Cable Crossings - Derating Considerations Part I - D tion of Derating Equations George Anders Ontario Hydro Technologies Toronto, Canada Abstract. Dangerously high interference temperatu occur at points where cables cross external heat sources even when the crossing occurs at 904 For perpendicular and oblique crossings, these interference temperatures are usually ignored for distribution circuits, whereas for transmission cables, corrective actions in physical installation condition are sometimes taken. Analytical solutions are almost never used to determine the effect of external heat source on the ampacity of the rated cable. The main reason no computations are performed is an absence of either derating formulas or derating tables (curves) and not the lack of a need. To fill this gap, an analytical solution for the computation of the derating factors has been developed and is presented in this paper. The solution i s simple and accurate enough to be suitable for standardization purposes. A numerical example involving the intersection of a pipe-type cable by a distribution circuit is presented to show the effect of perpendicular and oblique crossings on the ampacity of both circuits. In this practical example, the ampacity of the pipe-type cable is significantly affected for a range of crossing angles. A conservative practice, used by many utilities in cases like this, would be to assume that the cables are parallel. However, in our example for a 90" crossing, such an approach would unnecessarily decreases the ampacity of the pipe-type cable by almost 20%. 1. Introduction A great variety of plant can be found under the streets of congested urban areas. It is not uncommon to find power cables crossing steam pipes or other cables. When a cable is crossed by another heat source, its temperature will be higher than if it was isolated. As will be shown below, this additional conductor temperature rise may exceed 20C. Therefore, the ampacity of the rated cable should be reduced accordingly. Ten and often 20% reduction may be required as illustrated in the numerical example in the second part of this paper. This is PE-239-PWRD-0-09-1998 A paper recommended and approved by the IEEE Insulated Conductors Committee of the IEEE Power Engineering Society for publication in the IEEE Transactions on Power Delivery Manuscript submitted May 12, 1998 made available for printing October 7, 1998. Heinrich Brakelmann Gerhard-Mercator-Universi tat Duisburg, Germany much larger than the up to 5% reduction considered by some utilities. On the other hand, many utilities do not derate cables crossed by other heat sources. This practice may lead to premature cable failures, as reported for example in [l]. An informal survey conducted by the authors has clearly indicated a need to establish derating factors for cable crossings. The temperature increase in the rated cable resulting from the presence of another heat source will depend on several parameters. The most important are: 0 the amount of heat dissipated by the crossing heat source the distance between rated cable and the heat source at the point of intersection the angle between the heat source and the cable (the more parallel the two are, the larger the influence of the heat source on the rated cable) the size of the rated cable. 0 0 This paper examines the issues related to derating of cables caused by the presence of another heat source. Section 2 describes briefly the results of an informal survey whose aim was to find out the practices in various utilities with regard to cable crossings. Section 3 discusses modeling issues and outlines the work required to obtain derating factors. A second part of this paper examines computation required to obtain derating curves. 2. Utility practices In order to find out how cable crossings are dealt with in electric utilities, an informal survey was conducted among several engineers active in the field of cable ratings. Several utilities in Canada have been contacted, in addition, practices in England, Germany, Italy, the Netherlands, France, Belgium, Poland and Sweden were investigated. In general, all the contacted utilities deal with the subject of cable crossings in a similar way. For distribution installations (low and medium voltage), in a great majority of cases, no derating is considered at all. The most often quoted reason was that the cables are rated very conservatively (e.g., high soil thermal resistivity or a high ground ambient temperature are assumed). In some cases, for example in Sweden, special precautions are taken in the case when a distribution cable (0.4 - 24 kV) crosses a district heating pipe. 0885-8977/99/$10.00 0 1998 IEEE 710 In particular, the Swedish standards state that the cable should always be above the pipe, at the distance not smaller than 20 cm as perpendicular as possible. A heat isolating plate 50 mm thick is required between cable and the pipe system. In one utility, for cable ratings at steam pipe crossings it is typically assumed that the ambient temperature is higher by 5OC than the values used for isolated cables, which results in a 3% decrease in the cable rating. In several countries, a minimal distance is specified between the rated cable and the external heat source. This distance varies between 20 and 50 cm. The situation is only slightly different when a high voltage cable is involved. With the exception of France, no computations are performed to determine the actual effect of cable crossing another heat source (EDF may conduct a 3 dimensional finite element analysis in some important cases). However, most utilities would take special actions to reduce the mutual heating effect. Several approaches have been applied: 0 0 0 0 usage of larger cable isolation of the heat source from the cable usage of heat transfer pipes usage of thermal backfills in an increased trench cross- section usage of insulating liquid circulation installation of ventilating manholes at crossing points at steam heat crossings, utilities sometimes build a Styrofoam(closed cell) box around the steam heat pipe, then fill the box with Gilsulate, an underground insulating material used by steam heating companies in one instance, for 90 degree crossings, a utility followed a very rough approximation by doing ratings assuming parallel cables, but at twice the actual vertical separation distance. Finally, several engineers indicated that the main reason no computations are performed is an absence of either derating formulas or derating tables (curves) and not the lack of a need. All indicated that it would be very beneficial if a simple derating method was available. Such a method is presented in the next section. 0 3. Ampacity reduction modeling 3.1 Literature search A. literature search (in English) on cable crossings showed a very limited number of publications. In [2], the authors present the thermal analysis of temperature distributions along the crossing regions of high voltage cables. Analytical results for perpendicular crossing are developed and checked against measured values. The hot spot temperature for the experimental setup of 66 kV and 220 kV cables is measured. This temperature at the 66 kV cable is higher by about 25C than the cable temperature far away from the crossing region. The corresponding value for the 220 kV cable is only 8OC higher. The authors also consider the effect of *lying heating pipes and special backfill for hot spot elimination. nce [3] describes a type of anti-thermal interference system consisting of long heat pipes. A very simple mathematical model for heating of the cable by the interfering source is presented for the 90" crossing. In the example presented in the paper, the cable conductor erature rise at the intersection caused by steam pipe with rature of 15OoC located 1.8 m below the cable reaches . The effect of the steam pipe disappears about 6 m from the crossing. Similar problem is discussed in [4]. This paper described the evaluation of the thermal interference that the power cables receive from steam pipe located in a close vicinity. Experimental and analytical models are described. 90' crossings are considered. An equation, derived experimentally, for the effective thermal resistance of cable surroundings is given without the definition of the symbols. It appears to be an equation for the external thermal resistance of a cable located in a thermal backfill and does not appear to be related to the presence of an external heat source. 3.2 3.2.1 Derating factor A simple model is developed in this Section to account for the presence of crossing heat sources which includes all of the important factors mentioned in the introduction. To illustrate the development of the derating equation, consider two cables crossing as shown in Figure 1. Suppose that cable 2 is to be derated because of the heat W1 (W/m) generated by cable 1. Let A8- be the maximum permissible conductor temperature rise of the conductor of cable 2 for current dependent losses. Because of the mutual heating, the maximum allowable heat rate in cable 2 will be reduced as shown below. Proposed model for derivation of derating curves where W,, cable 2 (W/m). T,, ( K . r n ) T = total thermal resistance of cable 2 (K.m/W) with =reduced maximum allowable losses in conductor of =the mutual thermal resistance between cables 1 and 2 T =-+(I I; +al)G +(1 +a1 +a,)(& +&) n 71 1 To find the temperature at any point of the rated cable taking into account its longitudinal heat flux and the interfering temperature given by equation ( 5) , we will discretize the length of the qted circuit as shown in Figure. 2, [7]. z =O z=AZ 7.=2& z=N& I -- ---_-__ -_-_-___ , / , , I the notation is the same as in IEC 287 [5] and is also verbalized in Table 1 in Part 11of this paper. Y 4 / Y = Y l - Figure I . Crossing of two cables at an angle 90 O - p. Since, for the isolated cable w, =%!EL (3) T The reduced rating I,, of cable 2 can now be obtained by combining equations 1 and 3 as (4) where I2 is the rating of the isolated cable 2. Thus, the derating factor can be obtained from equation (4) when the mutual thermal resistance q2 is known. Computation of this resistance is discussed next. 3.2.2 Temperature distribution along the rated cable and the mutual thermal resistance Referring to Figure 1, the temperature rise in the conductor of cable 2 caused by the heat rate f l generated by the heat source 1, can be obtained by applying Kennellys principle {see eq. (9.18) in [6]}, as where p = thermal resistivity of the soil, (K.m/W). A8,,, =the temperature rise at the location of the conductor of cable 2 caused by the heat generated by the heat source 1, uninfluenced (index U) by any effect of cable 2 (K). Figure 2. Discretized length N. & of the rated cable with the thermal resistances AT corresponding to the length Az. of the discretization interval. Wg are the conductor joule losses and q is the conductor heat flux. In Figure 2, the thermal resistances with subscripts 1, 2, 3 and 4 are the characteristic quantities for the cable as defined in the IEC 287, [5]. ATL [W(W.m)] is the longitudinal thermal resistance of the conductor and its value per unit length is computed from P T -- L - A where A (m) is the cross-sectional area of the conductor. p is the thermal resistivity of the material (K.m/W). The thermal resistance is the radial directions is given by: T, =T,I n+T2+T3+T4 (7) The network representation in Figure 2 allows us to consider the heat flow in two directions: radial and longitudinal in what essentially is a three dimensional problem. The resulting differential equation is developed in the Appendix and has the following form: AO---=AO,,(Z) 1 d2A8 a2 dz2 where ~e =e-e,, (9) 712 W, . T +AB, +Bomb 1-AW-T (322 = a ' =[TL . (1- AW . T)]/T, (1 1) with aT = conductor temperature Coefficient Of resistance Figure 3. DiscretiUtion of the temperature AB,(z) in ( W Wgo = heat rate in the rated cable at the reference temperature 8, (usually 2OOC) (W/m). de, = temperature rise due to dielectric losses (K) equation (14) in an interval & . At the point of intersection, considering equations (15), (16) and (17), wehave eamb = ambient temperature (K) N can be written in a form of the following hyperbolic function. A general solution of equation (8) for any interval v AB"'(Z =0) =(ea'& - l ) xA Buv e-vcr'& ,=I (18) A&" =AB,,,, +av sinh(a.z)+ bv cosh(a-z) (14) with AB, = O where A),,,, is a discretization of the temperature AB&) in the interval as shown in Figure 3. The incremental temperature rise of the rated cable at the point of intersection is equal to The constants a, and b, are defined by the following AB"'(0) =WITl2 recursive relationships [7]: Thus, the mutual thermal resistance at the point of intersection can be obtained from equation (19) by substituting equations (12) and ( 5) into equation (18) as a, = with -(A',(,,-,) - AB,,).sinh[(v - 1)c&] a, =o (15) ( y , + y 2 ) 2 +(v4z-cosS)2 TI 2 = N 4 =-AB,, + AB,, (e-("-')& - e-"&) +AB,e-N& ( y , - y 2 ) 2 +(v*Az.cosS)2 ,=I b, =bv-l +(ABu(v-lf - AB,,)cosh[(v - l)c&] for v >1 (20) The solutions in the first (v =1) and the last (v =N) Equation (20) can be generalized for several cables crossing the rated cable. Let the rated cable have the designation n and z, be the z-coordinate of the hottest point in cable n. Then, for any other cable k (z =zt ) away from the point z =z, , we have intervals are given by: A8'" =AB,, +b, cosh(a. z) (16) 713 From equations (20) and (1 l), we can observe that the mutual thermal resistance q2 is a function of the heat rate W, . Therefore, an iterative procedure has to be used to evaluate this resistance in conjunction with equation (4). Alternatively, a conservative estimate of the reduced current ip cable 2 can be obtained by substituting the numerator equation (4) by the unaltered temperature A8,,2 comput from equation (5) at the point of intersection ( z =0); that is, If the external heat source is another cable, the most pessimistic result is obtained when the temperature deu,, is computed with W, corresponding to the ampacity of the external circuit being isolated. Note that the assumption that z =0 in equation (5) is equivalent to performing ampadty calculations with the external heat source parallel to the rated cable. 3.2.3 Heating by a steam pipe Equation (4) can also be used to derate a cable being crossed by a steam pipe. To illustrate the procedure, consider the installation shown in Figure 4. The heat generated by the pipe is a function of the surface temperature of the pipe w, =- TR where TR is the thermal resistance of the pipe insulation and the temperatures are shown in Figure 4. The pipe heat rate is influenced by the crossing cable. Therefore, in the first step, the temperature 8, is determined from where OU2] is the influence temperature of the cable on the pipe and T4R is the pipe external thermal resistance. pipe, and this value can be used in equation (4). Equations (23) and (24) give the heat generated in the A practical example the equations developed above is presented in the second part of the paper. REFERENCES I Insulation I External Covering Pipe Figure 4. Steam pipe crossing cable route. [2] Abdel Aziz, E.M., Aboul Zahab and A.A.E. Kassem, Prediction and elimination of hot spots at the crossing regions of H.V. cables, by M.M., IEEE Transactions on Power Delivery, Vol. 3 No.3, July 1988 pp. 845-849. Also presented at the 2nd Int. Conference on Power Cables and Accessories, London, UK, Nov. 26-28, 1986, [3] Z. Iwata, S., Sakuma, M. Dam-Andersen and E. J acobsen Heat pipe local cooling system applied for 145 kV transmission lines in Copenhagen, IEEE Transactions on Power Delivery, Vol. 7, No.2, April 1992, pp. 767-775. A companion paper Installation and Supervision of 145 kV cables in the Copenhagen City has been presented at 1990 CIGRE session, paper No. 21-204. [4] T. Imajo, H. Fukagawa and T. Itoh, Thermal Interference in underground cable heat dissipation by steam pipes and its prevention, presented at the 2nd Int. Conference on Power Cables and Accessories, London, UK, Nov. 26-28, [5] IEC Standard 287, Part 2-1, 1994, Calculation of thermal [6] Anders, G.J., Rating of Electric Power Cables. Ampacify Computations f or Transmission, Distribution and Industrial Applications, IEEE Press, 1997, New York. pp.227-23 1. 1986, pp. 221-226. resistances. [7] Brakelmann, H, Belastbarkeiten der Energiekabef, VDE-Verlag, 1985, Berlin. [l ] H. Orton, A. MacPhail, V. Buchholtz, Elevated Temperature Operation-A Precautionary Note, IEEE PES, Insulated Conductor Committee, Minutes of the 99 Meeting, Houston Texas, April 14-17, 1996, Appendix 5- K-1. 714 APPENDIX Derivation of the Heat Conduction Equation with the Longitudinal Heat Flux The radial temperature at the rated cable is described by the Fourier's law of heat conduction {see eq. (2.1) in [6]}. 1 d 8 W, =--- T, dr Similarly, in longitudinal direction, where T, is defined in equation(7). Consider now a small element of the cable with the length dz, as shown in Figure Al . In the steady-state, from the energy conservation principle {see eq. (2.8) in [6] 1 we have: w, +w' +Wg,drdz =wr+dr +wz+k (A21 where Wgt is the total rate at which energy is generated per unit volume of the body, (W/m3/m). Figure AI An element of the conductor with the length of dz.. Each conduction heat rate on the right-hand side of equation (A2) can then be expressed as a Taylor series expansion where, neglecting higher order terms, Computing derivatives in equations (A3) from equations (Al) and substituting equations (A3) into equation (A2), we obtain The last equation can be rewritten as d28 T, d28 dr2 TL dz2 -- =wgt * T, +-- The first and the second terms in the right-hand-side of equation (A4) represent the temperature rise of the conductor due to the radial and the longitudinal heat fluxes, respectively. The sum of these two temperature components gives the temperature 8 of the conductor Thus, equation (A4) can be rewritten as T, d28 8 = Wgt.T,+-- TL dz2 The first temperature in the right-hand-side of equation (A5) can be obtained from Figure 2 as where the variables are defined in the main body of the paper. The conductor joule losses Wg are temperature dependent. If we assume that the temperature 8,. in equation (A6) is computed with the conductor resistance at the temperature 8, then equation (A5) can be written as 1 d2Ae' A B - T ~ =AO:(z) a dz where A8' =8 -8i2 and a' =,/=and, where for the simplicity of notation, A8i ( z ) =AeUl 2( z) . Observe that if there is no external heat source (the last term in Eq. A7 disappears) and only radial heat flow is considered (the second term on the left-hand-side disappears), we have 8 = , as expected. However, more generally and substituting this into equation (A6) and then into (A5), we obtain equation (8).