1. Available firmware, archives and documentation
Firmware
Mhx file
IL-NT-AMF25-1.5.mhx
IL-NT-AMF20-1.5.mhx
IL-NT-MRS16-1.5.mhx
IL-NT-MRS15-1.5.mhx
IL-NT-MRS11-1.5.mhx
IL-NT-MRS10-1.5.mhx
IL-NT-AMF9-1.5.mhx
IL-NT-AMF8-1.5.mhx
IL-NT-MRS4-1.5.mhx
IL-NT-MRS3-1.5.mhx

Archives
Archives
IL-NT-AMF25-1.5.ail
IL-NT-AMF20-1.5.ail
IL-NT-MRS16-1.5.ail
IL-NT-MRS15-1.5.ail
IL-NT-MRS11-1.5.ail
IL-NT-MRS10-1.5.ail
IL-NT-AMF9-1.5.ail
IL-NT-AMF8-1.5.ail
IL-NT-MRS4-1.5.ail
IL-NT-MRS3-1.5.ail

Documentation
PDF files Description
IL-NT-AMF-1.5.pdf Manual for InteliLite NT AMF gen set controller
IL-NT-MRS-1.5.pdf Manual for InteliLite NT MRS gen set controller
IL-NT-MRS3,4-AMF8,9-1.5.pdf Manual for InteliLite NT MRS3,4-AMF8,9 gen set controller
IL-NT-1.5 New Features.pdf List of new features for software update version 1.5
2. Main changes in IL-NT-1.5
New features

Webserver for IB-Lite supported in IL-NT:
New secured way of monitoring and controlling the genset from any point in world using your web
browser! Clear overview control of the state of engine, its settings and history. Easy and user friendly
usage.
IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz



New features of IL-NT sw V1.5
Page 2 of
13

Scada window:

Measurement window:

Setpoints window:
IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz



New features of IL-NT sw V1.5
Page 3 of
13


History window:


Hint: This feature requires IB-Lite optional plug-in module and visible connection of controller to ethernet.

Measuring core update, support for AI measuring up to 15kOhm
IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz



New features of IL-NT sw V1.5
Page 4 of
13

IL-NT BIO8 Hybrid binary input/output module available
IL-NT BIO8 is optional plug-in card. Through this card controller can accommodate up to 8 binary
inputs or outputs. In LiteEdit PC configuration tool (version 4.4 and higher) it is possible to easily
choose if particular I/O will be binary input or output.

To insert the module, you must open the cover first (use screwdriver to open) and then insert the
module into slot. Once you have inserted it, the module will snap under plastic teeth. It is supposed
to be installed permanently. Should you need to remove it, the safest way is to remove whole back
cover and than remove module manually.
Installing IL-NT BIO8 module is similar to installing RS 232 module. The difference is that module fits
to extension module slot and after installing IL-NT BIO8 you do not put back the small cover.

IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz



New features of IL-NT sw V1.5
Page 5 of
13


Technical details:
IL-NT BIO8 plugs into IC-NT controller EXTENSION MODULE port.
8 dedicated pins of the plug-in cards terminal can be configured as binary inputs or outputs.
Binary inputs
Number of inputs 8
Input resistance 4.7 k
Input range 0-36 VDC
Voltage level for close contact indication (Logical 1) < 0.8 VDC
Voltage level for open contact indication (Logical 0) > 2 VDC
Max voltage level for open contact indication 8-36 VDC
Binary open collector outputs
Number of outputs 8
Maximum current per pin 0.5 A
Maximum switching common current 2 A
Maximum switching voltage 36 VDC
Hint:
Binary inputs are not galvanically isolated.
Total PF value newly calculated as PF = P / S. It will reflect weight of each phase in calculation.
Automatic checking of password during change to be maximally 9999, if it is bigger value it will
be automatically changed to 0. LE will prevent to write bigger value than 9999.
Cyclic rotation of value of password in case of using arrows on controller
Decimal switching for power measurement added
IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz



New features of IL-NT sw V1.5
Page 6 of
13

Possibility to select format for power measurement has been added.
Format can be set via LiteEdit PC configuration tool version 4.4 and higher using its
Units/Formats configuration dialog:

Informations about configured engine ECU (ESF file used) on Init screen of controller
New way of detection of shorted or opened AI sensor
Changed stopping of MAN and Scania engines stop solenoid used
Minor change in TSC1 frame in John Deere - Override Control Mode Priority changed
General update of Cummins CM850
Updated Cummins CM850 frame TSC1 frame is not sent because it caused issues with
controlling the ECU
Newly supported DaimlerChryslerADM2 in ECU lists Mobile a Allspeed. It is not available in ECU
lists InteliLite a Gensets
Customer Logo screen added
Screen dedicated to information provided by customers such as contact numbers, service
technician contact and customer message for end users of gen-set has been added.
Configuration of this screen is only done by LiteEdit PC software (v. 4.4 and higher).
Information is displayed on so called Init Screens which are displayed after controller is
switched on or reprogrammed. It is also possible to call these screens from any measurement
screen by pressing ENTER and PAGE buttons concurrently and then only PAGE button
separately.
IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz



New features of IL-NT sw V1.5
Page 7 of
13


User mode interface as default setting - IL-NT MRS3, MRS4, AMF8, AMF9
Update of AOUT curves new curves available
Power switch function

Power Switch
This switch is assigned to the gen-set active power. The setpoints PowerSwitch ON [kW] and
PowerSwitch OFF [kW] for on and off level adjustment are located in the setpoint group Engine
Params. Typical usage for this binary output can be switching of dummy load. The output behaves
IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz



New features of IL-NT sw V1.5
Page 8 of
13

based on the setpoint adjustment as described on picture lower:

New setpoints:
PowerSwitch ON [kW]
Threshold level for switching the binary output Power Switch on.
Step: 1
Range: 0 32000 kW

PowerSwitchOFF [kW]
Threshold level for switching the binary output Power Switch off.
Step: 1
Range: 0 32000 kW

Temperature switch function

Temp Switch
This switch is assigned to the controllers analog input 2 commonly used for water temperature
sensing. The setpoints TempSwitch ON and TempSwitchOFF for on and off level adjustment are located
in the setpoint group Engine Params. Typical usage for this binary output can be activation of fans or
heaters. The output behaves based on the setpoint adjustment as described on picture lower:
IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz



New features of IL-NT sw V1.5
Page 9 of
13


New setpoints:
TempSwitch ON [-]
Threshhold level for switching on the binary output TempSwitch. This function is connected with
controller's analog input 2.
Step: 1
Range: -100 .. 10000 [-]
TempSwitchOFF [-]
Threshhold level for switching off the binary output TempSwitch. This function is connected with
controller's analog input 2.
Step: 1
Range: -100 .. 10000 [-]

Actually chosen language saved into clone
Switching modes of generator connections based on parameter - Unnecessary generator
values are hidden according to chosen configuration in models IL-NT-MRS10..AMF25.

New setpoint:
ConnectionType [3Ph4Wire / 3Ph3Wire / Split Ph / Mono Ph]
Generator winding connection.
3Ph4Wire: STAR Connection, 3 phases and neutral - 4 wires,
Three phase wye measurement 3PY, 3x CTs
3Ph3Wire: DELTA Connection, 3 Phase without neutral - 3 Wires,
Three phase delta measurement 3PD, 3x CTs
Split Phase: DOUBLE DELTA Connection, Split Phase,
IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz



New features of IL-NT sw V1.5
Page 10 of
13

Single-phase measurement 1PH, 1xCT
Mono Phase: MONOPHASE,
Single-phase measurement 1PH, 1x CT

Renamed setpoint old setpoint Nominal Volts to NomVolts Ph-N
New setpoint NomVolts Ph-Ph
New Timer functions - Scheduled tasks per configuration for models IL-NT-MRS10..AMF25. In
models without history is only one timer available.

AMF models new setpoint:
Timer1..2Function [No Func/TEST/TEST OnLd/MFail Blk/Mode OFF]

It is possible to choose out of 5 following Timer functions. Binary output Exerc Timer X is always
activated when Timer is active regardless of chosen Timer function. Timer functions require controller
running in AUT mode.

No Func: There is no any other function, but binary output Timer1..2 activation.
TEST: When this option is chosen then the Timer output is also internally connected to the Remote
TEST binary input.
TEST OnLd: When this option is chosen then the Timer output is also internally connected to the
Rem TEST OnLd binary input.
MFail Blk: When this option is chosen then the Timer output is also internally connected to the
MainsFailBlock binary input.
Mode OFF: When this option is chosen then the Timer output is also internally connected to the Remote
OFF binary input.

MRS models new setpoint:
*Timer1..2Function [No Func/TEST/TEST OnLd/MFail Blk/Mode OFF]

It is possible to choose out of 3 following Timer functions. Binary output Exerc Timer X is always
activated when Timer is active regardless of chosen Timer function. Timer functions require controller
running in AUT mode.

No Func: There is no any other function, but binary output Timer1..2 activation.
Auto Run: When this option is chosen then the Timer output is also internally connected to the Remote
start binary input.
Mode OFF: When this option is chosen then the Timer output is also internally connected to the Remote
OFF binary input.

Support for hebrew font
DiagData value implemented for ComAp dignostics purposes
Unified latin fonts of texts in chinese language
New available dictionaries and updated older dictionaries German, Spain, French, Hebrew,
Chinese, Italian, Niederland, Portuguese and Russian
New context helps for setpoints, binary inputs / outputs and values in LiteEdit
Optional size of history based on configuration of additional peripheries like ECU or extension
modules. Unnecessary columns are hidden in history.
Running Hours switching improved
Running Hours switching between ECU and controller in case of ECU value is not valid has
been improved.


Repairs
IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz



New features of IL-NT sw V1.5
Page 11 of
13

Iveco Nef & Kursor / ECU Running Hours reading problem fixed
Problem with ECU Running Hours reading for Iveco Nef & Kursor engines has been fixed.
ScaniaS6AuxII / ECU DLN1 frame not sending problem fixed
Problem with ECU DLN1 frame not sending for ScaniaS6AuxII engine has been fixed.
Added BO Exerc Timer 1 to applications MRS10, MRS11 a AMF20

3. Main changes in IL-NT-1.4
New features

Improved characteristics of electrical measurement
Changed range of setpoint Nominal Power to 1..5000 [kW]
Text length of parameters in setpoints screen of controller has been enlarged to 9 characters
Changes in texts:

Old Text New Text Note
ProtectHoldoff ProtectHoldOff
Fwd Return Del Transfer Del
ValidFlt Start Del In Timer (default measuring
screen)
ValidFlt MainsFlt State of electrical automat
RetTransf ReturnDel
FwRet Brk Trans Del
Maintenance WrnMaintenance Text of setpoint
Sd StartFail Sd Start Fail
AutoMains Fail AMF Settings
FltResGoToMAN Reset To MAN
SD RPMMeasFail Sd RPMMeasFail
Diagnostic ECU ECU State
YellowLamp ECU ECU YellowLamp
Red Lamp ECU ECU RedLamp
WaitToStrt ECU ECU WaitToStrt
Gen-set Start Manual Start
Gen-set Stop Manual Stop
MainsFailStart AMF Start
MainsFail Stop AMF Stop
Gen Rem Start Remote Start
Gen Rem Stop Remote Stop
- Test Start Start of gen-set in case of
controller mode switched to TEST
Gen-set Stop Gen-set Stop
Stop in case of shutdown
Led MCB fdb -
Removed
Led GCB gr Led GCB Green

Led MCB gr Led MCB Green

Led GEN gr Led Gen Green

Led GEN red Led Gen Red

Led MAINS gr Led MainsGreen

Led MAINS red Led Mains Red

IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz



New features of IL-NT sw V1.5
Page 12 of
13

Gen freq Gen Freq

Mains freq Mains Freq

Gen Load char Gen Load Char

Ig nom Ig Nom

Under limit Under Limit

Over limit Over Limit

Over limit+Fls Over Limit+Fls

No protection No Protection

Sensor fail Sensor Fail

MCB close MCB Close

GCB open GCB Open

Fuel level Fuel Level

Fault reset Fault Reset

User mode User Mode


4. Main changes in IL-NT-1.3
New features

Improved characteristics of electrical measurement
Support for COM terminal at analog inputs support of HW version 1.3
Support of dual port communication modules, such as IL-NT RS232+RS485
Switchable User Interface in controller two modes User and Engineer
Register oriented modbus added
Both Stop button and Stop Button LBI has unified function stop command is repeated each 2
seconds while button is pressed/switched on.
Unified function of Start button and Start Button LBI. While pressing button/switch on LBI, first
command to start/prestart is issued immediately, Idle can be skipped after 2 seconds. Prestart cant
be skipped. Only edge of signal is evaluated
Newly is in engines driven by TSC1 frame altered value of bits 5-8 as 0xFF
MAN engines support for reading of diagnostic messages from multiple sources
Statistics can be changed only after password is filled in
Changed default curve for VDO 50-150
Alarm RPM Meas Fail renamed to SD RPMMeasFail
Updated chinese and spanish dictionaries
Range of AI1-3 Del and IOM AI1-3 Del setpoints extended to 900s
When IG-IOM/IGS-PTM module is not configured, relevant values and setpoints are hidden in
controller
Range of Maintenance setpoint lowered to 0..10000 hours
When Maintenance is setted to value 10000, maintenance counter is hidden in controller and does
not count. Default value is 9999 hours
Fuel Pump ON, Fuel Pump OFF setpoints moved to group Engine Params
Run Hours value is counted and displayed with one decimal
If the Run Hours value is negative number or goes over the range, it is changed to 0 and counter
continues
SMS/Active calls setpoint changed
New LBO Al Mains Fail
Range of EmergStart Del extended to 6000s
Mode of controller in history is displayed as text (OFF/MAN/AUT/TEST)
IG-IOM/IGS-PTM module relevant setpoints moved to common group Extension I/O
IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz



New features of IL-NT sw V1.5
Page 13 of
13

IL-NT V1.5 New Features / ComAp October 2009 / IL-NT-1.5 New Features.pdf


ComAp, spol. s r.o.
Kundratka 2359/17
180 00 Prague 8
Czech Republic
ISO 9001 Certified
C
o
m
Ap s
.r
.
o
.
Q
u
a
lit
y
Mana
g
e
m
e
n
t

Tel.: +420 246 012 111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz


At models MRS10-AMF25 changed alarm Wrn Batt Low to Wrn Batt Volt due to new setpoimt
Batt Overvolt
Renamed BOUT AL BatteryFlat in models MRS10-AMF25 to AL BatteryFail
Changed behavior of ECU SpeedAdj setpoint: For value 0% it request engine speed equal to
90% on nominal speed. For value 50% it request 100% of nom. speed. And for 100% it request
110% of engine nominal speed
Changed order of columns in history
Unified behavior of LBI Access Lock with InteliLite Classic controllers, Access Lock block only
change of mode and change of setpoints.
New setpoints Batt Overvolt, Cooling Speed, COM2 Mode, ModemIniString,
ModbusComSpeed
Changed list of options at setpoint COM1 mode


Repairs
Support of portugese and other west europe fonts improved
Wrong name of setpoint IOM AI3 Sd changed to IOM AI2 Sd
IG-IOM/IGS-PTM bargraphs had wrong range fixed
Part of events in history in models MRS15 and MRS16 were wrongly interpreted fixed
In MRS11 and MRS16 models controller did not colesd GCB in AUT mode fixed
Fixed evaluation of protections of binary inputs at IG-IOM/IGS-PTM.