Вы находитесь на странице: 1из 6

A)

Qty Unit
Rate
(Rs)
Amount
(Rs.)
1
6
1
1
1
1
1
1
2
1
3
2
1
1
1
1
2
1
1
1
1
1
1
1
1
1 No. 493,100.00 493,100.00
b) 1 No. 2,311.00 2,311.00
1 No. 1,260,000.00 1,260,000.00
Applicable
Standard
IS 11171-1985 with latest modification (if any) &
CBIP Specification
Rating 500 KVA
Type Resin impregnated type (Vacuum pressure
impregnated)
Voltage ratio Prime Voltage = 11000V
Secondary Voltage 415V
1 a)
2 a)
Proposed HT Sub-station for Market Complex at Baruipur of South 24 Parganas.
Triple pole non directional shunt trip OCEF relay having 2 over current
element of setting 50-2000 and 1 earth fault element of 20-80% (type-
CDG61)
Auxiliary relay for Wdg. Temp, A/T indication
The switchboard will be complete with 800A (2 inch X 1 inch) copper bus
bar, necessary connection. Fine wiring, copper earth bar etc.
3 phase 3 wire KWH meter
White lamp with push button for non-trip Indication
Undervoltage Relay
Description of Materials
Trip circuit Supervision relay
96 sq.mm MISC Type Ammeter with Selector switch
96 sq.mm. MISC type Voltmeter with Selector switch
Thermostatic heater ON/OFF switch (230V AC, 80 watt)
Emergency push button
Rectifier condenser unit (power pack)
11 KV/110V 3 Phase 3 limb star/star Connected drawout type resin cast
potential Transformer with 200 VA per phase output At class-1 accuracy for
metering purpose Provided with necessary HT/LT fuses, Shutters, etc.
100/50/5-5A or 60-30/5-5 A, resin cast Current Transformer with having 15
G A Output at 5 P 10 accuracy for protection and Class 1 for metering
Master trip relay
Name of Work
Supply and delivery of 11KV, 350 MVA, 800A single panel H.T. Gear with
VCB as per specification (AREVA/SIEMENS/BIECCO) below :
Fabricated indoor floor mounting type sheet steel housing
800 A single pole isolating plugs & sockets
Set of automatic safety shutters
800 A triple pole type Vacuum Circuit Breaker suitable for a rupturing
capacity of 350 MVA at 11 KV and fitted with motor operated independent
spring charged type LSM mechanism with mechanical ON/OFF indicators
containing 1 No. 110V DC shunt trip coil &1 no 110V DC closing coil.
Set of mechanical interlocks
Auxilary switch & 1 No. TNC Switch & 1 No. LR Switch
Sl. No.
Red/Green indicator lamps for CB ON/OFF Indication
Amber lamp for auto trip indication
Blue Iamp for spring charge indication
Rear entry cable termination arrangement/ Box for 3C X 300 sq.mm. XLPE
power cable,
Supply and delivery of 500 KVA, 3 Phase , 50 Hz, 1KV/415V Dry type
distribution transformer (Make Crompton / Baroda/ Equivalent with CPRI
approval) as per specification below :
Installation of above single panel, cubicle type HT switch board with PT
including carriage within a lead of 30 mtr. by placing in position & fixing on
floor, after leveling, fitting and checking up instruments and relays set
Side entry Coble box.
Shukla Saha:\\\vboxsrv\conversion_tmp\scratch_1\248641144.xls.ms_officeBOQ
Qty Unit
Rate
(Rs)
Amount
(Rs.)
Description of Materials Sl. No.
Links/ Tappings Off Circuit Links, tapping range +5% to -5%, in steps
of 2.5%
Range & Steps Air natural Cooled
Cooling As per IS 5 (Painted with synthetic Enamel)
Painting DYN 11
Vector Group Class H
Class of Insulation
IS.
The core shall be built up with high grade, Non aging,
low loss, high permeability, grain Oriented, cold rolled
silicon steel laminations. Especially suitable for core
material. Grade of Core should be M4 or better. The
specified. Evidence of procurement of core has to be
provided. The coils shall be manufactured from
Electrolytic copper conductor & fully Insulated for
rated voltage, coils shall be vacuum impregnated with
epoxy resin, non-encapsulated, Class H, naturally
cooled (AN). The manufacturer should have in house
core Cutting facility & in house testing facility.
Insulating material shall be proven design & should be
selected in such way that the Transformer will be
capable of supplying 110% continuous load. Coils
shall be so Insulated that impulse & power frequency
Voltage stress are minimum. Coil assembly shall be
suitably supported between adjacent by insulating
spacers & Barriers. All leads from the windings to the
terminal board & bushings shall be rigidly supported to
prevent injury from vibration or short circuit streses.
Guide tube shall be used where practicable.
The core and coil assembly shall be securely fixed in
position so that no shifting or deformation occurs
during movement of transformer or under short circuit
stresses.
Degree of Protection IP 23
Minimum 98.5% at 50% load
Efficiency at 98.5% at 75% load
Unit P.F. (approx.) 98.5% at 100% load
Impedance 4.75% (Allowable tolerance as per IS)
Testing Routine tests as per relevant IS
Terminal
Arrangement
Should be provided with HV & LV cable boxes
Fittings &
Accessories
Should be provided with essential fittings &
accessories including RTD & Temperature Scanner.
b) 1 2,236.00 2,236.00
Core & Coils
2 a)
Installation of 500 KVA transformer including carriage to the sub-station
building within a lead of 30 mrs. By placing in position & fixing after
leveling, fitting all components including S&F base Channels etc.
Shukla Saha:\\\vboxsrv\conversion_tmp\scratch_1\248641144.xls.ms_officeBOQ
Qty Unit
Rate
(Rs)
Amount
(Rs.)
Description of Materials Sl. No.
1 Set 225,000.00 225,000.00
a)
b) 1 No.
c) 1 No.
d) 3 No.
e) 3 No.
f) 3 No.
g) 1 Set
4 30 Mtr. 1,754.00 52,620.00
5 45 Mtr. 1,760.00 79,200.00
6 5 Set 12,812.00 64,060.00
7 6 Set 310.00 1,860.00
8 6 Set 646.00 3,876.00
9 1 Item 8,000.00 8,000.00
10 8 No. 5,499.00 43,992.00
11 8 Set 1,285.00 10,280.00
12 60 Mtr. 292.00 17,520.00
3
Finishing the end of 1.1 KV grade 3C x 240 mm2 XLPE insulated armoured Al.
cable, as per GS.
S & F Danger Board
S & F 0 - 800A Ammeter with selector switch (AE)
S & F current Transformer of 5A/80AO
S & F 415V sliding lock fuse with 6A HRC (E.E.)
Supply 1.1KV grade 3 x 240 mm
2
x LPE insulated armoured Al. cable & laying
the same in existing trench/duct/tray, as directed by EIC (3 nos. cable x 15 mtrs.)
Providing termination joint for 11 KV(E) grade 3C x 185 mm
2
XLPE H.T. cable
including S & F all jointing materials with socketing etc. as required
S & F of compression glands for 1.1 KV grade 3C x 240 mm
2
XLPE insulated
armoured Al. cable, as per GS.
S & F LED indicating lamp (RYB) (Siemens' make)
Supply & delivery of cubical type LT. panel Board made from 16 SWG CRCA
sheet with iron structure (40 x 40 x 6) mm and (75 x 40 x 40) mm. base channel
having suitable in size and depth for proper placement of following accessories
with separate compartment and multitier arrangement with cable ally. The cubical
should be made with proper spacing for incoming and outgoing cable/copper
conduct. The gland plate should be fixed separately. The connection of switches
with the electrolyte tinned copper bars should be extended having l000A (60 x
10mm) current carrying capacity of suitable in length and
dimension. The Panel Board should be painted with Powder Coted paint over two
coats of red lead primer after finishing of surface properly. The materials and
design should be approned by E.I.C. before fabrication.
S & F 415V 800A Pole drawout type Ajr Circuit Breaker (L & T make Cat
No. UW1088XDO) with earth fault, over load protection etc. complete with
breaking capacity 65 KA 1 Set
S & F 0 500V Voltmeter with selector switch (AE)
Metering arrangement
Supplying of 11KV(E) grade 3C X 185 mm
2
XLPE H.T. cable with Al. conductor
& laying the same in existing trench/duct/tray, as directed by EIC (1 no. length of
15mt. From Supplier's Switchrear to single Panel VCB and one no. length of
15mt. From VCB to Transformer)
Making, testing arrangements and submitting the test report for high voltage
testing of specified voltage including checking & testing of all H.T./L.T.
equipments by authorized firm of Directorate of Electricity
Earthing with 80mm dia 3.0 mt. long Gl. Pipe (TATA-Medium) and 1 no. 65 x
8mm galvanized (Hot Dip) steel strip (4 mt. long), 20mm dia x 125mm long
galvanized bolt, double nuts, double washers including finishing both ends by
making holes etc. and S&F 80mm dia Gl. pipe (ISI-Medium) protection (3 mt.
long) to be filled with bitumen party under the ground level and partly above
ground level to an average depth of 3.65mt.
Extra for providing masonry enclosure on the top of the earth electrode of overall
size 86.36 x 86.36x46 cm deep (below ground level) complete brick work (1.6) of
25 cm width duly plastered with cement morter (inside) Cl hinged inspection
cover of size 35.56 x 35.56 cm with locking arrangement, Gl reducer including
drilling of 46 no. 12mm. dia holes on the GI pipe.
S&F earth bus-bur of galvanize (Hot Dip) MS flat 65 x 8 mm on wall having
clearance of 6mm from wall including providing drilled holes on the bus-bar
complete with GI bolts, nuts, washers, spacing insulators etc. as required
Shukla Saha:\\\vboxsrv\conversion_tmp\scratch_1\248641144.xls.ms_officeBOQ
Qty Unit
Rate
(Rs)
Amount
(Rs.)
Description of Materials Sl. No.
13 40 Mtr. 114.00 4,560.00
14 30 Mtr. 182.00 5,460.00
15 6 Set 305.00 1,830.00
16 6 Set 2,488.00 14,928.00
17 2 Set 457.00 914.00
18 4 Set 72.00 288.00
19 2 Pair 200.00 400.00
20 8 No. 1,440.00 11,520.00
21 5 No. 83.00 415.00
22 1 Item 30,000.00 30,000.00
Rs. 2,334,370.00
B)
1 10 Mtr. 177.00 1,770.00
2 1 Set 3,019.00 3,019.00
i) 60 Mtr. 116.00 6,960.00
4 2 No. 69.00 138.00
i) 2 Set 22.00 44.00
ii) 12 Set 21.00 252.00
Sub-Total
2x6 sqmm PVC/A Al. cable
2x2.5 sqmm Single core stranded 'FR' PVC copper wire
S&F 250Vm 6-10A / way, 2+8-way SPN MCBDB with SS enclosure (607712)
double-door with IP-42/43 protection with dp isolators as incomer and SPMCBs
('C' Curve, 10KA) as outgoing, concealed in wall after cutting the wall & mending
good the damages to original finish including inter connection with suitable size of
copper [LEGRAND make] as follows : 40A DP Isolator, 8 no., 6A SPMCB
Supply and drawing 1.1 KV grade single core standed 'FR' PVC insulated &
unsheathed copper wire (approved make) of the folling sizes through 19mm dia
3mm thick polythene pipe, including cutting channel of 40 x 40mm, size on
masonry wall and S&F polythene pipe, by means of iron hooks and supply &
drawing 18 SWG GI flash wire including mending good damages to building
works and making necessary connection as required:
S&F of compression glands for 2 core 6 sqmm x LPE insulated PVC/A Al. cable
as per GS
Finishing the end of following as per GS
2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) as ECC [from MCBDB to
power plug]
3
5
Connecting the equipments body to earth bus-bar including S&F 25 x 6mm
galvanized (hot dip) MS flat on wall / floor with GI saddees as required and
connection to equipments including drilling holes, with bolts, nuts, washers etc.
(for equipment earthing)
Extra for connecting the neutral of Transformer / Earth bus-bar to earch electrode
including S&F 19/8 Stranded GI (Hot Dip) wire on wall / floor with GI saddles
and insulating the same by one layer of PVC tape over one layer of ampere tape
(flor neutral earthing)
S&F 9 Lt capacity round fire bucket including supplying & fixing of MS hook and
duly filled up by sand, as directed by EIC
Supply & delivery of 6' x 3' x " rubber mat for 6KV Sub-Station (best quality &
ISI approved)
S&F 2 kg. capacity gas pressure (DPC) fire extinguisher (MINIMAX / SUREX)
on wall including supplying & fixing of MS bracket, as directed by EIC
S&F best quality FIRST AID BOX (Al. Body) as per P.W.D. specification,
complete with all the items as required by Rule of Sub-Station, on MS bracket on
wall, including mending good the damages to original finish
S&F Shok Treatment Chart pasted on hard board on wall
S&F 6 KV Grade rubber hand gloves
S&F E I Danger Board of size 20cm x 30cm (8" x 12") on wall
Arrangement for different types of Routine Tests & Commissioning of HTVCB, 1
no. 400KVA 11/0.415KV Transformer and LT panels as per IS-2026, and
commissioning the installation after obtaining the approval from Directorate of
Electricity, as directed by EIC
Internal Electrification Work
Supplying & laying of 1.1KV grade 2 core 6 sqmm. X LPE insulated PVC/A Al.
cable (make Nicco/ISI Mark) [from panel to MCBDB for Sub-Station EI]
Shukla Saha:\\\vboxsrv\conversion_tmp\scratch_1\248641144.xls.ms_officeBOQ
Qty Unit
Rate
(Rs)
Amount
(Rs.)
Description of Materials Sl. No.
6 14 Point 642.00 8,988.00
7 4 Point 60.00 240.00
8 5 Set 261.00 1,305.00
9 5 Set 3,784.00 18,920.00
0.00
i) 7 Set 991.00 6,937.00
11 2 No. 140.00 280.00
Rs. 48,853.00
Part-C WBSEDCL Part
Sl.
No.
Qty. Unit
Rate
(Rs.)
Amount
(Rs.)
1 1 Job 138,000.00 138,000.00
2 200 Mtrs. 80.00 16,000.00
3 40 Mtrs. 2,049.00 81,960.00
4 1 Item 5,000.00 5,000.00
5 2 Set 12,138.00 24,276.00
6 3 Nos 1,800.00 5,400.00
7 50 Mtrs. 194.00 9,700.00
8 25 Mtrs. 500.00 12,500.00
Sub: Total: Rs. 292,836.00
Part - A Installation of Sub-Station equipment Rs. 2,334,370.00
Part - B Internal Electrification work Rs. 48,853.00
Part - C WBSEDCL Part Rs. 292,836.00
Rs. 2,676,059.00
Rs. 31,371.38
Gr. Total: Rs. 2,707,430.38
Say: Rs. 2,707,430.00
Supply and making outdoor type end joint termination of 11 KV grade 3 core 185
sq.mm. H.T. cable by H.T. Heat shrinkble jointing kit etc. complete
Description of Work
Distn. Wiring by 2x22/0.3 (Ph. & N) & 1x22/0.3 (as ECC) single core stranded
'FR' PVC insulated & unsheathed single pin plug point including S&F 250V 5A3-
pin flush type socket & plano key type switch (Anchor make), fixed on sheet metal
(16 SWG) switch board with bakelite/perspex (wall maching colour) top cover
(3mm thick) flushed in wall including mending good damages to original finish
[on existing switch board]
Supply and errection of H.T. lightening arrestor
Supply and laying of 50 x 6 mm G.I. strip for body earth of WBSEDCL Switch
Supply and laying after making of G.I. wire for caddle guard
Supply and errection of rail pole 12.81 mtrs. long 2 nos. rail pole for D.P. structure
for WBSEB service connection fabricated with angles channels Dise insulator
with TPGO gang over switch including stay wire stay set complete
Supply and drawing of 70 sq.mm. ACSR for line taping to D.P. structure
Supply and laying of 11KV grade 3 core 185 sq.mm. Alu XLPE H.T. cable
feeding from WBESB Gang switch to consumer/WBSEDCL's H.T. gear (VCB
switch)
Painting of Rail Pole DP Structure by approved paints over two coats of red lead
primer
Sub-Total
Philips CAT no. TMC 55/136 HPF
Distn. Wiring by 2 x 22/0.3 (Ph. & N) & 1x22/0.3 (as ECC) single core stranded
'FR' PVC insulated & unsheathed single core stranded copper wire (approved
make) in 19mm bore, 3mm thick polythene pipe complete with all accessories
embedded in wall to light/fan/call bell points with plano key type switch [Anchor
make] fixed on sheet metal [16 SWG] switch board with bakelite/perspex (wall
matching colour) top cover (3mm thick) flushed in wall including mending good
damages to original finish [Av. run 8 mt]
Add : Service Tax @ 10.3% on 33% except 1(a) & 2(a) of Part-A on Rs. 922959/-
10
S&F of 11W CFL lamp as per GS
S&F 250V florescent light fittings directly on wall / ceilling with HWround-block
and suitable size MS fastener, ceilling plate, nipples, etc. as required and painting
etc., including S&F 36W tube lamp as required, as directed by EIC, as follows:
S&F 250 V 3-pin 15A flush type-plug socket with 15A plano key type switch
(Anchor make) on sheet metal box with 3mm Thick bakelite top cover and
earthing attachment including S&F sheet metal box of size 175 x 100mm [16
SWG] and bakelite cover as per GS
S&F 250V, 50Hz, 350mm (15") 920 PM sweep heavy duty AC exhaust fan
(EPC), after making hole in wall and making good damages and smooth cement
finish etc. as practicable as possible and providing necessary length of PVC
copper wire and making connections as directed by EIC
Shukla Saha:\\\vboxsrv\conversion_tmp\scratch_1\248641144.xls.ms_officeBOQ
Qty Unit
Rate
(Rs)
Amount
(Rs.)
Description of Materials Sl. No.
Signature of SAE Signature of AE
South 24-Parganas Zilla Parishad South 24-Parganas Zilla Parishad
Signature of DE
South 24-Parganas Zilla Parishad
Shukla Saha:\\\vboxsrv\conversion_tmp\scratch_1\248641144.xls.ms_officeBOQ