push-on, or flanged joints.
adapters. Threaded and flanged joints will be used only for interior
No pipe manufactured is suitable for all installation piping. Steel pipe will be installed in accordance with
requirements and conditions. The pipe materials the manufacturer's recommendations, and Manual No.
covered in this paragraph are the ones most often used M11-Steel Pipe Design and Installation published by the
for force mains carrying sanitary and industrial wastes. American Water Works Association (AWWA).
Each type of pipe will be evaluated to determine its d. Concrete. Concrete pressure pipe will generally
suitability for the particular design. Where iron or be used where high strength or large diameter force
concrete pipe are to be considered, special attention will mains are required. The type of cement used for
be paid to subsurface and soil conditions. The concrete will be selected in accordance with paragraph
characteristics of the soil in which a pipe is placed affect 6-5a of TM 5-814-1/AFM 88-11, Vol. 1. Pretensioned
the rates of corrosion, with the most corrosive soils reinforced concrete pressure pipe is available in
being those having poor aeration and high values of diameters 10-inch through 42-inch, prestressed concrete
acidity, electrical conductivity, dissolved salts, and pressure pipe in diameters 16-inch through 144-inch,
moisture content. The relative potential for corrosion and reinforced concrete pressure pipe in diameters 24-
may be estimated by evaluating the degree of corrosion inch through 144-inch. Each type utilizes bell and spigot
of existing metallic or concrete pipelines previously joints with rubber gaskets. The Concrete Pressure Pipe
buried in the soil. Facility engineer personnel will Manual, Manual No. M9 published by the American
normally have knowledge of these matters. When this Water Works Association (AWWA) will be used for
information is not available, or is nonconclusive, design of force mains.
resistivity tests of the soil will be conducted and results e. Asbestos-cement. Force mains constructed of
evaluated as required in TM 5-811-4/AFM 88-11, Vol. asbestos-cement (A.C.) pressure pipe are durable and
4. Pipe materials found inappropriate for use will be light in weight. However, A.C. pipe is affected by
deleted from the project specifications. corrosive wastes and aggressive soils, and must be
b Ductile iron. Ductile iron (D.I.) pipe is suitable provided with plastic linings for protection. The type of
for force mains used at pumping stations and material required for A.C. pipe will be type II in
wastewater treatment facilities. Special uses include accordance with ASTM C 500. Pipe is available in
river crossings, pipe located in unstable soil, highway diameters 4-inch through 42-inch, and will be joined by
and rail crossings, and piping installed above ground. means of couplings utilizing rubber gaskets. Design of
D.I. pipe is susceptible to corrosion from acid wastes A.C. force mains will conform to the manufacturer's
and aggressive soils. Cement linings, bituminous recommendations.
coatings or polyethelene linings are usually provided for f. Plastic. Characteristics which make plastic pipe
interior protections. For extremely corrosive soils, a highly desirable for force main use include high
polyethelene encasement is recommended for external corrosion resistance, light weight, and low coefficient of
protection. Pipe is available in 3-inch through 54-inch friction. Disadvantages include the possibility of
diameters, and with mechanical, push-on or flanged excessive pipe wall deflections when installed
joints. Flanged joints are restricted to interior piping.

6-1
TM 5-814-2/AFM 88-11, Vol. 2

improperly or subjected to high temperature wastes, and b. Surge control valves. To protect pumps and
chemical breakdown caused by prolonged exposure to piping from surges caused by pump shutdown or power
sunlight. The following types of plastic pipe are suitable failure, gravity operated swing check or ball check
for use: valves, or automatically operated cone, plug, ball or
(1) Polyvinyl chloride (PVC). PVC pipe is butterfly valves will be installed in the pump discharge
available in diameters 4-inch through 12-inch, and with line. The operation of surge control valves is discussed
screw, push-on, or solvent weld joints. in paragraph 5-5.
(2) Polyethylene (PE). PE pipe may be used c. Blowoff valves. A valve outlet installed at the
in diameters 11/2-inch through 48-inch. Pipe joints low point in a force main, and arranged to drain or flush
consist of mechanical, flanged, or heat fusion type. the pipeline, is termed a blowoff. Normally, blowoffs will
(3) Polypropylene (PP). Pipe diameters be required only on long depressed sections of force
available with polypropylene pipe are 1/2-inch through main, or where an accumulation of solids is likely to
4-inch. All pipe will be joined by heat fusion methods. occur. Blowoff connections will be installed in manholes
Screwed and flanged joint pipe will not be used or valve structures, and will be protected against
underground. Manufacturer's recommendations will be freezing. A means of discharging to a suitable location
used in design of plastic pipe, in addition to the materials flushed from the system will be provided. The
Handbook of PVC Pipe-Design and Construction pipe size of the outlet connection should coincide with
published by the Uni-Bell Plastic Pipe Association. the size of the force main.
g. Fiberglass. Fiberglass pipe provides a good d. Air valves. Air valves will be installed at high
alternative for use in large diameter force mains. High points in force mains for the purpose of admitting and
structural integrity, low pipe friction coefficient, and a releasing air. When the pipeline is taken out of service
high resistance to internal/external corrosion and to high for draining, flushing and filling operations, a manually
temperature wastes, are important properties of operated valve will be adequate. However, where air
fiberglass pipe. The following types of fiberglass pipe pockets or pressures less than atmospheric are likely to
may be used: occur with the pipeline in service and under pressure,
(1) Reinforced thermosetting resin pipe automatic air release and/or air vacuum valves will be
(RTRP). RTRP pipe may be installed in diameters of used. Manual valves can also be used with the pipeline
6inch through 144-inch. Jointing systems for RTRP pipe under pressure by leaving the valve partially open.
include bell and spigot, flanged, or special mechanical Automatic valves are not recommended due to
type couplings. Elastomeric gaskets are used to provide maintenance problems, and should be used only where
flexible joints. absolutely required. Automatic valves will be of a type
(2) Reinforced plastic mortar pipe (RPMP). specially designed for sewage, and will be provided with
Pipe diameters available for RPMP pipe range from 8- backflushing connections. All valves will be installed in
inch to 144-inch. Pipe joints are made with grooved a manhole or valve structure with adequate drainage
couplings or bell and spigot joints utilizing rubber and protection against freezing.
gaskets. Design of fiberglass force mains will follow the
manufacturer's recommendations. 6-3. Installation
h. Interior piping. Pump suction and discharge a. Structural design. Structural design of force
piping inside the station will normally be ductible iron or mains will be in accordance with the requirements set
steel. However, other pipe materials covered in this forth for sewers in chapter 5 of TM 5-811/AFM 88-11,
paragraph are not precluded from use. Pipe, fittings and Vol. 1.
joints serving as force mains will be selected to b. Thrust restraint. Force mains will be restrained
withstand the maximum internal operating pressures, to resist thrusts that develop at bends, tees, wye
including transient surges, as determined in chapter 5. connections and plugs in the pipe. The magnitude of
The project specifications will indicate the appropriate such forces can be calculated with the use of formulas
pressure class and rating for each pipe application. found in standard hydraulics textbooks. Required
methods of restraint will consist of tie rods and clamps,
6-2. Valves and appurtenances. The use of valves or concrete thrust blocks, and will be designed in
in wastewater pumping can be divided into the following accordance with Section VI of the CIPRA Handbook of
categories: Ductile Iron Pipe, Cast Iron Pipe.
a. Isolation or shutoff valves. Where the need to c. Depth of cover. Force mains will be installed
isolate pumps or part of the piping system occurs, with sufficient depth to prevent freezing, and to protect
manually operated shutoff valves will be used. Gate the pipe from structural damage. A minimum
valves or butterfly valves generally serve as shutoff
valves, however ball valves or plug valves may also be
used. Shutoff valves are required on the suction and
discharge sides of all pumps.
6-2
TM 5-814-2/AFM 88-11, Vol. 2

cover depth of 3 feet will ordinarily be required for least 12 inches above the top of the pressure pipe.
freeze protection. However, in unusually cold climates, Where a pressure pipe must cross a potable water line,
a greater depth may be required. the pressure line will always be installed below the water
d. Protection of water supplies. Force mains and line with a minimum vertical clearance of 2 feet.
pressure sewers will not be installed closer than 10 feet Pressure pipe joints will not be closer than 3 feet to the
horizontally to potable water lines. If conditions prevent crossing unless fully encased in concrete.
a 10-foot clearance, a minimum distance of 6 feet will
be allowed provided the bottom of the water pipe is at

6-3
TM 5-814-2/AFM 88-11, Vol. 2

CHAPTER 7
PUMP STATION COMPONENTS

7-1. Construction requirements collection of wash down, seepage, and stuffing box
a. Station configuration. The space requirements leakage. These wastes will be piped or conveyed to the
of pumps, piping and equipment, along with the storage wet well, either by gravity or by sump pump. Openings
volume required in the wet well, will be carefully to the wet well and dry well through the main floor of the
determined so that the proper size, shape and station will be above the maximum flood level, or will
configuration of the pumping station can be selected. otherwise be protected from flooding.
The size and shape of the station will often be dictated c. Materials of construction. Large to medium
by equipment other than pumps, such as bar screens, sized, conventional type stations will ordinarily be
comminutors, grit collectors, etc. Rectangular or square constructed of reinforced concrete. The above ground
structures normally have more usable interior space portion of the building may be of masonry, wood or
than circular ones, and will be employed whenever metal panel construction. The requirements of
possible in the design of medium to large sized pumping Department of Defense (DOD) Construction Criteria
facilities. However, where the below ground portion of Manual 4270.1-M will be followed in designing for fire
the station must be made deep to accommodate resistive structures. Small package type stations will
incoming sewers, and where foundation conditions are generally be manufactured of steel or fiberglass, with
poor, circular caisson type structures will be required if separate wet wells constructed of precast concrete or
lateral earth pressures are excessively high. Factory fiberglass manhole sections. Where steel structures are
assembled or package type stations will generally be used, cathodic protection or appropriate corrosion
circular in design, and will be anchored to base slabs control measures will be provided for the underground
where warranted by subsurface conditions. Pump steel shell in conformance with TM 5-811-4 or AFM 88-
stations located in cold regions or in seismic zones will 45. Alternatively, steel structures may be protected by a
require special design considerations. concrete or gunite coating where proof can be furnished
b. Designing for operation and maintenance. The by the manufacturer of satisfactory design life. All
design of medium to large sized, conventional type structures will be designed to withstand flotation.
pumping facilities will include adequate floor openings, d. Personnel safety. Guards will be placed on and
doorways, or access hatches for the installation, around all equipment where operators may come in
removal, and replacement of the largest items of contact with moving parts. Railings will be required
equipment. Interior dimensions in the dry well will around all floor openings, and along platforms or
provide a minimum clearance of 4 feet between walkways, where there is a danger that personnel may
adjacent pump casings, and a minimum of 3 feet from fall. Warning signs will be placed at all hazardous
each outboard pump to the closest wall. Other major locations. Rubber mats will be provided in front of all
items of equipment will be provided similar spacing. A electrical equipment where the potential exists for
7-foot minimum clearance between floor and overhead electrical shock. Adequate lighting and ventilation will
piping will be maintained where practicable. Smaller be provided as required in paragraphs 7-2 and 7-3. In
package type stations will be furnished with necessary attended stations where the possibility exists for toxic,
access openings for removal of pumps and equipment, explosive, or otherwise hazardous atmospheres, proper
however interior dimensions and clearances will design for personnel safety will be in conformance with
generally be less than for field erected stations. Wet chapter 19 of TM 5-814-3/AFM 88-11, Vol. 3. Design
wells for medium to large sized stations will be divided for fire protection will be in accordance with DOD
into two or more compartments to facilitate cleaning and Manual 4270.1-M and TM 5-812-1. Wastewater
repairs. Wet wells for all stations will have no length, pumping stations will be classified as light hazard,
width or diameter smaller than 4 feet. Eye bolts or industrial type occupancies.
trolley beams will be provided in smaller stations, and
overhead bridge cranes in large stations, for hoisting 7-2. Heating and ventilation
and removing equipment from mountings. Stairs will be a. Heating. All pumping stations subject to
provided in medium to large sized stations so that possible freezing will be supplied with automatically
personnel may inspect and maintain equipment. controlled heaters in the equipment areas. For
Smaller stations, except those utilizing submersible
pumps, will require the use of vertical safety ladders. A
suitable means will be provided to service and maintain
all equipment. A floor drainage system will be provided
in the dry well, and throughout the superstructure, for

7-1
TM 5-814-2/AFM 88-11, Vol. 2

unattended stations, temperatures will be maintained at manholes, backup of wastes into buildings, or any
40 degrees F. Attended stations will be heated to 65 unlawful pollution of the environment, or health hazard
degrees F. Although wet wells are generally unheated, to personnel. Pumping stations located at or in
thermostatically controlled heaters may be used to conjunction with treatment facilities, such as those
prevent condensation on walls and floors during cool required for influent pumping, recycling or bypassing of
weather, provided the ventilation system is shut off. flows, and pumping of effluent, will require standby
b. Ventilation. power capability if the pumping is essential to critical
(1) Wet wells will be provided with a positive treatment processes, plant flow control, or is necessary
ventilation capacity of 30 air changes per hour during to maintain compliance with the discharge permit. If
occupancy, based on the wet well volume below grade fixed standby power is required, refer to paragraph 4-2
and above the minimum wastewater level. for design criteria when selecting pump drive units, and
(2) Unattended dry wells will be provided with descriptions of various arrangements to be used in
a positive ventilation capacity of 30 air changes per providing fixed, standby power capability at wastewater
hour. Attended dry wells will be provided with a pumping stations.
continuously-operated ventilation capacity of 6 air
changes per hour, supplemented with additional 7-5. Water supply. A potable water supply is
ventilation in warm climates to remove pump motor heat required at all large pump stations to supply washroom
to within 5 degrees F. of the outside air temperature. and toilet facilities, hydrants, hose bibs and pump seal
Supply intakes and exhaust outlets must be located systems. A wash basin and toilet facilities will be
properly to introduce fresh air and remove hazardous provided at pump stations which are attended regularly.
gases or fumes. The wet and dry well sides of the Hose bibs will be provided in wet wells, dry wells and
station will be provided with separate ventilation bar screen rooms. Freeze proof wall hydrants will be
systems. required for outdoor use. A positive separation will be
maintained between the potable water system and any
7-3. Electrical equipment and lighting. Pump piping or appurtenances subject to contamination.
station equipment will be suitable for operation at either Warning signs will be posted at all water taps not
208V, 230V, or 480V, 60 Hz, three phase power directly connected to the potable water supply. The
supplies. However, equipment with motors smaller than positive separation will be accomplished either by
0.5 horsepower, including meters, switches, timers, providing a break with an air gap, or by installing
clocks, and similar equipment, will be suitable for backflow prevention devices. Air force facilities will
operation at a 125V, 60 Hz, single phase power source. comply with AFM 85-21.
a Service transformers. Service transformer
installations will conform to the requirements of TM 5- 7-6. Flow measurement. Flow meters installed to
811-1/AFM 889, Chap. 1. indicate and record the discharge from the pump station,
b. Motor starters and controls. Motor starters and and from individual pumps, will be provided at all
controls will be provided and housed in a factory medium to large sized stations. A meter installed in the
assembled, free-standing control center located on the discharge header provides valuable information on the
ground floor. The center will include motor starters, operation of the station, and will be required where
switches or circuit breakers, instrumentation and pumping capacity is expected to increase significantly in
controls. A pump station requiring a few small sized the future. Pressure gages are required on individual
starters is an exception, and will employ wall mounted or pump discharge lines, and on the station discharge
stand mounted equipment. header. Elapsed time clocks will be mounted on all
c. Control for submersible pumps. Enclosures for pump motor starters. For smaller stations utilizing
submersible pump controls will be installed above constant speed pumps, an elapsed time clock may be
grade. used in lieu of a pipe mounted flow meter to measure
d. Trouble alarms. Local trouble alarms will be pump discharge. This will also aid in scheduling routine
provided at all pump stations. Alarms will be maintenance on the motor since most small stations are
annunciated remotely from unattended stations. Alarm unattended. A noncorrodible depth gage installed in the
systems will be provided with manual silencing. wet well will generally suffice for very small pumps;
flows can be estimated from depth measurements taken
7-4. Standby power. The requirement for fixed, manually. The types of flow measuring devices to be
standby power at wastewater pumping stations will used for large wastewater pumps of the constant,
depend upon the type, location, and critical nature of adjustable or variable speed type, include flow
each pumping facility. For stations situated in low lying
areas, or in areas remote from a treatment plant,
standby capability will be provided if a power outage
would result in flooding of the station, overflows at sewer

7-2
TM 5-814-2/AFM 88-11, Vol. 2

tubes, venturi meters, magnetic and ultrasonic flow humidity variations within the station. Coating systems
meters. will consist of adequate surface preparation, and the
application of prime and finish coats using compatible
7-7. Paints and protective coatings. The use of materials as recommended by the coatings
paints and protective coatings at wastewater pumping manufacturer. All pumps and equipment will receive
stations will be in accordance with Water Pollution protective coatings in conformance with the
Control Federation (WPCF) Manual of Practice No. 17. manufacturer's recommendations. All ferrous materials
A thorough investigation will be made in the design of including galvanized surfaces will be protected.
protective coating systems. Paint materials selected will Particular care will be taken to protect welds and threads
be appropriate for the types of surfaces being protected, at connections. Package type stations will be shipped to
both submerged and nonsubmerged. Coating systems the construction site with factory applied paints and
will be designed to resist corrosion from the wastes coatings sufficient for the required service.
being handled, and from gases and vapors present,
taking into consideration the expected temperature and

7-3
TM 5-814-2/AFM 88-11, Vol. 2

APPENDIX A
REFERENCES

Government Publications
Department of Defense
DOD 4270.1-M Construction Criteria Manual
Departments of the Army and the Air Force
TM 5-811-1/AFM 88-9, Ch. 1 Electric Power Supply and Distribution
TM 5-8114 Electrical Design: Corrosion Control
TM 5-812-1 Fire Prevention Manual
TM 5-814-1/AFM 88-11, Vol. 1 Sanitary and Industrial Wastewater
Collection-Gravity Sewers and Appurtenances
TM 5-814-3/AFM 88-11, Vol. 3 Domestic Wastewater Treatment
TM 5814-8 Evaluation Criteria Guide for Water Pollution
Prevention, Control and Abatement Program
Department of the Air Force
AFM 85-21 Operation and Maintenance of Cross Control and
Backflow Prevention Devices
AFM 88-45 Civil Engineering Corrosion Control-Cathodic Protection
System

Nongovernment Publications
American Society for Testing and Materials (ASTM): Race St., Philadelphia, PA 19103
C 500 Testing Asbestos-Cement Pipe
American Water Works Association (AWWA), 6666 W. Quincy, Denver, Co 80235
Manual No. M9 Concrete Pressure Pipe (1979)
Manual No. M11 Steel Pipe Design and Installation (1964)
Cast Iron Pipe Research Association (CIPRA), 1301 West 22nd St., Oak Brook, IL 60521
Handbook of Ductile Iron Pipe, Cast Iron Pipe (1978)
Uni-Bell Plastic Pipe Association, 2655 Villa Creek Dr., Suite 150, Dallas, TX 75234
Handbook of PVC Pipe-Design and Construction (1977)
Water Pollution Control Federation (WPCF), 2626 Pennsylvania Ave., NW, Washington, DC 20037
Manual of Practice No. 17 Paints and Protective Coatings for Wastewater
Treatment Facilities (1969)

A-1
TM 5-814-2/AFM 88-11, Vol. 2

BIBLIOGRAPHY

Brater, E. F. and King, H. W., Handbook of Hydraulics, 6th ed., McGraw-Hill, New York, 1976.
Hicks, T. G. and Edwards, T. W., Pump Application Engineering, McGraw-Hill, New York, 1971.
Joint Committee of the Water Pollution Control Federation and the American Society of Civil Engineers, Wastewater
Treatment Plant Design, WPCF Manual of Practice No. 8, Washington, D.C., 1977.
Joint Committee of the Water Pollution Control Federation and the American Society of Civil Engineers, Design and
Construction of Sanitary and Storm Sewers, 2nd ed., WPCF Manual of Practice No. 9, Washington, D.C., 1970.
Metcalf & Eddy, Inc., Wastewater Engineering: Collection and Pumping of Wastewater, McGraw-Hill, New York, 1981.
Morris, H. M. and Wiggert, J. M., Applied Hydraulics in Engineering, 2nd ed., Ronald Press, New York, 1972.
Water Pollution Control Federation, Design of Wastewater and Stormwater Pumping Stations, WPCF Manual of Practice
No. FD4, Washington, D.C., 1981.

BIBLIO-1
TM 5-814-2/AFM 88-11, Vol. 2

The proponent agency of this publication is the Office of the Chief


of Engineers, United States Army. Users are invited to send
comments and suggested improvements on DA Form 2028
(Recommended Changes to Publications and Blank Forms) direct
to HQDA (DAEN-ECE-G), WASH D.C. 20314-1000.

By Order of the Secretaries of the Army and the Air Force:

JOHN A. WICKHAM, JR.


General, United States Army
Official: Chief of Staff

DONALD J. DELANDRO
Brigadier General, United States Army
The Adjutant General

CHARLES A. GABRIEL, General USAF


Official: Chief of Staff

JAMES H. DELANEY, Colonel, USAF


Director of Administration

Distribution:
Army: To be distributed in accordance with DA Form 1234B, requirements for TM 54800 Series: Engineering
and Design for Real Property Facilities.
Air Force: F

*U.S. GOVERNMENT PRINTING OFFICE: 19-61U11001M/401-M


PIN: 025925-000

Вам также может понравиться