WIN-PAK VISTA INTEGRATION

SUPPORTED FEATURES

Alarm Monitoring
Controlling Vista panel from Control Map/Floor Plan
o Partition Arm/Disarm
o Zone Bypass/Unbypass
o Output On/Off
Virtual Keypad
o Send key-Strokes
o Display Update
Command File Support
Video Pop-up on Vista Alarms
Operator Action Report

INDEX
Section1: Vista Panel Programming For Home Automation Protocol
A. Equipments Required
B. Connections For Home/Facility Automation Control
C. Summary of programming commands
D. Programming for the ADEMCO 4100 SM Procedure
E. Configurations
Section2: Vista Configuration in WIN-PAK
A. Installation Instructions
B. Add Comm Server
C. Add HA Port
D. Add Vista Panel
E. Configure Control Map
F. Configure Floor Plan
G. Vista Command File Support
H. Virtual Keypad
I. Operator Action Report
J. Vista Action Group and Action Messages
K. Vista Monitoring and Control

Section1. Vista Panel Programming For Home Automation Protocol


A. Equipment Required
Vista 128/250 FBP - Revision 2.0 or higher
ADEMCO 4100SM Serial Interface Module
Serial to IP converter
Communication settings should be 1200-baud, 8 data bits, no parity, and one stop bit.

B. Connections for Home/Facility Automation Control


CONTROL PANEL

9
8

GREY

YELLOW
WHITE

VIOLET

4142TR CABLE (SUPPLIED WITH 4100SM)

RED

BROWN
BLUE

GREEN

BLACK

4100SM
SERIAL
MODULE
8

+ PWR

- (GND)

RXD

NOT USED

NOT USED

TXD

NOT USED

DTR

RED

BLUE

WHITE

J2 CONNECTOR

12

AUX GND.

11

AUX PWR.

TO
AUTOMATION
EQUIPMENT
(RS232 INTERFACE)
4100SM-015-V1

C. Summary of Programming commands

Find out the installer code. For 128/250 FBP it is 5140 by default.
To set defaults, enter *97
o 1 to load ADEMCO defaults; 2 to load ADT defaults; 0 to exit without changing
programming
*96 is used to set engineering defaults.
o If this is performed then you must do a *97 to set standard defaults.
To enter into program mode
o Enter installer code + [8] + [0]+ [0] +[0]
o Installer code can be modified *00 option once entered into program mode.
o Installer code must be provided in WIN-PAK from HA port page. It will be used to
perform Panel Reset from WIN-PAK.
To change to next page of program fields, press *94

Press *94 to move to 2nd page, (fields 1*01 1*76)


Press *99 to move back to 1st page
o Press *94 to move to 3rd page, (fields 2*00 2*88)
Press *99 to move back to 2nd page
o Press *94 to move to 4th page, (fields 3*00 3*85)
Press *99 to move back to 3rd page
To return to previous fields, press *99
o

Turn off if unused, 974 and 975 alarms - optional


Log in with installer code
*93 is used to set the alarm functions and prompts for Zone Prog press 1 for Yes
o Set to Confirm press 1 for Yes
o Enter Zone No press 974*
o Press * until you see 974 Zone Type NO RESPONSE change from 19 to 00
o Press * until you see Enter Zone No 000 = Quit 975 press 000* to Quit or
continue by pressing * to change 975
o Press * until you see 975 Zone Type NO RESPONSE change from 19 to 00
o Press * until you see Enter Zone No 000 = Quit 976 press 000* to Quit
o Quit Menu Mode press 1 for Yes
o *99 until you exit the programming mode

D. Programming for the ADEMCO 4100 SM Procedure

0*05 System Notify Event


o Enter 1 to view all zone faults/restores.
0*14 Trigger on RS232 input
o Enter 1 for Home Facility Automation Control
0*70 Enable event log type
o Enter 1.1.1.1.1 for all 5 types
0*79 Zone Type Restore Enable
o Enter 1.1.1.1.1.1.1.1 for 1-8 zone types
1*78 Extended Home Control Event Report
o Enter 1
1*79 Home Control Event Report Types
o Enter 1.1.1.1.1.1 for 1-6 zone types
2*30 Pager Installed
o Enter 0
3*19 Enable J2 Header Printer Port
o Enter 1 for Home Automation Control

E. Configurations

Number of partitions can enabled from 2*00 programming option


o Create Partition ADVs accordingly in WIN-PAK. Refer to section2
Zone information can be configured from programming options given in 0*93
o Create Zone ADVs accordingly in WIN-PAK. Refer to section2.
Output information can be configured from programming options given in 0*93

o Create output ADVs accordingly in WIN-PAK. Refer to section2.


Assign keypad to partition-1.
Create a Master user that should be able to Arm/Disarm partitions, Bypass/Unbypass
zones, etc. Assign all the partitions enabled.
o Tip: For adding user 002 with user code 1234, enter [5140][8][002][1234]
o Master user code must be provided in WIN-PAK from HA Port page. It will used to
perform Arm/Disarm/Bypass/Unbypass commands from WIN-PAK.

Section2: Vista Configuration in WIN-PAK


A. Install WIN-PAK - The Vista option is enabled based on the CDKey code number.
B. Add Communication Server Go to Device Map from the top-level menu Configuration

C. Add Vista Panel Port (Home Automation)


a. Enter name for the Vista Port Configuration and Add ADV.
b. The Loop Verification Interval is coded not to go below 40 to ensure proper Vista
operation.
c. Select communication COM port/TCP from next page. Please enter Master code and
installer code in the current page.
d. Finish

D. Add a Vista panel


a. Select Add New Vista Panel from the pop-up menu on Vista Panel Port
b. Enter name and add ADV
c. Add Vista Partition ADVs
i. Each partition ADV maps to a particular partition defined at the Vista panel.
d. Add Vista Zones ADVs
i. Each zone ADV maps to a particular zone defined at the Vista panel
ii. Each zone can be assigned a Type from Zone Type Combo box. Zone Type
shall be used to display zones of particular type using unique graphical icon in
Control Map.
iii. Each zone must be assigned to a partition from Partition Name Combo box.
e. Add Vista Output ADV's
i. Each Output ADV maps to a particular output defined at the Vista panel
f. Finish

E. Configure Control Map Define Control Map from top-level menu Configuration -> Define>Control Area.
a. Add Vista device(s) to an appropriate branch. Filters are provided in Add Devices
dialog box.

F. Configure Floor Plan Define Floor Plan from top-level menu Configuration

Currently Floor Plan representations for Vista devices are same as Galaxy devices. Tool Tip
over the icon exhibits the correct type.
G. Vista Command File Support Vista Command Files can be configured from top-level menu
Configuration->Command Files

H. Virtual Keypad can be launched from selected partition node in Control Map. A delay of up to
6 seconds may be seen before the Virtual Keypad is updated. 2 seconds is typical. If no
response is seen with in 6 seconds, you may need to re-enter the key pad strokes. Closing
and re-launching the Virtual Keypad will force a refresh of the display (less than 2 seconds).

I.

Operator Action Report displays the summary of action taken on Vista Devices.

J. Vista Action Groups and Action Messages: Digital Video Camera and Command Files can be
associated with Vista actions.

K. Monitoring and Control from Alarm View, Control Map and Floor Plan