Modular Cylindrical
FM-200™ Agent Storage Container
P/N 93-120XXX-001
93.120X-1
DESCRIPTION
These cylindrical agent storage containers, which are less
than ten inches high and contain from 20 to 30 pounds of
FM-200, are ideal for height-limited locations such as un-
der-floor applications. They are equipped with a pressure
gauge, a burst disc type discharge valve, a replaceable ini-
tiator will assembly a screen assembly, cable assembly,
mounting brackets and safety plug. Each ASC has a boss-
mounted check valve which accepts and optional Pressure
switch (see Fenwal Data Sheet 93.3119.0) and is used for
recharging the container
Initiator assemblies must be ordered for each container. See
Fenwal data Sheet 93.1932.0 for information.
Total pressure in a filled container is adjusted to 360 psi at
70oF by superpressurizing with dry nitrogen.
Nozzles and piping selected shall ensure a minimum dis-
charge rate of 84 lbs. FM-200 agent per second at the mini- A. QUARTERLY INSPECTION
mum operating temperature. Operating temperature shall 1. Check the pressure gauge. If the pressure is less than
be limited to 32o to 130oF. Nozzles and piping must be in 325 psig at 70oF (22.9 Kg/cm2 at 21oC) the container
accordance with Fenwal FM-200 Design Manual. must be removed by qualified personnel, inspected care-
fully then recharge or replaced as required. Pressure
OPERATION will vary with temperature. In the range of 55 to 85oF
The container is discharged when its initiator is actuated to (12.8 to 29.4oC), this change is approximately 3 psi per
rupture the burst disc valve. degree F (0.397 Kg/cm2 per degree C).
INSTALLATION 2. Check all components supporting hardware and tighten,
repair or replace as required.
The container must be securely mounted in position with the
valve down using the integral mounting brackets. The cen- 3. Visually check all components for evidence of physical
ter of four slots are located at the corners of a rectangle 8-1/ abuse and take whatever action is indicated. Replace
2 in. wide by 11-11/16 in. long. Use four 5/16 in. bolts or any component if at all in doubt of its ability to perform
studs to secure the container to a solid surface. properly.
The 93-120251-001 unit has mounting brackets on the bot- B. SEMI-ANNUL INSPECTION
tom as shown at right and the 93-120253-001 unit has the Qualified personnel are to remove and weight all agent stor-
mounting brackets on top. The 93-120351-001 and 93- age containers. Losses in net weight of agent must not ex-
120353-001 units have mounting brackets on the dies. All ceed 5% or 10% under pressure loss adjusted for
units must be mounted with the valve at the bottom: either temperature. Container, and agent weight are marked on
parallel to the floor or facing down. If not mounted in this the mounting bracket.
manner, proper discharge will not be possible. All outlet piping must be clean and free of dirt, chips, filings
After the container is secured in place, remove the safety and other foreign material that my become hazardous pro-
plug and screw the screen assembly into the valve body. jectiles or cause the system to become inoperative or inef-
Then connect the rest of the piping and nozzle specified in fective at the time of discharge.
the system drawing. Retain the safety plug for use when NOTE: The safety plug shipped with the container must be
reconditioning the container or whenever a filled container retained and secured to the container whenever the
is moved. piping is removed from a charged container.
MAINTENANCE Charged containers must have safety plug in-
stalled when removed from system for shipment.
The following inspection and/or maintenance procedures
should be scheduled or performed upon the occurrence of
any even which might bias the reliability of the system.
1
RECONDITIONING gauge and pressure switch assembly (optional). The con-
After a system has been actuated, it is recommended that tainers shall hold from 20 to 30 lbs. of FM-200 agent.
the local authorized Fenwal distributor be contacted to re- Container shall conform to all applicable specifications of
condition the system. Department of Transportation.
The Reconditioning Kit for this unit is P/N 31-193005-001. The burst disc valve assembly shall be an integral part of
This kit does not contain the initiator, which must be ordered the agent storage container and shall be operated by apply-
separately. ing electrical current to an initiator assembly which has an
electro-explosive device that provides on demand, and in-
SPECIFICATIONS stantaneous full bore release and discharge of the agent.
Cylinder Diameter: 9-3/8” (239mm) Valves with moving parts and seals are not acceptable.
Overall Height: 9-7/8” (251mm) Filled containers shall be super-pressurized with dry nitro-
Overall Length: 19-1/2” (495mm) gen to 360 psig at 70oF to aid in rapid agent distribution,
Empty Weight: 24 lbs. (10.8 Kg) approx. particularly at lower temperatures. It shall automatically re-
lieve between 850 to 1000 psi in even of excessive pressure
Volume: .442 cu. ft. (12.52 L) build up.
Minimum Fill: 20 lbs. (9.07 Kg) Devices and connecting leads shall be completely super-
Maximum Fill: 30 lbs. (13.61 Kg) vised.
ARCHITECT/ENGINEER SPECIFICATIONS The container design shall permit on-site reconditions and
refilling.
The agent storage container shall be a Fenwal cylindrical
(refillable) FM-200 container constructed of high strength low The integral mounting assembly shall provide a means for
HSLA alloy steel. It shall consist of: fill valve, burst disc valve mounting to a solid vertical or horizontal surface and shall
assembly, initiator, safety plug, screen assembly, cable as- withstand a thrust of 1000 lbs. for 5 seconds in any direc-
sembly, integral supporting flanges, 0-100 psig pressure tion.
www.fenwalfire.com R
93.120X-1 8/99 ©Kidde-Fenwal, Inc. Printed in U.S.A. CP
Protection Systems
Spherical Agent Storage
Effective: March 2000
Container
FM-200™ Agent Storage Container
P/N 93-11020X-001 93.1120.1
FEATURES
• 4 Convenient Sizes
• 20 to 196 Pound Capacities
• UL Listed, FMRC Approved
• Requires No Floor Space
• Electric Initiator Actuation
DESCRIPTION
Fenwal Modular Spherical Agent Storage Containers store
FM-200 super-pressurized with dry nitrogen to 360 psig at
70oF. These containers hold from 20 to 196 pounds of FM-
200 and are equipped with a burst disc type discharge valve,
a replaceable initiator well, a screen assembly, safety plug
and cable assembly. Each container has two identical boss-
mounted check valves which will accept a pressure gauge
(standard), and an optional pressure switch (see Data Sheet
93.3119.0). Either of these check valves may be used for
recharging the container.
Initiator assemblies must be ordered for each container. See 2. Check all component supporting hardware and tighten or
Data Sheet 93.1932.0 repair as required.
OPERATION 3, Visually check all components for physical abuse and
The container is discharged when the initiator is actuated to take whatever action is necessary. Replace the compo-
rupture the burst disc valve. nent if at all in doubt as to its ability to perform properly.
B. SEMI-ANNUAL INSPECTION
INSTALLATION
Qualified personnel are to remove and weigh all agent stor-
The container must be rigidly mounted in position with the age containers. Losses of agent must not exceed 5% in net
valve facing down. Fenwal mounting brackets provide a se- weight, or 10% reduction of pressure (adjusted for tempera-
cure means for wall mounting containers. A lifting ring on ture). Container and agent weight are marked on the
the container provides a means for raising the container to container’s nameplate.
its mounting location.
All outlet piping must be clean and free of dirt, chips, fillings
After the container is secured in place, remove the safety and other foreign material that may become hazardous pro-
plug and connect the rest of the piping and nozzles(s) speci- jectiles or cause the system to become inoperative or inef-
fied in the system drawing. Retain the safety plug for use fective at the time of the discharge.
when reconditioning the container and whenever a filled con-
tainer is moved. NOTE: The safety lug shipped with this container should be
retained and secured to the container whenever the
MAINTENANCE piping is removed from a charge container. Charged
Inspection and/or maintenance procedures should be sched- containers must have the safety plug installed
uled as listed below, or performed when an event occurs when removed from the system for shipment.
which might affect the reliability of the system. Observe proper handling procedures when in-
stalling or removing the initiator.
A. QUARTERLY INSPECTION
1. Check the pressure gauges of each agent storage con- RECONDITIONING
tainer. If the pressure is less than 325 psig at 70oF (22.9 After a system has been actuated, it is recommended that
Kg/cm2 at 21oC), the container should be removed and the local authorized Fenwal Distributor be contacted for re-
carefully inspected by qualified personnel. It should then conditioning the system.
be reconditioned, recharged or replaced depending upon The Reconditioning Kit for this unit is P/N 31-193005-001
its condition. Pressure varies with temperature, and in This kit does not contain the initiator, which must be ordered
the range of 55oF to 85oF (12.7oC-29.4oC) this change is separately.
approximately 3pse/oF (.38 Kg/cm2/oC)
1
ARCHITECT/ENGINEER SPECIFICATIONS Sphere
The agent storage container shall be a Fenwal modular Part No. Diameter Height* Empty WT**
spherical (refillable) container constructed of high strength,
IN mm IN mm LB Kg
low HSLA alloy steel. It shall consist of: fill check valve, burst
disc valve assembly, integral supporting flanges, 0-700 psig 93-110201-001 13.2 334 20.7 525 28.5 12.9
pressure gauge and pressure switch assembly (optional). 93-110202-001 14.8 377 22.4 569 36.7 16.6
The containers shall hold from 20 to 196 lbs. Of FM-200 93-110203-001 17.3 439 24.9 634 52.0 23.6
agent.
93-110204-001 21.5 547 29.3 745 99.1 45.0
Containers shall conform to too applicable specifications of
Dept. of Transportation, Underwriters Laboratories, and Fac- *Height is from top of lifting ring to bottom surface of flange.
tory Mutual Research Corp. Flange mounting holes 5/8 in. (15.9 mm) diameter located
on bolt circle 6-5/8 in. (162.3 mm) diameter. Flange is 1.4 in
The burst disc valve assembly shall be an integral part of
(6.4 mm) thick for all models except for 90-110204-001, which
the agent storage container and shall be operated by apply-
is 3.8 in. (9.5 mm).
ing electrical current to an initiator assembly, which has a
electro-explosive device that provides an instantaneous full **Average weight for shipping and mounting planning. Ac-
bore release and discharge of the agent on demand. The tual weight stamped on each unit.
releasing mechanism shall contain no moving parts. Fill Range Capacity
Filled containers shall be super-pressurized with dry nitro- Part No.
LB Kg Ft3
m3
gen to 360 psig at 70oF to aid in rapid agent distribution,
particularly at lower temperatures. It shall automatically re- 93-110201-001 20-44 9.1-20 .656 .019
lieve between 850 to 1000 psig in the event of excessive 93-110202-001 28-63 12.7-29 .932 .026
pressure build-up. 93-110203-001 45-101 20.3-46 1.488 .042
Releasing devices and connecting leads shall be completely 93-110204-001 85-196 38.6-89 2.833 .080
supervised.
The mounting bracket shall be designed for installation on a
wall, floor or other rigid surface and shall serve as support
for the agent storage container, and shall be capable of with-
standing a thrust of 1000 lbs. For 5 seconds in any direction.
www.fenwalfire.com R
93.1120.1 3/00 5M ©Kidde-Fenwal Inc. Printed in U.S.A. CP
Protection Systems
Effective: August 1999
Floor Mounted Spherical
FM-200™ Agent Storage Container
P/N 93-190000-00X
93.1225.1
FEATURES
• Designed for Under Floor Installation
• Contains 10 to 15 lbs. of FM-200 Agent
• UL Listed/FM Approved
• DOT Shipping Container
DESCRIPTION
This FM-200 spherical agent storage container is less than
10 inches in height to fit under most raised floors and con-
tains from 10 to 15 pounds of FM-200 superpressurized to
360 psig with dry nitrogen.
Each assembly is equipped with pressure gauge, burst disc
type discharge valve, replaceable initiator well, safety plug,
screen assembly, cable assembly and mounting brackets.
Each ASC has a boss-mounted check valve which accepts
and optional Pressure Switch (see Fenwal Data Sheet
93.3119.0) and is used for recharging the container. B. SEMI-ANNUAL INSPECTION
Initiator assemblies much be ordered for each container. See Qualified personnel are to remove and weight all agent stor-
Fenwal Data Sheet 93.1932.0 for ordering information age containers. Losses in net weight of agent much not ex-
OPERATION ceed 5 percent. Loss in pressure (adjusted for temperature)
must not exceed 10 percent. Container and agent weight
The container much be securely mounted to a rigid surface
are marked on the inspection tag.
with the valve horizontal/parallel to floor or down. Four holes
in the mounting brackets are drilled to accept 5/16 inch All outlet piping must be cleaned and free of dirt, chips, fil-
mounting bolts. The centers of the mounting holes are lo- ings and other foreign material that may become hazardous
cated at the corners of a rectangle 6.38 inches wide by 8.38 projectiles or cause the system to become inoperative or
inches long. ineffective at the time of discharge.
NOTE: The safety plug shipped with this container should
MAINTENANCE be retained and secured to the container whenever
The following inspection and/or maintenance procedures the piping is removed from a charge container.
much be scheduled as listed below or performed upon oc- Charged containers much have safety plug installed
currence of any event which might affect the reliability of a when removed from system for shipment. Observe
system. proper handling procedures when installing or re-
A. QUARTERLY INSPECTION moving the initiator.
1. Check the pressure gauges of each container. If the pres- RECONDITIONING
sure is less than 325 psig at 70oF (22.9 Kg/CM2 at 21o After a system has been actuated, it is recommended that
C), the container should be removed by qualified per- the local authorized Fenwal Distributor be contacted for re-
sonnel and carefully inspected, then reconditioned, re- conditioning the system. Refer to, “Filling and Recondition-
charged or replaced as its condition warrants. Pressure ing Fenwal’s FM-200 Agent Storage Containers.”
will vary with temperature. In the range of from 55 to
The Reconditioning Kit for this unit is P/N 31-193005-001.
85oF (12 to 29o C) this change is approximately 3 psi per
This kit does not container the initiator, which must be or-
degree F (.38 kg/cm2/oC).
dered separately.
2. Check all component supporting hardware and tighten
or repair as required.
3. Visually check all components for evidence of physical
abuse and take whatever action is indicated. Replace
the component if at all in doubt of its ability to perform
properly.
1
SPECIFICATIONS The burst disc valve assembly shall be an integral part of
Diameter: 9-3/8” (239mm) the agent storage container and shall be operated by apply-
ing electrical current to an initiator assembly which has an
Overall Height: 9-7/8” (251mm)
electro-explosive device that provides, on demand, and in-
Overall Length: 19-7/8” (495mm) stantaneous full bore release and discharge of the agent.
Empty Weight: 24 lbs. (10.8 Kg) Approx. The releasing mechanism shall contain no moving parts.
ARCHITECT/ENGINEER SPECIFICATIONS Filled containers shall be super-pressurized with dry nitro-
gen to 360 psig at 70oF to aid in rapid agent distribution,
The agent storage container shall be a Fenwal cylindrical
particularly at lower temperatures It shall automatically re-
(refillable) FM-200 container constructed of high strength
live between 850 to 100 psig in event of excessive pressure
low HSLA alloy steel. It shall consist of: Fill Valve, burst disc
build up.
valve assembly, initiator, safety plug, screen assembly, cable
assembly, integral supporting flanges, 0-700 psig pressure Releasing devices and connecting leads shall be completely
gauge and pressure switch assembly (optional). The con- supervised
tainers shall hold from 10 to 15 lbs. of FM-200 agent. The container design shall permit on-site reconditioning and
Container shall conform to all applicable specifications of refilling.
Department of Transportation, Underwriters Laboratories, The integral assembly shall provide a means or mounting to
Inc., and the Factory Mutual System. a solid vertical or horizontal surface and shall withstand a
thrust of 1000 lbs. for 5 seconds in any direction.
Tank construction per DOT-4BA-500.
www.fenwalfire.com R
93.1225.1 8/99 ©Kidde-Fenwal, Inc. Printed in U.S.A. CP
Protection Systems
FM-200® BOTTOM DISCHARGE Effective: September 1999
FEATURES
• 150-350, 240-560, and 370-850-lb. Capacities
• Electric Initiator Actuation
• 3-inch Discharge Valve
• Optional Liquid Level Indicator
• Standard Low Pressure Supervisory
Pressure Switch
• UL Listed
• FM Approved
DESCRIPTION
Fenwal FM-200 Bottom Discharge Agent Storage Contain-
ers store FM-200 super-pressurized with dry nitrogen to 360
psig (70oF). They are painted red and are equipped with a 3-
inch burst disc type discharge valve, a replaceable initiator
well, a screen assembly, pressure gauge, supervisory pres-
sure switch with cable assembly, fill port, overpressure relief
valve, safety cap, liquid level measuring device (optional)
and lifting lugs. A 3-inch Flex Hose (P/N 29-117134-002) is
available to facilitate piping connections. Initiator assemblies
P/N 93-191001-001 must be ordered for each container.
OPERATION
The agent storage container discharges when the initiator is
actuated, causing the burst-disc valve to rupture.
MAINTENANCE
According to NFPA standards the following inspection and/
INSTALLATION or maintenance procedure must be scheduled as listed be-
low and performed upon the occurrence of any event which
The container is installed in a vertical position with the valve might affect the reliability of the system.
assembly pointing up. Interconnection for discharge piping
is 3-inch NPT. A 3-inch flex hose is available to facilitate QUARTERLY INSPECTION
connection between the container and discharge piping. A 1. Check the pressure gauges of each agent storage con-
3-inch, 300-lb. malleable-iron threaded pipe union manufac- tainer. If the pressure is less than 325 psig at 70oF (22.9
tured per ANSI B16.39 is required to mate the tank discharge kg/cm2 at 21oC), the container should be removed and
port to the flex-hose assembly. carefully inspected by certified personnel. It should then
The container is secured in place by two mounting brackets be reconditioned, recharged or replaced as it’s condi-
(P/N 29-232334-00X) which are bolted together around the tion indicates. Pressure varies with temperature. In the
container and affixed to a solid wall or a strut assembly. Two range of 55 to 85oF (12.8 to 29.4oC) change is approxi-
1/2-inch diameter bolts are required to secure the mounting mately 3 psi per degree F (0.397 kg/cm2 per degree C).
brackets to a vertical surface and two 1/2-inch diameter 9- 2. Check all component supporting hardware and tighten,
inch long threaded rods are needed to hold the two mount- repair, or replace as required.
ing brackets together. 3. Visually check all components for evidence of physical
After the container is securely mounted, it is connected to abuse and take whatever action is required. Replace
discharge piping per the system drawings. The initiator as- any component if at all in doubt of its ability to perform
sembly is then installed. properly.
1
SEMI-ANNUAL INSPECTION SPECIFICATIONS
Qualified personnel are to determine the amount of agent in AGENT STORAGE CONTAINERS
all containers. The optional liquid level indicator may be used
to measure agent supply and compare it to the original net 93-192041-00X 93-192040-00X 93-192042-00X
weight which is marked on the container label. If the mea-
Fill Range
sured net weight is less than 95% of the original charged net (lb. w/o LLI)
150-350 240-560 370-850
weight the container should be tested for leakage, recharged
and reinstalled. Fill Range
200-350 320-560 480-850
(lb. w/ LLI)
Inspect all piping, fittings and nozzles for looseness, dirt or
other damage. All outlet piping must be clean and free of Height
57 58.5 60.5
(in.)
dirt, chips, fillings and other foreign material that may cause
the system to become inoperative or ineffective at the time Diameter
16 20 24
of discharge. (in.)
Internal Volume
5 8 12
(cu. ft.)
RECONDITIONING Empty Weight
250 350 480
After a system has been discharged, it is recommended that (lb.)
the local authorized Fenwal distributor be contacted to re- Maximum
600 910 1330
condition the system. Static Load
The reconditioning kit for these containers is P/N 31-193017- Temperature
32 to 130o F (0 to 54o C)
001. The initiator, not included, is ordered separately. Range
Safety Relief
850 to 1000 PSIG
Burst Range
ORDERING INFORMATION
Construction
KEY TO PART NUMBERS DOT-4BW500
Specification
Bracket (Black)
(Two Required 29-232334-004 29-232334-002 29-232334-000
per Container)
LLI
283894
Tape Assembly
LLI
Rod Assembly 31-194099-012 N/A
(Pre-Sept. 99)
2
DIMENSIONAL INFORMATION
TANK AND BRACKET DIMENSIONS BRACKET OUTLINE
9 3 -1 9 2 0 4 1 -0 0 X 9 3 -1 9 2 0 4 0 -0 0 X 9 3 -1 9 2 0 4 2 -0 0 X
D imen sio n
5 ft.3 (350 lb.) 8 ft.3 (560 lb.) 12 ft.3 (850 lb.)
(in .) G
A 57 58-1/2 62-1/4
B 16-1/2 16-1/2 17
C 16 20 24 J
D 7-1/8
E 7-7/8
F 4-3/16
H
G 5-5/8 7-1/4 8-3/4
I
H 19-1/4 22 26-5/8
R R
INSPECTION
TAG
F
B
E
NO LIFT NO LIFT
3
ARCHITECTURAL AND ENGINEERING
SPECIFICATIONS
The FM-200 shall be stored in vertically mounted cylindrical A compatible flex hose shall be available to facilitate instal-
containers with a 3-inch burst disc type discharge valve. Con- lation and connection to discharge piping.
tainers shall be super-pressurized with dry nitrogen to 360 psig The container shall be secured in place by two opposing
at 70oF. This container shall be Fenwal P/N 93-19204X-00X. steel mounting brackets. These brackets shall be Fenwal
Containers shall be U.L. Listed and FMRC Approved. P/N 29-232334-00X.
Each agent storage container shall have a fill range of 150-
350, 240-560, or 370-850 lbs. and be of a construction that
complies with DOT-4BW500.
The agent storage container shall incorporate lifting lugs, over-
pressure relief, 3-inch burst-disk type discharge valve, fill port,
cable assembly, pressure gauge, supervisory pressure switch,
liquid-level indicator (optional), and a safety cap. Electrical
device’s connecting leads shall be completely supervised.
www.fenwalfire.com R
93.1920.1 9/99 ©
1999 Kidde Fenwal Inc. Printed in USA
Protection Systems
Effective: August 1999
Initiator Assemblies
for Fire Suppression Systems
P/N 93-199932-00X
93.1932.0
DESCRIPTION
Initiator assemblies are used in Fenwal Fire Suppression
System to rupture the burst disc valve in Fenwal agent stor-
age containers.
! WARNING
The initiator is a Class “C” explosive. It must be
handle and stored in accordance with
appropriate local regulations governing Class
“C” explosives. The local Fire Marshall should
! CAUTION
Never handle, transport, store, or install the
initiator assembly unless the shorting cap
supplied with the assembly is properly secured Table 1
to its threaded end. Safety glasses or a face
shield must be worn when handling these MAX. EXPOSED TEMP. SERVICE LIFE
devices. Improper handling, misuse or abuse of
YEARS
this device can cause bodily injury. Fo Co
OPERATION 80 27 5
The initiator assembly is activated by an electrical current of
100 38 3
2.0 amps. The assembly is destroyed by its operation and
must be replaced whenever a system is actuated. 120 49 2
INSTALLATION 140 60 1
The initiator assembly is inserted into a well in the agent
At the end of it’s service life or seven years, whichever oc-
storage container. Consult Fenwal Publication 93-FM200M-
curs first, in initiator assembly must be removed and de-
004 and/or 93-FM200M-003 for details on the proper instal-
stroyed in accordance with local regulations.
lation and testing procedures for this device.
If an initiator is installed in an agent storage container that
MAINTENANCE has relieved as a result of an over-pressure, both the initia-
The initiator assembly should be stored in an area main- tor and well assembly should be replaced regardless of the
tained at 70-75oF (21-24oC). The storage area must be dry initiator’s age. The initiator must be destroyed in accordance
and secure from unauthorized access to these units. The with local regulations.
combined shelf life and service life of an initiator assembly SPECIFICATIONS
shall not exceed seven (7) years. The service life varies with
the maximum temperature to which it is exposed for an ap- Assembly
Dim. "A" Appropriate
Weight
preciable length of time. See Table 1. ASC
Part No. Oz . Gm. In. mm
Protection Systems
Effective: August 1999
FM-200™ Pendant Nozzles
P/N 93-1940.1
93.1940.1
FEATURES
• 180o and 360o Styles
• Six Pipe Sizes - 1/2” to 2” NPT
• Specially designed for FM-200
• Uniform Agent Distribution
• Custom Orifice Sizing
• UL Listed
• FMRC Approved
DESCRIPTION
These nozzles are used in Fenwal FM-200 Fire Suppres-
sion Systems to disperse FM-200 uniformly throughout the
hazard area. Patterns direct discharged FM-200 parallel to
the ceiling. Nozzles are available to discharge in either 180o
or 360o patterns, depending on location within the hazard
area. A selection of orifices is available for each nozzle size
to provide correct sizing for appropriate agent distribution.
Nozzles are constructed of brass, nozzle sizes are 1/2, 3/4,
1/ 1-1/4, 1-1/2 and 2 inch NPT. See Ordering Information for 360o Nozzle
sizes and part numbers.
DESIGN/INSTALLATION
The nozzles are equipped with female National Pipe Threads
and provide and equal distribution of agent throughout the
protected area. Nozzles should be mounted in a downward
vertical position only. The Placement of the nozzles for ad-
equate coverage to all portions of the hazard area is deter-
mined by considering the indicated throw of each nozzle.
When using large nozzles in an area where smaller nozzles
have a sufficient throw, care should be used to avoid any
unnecessary and unwanted turbulence.
ARCHITECT/ENGINEER SPECIFICATION
This FM-200 Fire Suppression System shall use discharge
nozzles that distributed the FM-200 uniformly throughout the
protected area. The nozzle shall be Fenwal P/N 93-1940XX-
XXX.
180o Nozzle
1
OUTLINE DIMENSIONS (INCHES)
360o NOZZLE
Pipe Siz e A B C D
1/2" (12.2mm) 1.250" (31.75mm) 1.468" (37.28mm) 1.937" (49.19mm) 1.250" (31.75mm)
3/4" (19.05mm) 1.500" (38.1mm) 1.578" (40.08mm) 2.125" (53.97mm) 1.500" (38.1mm)
1" (25.4mm) 1.750" (44.45mm) 1.718" (43.63mm) 2.375" (60.32mm) 1.750" (44.45mm)
1-1/4" (31.75mm) 2.250" (57.15mm) 1.950" (49.53mm) 2.750" (69.85mm) 2.250" (57.15mm)
1-1/2" (38.1mm) 2.500" (63.50mm) 2.000" (50.80mm) 2.937" (74.59mm) 2.500" (63.50mm)
2" (50.8mm) 3.000" (76.20mm) 2.062" (52.37mm) 3.125" (79.37mm) 3.000" (76.20mm)
180o NOZZLE
Pipe Siz e A B C D
1/2" (12.2mm) 1.250" (31.75mm) 1.250" (31.75mm) 1.687" (42.84mm) 2.000" (50.8mm)
3/4" (19.05mm) 1.500" (38.1mm) 1.375" (34.92mm) 1.950" (48.89mm) 2.296 (58.31mm)
1" (25.4mm) 1.750" (44.45mm) 1.562" (39.67mm) 2.218" (56.33) 2.671" (67.84mm)
1-1/4" (31.75mm) 2.250" (57.15mm) 1.750" (44.45mm) 2.656" (67.46mm) 3.250" (82.55mm)
1-1/2" (38.1mm) 2.500" (63.50mm) 1.950" (48.89mm) 2.950" (74.93mm) 3.625" (92.07mm)
2" (50.8mm) 3.000" (76.20mm) 1.968" (49.98mm 2.875" (73.02mm) 3.656" (92.86mm)
www.fenwalfire.com R
93.1940.1 8/99 ©Kidde-Fenwal, Inc. Printed in U.S.A.
Protection Systems
Pressure Switch Assembly
Effective: January 2000
P/N 31-194133-0X
93.3119.0
FEATURES
• Easy Installation
• Available Normally Open or Normally Closed
• Explosion Resistant Cable Option
DESCRIPTION
This pressure switch assembly mounts directly to a check
valve on Fenwal spherical FM-200® agent storage contain-
ers to trigger a TROUBLE condition when container pres-
sure drops below 200 psig ±15 psi. Assemblies are available
with normally open or normally closed contacts, and with
standard or explosion resistant cable assemblies.
OPERATION
Normally Open - The pressure switch contacts are closed
when the container is pressurized in accordance with speci-
fications. The contacts open when pressure drops below 200
psig.
Normally Closed - The pressure switch contacts are open
when the container is pressurized in accordance with speci-
fications. The contacts close when pressure drops below
200 psig.
ORDERING INFORMATION
! CAUTION
Pressure in a normally filled container will drop Standard Pressure Switch Assembly -
below 200 psig at or below a temperature of Normally Open: P/N 31-194133-001
+10oF (-12oC). Accordingly, this modification is W/Explosion Resistant
not recommended for low temperature Cable Assembly*: P/N 31-194133-002
applications. Standard Pressure Switch Assembly -
INSTALLATION Normally Closed: P/N 31-194133-00
To install the pressure switch assembly, first unscrew the W/Explosion Resistant
guard around the unused boss on the container and remove Cable Assembly*: P/N 31-194133-004
the safety plug from the check valve. Secure the check valve
hex with a wrench to guard against loosening the check valve.
Screw the pressure switch into the check valve 3 turns be- SPECIFICATIONS
yond hand tight and then attach the cable assembly by screw- Current Rating: 1 amp @ 120/240VAC,
ing the housing over the threaded boss. Connect the cable Resistive 2 amps @ 24 VDC
assembly to the control unit in accordance with the system
Contacts Open: 200 ±15 psig
schematic.
*Explosion resistant cable assemblies for Class 1, Groups C and
! CAUTION D; Class 2, Groups E, F and G locations.
Use wrench on check valve to avoid over
ARCHITECT/ENGINEER SPECIFICATIONS
tightening and when loosening components for
removal. The Pressure Switch Assembly shall be used with Fenwal
spherical FM-200 agent storage containers to provide su-
pervision of loss of pressure and/or extinguishing agent by
indication of a Trouble signal at the Fenwal control unit. It
shall consist of a cable assembly and a pressure switch. It
shall be mounted directly on the container by means of a
1
boss-mounted check valve to facilitate removal of the pres-
sure switch without losing FM-200 agent.
Normally Open - The contacts of the switch shall be closed
when the container is pressurized in accordance with speci-
fications. The contacts will open when container pressure
drops below 200 ±15 psig. This switch shall not be used for
applications where ambient temperatures could drop to 10oF
(12oC) or lower as this temperature will cause normal vessel
pressure to drop below 200 psig.
Normally Closed - The contacts of the switch shall be open
when the container is pressurized in accordance with speci-
fications. The contacts will close when container pressure
drops below 200 ±15 psig. This switch shall not be used for
applications where ambient temperatures could drop to 10oF
(12oC) or lower as this temperature will cause normal vessel
pressure to drop below 200 psig.
The explosion resistant cable assembly shall be designed
for hazardous locations, Class 1, Groups C and D, Class 2,
Groups E, F and G. Its contacts shall be rated at 1 Amp at
120/240VAC and 2 Amps at 24VDC.
www.fenwalfire.com R
P/N 31-194019-001
93.3119.1
DESCRIPTION
The Wall Bracket shown is used to mount Fenwal Modular
Spherical FM-200™ Agent Storage containers.
INSTALLATION
The bracket may be mounted with in the position shown or
inverted. Six bolt holes are provided for secure mounting,
using 1/2 in. (12.7 mm) hardware. The bracket also may be
welded to stanchions, beams or bulkheads. The mounting
holes bust be laid out to the dimensions shown below to a
tolerance of 1/32 in. (.79 mm) on each hole location. Mount
against a rigid structural member or wall.
Manufactured from
0.250 in. (6.4mm) stock
Protection Systems
Effective: August 1999
Floor Mounting Bracket
P/N 31-194023-002
93.3119.2
DESCRIPTION
The floor mounting bracket shown is used to mount Fenwal
Modular Spherical FM-200™ Agent Storage Containers.
INSTALLATION
The bracket is fastened to the floor through six 0.625 in.
(15.9 mm) holes. Use 1/2 inch (12.7 mm) lag screws or bolts
with lockwashers to prevent loosening. The agent storage
container is then mounted on top of the bracket with the
valve extending down through the 4 inch (102 mm) hole.
Protection Systems
Effective January 2000
FM-200 COMPONENT DESCRIPTION
Cylinder and Valve Assemblies 10LB (4.5 KG) - 70
LB (31.7 KG) Capacity, Vertical Mount Only
F-93-2010
Features
• For use with UL Listed, ULC Listed & FMRC approved systems • See Kidde Manual 90-FM200M-021 for USCG Approval
CYLINDER VALVE
SAFETY CAP
NOTES:
1. THE SAFETY CAP MUST BE INSTALLED ON THE VALVE
OUTLET AT ALL TIMES EXCEPT WHEN THE CYLINDERS ARE
CONNECTED TO THE SYSTEM PIPING OR BEING FILLED. THE
SAFETY CAP MUST NOT BE REMOVED FROM ITS CHAIN.
2. SEE F-90-2070 FOR ADDITIONAL INFORMATION.
3. CYLINDERS ARE VERTICAL MOUNT ONLY.
SYPHON TUBE
C ORDERING INFORMATION
CYLINDER
Dimensions
B Part Number Cyl. Size
A* B* C*
A
93-100010-001 10 Lbs. 7.07 13.34 17.30
www.fenwalfire.com R
F-93-2020
• For use with UL listed, ULC listed & FMRC approved systems
NOTES:
1. THE SAFETY CAP MUST BE INSTALLED ON THE VALVE
OUTLET AT ALL TIMES EXCEPT WHEN THE CYLINDERS ARE
CONNECTED TO THE SYSTEM PIPING OR BEING FILLED. THE
SAFETY CAP MUST NOT BE REMOVED FROM ITS CHAIN.
2. SEE F-90-2070 FOR ADDITIONAL INFORMATION.
3. CYLINDERS ARE HORIZONTAL MOUNT ONLY.
4. NOT FOR USE WITH ENGINEERED SYSTEMS
ORDERING INFORMATION
Dimensions
Part Number Cyl. Size
A* B* C*
www.fenwalfire.com R
F-93-2030
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
VALVE OUTLET
30°
PLAN VIEW
CYLINDER
35.93” 31.97”
CYLINDER
NAMEPLATE
12,75” DIA
www.fenwalfire.com R
F-93-2040
FEATURES
FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
NOTES:
1. THE SAFETY CAP MUST BE INSTALLED ON THE VALVE
OUTLET AT ALL TIMES EXCEPT WHEN THE CYLINDERS
ARE CONNECTED TO THE SYSTEM PIPING OR BEING
FILLED. THE SAFETY CAP MUST NOT BE REMOVED FROM
ITS CHAIN.
2. SEE F-93-2070 FOR ADDITIONAL INFORMATION.
ORDERING INFORMATION
P/N DESCRIPTION
MATERIALS
VALVE BODY: BRASS 93-100200-101 STD
CYLINDER: STEEL, PAINTED RED 93-100201-101 W/LLI
P/N: 93-10020X-101
www.fenwalfire.com R
F-93-2050
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
VALVE OUTLET
30°
PLAN VIEW
16.00" DIA
ORDERING INFORMATION
P/N DESCRIPTION
93-100350-001 STD
93-100351-001 W/LLI
MATERIALS
VALVE BODY: BRASS P/N: 93-10035X-001
CYLINDER: STEEL, PAINTED RED
www.fenwalfire.com R
F-93-2060
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
VALVE OUTLET
30°
NOTES:
1. THE SAFETY CAP MUST BE INSTALLED ON THE
PLAN VIEW VALVE OUTLET AT ALL TIMES EXCEPT WHEN THE
CYLINDERS ARE CONNECTED TO THE SYSTEM
SAFETY CAP CYLINDER VALVE
PIPING OR BEING FILLED. THE SAFETY CAP
MUST NOT BE REMOVED FROM ITS CHAIN.
2. SEE F-93-2070 FOR ADDITIONAL INFORMATION.
LIQUID LEVEL INDICATOR
LIFTING LUGS
CYLINDER
56.72" 50.51"
CYLINDER
NAMEPLATE
22.00" DIA
ORDERING INFORMATION
P/N DESCRIPTION
P/N: 93-10060X-001
www.fenwalfire.com R
F-93-2070
(Sheet 1 of 2)
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
GROSS WEIGHT
EMPTY
FILL RANGE HEIGHT DIAMETER VOLUME
PART WEIGHT
MIN FILL MAX FILL W/LLI
NUMBER
LB KG LB KG LB KG LB KG IN CM IN CM FT3 M3
93-100121-001 54-125 25-57 98 45 152 69 223 101 YES 35.93 92 12.75 33 1.788 0.0506
93-100125-001 54-125 25-57 98 45 152 69 223 101 NO 35.93 92 12.75 33 1.788 0.0506
93-100200-001 86-200 39-91 139 63 225 102 341 154 NO 50.35 128 13.60 35 2.859 0.0810
93-100201-001 86-200 39-91 141 64 227 103 343 155 YES 50.35 128 13.60 35 2.859 0.0810
93-100200-101 86-200 39-91 133 60 219 100 333 151 NO 52.75 134 12.75 33 2.859 0.0810
93-100201-101 86-200 39-91 133 60 219 100 333 151 YES 52.75 134 12.75 33 2.859 0.0810
93-100350-001 150-350 68-159 201 91 351 159 555 250 NO 58.36 149 16.00 41 5.000 0.1416
93-100351-001 150-350 68-159 203 92 341 160 557 251 YES 58.36 149 16.00 41 5.000 0.1416
93-100600-001 258-600 114-272 335 152 593 270 935 425 NO 56.72 145 22.00 56 8.572 0.2427
93-100601-001 258-600 114-272 337 153 595 270 937 426 YES 56.72 145 22.00 56 8.572 0.2327
www.fenwalfire.com R
F-93-2070
(Sheet 2 of 2)
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
GROSS WEIGHT
EMPTY
FILL RANGE HEIGHT DIAMETER VOLUME
PART WEIGHT
MIN FILL MAX FILL W/LLI
NUMBER
LB KG LB KG LB KG LB KG IN CM IN CM FT3 M3
93-100121-001 71-125 32-57 98 45 169 77 223 101 YES 35.93 92 12.75 33 1.788 0.0506
93-100125-001 71-125 32-57 98 45 169 77 223 101 NO 35.93 92 12.75 33 1.788 0.0506
93-100200-001 126-200 56-91 139 63 265 120 339 154 NO 50.35 128 13.60 35 2.859 0.0810
93-100201-001 126-200 57-91 141 64 267 121 341 155 YES 50.35 128 13.60 35 2.859 0.0810
93-100200-101 126-200 57-91 133 60 259 118 333 151 NO 52.75 134 12.75 33 2.859 0.0810
93-100201-101 126-200 57-91 133 60 259 118 333 151 YES 52.75 134 12.75 33 2.859 0.0810
93-100350-001 201-350 91-159 201 91 406 182 555 250 NO 58.36 149 16.00 41 5.000 0.1416
93-100351-001 201-350 91-159 203 92 408 183 557 251 YES 58.36 159 16.00 41 5.000 0.1416
*93-100600-001 351-500 159-227 335 152 686 312 835 380 NO 56.72 145 22.00 56 8.572 0.2427
*93-100601-001 351-500 159-227 337 153 688 313 837 380 YES 56.72 145 22.00 56 8.572 0.2470
www.fenwalfire.com R
F-93-2080
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
PROTECTION
CAP
BODY
SLAVE CYLINDER
ACTUATION PORT
1/8" NPT
A
SAFETY
DISC
PRESSURE
GAGE
MATERIALS
VALVE BODY: BRASS
PISTON: BRASS P/N: 93-1X0000-000
FINISH: NATURAL
SEAT: RUBBER
www.fenwalfire.com R
F-93-2090
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
1.56"
2.12"
ORDERING INFORMATION
OPERATION P/N
2.93”
www.fenwalfire.com R
F-93-2100
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
D C
ORDERING INFORMATION
1.874
283904 1-1/2 1-1/2" NPT 2.69 2.50 HEX
12UNJ
2.500
283905 2 2" NPT 3.12 3.00 HEX
12 UNJ
3.000
283906 2-1/2 2-1/2" NPT 3.00 3.75 HEX
12 UNJ
P/N: 28390X
www.fenwalfire.com R
F-93-2100 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Protection Systems
Effective June1999
FM-200 COMPONENT DESCRIPTION
Liquid Level Indicator
F-93-2110
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
CAP
GRADUATED TAPE
P/N: SEE TABLE
TAPE IN MAGNETIC INTERLOCK
READING TAKEN AT TOP POSITION READY TO TAKE
EDGE OF FITTING READING.
O-RING
P/N: WK-566109-160
BRASS TUBE
TAPE INSIDE
BRASS TUBE FM-200
CYLINDER
FM-200
LIQUID LEVEL
MAGNETIC END OF
TAPE ENGAGES
IN MAGNETIC FIELD
OF FLOAT WHEN
TAPE IS PULLED
UP TO TAKE READING
MAGNET EMBEDDED
ORDERING INFORMATION
IN FLOAT
CY LINDER LLI TAPE P/N
FLOAT - FLOATS ON SURFACE
OF LIQUID FM-200. 125 235681
FREE TO MOVE UP OR DOWN
OUTSIDE OF BRASS TUBE.
200 283894
350 283894
RETAINER - FLOAT RESTS
HERE WHEN CYLINDER
IS EMPTY. 600 283894
www.fenwalfire.com R
F-93-2120
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
HOSE
FM-200 CYLINDER VALVE SYSTEM PIPE CONNECTION,
CONNECTION, SWIVEL NUT MALE NPT THREAD
ORDERING INFORMATION
283899 2 31 13.5
www.fenwalfire.com R
Protection Systems
F-93-2120 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Manifold El-Check
F-93-2130
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
VALVE BODY
B C
FOR CONNECTION TO
SYSTEM MANIFOLD
ARROW INDICATES
FLOW DIRECTION
C CHECK
www.fenwalfire.com R
Protection Systems
F-93-2130 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Typical Installation of El-Check
F-93-2131
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
EL-CHECK MAY BE ADJUSTED AS SHOWN TO OB- NOTES: INSTALL EL-CHECKS SO THAT ARROW IS IN
TAIN A SMOOTH RADIUS IN FLEXIBLE DISCHARGE DIRECTION OF FLOW
HOSE.
www.fenwalfire.com R
Protection Systems
F-93-2131 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
360 Degree Pendant Nozzle
F-93-2140
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
FE
C
Pipe Size A B C D
1/2" (12.20mm) 1.250" (31.75mm) 1.468" (37.28mm) 1.937" (49.19mm) 1.250" (31.75mm)
3/4" (19.05mm) 1.500" (38.10mm) 1.578" (40.08mm) 2.125" (53.97mm) 1.500" (38.10mm)
1" (25.40mm) 1.750" (44.45mm) 1.718" (43.63mm) 2.375" (60.32mm) 1.750" (44.45mm)
1-1/4" (31.75mm) 2.250" (57.15mm) 1.950" (49.53mm) 2.750" (69.85mm) 2.250" (57.15mm)
1-1/2" (38.10mm) 2.250" (63.50mm) 2.000" (50.80mm) 2.937" (74.59mm) 2.500" (63.50mm)
2" (50.80mm) 3.000" (76.20mm) 2.062" (52.37mm) 3.125" (79.37mm) 3.000" (76.20mm)
www.fenwalfire.com R
Protection Systems
F-93-2140 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
180 Degree Pendant Nozzle
F-93-2150
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
C
A
60°
FENWAL
30°
Pipe Size A B C D
1/2" (12.20mm) 1.250" (31.75mm) 1.250" (31.75mm) 1.687" (42.84mm) 2.000" (50.80mm)
3/4" (19.05mm) 1.500" (38.10mm) 1.375" (34.92mm) 1.950" (48.89mm) 2.296" (58.31mm)
1" (25.40mm) 1.750" (44.45mm) 1.562" (39.67mm) 2.218" (56.33mm) 2.671" (67.84mm)
1-1/4" (31.75mm) 2.250" (57.15mm) 1.750" (44.45mm) 2.656" (67.46mm) 3.250" (82.55mm)
1-1/2" (38.10mm) 2.250" (63.50mm) 1.950" (48.89mm) 2.950" (74.93mm) 3.625" (92.07mm)
2" (50.80mm) 3.000" (76.20mm) 1.968" (49.98mm) 2.875" (73.02mm) 3.656" (92.86mm)
www.fenwalfire.com R
Protection Systems
F-93-2150 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Pressure Operated Control Head
F-93-5010
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
1.00" HEX
1/8"-27 NPT
PRESSURE INLET
PISTON
2.19"
SWIVEL NUT
SET
OPERATED 1.250-18
UNEF-3B
1.50" HEX
www.fenwalfire.com R
Protection Systems
F-93-5010 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Pressure Operated Control Head, Stackable
F-93-5020
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
MATERIAL
BODY, RETAINER CAP, PISTON & MTG. NUT: BRASS P/N: 878750
www.fenwalfire.com R
Protection Systems
F-93-5020 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Lever or Pressure Operated Control Head
F-93-5030
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
MATERIALS
LEVER: STAINLESS STEEL P/N: 878751
BODY & PISTON: BRASS
www.fenwalfire.com R
Protection Systems
F-93-5030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Pilot Actuation Fittings
F-93-5040
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
MATERIAL: BRASS
www.fenwalfire.com R
Protection Systems
F-93-5040 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Nitrogen Pilot Cylinder, Bracket, and Adapter
F-93-5050
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
GAUGE
PLUG OUTLET PORT-1/8" NPT FEMALE,
ATTACH ADAPTER HERE
1-1/4"-18 NF-3
FOR CONTROL HEAD CONNECTION
Normally Closed
06-129773-001
Open Under Pressure
Normally Open
MATERIALS 06-129773-002
Closed Under Pressure
CYLINDER: STEEL, PAINTED BLACK
VALVE: BRASS
BRACKET: STEEL, PAINTED BLACK
ADAPTER: BRASS
www.fenwalfire.com R
Protection Systems
F-93-5050 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
1/4" Flexible Actuation Hoses
F-93-5070
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
MATERIALS
HOSE: WIRE BRAIDED, TEFLON LINING (CRES T304)
COUPLINGS: BRASS
MINIMUM BURST PRESSURE: 12,000 PSIG
OPERATING PRESSURE: 3000 PSIG
TEST PRESSURE: 4500 PSIG P/N: 26498x
MINIMUM BEND RADIUS 2.5"
www.fenwalfire.com R
Protection Systems
F-93-5070 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Master Cylinder Adapter Kit
F-93-5080
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
CAUTION
INSTALL CAP
WHEN
NOT IN
USE
LABEL
1.42"
MATERIALS
ADAPTER & CAP: BRASS
P/N: 844895
CHAIN: STAINLESS STEEL
LABEL: MYLAR
www.fenwalfire.com R
Protection Systems
F-93-5080 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
1/4" Check Valve
F-93-5090
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
P/N: 264985
www.fenwalfire.com R
Protection Systems
F-93-5090 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
3/8" Check Valve
F-93-5100
2.35" 1.00"
(60 MM) (25 MM)
HEX
3"
NPT BOTH ENDS
8
TECHNICAL DATA
WORKING PRESSURE: 0 TO 5000 PSI (0 TO 345 BAR)
PROOF PRESSURE: 10,000 PSI (690 BAR)
CRACKING PRESSURE: 2 TO 4 PSI (.14 TO .28 BAR)
OPERATING TEMPERATURE: -40F TO 250F (-40F TO 121C)
MATERIALS
BODY: BRASS
SEAL: BUNA-N P/N: 261193
www.fenwalfire.com R
Protection Systems
F-93-5100 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Check Valves, 1/2" Thru 2"
F-93-5110
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
www.fenwalfire.com R
Protection Systems
F-93-5110 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Check Valves, 2-1/2" & 3"
F-93-5120
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
ORDERING INFORMATION
3" 6810-1200 2
VALVE MUST BE INSTALLED WITH ARROW POINT-
ING IN THE DIRECTION OF FLOW P/N: 870100
www.fenwalfire.com R
Protection Systems
F-93-5120 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Stop (Directional) Valves, 1/2" Thru 2"
F-93-5130
OUTLET
A B
MATERIALS NOTES:
BODY: BRASS 1. VALVE MUST BE INSTALLED WITH ARROW POINTING IN
DIRECTION OF FLOW.
2. VALVE MAY BE INSTALLED IN HORIZONTAL OR VERTI-
CAL PIPE RUN.
www.fenwalfire.com R
Protection Systems
F-93-5130 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Stop (Directional) Valves, 2-1/2" & 3"
F-93-5140
9.81"
INLET
(249mm)
ORDERING INFORMATION
WELDING NECK
CHECK VALVE
P/N FLANGE P/N
SIZE
(2 REQUIRED)
MATERIALS
VALVE BODY: BRASS 2-1/2" 890010 263716
www.fenwalfire.com R
Protection Systems
F-93-5140 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
4" Stop (Directional) Valve
F-93-5150
12.12"
(308mm)
11.06"
INLET
(281mm)
www.fenwalfire.com R
Protection Systems
F-93-5150 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Discharge Indicators
F-93-5160
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
3.25"
(83mm) NORMAL
POSITION
DISCHARGE
INDICATION
POSITION
BODY
P/N 967082 CAP
3"
NPT MALE
4 STEM
1.12"(29mm) HEX
ACROSS FLATS
2.62"
(67mm) NORMAL
POSITION
DISCHARGE
INDICATION
POSITION
BODY
P/N 875553
1"
2 NPT MALE CAP
ORDERING INFORMATION
SIZE P/N
MATERIALS
BODY-967082: BRASS 3/4" (BRASS) 967082
BODY-875553: ALUMINUM
1/2" (AL) 875553
CAPS: CLEAR CELLULOSE ACETATE
www.fenwalfire.com R
Protection Systems
F-93-5160 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Safety Outlets
F-93-5170
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
RETAINING NUT
SAFETY DISC
SEAL WIRE
BODY
1.78"
(45mm)
3"
4 NPT MALE
PRESSURE RELIEF
PART
AGENT OPERATES AT
NUMBER
PSI BAR
803242 N2/CO2 2400-2800 166-193
844346 FM-200 750-900 52-62
MATERIALS
BODY & RETAINING NUT: BRASS
SEAL WIRE: COPPER & LEAD
www.fenwalfire.com R
Protection Systems
F-93-5170 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Pressure Operated Switch
F-93-5180
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
NOTES:
1. SWITCH MAY BE MOUNTED IN ANY POSITION
BUT PREFERRED INSTALLATION IS UPRIGHT AS
SHOWN.
2. ANY LOAD CONNECTION TO THE SWITCH MUST
NOT EXCEED SWITCH RATING AND SHALL UTILIZE
A SUITABLE PROTECTION DEVICE (ie. CIRCUIT
BREAKER, FUSE)
3. CONTACT RATINGS (3PDT)
15 AMP @ 125 VAC P/N: 486536
10 AMP @ 250 VAC
3/4 HP @ 250 VAC
1, 2 OR 3 PHASE
www.fenwalfire.com R
Protection Systems
F-93-5180 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Pressure Operated Switch, Explosion Proof
F-93-5190
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
P/N: 981332
www.fenwalfire.com R
Protection Systems
F-93-5190 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Pressure Trip
F-93-5200
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
STEM
RING
PISTON
SPRING
2.50"
(64mm)
1.37"
(41mm) BODY
HEX
PRESSURE INLET
½”NPT - FEMALE
1.62"
(41mm)
www.fenwalfire.com R
Protection Systems
F-93-5200 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Pressure Trip Applications - Installation Detail
F-93-5201
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
www.fenwalfire.com R
Protection Systems
F-93-5201 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Lever Operated Control Head
F-93-6010
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
www.fenwalfire.com R
Protection Systems
F-93-6010 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Cable Operated Control Head
F-93-6020
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
4.25"
(108mm)
3/8" PIPE (OR 1/2" EMT
SWIVEL WITH ADAPTER P/N
NUT 843837 - SEE F-93-6120)
1.50"
(38mm)
5.25"
(133mm)
1-1/4"-18 NF-3
FEMALE
P/N: 979469
www.fenwalfire.com R
Protection Systems
F-93-6020 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Tandem Cable Operated Control Heads - Installation Detail
F-93-6021
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
1/16” CABLE
CYLINDER CENTERS
FLARE ON CABLE
HOUSING FITS INTO
SLOT IN CONTROL
HEAD (CLOSURE DISC REMOVED)
www.fenwalfire.com R
Protection Systems
F-93-6021 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Cable Housing for Cable Operated Control Heads
F-93-6030
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
CYLINDERS CYLINDER
"A" DIMENSION
USED WITH CENTERS
PART
NUMBER
LB S KG IN mm IN mm
www.fenwalfire.com R
Protection Systems
F-93-6030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Pull Box, Break Glass
F-93-6040
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
2 - NAMEPLATE
BRACKETS-
OPTIONAL
(SUPPLIED WITH
NAMEPLATE PULL BOX)
(BY INSTALLER) 4-COVER
SCREWS
P/N
FOR FIRE WK-524906-080
BREAK GLASS PULL HANDLE
Kidde
R
3/8” PIPE
PULL
5.87" HANDLE
(149mm) PULL HARD
5.00" 2.25"
(127mm) (57mm)
BREAK GLASS
P/N WK-928103-000 PULL HANDLE
P/N WK-803246-000
MATERIALS
Body: Aluminum P/N: 871403
Handle: Brass
www.fenwalfire.com R
Protection Systems
F-93-6040 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Break Glass Pull Box used with Z-Bracket - Installation Detail
F-93-6041
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
4.50"
(114mm)
1"
16
CABLE
3"
8
NPT NIPPLE
WATERTIGHT CORNER
PULLEY P/N 803808
SEE F-93-6080
Z-BRACKET 3.56"
P/N 60532 (90mm)
3 HOLES FOR
1"
4
MOUNTING BOLTS HERE
4.50"
(114mm)
1"
16
CABLE
1"
2
E.M.T.
1"
2
E.M.T. CORNER
PULLEY-P/N 844648-
SEE F-93-6080
Z-BRACKET 3.56"
P/N 60532 (90mm)
www.fenwalfire.com R
Protection Systems
F-93-6041 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Dual Pull Mechanism
F-93-6100
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
P/N: 840058
www.fenwalfire.com R
Protection Systems
F-93-6100 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Dual Pull Equalizer
F-93-6110
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
P/N: 840051
www.fenwalfire.com R
Protection Systems
F-93-6110 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Adapter, 3/8" Pipe (Male) to 1/2" EMT (Female)
F-93-6120
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
www.fenwalfire.com R
Protection Systems
F-93-6120 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Cylinder Recharge Adapters
F-93-7145
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
"A"
"B"
HEX
3/8"-18NPT
(CHARGE CONNECTION)
www.fenwalfire.com R
Protection Systems
F-93-7145 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Electric Control Head
F-93-8010
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
SEAL WIRE
PU
ELECTRIC
CONTROL HEAD
LOCAL MANUAL
RELEASE LEVER
6.18" VOLTS
AMPS
(157mm) PART NO.
SWIVEL NUT
INDICATOR AND TO RESET
USE SCREWDRIVER
1.50" (38mm) HEX
RESET STEM 1-1/4"-18 NF-3 THREAD
SET RELEASED
MADE IN U. S. A.
KIDDE-FENWAL, INC.
400 MAIN STREET
ASHLAND, MA 01721
4.00"
(102mm)
ORDERING INFORMATION
PART CONTROL HEAD
NUMBER VOLTAGE CURRENT
www.fenwalfire.com R
Protection Systems
F-93-8010 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Electric Control Head, Stackable Explosion Proof
F-93-8017
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
2.90"
1.25-18 UNEF-2A
CONNECTION
1/2"-14 NPT
CONDUIT
CONNECTION
ELECTRIC CONTROL HEAD, PART
NO. 486500-01 IS RATED FOR USE
IN HAZARDOUS (CLASSIFIED)
LOCATIONS CLASS 1, DIV. l,
GROUPS C, D AND CLASS ll, DIV. ll, 5.28"
GROUPS E, F, G BETWEEN
-40F AND 140F. USE CONDUIT
SEAL WITHIN 18 IN. (45cm) OF
THIS DEVICE. (3) 18 AWG-LEADS
18" LONG
NOTE:
THIS CONTROL HEAD IS POLARIZED. IMPROPER
WIRING WILL RESULT IN FAILURE OF THIS DEVICE TO
OPERATE
SWIVEL NUT
1.25-18 UNEF-2B
WARNING CONNECTION
ELECTRIC CONTROL HEAD, P/N: 486500-01, IS DESIGNED
FOR INSTALLATION DIRECTLY ON 487 SERIES HALON
AND MODEL 9300 FM-200 VALVES ONLY. THIS CONTROL
VOLTAGE: 24VDC
HEAD MUST NOT BE INSTALLED ON ANY OTHER TYPE CURRENT: 0.2A CONTINUOUS DRAW
OF HALON OR FM-200 CYLINDER VALVE, NITROGEN
VALVE, CARBON DIOXIDE CYLINDER VALVE, FE-13 CYL-
INDER VALVE OR STOP (DIRECTIONAL) VALVE. INSTAL- P/N: 486500-01
LATION OF THIS CONTROL HEAD TO ANY OTHER DE-
VICE (E.G., PRESSURE OPERATED CONTROL HEAD) WILL
RESULT IN FAILURE OF DEVICE TO OPERATE.
www.fenwalfire.com R
Protection Systems
F-93-8017 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Electric And Cable Operated Control Head
F-93-8030
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
LOCKING PIN
LOCAL MANUAL
RELEASE LEVER
PU
INDICATOR AND
ELECTRIC
CONTROL HEAD RESET STEM
VOLTS
AMPS
SWIVEL NUT
7.56" PART NO.
1.50" (38mm) HEX
(192mm)
TO RESET
1 1/4-18NF-3 THREAD
USE SCREWDRIVER
SET RELEASED
MADE IN U. S. A.
KIDDE-FENWAL, INC.
400 MAIN STREET
ASHLAND, MA 01721
5.44"
1/2" E.M.T. CONNECTION (138mm)
COMPRESSION TYPE TO
SECOND CONTROL HEAD
IF USED
CONTROL HEAD
PART No.
VOLTAGE AMPS
895630 24 VDC 2.0
895628 125 VDC 0.3
895627 115 VAC 1.0
www.fenwalfire.com R
Protection Systems
F-93-8030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Electric and Cable Operated Control Head with
Explosion Proof Solenoid
F-93-8040
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
PU
SEAL WIRE
INSTRUCTIONS
MAINTENANCE
PART NO.
SEE
FOR
INDICATOR AND
KIDDE-FENWAL, INC.
ASHLAND, MA 01721
400 MAIN STREET
SET
MADE IN U.S.A.
RESET STEM
USE SCREWDRIVER
CONNECTION FOR
CONTROL HEAD
TO RESET
HZ
CABLE
VOLTS
PULL
PIPE OR CONDUIT
AMPS
RELEASED
LOCAL MANUAL
RELEASE LEVER
4.937
(125 MM) SWIVEL NUT
1.500 (38 MM) HEX
CONNECTION FOR CABLE 1.250-18 NF-3 THREAD
HOUSING TO SECOND
CONTROL HEAD IF USED
3/8" NPS FEMALE.
USE PNEUMATIC CONTROL
HEAD CABLE HOUSINGS
SEE F-93-5020.
CONTROL HEAD
PART
NUMBER POWER
VOLTAGE
CONSUMPTION
897494 24 VDC 33 WATTS
897560 120 VAC 15.4 WATTS
www.fenwalfire.com R
Protection Systems
F-93-8040 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Electric Main-To-Reserve Transfer Switch
F-93-8070
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
P/N: 802398
MATERIALS
CONDUIT BOX: STEEL WITH RED ENAMEL FINISH
TOGGLE SWITCH LEVER: BAKELITE
www.fenwalfire.com R
Protection Systems
F-93-8070 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Cylinder Mounting Straps
F-93-8130
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
www.fenwalfire.com R
Protection Systems
F-93-8130 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Cylinder Wall Brackets
F-93-8140
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
www.fenwalfire.com R
Protection Systems
F-93-8140 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Cylinder Mounting Cradle
F-93-8150
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
www.fenwalfire.com R
Protection Systems
F-93-8150 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Main and Reserve Nameplates
F-93-9010
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
5.00"
(127mm)
1.62" MAIN
(41mm)
5.00"
(127mm)
1.62" RESERVE
(41mm)
www.fenwalfire.com R
Protection Systems
F-93-9010 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
Warning Nameplate (FM-200)
F-93-9030
FEATURES
• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
10.000 ±.063
.340 9.360
.340
WARNING
THIS AREA IS
TM
PROTECTED BY A
±.062 FM-200 EXTINGUISHING
5.000 4.360
SYSTEM. DO NOT ENTER WITHOUT
AUTHORIZATION DURING OR
AFTER DISCHARGE
www.fenwalfire.com R
Protection Systems
F-93-9030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Effective June 1999
FM-200 COMPONENT DESCRIPTION
3" Swing Check Valve
F-93-9040
FEATURES
FOR USE WITH UL LISTED AND FMRC APPROVED SYSTEMS
9.360
MATERIAL:
VALVE BODY & COVER: BRASS
HEX BOLTS, HINGE, & HINGE PIN: STAINLESS STEEL
P/N: 06-118058-001
www.fenwalfire.com R
Protection Systems
F-93-9040 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
FM-200® COMPONENT DESCRIPTION Effective: November 1999
F-93-9041
FEATURES
• FOR USE WITH UL LISTED AND FMRC APPROVED SYSTEMS
90°
NOTES:
1.INSTALL CHECK VALVE SO THAT ARROW
IS IN DIRECTION OF FLOW.
2. INSTALL BETWEEN O AND 90 DEGREES
FROM THE HORIZONTAL.
R
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes no
responsibility for the product's suitability for a particular application. The product must be
properly applied to perform as described herein.
KIDDE-FENWAL, INC. If you need more information on this product, or if you have a question, contact KIDDE-
400 MAIN STREET, ASHLAND, MA 01721 FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
R