SIPROTEC

Motor Protection
2
Protection
n Stator thermal overload
protection
n 2 Protection principles for the
rotor overload protection
n Motor starting time supervision
n Restart inhibit
n Earth-fault protection
(I
0
>;U
0
>; (U
0
, I
0
))
n Overcurrent time protection
n Current differential protection
n Negative sequence protection (I
2
/I
N
)
n Temperature sensors (RTDs)
n Undercurrent protection,
Active power protection (P<)
n Undervoltage protection
n Underexcitation protection
SIPROTEC
Motor protection
Protection functions for various
types of motor faults
Fault
n Stator thermal
overload
n Rotor thermal overload
during start
n too long or blocked
n too frequent
n Earth-fault
n Short-circuit
n Loss of phase
n Bearing overload
n Overheating of plant
on unloaded drives
(Pumps, compressors)
n Undervoltage
(Starting torque not reached
M ~ U
2
or start too long)
n Asynchronous operation
(of a synchronous motor)
49
ANSI - No.
48
49R 66
67G 50G 64G
51
87
50
46
38
32U
37
40
27
3
Stator overload protection
Starting time supervision
Locked rotor protection
Restart
inhibit
Earth-fault protection
non-directional
directional
Overcurrent time protection
Current differential protection
Negative sequence protection
Temperature supervision
(via RTD - module)
Undercurrent protection
Active power protection
(P<)
Undervoltage protection
Underexcitation protection
Frequency protection
Breaker failure protection
Freely programmable
logic (PLC)
Control functions
Measuring
transducers
Flexible serial
interfaces
Scope of motor protection functions
provided by SIPROTEC devices.
Protection functions ANSI 7SJ60 7SJ61 7SJ62 7SJ63/64 7UM61 7UM62
49 X X X X X X
48 X X X X X X
48 X X X X X X
66, X X X X X X
49R
64G X 1) X X X X
50G X X X X X X
67G X 1) X X X X
50, 51 X X X X X X
87 X
46 X X X X X X
38 X 1) X X X X
nn
37 X 1) X X X X X
32U X X
(37)
27 X X X X
40 X X
81 X X X X
50BF X1) X X X X X
X X X X X
X X X X X X
X X
1 2 2 2/3 2 3
A device that best suits your
requirement can be selected
1)
in preparation (7SJ602)
4
100 kW - 500 kW
7SJ60 7SJ61
Basic device + more I/Os
+ control functions
+ flexible serial interfaces
+ better local HMI
(4line display; digital keyboard)
Motor protection
selection table
Asynchronous Motor
500 kW - (1-2) MW
7SJ62 7UM61
Basic device + more I/Os (7UM612)
+ control functions + control functions
+ high accuracy
+ high sensitivity
+ operating range in a wide
frequency band (11Hz - 68Hz)
or with control functions via
bay mimic diagram in graphic display
7SJ63 7SJ64
Basic device + synchro check function
+ high sensitivity
+ extensive control function
+ 1 serial interface more
> 2 MW
7UM62
+ differential protection
+ control functions
+ high accuracy
+ high sensitivity
+ operating range in a wide
frequency band (11Hz - 68Hz)
< 10 MW
7UM62
(Option:
Generator Basic)
< 2MW
7UM61
(Option:
Generator Basic)
Synchronous Motor
+
+
> 10 MW
7UM61
(Option:
Generator Basic)
7UM62 or with control functions
(Option: via bay mimic diagram
Generator Basic) in graphic display
7SJ64
(Option:
Maximum functionality
+ Synchro check)
5
7SJ600/602
n Stator thermal overload
protection 49
n Starting time supervision 48
n Earth-fault protection 50G
n Overcurrent time protection 50, 51
n Negative sequence protection 46
Application example:
Protection of a small motor
100 kW - 500 kW
A (L 1)
B (L 2)
C (L 3)
A (L 1)
B (L 2)
C (L 3)
N
Motor
ANSI
52
6
Application example:
Protection of a medium sized motor
7SJ62/63
n Stator thermal overload
protection 49
n Restart inhibit
(rotor protection) 66, 49R
n Starting time supervision 48
n Earth-fault protection 50G
(non-directional, 64G
directional) 67G
n Overcurrent time protection 50, 51
n Negative sequence
protection 46
n Undervoltage protection 27
n Undercurrent protection 37
n Breaker failure protection 50BF
n external RTD - module 38
500 kW - (1-2) MW
A (L 1)
B (L 2)
C (L 3)
Motor
A (L 1)
C (L 3)
I
EE
V
E
A (L 1)
B (L 2)
C (L 3)
N
ANSI
52

A
B
C
R
7
7UM62
n Stator thermal overload
protection 49
n Restart inhibit
(rotor protection) 66, 49R
n Starting time supervision 48
n Earth-fault protection 50G
(non-directional, 64G
directional) 67G
n Differential protection 87M
n Overcurrent time
protection 50, 51
n Negative sequence
protection 46
n Undervoltage protection 27
n Undercurrent protection 37
n Active power protection 32U
n Frequency protection 81
n Breaker failure protection 50BF
Application example:
Protection of a large motor
> 2 MW
A (L 1)
B (L 2)
C (L 3)
Port C or D From RTD module
R 13
R 14
R 15
R 17
R 18
R 16
7UM62
J 1
J 2
J 3
J 4
J 5
J 6
Q 8
Q 7
K 13 +
K 14
K 15 +
K 16
K 17 +
K 18
J 7
J 8
Q 6
Q 1
Q 2
Q 3
Q 4
Q 5
I
C(L3)S2
I
B(L2)S2
I
A(L1)S2
I
EE1
TD3
TD2
TD1
I
EE2
I
C(L3)S2
I
B(L2)S2
I
A(L1)S2
V
A(L1)
V
B(L2)
V
C(L3)
V
E
e
n
k
RTD module
7XV5662
(6 meas.
junctions)
To serial
interface
Measuring transducer
for injection of any
analog signal
e.g. speed,
vibration, pressure
ANSI
52
Siemens AG
Power Transmission
and Distribution
Power Automation Division
P.O. Box 48 06
90026 Nuremberg
Germany
www.siprotec.com
Editor and Layout:
Dept. Marketing Services
Power Automation Division