In stru ctio n M a n u a l
This m anual is a guide to the Installation,
O peration and M aintenance of the
ERITEC H SI IN TERC EPTO R Lightning
Protection System . It assum es that the
system to be installed has been designed by
an authorized ERIC O representative. The
system design w ill include:
G rounding system s design a configura-
tion should be designed as a result of
soil resistivity analysis.
D ow nconductor routes - chosen to avoid
other services, m aintain m inim um
bending radii and m inim ize dow n
conductor run length.
D ow nconductor securing requirem ents.
LPSD - C A D analysis design softw are
w hich determ ines term inal placem ent,
m ast & height requirem ents as w ell as
protection level calculation.
A ll of the above are recom m ended for a
successful installation. If there is any
doubt about any of the points
m entioned, please contact ERIC O or its
nearest representative for clarification.
Warning - Only attempt to
install the ERITECH SI
INTERCEPTOR during
storm-free periods.
The SI IN TERC EPTO R m ust be at least 2
m eters higher than any other point on
the structure it is intended to protect.
The resistance of the lightning protection
grounding system m ust be less than 10
ohm s. This should be m easured w ithout
dow nconductor(s) connected and w ith-
out interconnection to other grounding
system s.
www.erico.com
2
ERI TECH SI I NTERCEPTOR - I NSTRUCTI ON MANUAL
Installation Guidelines
For full details on installing your SI
IN TERC EPTO R, please refer to ERIC O s
technical notes and the French national
standard N FC 17-102. It is also
recom m ended to adhere to local
standards for relevant local dow n
conductor and grounding requirem ents.
Certif ication
The certification of the ERITEC H SI
IN TERC EPTO R installation m ust be
perform ed by an authorised ERIC O
representative. This is done in conjunction
w ith issuing of a C ertificate of C om pliance,
w hich is available from your nearest ERIC O
office. W hen this certificate has been
com pleted and signed, a copy m ust be
either taken by the ERIC O representative or
sent to the nearest ERIC O office. D uring the
process of certification, the follow ing w ill
be checked:
Installation m atches the Benji design.
The integrity of the m ast and any
associated brackets and fastenings.
G uying, anchor points and fastenings.
D ow nconductor routing, securing and
seals.
G round term ination of dow n-conductor.
G rounding System .
Labelling.
C ertificate of C om pliance and W arranty
C ard com pleted and returned.
G eneral m echanical check of all
fastenings.
www.erico.com
3
ERI TECH SI I NTERCEPTOR - I NSTRUCTI ON MANUAL
Operation and Maintenance
The ERITEC H SI IN TERC EPTO R lightning
protection system requires no user
operation and is com pletely autom atic in
operation.
The SI becom es active only during
storm activity.
The system does not require any external
pow er requirem ents or replacem ent
com ponents for norm al operation.
It is essential that the ERITEC H SI
IN TERC EPTO R Lightning Protection
System be regularly m aintained.
M aintenance should be undertaken:
1. A fter each know n strike to the SI
IN TERC EPTO R or at least once per year.
2. If any changes have been m ade to the
structure, w hether they be structural,
antennae or Building M aintenance U nit
additions, etc.
M aintenance should be undertaken as
follow s:
Do not attempt
maintenance during
potential lightning periods.
1.C heck that the building is the sam e
physical shape and that no additional
structures such as antennae, advertising
signs, satellite dishes, Building
M aintenance U nits or sim ilar have been
installed w ithin 2m (80in.) height of the
SI IN TERC PTO R.
2. Inspect the SI IN TERC EPTO R to ensure
that it is not dented or physically
dam aged in any w ay.
3. Inspect the Finial Tip on top of the SI
IN TERC EPTO R to ensure that it is not
excessively burnt, deform ed or m issing.
4. C heck that the m ast is securely attached
to the structure. C heck that the guys are
secure and undam aged. Replace if
necessary. C heck that all fastenings are
secure and tight.
5. Look for signs of dam age to the
dow nconductor (w hether by lightning,
careless handling, vandalism or other
causes).
6. C heck that the Lightning Event C ounter
is secure, if the display is registering a
reading, then record the reading and
date.
7. Ensure the grounding resistance is less
than 10 .
8. C heck the continuity of all bonding
conductors
Installation Instructions
The recom m ended order of installation is as
follow s:
1.Full installation of the grounding system .
2.Full installation of the dow nconductor.
3.Term ination of the dow nconductor to the
grounding system .
4.Term inate the top of the dow nconductor
to the SI IN TERC EPTO R m ast.
5. Raise the m ast into position and secure.
DOWNCONDUCTOR
Refer to your local
standard for downconductor
requirements.
MAST
(ER1-1000-SS)
or (ER1-2000-SS)
SI-125, SI-140 or SI-60
CABTIE-SS
ALOF-1-GS
1m
TERMINATION
COUPLER
supplied with
ER1-1000-SS
or ER1-2000-SS
TMC-SS TMC-SS LPC580
MAST
OPTIONS
ER1-1000-SS
ER1-2000-SS
ER2-2000-SS
ER2-3000-SS
ER3-2000-SS
ER3-3000-SS
MAST
(ER2-2000-SS)
or (ER2-3000-SS)
For Cantilevered Mast
(range 2-4 metres)
www.erico.com
4
ERI TECH SI I NTERCEPTOR - I NSTRUCTI ON MANUAL
Typical MAST Installation Arrangement
www.erico.com
5
ERI TECH SI I NTERCEPTOR - I NSTRUCTI ON MANUAL
DOWNCONDUCTOR
Refer to your local
standard for downconductor
i t
MAST
(ER1-1000-SS)
or (ER1-2000-SS)
MAST
(ER2-2000-SS)
or (ER2-3000-SS)
SI-125, SI-140 or SI-60
CABTIE-SS
ALOF-1-GS
1m
1m
TERMINATION
COUPLER
supplied with
ER1-1000-SS
or ER1-2000-SS
TMC-SS TMC-SS LPC580
MAST
OPTIONS
ER1-1000-SS
ER1-2000-SS
ER2-2000-SS
ER2-3000-SS
ER3-2000-SS
ER3-3000-SS
MAST
(ER2-2000-SS)
or (ER2-3000-SS)
For Cantilevered Mast
(range 4-6 metres)
MAST
(ER3-2000-SS)
or (ER3-3000-SS)
Typical MAST Installation Arrangement
www.erico.com
6
ERI TECH SI I NTERCEPTOR - I NSTRUCTI ON MANUAL
Guy Kit
(GUY KIT 4)
Anchor Points
not supplied with
GUYKIT 4
Do not over-tension
Guy Wires
(Slightly sagging)
Mast
(ER2-3000-SS
or ER2-2000-SS)
Preferred
Angle
45- 60
Support Base
(ER2-BASE-SS)
ER1-1000-SS
ER1-2000-SS
ER2-2000-SS
ER2-3000-SS
ER2-BASE-SS
ER3-2000-SS
ER3-3000-SS
ER3-BASE-SS
MAST
OPTIONS
4 Holes, 12.5mm
1
7
8
m
m
2
2
9
m
m
TMC-SS TMC-SS LPC580
DOWNCONDUCTOR
Refer to your local
standard for downconductor
requirements.
CABTIE-SS
MAST
(ER1-1000-SS)
or ER1-2000-SS)
S125, S140 or S160
TERMINATION
COUPLER
suppiled with
ER1-1000-SS
or ER1-2000-SS
For Guyed Mast
(range 3-5 metres)
Typical MAST Installation Arrangement
www.erico.com
7
ERI TECH SI I NTERCEPTOR - I NSTRUCTI ON MANUAL
Guy Kit
(GUYKIT 7)
Anchor Points
not supplied with
GUYKIT 7
Do not over-tension
Guy Wires
(Slightly sagging)
Mast
(ER3-2000-SS
or ER3-3000-SS)
Preferred
Angle
45- 60
Support Base
(ER3-BASE-SS)
ER1-1000-SS
ER1-2000-SS
ER2-2000-SS
ER2-3000-SS
ER2-BASE-SS
ER3-2000-SS
ER3-3000-SS
ER3-BASE-SS
MAST
OPTIONS
4 Holes, 12.5mm
1
7
8
m
m
2
2
9
m
m
TMC-SS TMC-SS LPC580
DOWNCONDUCTOR
Refer to your local
standard for downconductor
requirements.
CABTIE-SS
MAST
(ER1-1000-SS)
or ER1-2000-SS)
MAST
(ER2-2000-SS)
or ER2-3000-SS)
S125, S140 or S160
TERMINATION
COUPLER
suppiled with
ER1-1000-SS
or ER1-2000-SS
For Guyed Mast
(range 5-8 metres)
Guy point
midway on
ER2 Series
mast
Typical MAST Installation Arrangement
www.erico.com
8
ERI TECH SI I NTERCEPTOR - I NSTRUCTI ON MANUAL
Options De Support / Support Options / Opciones del Montaje
P/N o. IN TC PT-A D BU TT (#702296)
INTERCEPTOR
INTCPT-ADBUTT
MASTBUTT
ADAPTOR
LOCKSCREW
ERICORE
UPPER
TERMINATION
FRPMAST
P/N o. TERM LU G C O U P (#701840)
Option : 1 ERIC O RE D ow nconductor
Opcin : 1 ERIC O RE C onducteur de descente
Option : 2 Standard D ow nconductor
Opcin : 2 C onducteur de descente
INTERCEPTOR
INTCPT-ADBUTT
MASTBUTT
ADAPTOR
LOCKSCREW
TERMLUGCOUP
ERICO
ALUMINIUM
TUBULAR MAST
www.erico.com
9
ERI TECH SI I NTERCEPTOR - I NSTRUCTI ON MANUAL
Options De Support / Support Options / Opciones del Montaje
P/N o. IN TC PT-A D M 3/4U N C (#702299)
P/N o. IN TC PT-A D F2BSPF (#702297)
P/N o. IN TC PT-A D F2N SP (#702298)
Option : 3 Standard D ow nconductor
Opcin : 3 Standard C onducteur de descente
Option : 4 Standard D ow nconductor
Opcin : 4 Standard C onducteur de descente
INTERCEPTOR
INTCPT3
OR
INTCPT3SS
INTCPT-ADM3/4UNC
CONDUCTIVE MAST
INTERCEPTOR
INTCPT3
OR
INTCPT3SS
INTCPT-AMD2NPS
OR
INTCPT-ADMSBSPF
2" PIPE
N ote:
IN TC PT-
A D M 3/4U N C
3/4"
U N C thread
N ote:
IN TC PT-A D F2BSPF
2" British
Standard Pipe
thread.
IN TC PT-A D F2N SP
2" (U SA ) N ational
Standard Pipe
thread.
www.erico.com
10
ERI TECH SI I NTERCEPTOR - I NSTRUCTI ON MANUAL
www.erico.com
5 YEAR LIMITED WARRANTY
This product has a lim ited w arranty to be free from defects in m aterials and w orkm an-
ship for a period of ten (5) years from the date of dispatch from the M anufacturer.
The Purchaser acknow ledges that lightning is a natural event w ith statistical variation
in behavior and energy levels w hich m ay exceed product ratings, and 100% protec-
tion is not offered and cannot be provided for. Therefore the M anufacturer's liability is
lim ited to the repair or replacem ent of the product (at the M anufacturer's sole option)
w hich in its judgem ent has not been abused, m isused, interfered w ith by any person
not authorized by the M anufacturer, or exposed to energy or transient levels exceed-
ing the M anufacturer's specifications for the product. The product m ust be installed
and earthed (w here applicable) in strict accordance w ith the M anufacturer's specifi-
cations and all relevant national Electricity and Safety Standards. The M anufacturer
and the Purchaser m utually acknow ledge that the product by its nature m ay be sub-
ject to degradation as a consequence of the num ber and severity of surges and tran-
sients that it experiences in norm al use and this w arranty excludes such gradual or
sudden degradation. This w arranty does not indem nify the Purchaser of the product
for any consequential claim for dam ages or loss of operations or service or profits.
C ustom ers should contact their nearest ERIC O agent to obtain a Product Repair
Authorization N um ber prior to m aking any claim under this w arranty. This is only a
sum m ary of the w arranty given by the M anufacturer. The full text of the w arranty is set
out in the M anufacturer's C onditions of Q uotation and Sale.
www.erico.com
11
ERI TECH SI I NTERCEPTOR - I NSTRUCTI ON MANUAL
WARNING:
1. These products shal l be used onl y as i l l ustrated and recommended i n product i nstructi on sheets (addi ti onal
i nstructi on sheets are avai l abl e at www.eri co.com). Mi suse or mi sappl i cati on may cause fai l ure resul ti ng i n
possi bl e property damage or bodi l y i nj ury.
2. These products must be used onl y i n the manner depi cted i n the i l l ustrati ons that accompany them.
3. Fai l ure to observe these speci fi cati ons may cause product mal functi ons resul ti ng i n property damage or bodi l y
i nj ury. ERICO products at the ti me of shi pment are warranted to conform to any appl i cabl e wri tten descri pti on
furni shed to the Buyer by ERICO, and to be free from defects i n materi al and workmanshi p. NO OTHER WARRANTY,
WHETHER EXPRESSED OR IMPLIED, (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS), SHALL
EXIST IN CONNECTION WITH THE SALE OR USE OF ANY ERICO PRODUCT.
4. Al l i nstructi ons must be compl etel y fol l owed to ensure proper and safe operati on.
SAFETY WARNING:
SAFETY INSTRUCTIONS: Al l governi ng codes and regul ati ons and those requi red by the j ob si te must be observed.
Al ways use appropri ate safety equi pment such as eye protecti on, hard hat, and gl oves as appropri ate to the
appl i cati on.Wear gl oves to avoi d spl i nters and cuts.
HAZARDOUS VOLTAGES EXIST INTERNAL TO THE SI INTERCEPTOR. THIS UNIT SHOULD BE INSTALLED
AND SERVICED ONLY BY QUALIFIED PERSONNEL IN CONFORMANCE WITH ALL GOVERNING CODES.
The power suppl y to the SI INTERCEPTOR shoul d al ways be turned (and l ocked) OFF before the uni t i s accessed for
any reason.
Pri or to i nstal l ati on, ensure that the SI INTERCEPTOR i s of the correct vol tage, current, phasi ng, frequency rati ng
and i s the type recommended by the manufacturer of the power di stri buti on system.
Al l i nstructi ons must be fol l owed to ensure proper and safe operati on of the SI INTERCEPTOR.
Fai l ure to fol l ow i nstructi ons or warni ngs may resul t i n bodi l y i nj ury, equi pment damage or i neffecti ve protecti on.
DANGER: El ectri cal shock or burn hazard. Instal l ati on of thi s SI INTERCEPTOR shoul d onl y be made by qual i fi ed
personnel . Fai l ure to l ockout el ectri cal power duri ng i nstal l ati on or mai ntenance can resul t i n fatal el ectrocuti on or
severe burns. Before maki ng any connecti ons to thi s el ectri cal panel be sure that power has been removed from al l
associ ated wi ri ng, el ectri cal panel s, and other el ectri cal equi pment.
CAUTION: Check to make sure l i ne vol tage does not exceed SI INTERCEPTOR vol tage requi rement.
CAUTION: Thi s uni t must be i nstal l ed i n conformance wi th al l governi ng codes and must be i nstal l ed on the l oad si de
of the mai n over- current protecti on.
Di agrams are for reference onl y. Schemati cs are representati ve of typi cal appl i cati ons and are onl y to be used for
reference.
E668LT03US FEP-LT04-8
www.erico.com
AUSTRALIA
6 Chilvers Road
P.O. Box 148
Thornleigh (Sydney) NSW 2120
Australia
Phone 61-2-9479-8500
Fax 61-2-9484-9188
BELGIUM
Postbus 33
3110 Rotselaar
Belgium
Phone 32-14-69-96-88
Fax 32-14-69-96-90
CANADA
34600 Solon Road
Solon, Ohio 44139
U.S.A.
Phone 1-800-677-9089
Fax 1-800-677-8131
CHILE
Alcantara 200, piso 6 Of. 17
Las Condes, Santiago
Chile
Phone 56-2-370-2908
Fax 56-2-370-2914
CHINA
Room 1204
Tomson Commercial Building
No. 710, Dongfang Road
Pudong, Shanghai
P.R. China 200122
Phone 86-21-5081-3900
DENMARK
Box 211
201 22 Malm
Sweden
Phone 46-40-611-13-60
Fax 46-40-611-94-15
FRANCE
Rue Benot Fourneyron Z.I. Sud
Bote Postale 31
42161 Andrezieux Cedex
France
Phone 33-4-77-36-56-56
Fax 33-4-77-55-37-89
GERMANY
66851 Schwanenmuehle
Germany
Phone 49-6307-918-10
Fax 49-6307-918-150
HONGKONG
Unit 1, 2nd Floor, Block A
Po Yip Building
62-70 Texaco Road
Tsuen Wan, New Territories
Hong Kong
Phone 852-2764-8808
Fax 852-2764-4486
HUNGARY
Cegldi t 1-3
1107 Budapest
Hungary
Phone 36-1-431-3464
Fax 36-1-431-3471
INDONESIA
Wisma Danamon Aetna Life 19th
Floor
Jalan Jend. Sudirman Kav. 45-46
Jakarta 12930
Indonesia
Phone 62-21-575-0941
Fax 62-21-575-0942
ITALY
A&B Business Center
Via Valla 16, nr. 17
20141 Milano
Italy
Phone 39-02-8474-2250
Fax 39-02-8474-2251
MEXICO
Melchor Ocampo 193
Torre A piso 13
Col. Veronica Anzures
11300 Mexico D.F.
Mexico
Phone 52-55-5260-5991
Fax 52-55-5260-3310
NETHERLANDS
Postbus 487
5000 AL Tilburg
Netherlands
Phone 31-13-58-35-400
Fax 31-13-58-35-499
POLAND
ul. Krzemieniecka 17
54-156 Wroclaw
Poland
Phone 48-71-374-40-22
Fax 48-71-374-40-43
SINGAPORE
16 Wan Lee Road
Jurong Industrial Estate
Singapore 627946
Phone 65-6-268-3433
Fax 65-6-268-1389
SPAIN
C/Provenza 288, Pral.
08008 Barcelona
Spain
Phone 34-93-467-7726
Fax 34-93-467-7725
SWEDEN
Box 211
201 22 Malm
Sweden
Phone 46-40-611-13-60
Fax 46-40-611-94-15
SWITZERLAND
Postfach 54
3280 Murten
Switzerland
Phone 00-800-5000-1090
Fax 00-800-6000-1090
UNITEDKINGDOM
52 Milford Road
Reading, Berkshire RG1 8LJ
United Kingdom
Phone 44-118-958-8386
Fax 44-118-955-0925
UNITEDSTATES
34600 Solon Road
Solon, Ohio 44139
U.S.A.
Phone 1-440-248-0100
Fax 1-440-248-0723
NORWAY
Postboks 148
1366 Lysaker
Norway
Phone 47-67-53-12-00
Fax 47-67-12-42-68
BRAZIL
R. Dom Pedro Henrique de Orleans
e Braganca, 276
Vila Jaguara CEP 05117-000
So Paulo
Brazil
Phone 55-11-3621-4111
Fax 55-11-3621-4066
THAILAND
163 Ocean Insurance Building,
16th Floor, Unit B
Surawongse Road, Bangrak
Bangkok 10500
Thailand
Phone 66-2-634-1692
Fax 66-2-634-1694
Copyright 2004 ERICO International Corporation. All rights reserved.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.

Вам также может понравиться