and switch-disconnectors
Masterpact Merlin Gerin
52387
Catalogue
Sans titre-1
21/12/01, 9:26
Schneider Electric SA
5, rue Nadar
92506 Rueil-Malmaison Cedex
France
Tel: +33 (0)1 41 29 82 00
Fax:+33 (0)1 47 51 80 20
http://www.schneiderelectric.com
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
ce
document
a thas
imprim
This
document
been printed on ecological paper.
sur du papier cologique.
Created by:
Photos: Schneider
Printing by:
0000 000
Sans titre-1
12-96
21/12/01, 9:26
Masterpact: presentation
035928PC
Many versions
c 3 or 4 poles;
c fixed or drawout versions;
c current-limiting version up to 2500 A;
c wide range of control units offering
multiple functions.
Circuit breakers designed for all
applications
c 1000 V AC version;
c DC version;
c anti-corrosion version;
c source-changeover version;
c merchant-marine and military versions.
Masterpact circuit breakers comply with all
major international standards and meet
T2 tropicalisation criteria.
front face
2
5
1
6
12
13
E28760
c "charged"
charged
c "discharged"
discharged
10
11
c "ON" (I).
E28761
14
OFF
ON
E28791
M63
M50
M40
M08 toM32
M32
M08
IG
LI
G
off
LIG
reset V
push to reset
LG
MERLIN GERIN
masterpact
I
I3
I2
I1
90%
push OFF
I
push ON
STR 58 UE
M32 H1
Ui
1000V
50/60Hz
Ue 380/440V
480/690V
Icu 100kA
85kA
Ics 100kA
85kA
Icw 75kA 1s
50%
IEC 947-2
discharged
20%
%Ir
.92
.95 60
.9
.88
0.8
0.63
90
.98 30
.85
.8
0.5
105
tr
Ir
Io
xIo
xIn
Im
Ir :
t
Ir fault
.2
.1
0
.1
2
on I t off
.2
10
xIo
12
17
22
Im :
480
off
xIn
tr
th :
Ih
600
800
500
Ih
400
Im fault
tm
fault
th
th .4
.4
.3
.3
.2
.1
.1
2
on I t off
1000 .2
320
250
i
+S
1200
Ic1 .9
.8
T+
Ic2.8
.93
.95
.7
.98
.6
.85
.9
.86
.85
test
00000
.3
6 .3
3
2
1.5
O OFF
240
15
at 1,5Ir
tm.4
120
Reduced dimensions
c AC circuit breakers:
v a single frame size from 800 to 3200 A,
v common height and depth from 800 to
6300 A;
c DC circuit breakers:
v common height and length from 1000 to
8000 A for operational voltages of up to 500
V DC,
v common height and length from 1000 to
4000 A for operational voltages greater than
500 V DC.
1
xIr
.95
1
.5
xIr
test
connected
test
disconnected
2
BTP207E-1.010-presentation
Merlin Gerin
21/12/01, 9:34
015159
3
4
6
7
8
10
9
drawout version
1
2
3
4
5
6
7
8
9
10
Merlin Gerin
BTP207E-1.010-presentation
21/12/01, 9:34
E29490
Masterpact: presentation
50%
20%
Io
0.8
0.63
90
.9
xIo
tm
Im
tr
6 .3
.2
2
1.5
.2
.1
I
Ir :
Ir fault
14
12
19
22
Max.
4
2
Ih
xIn
Ih 1200A Max th
th :
th
600
800
500
400
Im fault
tm
fault
0
.1
on I2t off
10
xIr
Im :
tr
320
250
i
overcurrent
test
Ic2
Ic1
.9
.86
.8
.93
.95
.7
.98
.6
xIr
.4
.4
.3
.3
.2
1000 .2
.1
.1
1200
on I2t off
.85
ground
.3
.4
15
at 1.5Ir
.8
xIn
norm
min.
480
.98 30
.85
0.5
240
120
.92
.95 60
.88
%Ir
105
tr
Ir
R
.85
.9
.8
.95
.5
xIr
test
isolation renforce
sparation totale
classe II insulation
double
entre phase
chaque phase
total
separation
dclencheurs voltmtriques
accessibles
l'avant
voltage
releases
accessible from the
front
035929
other possibilities
c Switch version
The switch (unprotected) version is derived
directly from the standard circuit breaker, but
does not implement a control unit (or the
magnetic trip units used with the DC circuit
breakers). Available models are:
v standard: type HI and NI;
v high performance: type HF, equipped with
a protection system that instantaneously
opens the circuit breaker in the event of
closure under fault conditions.
053060
c Earthing switch
A special short-circuit and earthing switch is
available on request for the M08 to M32H
drawout types, 3 or 4 poles. Please consult
us.
common auxiliaries
from 800 A to 6300 A
Auxiliaries
c accessible from the front, mounted in a
separate compartment insulated from power
circuits;
c secured by a single screw;
c adjustment-free;
c can be fitted on site.
c Source changeover system
Four solutions are available:
v mechanical interlocking for 2 or 3 circuit
breakers, adaptable to various sourcechangeover configurations;
v automatic source-changeover controller,
easy to implement on any two suitably
equipped circuit breakers (electrically
charged operating mechanism, etc.) (for 3
circuit breakers, consult us);
v complete assembly including 2 or
3 mechanically (rod assembly) interlocked
circuit breakers, adaptable to various
source-changeover configurations;
v complete assembly including
2 mechanically (rod assembly) interlocked
circuit breakers and an automatic sourcechangeover controller, adaptable to various
source-changeover configurations. Ready
for connection.
053061
053058
4
BTP207E-1.015-presentation
Merlin Gerin
21/12/01, 9:35
86094
DC circuit breakers
86096
Auxiliaries
All the auxiliaries designed for the
Masterpact AC circuit breakers may be used
on the DC versions, with the exception of the
position switches, indicating the connected
(CE), disconnected (CD) and test (CT)
positions.
Auxiliary connections are made via one or
two manually disconnectable plugs that
remain accessible from the front.
Accessories
Standard Masterpact DC range equipment
includes an arc-chute cover (CC) and, on
drawout versions, safety shutters (VO).
Interphase barriers (EIP) are not available
for the DC range.
device identification
M 20 H1
breaking capacity;
c N1: standard;
c H1: H2: high performance;
c L1: current limiting;
c DC: direct current.
rating
c rated current / 100.
family
c Masterpact: LV power air
circuit breaker.
Merlin Gerin
BTP207E-1.015-presentation
21/12/01, 9:35
ease of installation
Masterpact is a complete and rationally
designed range.
c 10 ratings;
c 4 breaking-capacity levels;
c 6 control units;
c a complete range of auxiliaries and
accessories;
c numerous versions (three and four-pole
devices, fixed and drawout versions, etc.).
025179
continuity of service
Masterpact circuit breakers are designed
with continuity of service in mind. The
result is:
c total time discrimination on the N1 and H1
circuit breakers and maximum discrimination
on H2 circuit breakers;
c factory pre-setting of Masterpact circuit
breakers which never require any periodic
maintenance;
c high electrical endurance: 10 000 cycles at
1600 A and 30 cycles at 50 kA, without
maintenance;
c preventive indications: load-shedding
indication switch, long-time threshold
overrun alarm, etc.;
c easy access to the main contacts fitted
with mechanical wear indicators. An optional
function on the STR68 control unit is the
remote indication of contact wear, thus
making possible continuous monitoring of
circuit breakers during their service life.
,
036634
Masterpact: presentation
operating safety
The insulating casing of Masterpact
circuit breakers provides for:
c user safety:
v double insulation on the front face
(class II),
v auxiliary circuits in a compartment
insulated from the power circuits;
c switchboard safety when the circuit
breaker is in the open position:
v each pole is effectively isolated in its own
housing,
v limitation of external disturbances.
Positive contact indication
The position indicator cannot indicate
open unless the poles are effectively
separated by the required distance.
The circuit breakers automatically open
during racking in and out.
reliability
c Masterpact circuit breakers comprise ten
times fewer parts than traditional devices.
They are easier to produce and more
reliable.
c the Masterpact circuit-breaker factory is
certified ISO 9002;
c the design of Masterpact circuit breakers
is modular with delayed differentiation
(highest possible number of common parts
on all models). The result is shorter delivery
times and enhanced reliability.
6
BTP207E-1.020-contents
Merlin Gerin
21/12/01, 9:38
LV power air
circuit breakers and
switch-disconnectors
Masterpact
2/ functions and
characteristics
page
generales characteristics
circuit breaker selection
switch-disconnectors
dimensions an weights
control unit selection
control unit accessories
electrical auxiliaries
mechanical accessories
source changeover systems
0
0
0
0
0
0
0
0
0
BTP207E-2.001-content
21/12/01, 9:39
general characteristics
E29049
MERLIN GERIN
masterpact
M32 H2
Ui
1000V
50/60Hz
Ue 380/440V 480/690V
Icu 100kA
85kA
Ics 100kA
85kA
Icw 75kA 1s
IEC 947-2
IEC 947-2
This standard replaces IEC 157-1,
applicable since 1973.
The circuit breaker selection criteria are
unchanged, but the new standard provides
the user with a better guarantee concerning
quality and performance.
Circuit breakers are subjected to tests that
are more representative of real operating
conditions.
IEC 947-2 also clarifies the notion of
breaking capacity.
c Icu : the ultimate breaking capacity, which
must be greater than or equal to the 3-phase
short-circuit current at the point of
installation of the circuit breaker, a value
unlikely to be reached under real conditions;
c Ics : the service breaking capacity,
generally expressed as a percentage of the
ultimate breaking capacity (25, 50, 75 or
100 % of Icu). It corresponds to a shortcircuit current that is more likely to be
reached under real conditions. The circuit
breaker must continue to operate normally
after having interrupted a current equal to
Ics several times;
c Icw : short-time withstand current for
circuit breakers belonging to category B
(category B refers to circuit breakers with
time discrimination and category A to those
without time discrimination).
Furthermore, IEC 947-2 takes into account
recent technological advances:
c suitability for isolation recognised for
circuit breakers having passed special
electrical and mechanical tests;
c industrial earth-fault circuit breakers
covered by an appendix;
c definition of tests designed to ensure
coordination between two circuit breakers.
tropicalisation
As standard, Masterpact circuit breakers
comply with NF C 63-100 standard level 2
conditions (95 % relative humidity at 45 C
or 80 % at 55 C, hot and humid climate
conditions). They also comply with the
following standards:
c IEC 68-2-30 damp heat;
c IEC 68-2-2 dry heat;
c IEC 68-2-11 salt spray;
c IEC 68-2-1 low temperatures during
storage.
Corrosive atmospheres: Special grease or
other surface coatings available (please
consult us).
pollution degree
Masterpact circuit breakers are certified for
operation in pollution degree IV
environments as defined by
IEC standard 947 (industrial environments).
8
BTP207E-2.020-gen. charact..
Merlin Gerin
21/12/01, 9:40
E18569
035932RC
maximum dependability
installation
Masterpact circuit breakers may be installed
on horizontal metal surfaces or on rails.
They are secured by four points accessible
at the bottom of the chassis (drawout
versions) or on either side of the circuit
breaker (fixed versions). A single door
cut-out is required for the entire range and
provides access to Masterpact controls
(see the description on page 2).
.
degree of protection
E28757
IP 30-5
IP 40-5
IP 54-9
E28763
E28758
Merlin Gerin
BTP207E-2.020-gen. charact..
21/12/01, 9:40
035928
40 C
Ui
Uimp
Ue
AC 50/60 Hz
Icu
AC 50/60 Hz
Ics
Icw
(% Icu)
AC 50/60 Hz
Icm
AC 50/60 Hz
mechanical
with maintenance
no maintenance
no maintenance
electrical
220/415 V
440 V
500/690 V
0.5 s
1s
3s
220/415 V
440 V
500/690 V
440 V - In
690 V - In
690 V
480 V
600 V
instantaneous
distribution
selective
universal
STR 18 M
STR 28 D
STR 38 S
STR 58 U
STR 68 U
drawout
fixed
control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)
6
BTP207E-2.060-M08...16
21/12/01, 9:41
M08
M10
M12
M16
3, 4
3, 4
3, 4
3, 4
800
800
1000
8000
690
1000
1000
1000
8000
690
1250
1250
1000
8000
690
1600
1600
1000
8000
690
N1
N1
H1
H2
L1
N1
H1
H2
L1
40
65
100
130
40
65
100
130
40
65
100
110
40
65
100
110
40
65
85
65
40
65
85
65
100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 %
40
65
65
12
40
65
65
12
30
50
50
12
30
50
50
12
22
32
32
12
22
32
32
12
84
143
220
286
84
143
220
286
84
143
220
242
84
143
220
242
84
143
187
143
84
143
187
143
84
143
143
24
84
143
143
24
B
B
B
B
B
B
B
B
c
c
25 to 30 ms without intentional time delay and 9 ms for type L1
70 ms
20
20
20
20
20
20
20
20
10
10
10
10
10
10
10
10
10
10
10
3
10
10
10
2.7
10
10
10
3
10
10
10
2.7
10
10
10
10
10
10
-
H1
40
40
40
100 %
40
30
22
84
84
84
84
B
c
65
65
65
100 %
65
50
32
143
143
143
143
B
100
100
85
100 %
65
50
32
220
220
187
143
B
130
110
65
100 %
12
12
12
286
242
143
24
B
40
40
40
100 %
40
40
22
84
84
84
84
B
c
65
65
65
100 %
65
50
32
143
143
143
143
B
100
100
85
100 %
65
50
32
220
220
187
143
B
130
110
65
100 %
17
17
12
286
242
143
34
B
20
10
10
10
10
20
10
10
10
10
20
10
10
10
10
15
10
2.5
2.5
-
20
10
10
10
10
20
10
10
10
10
20
10
10
10
10
15
10
2.2
2.2
-
40
40
40
40
65
65
100
65
40
40
65
65
100
65
c
c
c
c
c
c
c
c
c
c
c
c
c
c
65
65
H2
100
65
c
c
c
c
c
L1
N1
H1
40
40
65
65
c
c
c
H2
100
65
c
c
c
c
c
L1
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
7
Merlin Gerin
BTP207E-2.060-M08...16
21/12/01, 9:41
036635
40 C
Ui
Uimp
Ue
AC 50/60 Hz
Icu
AC 50/60 Hz
Ics
Icw
(% Icu)
AC 50/60 Hz
Icm
AC 50/60 Hz
mechanical
with maintenance
no maintenance
no maintenance
electrical
220/415 V
440 V
500/690 V
0.5 s
1s
3s
220/415 V
440 V
500/690 V
440 V - In
690 V - In
690 V
480 V
600 V
instantaneous
distribution
selective
universal
STR 18 M
STR 28 D
STR 38 S
STR 58 U
STR 68 U
drawout
fixed
control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)
8
BTP207E-2.070-M20...63
21/12/01, 9:42
M20
M25
M32
M40
M50
M63
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
2000
2000
1000
8000
690
2500
2500
1000
8000
690
3200
3200
1000
8000
690
4000
4000
1000
8000
690
5000
2500 (5)
1000
8000
690
6300
N1
H1
H2
H1
H2
H1
H2
H1
H2
55
75
100
130
55
75
100
130
75
55
75
100
110
55
75
100
110
75
55
75
85
65
55
75
85
65
75
100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 %
55
75
75
17
55
75
75
17
75
55
75
75
17
55
75
75
17
75
50
57
57
17
50
75
75
17
75
121
165
220
286
121
165
220
286
165
121
165
220
242
121
165
220
242
165
121
165
187
143
121
165
187
143
165
121
165
165
34
121
165
165
34
165
B
B
B
B
B
B
B
B
B
c
c
c
25 to 30 ms without intentional time delay and 9 ms for type L1
70 ms
15
15
15
15
15
15
15
15
15
10
10
10
10
10
10
10
10
10
9
9
9
2
8
8
8
1.8
4
7
7
7
2
6
6
6
1.8
2.6
7
7
7
6
6
6
2.6
100
100
85
100 %
75
75
75
220
220
187
165
B
75
75
75
100 %
75
75
75
165
165
165
165
B
c
100
100
85
100 %
75
75
75
220
220
187
165
B
100
100
85
100 %
100
100
100
220
220
187
220
B
c
150
150
85
100 % (4)
100
100
100
330
330
187
220
B
100
100
85
100 %
100
100
100
220
220
187
220
B
c
150
150
85
100 % (4)
100
100
100
330
330
187
220
B
15
10
4
2.6
2.6
80 ms
10
5
3
2.5
2.5
10
5
3
2.5
2.5
10
5
3
2.5
2.5
10
5
3
2.5
2.5
10
5
2
1.5
1.5
10
5
2
1.5
1.5
55
55
100
75
75
75
100
75
100
100
125
100
100
100
150
100
75
75
H2
100
75
L1
N1
H1
75
75
H2
55
55
100
75
c
c
c
L1
H1
3200
1000
8000
690
75
75
c
c
c
600 to 3200
c
c
c
c
c
c
c
c
c
c
2000 to 4000
c
c
c
c
c
c
c
c
c
c
2000 to 5000
c
c
c
c
c
c
c
c
c
c
2000 to 6300
c
c
c
c
c
c
c
c
c
c
c
c
c
c
rear connections
c
c
c
c (3P only)
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c (3P only)
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
9
Merlin Gerin
BTP207E-2.070-M20...63
21/12/01, 9:42
052380
40 C
Ui
Uimp
Ue
AC 50/60 Hz
Icu
AC 50/60 Hz
Ics
Icw
(% Icu)
AC 50/60 Hz
Icm
AC 50/60 Hz
mechanical
with maintenance
no maintenance
no maintenance
electrical
220/415 V
440 V
500/690 V
1000 V
0.5 s
1s
3s
220/415 V
440 V
500/690 V
1000 V
440 V - In
690 V - In
690 V
instantaneous
distribution
selective
universal
STR 18 M
STR 28 D
STR 38 S
STR 58 U
STR 68 U
drawout
fixed
control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)
Merlin Gerin
10
BTP207E-2.080-M08...32
10
21/12/01, 9:42
M08
M10
M12
M16
M20
M25
M32
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
800
800
1000
8000
1000
1000
1000
1000
8000
1000
1250
1250
1000
8000
1000
1600
1600
1000
8000
1000
2000
2000
1000
8000
1000
2500
2500
1000
8000
1000
3200
3200
1000
8000
1000
H1
H1
H1
H1
H1
H1
H1
65
65
65
65
65
65
65
65
65
65
65
65
45
45
45
45
100 %
100 %
100 %
100 %
45
45
45
45
45
45
45
45
32
32
32
32
95
95
95
95
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
B
B
B
B
c
c
c
c
25 to 30 ms without intentional time delay and 9 ms for type L1
70 ms
20
20
20
20
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
75
75
75
45
100 %
45
45
45
95
165
165
165
165
B
c
75
75
75
45
100 %
45
45
45
95
165
165
165
165
B
c
75
75
75
45
100 %
45
45
45
95
165
165
165
165
B
c
15
10
9
7
7
15
10
8
6
6
15
10
4
2.6
2.6
600 to 3200
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
11
Merlin Gerin
BTP207E-2.080-M08...32
11
21/12/01, 9:42
052384
switch-disconnectors
Masterpact switch-disconnectors
number of poles
In
40 C
Ui
Uimp
Ue
AC 50/60 Hz
type of switch-disconnector
short-time withstand current
(kA rms)
Icw
AC 50/60 Hz
Icm
AC 50/60 Hz
mechanical
with maintenance
no maintenance
no maintenance
Masterpact M10 NI
electrical
0.5 s
1s
3s
440 V
500/690 V
440 V - In
690 V - In
690 V
protection
STR 08 dummy unit (no protection)
STR 18I (protection against short-circuits when closing)
drawout
fixed
control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)
12
BTP207E-2.082-inter M08
12
21/12/01, 9:42
M08
M10
M12
M16
3, 4
3, 4
3, 4
3, 4
800
800
1000
8000
690
1000
1000
1000
8000
690
1250
1250
1000
8000
690
1600
1600
1000
8000
690
NI
HI
HF
NI
HI
HF
NI
HI
HF
NI
HI
HF
40
30
22
84
84
84
c
70 ms
20
10
10
10
10
65
50
32
105
105
143
65
50
32
143
143
143
40
30
22
84
84
84
c
65
50
32
105
105
143
65
50
32
143
143
143
40
30
22
84
84
84
c
65
50
32
105
105
143
65
50
32
143
143
143
40
30
22
84
84
84
c
65
50
32
105
105
143
65
50
32
143
143
143
20
10
10
10
10
20
10
10
10
10
20
10
10
10
10
20
10
10
10
10
20
10
10
10
10
20
10
10
10
10
20
10
10
10
10
20
10
10
10
10
20
10
10
10
10
20
10
10
10
10
20
10
10
10
10
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
13
Merlin Gerin
BTP207E-2.082-inter M08
13
21/12/01, 9:42
052388
switch-disconnectors (cont.)
Masterpact switch-disconnectors
number of poles
In
40 C
Ui
Uimp
Ue
AC 50/60 Hz
type of switch-disconnector
Masterpact M50 HI
Icw
AC 50/60 Hz
Icm
AC 50/60 Hz
mechanical
with maintenance
no maintenance
no maintenance
electrical
0.5 s
1s
3s
440 V
500/690 V
440 V - In
690 V - In
690 V
protection
STR 08 dummy unit (no protection)
STR 18 I (protection against short-circuits when closing)
drawout
fixed
control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)
12
BTP207E-2.084-inter M20
12
21/12/01, 9:43
M20
M25
M32
M40
M50
M63
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
2000
2000
1000
8000
690
2500
2500
1000
8000
690
3200
3200
1000
8000
690
4000
4000
1000
8000
690
5000
2500
1000
8000
690
6300
3200
1000
8000
690
NI
HI
HF
NI
HI
HF
HI
HF
HI
HF
HI
HF
HI
HF
55
55
50
84
84
121
c
70 ms
15
10
9
7
7
75
75
57
105
105
165
75
75
57
165
165
165
55
55
50
84
84
121
c
75
75
75
105
105
165
75
75
75
165
165
165
75
75
75
105
105
165
c
75
75
75
165
165
165
75
75
75
165
165
165
100
100
100
187
187
220
c
100
100
100
220
220
220
100
100
100
187
187
220
c
100
100
100
220
220
220
15
10
9
7
7
15
10
9
7
7
15
10
8
6
6
15
10
8
6
6
15
10
8
6
6
15
10
4
2.6
2.6
15
10
4
2.6
2.6
75
75
75
105
105
165
c
80 ms
10
5
3
2.5
2.5
10
5
3
2.5
2.5
10
5
3
2.5
2.5
10
5
3
2.5
2.5
10
5
2
1.5
1.5
10
5
2
1.5
1.5
c
c
c
c
c
c
c
c
c
c
c
c
rear connections
c
c
c
c (3P only)
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c (3P only)
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
13
Merlin Gerin
BTP207E-2.084-inter M20
13
21/12/01, 9:43
drawout
3P
4P
3P
4P
3P
4P
3P
4P
fixed
maximum weight
(kg)
drawout
fixed
drawout
3P
4P
3P
4P
3P
4P
3P
4P
fixed
maximum weight
(kg)
drawout
fixed
drawout
maximum weight
(kg)
drawout
3P
4P
3P
4P
sensor selection
In (A)
Ir threshold
settings (A)
In (A)
Ir threshold
settings (A)
200
80
to 200
1250
500
to 1250
250
100
to 250
1600
640
to 1600
320
125
to 320
2000
800
to 2000
400
160
to 400
2500
1000
to 2500
500
200
to 500
3000
1200
to 3000
600
240
to 600
3200
1280
to 3200
630
250
to 630
4000
1600
to 4000
800
320
to 800
5000
2000
to 5000
1000
400
to 1000
6000
2400
to 6000
1200
480
to 1200
6300
2500
to 6300
Merlin Gerin
12
BTP207E-2.090-M08...63
12
21/12/01, 9:47
M08
M10
M12
M16
M20
M25
M32
N1/H1/H2/L1
NI/HI/HF
N1/H1/H2/L1
NI/HI/HF
N1/H1/H2/L1
NI/HI/HF
N1/H1/H2 L1
NI/HI/HF
N1/H1/H2 L1
NI/HI/HF
N1/H1/H2 L1
NI/HI/HF
H1/H2
HI/HF
M40
M50
M63
H1/H2
HI/HF
H1/H2
HI/HF
H1/H2
HI/HF
215
230
110
245
265
M08
M10
M12
M16
M20
M25
M32
H1
H1
H1
H1
H1
H1
H1
13
Merlin Gerin
BTP207E-2.090-M08...63
13
21/12/01, 9:47
80
160
400
E31218
1250
1600
2000
2500
3200
4000
5000
6300
STR 18 M
STR 28 D
STR 38 S
STR 58 U
STR 68 U
instantaneous protection
distribution protection
selective protection
universal protection
protection
push to reset
E31219
E30703
STR 18 M
Key:
instantaneous pick-up.
test connector.
STR 18 M
2
5
0
other functions
c fault indication.
I 12 14
8
19
2
22
max
4
xIn
test
Merlin Gerin
14
BTP207E-2.110-unit cont.
14
21/12/01, 9:47
protection
1
push to reset
E31220
E30704
STR 28 D
Key:
2
I1
I2
I3
3
STR 28 D
50%
20%
90
Ir
0.8
%Ir
105
11
Io
0.63
0.5
.88
.9 .92
.95
.85
.98
.8
xIn
xIo
4 5
6
2
8
1.5 xIr 10
3
c
c
c
c
Ir :
Ir
Im :
Ir
noted settings.
10 test connector.
11 holes for sealable cover plate screws.
other functions
Im
90%
fault indication;
indication of LT overrun;
ammeter;
self-monitoring (internal overheating).
Im
i
+
10
test
11
protection
E33950
E31221
STR 38 S
Key:
I2t ON
push to reset
7
I2t OFF
2
I1
I2
I3
90%
12
3
50%
20%
16
Ir
0.8
%Ir
1
0.5
.88
.9 .92
.95
.85
.98
.8
xIn
Im
tm
4 5
2
1.5
.3
8
10
.2
xIr
t
.2
.1
0
.1
on I2t off
9
11
Im :
Ih
fault
th
14
16
max. off
xIn
th :
Ih
T
th
500 600
.4 .4
Im fault
400
tm
800 .3
.3
I
320
1000 .2
.2
.1
250 1200
.1
i
A
on I2t off
overcurrent
+
12
13
c
c
c
c
c
short-time delay.
10 noted settings.
11 instantaneous pick-up.
12 earth fault pick-up.
fault indication;
indication of LT overrun;
ammeter;
self-monitoring (internal overheating);
indication of type of fault (F).
15
test
.4 .3
Ir :
Im
other functions
Ir fault
tr
Ir
1
xIo
10
11
Io
0.63
90
105
13
STR 38 S
ground
F
test
17
19
18
15
Merlin Gerin
BTP207E-2.110-unit cont.
15
21/12/01, 9:47
protection
E31222
E30705
STR 58 U
V
1
push to reset
reset V
I+T L+I
L+I+T
L+T
T
L off
I
Key:
t
I2t ON
8
I2t OFF
9
3
I1
I2
I3
10
90%
14
4
STR 58 U
11
15
50%
21
20%
Ir
Io
0.63
120 240
.9 .92
.95 60
480
.98 30
1
15
.8
xIn
at 1.5Ir
xIo
Max.
Im
tm
4 5
.4 .3
tr
3
.3
6
.2
2
.2
norm
8
.1
0
1.5 10
.1
on I2t off
xIr
I 12 14
Ir :
8
19
Ir fault
4
22
Im :
2 off
tr
xIn
th :
Ih 1200A Max th
T
Ih
500 600
.4 .4
fault
Im fault
400
800 .3
.3
tm
th
320
1000 .2
.2
I
.1
250 1200
.1
i
A
on I2t off
overcurrent Ic1
Ic2
R
+
.9 .93
.8 .85
test
.86
.95 .7
.9
.85
+
.98 .6
.95
ground
1
8 1
.5
xIr
xIr
90
0.8
%Ir
105
7
12
10
16
19
21
24
F
.88
.85
0.5
13
tr
test
Ir
Im
other functions
c
c
c
c
c
c
fault indication;
indication of LT overrun;
ammeter;
self-monitoring (internal overheating);
fault type indication (F);
segregated alarm switch for selected
fault type (V);
c zone selective interlocking (Z);
c load monitoring (R);
c communication (COM).
11
13
14
15
17
18
20
23
22
protection
1
reset
E31223
E33949
STR 68 U
I2t ON
Key:
1
V
N
LT setting
(Ir)
Hz
I2t OFF
Cos
LT time delay
(tr)
kW
MWh
ST pick-up
(Im)
ST time delay
(tm)
STR 68 U
earth fault
pick-up (Ih)
685812
A
KA
S
test
earth fault
time delay (th)
instantaneous
pick-up (I)
Ir
Im
max
other functions
fault
tr
tm
th
Ih
Ir
Im
11
load monitoring
10
8
%
maintenance
trip
no trip
test
MEM
c
c
c
c
c
c
c
+
24 V DC
adjustments
8
Merlin Gerin
16
BTP207E-2.120-unit cont.
16
21/12/01, 9:50
E31225
installation.
Opto-electronic outputs
The use of opto-transistors ensures total
isolation between the internal circuits of the
control unit and the circuits wired by the
user.
I2t ON
I2t OFF
Ih
Th
E26037
Ic2
Ic1
communication: STR 58 U
transmission: STR 68 U
indication and
measurement
17
Merlin Gerin
BTP207E-2.120-unit cont.
17
21/12/01, 9:50
048449
basic protection
long time protection LT
current setting (Ir) as a function of Io and Ir
settings tripping between 1.05 and 1.20 x Ir
time delay (tr)
accuracy: + 0 - 20 %
short-time protection ST
pick-up (Im) adjustable by Im setting
time delay (tm)
Io = In x ...
Ir = Io x ...
tr at 1.5 Ir (s)
tr at 6 Ir (s)
tr at 7.2 Ir (s)
Im = Ir x ...
tm setting with I2t OFF
tm setting with I2t ON
max. overcurrent time before tripping (ms)
max. break time (ms)
instantaneous protection I
pick-up setting
setting range
accuracy
OFF switch on front face
STR 58 U
basic functions
fault indication
for tripping on a fault
for LT setting overrun
self-monitoring
optional functions
N1/H1
22
22
22
17
12
10
8
H2
28
28
24
20
14
12
10
L1
14
10
8
6
6
ammeter (I)
display between 0.2 and 1.20 In
current readings with an accuracy of 1.5 % (1) (3)
bargraph indication of current levels with a resolution of 10 %
self-powered
earth fault protection: residual current (T) or source ground return (W) type on request
pick-up adjustable by Ih setting
Ih = In x ...
time delay (th)
th setting with I2t ON and I2t OFF
max. overcurrent time before tripping (ms)
max. break time (ms)
indication of type of fault (F) (LT - CT/Inst. - Earth) by LEDs on front face
power supply
with battery module
with external power supply by AD module
segregated alarm switch for selected fault type (V) (LT - CT/Inst. - Earth)
output via relay contact
power supply by AD module
zone selective interlocking (Z)
by opto-electronic contact on ST and earth (T/W) fault
load monitoring (R)
adjustment of load limit thresholds by Ic1 and Ic2 settings Ic1 = Ir x ... / Ic2 = Ir x ...
time delay tr1 at 1.5 Ic1
time delay tr2 at 1.5 Ic2
output via opto-electronic contact 0.1 A / 240 V
time delay for load reconnection
communication (COM)
2 outputs for data transmission to Dialpact module
transmitted values
all control unit settings
alarms: Ir warning, fault type, self-monitoring
load monitoring thresholds
current values I1, I2, I3, IN
power supply by AD module
18
BTP207E-2.130-STR1858
18
21/12/01, 9:51
STR 18 M
STR 28 D
STR 38 S
STR 58 U
N1, H1, H2
N1, H1, H2
c
0.5 to 1 (4 settings)
0.8 to 1 (8 settings)
fixed
120
7.5
5.2
c
0.5 to 1 (4 settings)
0.8 to 1 (8 settings)
fixed
120
7.5
5.2
c
1.5 to 10 15 %
0
0.1
0.2
0.3
0.1
0.2
0.3
0
80
140
230
80
140
230
350
c
I = In x ...
fixed at high set (Max) (2)
20 %
on types N1 and H1
c
0.5 to 1 (4 settings)
0.8 to 1 (8 settings)
adjustable
15
30
60
120
0.94 1.88 3.75 7.50
0.65 1.30 2.60 5.20
c
1.5 to 10 15 %
0
0.1 0.2 0.3
0.1 0.2 0.3
0
80
140 230
80
140 230 350
c
I = In x ...
2 x In to Max (2)
15 %
on types N1 and H1
0.4
350
500
240
15
10
480
30
21
0.4
350
500
c
Im = In x ...
2 x In to Max (2)
15 %
on types N1 and H1
c
Im = Ir x ...
1.5 to 10 x Ir
15 %
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
I1, I2, I3, IN, Imax (6)
I1, I2, I3
c
c
I1, I2, I3, IN, Ih, Imax (6)
I1, I2, I3
c
c
0.1 at 1 (max 1200 A) (4) 15 %
0.1
0.2
0.3
0.4
60
140
230
350
140
230
350
500
c
c
c
c
I1, I2, I3, IN, Ih, Imax (6)
I1, I2, I3
c
c
0.1 at 1 (max 1200 A) (4) 15 %
0.1 0.2 0.3 0.4
60
140 230 350
140 230 350 500
c
c
c
c
c
c
0.8 to 1 (8 settings) 1 % (5)
0.5 x tr
0.25 x tr
c
fixed at 10 s
c
c
c
c
c
c
19
Merlin Gerin
BTP207E-2.130-STR1858
19
21/12/01, 9:51
036630
protection
basic functions
c ammeter;
c maintenance indicator;
c fault indications and values of the
interrupted currents;
c self-monitoring: in the event of
overheating of the control unit or a
malfunction of the microprocessor, an alarm
signal is transmitted. Unless the "service
continuity" option was ordered, the circuit
breaker will trip ;
c test.
Merlin Gerin
20
BTP207E-2.140-unit cont.
20
21/12/01, 9:51
optional functions
21
Merlin Gerin
BTP207E-2.140-unit cont.
21
21/12/01, 9:51
STR 68 U
basic protection
long time protection LT
current setting (Ir) adjustable in 2 % steps
tripping
time delay (tr)
accuracy: + 0 - 20 %
Ir = In x ...
tr at 1.5 Ir (s)
tr at 6 Ir (s)
tr at 7.2 Ir (s)
Im = Ir x ...
tm setting with I2t OFF
tm setting with I2t ON
max. overcurrent time before tripping (ms)
max. break time (ms)
c
0.4 to 1 (mini 160 A)
between 1.05 and 1.20 x Ir
adjustable
15
30
60
120 240 480
0.94 1.88 3.75 7.50 15
30
0.65 1.30 2.60 5.20 10
21
standard + OFF position
c
0.4 to 15 10 %
0.1 0.2 0.3 0.4
0.1 0.2 0.3 0.4
60
140 230 350
140 230 350 500
standard
c
M08 to M16 : 65. M20 to M63: 75.
from In to fixed pick-up (mini at 1.6 kA)
15 %
on types N1 and H1
basic functions
fault indication
for tripping on a fault
for Ir setting overrun
indication of fault type
and value of interrupted current
self-monitoring
maintenance indicator
displays degree of wear of main contacts
ammeter
current readings with an accuracy of 3 %
self-powered
integrated test
c
c
c
c
c
c
110 V - 220 V - 380 V AC 50/60 Hz
c
c
between 0 and 655
c
I1. I2. I3. Imax (1)
c
c
22
BTP207E-2.160-STR68U
22
21/12/01, 9:52
optional functions
earth fault protection: residual current (T) or source ground return (W) type on request
pick-up (Ih) adjustable in 2 % steps
Ih = In x ...
time delay (th)
th setting
max. overcurrent time before tripping (ms)
max. break time (ms)
thermal memory (10 mn)
power measurement (P) (see opposite page for details)
output characteristics
integrated power supply
voltage measurements
U12. U23. U31
V1N. V2N. V3N
frequency measurement: f
power factor measurement: cos
instantaneous active power measurement: P
instantaneous active energy measurement: EP
indication and control (M): 31 modules (1 per control unit) providing the following combinations:
load monitoring
option 1: 2 load limit pick-ups Ic1 and Ic2 Ic1 = In x ...
delay tr1 =
Ic2 = In x ...
delay tr2 =
option 2: 1 load limit pick-up Ic1
Ic1 = In x ...
1 load reconnection pick-up Ic2 delay tr1 =
Ic2 = In x ...
delay tr2 =
zone selective interlocking
trip indications
for type of fault
for self-monitoring (1)
transmission
characteristics
type
protocol
speed
max. number of addresses
values transmitted:
type of fault
circuit breaker status
self-monitoring
settings
circuit breaker status
values transmitted:
ammeter
power system status
voltmeter
power factor, frequency
instantaneous active power and energy: P. EP
instantaneous reactive power and energy: Q. EQ
power supply
(1) Depending on the equipment, the "self-monitoring" alarm signal may or may not trip the circuit breaker, see "service continuity" option on the order form.
23
Merlin Gerin
BTP207E-2.160-STR68U
23
21/12/01, 9:52
m01
m02
m03
m04
m05
m06
m07
m08
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
m09
m10
m11
c
c
c
c
c
c
c
c
c
m12
m13
m14
m15
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
m16
c
c
c
c
c
c
c
c
c
c (1)
c
c
m17
m18
m19
m20
m21
m22
m23
m24
m25
m26
m27
m28
m29
m30
m31
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
24
BTP207E-2.170-STR68U
24
21/12/01, 9:52
Factory adjustments
The STR68U control unit is factory adjusted
as follows:
LT
E26042
E26039
operating zones
I2t ON
ST
I2t ON
1
I2t OFF
INST
T
I2t OFF
setting Ir
time delay tr
pick-up Im
time delay tm
pick-up I
earth fault pick-up Ih
time delay th
load monitor
Ic1
Ic2
In
480 s
4 In
0,2 s
maxi
0,2 In
0,1 s
In
In
T1
T2
4
5
0
Ir
Im
overcurrent settings
1 : LT setting Ir (long time)
2 : LT time delay tr (long time)
3 : ST pick-up Im ( short time)
4 : ST time delay tm ( short time)
5 : INST pick-up I (instantaneous)
E26038
E26037
Ic2
Ic2
Ic1
Ic1
Merlin Gerin
BTP207E-2.170-STR68U
25
25
21/12/01, 9:52
048327
048321
025172
025173
025171
047035
052172
This module is equipped with a button for reactivation, of fault indications that have been
de-activated by the battery power-saving
feature. A test button is used to check the
battery status.
Merlin Gerin
26
BTP207E-2.180-unit cont
26
21/12/01, 9:56
self-powered
terminals
battery
no (1)
yes (2)
F1/F2
no
no (1)
no (1)
yes
yes
F1/F2
F1/F2
yes
no
no (1)
yes
F1/F2
no
STR 28 / 58
protection : LT, ST, INST
option I
if I u 20% In
if I < 20% In
or single phase load
option F
option FV
option ALR
option R
option T/W
if Ih u 0.2 x In
if Ih < 0.2 x In
yes
yes
no
no
no
yes
yes
yes
no (3)
STR 68
protection : LT, ST, INST, T, W
yes
27
Merlin Gerin
BTP207E-2.180-unit cont
27
21/12/01, 9:56
013282
auxiliaries
electrical operating
mechanism
Added to the manual charging mechanism,
a motor charges and automatically
recharges the stored-energy spring upon
breaker closing making possible fast
O-C-O cycles.
Opening and closing operations are
instantaneous.
The manual mechanism remains available
for emergency use.
characteristics
power supply 50/60 Hz (V)
consumption (VA)
DC (V)
consumption (W)
motor start-up surge
charging time
14
BTP207E-2.202-circuit-breaker
Merlin Gerin
14
21/12/01, 9:58
035932
operation counter
(CDM)
With gear-motor option only. The operation
counter is read from the front and gives the
total number of breaker operating cycles.
15
Merlin Gerin
BTP207E-2.202-circuit-breaker
15
21/12/01, 9:58
016813
auxiliaries (cont.)
releases
Two types of voltage releases can be used
for remote opening of Masterpact circuit
breakers.
Undervoltage releases
c instantaneous (MN)
This release instantaneously opens the
breaker when its supply voltage drops below
a value between 35 % and 70 % of its rated
voltage.
If the release is not energised, the breaker
cannot be closed (either manually of
electrically). Any attempt to close will have
no effect on the main contacts.
Closing is possible when the release voltage
reaches 85 % of its rated value.
c time delayed (MNR)
To prevent the breaker tripping in the event
of transient voltage dips, this release has a
built-in time delay.
A special version, available on request,
allows instantaneous tripping (from a
mushroom-head emergency off button) by
the wiring of an external contact.
characteristics
breaker response time
at Un
operating thresholds
opening
closing
power supply
AC 50/60 Hz (V)
036051
consumption (VA)
DC (V) (2)
consumption (W)
closing release
XF
70 ms + 10, 15
i 3 200 A
80 ms 10 > 3 200 A
0.7 to 1.1 Un
0.85 to 1.1 Un
Release combinations
Each Masterpact circuit breaker can be
equipped with:
1 MX + 1 MN + 1 XF, or
2 MX + 1 XF
16
BTP207E-2.204-auxiliaries
Merlin Gerin
16
21/12/01, 10:08
016814
"spring charged"
contact (CH)
auxiliary switches
018242
016524
Optional:
This contact simultaneously indicates the
following:
c the breaker is open;
c the stored-energy mechanism is charged;
c the mechanism is correctly reset;
c the breaker opening pushbutton is not
locked;
c no opening order is present.
This contact can be series connected to the
closing release (XF) to disable the antipumping function.
connected/disconnected
position carriage switches
Changeover switches to indicate "connected"
position "CE"
contact characteristics
auxiliary contacts
quantity
DC (A)
L/R i 0.01 s
type
O
changeover
NO
2 NO
NC
2 NC
10
110 V
240 V
10
380 V
6
480 V
6
600 V
3
48 V
3
125 V
0.5
250 V
0.25
500 V
OF
4
OFSUP SDE PF
24
1
1
CE
4
CD
2
CT
1
CH
1
10
15
10
10
10
6
5
3
3
0.5
10
10
10
10
10
10
10
10
6
6
3
3
0.5
0.25
10
5
10
5
10
6
6
3
3
0.5
0.25
10
6
6
3
3
0.5
0.25
10
6
6
3
3
0.5
0.25
17
Merlin Gerin
BTP207E-2.204-auxiliaries
10
6
6
3
3
3
3
0.3 0,3 0.5
0.15 0.15 0.25
17
21/12/01, 10:08
013280
accessories
interphase barrier
(EIP)
035928
016818
560
pole)
etand
560
(4(4
ples)
28518
360
datum
rfrence
a
plan
de fixation
chassis
chssis
fixing
60
18
BTP207E-2.206-accessories
Merlin Gerin
18
21/12/01, 10:09
016819
016814
auxiliaries connection
"Connected/disconnect/test" position
contacts
Installed on the fixed chassis, these contacts
are directly connected by 6.35 mm
connectors.
Fixed version
Connection by one or two plugs,
disconnectable and accessible from the front
(screwless tunnel terminals for flex cable up
to 2.5 mm2).
Drawout version
c standard: connection to a terminal block
in the front of the fixed frame (screwless
tunnel terminals for flex cable up to
2.5 mm2).
The breaker auxiliary circuits are connected
by connection blocks that operate
automatically to isolate the auxiliaries when
the breaker is in "disconnected" position.
On request, an additional 5-way terminal
block (BS) is available to provide five
common points.
c optional: by one or two plugs,
disconnectable and accessible from the
front, installed on the mobile part of the
assembly.
015561
035940
breaker mismatch
protection
Optional: for drawout version only, this
systems allows only correctly matched
breakers (rating, type wiring, etc.) to be
inserted in a given fixed frame.
Two matching parts (1 for the fixed chassis
and 1 for the mobile assembly) can be used
to create 20 different user selected
combinations.
Earth connection
The earth connection terminal (drawout
pattern) is on the left hand side of the
chassis. It is marked with the symbol t
19
Merlin Gerin
BTP207E-2.206-accessories
19
21/12/01, 10:09
035932
accessories (cont.)
VBP
035931
"disconnected",
"connected" and "test"
position locking (1)
Mounted on the frame and accessible with
the cubicle door locked, this system is
available in two versions:
c "disconnected" position locking;
v as standard by 1 padlocking device (1 to 3
padlocks not supplied),
v optional: by a locking device with 1 or 2
Profalux key locks;
c "disconnected", "connected" and "test"
position locking (optional);
v by 1 padlocking device, with 1 to 3
padlocks not supplied (VEC),
v by 1 locking device, with 1 or 2 Profalux
key locks (VSPEC),
padlocks
"disconnected"
standard
"disconnected"
standard
"disconnected"
standard
"disconnected,
connected"
"disconnected,
connected"
"disconnected,
connected"
1 keylock
VSPA1
VSPA2
VSPRAC
VSRA1
VSRA2
VSCA
VSKA
Remarks
c the keylocks are of the captive key type,
i.e. key free when locked;
c Profalux and Ronis keylocks can be used
together;
c a second Profalux or Ronis lock, identical
to the one mounted on the chassis, can be
supplied separately.
2 keylocks
"disconnected"
optional
"disconnected" "disconnected"
optional
optional
"disconnected,
connected"
"disconnected, "disconnected,
connected"
connected"
20
BTP207E-2.208-accessories
Merlin Gerin
20
21/12/01, 10:09
as standard
VSPC1
VSPC2
2 VSPC1
VSPRCC
On request
1 Ronis key lock
2 Ronis key locks, identical profiles
2 Ronis key locks, different profiles
adaptation fixture for Castell key lock (lock not supplied)
adaptation fixture for Kirk key lock (lock not supplied)
adaptation fixture for Trayvou key lock (lock not supplied)
VSRC1
VSRC2
2 VSRC1
VSCC
VSKC
VSTC
VEC
VSEPC
2 VSEPC
On request
1 Ronis key lock
2 Ronis key locks, differents profiles
adaptation fixture for Castell key lock (lock not supplied)
adaptation fixture for Kirk key lock (lock not supplied)
VSERC
2 VSERC
VSECC
VSEKC
016817
door interlock
Optional: mounted on the chassis, this lock
prevents the cubicle door from being opened
when the breaker is in the "connected"
position. If the breaker is put into the
"connected" position with the door open, the
latter can be closed without disconnecting
the breaker.
withdrawal/spring charged
interlock
Optional: this lock prevents withdrawal of
the breaker from the chassis when the
springs are charged.
Incompatible with MN or MNR release.
racking interlock
door interlock
right-hand side
left-hand side
racking interlock
withdrawal/spring charged interlock
a: racking interlock
b: door latch
VPECD
VPECG
VPOC
VEAA
21
Merlin Gerin
BTP207E-2.208-accessories
21
21/12/01, 10:09
053060
025186
053061
053058
Controller
E33079
E33078
3
2
with controller
E33082
MERLIN
N
R
N
UN =
UN =
UR
0,5s
UN
ON /
ON /
OFF
OFF
0,5s
/O
/O
fault
fault
stop
test
manu
R
N
4
6
GERIN
MERLIN
multi
0 . OFF
P25M
GERIN
MERLIN
multi
0 . OFF
660V
2-1
AC3-IEC29
P25M
660V
2-1
AC3-IEC29
Test
B US
Test
MERLIN
IN
GER
N
R
UN =
UN =
generat
or
UR
UN
ON /
ON /
OFF
OFF
I
/O
/O
fault
fault
auto
stop
manu
test
STOP
R
N
5
Merlin Gerin
36
BTP207E-2.220-invers source
36
21/12/01, 10:10
E33080
3
2
E33383
GERIN
MERLIN
multi
0 . OFF
P25M
GERIN
MERLIN
multi
0 . OFF
660V
2-1
AC3-IEC29
P25M
660V
2-1
AC3-IEC29
MERLIN
IN
GER
Test
UN =
UN =
UR
0,5s
Test
UN
ON /
I
ON /
OFF
OFF
0,5s
/O
/O
fault
fault
stop
test
manu
R
N
B US
5
MERLIN
IN
GER
N
R
UN =
UN =
UR
UN
ON /
ON /
OFF
OFF
I
/O
/O
fault
fault
auto
stop
manu
test
STOP
gen
erator
R
N
37
Merlin Gerin
BTP207E-2.220-invers source
37
21/12/01, 10:10
mechanical interlocking by
connecting rods for 2 or 3
stack-mounted breakers
This involves:
c 2 or 3 Masterpact circuit breakers and/or
switch-disconnectors;
c an adaptation fixture on the right side of
each breaker;
c 1 or 2 sets of connecting rods with no-slip
adjustments;
The various parts are mounted by the user.
The changeover system with interlocking by
connecting rods is also available in a version
which is factory mounted on a steel frame.
Maximum distance between fixing
planes: 900 mm.
025186
mechanical interlocking by
cables for 2 side-by-side
breakers
This involves:
c 2 Masterpact circuit breakers and/or
switch-disconnectors;
c an adaptation fixture on the right side of
each breaker;
c a set of cables with no-slip adjustments;
The various parts are mounted by the user.
Distance between fixing planes:
c maximum: 2 000 mm;
c minimum: breaker height with arc chute
cover (see pages ????).
device combinations
Merlin Gerin
38
BTP207E-2.230-invers source
38
21/12/01, 10:11
power circuit
possible combinations
configuration type
cat. No.
Q1
0
0
1
Q2
0
1
0
electrical interlocking
automatic control
with generator set
with permanent "Replacement"
source
685363
Q1
0
1
0
1
0
Q2
0
0
0
1
1
Q3
0
0
1
0
0
Q1
0
1
0
0
Q2
0
0
1
0
Q3
0
0
0
1
electrical interlocking
with lockout after fault
without lockout after fault
688188
688187
Q1
0
1
0
0
1
0
1
Q2
0
0
1
0
1
1
0
Q3
0
0
0
1
0
1
1
electrical interlocking
with lockout after fault
without lockout after fault
automatic control
688189
688190
689651
E30736
Q1
Q2
E30737
Q1
Q2
Q3
E30738
Q1
Q2
Q3
E30739
Q1
Q2
Q3
39
Merlin Gerin
BTP207E-2.230-invers source
688784
688942
39
21/12/01, 10:11
E32704
E32705
Installation
Two possibilities:
c mounted directly on the auxiliaries control
plate ACP.
MERLI
multi
0 . OFF
N GERIN
MERLI
multi
N GERIN
660V
292-1
AC3-IEC
0 . OFF
N GERIN
MERLI
multi
0 . OFF
N GERIN
0 . OFF
660V
292-1
AC3-IEC
P25M
660V
292-1
AC3-IEC
660V
292-1
AC3-IEC
Test
Test
Test
Test
B US
multi
P25M
P25M
MERLI
P25M
RIN
IN GE
MERL
N
R
B US
RIN
IN GE
MERL
N
R
UN =
/O
ON /
OFF
/O
OFF
/O
OFF
/O
UN =
fault
auto
stop
OFF
ON /
ON /
fault
UR
UN
ON /
UN =
UR
UN
manu
UN =
test
STO
genera
tor
R
N
fault
fault
auto
stop
manu
test
tor
P
STO
genera
R
N
customer
connection
Power supply:
Power is supplied by the "Normal" and
"Replacement" sources. The control
voltage for the auxiliaries control plate must
be the same as for the IVE unit and the
motor mechanisms.
Control voltages
c 220 to 240 V 50/60 Hz;
c 380 to 415 V 50/60 Hz - 440 V 60 Hz.
Installation:
The auxiliaries control plate ACP must be
wired to the IVE unit by the customer.
Merlin Gerin
40
BTP207E-2.240-invers source
40
21/12/01, 10:12
053058
controller
Controller UA
controller
BA
UA
4-position switch
automatic operation
forced operation on "Normal" source
forced operation on "Replacement" source
stop (both "Normal" and "Replacement" sources off)
c
c
c
c
c
c
c
c
c
c
c
automatic operation
monitoring of the "Normal" source and automatic changeover
generator set control
load shedding and reconnection of non-priority circuits
changeover to the "Replacement" source if one of the phases of the
"Normal" phase is absent
test
by opening the P25M circuit breaker supplying the controller
by pressing the test button on the front of the controller
c
c
indications
circuit breaker status indication on the front of the controller: on, off,
fault trip, automatic mode indicating contact
automatic mode indicating contract
c
c
c
c
c
c
other functions
selection of type of "Normal" source (single-phase or three-phase)
voluntary transfer to "Replacement" source (e.g. energy management commands)
during peak-tariff periods (energy management commands), forced operation
on "Normal" if "Replacement" source not operational
supplementary control contact (not carried out by the controller). Transfer to
"Replacement" source only if contact closed. (ex: UR frequency control)
setting of maximum startup time for the replacement source
c
c
c
c
power supply
control voltages (1)
options
c
communication option
(1) The same voltage must be used for the ACP plate, the IVE unit and the circuit breaker motor mechanisms. If this voltage is the same as the source voltage, then
the Normal and Replacement sources can be used directly for the power supply. If not, a BC type or equivalent isolation transformer must be used.
Merlin Gerin
BTP207E-2.240-invers source
41
41
21/12/01, 10:12
E30184
controller BA
MERLIN GERIN
compact / masterpact
BA automatism
220/240 V 50/60 Hz
UN
UR
ON/I
ON/I
OFF/O
OFF/O
fault
fault
UN = 0
2 4
t1
1
8 s
15
0.5
0.1 30
0.5s
0.5s
t2
s
stop
manu
reset
15 30
8
60
120
4
0.1 240
UN = I
auto
Electrical characteristics
Power is supplied from the auxiliaries control
plate ACP. The same voltage must be used
to supply the ACP plate, the IVE unit and the
circuit breaker motor mechanisms. If this
voltage is the same as the source voltage,
the "Normal" and "Replacement" sources
can be used directly for the power supply.
If not, a BC type or equivalent isolation
transformer must be used.
Control voltages
c 220 to 240 V 50/60 Hz;
c 380 to 415 V 50/60 Hz - 440 V 60 Hz.
Operation
c a four-position switch can be used to
select:
v automatic operation;
v forced operation on source N;
v forced operation on source R;
v stop (both "Normal" and "Replacement"
sources off);
c adjustment of time delays in front:
v t1 from 0.1 to 30 seconds;
v t2 from 0.1 to 240 seconds;
c circuit breaker status indication on the
front of the controller: on, off, fault trip;
Merlin Gerin
42
BTP207E-2.250-BA
42
21/12/01, 10:12
QN et QR open
off
N
I
operat. on
source N
R
O
"auto"
reset
E27107
E21108
duration a 1 s
QR opens
QN opens
t > 0,5 s
end of reset
t > 0,5 s
QN closes
QR closes
QN ferm
"stop"
operat. on
source N
QR closed
N
O
operat. on
source R
R
I
N
I
R
O
QR opens
t > 0,5 s
QN closed
t > 0,5 s
QR closes
QR closed
operat. on
source R
N
O
R
I
Merlin Gerin
BTP207E-2.250-BA
43
43
21/12/01, 10:12
E30183
053059
Control voltages
c 220 to 240 V 50/60 Hz;
c 380 to 415 V 50/60 Hz - 440 V 60 Hz.
Operation
c a four-position switch can be used to
select:
v automatic operation;
v forced operation on source N;
v forced operation on source R;
v stop (circuit breakers open and manual
operation);
c adjustment of time delays in front:
v t1 from 0.1 to 30 seconds;
v t2 from 0.1 to 240 seconds;
v t3 from 0.5 to 30 seconds;
v t4 from 0.5 to 30 seconds;
v t5 from 60 to 600 seconds;
c circuit breaker status indication on the
front of the controller: on, off, fault trip;
c test button on the front of the controller
to check the transfer from the Normal
source to the "Replacement" source and the
return to the "Normal" source;
MERLIN GERIN
compact / masterpact
UA automatism
220/240 V 50/60 Hz
UN
ON/I
ON/I
OFF/O
OFF/O
fault
fault
stop
manu
reset
auto
test
UR
UN = 0
t4
s
5 10
2
15
20
1
0.5 30
t2
s
15 30
8
60
120
4
0.1 240
240 300
160
360
480
120
60 600
2 4
t1
1
8 s
15
0.5
0.1 30
5 10 t3
2
15 s
20
1
0.5 30
UN = I
t5
s
R
STOP
generator
44
BTP207E-2.260-UA
Merlin Gerin
44
21/12/01, 10:12
E30185
E27107
QN and QR open
stop
"auto"
reset
N
I
operat. on
source N
R
genset off
O
end of reset
genset startup
t > t4
QN closes
QN closed
"stop"
operat. on
source N
t > t3
QR closes
N
I
R
genset off
O
QR closed
R
genset on
I
N
O
operat. on
source R
QN closed
t > t3
genset remains on
QR closes
UN present for t > t5 and no
voluntary switching order received
QR closed
genset off
operat. on
source R
N
O
R
genset on
I
UR absent
action on 4-position switch
45
Merlin Gerin
BTP207E-2.260-UA
45
21/12/01, 10:12
Merlin Gerin
40
BTP207E-3.001-sommaire
40
21/12/01, 10:13
Masterpact
3/ installation
and connection
page
installation
general
safety clearance
fixed circuit breakers M08 to M32
drawout circuit breakers M08 to M32
fixed circuit breaker M40
drawout circuit breaker M40
fixed circuit breaker M50
drawout circuit breaker M50
drawout circuit breaker M63
manual source changeover systems
manual and automatic source
changeover systems
connection
fixed and drawout circuit breakers
M08N/M10N/M12N
fixed and drawout circuit breakers
M08H,L/M10H,L/M12H,L/M16N,H,L
fixed and drawout circuit breakers
M20N,H/M25N,H
fixed and drawout circuit breakers
M20L/M25L/M32H
fixed and drawout circuit breaker M40
fixed and drawout circuit breaker
M08 to M16
fixed and drawout circuit breaker
M50 to M63
wiring diagrams:
c STR 18 M / 28 D / 38 S / 58 U
c STR 28 D / 38 S / 58 U avec options
c STR 68 U avec options m01 m31
c automatic source changeover
c manual source changeover
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
41
BTP207E-3.001-sommaire
41
21/12/01, 10:13
general
installation
E31256
E31254
"Connected" position
26
"Test" position
ample clearance between contacts
E31255
018241
Installation on rails
45
"Disconnected" position
easy withdrawal, short travel
E31257
E29026
E28811
305
"Withdrawn" position
compact dimensions
Merlin Gerin
42
BTP207E-3.200-gnralit
42
21/12/01, 10:14
safety clearance
100
C
A
E31230
100
E31233
E31232
A
B
to insulated barrier
A
B
C
front connection without cover (1) 360
30
0
rear connection without cover 150
30
20
rear connection with cover
0
0
20
to metal parts
A
B
360
70
250
70
0
0
D (2)
0
0
0
95
95
D (2)
0
0
to live bars
A
B
1085
420
1085
420
145
105
495
125
D (2)
0
0
0
100
C
E31231
E31229
213
to insulated barrier
A
B
front connection without cover (1) 300
15
rear connection without cover 150
15
rear connection with cover
0
0
C
0
45
45
to metal parts
A
B
300
50
150
50
0
0
45
45
445
75
43
Merlin Gerin
BTP207E-3.200-gnralit
to live bars
A
B
1000
400
1000
400
60
85
43
21/12/01, 10:14
Masterpact: connection
general
Conductor materials
The terminals of Masterpact circuit breakers
can be used to connect bare copper, tinned
copper or tinned aluminium conductors
without any special surface treatment.
016807
016806
016808
025179
Front connection
electrodynamic forces
Mixed connection.
Upper terminals: front connection.
Bottom terminals: vertical connection.
30
350
50
300
65
250
80
150
150
150
Merlin Gerin
44
BTP207E-3.210-gnralit
100
150
44
21/12/01, 10:16
Note:
The indicated values come from tests and
theoretical calculations made for the
parameters given below. These tables are
intended to serve as a general guide for
connection design and not to replace
experience acquired for a certain type of
connection or the need for subsequent tests.
parameters used in
establishing the tables
E31258
Ta = 40 C
800
1000
1250
1400
1600
1800
2000
2200
2500
2800
3000
3200
3600
4000
4700
5000
5100
5700
6300
M08
M10
M12
M16
M16
M20
M20
M25
M25
M32
M32
M32
M40
M40
M50
M50
M63
M63
M63
Masterpact
Ta = 50 C
number of bars
5 thick bars 10 thick bars
2b.50 x 5
1b.50 x 10
2b.50 x 5
1b.50 x 10
2b.63 x 5
1b.63 x 10
2b.63 x 5
1b.63 x 10
2b.80 x 5
1b.80 x 10
2b.80 x 5
1b.80 x 10
2b.100 x 5
2b.63 x 10
2b.100 x 5
2b.63 x 10
4b.80 x 5
2b.80 x 10
4b.100 x 5
2b.100 x 10
5b.100 x 5
3b.80 x 10
6b.100 x 5
3b.100 x 10
4b.100 x 10
4b.100 x 10
5b.100 x 10
5b.100 x 10
5b.100 x 10
6b.100 x 10
6b.100 x 10
Masterpact
M08
M10
M12
M16
M16
M20
M20
M25
M25
M32
M32
M40
M40
M50
M50
M50
M63
M63
Ta = 60C
number of bars
5 thick bars 10 thick bars
2b.50 x 5
1b.50 x 10
2b.50 x 5
1b.50 x 10
2b.63 x 5
1b.63 x 10
2b.63 x 5
1b.63 x 10
2b.80 x 5
1b.80 x 10
2b.80 x 5
2b.50 x 10
2b.100 x 5
2b.63 x 10
2b.100 x 5
2b.63 x 10
4b.80 x 5
2b.80 x 10
4b.100 x 5
2b.100 x 10
6b.100 x 5
3b.100 x 10
3b.100 x 10
4b.100 x 10
4b.100 x 10
5b.100 x 10
5b.100 x 10
6b.100 x 10
6b.100 x 10
Masterpact
M08
M10
M12
M16
M20
M20
M25
M25
M32
M32
M40
M40
M50
M50
M50
M63
M63
Merlin Gerin
BTP207E-3.210-gnralit
number of bars
5 thick bars 10 thick bars
2b.50 x 5
1b.50 x 10
2b.63 x 5
1b.63 x 10
3b.50 x 5
2b.50 x 10
3b.50 x 5
2b.50 x 10
3b.63 x 5
2b.50 x 10
3b.80 x 5
2b.63 x 10
3b.100 x 5
2b.80 x 10
3b.100 x 5
2b.80 x 10
4b.100 x 5
3b.80 x 10
4b.100 x 5
3b.80 x 10
3b.100 x 10
4b.100 x 10
4b.100 x 10
5b.100 x 10
5b.100 x 10
6b.100 x 10
6b.100 x 10
45
45
21/12/01, 10:16
Masterpact: installation
dimensions
E30742
553
E30749
E30748
3 or 4 poles
438
493
378
90 130
45
311
(*)
(*)
30 mini
60 maxi
150
400
11
68
11
422 (3p)
290
515
11
11
537 (4p)
(*) Datum
mounting
on a base plate
mounting detail
14
E30775
E30766
E30765
on rails
11
150
150
30 mini
60 maxi
A
B
30 mini
60 maxi
3 poles
150
400
2 11 x 6
4 poles
150
515
cut-outs
holes for escutcheon
E30764
E30763
cut-outs de porte
152,5
270
14,5
148,5
(*)
71,5
69
27
37,5
80 mini
80
mini
325
11 5
180
180
17,5
(*)
(*) Datum
Merlin Gerin
48
BTP207E-3.230-M0832
48
21/12/01, 10:17
Masterpact: installation
E30746
3 or 4 poles
"disconnected" position
E30747
dimensions
E30741
45
a
439
800
mini
(*)
60
101
175
55
325
55
128
435 (3p)
85
367
55
425
70
550 (4p)
(*)
(*) Datum
mounting
mounting detail
E30768
E30767
E30775
on rails
on a base plate
14
11
101
175
101
cut-outs
E30761
A
B
175
3 poles
175
325
2 11 x 6
4 poles
175
425
E30760
ACB's side
152,5
270
148,5
71,5
47
55
100
mini
ACB's basis
100
mini
325
Merlin Gerin
BTP207E-3.230-M0832
19
69
18,5
11 5
180
180
17,5
49
49
21/12/01, 10:17
Masterpact: installation
dimensions
E31226
E30752
45
819
E30753
3 or 4 poles
553
759
493
130
311
(*)
(*)
30 mini
60 maxi
150
290
11
515
11
68
537 (3p)
11
780
11
802 (4p)
(*) Datum
mounting
on a base plate
mounting detail
E30775
E30772
E30771
on rails
14
11
150
50 maxi
150
50 maxi
A
B
30 mini
60 maxi
30 mini
60 maxi
3 poles
150
515
2 11 x 6
4 poles
150
780
cut-outs
holes for escutcheon
E30764
E30763
152,5
270
14,5
148,5
(*)
71,5
69
27
37,5
80 mini
80
mini
325
11 5
180
180
17,5
(*)
(*) Datum
Merlin Gerin
50
BTP207E-3.240-M40
50
21/12/01, 10:17
Masterpact: installation
E30743
E30750
3 or 4 poles
"disconnected" position
E30751
dimensions
45
a
439
484
(*)
800
mini
128
(1)
60
101
55
425
70
85
175
550 (3p)
367
60
55
350
350
815 (4p)
(*)
(*) Datum
(1) 4-pole version only.
mounting
on a base plate
mounting detail
E30777
E30773
E30774
on rails
40
40
30
350
150
350
101
101
175
cut-outs
2 11 x 6 (3p)
6 11 x 22 (4p)
175
ACB's side
E30760
E30762
175
(1)
(1)
152,5
270
47
19
45 (1)
55
100
mini
325
ACB's basis
69
18,5
11 5
180
180
17,5
51
Merlin Gerin
BTP207E-3.240-M40
148,5
71,5
51
21/12/01, 10:17
Masterpact: installation
dimensions
E31226
E30752
45
819
E30753
3 or 4 poles
553
759
493
130
311
(*)
(*)
30 mini
60 maxi
150
290
11
515
11
68
537 (3p)
11
780
11
802 (4p)
(*) Datum
mounting
on a base plate
mounting detail
E30775
E30772
E30771
on rails
14
11
150
50 maxi
150
50 maxi
A
B
30 mini
60 maxi
30 mini
60 maxi
3 poles
150
515
2 11 x 6
4 poles
150
780
cut-outs
holes for escutcheon
E30764
E30763
152,5
270
14,5
148,5
(*)
71,5
69
27
37,5
80 mini
80
mini
325
11 5
180
180
17,5
(*)
(*) Datum
Merlin Gerin
50
BTP207E-3.240-M40
50
21/12/01, 10:17
Masterpact: installation
E30743
E30750
3 or 4 poles
"disconnected" position
E30751
dimensions
45
a
439
484
(*)
800
mini
128
(1)
60
101
55
425
70
85
175
550 (3p)
367
60
55
350
350
815 (4p)
(*)
(*) Datum
(1) 4-pole version only.
mounting
on a base plate
mounting detail
E30777
E30773
E30774
on rails
40
40
30
350
150
350
101
101
175
cut-outs
2 11 x 6 (3p)
6 11 x 22 (4p)
175
ACB's side
E30760
E30762
175
(1)
(1)
152,5
270
47
19
45 (1)
55
100
mini
325
ACB's basis
69
18,5
11 5
180
180
17,5
51
Merlin Gerin
BTP207E-3.240-M40
148,5
71,5
51
21/12/01, 10:17
Masterpact: installation
dimensions
90
45
E30757
E30756
E31227
3 poles
819
759
130
311
(*)
(*)
30 mini
60 maxi
150
780
11
68
11
802
290
(*) Datum
mounting
on a base plate
mounting detail
E30775
E30772
E30771
on rails
14
11
150
50 maxi
150
50 maxi
A
B
30 mini
60 maxi
30 mini
60 maxi
2 11 x 6
3 poles
150
780
cut-outs
holes for escutcheon
E30764
E30763
152,5
270
14,5
148,5
(*)
71,5
69
27
37,5
80 mini
80
mini
325
11 5
180
180
17,5
(*)
(*) Datum
Merlin Gerin
52
BTP207E-3.250-M50
52
21/12/01, 10:18
Masterpact: installation
E30744
3 or 4 poles
"disconnected" position
E30755
E30754
dimensions
45
45
a
484
800
mini
(*)
128
60
101
175
60
85
55
350
350
815 (3p)
367
40
475
55
475
1045 (4p)
(*)
(*) Datum
mounting
on a base plate
mounting detail
E31228
E30770
E30769
on rails
40
40
30
350
150
350
175
101
101
175
cut-outs
175
E30762
6 11 x 22 (3p)
6 11 x 33 (4p)
E30760
ACB's side
152,5
270
47
19
45 (1)
55
100
mini
325
ACB's basis
BTP207E-3.250-M50
148,5
71,5
69
18,5
11 5
180
180
17,5
53
53
21/12/01, 10:18
Masterpact: installation
E30745
3 poles or 4 poles
"disconnected" position
E30759
E30758
dimensions
45
45
a
484
800
mini
(*)
128
60
101
175
40
85
55
475
475
1045
367
(*)
(*) Datum
mounting
on a plate
mounting detail
E30778
E30770
E30769
on rails
40
40
30
475
150
475
175
101
101
175
cut-outs
175
side of c.b.
E30760
E30762
6 11 x 33
152,5
270
47
148,5
71,5
19
55
325
45 (1)
18,5
100
mini
11 5
base of c.b.
180
180
17,5
Merlin Gerin
54
BTP207E-3.260-M63+inv sour
69
54
21/12/01, 10:18
Masterpact: installation
source-changeover system
E30779
50
50
5
52
40
30
14
30
125
125
900
max.
900
max.
900
max.
175
153
105
(*)
163
30 base of c.b.
180
30 mini
60 maxi
45
65
166
base of c.b.
for ratings :
M08 to M40 (3p)
base of c.b.
for ratings :
M40 (4p) to M63
(*)
82
(*)
44
(*)
E30781
50
5
40
52
180
60
14
60
14
60
180
900
max.
900
max.
50
50
5
40
52
180
60
180
900
max.
900
max.
153
175
900
max.
105
(*)
163
45
65
166
base of c.b.
for ratings :
M08 to M40 (3p)
base of c.b.
for ratings :
M40 (4p) to M63
100
(*)
30 base of c.b.
180
30 mini
60 maxi
62
(*)
(*) Datum
Merlin Gerin
BTP207E-3.260-M63+inv sour
55
55
21/12/01, 10:18
Masterpact: installation
source-changeover system
200 mini
r= 120 mini
r= 120 mini
10
11 1 2 1 3 1 4 1 5 1 6
E33352
H48
E30784
E33353
mounted on a frame
H47
H43
H49
R
controller
P58
L33
P62
L34
L35
M32(4p)
M40(3p)
M32(3p)
E33354
E33355
2100
P60
1940
H51
1640
H50
H52
940
P61
P59
P63
L36
L37
56
56
56
E33364
E33363
150
56
600
750
C34
C34
Dimensions (mm)
type
C34 H43
140
120
H47
151
H48
137
H49
160
H50
200
H51
255
H52
22
L33
6
L34
48
L35
84
L36
138
L37
150
P58
61,5
P59
170
P61
90
P62 P63
150(min) 187
Merlin Gerin
56
BTP207E-3.270-inv sour+M08N
P60
95
56
21/12/01, 10:19
Masterpact: connection
rear connection
front connection
E30786
E30785
115
115
85
45
12,5
115
25
10
N
(1)
10
25
112
horizontal terminals
15
17
115
E30787
12,5
107
115
85
115
45
23
17,5
(*)
rear connection
132
53
175 (**)
2 12
50
335
25
10
(*)
12,5
221
2 12
10
233
(*)
12,5
vertical terminals
E30788
278
115
115
85
115
10
2 12
(*) Datum.
(*)
rear connection
front connection
E30789
E30790
115
115
115
47,5
80
25 25
12,5
15
N
(1)
3 12
10
(*)
45
rear connection
112
25
92
10
horizontal terminals
112
74,5
115
E30791
306
115
25
12,5
273
300,5
12,5
47,5
45
25
30
175
115
10
15
12,5
2 12
10
(*)
306
vertical terminals
E30792
(*)
115
115
47,5
2 12
(*) Datum.
(*)
BTP207E-3.270-inv sour+M08N
115
57
57
21/12/01, 10:19
Masterpact: connection
E30819
horizontal terminals
100
30
200
112
53
(*)
25
25
25
25 52
15
246
55
306
12,5
15
E30810
horizontal terminals
100
30
112
25 157
25
25
92
137
79,5
12,5
43
25
15
345
363
15
(*)
E30820
horizontal terminals
100
30
112
25 157
25
25
92
137
79,5
12,5
25
43
15
345
363
15
(*)
(*) Datum.
Merlin Gerin
64
BTP207E-3.310-raccord M50-M63
64
21/12/01, 10:22
E30826
E30827
horizontal terminals
248
248
213
248
226
142,5
35
142,5
12
213
10
10
25 25 25
20
13
145
20
12
175
145
(*)
(*)
E30828
E30829
horizontal terminals
252,5
252,5
252,5
252,5
10
12
220
12,5
100
72,5
100
10
25 25 25 45 25 25 25
12
145
(*)
(*)
297,5
vertical terminals
245
245
100
100
12,5
12,5
245
245
100
35
10
220
25 25 25
297,5
E30831
E30830
horizontal terminals
72,5
10
10
12
10
25 25 25 45 25 25 25
12
(1)
70
(*)
(1)
145
(*)
horizontal terminals
E30822
350
350
350
350
117,5
92,5
117,5
10
12
260
10
25 25 25 85 25 25 25
12
(*)
185
(*)
E30824
E30825
horizontal terminals
206
100
287
287
260
260
206
287
12
10
10
25 25 25 85 25 25 25
12
(*)
(1)
(*) Datum.
(1)
70
185
(*)
BTP207E-3.310-raccord M50-M63
117,5
92,5
260
25 25 25
287
35
117,5
65
65
21/12/01, 10:22
Masterpact: connection
E30809
horizontal terminals
100
30
112
252
53
(*)
25
25
25
25
15
243
55
306
12,5
15
(*) Datum.
E30810
horizontal terminals
100
30
112
25 157
25
25
92
137
79,5(4p)
12,5
175
34,5(3p)
15
345
363
15
(*)
(*) Datum.
Merlin Gerin
62
BTP207E-3.300-raccord M40
62
21/12/01, 10:22
180
100
vertical terminals
165
E30812
E30811
horizontal terminals
85
130
25 25 25
172,5
85
35
80
100
25 25 25
172,5
145
10
10
12,5
12,5
12
(*)
12
80
(*)
230
100
vertical terminals
216
165
100
85
130
25 25 25
208,5
172,5
85
35
80
100
25 25 25
230
E30814
E30813
horizontal terminals
80
145
10
10
12,5
12,5
12
12
(1)
(*)
80
(1)
(*)
(*) Datum.
(1) On request, neutral on the right.
E30815
155
vertical terminals
155
100
12,5
E30816
horizontal terminals
65
172,5
35
155
25 25 25
47,5
172,5
10
10
25 25 25 40
12
(*)
12
70
(*)
230
155
191
155
155
100
65
230
E30818
E30817
horizontal terminals
208,5
25 25 25
47,5
35
155
10
10
25 25 25 40
12,5
12
12
(1)
172,5
(*)
70
(1)
(*)
(*) Datum.
(1) On request, neutral on the right.
Merlin Gerin
BTP207E-3.300-raccord M40
63
63
21/12/01, 10:22
Masterpact: connection
rear connection
front connection
115
E30901
E30802
115
85
115
80
25 25
15
15
N
(1)
3 12
100
335
rear connection
112
horizontal terminals
25 162
87
18
12,5
15
18
(*)
221
30
E30803
25
25
53
175 (**)
(*)
30
115
140
115
72,5
85,5
25 25
11,5
15
15
3 12
(*)
236
268
E30804
vertical terminals
115
140
140
60
25
4 12
(*)
(*) Datum.
(**) Hole for securing front connection support bracket.
(1) On request, neutral on the right.
Merlin Gerin
60
BTP207E-3.290-raccorde
60
21/12/01, 10:20
Masterpact: connection
rear connection
front connection
115
E30805
E30806
125
125
37,5
100
25 25 25
12,5
15
N
(1)
30
4 12
(*)
100
rear connection
363
112
115
E30807
92
horizontal terminals
25 157
25
25
125
37,5
100
34,5
37
125
25 25 25
15
329
344
12,5
12,5
4 12
30
(*)
15
344
15
vertical terminals
E30808
(*)
115
152,5
152,5
10
25
4 12
(*)
(*) Datum.
(1) On request, neutral on the right.
Merlin Gerin
BTP207E-3.290-raccorde
61
61
21/12/01, 10:20
Masterpact: connection
front connection
E30793
115
E30901
front connection
115
85
115
80
12,5
25 25
15
N
(1)
10
112
107
15
horizontal terminals
17
17,5
115
E30832
15
(*)
rear connection
132
25
25
53
175 (**)
3 12
80
335
115
115
85
80
25 25
15
(*)
12,5
221
10
233
12,5
(*)
115
85
vertical terminals
115
E30794
278
3 12
115
10
3 12
(*) Datum.
(*)
front connection
E30795
115
E30790
front connection
115
115
47,5
80
25 25
12,5
15
N
(1)
3 12
10
(*)
80
rear connection
306
112
92
15
horizontal terminals
E30796
25 112
25
115
115
115
25 25
30
175
25
12,5
273
300,5
12,5
47,5
80
57
15
15
12,5
3 12
10
(*)
306
vertical terminals
E30797
(*)
115
115
47,5
10
3 12
(*) Datum.
(*)
Merlin Gerin
58
BTP207E-3.280-raccorde
115
58
21/12/01, 10:19
Masterpact: connection
front connection
E30798
E30901
front connection
115
115
80
25 25
12,5
85
115
15
N
(1)
20
335
25
25
152
horizontal terminals
115
E30832
53
115
115
15
18
85
80
15 3
107
(*)
rear connection
112
175 (**)
3 12
80
25 25
17,5
15
12,5
(*)
12,5
221
3 12
16
(*)
233
283
E30799
vertical terminals
115
115
85
115
20
3 12
(*) Datum.
(*)
front connection
E30800
115
E30790
front connection
115
115
47,5
80
25 25
12,5
15
N
(1)
3 12
(*)
20
80
rear connection
306
112
92
15
horizontal terminals
115
E30796
25 112
25
115
115
25 25
30
175
25
12,5
273
300,5
12,5
47,5
80
62
15
15
12,5
3 12
20
(*)
306
vertical terminals
E30801
(*)
115
115
47,5
16
3 12
(*) Datum.
(*)
BTP207E-3.280-raccorde
115
59
59
21/12/01, 10:19
Masterpact: connection
E30721
wiring diagrams
STR 18 M / 28 D / 38 S / 58 U
CHASSIS AUXILIARIES
CN 1
- CN
BREAKER AUXILIARIES
CONTROL UNIT
+
Fu
AT
fault
disconnected
connected
closed
ready
to
close
BPO
BPF
open
springs
charged
314 312 324 322 334 332 344 342 352 354 362 364 372 374
82
84
212 222
234 244
12
14
24
22
32
34
44
42
D4
C12
C2
CE
or
MN
or
MNR
M
MX
XF
MX
OF
F
O
CH
SDE
processing
unit
CD
311
321
331
341
351
361
PF
CT
371
81
211 221
231 241
11
21
31
41
D1
C11
C1
A1
251
B1
Fu
- CN
AT:
BPO:
BPF:
CE:
emergency off
"open" pushbutton
"close" pushbutton
"connected" position contact
(10 A/240 V AC)
M:
spring charging motor
(180 VA/240 V AC)
XF:
closing release
(20 VA/240 V AC)
MX: shunt release (20 VA/240 V AC)
MN: undervoltage release
(20 VA/240 V AC)
MNR: time delayed undervoltage release
(20 VA/240 AC)
OF: auxiliary changeover contacts
(10 A/240 V AC)
O:
2 auxiliary NO contacts
(10 A/240 V AC)
F:
2 auxiliary NC contacts
(10 A/240 V AC)
SDE: fault trip indication contact
(10 A/240 V AC)
CH: charging motor limit switch contact
PF:
"ready to close" contact
(10 A/240 V AC) (closing possible if
breaker is open, not locked and
operating mechanism charged)
CD: "disconnected" position contact
(10 A/240 V AC)
CT:
test posiiton contact
(10 A/240 V AC)
CN2
D4
254
MNR
D1
Merlin Gerin
66
BTP207E-3.320-raccord
262
66
21/12/01, 10:23
Masterpact: connection
E30720
wiring diagrams
STR 28 D / 38 S / 58 U with options
CHASSIS AUXILIARIES
CN 1
- CN
BREAKER AUXILIARIES
CONTROL UNIT
+
Fu
N
P1
S1
P2
S2
AT
(4)
(4)
LR
alarm
disconnected
connected
372
374
362
364
354
342
352
344
332
322
324
334
312
314
(2)
Z11 Z12
LR2
BPF
closed
fault
ready
to
close
BPO
open
springs
charged
Ic1 Ic2
V2
T2 T1
R1 R2
e+ e
82
(5)
84 212 222
234 244
12
14
22
24
32
34
42
44
D4
C12 C2
CE
or
MN
or
MNR
M
MX
XF
MX
OF
F
F
V
CH
SDE
ammeter
ALR
PF
processing
unit
CD
311
321
331
341
351
361
CT
371
Z21
Z22
(3)
LR1
F2 F1
V1
81 211 221
231 241
11
21
41
31
D1
C11 C1
A1
251
B1
power supply
(1)
Fu
AT:
BPO:
BPF:
LR:
CR:
T:
CE:
emergency off
"open" pushbutton
"close" pushbutton
long time trip (LT) indicating lamp
short time trip (ST) indicating lamp
earth fault trip indicating lamp
"connected" position contact
(10 A/240 V AC)
M:
spring charging motor
(180 VA/240 V AC)
R:
load monitoring and control
XF:
closing release (20 VA/240 V AC)
T:
earth fault protection (EZ and SZ:
input and output for zone selective
interlocking)
MX: shunt release (20 VA/240 V AC)
MN: undervoltage release
(20 VA/240 V AC)
MNR: time delayed undervoltage release
(20 VA/240 V AC)
OF: auxiliary changeover contacts
(10 A/240 V AC)
O:
2 auxiliary NC contacts
(10 A/240 V AC)
F:
2 auxiliary NC contacts
(10 A/240 V AC)
SDE: fault trip indication contact
(10 A/240 V AC)
CH: charging motor limit switch contact
F:
fault trip local indicator
FV:
segregated fault trip indication contact
(5 A/240 V AC)
PF:
"ready to close" contact
(10 A/240 V AC) (closing possible if
breaker is open, not locked and
operating mechanism charged)
CD:
CT:
C:
- CN
D4
D1
V contact wiring:
for breaker locking, depending on the
selected fault.
CN1/CN +
BPO
C2
V
V
(1) Power supply terminals for I or T or F options
(AD module with BAT battery module for backup
power).
(2) Zone selective interlocking with line side
breaker.
(3) Zone selective interlocking with load side
breaker (remove jumper).
(4) DC power supply. R contacts reset request
wiring of an external contact.
(5) With Z and/or C options, terminal 84 is not
available.
CN2/CN
MX
C1
Merlin Gerin
BTP207E-3.320-raccord
262
254
MNR
E30719
CN2
67
67
21/12/01, 10:23
Masterpact: connection
E30722
wiring diagrams
STR 68 U
with options m01 to m31
CHASSIS AUXILIARIES
CN 1
- CN
BREAKER AUXILIARIES
CONTROL UNIT
+
Fu
N
P1
S1
P2
S2
AT
(5)
disconnected
connected
closed
ready
to
close
BPO
BPF
open
374
372
362
364
352
354
332
342
334
344
322
324
312
314
springs
charged
T21
T2 T1(3)
T22
234 244
82 212 222
12
14
22
24
32
34
42
44
D4
C12
C2
CE
or
MN
or
MNR
M
MX
XF
MX
OF
F
O
CH
SDE
EZ(4)
M01
to
M16
processing
unit
CD
311
321
331
341
351
361
PF
CT
371
F1 F2
F12 F11 512 522 532 542 552 562
+
power supply (2)
81
211 221
231 241
11
21
31
41
D1
C11
C1
A1
251
B1
E56
E55
E54
E53
E52
E51
MR6
411
412
414
421
422
424
431
432
434
441
442
444
451
452
454
461
462
464
power supply
(1)
E2
Fu
AT:
BPO:
BPF:
CE:
M:
XF:
MX:
MN:
MNR:
OF:
O:
F:
SDE:
CH:
M01:
to
M16
PF:
MR6:
- CN
emergency off
"open" pushbutton
"close" pushbutton
"connected" position contact
(10 A/240 V AC)
spring charging motor
(180 VA/240 V AC)
closing release (20 VA/240 V AC)
shunt release (20 VA/240 V AC)
undervoltage release
(20 VA/240 V AC)
time delayed undervoltage release
(20 VA/240 V AC)
auxiliary changeover contacts
(10 A/240 V AC)
2 auxiliary NO contacts
(10 A/240 V AC)
2 auxiliary NC contacts
(10 A/240 V AC)
fault trip indication contact
(10 A/240 V AC)
charging motor limit switch contact
indication option equipped with
6 opto-decoupled
outputs to contacts (0.2 A/24 V DC),
for programming as per table on
page C54 (EZ: input for earth fault
protection zone selective interlocking)
"ready to close" contact
(10 A/240 V AC) (closing possible if
breaker is open, not locked and
operating mechanism charged)
relay module with 6 changeover
contacts (3 A, 24 V DC)
CD:
CT:
E30718
CN2
D4
254
MNR
D1
68
BTP207E-3.330-raccord
262
68
21/12/01, 10:24
relay outputs
basic version
m01
other versions
m02
m03
m04
m05
m06
m07
m08
m09
m10
m11
m12
m13
m14
m15
m16
transmission
m17
reception outputs m18
m19
m20
m21
m22
m23
m24
m25
m26
m27
m28
m29
m30
m31
terminal number
512
522
LT
ST/Inst.
LT
LT
LT
limit 2
LT
LT
LT
LT
LT
limit 2
LT
limit 1
limit 1
Z
LT
512
ST/Inst.
ST/Inst.
T
T
T
Z
Z
Z
T
ST/Inst.
ST/Inst.
limit 2
shed 2
reconn. 2
shed 1
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST
522
LT
AS
ST/Inst.
AS
Z
AS
limit 1
shed 1
shed 1
limit 1
shed 1
limit 1
shed 1
shed 1
AS
Protection:
LT
long time trip indication
ST/Inst. short time or instantaneous trip
indication
T
earth fault trip indication
Z
zone selective interlocking output
Load monitoring and control:
limit 1
indication of Ic1 setting overrun
limit 2
indication of Ic2 setting overrun
shed 1 load shedding command
according to Ic1 setting (limit 1)
shed 2 load shedding command
according to Ic2 setting
reconn. 2 load reconnection command
according to Ic2 setting (limit 2)
532
542
552
562
shed 1
shed 1
shed 1
shed 1
shed 1
shed 1
limit 1
shed 1
shed 1
shed 1
shed 1
shed 1
shed 1
shed 1
T
5
shed 2
reconn. 1
shed 2
shed 2
reconn. 2
shed 2
Z
shed 2
shed 2
shed 2
reconn. 2
shed 2
shed 2
reconn. 2
AS
limit 1
limit 1
limit 1
limit 1
limit 1
T
T
T
T
T
T
T
T
T
Inst.
1
limit 2
limit 2
AS
AS
AS
limit 1
AS
AS
Z
limit 1
Z
AS
Z
AS
AS
6
data transmission
e+
output
e
output
s+
input
s
input
module
T2
T1
T21
datatransmission
M17
to
M31
processing
unit
T22
e+
r+
self-monitoring:
AS
indication of control unit fault or
overtemperature.
F1
F2
F12 F11
512 522
power supply
(2)
(3)
0V
4
5
8
9
ET 44 interface (1)
(3) S1 (4)
S2 (4)
24V
Sub D9
connector
(5)
(3)
Merlin Gerin
BTP207E-3.330-raccord
RD
TD
RD+
TD+
69
69
21/12/01, 10:24
Masterpact: connection
wiring diagrams
STR 68 U
with options m01 to m31 (cont.)
T2
T1
T21
E30725
E30724
module P
1 3
2 1 3
r
S1
S2
r+ 4
e 3
ET 44
e+ 2
1
2
4
5
8
9
RD
TD Sub D 9
RD+ connector
(6)
TD+
H1
H2
H1
H2
H4
BAT
H4
processing
unit
H3
H3
(4)
M17
to
M31
e+er+ r
Sub D 9
connector
(1)
Sub D 15
connector
module P
F1 F2
F12
N L1 L2 L3
CN1 CN2 H1 H2 H3 H4
(5)
+
power supply
(2)
(3)
Merlin Gerin
70
BTP207E-3.340-raccord
70
21/12/01, 10:24
E30727
control
unit
F1
M01 to M16
option
F2
F11
module
MR6
control
unit
F12
F1
M17 to M31
option
F2
F11
module
ET 44
F12
0V
24V
module
AD
module
AD
E30729
E30730
control
unit
F1
M01 to M16
option
F2
F11
module
MR6
F12
control
unit
F1
F2
M17 to M31
option
F11
F12
module
BAT
module
BAT
module
BAT
module
AD
module
AD
0V
24V
+
module
BAT
module
AD
module
ET44
+
module
AD
E30731
control
unit
F1
module
BAT
F2
M17 to M31
option
F11
F12
module
P
Cn1+
control
unit
module
MR6
F1
module
BAT
F2
M01 to M16
option
F11
module
MR6
F12
module
P
Cn1+
Cn2-
Cn2-
100/240 V 50/60 Hz
24/28 - 125 V CC
100/240 V 50/60 Hz
24/28 - 125 V CC
BTP207E-3.340-raccord
71
71
21/12/01, 10:24
Masterpact: connection
E33097
Version represented:
c 2 sources + 1 coupling;
c 2 circuit breakers closed;
c electrical interlocking with lockout after a
fault (SDE wiring): inoperative with
automatic reset option.
S1
1
0
1
0
1
1
1
0
0
0
1
0
0
0
1
S2
CN1
CN2
D
to A
t1
COUPLING
t2
t3
t4
R1
B4
262
254
252
A4
C2
34
32
84
24
22
82
322
14
12
CE
312
324
B4
262
254
252
A4
C2
34
32
84
24
22
82
322
14
314
CE
XF
12
CE
312
324
B4
262
254
252
A4
C2
34
32
84
24
22
82
322
14
314
CE
R3
12
312
324
314
R2
M
MX
Q1
OF
OF
CE
XF
CE
OF
MX
SDE
QC
OF
OF
XF
OF
CH
MX
SDE
PF
OF
Q2
OF
CH
OF
SDE
PF
Q1:
QC:
Q2:
D:
t1:
Masterpact on source 1
Masterpact used for coupling
Masterpact on source 2
P25M circuit breaker (2 x 10 A)
coupling signal: source 1 failure
(minimum time delay 250 ms)
t2:
coupling signal: source 2 failure
(minimum time delay 250 ms)
t3:
uncoupling signal: source 1
restored (minimum time delay 250
ms)
t4:
uncoupling signal: source 2
restored (minimum time delay 250
ms)
R1,R2,R3: external relays for interlocking of
SDE auxiliary switches.
M:
XF:
MX:
CE:
OF:
SDE:
CH:
PF:
motor mechanism
closing release
shunt release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).
B1
A1
C1
31
81
21
251
Merlin Gerin
88
BTP207E-3.430-raccord
11
321
311
B1
251
A1
C1
31
81
21
11
321
311
B1
251
A1
C1
31
81
21
11
321
311
CH
PF
88
21/12/01, 10:27
Masterpact: connection
E33098
Version represented:
c 2 sources + 1 coupling;
c 2 circuit breakers closed;
c electrical interlocking without lockout after
a fault.
S1
1
0
1
0
1
1
1
0
0
0
1
0
0
0
1
S2
CN1
CN2
D
to A
t1
COUPLING
t2
t3
B4
262
254
252
A4
C2
34
32
24
22
14
322
CE
XF
12
312
324
314
B4
262
254
252
A4
C2
34
32
24
22
14
322
12
CE
312
324
314
B4
262
254
252
A4
C2
34
32
24
22
14
322
12
312
324
314
t4
M
MX
Q1
OF
OF
CE
XF
OF
M
XF
MX
QC
OF
OF
OF
MX
CH
PF
Q2
OF
OF
OF
CH
PF
CH
Q1:
QC:
Q2:
D:
t1:
t2:
t3:
t4:
Masterpact on source 1
Masterpact used for coupling
Masterpact on source 2
P25M circuit breaker (2 x 10 A)
coupling signal: source 1 failure
(minimum time delay 250 ms)
coupling signal: source 2 failure
(minimum time delay 250 ms)
uncoupling signal: source 1
restored (minimum time delay 250
ms)
uncoupling signal: source 2
restored (minimum time delay 250
ms)
M:
XF:
MX:
CE:
OF:
SDE:
CH:
PF:
motor mechanism
closing release
shunt release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).
251
A1
C1
31
21
11
B1
A
Merlin Gerin
BTP207E-3.430-raccord
321
311
B1
251
A1
C1
31
21
11
321
311
B1
251
A1
C1
31
21
11
321
311
PF
89
89
21/12/01, 10:27
Masterpact: connection
E33095
Version represented:
c 3 sources, 1 circuit breaker closed;
c electrical interlocking with lockout after a
fault (SDE wiring).
possible states
source 1
0
source 2
0
source 3
0
S1
S2
1
0
0
0
1
0
0
0
1
S3
CN1
CN2
D
to A
t1
t2
t3
R1
B4
262
254
252
A4
C2
34
32
84
82
22
24
14
322
12
CE
312
324
B4
262
254
252
A4
C2
34
32
24
84
82
22
322
14
314
CE
XF
12
CE
312
324
B4
262
254
252
A4
C2
34
32
24
84
82
22
322
14
314
CE
R3
12
312
324
314
R2
M
MX
Q1
OF
OF
CE
XF
CE
OF
MX
SDE
Q2
OF
OF
XF
OF
CH
MX
SDE
PF
OF
Q3
OF
OF
CH
SDE
PF
B1
251
A1
C1
31
81
21
11
321
311
B1
251
A1
C1
31
81
21
11
321
311
B1
251
A1
C1
31
81
21
11
321
311
CH
PF
Q1:
Q2:
Q3:
D:
t1:
Masterpact on source 1
Masterpact on source 2
Masterpact on source 3
P25M circuit breaker (2 x 10 A)
signal for transfer to source 1
(minimum time delay 250 ms)
t2:
signal for transfer to source 2
(minimum time delay 250 ms)
t3:
signal for transfer to source 3
(minimum time delay 250 ms)
R1,R2,R3: external relays for interlocking of
SDE auxiliary switches.
M:
XF:
MX:
CE:
OF:
SDE:
CH:
PF:
motor mechanism
closing release
shunt release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication
switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).
Merlin Gerin
86
BTP207E-3.420-raccord
86
21/12/01, 10:27
Masterpact: connection
E33096
Version represented:
c 3 sources, 1 circuit breaker closed;
c electrical interlocking without lockout after
a fault.
possible states
source 1
0
source 2
0
source 3
0
S1
S2
1
0
0
0
1
0
0
0
1
S3
CN1
CN2
to A
t1
t2
B4
262
254
252
A4
C2
34
24
32
22
14
322
12
CE
XF
312
324
314
B4
262
254
252
A4
C2
24
34
22
32
14
322
CE
12
312
324
314
B4
262
254
252
A4
C2
24
34
22
32
14
322
12
312
324
314
t3
M
Q1
OF
OF
CE
XF
MX
OF
MX
OF
Q2
OF
XF
M
OF
MX
CH
Q3
PF
OF
OF
OF
CH
PF
B1
251
A1
31
C1
21
11
321
311
B1
A1
251
C1
31
21
11
321
311
B1
A1
251
C1
31
21
11
321
311
CH
PF
Q1:
Q2:
Q3:
D:
t1:
t2:
t3:
Masterpact on source 1
Masterpact on source 2
Masterpact on source 3
P25M circuit breaker (2 x 10 A)
signal for transfer to source 1
(minimum time delay 250 ms)
signal for transfer to source 2
(minimum time delay 250 ms)
signal for transfer to source 3
(minimum time delay 250 ms)
M:
XF:
MX:
CE:
OF:
SDE:
CH:
PF:
motor mechanism
closing release
shunt release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).
Merlin Gerin
BTP207E-3.420-raccord
87
87
21/12/01, 10:27
Masterpact: connection
E33093
Version represented:
c 2 sources + generator set;
c electrical interlocking with lockout after
a fault: inoperative with automatic reset
option;
c with auxiliary source;
c with MN undervoltage release;
c with choice of sources.
possible states
"Normal 1"
0
"Normal 2"
0
"Replacement"
0
1
1
0
0
0
1
1
0
0
0
1
0
N1 N2 R
auxiliary
source
undervoltage relay
to B
U=0
genset fault
contact
OFF
R
N
AUTO
CMa
Fu
Fu
N1
RTn2
N1-2
Fu
N2
RTn3
RX3
Fu
RTn1
RX2
RX1
R1
OF
OF
B4
262
254
252
A4
D4
24
22
14
12
312
314
CE
84
CE
82
CE
XF
QN1
322
324
B4
262
254
252
A4
D4
24
22
14
12
312
314
322
324
CE
84
CE
82
CE
332
334
B4
262
254
252
A4
D4
24
22
14
12
312
84
82
314
322
324
332
334
R2
MN
XF
SDE
CE
CE
MN
OF
QN2
XF
OF
MN
SDE
CH
OF
QR
PF
OF
SDE
CH
PF
CH
B1
251
A1
D1
21
11
81
311
321
B1
251
A1
D1
21
11
81
311
321
331
B1
251
A1
D1
21
11
81
311
321
331
PF
M:
XF:
MN:
CE:
OF:
SDE:
CH:
PF:
motor mechanism
closing release
undervoltage release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication
switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).
Merlin Gerin
84
BTP207E-3.410-raccord
84
21/12/01, 10:26
Masterpact: connection
E33094
Version represented:
c 2 sources + generator set;
c electrical interlocking with lockout after a
fault: inoperative with automatic reset
option;
c with auxiliary source;
c with MN undervoltage release;
c with choice of sources.
possible states
"Normal 1"
0
"Normal 2"
0
"replacement"
0
1
1
0
0
0
1
1
0
0
0
1
0
N1 N2 R
auxiliary
source
undervoltage relay
to B
U=0
genset fault
contact
OFF
R
N
AUTO
CMa
Fu
Fu
N1
RTn2
N1-2
Fu
N2
RTn3
RX3
Fu
RTn1
RX2
RX1
R1
OF
OF
B4
262
254
252
A4
D4
24
22
14
12
312
84
314
CE
82
CE
XF
QN1
322
324
B4
262
254
252
A4
D4
24
22
14
12
84
312
314
CE
82
CE
322
324
B4
262
254
252
A4
D4
24
22
14
12
84
312
314
82
322
324
R2
MN
XF
SDE
CE
CE
MN
QN2
OF
XF
OF
MN
SDE
CH
QR
PF
OF
OF
SDE
CH
PF
CH
B1
251
A1
D1
21
11
81
311
321
B1
251
A1
D1
21
11
81
311
321
B1
251
A1
D1
21
11
81
311
321
PF
M:
XF:
MN:
CE:
OF:
SDE:
CH:
PF:
motor mechanism
closing release
undervoltage release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication
switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).
Merlin Gerin
BTP207E-3.410-raccord
85
85
21/12/01, 10:26
Masterpact: connection
E33091
Version represented:
c 2 Normal sources + 1 Replacement
source;
c electrical interlocking with lockout after a
fault (SDE wiring): inoperative with
automatic reset option.
possible states
"Normal 1"
0
"Normal 2"
0
"Replacement"
0
N1
N2
0
0
1
1
0
0
0
1
0
1
1
0
R
CN1
CN2
D
to A
t1
t2
R1 (1)
QN1
OF
M
OF
B4
262
254
XF
MX
QN2
252
CE
XF
OF
SDE
A4
C2
24
22
84
82
312
CE
M
14
XF
MX
12
314
B4
262
254
252
A4
C2
24
22
84
82
312
14
CE
12
314
B4
262
254
252
A4
C2
24
22
84
82
312
14
12
314
R2 (1)
OF
MX
CH
SDE
PF
QR
OF
CH
OF
SDE
PF
CH
B1
251
A1
C1
21
81
11
311
B1
251
A1
C1
21
81
11
311
B1
251
A1
C1
21
81
11
311
PF
M:
XF:
MX:
CE:
OF:
SDE:
CH:
PF:
motor mechanism
closing release
shunt release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).
Merlin Gerin
82
BTP207E-3.400-raccord
82
21/12/01, 10:26
Masterpact: connection
E33092
Version represented:
c 2 Normal sources + 1 Replacement
source;
c electrical interlocking without lockout after
a fault.
possible states
"Normal 1"
0
"Normal 2"
0
"Replacement"
0
N1
N2
1
1
0
0
0
1
1
0
0
0
1
0
CN1
CN2
D
to A
t1
B4
262
254
252
A4
C2
24
22
14
312
CE
XF
12
314
B4
262
254
252
A4
C2
24
22
14
312
CE
12
314
B4
262
254
252
A4
C2
24
22
14
312
12
314
t2
M
QN1
OF
CE
XF
MX
OF
M
XF
MX
QN2
OF
OF
M
MX
CH
QR
PF
OF
OF
CH
PF
CH
B1
251
A1
C1
21
11
311
B1
251
A1
C1
21
11
311
B1
251
A1
C1
21
11
311
PF
M: motor mechanism
XF: closing release
MX: shunt release
CE: connected position switch
OF: auxiliary changeover switch
SDE: overcurrent fault-trip indication switch
CH: springs charged switch
PF: ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).
Merlin Gerin
BTP207E-3.400-raccord
83
83
21/12/01, 10:26
Masterpact: connection
Version represented:
c with generator set;
c with lockout after a fault (SDE wiring):
v inoperative with automatic reset option,
v if lockout after a fault is not required, the
SDE must be shorted on both breakers;
possible states
"Normal"
0
"Replacement"
0
E33089
1
0
0
1
R
genset startup signal
auxiliary
source
unvoltage relay
U=0
to B
genset fault
contact
C
OFF
STANDBY
N
AUTO
Fu
RTn2
RX3
RTn1
Fu
RX1
CE
XF
B4
262
254
252
A4
D1
24
22
14
12
84
312
82
CE
322
314
B4
262
254
252
A4
D1
24
22
14
12
312
84
324
CE
82
322
314
324
RX2
CE
M
XF
MN
QN
OF
OF
M
MN
SDE
QR
OF
CH
OF
SDE
PF
CH
B1
251
A1
D4
21
11
81
311
321
B1
251
A1
D4
21
11
81
311
321
PF
QN:
QR:
D:
C:
FU:
Rtn1:
Rtn2:
RX1:
RX2:
RX3:
M:
XF:
MN:
CE:
OF:
SDE:
CH:
PF:
motor mechanism
closing release
undervoltage release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).
Merlin Gerin
80
BTP207E-3.390-raccord
80
21/12/01, 10:26
Masterpact: connection
E33090
Version represented:
c with permanent Replacement source;
c with lockout after a fault (SDE wiring):
v inoperative with automatic reset option,
v if lockout after a fault is not required, the
SDE must be shorted;
possible states
"Normal"
0
"Replacement"
0
1
0
0
1
R
auxiliary
source
D
to B
C
N
STANDBY AUTO
OFF
Fu
RTn2
RTn1
Fu
Fu
RTn3
RX1
Fu
CE
XF
B4
262
254
252
A4
D1
24
22
14
12
84
312
82
CE
322
314
B4
262
254
252
A4
24
D1
22
14
12
312
84
324
CE
82
322
314
324
RX2
CE
M
XF
MN
QN
OF
OF
M
MN
SDE
OF
QR
CH
OF
SDE
PF
CH
B1
251
A1
D4
21
11
81
311
321
B1
251
A1
D4
21
11
81
311
321
PF
QN:
QR:
CE:
M:
XF:
MN:
OF:
SDE:
CH:
PF:
Merlin Gerin
BTP207E-3.390-raccord
81
81
21/12/01, 10:26
Masterpact: connection
E27121
BA operation
I
O
I
UR
O
I
KR
O
UN or KT
I
O
I
QR
O
QN
T1
0,130 s
500 ms
250 ms
T2
0,1240 s
500 ms
250 ms
UA operation
E30189
UN or KT
I
O
UR
KR
I
O
I
O
KG
I
O
SH I
O
QN I
O
QR I
O
T1
0,1...30s
120-180s
Inputs
UN : normal-source voltage
UR : replacement-source voltage
KT : forced operation on replacementsource control signal
KR : additional check before transfer.
T3
0,5...30s
T2
10...240s
T4
0,5...30s
T5
60...600s
Legend
c O position: circuit open
c I position: circuit closed
: no effect O or I.
c
Outputs
KG : engine-generator set control signal
SH : load-shedding control signal
QN : normal-source Masterpact
QR : replacement-source Masterpact.
Merlin Gerin
78
BTP207E-3.380-raccord
78
21/12/01, 10:25
Masterpact: connection
E33088
possible states
"Normal"
0
"Replacement"
0
CONTROL PRINCIPLE
1
0
CN1
control
voltage
CN2
F1 (1)
0
1
F2 (1)
D
to B
to A
to C
fault
RTs
closed
fault
closed
RTn
open
open
B4
262
254
252
A4
C2
24
22
14
(2)
12
84
82
314
CE
312
B4
262
254
252
A4
C2
24
22
14
(2)
F4 (1)
12
84
82
314
312
F3 (1)
CE
XF
M
XF
MX
QN
OF
OF
M
MX
SDE
QR
OF
CH
OF
SDE
PF
CH
B1
251
A1
C1
21
11
81
311
B1
251
A1
C1
21
11
81
311
PF
B
A
M: motor mechanism
XF: closing release
MX: shunt release
CE: connected position switch
OF: auxiliary changeover switch
SDE:overcurrent fault-trip indication switch
CH: springs charged switch
PF: ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).
Merlin Gerin
BTP207E-3.380-raccord
79
79
21/12/01, 10:25
Masterpact: connection
1
0
0
1
(1)
(1)
WH
VT
BK
RD
GN
possible states
"Normal"
0
"Replacement"
0
IVE
XF
WH
B4
262
254
252
A4
C2
VT
BK
84
82
GN
RD
14
CE
312
314
(3)
12
B4
262
254
252
A4
C2
84
82
312
14
12
314
(3)
CE
MX
OF
XF
SDE
OF
SDE
CH
251
A1
C1
81
11
311
GY
YE
(2)
BN
BN
(3)
CH
B1
A1
251
C1
(2)
YE
(3)
81
311
11
PF
B1
PF
MX
QR
GY
QN
Merlin Gerin
72
BTP207E-3.350-raccord
72
21/12/01, 10:25
E33075
controller UA
Q1
E33076
UA
genset
startup
Q2
23 22 27 26 28 30 29 31
ACP
24
load
shedding
10
load
shedding
25
load reconnection
genset
startup
genset shutdown
24
E33077
BatiBUS option
25
23 22
controller status
indication
BatiBUS
loop
BatiBUS
loop
0V
24V
17 18 20
BA/UA
24V 0V
21
supplementary
control contact
NR
voluntary transfer
command (e.j. for
energy management)
11 12
13 14 15 16 10
UA
11 12 13 14 15 16
IVE
R
1
10
Merlin Gerin
BTP207E-3.350-raccord
73
73
21/12/01, 10:25
Masterpact: connection
E33099
Version represented:
c 2 sources + 1 coupling;
c 2 circuit breakers closed;
c electrical interlocking with lockout after a
fault: inoperative with automatic reset
option.
S1
0
1
0
0
0
1
1
1
0
0
1
1
1
0
1
S2
CMa
permanent
OFF
auto
Fu
RTn1
RTn2
Fu
Fu
CMb
RTn3
COUPLER
N1+C
N1+N2
N2+C
RTn4
Fu
RX1
Fu
RX2
Fu
B4
262
254
252
A4
C2
24
22
14
12
84
312
82
CE
322
314
B4
262
254
252
A4
C2
24
22
14
12
312
84
324
CE
XF
82
CE
322
314
324
B4
262
254
252
A4
C2
24
22
14
12
84
82
322
314
CE
312
324
RX3
M
OF
CE
XF
MX
OF
CE
M
XF
MX
SDE
OF
OF
M
MX
CH
SDE
PF
OF
CH
OF
SDE
PF
CH
Q1:
QC:
Q2:
Cma:
FU:
Rtn1:
Rtn2:
Rtn3:
Rtn4:
Cmb:
RX1:
RX2:
RX3:
Masterpact on source 1
Masterpact used for coupling
Masterpact on source 2
3-position switch
fuses
voltage relay with 10 to 180 s time
delay
voltage relay with 0.1 to 30 s time
delay
voltage relay with 10 to 180 s time
delay
voltage relay with 0.1 to 30 s time
delay
coupling selection switch
relay with 0.25 s time delay
relay with 0.25 s time delay
relay with 0.25 s time delay
M:
XF:
MX:
CE:
OF:
SDE:
CH:
PF:
motor mechanism
closing release
shunt release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication
switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).
B1
251
A1
C1
21
11
Merlin Gerin
90
BTP207E-3.440-raccord
81
311
321
B1
251
A1
C1
21
11
81
311
321
B1
251
A1
C1
21
11
81
311
321
PF
90
21/12/01, 10:28
LV power air
circuit breakers
and switch-disconnectors
Masterpact
4/ complementary technical
information
page
tripping curves
effect of ambient temperature
0
0
77
BTP207E-4.001-sommaire
77
21/12/01, 10:29
E30715
Ir = 0,41 x In
2000
Ic1 = 0,21 x In
1000
Ic2 = 0,21 x In
500
tr = 15480s
200
tr1 = tr / 2
100
tr2 = tr / 4
50
20
10
5
t(s)
2
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.05 .06
.08
.1
.2
.3
.4
.5 .6
.8
8 10
20
30
x In
In: CT rating
Ir: LT protection current setting (delay: tr)
Merlin Gerin
86
BTP207E-4.100-courbe dcl
86
21/12/01, 10:32
E30717
Ir = 0,41 x In
2000
Ic1 = 0,21 x In
1000
Ic2 = 0,21 x In
500
tr = 15480s
200
tr1 = tr / 2
100
50
20
tr2 = 60s
10
5
t(s)
2
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.05.06
.08 .1
.2
.3
.4
.5 .6
.8
5 6
10
20
30
x In
Ic1: load-shedding pick-up (delay: tr1)
Ic2: load-reconnection pick-up 2 (delay: tr2)
Merlin Gerin
BTP207E-4.100-courbe dcl
87
87
21/12/01, 10:32
E30714
STR 68 U
10000
5000
Ir = 0,4 1 x In
2000
tr = 15480s
1000
500
200
100
50
20
10
5
t(s)
I2t ON
Im = 0,4 15 x In
1
.5
.2
.1
I2t OFF
0,4
0,4
0,3
0,3
0,2
0,2
0,1
0,1
.05
I (*)
.02
.01
.005
.002
.001
.5 .6
.8 1
10
30
20
40 50 60
80 100
x In
200
300
kA
(*)I
In (A)
800
1000
type H2 : I =
type H1 : I =
type L1 : I =
1,6 kA ... 65 kA
In ou 1,6 kA ... 50 kA
1,6 kA ... 11 kA
1250
1600
2000
2500
3200
5000
6000
In ... 75 kA
In ... 15 kA
Merlin Gerin
84
BTP207E-4.090-courbe dcl
4000
84
21/12/01, 10:31
10000
5000
2000
Ih = 0,21 x In
Max. 1200A
1000
500
200
100
50
20
10
5
t(s)
2
1
.5
0,4
0,3
.2
0,2
.1
0,1
.05
.02
.01
.005
.002
.001
.05 .06
.08 .1
.2
.3
.4
.5 .6
.8
5 6
10
20
30
x In
In: CT rating
Ir: LT protection current setting (delay: tr)
Im: ST protection pick-up (delay: tm)
INST: instantaneous protection pick-up
Merlin Gerin
BTP207E-4.090-courbe dcl
85
85
21/12/01, 10:31
10000
5000
2000
Ih = 0,11 x In
Max 1200A
1000
500
200
100
50
20
10
5
t(s)
I2t ON
2
1
.5
0,4
0,3
.2
0,2
I2t OFF
.1
0,1
.05
.02
.01
.005
.002
.001
.05 .06
.08 .1
.2
.3
.4
.5 .6
.8
10
20
30
x In
In: CT rating
Ih: earth fault protection pick-up (delay: th)
Merlin Gerin
82
BTP207E-4.080-courbe dcl
82
21/12/01, 10:31
E30710
Ir = 0,41 x In
2000
Ic1 = 0,81 x Ir
1000
Ic2 = 0,51 x Ir
500
tr1 = tr / 2
200
tr2 = tr / 4
100
50
20
10
5
t(s)
2
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.05 .06
.08 .1
.2
.3
.4
.5 .6
.8
5 6
10
20
30
x In
Ir: LT protection current setting (delay: tr)
Ic1: load-shedding pick-up 1 (delay: tr1)
Ic2: load-shedding pick-up 2 (delay: tr2)
Merlin Gerin
BTP207E-4.080-courbe dcl
83
83
21/12/01, 10:31
E30711
STR 38 S
10000
5000
Ir = 0,4 1 x In
2000
1000
500
200
100
50
20
10
5
t(s)
Inst (*)
I2t ON
Im = 1,5 10 x Ir
1
.5
0,4
.2
I2t OFF
.1
0,3
0,3
0,2
0,2
0,1
0,1
.05
.02
0
.01
.005
.002
.001
.5 .6
.8
5 6
10
20
5 6
8 10
20
30
x In
x Ir
(*)Inst
In (A)
630
800/1000
1200/1600
2000
2500
3000/3200
4000/5000/6300
I = In x ... (N-H)
28
28
24
20
14
12
10
I = In x ... (L)
14
10
Merlin Gerin
80
BTP207E-4.070-courbe dcl
80
21/12/01, 10:30
E30712
STR 58 U
10000
5000
Ir = 0,4 1 x In
2000
tr = 15480s
1000
500
200
100
50
20
10
5
t(s)
Im = 1,5 10 x Ir
I2t ON
2
1
.5
0,4
0,3
.2
2
I t OFF
.1
0,3
0,2
0,2
0,1
0,1
.05
0
I = 2 x InMax (*)
.02
.01
.005
.002
.001
.5 .6
.8
5 6
10
20
5 6
10
20
30
x In
x Ir
(*)Max
In (A)
630
800/1000
1200/1600
2000
2500
3000/3200
4000/5000/6300
28
28
24
20
14
12
10
14
10
Merlin Gerin
BTP207E-4.070-courbe dcl
81
81
21/12/01, 10:30
tripping curves
E30708
STR 18 M
10000
5000
2000
1000
500
200
100
50
20
I = 2 x In Max (*)
10
5
t(s)
2
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.5 .6
.8
8 10
20
30
40 50 60
80 100
200
300
x In
(*)Max
In (A)
630
800/1000
1200/1600
2000
2500
3000/3200
4000/5000/6300
Max = In x ...
28
28
24
20
14
12
10
Merlin Gerin
78
BTP207E-4.060-courbe dcl
78
21/12/01, 10:30
E30709
STR 28 D
10000
5000
Ir = 0,4 1 x In
2000
1000
500
200
100
50
20
10
5
t(s)
Im = 1,5 10 x Ir
Inst (*)
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.5 .6
.8
5 6
10
20
x Ir
5 6
10
20
30
x In
BTP207E-4.060-courbe dcl
79
79
21/12/01, 10:30
ambient temperature
M12H
M12L
M16N/H M16L
M20N/H M20L
M25N/H M25L
M32H
M40H
M50H
M63H
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 600
1 600
1 600
1 600
1 550
1 600
1 600
1 600
1 600
1 550
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 500
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
2 000
2 000
2 000
2 000
1 900
2 000
2 000
2 000
2 000
1 900
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
1 900
2 000
2 000
2 000
2 000
1 900
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 500
2 500
2 430
2 350
2 250
2 500
2 500
2 500
2 500
2 400
2 500
2 500
2 500
2 500
2 500
2 500
2 500
2 500
2 500
2 500
2 500
2 350
2 250
2 150
2 000
2 500
2 500
2 500
2 350
2 200
2 500
2 500
2 500
2 500
2 300
2 500
2 500
2 500
2 500
2 500
3 150
3 080
3 000
2 900
2 800
3 200
3 200
3 100
3 000
2 900
3 200
3 200
3 200
3 200
3 100
3 200
3 200
3 200
3 200
3 100
3 800
3 650
3 500
3 300
3 100
4 000
3 800
3 600
3 400
3 200
4 000
4 000
4 000
3 900
3 800
4 000
4 000
4 000
4 000
3 900
5 000
4 750
4 500
4 250
4 000
5 000
5 000
5 000
5 000
4 700
5 000
5 000
5 000
5 000
5 000
5 000
5 000
5 000
5 000
5 000
6 000
5 700
5 400
5 100
4 800
6 300
6 000
5 700
5 400
5 100
230
100
32
16
360
150
50
36
390
170
32
16
460
220
31
12
365
180
18
9
500
250
23
10
520
260
17
8
780
390
23
10
803
500
15
10
1 250
780
15
10
1 150
700
9
8
1 200
Merlin Gerin
88
BTP207E-4.110-dclassement
88
21/12/01, 10:32
Merlin Gerin
BTP207E-4.110-dclassement
89
89
21/12/01, 10:32