Outdoor Units R-410A RZQS-DV1

1
t A i n y U k 1S r V o AD t o0- i d1S lt4Q puZ- SRO

Outdoor units for pair, twin, triple, double twin application


The Sky Air Inverter is developed for use in shops, restaurants and
small offices. This innovative Daikin unit provides a more
comfortable environment and offers great savings in energy
consumption to shop and office owners.

During start up, the room can be cooled down or heated very quickly.
Once the temperature in the room has reached its set point, the low
power operation starts to save energy.

Daikin outdoor units are neat and sturdy and can be mounted easily
on a roof or terrace or simply placed against an outside wall.

The use of inverter type outdoor units results in an air conditioning


system with a high energy efficiency and very low sound level

Outdoor units are fitted with either a swing or scroll compressor,


renowned for low noise and high energy efficiency

An inverter driven compressor allows the capacity to be adjusted


precisely to match variations in room and outside temperatures.

A special acryl precoated fin for anti-corrosion treatment on the heat


exchanger ensures greater resistance against severe weather
conditions

Features

Split Sky Air Outdoor Units

Outdoor Units R-410A RZQS-DV1

Specifications

2-1 NOMINAL CAPACITY AND


NOMINAL INPUT

RZQS71D7V1B

RZQS100D7V1B

RZQS125D7V1B

RZQS140D7V1B

FCQ71C7VEB

FCQ100C7VEB

FCQ125C7VEB

FCQ140C7VEB

For
combination
indoor units +
outdoor units

Indoor Units

Cooling
capacity

Standard

kW

7.1

10.0

12.5

14.0

Heating
capacity

Standard

kW

8.0

11.2

14.0

16.0

Power Input
For
combination
indoor units +
outdoor units

1
Cooling

Standard

kW

2.28

3.22

4.02

5.36

Heating

Standard

kW

2.35

3.28

4.06

4.98

EER

Nominal

3.11

3.11

3.11

2.61

COP

Nominal

3.41

3.41

3.45

3.21

Energy Label

Cooling

Heating

1,141

1,608

2,010

2,682

Annual energy consumption kWh

FCQH71D7VEB

FCQH100D7VEB

FCQH125D7VEB

FCQH140D7VEB

Cooling
capacity

Indoor Units
Standard

kW

7.1

10.0

12.5

14.0

Heating
capacity

Standard

kW

8.0

11.2

14.0

16.0

Power Input
For
combination
indoor units +
outdoor units

Cooling

Standard

kW

2.15

2.90

3.88

4.65

Heating

Standard

kW

2.16

2.95

3.79

4.69

EER

Nominal

3.30

3.45

3.22

3.01

COP

Nominal

3.70

3.80

3.69

3.41

Energy Label

Cooling

Heating

1,076

1,449

1,941

2,326

Annual energy consumption kWh

FBQ71C7VEB

FBQ100C7VEB

FBQ125C7VEB

FBQ140C7VEB

Cooling
capacity

Indoor Units
Standard

kW

7.1

10.0

12.5

13.4

Heating
capacity

Standard

kW

8.0

11.2

14.0

15.0

Power Input
For
combination
indoor units +
outdoor units

Cooling

Standard

kW

2.18

3.03

3.98

4.77

Heating

Standard

kW

2.25

3.07

4.11

4.67

EER

Nominal

3.26

3.30

3.14

2.81

COP

Nominal

3.55

3.65

3.41

3.21

Energy Label

Cooling

Heating

1,089

1,515

1,990

2,384

Annual energy consumption kWh

FHQ71BVV1B

FHQ100BVV1B

FHQ125BVV1B

Cooling
capacity

Indoor Units
Standard

kW

7.1

10.0

12.5

Heating
capacity

Standard

kW

8.0

11.2

14.0

Power Input
For
combination
indoor units +
outdoor units

Cooling

Standard

kW

2.51

3.56

4.55

Heating

Standard

kW

2.75

3.85

4.86

EER

Nominal

2.83

2.81

2.75

COP

Nominal

2.91

2.91

2.88

Energy Label

Cooling

Heating

1,254

1,779

2,273

Annual energy consumption kWh

FAQ71BVV1B

FAQ100BVV1B

FDQ125B8V3B9

Cooling
capacity

Indoor Units
Standard

kW

7.1

10.0

12.5

Heating
capacity

Standard

kW

8.0

11.2

14

Cooling

Standard

kW

2.44

3.56

4.30

Heating

Standard

kW

2.49

3.49

3.97

Power Input

Split Sky Air Outdoor Units

Outdoor Units R-410A RZQS-DV1

Specifications

2-1 NOMINAL CAPACITY AND


NOMINAL INPUT

For
combination
indoor units +
outdoor units

RZQS71D7V1B

RZQS100D7V1B

RZQS125D7V1B

Nominal

2.91

2.81

2.91

COP

Nominal

3.21

3.21

3.53

Energy Label

Cooling

Heating

1,220

1,779

2,148

EER

Annual energy consumption kWh

FVQ71BV1B

FVQ100BV1B

FVQ125BV1B

Cooling
capacity

Indoor Units
Standard

kW

7.1

10.0

12.5

Heating
capacity

Standard

kW

8.0

11.2

14.0

Power Input
For
combination
indoor units +
outdoor units

Cooling

Standard

kW

2.53

3.56

4.45

Heating

Standard

kW

2.49

3.49

4.36

EER

Nominal

2.81

2.81

2.81

COP

Nominal

3.21

3.21

3.21

Energy Label

Cooling

Heating

1,265

1,779

2,225

RZQS71D7V1B

RZQS100D7V1B

Annual energy consumption kWh

2-2

TECHNICAL SPECIFICATIONS

Casing

Colour

Dimensions

Unit

Weight

Paintable galvanized steel plate


Height

mm

770

1,170

1,170

1,170

Width

mm

900

900

900

900

Depth

mm

320

320

320

320

Height

mm

900

1,349

1,349

1,349

Width

mm

980

980

980

980

Depth

mm

420

420

420

420

kg

68

103

103

103

Unit
Packed Unit

Heat
Exchanger

Dimensions

Length

kg

72

119

119

119

mm

857

857

857

857

mm

1.4

1.4

1.4

1.4

Nr of Rows
Fin Pitch

Nr of Passes
Face
Area

Nr of Stages

10

10

10

0.641

0.98

0.98

0.98

34

52

52

52

Tube type
Fin

Hi-XSS(8)
Type

WF fin

Treatment
Fan

Anti-corrosion treatment (PE)

Type

Propeller

Discharge direction

Horizontal

Quantity

Air Flow Rate


(nominal at
230V)

Cooling

m/min

52

96

100

97

Heating

m/min

48

90

90

90

Motor

Quantity
Model

Motor

Fan

Speed
(nominal)

Motor

Steps

KFD-325-70-8A

Brushless DC Motor

Brushless DC Motor

Brushless DC Motor

rpm
Cooling
(Standard
)

800

800

850

830

rpm
Heating
(Standard
)

745

760

760

760

Output

70

70

70

70

Drive

RZQS140D7V1B

Ivory White

Material

Packing

RZQS125D7V1B

RZQS140D7V1B

Direct drive

Split Sky Air Outdoor Units

Outdoor Units R-410A RZQS-DV1

2
2-2

Specifications
TECHNICAL SPECIFICATIONS

Compressor

Quantity
Motor

RZQS71D7V1B

RZQS100D7V1B

RZQS125D7V1B

RZQS140D7V1B

Model

2YC63DXD

JT100G-VD

JT100G-VD

JT100G-VD

Type

Hermetically sealed swing


compressor

Hermetically sealed scroll


compressor

Hermetically sealed scroll


compressor

Hermetically sealed scroll


compressor

1,700

2,200

2,200

2,200

33

33

33

-5.0

Motor
Output

Crankcas W
e Heater
Starting Method
Operation
Range

Sound Level
(nominal)

Cooling

CDB

-5.0

-5.0

-5.0

Max

CDB

46

46

46

46

Heating

Min

CWB

-15

-15

-15

-15

Max

CWB

15.5

15.5

15.5

15.5

Cooling

Sound
Power

dBA

65

67

67

68

Sound
dBA
Pressure
(Standard
)

49

51

51

52

Sound
dBA
Pressure
(Standard
)

51

55

53

54

dBA

47

49

49

50

2.75

3.7

3.7

3.7

Sound Level
(Night quiet)

Sound Pressure

Refrigerant

Type
kg

Control

Expansion valve (electronic type)

Nr of Circuits
Type
Charged Volume
Piping
connections

Liquid (OD)

l
Quantity

FVC50K

Daphne FVC68D

Daphne FVC68D

Daphne FVC68D

0.75

1.0

1.0

1.0

9.52

9.52

15.9

15.9

26

26

Type

Flare connection

Diameter
(OD)
Gas

mm

Quantity

9.52

9.52

Type

Flare connection

Diameter
(OD)
Drain

mm

Quantity

15.9

15.9

Type

Piping Length

Hole

Diameter
(OD)

mm

Minimum

26

26

Maximum m

30

50

50

50

Equivalen m
t

40

70

70

70

Chargele
ss

30

30

30

30

Additional Refrigerant
Charge
Installation
height
difference

R-410A

Charge

Refrigerant Oil

Inverter driven

Min

Heating

m
kg/m

Maximum m

Max. internunit level


difference

see installation manual 4PW49302-1


15

30

30

30

0.5

0.5

0.5

0.5

Heat Insulation

Both liquid and gas pipes

Defrost Method

Pressure equalising

Defrost Control

Temperature

Capacity Control Method

Inverter controlled

Split Sky Air Outdoor Units

Outdoor Units R-410A RZQS-DV1

2
2-2

Specifications
TECHNICAL SPECIFICATIONS

RZQS71D7V1B

RZQS100D7V1B

Safety Devices

RZQS125D7V1B

RZQS140D7V1B

High pressure switch


Fan motor thermal protector

1
2

Fuse
Standard
Accessories

Item

Tie-wraps

Quantity

Item

Installation manual

Quantity

Notes

Nominal cooling capacities are based on : indoor temperature : 27CDB, 19CWB, outdoor temperature : 35CDB,
equivalent refrigerant piping : 5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20CDB, outdoor temperature : 7CDB, 6CWB,
equivalent refrigerant piping : 5m, level difference : 0m

2-3

ELECTRICAL SPECIFICATIONS

Power Supply

RZQS71D7V1B

RZQS100D7V1B

Name
Phase

Current
Wiring
connections

Hz

Voltage

V
Minimum

50

50

50

50
220-240

198

198

198

198

Maximum V

264

264

264

264

32

32

Minimum Ssc () value

kVa

Recomended fuses

For Power
Supply

RZQS140D7V1B

1~

Frequency
Voltage range

RZQS125D7V1B

V1

Dummy
20

32

Remark

see installation manual 4PW49302-1

For connection Remark


with indoor

see installation manual 4PW49302-1

Power Supply Intake

Outdoor unit only

Notes

See separate drawings for electrical data


(1) European/international technical standard setting the limits for harmonic currents produced by equipment
connected to public low-voltage system with input current > 16A smaller than or equal to 75A per phase.
(2) Short-circuit power
Power supply to the FDQ
indoor unit is separate

Split Sky Air Outdoor Units

Outdoor Units R-410A RZQS-DV1

Electrical data

RZQS71-140DV1
Unit combination
Indoor unit
Outdoor unit

Hz-volts

Power supply
Comp.
Voltage range MCA TOCA MFA MSC RLA

OFM
kW

IFM
FLA

kW

FLA

1
3

NOTES
1

2
3

4
5

6
7

RLA is based on the following conditions:


Power supply: 50Hz - 230V
Cooling
Indoor temperature 27CDB/19CWB
Outdoor temperature 35CDB
Heating
Indoor temperature 20.0CDB
Outdoor temperature 7.0CDB/6.0CWB
TOCA means the total value of each OC set
Voltage range
Units are suitable for use on electrical systems where
voltage supplied to unit terminals is not below or
above listed operation range limits
Maximum allowable voltage unbalance between
phases is 2%
MCA represents maximum input current., MFA
represents capacity which may accept MCA
(next lower standard fuse rating, min.15A)
Select wire size based on the larger value of MCA or
TOCA
MFA is used to select the circuit breaker and the
ground fault circuit interrupter (earth leakage circuit
breaker)

SYMBOLS
MCA
TOCA
MFA
MSC
RLA
OFM
IFM
FLA
kW

: Min. Circuit Amps (A)


: Total Over Current Amps (A)
: Max. Fuse Amps (A) (See note 7)
: MSC means the max. current during the
starting of compressor. (A)
: Rated Load Amps (A)
: Outdoor Fan Motor (A)
: Indoor Fan Motor
: Full Load Amps
: Fan Motor Rated Output (kW)

3D063321

Split Sky Air Outdoor Units

Outdoor Units R-410A RZQS-DV1

Options

RZQ(S)71-140DV1
Kit name

1
4

Name of option

RZQ71D7V1B

RZQ100D7V1B

RZQ125D7V1B

RZQ140D7V1B

RZQS71D7V1B

RZQS100D7V1B

RZQS125D7V1B

RZQS140D7V1B

RZQ100B8W1B

RZQ125B8W1B

RZQ140B8W1B

Central drain plug

EKDK04
Twin

Refrigerant branch piping

KHRQ22M20TA (KHRQ58T): see note

Triple

Double-twin

Demand adapter kit

KHRQ127H (KHRQ58H): see note


KHRQ22M20TA (KHRQ58T): see note
(3x)
KRP58M51

NOTE
1

For RZQ100-140B8W1B in combination with FCQ35-71C, FCQH71C or FCQH71D use the refrigerant branch piping mentioned between brackets.

3TW26739-1F

Split Sky Air Outdoor Units

Outdoor Units R-410A RZQS-DV1

Capacity tables

5-1

Combination table

RZQ(S)71-140DV1
Multi Combination Possibilities:

P = Pair

71

100

125

140

2 = Twin

35+35

50+50

60+60

71+71

3 = Triple

35+35+35

4 = Double Twin

50+50+50 (*)

50+50+50 (*)

35+35+35+35 (*)

35+35+35+35

1
5

(*) Max capacity depend on outdoor unit

RZQ71D7V1B

P
2

P
2

FVQ125BV1B

FVQ71BV1B

FVQ125BV1B

FVQ71BV1B

FVQ100BV1B

FDQ125B8V3B

Floor standing

P
P

FVQ100BV1B

FDQ125B8V3B

FAQ71BVV1B

FAQ100BVV1B

FUQ125BVV1B

FUQ71BVV1B

P
P

FAQ100BVV1B

Wall mounted High ESP Duct


FAQ71BVV1B

FUQ125BVV1B

FHQ125BVV1B

P
2

4way ceiling

FUQ100BVV1B

FHQ125BVV1B

FHQ71BVV1B

FHQ60BVV1B

FHQ100BVV1B

FHQ100BVV1B

FHQ35BVV1B

FBQ140C7VEB

2
P

P
P

FUQ100BVV1B

Floor standing

FUQ71BVV1B

Wall mounted High ESP Duct

Ceiling suspended

FHQ50BVV1B

FHQ35BVV1B

FBQ140C7VEB

FBQ125C7VEB

FBQ71C7VEB

FBQ100C7VEB

FBQ60C7VEB

New Duct (medium ESP)


FBQ35C7VEB

FFQ60B8V1B

FFQ50B8V1B

P
P

FHQ71BVV1B

FHQ60BVV1B

4way ceiling

FHQ50BVV1B

FBQ125C7VEB

2
P

FBQ100C7VEB

FBQ71C7VEB

Ceiling suspended

FBQ60C7VEB

FFQ35B8V1B

FCQ140C7VEB
P

FBQ50C7VEB

FFQ60B8V1B

FBQ35C7VEB

FFQ50B8V1B
2

2
P

2x2 cassette

P
2

New Duct (medium ESP)

FBQ50C7VEB

FFQ35B8V1B

FCQ140C7VEB

FCQ125C7VEB

FCQ71C7VEB

FCQ100C7VEB

2
P

RZQ125D7V1B

FCQ60C7VEB

FCQ50C7VEB

FCQH140D7VEB

FCQ35C7VEB

Thin cassette

RZQ100D7V1B
RZQ140D7V1B

FCQ125C7VEB

Model name

HH Cassette
FCQH71D7VEB

Sky-air

2
P

FCQ100C7VEB

FCQ71C7VEB

RZQ140B8W1B

2x2 cassette

FCQ60C7VEB

RZQ140D7V1B

2
P

FCQ50C7VEB

RZQ125B8W1B

FCQ35C7VEB

RZQ125D7V1B

Thin cassette

FCQH140D7VEB

RZQ100B8W1B

FCQH125D7VEB

RZQ71D7V1B
RZQ100D7V1B

FCQH100D7VEB

Model name

FCQH125D7VEB

FCQH71D7VEB

HH Cassette
FCQH100D7VEB

Sky-air

P
P

NOTES

1
2

Individual indoor capacities are not given because the combinations are for simultaneous operation (= indoor units installed in the same room)
When different indoor models are used in combination, designate the remote control that is equipped with the most function as the main unit.

3TW26739-2C

Split Sky Air Outdoor Units

Outdoor Units R-410A RZQS-DV1

Capacity tables

5-2

Cooling capacity tables

RZQS71DV1

1
5

Coefficient of power input. (-)

Cooling

Capacity range

Rated point

Cooling capacity (kW)


Cooling capacity

Indoor

Outdoor temp. (CDB)

EWB

EDB

(C)

(C)

TC
(kW)

25
SHC
(kW)

CPI
(-)

TC
(kW)

30
SHC
(kW)

CPI
(-)

TC
(kW)

35
SHC
(kW)

CPI
(-)

TC
(kW)

40
SHC
(kW)

CPI
(-)

3DTW3172-2

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1BF) x (DB*EDB)
Add SHC* to SHC.
4. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
:0m
5. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
6. The value contains less than 5% error acording to indoor unit type.
7. Air flow rate and BF are tabulated below.
(Pair)

Model
AFR
(BF)

FCQH71D
21
(0.17)

FCQ71C
15.5
(0.19)

FBQ71
18
(0.08)

FHQ71
17
(0.10)

Model
AFR
(BF)

FCQ35Cx2
10.5x2
(0.28x2)

FFQ35x2
10x2
(0.25x2)

FBQ35Cx2
15x2
(0.15x2)

FHQ35x2
13x2
(0.2x2)

FAQ71
19
(0.08)

FVQ71
18
(0.16)

(Twin)

8. Rated power input of each model is tabulated below.


(Pair)

Model
Cooling

FCQH71D
2.15

FCQ71C
2.28

FBQ71C
2.18

FHQ71
2.51

FCQ35Cx2
2.59

FFQ35x2
2.61

FBQ35x2
2.25

FHQ35x2
2.66

FAQ71
2.44

FVQ71
2.53

(Twin)

Model
Cooling

Split Sky Air Outdoor Units

AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.

Caution:
TC and SHC are shown by kW

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)
(-)

Outdoor Units R-410A RZQS-DV1

Capacity tables

5-2

Cooling capacity tables

RZQS100DV1
Cooling

Coefficient of power input. (-)

1
5

Capacity range

Rated point

Cooling capacity (kW)


Cooling capacity

Indoor

Outdoor temp. (CDB)

EWB

EDB

(C)

(C)

TC
(kW)

25
SHC
(kW)

CPI
(-)

TC
(kW)

30
SHC
(kW)

CPI
(-)

TC
(kW)

35
SHC
(kW)

CPI
(-)

TC
(kW)

40
SHC
(kW)

CPI
(-)

3TW31722-2

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1BF) x (DB*EDB)
Add SHC* to SHC.
4. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
:0m
5. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
6. The value contains less than 5% error acording to indoor unit type.
7. Air flow rate and BF are tabulated below.
(Pair)

Model
AFR
(BF)

FCQH100D
34
(0.17)

FCQ100C
23.5
(0.16)

FBQ100C
32
(0.13)

FHQ100
24
(0.14)

Model
AFR
(BF)

FCQ50Cx2
12.5x2
(0.21x2)

FFQ50x2
12x2
(0.16x2)

FBQ50Cx2
16x2
(0.16x2)

FHQ50x2
13x2
(0.1x2)

Model
AFR
(BF)

FCQ35Cx3
10.5x3
(0.28x3)

FFQ35x3
10x3
(0.25x3)

FBQ35Cx3
16x3
(0.15x3)

FHQ35x3
13x3
(0.2x3)

FAQ100
23
(0.10)

AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)
(-)

Caution:
TC and SHC are shown by kW

FVQ100
28
(0.19)

(Twin)

(Triple)

8. Rated power input of each model is tabulated below.


(Pair)

Model
Cooling

FCQH100D
2.90

FCQ100C
3.22

FBQ100C
3.03

FHQ100
3.56

FCQ35Cx2
3.58

FFQ35x2
3.58

FBQ35x2
3.16

FHQ35x2
3.90

FCQ35Cx3
3.58

FFQ35x3
3.58

FBQ35x3
3.16

FHQ35x3
3.90

FAQ100
3.56

FVQ100
3.56

(Twin)

Model
Cooling
(Triple)

Model
Cooling

Split Sky Air Outdoor Units

10

Outdoor Units R-410A RZQS-DV1

Capacity tables

5-2

Cooling capacity tables

RZQS125DV1

1
5

Coefficient of power input. (-)

Cooling

Capacity range

Rated point

Cooling capacity (kW)


Cooling capacity

Indoor

Outdoor temp. (CDB)

EWB

EDB

(C)

(C)

TC
(kW)

25
SHC
(kW)

CPI
(-)

TC
(kW)

30
SHC
(kW)

CPI
(-)

TC
(kW)

35
SHC
(kW)

CPI
(-)

TC
(kW)

40
SHC
(kW)

CPI
(-)

3TW31732-2

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1BF) x (DB*EDB)
Add SHC* to SHC.
4. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
:0m
5. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
6. The value contains less than 5% error acording to indoor unit type.
7. Air flow rate and BF are tabulated below.
(Pair)

Model
AFR
(BF)

FCQH125D
34
(0.19)

FCQ125C
27.5
(0.19)

FBQ125C
39
(0.16)

FHQ125
30
(0.13)

Model
AFR
(BF)

FCQ60Cx2
13.5x2
(0.21x2)

FFQ60x2
15x2
(0.11x2)

FBQ60Cx2
18x2
(0.15x2)

FHQ60x2
17x2
(0.2x2)

Model
AFR
(BF)

FCQ50Cx3
12.5x3
(0.21x3)

FFQ50x3
12x3
(0.16x3)

FBQ50Cx3
16x3
(0.16x3)

FHQ50x3
13x3
(0.1x3)

FDQ125
45
(0.25)

AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.

Caution:
TC and SHC are shown by kW

FVQ125
32
(0.16)

(Twin)

(Triple)

(Double Twin)

Model
AFR
(BF)

FCQ35Cx4
10.5x4
(0.28x4)

FFQ35x4
10x4
(0.25x4)

FBQ35Cx4
16x4
(0.15x4)

FHQ35x4
13x4
(0.2x4)

8. Rated power input of each model is tabulated below.


(Pair)

Model
Cooling

FCQH125D
3.88

FCQ125C
4.02

FBQ125C
3.98

FHQ125
4.55

FCQ60Cx2
4.17

FFQ60x2
4.22

FBQ60x2
4.18

FHQ60x2
4.57

FCQ50Cx3
4.17

FFQ50x3
4.22

FBQ50x3
4.18

FHQ50x3
4.57

FAQ125
4.45

FUQ125
3.30

(Twin)

Model
Cooling
(Triple)

Model
Cooling

11

(Double Twin)

Model
Cooling

Split Sky Air Outdoor Units

FCQ35Cx4
4.17

FFQ35x4
4.22

FBQ35x4
4.18

FHQ35x4
4.57

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)
(-)

Outdoor Units R-410A RZQS-DV1

Capacity tables

5-2

Cooling capacity tables

RZQS140DV1
Cooling

Coefficient of power input. (-)

1
5

Capacity range

Rated point

Cooling capacity (kW)


Cooling capacity

Indoor

Outdoor temp. (CDB)

EWB

EDB

(C)

(C)

TC
(kW)

25
SHC
(kW)

CPI
(-)

TC
(kW)

30
SHC
(kW)

CPI
(-)

TC
(kW)

35
SHC
(kW)

CPI
(-)

TC
(kW)

40
SHC
(kW)

CPI
(-)

3TW31742-2

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1BF) x (DB*EDB)
Add SHC* to SHC.
4. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
:0m
5. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
6. The value contains less than 5% error acording to indoor unit type.
7. Air flow rate and BF are tabulated below.
(Pair)

Model
AFR
(BF)

FCQH140D
34
(0.20)

Model
AFR
(BF)

FCQH71Dx2 FCQ71Cx2
21x2
15.5x2
(0.17x2)
(0.19x2)

FBQ71Cx2
18x2
(0.08x2)

FHQ71x2
17x2
(0.1x2)

Model
AFR
(BF)

FCQ50Cx3
12.5x3
(0.21x3)

FBQ50Cx3
16x3
(0.15x3)

FHQ50x3
13x3
(0.1x3)

AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)
(-)

Caution:
TC and SHC are shown by kW

FCQ140C
27.5
(0.22)

(Twin)

(Triple)

FAQ71x2
19x2
(0.08x2)
(Double Twin)

FFQ50x3
12x3
(0.16x3)

Model
AFR
(BF)

FCQ35Cx4
10.5x4
(0.28x4)

FFQ35x4
10x4
(0.25x4)

FBQ35Cx4
16x4
(0.15x4)

FHQ35x4
13x4
(0.2x4)

8. Rated power input of each model is tabulated below.


(Pair)

Model
Cooling

FCQH140D
4.65

FCQ140C
5.36

(Twin)

Model
Cooling

FCQH71Dx2 FCQ71Cx2
4.99
5.12

FBQ71Cx2
4.95

FHQ71x2
5.10

FCQ50Cx3
5.12

FBQ50x3
4.95

FHQ50x3
5.10

(Triple)

Model
Cooling

FAQ71x2
5.01
(Double Twin)

FFQ50x3
4.89

Model
Cooling

Split Sky Air Outdoor Units

FCQ35Cx4
5.12

FFQ35x4
4.89

FBQ35x4
4.95

FHQ35x4
5.10

12

Outdoor Units R-410A RZQS-DV1

Capacity tables

5-2

Cooling capacity tables

RZQS140DV1

1
5

Coefficient of power input. (-)

Cooling

Capacity range

Rated point

Cooling capacity (kW)


Cooling capacity

Indoor

Outdoor temp. (CDB)

EWB

EDB

(C)

(C)

TC
(kW)

25
SHC
(kW)

CPI
(-)

TC
(kW)

30
SHC
(kW)

CPI
(-)

TC
(kW)

35
SHC
(kW)

CPI
(-)

TC
(kW)

40
SHC
(kW)

CPI
(-)

3TW31742-3

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1BF) x (DB*EDB)
Add SHC* to SHC.
4. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
:0m
5. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
6. The value contains less than 5% error acording to indoor unit type.
7. Air flow rate and BF are tabulated below.
(Pair)

Model
AFR
(BF)

FBQ140C
39
(0.14)

8. Rated power input of each model is tabulated below.


(Pair)

Model
Cooling

13

FBQ140C
4.77

Split Sky Air Outdoor Units

AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.

Caution:
TC and SHC are shown by kW

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)
(-)

Outdoor Units R-410A RZQS-DV1

Capacity tables

5-2

Cooling capacity tables

RZQS71-140DV1
Capacity in function of field piping length for non-inverter

1
5

Capacity (%)

Field piping length (m)


Cooling
Heating

Split Sky Air Outdoor Units

3TW31712-1

14

Outdoor Units R-410A RZQS-DV1

Capacity tables

5-3

Heating capacity tables

RZQS71DV1

1
5

Coefficient of power input. (-)

Heating

Rated point

Capacity range

Heating capacity (kW)


Heating capacity

Indoor
EDB

-15
TC
(kW)

(C)

-10
CPI
(-)

TC
(kW)

CPI
(-)

Outdoor temp. (CDB)


-5
0
TC
CPI
TC
CPI
(kW)
(-)
(kW)
(-)

6
TC
(kW)

10
CPI
(-)

TC
(-)

CPI
(-)

3TW31712-2

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1BF) x (DB*EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
(Pair)

Model
AFR
(BF)

FCQH71C
21
(0.17)

FCQ71C
15.5
(0.19)

FBQ71
18
(0.08)

FHQ71
17
(0.10)

Model
AFR
(BF)

FCQ35Cx2
10.5x2
(0.28x2)

FFQ35x2
10x2
(0.25x2)

FBQ35Cx2
16x2
(0.15x2)

FHQ35x2
13x2
(0.2x2)

FAQ71
19
(0.08)

FVQ71
18
(0.16)

(Twin)

10. Rated power input of each model is tabulated below.


(Pair)

Model
Heating

FCQH71D
2.16

FCQ71C
2.35

FBQ71
2.25

FHQ71
2.75

FCQ35Cx2
2.75

FFQ35x2
2.70

FBQ35Cx2
2.20

FHQ35x2
2.85

FAQ71
2.49

FVQ71
2.49

(Twin)

Model
Heating

15

Split Sky Air Outdoor Units

AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.

Caution:
TC and SHC are shown by kW

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)
(-)

Outdoor Units R-410A RZQS-DV1

Capacity tables

5-3

Heating capacity tables

RZQS100DV1
Heating

Coefficient of power input. (-)

1
5

Rated point

Capacity range

Heating capacity (kW)


Heating capacity

Indoor
EDB

-15
TC
(kW)

(C)

-10
CPI
(-)

TC
(kW)

CPI
(-)

Outdoor temp. (CDB)


-5
0
TC
CPI
TC
CPI
(kW)
(-)
(kW)
(-)

6
TC
(kW)

10
CPI
(-)

TC
(-)

CPI
(-)

3TW31722-2

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1BF) x (DB*EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.

AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)
(-)

Caution:
TC and SHC are shown by kW

(Pair)

Model
AFR
(BF)

FCQH100D
34
(0.17)

FCQ100C
23.5
(0.16)

FBQ100C
32
(0.13)

FHQ100
24
(0.14)

Model
AFR
(BF)

FCQ35Cx2
12.5x2
(0.21x2)

FFQ35x2
12x2
(0.16x2)

FBQ35Cx2
16x2
(0.16x2)

FHQ35x2
13x2
(0.1x2)

Model
AFR
(BF)

FCQ35Cx3
10.5x3
(0.28x3)

FFQ35x3
10x3
(0.25x3)

FBQ35Cx3
16x3
(0.15x3)

FHQ35x3
13x3
(0.2x3)

FAQ100
23
(0.10)

FVQ100
28
(0.19)

(Twin)

(Triple)

10. Rated power input of each model is tabulated below.


(Pair)

Model
Heating

FCQH100D
2.95

FCQ100C
3.28

FBQ100C
3.07

FHQ100
3.85

FCQ35Cx2
3.55

FFQ35x2
3.44

FBQ35x2
3.15

FHQ35x2
3.89

FCQ35Cx3
3.55

FFQ35x3
3.44

FBQ35x3
3.15

FHQ35x3
3.89

FAQ100
3.49

FUQ100
3.49

(Twin)

Model
Heating
(Triple)

Model
Heating

Split Sky Air Outdoor Units

16

Outdoor Units R-410A RZQS-DV1

Capacity tables

5-3

Heating capacity tables

RZQS125DV1

1
5

Coefficient of power input. (-)

Heating

Capacity range

Rated point

Heating capacity (kW)


Heating capacity

Indoor
EDB

-15
TC
(kW)

(C)

-10
CPI
(-)

TC
(kW)

CPI
(-)

Outdoor temp. (CDB)


-5
0
TC
CPI
TC
CPI
(kW)
(-)
(kW)
(-)

6
TC
(kW)

10
CPI
(-)

TC
(-)

CPI
(-)

3TW31732-2

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1BF) x (DB*EDB)
Add SHC* to SHC.
4. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
:0m
5. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
6. The value contains less than 5% error acording to indoor unit type.
7. Heating capacity include the drop of frost formation.
8. Air flow rate and BF are tabulated below.

AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.

Caution:
TC and SHC are shown by kW

(Pair)

Model
AFR
(BF)

FCQH125D
34
(0.19)

FCQ125C
27.5
(0.19)

FBQ125C
39
(0.16)

FHQ125
30
(0.13)

Model
AFR
(BF)

FCQ60Cx2
13.5x2
(0.21x2)

FFQ60x2
15x2
(0.11x2)

FBQ60Cx2
18x2
(0.15x2)

FHQ60x2
17x2
(0.2x2)

Model
AFR
(BF)

FCQ50Cx3
12.5x3
(0.21x3)

FFQ50x3
12x3
(0.16x3)

FBQ50Cx3
16x3
(0.16x3)

FHQ50x3
13x3
(0.1x3)

FDQ125
45
(0.25)

FVQ125
32
(0.16)

(Twin)

(Triple)
(Double Twin)

Model
AFR
(BF)

FCQ35Cx4
10.5x4
(0.28x4)

FFQ35x4
10x4
(0.25x4)

FBQ35Cx4
16x4
(0.15x4)

FHQ35x4
13x4
(0.2x4)

9. Rated power input of each model is tabulated below.


(Pair)

Model
Heating

FCQH125D
3.79

FCQ125C
4.06

FBQ125C
4.11

FHQ125
4.86

FCQ60Cx2
4.68

FFQ60x2
4.34

FBQ60x2
4.19

FHQ60x2
4.84

FCQ50Cx3
4.68

FFQ50x3
4.34

FBQ50x3
4.19

FHQ50x3
4.84

FAQ125
4.36

FUQ125
3.97

(Twin)

Model
Heating
(Triple)

Model
Heating

17

(Double Twin)

Model
Heating

Split Sky Air Outdoor Units

FCQ35Cx4
4.68

FFQ35x4
4.34

FBQ35x4
4.19

FHQ35x4
4.84

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)
(-)

Outdoor Units R-410A RZQS-DV1

Capacity tables

5-3

Heating capacity tables

RZQS140DV1
Heating

Coefficient of power input. (-)

1
5

Rated point

Capacity range

Heating capacity (kW)


Heating capacity

Indoor
EDB

-15
TC
(kW)

(C)

-10
CPI
(-)

TC
(kW)

CPI
(-)

Outdoor temp. (CDB)


-5
0
TC
CPI
TC
CPI
(kW)
(-)
(kW)
(-)

6
TC
(kW)

10
CPI
(-)

TC
(-)

CPI
(-)

3TW31742-2

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1BF) x (DB*EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.

AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)
(-)

Caution:
TC and SHC are shown by kW

(Pair)

Model
AFR
(BF)

FCQH140D
34
(0.20)

FCQ140C
27.5
(0.22)

Model
AFR
(BF)

FCQH71Dx2 FCQ71Cx2
21x2
15.5x2
(0.17x2)
(0.19x2)

FBQ71Cx2
18x2
(0.08x2)

FHQ71x2
17x2
(0.1x2)

Model
AFR
(BF)

FCQ50Cx3
12.5x3
(0.21x3)

FBQ50Cx3
16x3
(0.16x3)

FHQ50x3
13x3
(0.1x3)

(Twin)

FAQ71x2
19x2
(0.08x2)

(Triple)

(Double Twin)

FFQ50x3
12x3
(0.16x3)

Model
AFR
(BF)

FCQ35Cx4
10.5x4
(0.28x4)

FFQ35x4
10x4
(0.25x4)

FBQ35Cx4
16x4
(0.15x4)

FHQ35x4
13x4
(0.2x4)

10. Rated power input of each model is tabulated below.


(Pair)

Model
Heating

FCQH125D
4.69

FCQ125C
4.98

(Twin)

Model
Heating

FCQH71Dx2 FCQ71Cx2
5.26
5.46

FBQ71Cx2
5.06

FHQ71x2
5.70

FCQ50Cx3
5.46

FBQ50x3
5.06

FHQ50x3
5.70

(Double Twin)

(Triple)

Model
Heating

FAQ71x2
5.54

FFQ50x3
5.61

Split Sky Air Outdoor Units

Model
Heating

FCQ35Cx4
5.46

FFQ35x4
5.61

FBQ35x4
5.06

FHQ35x4
5.70

18

Outdoor Units R-410A RZQS-DV1

Capacity tables

5-3

Heating capacity tables

RZQS140DV1

1
5

Coefficient of power input. (-)

Heating

Capacity range

Rated point

Heating capacity (kW)


Heating capacity

Indoor
EDB

-15
TC
(kW)

(C)

-10
CPI
(-)

TC
(kW)

CPI
(-)

Outdoor temp. (CDB)


-5
0
TC
CPI
TC
CPI
(kW)
(-)
(kW)
(-)

6
TC
(kW)

10
CPI
(-)

TC
(-)

CPI
(-)

3TW31742-3

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1BF) x (DB*EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
(Pair)

Model
AFR
(BF)

FBQ140C
41
(0.14)

10. Rated power input of each model is tabulated below.


(Pair)

Model
Heating

19

FBQ140C
4.67

Split Sky Air Outdoor Units

AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.

Caution:
TC and SHC are shown by kW

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)
(-)

Outdoor Units R-410A RZQS-DV1

Dimensional drawing & centre of gravity

6-1

Dimensional drawing
unit (mm)

RZQS71DV1
Hole for anchor bolt
4-M12

1
2
3
4
5
6
7
8

Gas pipe connection J15.9 flare


Liquid pipe connection - J9.5 flare
Service port (in the unit)
Grounding terminal M5 (in switch box)
Refrigerant piping intake
Power supply wiring intake (knock out hole J34)
Control wiring intake (Knock out hole J27)
Drain outlet

3
1
6

3TW25144-1A

RZQS100-125-140DV1

Hole for anchor bolt


4-M12

1
2
3
4
5
6
7
8

Gas pipe connection J15.9 flare


Liquid pipe connection - J9.5 flare
Service port (in the unit)
Grounding terminal M5 (in switch box)
Refrigerant piping intake
Power supply wiring intake (knock out hole J34)
Control wiring intake (Knock out hole J27)
Drain outlet

3TW26364-1

Split Sky Air Outdoor Units

20

Outdoor Units R-410A RZQS-DV1

Dimensional drawing & centre of gravity

6-2

Centre of gravity

RZQS71DV1

1
6

4TW30469-3

RZQS100,125,140DV1

4TW29169-4

21

Split Sky Air Outdoor Units

Outdoor Units R-410A RZQS-DV1

Piping diagram

RZQS71-140DV1 (Pair)

Electronic
expansion
valve

7
Filter

Filter

Heat exchanger

4-way valve

Heat exchanger
High pressure
switch

Low pressure
sensor

Field piping J9.5 C1220T-0

Service port
5/16

Compressor
Filter
Field piping J15.9 C1220T-0
Accumulator

Indoor unit

Heating
Cooling

Outdoor unit
Stop valve
(with service port 5/16 flare)

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

3TW29165-1

RZQS71-140DV1 (Twin)
Electronic
expansion valve

Heat exchanger

Filter

Filter

Heat exchanger

Field piping
Filter

4-way valve

Field piping

Indoor unit
Low pressure
sensor

High pressure
switch

Heat exchanger

Branch duct
connection

Service port
5/16

Field piping J9.5

Compressor

Option
Field piping J15.9

Accumulator

Outdoor unit

Field piping

Filter

Indoor unit

Heating
Cooling

Field piping

Stop valve
(with service port 5/16 flare)

Note: 1. The pipes between the branch and the indoor units should have the same size as
the indoor connections.

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

Split Sky Air Outdoor Units

3TW29165-2

22

Outdoor Units R-410A RZQS-DV1

Piping diagram

RZQS100,125,140DV1 (Triple)
Indoor unit
Heat exchanger

Electronic
expansion valve

Stop valve
(with service port 5/16 flare)

Heat exchanger
Filter

Filter

Field piping

Filter

Field piping

Indoor unit
Heat exchanger

4-way valve

Low pressure High pressure


switch
sensor

Field piping J9.5

Field piping
Field piping

Filter

Field piping J15.9


Indoor unit
Heat exchanger

Service port
5/16

Compressor

Branch duct
connection
Option

Accumulator

Note: 1. The pipes between the branch and the indoor units
should have the same size as the indoor connections.
Heating
Cooling

Field piping

Filter

Outdoor unit

Field piping

3TW29165-3

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

RZQS125-140DV1 (Double twin)


Heat exchanger

Indoor unit

Electronic
expansion
valve
Field piping

Filter

Filter

Field piping

Heat exchanger

Indoor unit

4-way valve

Field piping

Low pressure High pressure


sensor
switch

Field piping

Heat
exchanger

Indoor unit

Heat exchanger

Field piping
J9.5
Field piping
J15.9

Filter

Filter

Branch duct
connection
Option

Field piping J9.5

Service
port
5/16

Compressor
Field piping J15.9

Accumulator
Field piping

Filter

Outdoor unit

Field piping

Heat exchanger

Stop valve
(with service port 5/16 flare)

Heating
Cooling

Field piping
J9.5
Field piping
J15.9
Field piping

Filter

Note: 1. The pipes between the branch and the indoor


units should have the same size as the indoor connections.

Field piping

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

23

Split Sky Air Outdoor Units

3TW29165-4

Outdoor Units R-410A RZQS-DV1

Wiring diagram

8-1

Wiring diagram

RZQS71DV1

Indoor

Outdoor
ON
OFF

(Note 4)

El. comp. Assy


Position of elements

: Printed circuit board (Main)


: Printed circuit board (Inverter)
: Push button switch
: Capacitor
: Dip switch
: Fuse (T 6.3A / 250V)
: Fuse (T 3.15A / 250V)
: Light emitting diode (service monitor orange)
: Light emitting diode (service monitor green)
: Magnetic relay (Y1S)
: Magnetic relay
: Magnetic relay
: Reactor
: Motor (compressor)
: Motor (fan)
: Switching power supply
: Field earth leakage breaker (30mA)
: Resistor
: Resistor
: Thermistor (air)
: Thermistor (discharge)
: Thermistor (Suction)
: Thermistor (Heat exchanger)
: Thermistor (Thermistor (heat exchanger middle))
: Thermistor (liquid)
: Thermistor (fin)
: Signal receiver circuit
: Pressure sensor
: Pressure switch (High)
: Signal transmission circuit
: Power module
: Diode module
: IGBT
: Terminal strip (Power supply)
: Electronic expansion valve
: Solenoid valve (4 way valve)
: Noise filter (ferrite core)
: Noise filter

1
8

Notes:
1. This wiring diagram only applies to the outdoor unit
: Field wiring
2. L: Live, N: Neutral,
: Terminal strip
: Connector
: Connection
3.
: Protective earth (screw)
: Relay connector
: Noiseless earth
: Terminal
4. Refer to the option manual, for connecting wiring to x6A.
5. Refer to the Wiring diagram sticker (on back of front plate) on how to use BS1 BS4
and DS1 switch.
6. Do not operate the unit by short-circuiting protection device S1PH
7. Colours: WHT: White / RED: Red / BLU: Blue / ORG: Orange
BRN: Brown / GRN: Green / YLW: Yellow
8. Confirm the method of setting the selector switches (DS1) by service manual.
Factory setting of all switches: OFF.

Position of
compressor
terminal

(Back)

A1P
A2P
BS1BS4
C1C3
DS1
F1U
F6U
H1P7P (A2P)
HAP (A1P)
K1R
K10R
K11R
L1R
M1C
M1F
PS
Q1DI
R1
R2
R1T
R2T
R3T
R4T
R5T
R6T
R10T
RC
S1NPH
S1PH
TC
V1R
V2R,V3R
V1T
X1M
Y1E
Y1S
Z1C
Z1FZ4F

(Front)

2TW30466-1B
RZQS100-140DV1

Indoor

Outdoor
ON
OFF

(Note 4)

El. comp. Assy


Position of elements
Position of
compressor
terminal
Wire entrance
(Back)

(Front)

A1P
A2P
A3P
A4P
BS1BS4
C1C4
DS1
E1HC
F1U, F3U, F4U
F6U
H1P7P (A2P)
HAP (A1P)
K1R
K4R
K10R
K11R
L1R
M1C
M1F
M2F
PS
Q1DI
R1
R2
R1T
R2T
R3T
R4T
R5T
R6T
R10T
RC
S1NPH
S1PH
TC
V1R
V2R,V3R
V1T
X1M
Y1E
Y1S
Z1C
Z1FZ4F

: Printed circuit board (Main)


: Printed circuit board (Inverter)
: Printed circuit board (Noise filter)
: Printed circuit board
: Push button switch
: Capacitor
: Dip switch
: Crankcase heater
: Fuse (T 6.3A / 250V)
: Fuse (T 5,0A / 250V)
: Light emitting diode (service monitor orange)
(H2P) Prepare, Test --------- Flickering
Malfunction Detection -- Light up
: Light emitting diode (service monitor green)
: Magnetic relay (Y1S)
: Magnetic relay (E1HC)
: Magnetic relay
: Magnetic relay
: Reactor
: Motor (compressor)
: Motor (fan) (upper)
: Motor (fan) (lower)
: Switching power supply
: Field earth leakage breaker (30mA)
: Resistor
: Resistor
: Thermistor (air)
: Thermistor (discharge)
: Thermistor (Suction)
: Thermistor (Heat exchanger)
: Thermistor (Thermistor (heat exchanger middle))
: Thermistor (liquid)
: Thermistor (fin)
: Signal receiver circuit
: Pressure sensor
: Pressure switch (High)
: Signal transmission circuit
: Power module
: Diode module
: IGBT
: Terminal strip (Power supply)
: Electronic expansion valve
: Solenoid valve (4 way valve)
: Noise filter (ferrite core)
: Noise filter

Notes:
1. This wiring diagram only applies to the outdoor unit
: Field wiring
2. L: Live, N: Neutral,
: Terminal strip
: Connector
: Connection
3.
: Protective earth (screw)
: Relay connector
: Noiseless earth
: Terminal
4. Refer to the option manual, for connecting wiring to x6A.
5. Refer to the Wiring diagram sticker (on back of front plate) on how to use BS1 BS4
and DS1 switch.
6. Do not operate the unit by short-circuiting protection device S1PH
7. Colours: WHT: White / RED: Red / BLU: Blue / ORG: Orange
BRN: Brown / GRN: Green / YLW: Yellow
8. Confirm the method of setting the selector switches (DS1) by service manual.
Factory setting of all switches: OFF.

2TW29166-2

Split Sky Air Outdoor Units

24

Outdoor Units R-410A RZQS-DV1

Sound data

9-1

Sound pressure spectrum

RZQS71DV1 - Cooling
Sound pressure level (dB)

Sound pressure level (dB)

RZQS71DV1 - Heating

3TW30467-2

3TW30467-1

Octave band center frequency (Hz)

Octave band center frequency (Hz)

NOTES
1
2
3
4

Data is valid at free field condition


Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale according to
IEC)
Reference acoustic pressure 0dB = 20Pa

NOTES
1
2
3
Measuring location
(discharge side)

RZQS100DV1 - Cooling

Data is valid at free field condition


Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale according to
IEC)
Reference acoustic pressure 0dB = 20Pa

Sound pressure level (dB)

Sound pressure level (dB)

RZQS100DV1 - Heating

3TW31727-2

3TW31727-1

Octave band center frequency (Hz)

Octave band center frequency (Hz)

NOTES
1
2
3
4

25

Measuring location
(discharge side)

NOTES

Data is valid at free field condition


Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale according to
IEC)
Reference acoustic pressure 0dB = 20Pa

1
2
3
Measuring location
(discharge side)

Split Sky Air Outdoor Units

Data is valid at free field condition


Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale according to
IEC)
Reference acoustic pressure 0dB = 20Pa

Measuring location
(discharge side)

Outdoor Units R-410A RZQS-DV1

Sound data

9-1

Sound pressure spectrum

RZQS125DV1 - Cooling

Sound pressure level (dB)

Sound pressure level (dB)

RZQS125DV1 - Heating

1
9

3TW29167-2

3TW29167-1

Octave band center frequency (Hz)

Octave band center frequency (Hz)

NOTES
1
2
3
4

Data is valid at free field condition


Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale according to
IEC)
Reference acoustic pressure 0dB = 20Pa

NOTES
1
2
3
Measuring location
(discharge side)

RZQS140DV1 - Cooling

Data is valid at free field condition


Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale according to
IEC)
Reference acoustic pressure 0dB = 20Pa

Measuring location
(discharge side)

Sound pressure level (dB)

Sound pressure level (dB)

RZQS140DV1 - Heating

3TW29177-2

3TW29177-1

Octave band center frequency (Hz)

Octave band center frequency (Hz)

NOTES
1
2
3
4

Data is valid at free field condition


Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale according to
IEC)
Reference acoustic pressure 0dB = 20Pa

NOTES
1
2
3
Measuring location
(discharge side)

Split Sky Air Outdoor Units

Data is valid at free field condition


Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale according to
IEC)
Reference acoustic pressure 0dB = 20Pa

Measuring location
(discharge side)

26

Outdoor Units R-410A RZQS-DV1

Sound data

9-2

Sound power spectrum

Sound power level (dB)

RZQS100DV1

Sound power level (dB)

RZQS71DV1

3TW30467-3

3TW0477-3

Octave band center frequency (Hz)

NOTES

NOTES

dB(A) = A-weighted sound pressure level (A-scale according to IEC)


Reference acoustic intensity 0dB = 10E-6W/m2
Measured according to ISO 3744

1
2
3

dB(A) = A-weighted sound pressure level (A-scale according to IEC)


Reference acoustic intensity 0dB = 10E-6W/m2
Measured according to ISO 3744

1
2
3

Sound power level (dB)

RZQS140DV1

Sound power level (dB)

RZQS125DV1

3TW29167-3

Octave band center frequency (Hz)

3TW29177-3

NOTES
1
2
3

27

Octave band center frequency (Hz)

Octave band center frequency (Hz)

NOTES

dB(A) = A-weighted sound pressure level (A-scale according to IEC)


Reference acoustic intensity 0dB = 10E-6W/m2
Measured according to ISO 3744

Split Sky Air Outdoor Units

1
2
3

dB(A) = A-weighted sound pressure level (A-scale according to IEC)


Reference acoustic intensity 0dB = 10E-6W/m2
Measured according to ISO 3744

Outdoor Units R-410A RZQS-DV1

10

Installation

10 - 1 Installation method

RZQS71-140DV1
A. Non stacked installation

Legend
Suction side obstacle

Discharge side obstacle

10

Left side obstacle


Right side obstacle
Top side obstacle
Obstacle is present
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.

In these cases, only 2 units can be


installed.

This situation is not allowed.


Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.

B. Stacked installation
1. Obstacles exist in front of the outlet side

2. Obstacles exist in front of the air inlet

Do not stack more than one unit.


About 100mm is required as the dimension for laying the upper outdoor units drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.

C. Multiple-row installation
1. Installation of one unit per row

2. Installing multiple units (2 units or more) in lateral


connection per row

Relation of dimensions of H, A, and L are shown in the


table below.
LH
H<L

L
0 < L 1/2 H
1/2 H < L
Installation impossible

A
150 (250)
200 (300)

3TW26739-4

Split Sky Air Outdoor Units

28

Outdoor Units R-410A RZQS-DV1

11

Operation range

RZQS71-140DV1
(Cooling)

Indoor temp. (CWB)

Operation range

Allowable range of
operation (warming-up)

(Heating)

Outdoor temp. (CWB)

Allowable range of operation (pull-down)

Operation range

Outdoor temp. (CDB)

11

Indoor temp. (CDB)

NOTE
1
2

Depending on operation and istallation conditions. The indoor unit can change over to freeze-up operation (indoor de-icing)
To reduce the freeze-up operation (indoor de-icing) frequency it is recommended to install the outdoor unit in a location not exposed to wind.

3TW29063-1D

29

Split Sky Air Outdoor Units