Вы находитесь на странице: 1из 2

LeakControl

Continuous fow monitoring


with ultrasonic sensors
Data transmission for continuous
network monitoring
Quick allocation of a leak to
a particular network area
Installation without supply inter-
ruption orchamber construction
Special features
LeakControl enables the continuous fow monitoring
of a pipe network section (DMA District Metering
Area) through the use of ultrasonics. Since the
sensors are simply attached to the outside of the
pipe, installation can be carried out without
interrupting the water supply. In addition, LeakControl
is completely maintenance-free after set-up.
For electricity supply, cables which have already
been laid (e. g. for street lighting) can be used. These
charge a battery which enables measurements to be
carried out even during the day. The collected data
is sent via GSM modem or SMS directly to a PC or
laptop.
Using the provided software, the data can be easily
read and evaluated. An alarm function and threshold
setting function are included, so you can react
quickly and effciently in emergencies. LeakControl
also supports remote maintenance and remote
confguration via GSM, so that once LeakControl
has been installed, it can be easily controlled and
maintained from the head offce.
Description
Simple and inexpensive installation without chamber construction
Professional above-ground installation of the telemetry unit
We reserve the right to make technical changes. dat_leakcontrol_en_140108.pdf ISO 9001:2008
LeakControl
Technical data
Operating range Up to DN 1400
Power supply
230 V external; battery operation
possible
Battery power 4 hours
UPS 24 hours
Data transmission GSM
Operating temperature -30 C to +100 C
Sensors M5 and Q5
Protection class
Sensors IP 68
Distribution box IP 43 II
SebaKMT Dr.-Herbert-Iann-Str.6 96148 Baunach/Germany
Tel. +49
(
0
)
9544 - 680 Fax +49
(
0
)
9544 - 2273
sales@sebakmt.com www.sebakmt.com
High-resolution monitoring of fow for better network analysis
Measurement range of the sensors
Flow speed 0.01 m/s 25 m/s
Resolution 0.025 cm/s
Reproducibility 0.25% of measured value 1 cm/s
Volumetric fow 2% of measured value 1 cm/s
Dimensions
Distribution box without
base
350 x 272 x 1300 mm
Distribution box with
base
350 x 272 x 1700 mm
Infow measurement (stationary + continuous)
Infow measurement
(stationary + continuous)
Tank outfow measurements
Division of the supply structure
intonetwork areas
Simultaneous monitoring of the fows
inall areas
Concentration on problem zones
andlarger network areas
Water tank