Академический Документы
Профессиональный Документы
Культура Документы
HPSPS Series
Content
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Appendix
Appendix
Appendix
Appendix
System summary
System Identification
Voltage Control Summary
Equalize
Fast Charge
Temperature Compensation
Battery Test
Battery Current Limit
Active Voltage Control
LVD1 (Low Volts Disconnect 1)
LVD2 (Low Volts Disconnect 2)
Even Log and Data Log Configuration
Rectifier Overview
A
B
C
D
HPSPS
HPSPS
HPSPS
HPSPS
Series
Series
Series
Series
Configuration
Configuration
Configuration
Configuration
Setting
Setting
Setting
Setting
Non
CDC
Non
CDC
CDC 48V
48V
CDC 24V
24V
1. System Summary
Includes a diagram of the NES, which shows DC distribution, rectifier, Supervisory Module, and
battery tray graphics.
Note
While the number of rectifier graphics is representative, only one battery tray graphic is
shown in all cases (regardless of the actual number of trays at the power system).
Special right-click menus apply, with functions enabling you to shut down and restart a
rectifier, show load indicators, change the rack layout, copy, paste, and so on.
Icons are superimposed when related alarms occur and when the Show Load option is
selected, as follows.
Urgent alarm applies for the unit (rectifier, Supervisory Module, or battery tray)
Non-Urgent alarm applies for the unit
Phase Fail alarm applies for the unit
Indicates relative load of the rectifier or (on Supervisory Module graphic) total
for system
Rest the mouse pointer over a graphic to show a popup panel containing brief details
about that rectifier or Supervisory Module.
Displays, as part of the power system diagram, the following main operating values (read-only,
sent by the Supervisory Module):
o
o
o
o
o
Load Current
Rectifier Current
Battery Current
Bus Voltage
AC Voltage and AC Current (only if AC Metering is enabled).
Load Current
Bus Voltage
Rectifier Current
Battery Current
Lists, in the Alarms area, all active alarms and Digital Inputs, showing each item's type, as
follows.
Urgent
Non-Urgent
Informational (not mapped as Urgent nor Non-Urgent)
Tip
In the Battery Trays area, displays the following battery-related values (read-only, sent by the
Supervisory Module):
Battery Temperature
Ah Discharge
If a valid temperature value is received, displays a thermometer icon and the ambient room
temperature at the power system, in degrees Celsius or Fahrenheit, depending on the language
setting (read-only, sent by the Supervisory Module).
Indicates, in the Voltage Control Summary area, each Control Functions present status, as
follows.
Active
Enabled but inactive (manual process) (also Battery Test passed)
Enabled but inactive (automatic process)
Disabled or Unknown
Failed (Battery Test and LVD only)
No information has been received from the power system
Tip
Shows ? data values when no information has been received from the Supervisory Module
Shows O/R for values that are outside their full normal operating range (usually with a
temperature value where the relevant sensor is faulty or not connected)
In the System Summary view, right-click the correct rectifier graphic and select Shutdown
Rectifier from the menu.
A dialog will then appear, asking you to confirm your action.
To restart a rectifier
1
In the System Summary view, right-click the correct rectifier graphic and select Restart
Rectifier from the menu.
A dialog will then appear, asking you to confirm your action.
2. System Identification
2.1 Identity
The System Identification view shows the following identification parameter values at the Supervisory
Module, and a button. The Editable column indicates values you can change.
Value
Editable
Interface Version
No
Description
S3P interface version.
No
Product Type
No
Software Version
No
No
BSP SW Version
No
LDR SW Version
No
Hardware Version
No
Run Up Date
No
Serial Number
No
Manufacturer Name
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Contact (h)
Yes
Yes
Note
A ? indicates that no information has been received from the Supervisory Module.
In the System Identification view, click on the value you want to change. That field is
given the focus - it changes to white and shows a cursor.
Edit the field as required entering your new value.
Press ENTER.
SM45 Date Time is must be same with local site date and time.
Click button
Note
Monitor Communications view shows parameter values related to Supervisory Module communications in a
network, including the automatic sending of e-mail messages to report alarms (optional).
Items are listed here in display order, under each display area.
Serial Area
This area shows the following items.
S3P Address (c)
Baud Rate (d)
Modem Area
This is for next implementation.
Ethernet Area
This is for next implementation.
SNMP Area
This is for next implementation.
Voltage at which to float charge the batteries. The actual bus voltage
will be adjusted by Temperature Compensation and othe control
functions.
Min Voltage
Battery Temperature
Operating Voltage
Battery Current
The total current flowing into the batteries. The supervisory module
uses the sum of any current inputs mapped as battery shunts. If no
input is mapped and a load current is available, the battery current is
calculated as Rectifier Current Load Current, otherwise its is
unavailable. If positive, the battery is being charged.
Target Voltage
The voltage maintained by AVC. AVC will set the Base Voltage to
attempt to maintain the Bus Voltage to this value.
Bus Voltage
DC output bus voltage. The processed system bus voltage from the
bus voltage sensor. If the bus voltage sensor has failed, the system
bus voltage is determined from the rectifier output voltages.
Control Voltage
The voltage sent to the rectifiers. This is set to the Target Voltage plus
the AVC Offset.
4. Equalize
The Equalize process applies an elevated charge to the battery. The aim of the Equalize process is to
replenish and balance the charge loss between batteries cells, caused by self-discharge over time.
Equalize may be initiated automatically after a period (period equalize) or manually.
When Periodic Equalize is activated, the Bus Voltage is raised (typically by a few volts) for a specified
time, or until the equalize process is stopped manually.
The time until the current Equalize cycle will stop automatically .
The time at which the next Periodic Equalize cycle will start.
Enable (a)
Voltage (b)
The bus voltage maintained during an Equalize cycle. The bus voltage
is further adjusted by Temperature Compensation.
Duration (c)
The date and time of the first Periodic Equalize cycle. Subsequent
cycles will accord every Equalize Interval after that.
Interval (e)
Start button Click to send a command to start Manual Equalize at the power system
(unavailable when this function cannot operate)
Stop button Click to send a command to stop Manual Equalize in progress at the power
system (unavailable when this function cannot operate).
5. Fast Charge
Fast Charge automatically provides a higher-than-normal charge to the power system's batteries, to
quickly boost their charge after an AC power failure, when either of the following trigger events occur.
The batteries are partially discharged and bus voltage drops below a configured value.
When Fast Charge is active, an Offset Voltage is applied to boost the Operating Voltage. If AC power
then fails at the power system, the Fast Charge Status changes to Suspended.
An active Fast Charge will stop when any of the following occur.
The configured Maximum Duration time expires, or the accumulated Ampere-hours of charging
reaches the required Recharge percentage.
Note
Bus Voltage
The present voltage of the bus at the power system, as read by the Supervisory
Module
Battery Capacity
Ah Discharged
Offset
The voltage adjustment calculated by the Fast Charge process (non-zero only
when Periodic Equalise is active)
Active
Enabled but inactive
Disabled or unknown
No information received from power system
Click to send a command to stop a Fast Charge in progress at the power system
(unavailable when this function cannot operate).
When Fast Charge is active, this value shows the number of minutes since it
was started.A zero indicates that Fast Charge has been active less than a
minute. N/A indicates it is inactive or disabled.
Indicates if Fast Charge is enabled or disabled at present you can change this
value (see below)
The voltage the power system attempts to maintain during a Fast Charge.This
excludes adjustments for Temperature Compensation.
Stop button
Elapsed Time
Enable (a)
Voltage (b)
Start Conditions
Voltage Threshold (c)
Stop Conditions
Recharge percentage (e)
The system voltage below which, if the batteries are not fully charged,
a Fast Charge will automatically start when AC power is restored.
The percentage of discharge below which a Fast Charge will
automatically start when AC power is restored (percentage of rated
Ampere-hours of battery capacity).
The battery recharge level at which a Fast Charge will stop. This is
expressed as a percentage of the amount the batteries have
discharged.For example, if:
Note
A ? indicates that no information has been received from the Supervisory Module. N/A indicates a
value that does not currently apply.
On the Fast Charge view, click in the Fast Charge field and select the new value.
On the Fast Charge page, click the Stop button (unavailable if Fast Charge is not Active).
Check the Supervisory Modules response. The Status box at the top should immediately
change to Stopping, and then (when the Supervisory Module responds) to Inactive.
6. Temperature Compensation
Temperature Compensation is an automatic process whose purpose is to maintain battery charge level
when battery temperature varies from the manufacturers specified Reference Temperature.
Use the Temperature Compensation view to:
Battery Temperature
Enable (a)
Slope (b)
The battery temperature above which the voltage adjustment for Temperature
Compensation remains a negative constant. This sets the minimum voltage
adjustment.
The battery temperature below which the voltage adjustment for Temperature
Compensation remains a positive constant. This sets the maximum voltage
adjustment.
The total amount of voltage adjustment calculated by the Temperature
Compensation process, in millivolts. This positive or negative value is summed
with the uncompensated voltage* to provide the system Operating Voltage, and
is:
Constant for battery temperatures above the High Cutoff, or below the
Low Cutoff
Offset voltage
Float Voltage
Note
A ? indicates that no information has been received from the Supervisory Module. N/A indicates a
value that does not currently apply.
In the Temperature Compensation view, click in the Temperature Compensation field and select
the new value.
7. Battery Test
Battery Tests should be done on-site during power system installation and when new battery strings are
installed at the power system. They should also be done at regular intervals (typically every six months).
Note
Use the
A manually started Battery Test will interrupt any other active Control Function process. When a
Battery Test is active, other Control Functions are disabled.
Battery Test view to:
View Battery Test parameters and related system values.
Enable and disable Battery Test.
Change Battery Test parameter settings if required.
Manually start and Stop a Battery Test.
Manually reset a Failed Battery Test alarm.
To enable or disable Battery Test
In the Battery Test view, click in the Battery Test field and select the new value.
To manually start a Battery Test
1
In the Battery Test view, check the configured values and enable Battery Test if necessary
(see above).
2
Click the Start button.
Provided all Battery Test start conditions are met, the status should change to Active when the
Supervisory Module responds.
Note
A scheduled Battery Test will automatically start when all its start conditions* are met.
The status should change to Inactive when the Supervisory Module responds.
Note
The status should change from Failed to Inactive when the Supervisory Module responds.
Battery Current
The Battery Current at the power system, in Amps.
Start button
Click to send a command to the Supervisory Module to start a Battery Test at the power system.
Unavailable when this function cannot operate.
Stop button
Click to send a command to the Supervisory Module to stop a Battery Test in progress at the power
system.
Unavailable when this function cannot operate.
Remaining Time
The number of minutes since Battery Test was started (non-zero only when Battery Test is active)
Next Start Time
The time remaining before the next scheduled Battery Test is due to start; based on the configured
Interval value and the time of the last Battery Test or Supervisory Module reset.
(N/A if Battery Test is active.)
Lockout Remaining
The amount of lockout time remaining (in hours and minutes), before a Battery Test can start, following
restoration of AC power.
A zero or N/A value indicates that Battery Test is not locked out.
Enable (a)
Indicates if Battery Test is enabled or disabled at present you can change this value (see below)
First Date / Time
The date and time of the first Battery Test. Subsequent cycles will accord every battery test interval after
that.
Interval
The minimum number of days before a scheduled Battery Test can activate (0 to 365)
This whole number of days must elapse following the last Battery Test or Supervisory Module reset
(whichever is the later).
Zero indicates that no Battery Tests are scheduled to start automatically.
Duration
The maximum number of minutes that a Battery Test can be active at the power system. After this time,
an active Battery Test will be automatically stopped.
Termination Voltage
The minimum bus voltage the power system can drop to during an active Battery Test. On reaching or
falling below this voltage, the test will be automatically stopped by the Supervisory Module.
The configured value should be greater than:
Enable (a)
Current Limit (b)
Engine Run
Present status (icon)
Active
Enabled but inactive
Disabled or unknown
No information received from power system
Enable (c)
Limit
Digital Input
Number of digital input. If Engine Run is enabled and the digital input
is active, the Target Voltage setting will be reduced until the battery
charge falls below this value.
Note
A ? indicates that no information has been received from the Supervisory Module. N/A indicates a
value that does not currently apply.
On the Battery Current Limit view, click in the Enable field and select the new value.
Bus Voltage
Target Voltage
The Bus Voltage reading at the power system (read-only)This and the Target
Voltage are the inputs to the AVC process.
A voltage determined from the Operating Voltage (as calculated by the Battery
Current Limit process when enabled) (read-only)If AVC is also operating, the
system will further adjust the Target Voltage to give the final Control Voltage.
Active
Enabled but inactive
Disabled or unknown
No information received
Enable (a)
Rectifier Base Voltage is the voltage the Supervisory Module instructs the rectifiers to provide.
Note
A ? indicates that no information has been received from the Supervisory Module. N/A indicates a
value that does not currently apply.
In the Active Voltage Control view, click in the Active Voltage Control field and select the
new value.
Bus Voltage
Present status (icon)
The present voltage of the bus at the power system, as read by the
Supervisory Module
Active
Enabled but inactive
Disabled or unknown
No information received
Enable (a)
LVD1 is enabled.
Note
A ? indicates that no information has been received from the Supervisory Module. N/A indicates a
value that does not currently apply.
On the LVD1 view, click in the Enable field and select the new value.
Bus Voltage
Present status (icon)
The present voltage of the bus at the power system, as read by the
Supervisory Module
Active
Enabled but inactive
Disabled or unknown
No information received
Enable (a)
LVD2 is enabled.
Disconnect Voltage
Reconnect Voltage
Recognition Period
Inhibit Period
Note
A ? indicates that no information has been received from the Supervisory Module. N/A indicates a
value that does not currently apply.
On the LVD1 view, click in the Enable field and select the new value.
The size of the even log. When the even log size is changed,
all existing even log entries are erased.
The time between each data log record. The Data Log Off
Normal Interval is used instead when the Bus Voltage differs
from the Float Voltage by more than the Data Log Off Normal
Offset Voltage. Data log entries are also written whenever an
event is logged.
The time between each log record when the Bus Voltage
differs from the Float Voltage by more than the Data Log Off
Normal Offset Voltage.
The off normal data log runs when the Bus Voltage differs
from the Float Voltage by this value.
The size of the data log. When the data log size is changed,
all existing even log entries are erased.
View the registration status and latest operating values received from the rectifiers.
Restart all rectifiers when required.
Reset all Comms Lost rectifier alarms.
View and possibly change rectifier configuration parameters.
(SM60/65 only) View and possibly change rectifier addressing parameters (these settings are
fixed for SM40/45s).
Items are listed below in display order, under each display area.
Displayed N/A or - values indicate that no information has been received from the Supervisory Module
about the rectifier, or that the rectifier is not communicating with the Supervisory Module.
Rectifiers Table
This table shows the following Rectifier status and operating values.
You cannot edit any of these values.
Num
Registered
Indicates whether or not the rectifier is registered with the Supervisory Module
Identity
AC Voltage
Voltage
Current
Heatsink Temperature
AC Fail
Comms Lost
Indicates whether or not a Comms Lost condition applies for the rectifier
Status
In Startup
Rectifier Is Shutdown
Low Mains
Low Voltage
High Mains
High Voltage
OVSD Tripped
Comms Lost
Fan Fail
Fuse Fail
Phase Fail
Current Limit
Power Limit
Temp Limit
You can also shut down and restart individual rectifiers from the System Summary
diagram. Right-click on the rectifier graphic and select Shutdown Rectifier or Restart
Rectifier as required.
Set about 0.75 to 1.5V greater than Maximum System Voltage to prevent false OVSD trips.
Ensure the load can operate safely at this voltage.
Time a rectifier waits before commencing to ramp up its output current during the power-up
sequence - (2 to 600 sec)
If LVD is enabled and Rectifier Shutdown is used, this value should not exceed LVD
Recognition Time. This allows time for the Supervisory Module to restart rectifiers before an
LVD trip occurs.
Output Ramp-up Slope (d)
Rate at which a rectifier increases its current limit level while powering up (1 to 100 A/sec).
Set slow enough to limit any current surges, yet fast enough to allow the system to become
operational as quickly as possible.
AC Voltage setpoint above which the rectifier starts limiting its input current and generates a
High AC Voltage condition.
(Allowed range 1 to 600 V)
Low AC Threshold (f)
AC Voltage setpoint below which the rectifier starts limiting its input current and generates a Low
AC Voltage condition (allowed range 1 to 600 V)
Setting values below 180V will result in rejected rectifier commands.
If there is a requirement to limit the rectifier input current, adjust this value to:
Out Power / (AC In Current x Rectifier Efficiency)
Where: