Bull Earthquake Eng (2013) 11:24292446

DOI 10.1007/s10518-013-9474-z
ORIGINAL RESEARCH PAPER
On the dimensioning of viscous dampers for the
mitigation of the earthquake-induced effects in
moment-resisting frame structures
Michele Palermo Saverio Muscio Stefano Silvestri
Luca Landi Tomaso Trombetti
Received: 11 December 2012 / Accepted: 23 June 2013 / Published online: 5 July 2013
Springer Science+Business Media Dordrecht 2013
Abstract The effectiveness of viscous dampers in mitigating the seismic excitation impacts
upon building structures has been widely proved. Recently, with reference to the specic case
of equal mass, equal stiffness, shear-type structures, the authors developed a direct practical
procedure which gives the mechanical characteristics of the manufactured viscous dampers
capable of providing the frame structure with a prescribed value of the rst damping ratio. In
this paper, a comprehensive rational framework is presented, which allows to formally extend
the validity of the proposed procedure to the more realistic case of a generic moment-resisting
frame structure. Also the inuence of various lateral stiffness distributions is investigated.
Keywords Moment-resisting frame structures Added viscous dampers Design
procedure Seismic response Target damping ratio
1 Introduction
Manufactured viscous dampers are hydraulic devices which can be installed in structures in
order to mitigate the seismic effects through dissipating the kinetic energy transmitted by
the earthquake to the structure (Soong and Dargush 1997; Constantinou et al. 1998; Hart
M. Palermo (B) S. Muscio S. Silvestri L. Landi T. Trombetti
Department DICAM, University of Bologna, Viale Risorgimento 2, 40136 Bologna, Italy
e-mail: michele.palermo7@unibo.it
S. Muscio
e-mail: saverio.muscio3@unibo.it
S. Silvestri
e-mail: stefano.silvestri@unibo.it
L. Landi
e-mail: l.landi@unibo.it
T. Trombetti
e-mail: tomaso.trombetti@unibo.it
1 3
2430 Bull Earthquake Eng (2013) 11:24292446
and Wong 2000; Chopra 1995; Christopoulos and Filiatrault 2006). These devices have been
the object of several research works since the 1980s (Constantinou and Tadjbakhsh 1983;
Constantinou and Symans 1993; Takewaki 1997, 2000 and 2009, Singh and Moreschi 2002;
Trombetti and Silvestri 2004, 2007; Levy and Lavan 2006; Silvestri and Trombetti 2007; Dio-
tallevi et al. 2012; Adachi et al. 2013). Most of these works basically develop sophisticated
algorithms for dampers optimization, sometimes leading to complex design procedures. Nev-
ertheless, even if all the above cited works are remarkable froma scientic point of view, they
require a computational effort which is often beyond the common capabilities of the practical
engineers. Indeed, the issue of developing a practical method (i.e. a direct and immediate
help for the practitioners) in order to size the viscous dampers which are capable of achieving
a target level of seismic performances is still open.
In this respect, in 1992, the report NCEER-92-0032 (Constantinou and Symans 1992)
rst investigated the problem of selecting the damping coefcient of linear viscous dampers
in an elastic system to provide a specic damping ratio. In 2000, the report MCEER-00-
0010 (Ramirez et al. 2000) proposed an analytical relationship between the viscous damping
ratio in a given mode of vibration and the damping coefcients on the basis of an energetic
approach, assuming a given undamped mode shape. Starting from the fundamental results
of this research work, other methods have been proposed. Among these, the most useful for
the practitioners are likely to be the following ones: (1) Lopez Garcia (2001) developed a
simple algorithm for optimal damper conguration in Multi-Degree-Of-Freedom (MDOF)
structures, assuming a constant inter-storey height and a straight-line rst modal shape; (2)
ASCE 7 (2005) absorbed the MCEER-00-0010 approach.
However, also alternative approaches leading to practical design procedures for the sizing
of the viscous dampers have been proposed in the years. Among these, the following ones
should be mentioned: (1) Christopoulos and Filiatrault (2006) suggested a design approach
for estimating the damping coefcients of added viscous dampers consisting in a trial and
error procedure; (2) Silvestri et al. (2010) proposed a direct design approach, called the
ve-step procedure. A recent work by Whittle et al. (2012) compares the effectiveness of
some of the above mentioned design approaches.
The ve-step procedure, which has been proposed in 2010 by some of the authors, aims
at guiding the professional engineer from the choice of the target objective performance to
the identication of the mechanical characteristics (i.e. damping coefcient and oil stiff-
ness, for given alpha exponent) of commercially available viscous dampers. The original
version of the procedure (Silvestri et al. 2010) was developed with reference to the follow-
ing assumptions: (1) a Shear-Type (referred hereafter to as ST) structure schematisation, (2)
uniform lateral stiffness distribution along the height of the building, and (3) equal oor
masses. On the other hand, in the same work (Silvestri et al. 2010), the authors added
two simple applications of the procedure developed on two moment-resisting frames (a
reinforced-concrete frame and a steel frame), which lead to overtake the assumption of ST
schematization.
The purpose of the present research work is to provide a comprehensive theoretical frame-
work, which also allows to formally extend the validity of the proposed procedure to the
general case of a Flexible-Type (FT) structure schematisation, i.e. a structural model which
considers the actual stiffness of the beams. This objective will require a further insight
(Cheng 2001; Occhiuzzi 2009) into the damping properties of systems characterized by
not proportional damping. Moreover, a parametric study will be presented to show the
inuence of the lateral stiffness distribution on the effectiveness of the proposed proce-
dure.
1 3
Bull Earthquake Eng (2013) 11:24292446 2431
2 The rationale behind the ve-step procedure
Most of the procedures proposed in the scientic literature are grounded on the energetic
approach suggested by the report MCEER-00-0010: the viscous damping ratio in a given
mode of vibration is analytically obtained as a function of the energy dissipated by the
damping system per cycle of motion in the given mode, and the maximum strain energy of
the system. However, an assumption on the modal shape is required in order to numerically
evaluate the damping ratio.
In recent years, the authors faced the same problem in an alternative way: starting from
the study of the equations of motion for damped ST structures (Trombetti and Silvestri
2006), a direct ve-step procedure has been proposed for the dimensioning of the damping
coefcients of the viscous dampers (Silvestri et al. 2010). The core of this procedure (i.e.
Step 2) lies in the simple analytical relationship between the fundamental damping ratio and
the total damping coefcient of the damper system which only requires the knowledge of the
oor masses and the fundamental period of vibration of the structure. No assumption on the
fundamental modal shape is necessary, given that the effective modal shape of the rst mode
of vibration of an equal mass, equal stiffness, ST system is implicitly used. The interested
reader is referred to the discussion of the underlying eigenproblem presented in sections 6,
7 and 8 of the paper by Trombetti and Silvestri (2006).
The ve-step procedure has been formally developed assuming:
i Shear-type (ST) schematisation of the structure;
ii Equal lateral stiffness distribution (along the height of the building);
iii Equal mass distribution (along the height of the building).
Provided that assumption (iii) is close to the actual characteristics of common frame struc-
tures, the objective of this research work is twofold:
i To extend the procedure to generic moment-resisting frames (i.e. to remove the ST
assumption);
ii To investigate the effectiveness of the procedure with reference to other stiffness distri-
butions.
The rst objective will be reached in Sect. 3, by means of an original comprehensive frame-
work and a parametric study carried out in the eld of complex damping theory.
The second objective will be reached in Sect. 4, by means of a parametric study. Once
the characteristics of the linear viscous dampers are obtained through the rst two steps of
the procedure, the designer can identify the characteristics of the actual non-linear viscous
dampers (i.e. identication of a system of manufactured viscous dampers) capable of pro-
viding the structure with actions (on the structural members) comparable to those obtained
using the linear viscous dampers identied in Step 2. All the details, including applications
of the procedure, can be found in the work by Silvestri et al. (2010).
3 Objective 1: the inuence of the frame exibility on the effectiveness of the proposed
procedure
3.1 Problem formulation
The system dened here is composed of a 2-D specic frame structure (characterized by
oor mass m
i
=m i =1,,N; column moment of inertia J
i
, with i =1,. . . , N; N indicates
1 3
2432 Bull Earthquake Eng (2013) 11:24292446
Fig. 1 Schematic representation
of: a system A; b system B; c
system C
the total number of storeys) equipped with a specic dampers system (damping coefcients
c
j
, j = 1,. . . N x n, where n is the number of dampers per each oor).
System A, graphically represented in Fig. 1a, is dened as a FT frame structure (oor
mass m
A,i
, columns moment of inertia J
A,i
) equipped with Inter-Storey viscous dampers
(damping coefcients c
A, j
; total damping coefcient c
A,t ot
, dened as the sum of the
c
A, j
).
The rst objective of this research work is the identication of the total damping coefcient
c
A,t ot
of system A in order to obtain a target value,

, of the rst damping ratio of system A,

A
:
c
A,t ot
= f (
A
) with
A
=

(1)
For this purpose, it is necessary to introduce the following auxiliary systems:
System B, that is graphically represented in Fig. 1b, is dened as the ST frame structure,
with the same properties (m
B,i
= m
A,i
, J
B,i
= J
A,i
) as dened in systemA, but different
translational stiffness (k
B,i
= k
A,i
, due to the restrained rotations of the nodes), equipped
with Inter-Storey viscous dampers, characterised by the same total damping coefcient
of the damping system of system A (c
B,t ot
= c
A,t ot
). It should be mentioned that the
fundamental frequencies of the two systems,
B
and
A
, are different.
System C, that is graphically represented in Fig. 1c is dened as the ST frame structure,
with the same properties (m
C,i
= m
B,i
, J
C,i
= J
B,i
, and same restrained rotations of the
1 3
Bull Earthquake Eng (2013) 11:24292446 2433
Fig. 2 Flowchart of the scheme adopted to reach the rst objective of the research work
nodes) as dened in systemB, equipped with Fixed-Point viscous dampers, characterised
by the same total damping coefcient of the damping systemof systems Band A(c
C,t ot
=
c
B,t ot
= c
A,t ot
). Clearly, systems B and C are characterized by the same fundamental
frequency (
B
is equal to
C
). According to structural dynamics (Chopra 1995), it is well
known that the total damping coefcient of system C can be expressed as a function of
the corresponding damping ratio by the following equation (mass proportional damping
schematization):
c
C,t ot
= 2
C

C
m
t ot
(2)
Since no analytical relationships are currently available in order to express the total damping
coefcient of system A as a function of its fundamental damping ratio (i.e. Eq. (1)), then the
procedure schematically illustrated in the owchart reported in Fig. 2 is introduced.
Provided that the three systems (A, B, and C) have been chosen so that:
c
A,t ot
= c
B,t ot
= c
C,t ot
(3)
Equation (2) may be rewritten as follows:
c
A,t ot
= 2
C

C
m
t ot
(4)
At this point, in order to achieve the objective stated by Eq. (1),
C
should be expressed as a
function of
A
. This is obtained in two stages through the introduction of system B.
The rst stage consists in the derivation of the relationship between the fundamental
damping ratios of systems C and B, and also represents the fundamental result of a previous
research work developed by the authors (Trombetti and Silvestri 2006).
The second stage consists in the derivation of the relationship between the fundamental
damping ratios of systems B and A, and represents the core of the present research work.
Details are given in the next sections.
1 3
2434 Bull Earthquake Eng (2013) 11:24292446
Fig. 3 Effectiveness of the approximation
k
m
2
C

=
N(N+1)
2
for N varying between 1 and 20
3.2 The relationship between the fundamental damping ratios of systems B and C
In a previous research work (Trombetti and Silvestri 2006), under the assumption of equal
lateral stiffness and oor mass at every storey (m
i
= m, i and k
i
= k, i) and under the
equal total damping coefcient constraint, the authors demonstrated that the fundamental
damping ratio of system C can be expressed as a function of the fundamental damping ratio
of system B, as follows:

C
=
k
m
2
C

B
(5)
that can be well approximated by (Trombetti and Silvestri 2006):

C

=
N(N +1)
2

B
(6)
where N is the total number of storeys.
Figure 3 shows the effectiveness of the approximation
k
m
2
C

=
N(N+1)
2
for N varying
between 1 and 20. The quality of the approximation increases as the total number of storeys
decreases.
3.3 The relationship between the fundamental damping ratios of systems A and B
In the previous sections it has been shown that, while for systems B and C it is possible to
dene the damping matrix on the basis of the Stiffness Proportional Damping (SPD) or the
Mass Proportional Damping (MPD) limiting cases respectively, for system A it is necessary
to resort to the complex damping theory (Cheng 2001; Occhiuzzi 2009). In detail, instead
of searching for an exact analytical relationship between the fundamental damping ratios of
systems A and B, an approximated numerical one has been searched.
For damped Single-Degree-Of-Freedom (SDOF) systems, an analytical relationship
between the fundamental damping ratios of systems A and B can be drawn starting from
the basic concepts of structural dynamics (Sect. 3.3.1).
1 3
Bull Earthquake Eng (2013) 11:24292446 2435
Fig. 4 a Shear-Type SDOF
system equipped with viscous
damper; b Flexible-Type SDOF
system equipped with viscous
damper
Fig. 5 Schematic representation of the MDOF frame systems used to perform the numerical analysis
For damped MDOF systems, a numerical analysis performed in the eld of complex
damping has been conducted in order to verify if the same relationship still holds (Sect.
3.3.2).
3.3.1 The basic idea
Two equivalent (same mass m, same column moment of inertia J and same damping coef-
cient c) SDOF systems, represented in Fig. 4, are considered. The rst one represents a
one-storey one-bay ST structure equipped with an Inter-Storey viscous damper system; and
the second one represents a one-storey one-bay FT structure equipped with an Inter-Storey
viscous damper system. Due to the difference in the beam stiffness, the fundamental circular
frequencies (
ST
and
FT
) and periods (T
ST
and T
FT
) of the two systems are not equal.
Under the above mentioned assumptions, it is easy to show that the ratio of the modal damp-
ing ratios pertained to the two systems is exactly the same as the corresponding ratio of the
fundamental periods:

=

FT

ST
=
c/ (2 m
FT
)
c/ (2 m
ST
)
=

ST

FT
=
T
FT
T
ST
=
T
(7)
3.3.2 Numerical analyses: main results
The numerical analysis has been carried out on the FT structures schematized in Fig. 5, that
are characterized by the following main properties:
1 3
2436 Bull Earthquake Eng (2013) 11:24292446
0 1 2 3 4 5
infinity
1
1.2
1.4
1.6
1.8
2
2.2

2-storey systems
3-storey systems
4-storey systems
5-storey systems
6-storey systems
Fig. 6

versus
R
Total number of storeys, N, variable from 2 to 6;
Number of bays equal to 1;
Bay width equal to 6m;
Inter-storey height equal to 3m;
Square columns with constant cross section 40 cm 40 cm at each storey (xed for all
the models);
Beams with constant cross section for all storeys (different for each model);
Floor mass m equal to 80,000kg;
Beamcolumn stiffness ratio,
R
= k
beam
/k
column
, variable from 0.5 to (ST system);
Elastic material with Youngs modulus, E, equal to 20,000MPa.
In these analyses, where the main purpose is to investigate the inuence of the exural exi-
bility of beams, the axial exibility of the structural elements has been neglected. Considering
the kth FT system, each single analysis included the following phases: (1) evaluation of the
fundamental modal damping ratio,
FT,k
, by means of the complex damping theory (Cheng
2001; the interested reader can nd additional details in Muscio 2009); (2) evaluation of
the rst modal damping ratio of the equivalent ST system by means of the Rayleigh theory,

ST,k
; (3) evaluation of the ratio between the fundamental modal damping ratio of the FT
structure and the one of the equivalent ST structure,

K
; (4) evaluation of the ratio between
the fundamental period of the FT structure and the one of the equivalent ST structure,
T
K
.
The main results are briey illustrated through Figs. 6, 7, 8.
Figures 6 and 7 display the ratios

and
T
versus the ratio
R
, respectively. Inspection
of the graphs leads to the following deductions:
For all values,

is always higher than the corresponding


T
;
As it might be reasonably expected, for all
R
values, both

and
T
increase with the
increase of the total number of storeys N;
As it might be reasonably expected, both

and
T
decrease with the increase of
R
.
Figure 8 renders the graphical representation of the correlation between

and
T
. Inspection
of the graph leads to the following deductions:

and
T
exhibit a strong linear correlation, with correlation coefcient equal to 0.998;
1 3
Bull Earthquake Eng (2013) 11:24292446 2437
0 1 2 3 4 5 infinity
1
1.2
1.4
1.6
1.8
2
2.2

T
2-storey systems
3-storey systems
4-storey systems
5-storey systems
6-storey systems
Fig. 7
T
versus
R
Fig. 8

versus
T
1 1.2 1.4 1.6 1.8 2 2.2
1
1.2
1.4
1.6
1.8
2
2.2

2-storey systems
3-storey systems
4-storey systems
5-storey systems
6-storey systems

values are larger than the corresponding


T
values; thus,
T
can be assumed as a
lower bound for

;
For practical applications,

can be approximately assumed equal to


T
; the assumption


=
T
is conservative.
Based on the main result of these numerical simulations (


=
T
), the fundamental damping
ratio of system B can be expressed as a function of the fundamental damping ratio of system
A, as follows:

B

=
A

T
B
T
A
(8)
1 3
2438 Bull Earthquake Eng (2013) 11:24292446
or:

B

=
A


A

B
(9)
which represents the extension (for the case of MDOF systems) of the result given by Eq.
(7) for the case of SDOF systems.
3.4 The total damping coefcient for system A
Substitution of Eq. (9) into (6) leads to:

C

=
N(N +1)
2


A

B

A
(10)
Substitution of Eq. (10) into (4) leads to:
c
A,t ot
= 2
N(N +1)
2


A

B

A

C
m
t ot
(11)
Given that
B
=
C
, Eq. (11) can be nally simplied as follows:
c
A,t ot
= N(N +1)
A

A
m
t ot
(12)
Imposing that the rst modal damping ratio of system A is equal to a target damping ratio
(
A
=

) leads to the following fundamental result:
c
A,t ot
= N(N +1)
A


m
t ot
(13)
which represents a simple formula for the dimensioning of the total damping coefcient of
system A (in a given direction) in order to achieve the target damping ratio

.
It is possible to observe that Eq. (13) is formally coincident with Eq. (27) of (Silvestri
et al. 2010). However, while the latter was derived assuming a ST structure schematization,
Eq. (13) keeps its validity also for a generic FT frame structure.
3.5 The dimensioning of each viscous damper
Once the total damping coefcient c
A,t ot
has been obtained, the damping coefcient of each
single damper should be evaluated.
Several studies have been carried out in the past in order to estimate the optimal dampers
distribution for inter-storey dampers placement. In a recent work, Takewaki (1997) provided a
comprehensive literature reviewon this topic. Basically, to date, the design methods of added
viscous dampers to buildings may be subdivided into two main categories. The rst is the
most commonly used method by practical engineers, which has focused on the development
of simple design formulas for calculating the added damping ratio to the building, like
the approach proposed in this paper. However, adopting these design formulas, a limited
number of methods (Lee et al. 2008; Hwang et al. 2013) have been provided on how to
distribute the total required damping coefcients to each storey. The second category includes
several designmethods basedoniterative procedures aimedat obtainingthe optimal damper
distribution which satises a certain target objective (a complete list of the works on this
subject may be found in the introduction of the book by Takewaki (2009)).
Almost all these studies highlighted that, for regular stiffness and mass distributions, a
uniform added dampers distribution usually leads to a building performance which is close
to the optimal solution. Thus, for design purposes, in the case of regular buildings, once the
total damping coefcient c
t ot
is evaluated, a uniform dampers distribution can be adopted.
1 3
Bull Earthquake Eng (2013) 11:24292446 2439
1
2
3
4
5
6
7
1 3 5 7 9 11 13 15 17
S
t
o
r
e
y
Normalized stiffness
SD-II
SD-I
Fig. 9 The two stiffness distributions (SD-I and SD-II) adopted for the parametric study
Under this assumption, the storey damping coefcient c
st orey
is given by the following
relationship:
c
st orey
= (N +1)
A


m
t ot
(14)
If n equal dampers are installed at each storey (diagonal inter-storey dampers), the damping
coefcient c of each viscous damper is given by the following simple formula:
c =
(N +1)
A


m
t ot
n cos
2

(15)
where the termcos
2
accounts for the inclination of the damper with respect to the horizontal.
A further insight into the assumption of different stiffness distributions is provided in the
next section.
4 Objective 2: the inuence of the lateral stiffness distribution on the effectiveness of
the proposed procedure
4.1 Problem formulation
Let us consider a reference system, referred to as System 0, composed of a ST structure,
characterised by oor mass m
i
= m, with i = 1,,N; column moment of inertia J
i
, = J,
with i = 1,. . . , N (where N indicates the total number of storeys), and equipped with a
uniform distribution of inter-storey viscous dampers with damping ratio evaluated according
to Eq. (14) of the present paper.
In order to investigate the effectiveness of the proposed approach for the cases of not-
uniform lateral stiffness distributions, a parametric study has been developed. In detail, two
different not-uniform stiffness distributions (Fig. 9) are considered:
1 3
2440 Bull Earthquake Eng (2013) 11:24292446
Table 1 The systems dened for the parametric analysis
Stiffness distribution
SD-0 (uniform) SD-I (area-based) SD-II (inertia-based)
Dampers distribution
DD-a uniform System 0
(reference
system)
System 1 System 3
DD-b stiffness
proportional
System 2 System 4
Stiffness distribution I (referred to as SD-I): columns cross section area linearly increases
starting from a minimum value at the top storey. This case is representative of r/c frame
structures designed for vertical loads;
Stiffness distribution II (referred to as SD-II): lateral stiffness is assumed proportional
to the storey shear due to a triangular horizontal forces distribution (typically of an
equivalent static seismic analysis).
The uniform stiffness distribution is referred to as SD-0. It should be noted that SD-I cor-
responds to a constant static axial stress criterion (area-based distribution), while SD-II
corresponds to a constant inter-storey drift criterion (inertia-based distribution).
Also two different damper distributions are considered:
Dampers distribution a (referred to as DD-a): uniform dampers distribution. In this
case, the storey damping coefcient is given by Eq. (14);
Dampers distribution b (referred to as DD-b): dampers distribution (along the height)
proportional to the lateral stiffness distribution (Christopoulos and Filiatrault (2006)
proposed an alternative procedure in order to evaluate a dampers distribution proportional
to the stiffness distribution of the unbraced structure). In this case, the generic storey
damping coefcient at the kth storey, c
st orey,k
, can be calculated with the following
formula:
c
st orey,k
=
J
k
J
t ot
N(N +1)

m
t ot
(16)
which is obtained assuming a total damping coefcient c
t ot
as per Eq. (13).
Based on the above introduced lateral stiffness and viscous dampers distributions, in
order to investigate the effectiveness of the procedure for different stiffness distributions, the
following classes of systems are introduced as (see Table 1):
System 1: the system characterised by the same mass distribution of System 0, SD-I and
DD-a;
System 2: the system characterised by the same mass distribution of System 0, SD-I and
DD-b;
System 3: the system characterised by the same mass distribution of System 0, SD-II and
DD-a;
System 4: the system characterised by the same mass distribution of System 0, SD-II and
DD-b.
1 3
Bull Earthquake Eng (2013) 11:24292446 2441
Table 2 Effectiveness of the procedure in terms of achieved fundamental damping ratio given a target damping
ratio equal to 0.30
Total number of storeys System 0 System 1 System 2 System 3 System 4
7 0.39 0.51 0.31 0.39 0.43
6 0.39 0.53 0.34 0.41 0.43
5 0.39 0.48 0.37 0.44 0.44
4 0.39 0.50 0.39 0.46 0.44
3 0.38 0.51 0.40 0.46 0.43
Average 0.39 0.51 0.36 0.43 0.43
4.2 Parametric study
With reference to the 4 classes of systems introduced in the previous section (see Table 1),
a parametric analysis has been carried out aimed at investigating the effectiveness of the
proposed procedure. The characteristics of the systems are summarized as follows:
Total number of storeys, N, variable from 3 to 7;
Number of bays equal to 1;
Bay width equal to 6m;
Inter-storey height equal to 3m;
Beams with square cross section calibrated in order to provide a ratio
R
=
k
beam
/k
column
= 1.0;
Floor mass m equal to 80,000kg;
Elastic material with Youngs modulus, E, equal to 20,000MPa.
Damping target ratio

= 0.30
Numerical time-history analyses have been performed. In these analyses, both the exural
and the axial exibility of the structural elements have been considered. Each systemhas been
subjected to a base seismic input. A set of ten articial accelerograms generated using the
software SIMQKE (Vanmarcke et al. 1990), compatible with the design spectrum prescribed
by the Italian seismic code (NTC 2008), and corresponding to an average PGA equal to
0.25g have been used. The following response parameters have been considered: the top-
storey absolute acceleration, a, the top-storey displacement, , and the base shear, V. The
results of the time-history analyses are presented in terms of reduction factors
a
,

and
V
.
For instance, the mean value (over the ten seismic records) of the displacement reduction
factor,

mean
, of

i
, is computed as:

mean
=
1
10

10
i =1

i
, with

i
=

i ()

i (=0.05)
, where

i (=0.05)
is the maximum value of the displacement response obtained for the bare system
(i.e. the structure without added dampers) under the i th seismic record.
Also snap-back tests have been performed in order to calculate the equivalent rst-modal
damping ratio, by means of the method of the logarithmic decrement (Chopra 1995).
4.3 The main results of the parametric study
The results of the parametric analysis are summarized through Tables 2, 3, 4, 5.
First, the results of the snap-back tests are commented. Table 2 provides a summary of the
obtained damping ratios for all analyzed systems. Inspection of these results clearly shows
that the proposed procedure leads to conservative results: in all cases, the obtained damping
ratio is higher than the target one (which was equal to 0.30). The average damping ratio over
1 3
2442 Bull Earthquake Eng (2013) 11:24292446
Table 3 Effectiveness of the procedure in terms of top-storey absolute acceleration reduction factor (
a
mean
)
Total number of storeys System 0 System 1 System 2 System 3 System 4
7 0.30 0.24 0.21 0.23 0.25
6 0.31 0.28 0.25 0.25 0.26
5 0.32 0.32 0.29 0.26 0.27
4 0.33 0.32 0.29 0.29 0.28
3 0.35 0.35 0.33 0.33 0.33
Average 0.32 0.30 0.27 0.27 0.28
Table 4 Effectiveness of the procedure in terms of top-storey displacement reduction factor (

mean
)
Total number of storeys System 0 System 1 System 2 System 3 System 4
7 0.44 0.35 0.43 0.44 0.41
6 0.44 0.37 0.45 0.43 0.44
5 0.44 0.40 0.47 0.44 0.45
4 0.45 0.43 0.48 0.45 0.46
3 0.41 0.40 0.43 0.47 0.48
Average 0.44 0.39 0.45 0.45 0.45
Table 5 Effectiveness of the procedure in terms of base shear reduction factor (
V
mean
)
Total number of storeys System 0 System 1 System 2 System 3 System 4
7 0.40 0.66 0.47 0.61 0.53
6 0.41 0.65 0.46 0.60 0.54
5 0.41 0.65 0.47 0.59 0.51
4 0.43 0.59 0.44 0.55 0.54
3 0.41 0.47 0.37 0.51 0.46
Average 0.41 0.60 0.44 0.57 0.52
all systems is equal to 0.41. It has to be noted that, if only the reference cases are considered
(i.e. STsystems with uniformstiffness distribution), an average damping ratio equal to 0.39 is
obtained. On the contrary, if only the remaining systems (i.e. those systems with not-uniform
stiffness distributions) are considered, anaverage dampingratioequal to0.42is obtained. This
suggests that stiffness distribution does not signicantly affect, on average, the effectiveness
of the procedure, leadingonlytoslightlymore conservative results. Moreover, as expected, the
total number of storeys (i.e. the fundamental period of the system) does not signicantly affect
the response, provided that the inuence of system exibility is already taken into account
in the formula of the c
t ot
(Eq. 13). The conrmation of the effectiveness of the procedure
highlights also the negligible inuence of the axial exibility of the structural elements.
As far as the single classes of systems are concerned, the following observations may be
given:
If the SD-I is considered (i.e. the one farther from the uniform distribution with respect
to the SD-II), the adoption of the two dampers distributions leads to different responses:
the average damping ratio jumps from 0.50 (very conservative) for the uniform dampers
1 3
Bull Earthquake Eng (2013) 11:24292446 2443
distributions to 0.36 (slightly conservative) for the stiffness proportional dampers distri-
bution.
If the SD-II is considered, it is possible to observe that the two dampers distributions lead
to very close values (i.e. robust behaviour) of average damping ratios: 0.42 and 0.43
for the uniformdampers distributions and the stiffness proportional dampers distribution,
respectively.
In order to check the snap-back tests results, a further verication has been developed: each
bare system has been subjected to a modal time history analysis with an imposed modal
damping ratios (for all modes) as obtained from the snap-back test (as also suggested by
Christopoulos and Filiatrault 2006). The results of these time history analyses have been
compared with those obtained for the systems equipped with diagonal inter-storey viscous
dampers having damping coefcients calculated with the proposed procedure (these results
will be commented later in the present section). The comparison showed a good agreement,
thus providing a further conrmation of the effectiveness of the damping ratios as evaluated
from the snap-back tests. For sake of conciseness, Fig. 10 reports only the comparison, in
terms of average inter-storey drift proles, of the 3- and 7-storey systems.
1
2
3
4
5
6
7
0 0.005 0.01 0.015 0.02
s
t
o
r
e
y
inter-storey drift ratio
Bare
SD-II & DD-a
SD-II Modal
1
2
3
0 0.005 0.01 0.015 0.02 0.025
s
t
o
r
e
y
inter-storey drift ratio
Bare
SD-I & DD-a
SD-I Modal
(a)
(b)
Fig. 10 Seismic inter-storey drift proles for a 7-storey systems and b 3-storey systems, with and without
added dampers
1 3
2444 Bull Earthquake Eng (2013) 11:24292446
The results of the time-history analyses performed on the systems equipped with diagonal
inter-storey dampers, summarized through Tables 3, 4, 5, lead to the following observations:
The average top-absolute acceleration reduction factor (Table 3) is equal to 0.29. As
expected, the top-absolute acceleration reduction is affected by the fundamental period:
the reduction increases (i.e. the reduction factor decreases) as the total number of storeys
(i.e. the fundamental period) increases. Reference systems exhibit an higher average
reduction factor, 0.32, with respect to the other cases, 0.28, since the former (ST struc-
tures) are characterized by fundamental period quite lower than the latter. Despite the
inuence of the fundamental period, the variability of the absolute acceleration reduction
factor is very limited;
The average top-displacement reduction factor (Table 4) is equal to 0.43 (which leads to
an equivalent damping ratio equal to 0.52 calculated inverting the formula by Bommer
et al. 2000). All classes of systems exhibit almost the same average reduction factor
1
2
3
4
5
6
0 0.005 0.01 0.015 0.02 0.025
s
t
o
r
e
y
inter-storey drift ratio
Bare
DD-a
DD-b
1
2
3
4
5
6
0 0.005 0.01 0.015 0.02 0.025
s
t
o
r
e
y
inter-storey drift ratio
Bare
DD-a
DD-b
(a)
(b)
Fig. 11 The seismic inter-storey drift proles for the 6-storey system: a with SD-I stiffness distribution and
b SD-II stiffness distribution
1 3
Bull Earthquake Eng (2013) 11:24292446 2445
(0.440.45 with a limited dispersion), except System1 which shows the smallest average
reduction factor (0.39);
The average base shear reduction factor (Table 5) is equal to 0.50. If only the reference
cases are considered, an average base shear reduction factor of 0.41 is obtained. On the
contrary, if only the remaining systems are considered, an average base shear reduction
factor approximately equal to 0.52 is obtained. It can be noted that the variability of the
base shear reduction is larger than the variability of the other parameters.
In order to provide a further insight into the seismic response of the studied systems, Fig. 11
displays the graphs of the average (over the ten seismic records) inter-storey drift proles
for the specic case of the 6-storey structure. It can be observed that the DD-b (damper size
proportional to lateral stiffness, i.e. large size at the base) reduces the rst inter-storey drift
more than the DD-a (uniform dampers distribution), which on the contrary is more effective
at the higher storeys.
5 Conclusions
This research work investigates the effectiveness of a ve-step design procedure recently
proposed by some of the authors for sizing the damping coefcients of added viscous dampers
to be inserted in moment-resisting frame systems.
The procedure provides a simple design formula for the evaluation of the total damping
coefcient of the added dampers systems leading to a specic target damping ratio, which
is only based on the knowledge of the total building mass and fundamental period. The
procedure was originally developed for the specic case of shear-type structures with uniform
distribution of oor mass and lateral stiffness.
In this paper, a comprehensive framework is presented, which allows to formally extend
the validity of the proposed procedure to the more realistic case of a generic moment-resisting
frame structure with uniform distribution of oor mass and lateral stiffness. For this purpose,
numerical analyses in the eld of complex damping theory have been performed.
Moreover, the effectiveness of the ve-step procedure has been investigated removing the
assumption of uniform stiffness distribution, through the development of a parametric study.
The results show that the application of the proposed procedure for the dimensioning of the
added viscous dampers in the case of not-uniformstiffness distribution leads to slightly more
conservative results with respect to the application of the procedure in the case of uniform
stiffness distribution.
Acknowledgments Financial supports of Department of Civil Protection (Reluis 20102013 Grant
Thematic Area 2, Research line 3, Task 2: Development and analysis of new technologies for the seismic
retrot) is gratefully acknowledged.
References
Adachi F, Yoshitomi S, Tsuji M, Takewaki I (2013) Nonlinear optimal oil damper design in seismically
controlled multi-story building frame. Soil Dyn Earthq Eng 44(1):113
American Society of Civil Engineers, ASCE 705 (2005) Minimum design loads for buildings and other
structures. Reston, VA
Bommer JJ, Elnashai AS, Weir AG (2000) Compatible acceleration and displacement spectra for seismic
design codes. In: Proceedings of the 12th World Conference on Earthquake Engineering. Auckland, New
Zealand.
Cheng FY (2001) Matrix analysis in structural dynamics. CGC, Rolla Missouri
1 3
2446 Bull Earthquake Eng (2013) 11:24292446
Chopra AK (1995) Dynamics of structures. Theory and applications to earthquake engineering. Prentice-Hall,
Upper Saddle River
Christopoulos C, Filiatrault A (2006) Principles of passive supplemental damping and seismic isolation. IUSS
Press, Pavia
Constantinou MC, Symans MD (1992) Experimental and analytical investigation of seismic response of
structures with supplemental uid viscous dampers. NCEER-92-0032. National Center for Earthquake
Engineering Research, Technical report, Buffalo
Constantinou MC, Soong TT, Dargush GF (1998) Passive energy dissipation systems for structural design and
retrot, monograph No. 1. Multidisciplinary Center for Earthquake Engineering Research, Buffalo, New
York
Constantinou MC, Tadjbakhsh IG (1983) Optimum design of a rst story damping system. Comput. Struct.
17(2):305310
Constantinou MC, Symans MD (1993) Seismic response of structures with supplemental damping. Struct Des
Tall Build 2:7792
Diotallevi PP, Landi L, Dellavalle A (2012) A methodology for the direct assessment of the damping ratio of
structures equipped with nonlinear viscous dampers. J Earthq Eng 16:350373
Hart GC, Wong K (2000) Structural dynamics for structural engineers. Wiley, New York
Hwang JS, Lin WC, Wu NJ (2013) Comparison of distribution methods for viscous damping coefcients to
buildings. Struct Infrastruct Eng 9(1):2841
Lee SH, Park JH, Lee SK(2008) Allocation and slip load of friction dampers for a seismically excited building
structure based on story shear force distribution. Eng Struct 30(4):930940
Levy R, Lavan O (2006) Fully stressed design of passive controllers in framed structures for seismic loadings.
Struct Multidiscip Optimiz 32(6):485498
Lopez Garcia D(2001) Asimple method for the design of optimal damper congurations in MDOF structures.
Earthq Spectra 17(3):387398
Muscio S (2009) Evaluation of the effects of insertion of viscous dampers in moment-resisting frames, Ph.D.
Thesis, University of Bologna, Bologna, Italy, 2009. Available online on http://amsdottorato.cib.unibo.it/
3134/
NTC (2008) Norme Tecniche per le Costruzioni, Italian building code, adopted with D.M. 14/01/2008, pub-
lished on S.O. n. 30 G.U. n. 29 04/02/2008
Occhiuzzi A (2009) Additional viscous dampers for civil structures: analysis of design methods based on
effective evaluation of modal damping ratios. Eng Struct 31(5):10931101
Ramirez OC, Constantinou MC, Kircher CA, Whittaker AS, Johnson MW, Gomez JD, Chrysostomou CZ
(2000) Development and evaluation of simplied procedures for analysis and design of buildings with
passive energy dissipation systems. MCEER-00-0010. Technical report, Buffalo
Silvestri S, Trombetti T (2007) Physical and numerical approaches for the optimal insertion of seismic viscous
dampers in shear-type structures. J Earthq Eng 11(5):787828
Silvestri S, Gasparini G, Trombetti T (2010) A ve-step procedure for the dimensioning of viscous dampers
to be inserted in building structures. J Earthq Eng 14(3):417447
Singh MP, Moreschi LM (2002) Optimal placement of dampers for passive response control. Earthq Eng
Struct Dyn 31:955976
Soong TT, Dargush GF (1997) Passive energy dissipation systems in structural engineering. Wiley, Chichester
Takewaki I (1997) Optimal damper placement for minimum transfer functions. Earthq Eng Struct Dyn
26:11131124
Takewaki I (2000) Optimal damper placement for critical excitation. Prob Eng Mech 15:317325
Takewaki I (2009) Building control with passive dampers: optimal performance-based design for earthquakes.
Wiley, Singapore
Trombetti T, Silvestri S (2004) Added viscous dampers in shear-type structures: the effectiveness of mass
proportional damping. J Earthq Eng 8(2):275313
Trombetti T, Silvestri S (2006) On the modal damping ratios of shear-type structures equipped with Rayleigh
damping systems. J Sound Vib 292(2):2158
Trombetti T, Silvestri S (2007) Novel schemes for inserting seismic dampers in shear-type systems based upon
the mass proportional component of the Rayleigh damping matrix. J Sound Vib 302(3):486526
Vanmarcke EH, Cornell CA, Gasparini DA, Hou S (1990) SIMQKE-I: simulation of earthquake ground