Вы находитесь на странице: 1из 7

CURRENT TRANSFORMER REQUIREMENTS FOR VA TECH REYROLLE RELAYS

1 Argus 1 to 6 (Numeric); 2TJM10 (Electro- The internal burden of the c.t. (eg. Its secondary
mechanical): I.D.M.T.L., Definite Time and resistance) must be taken into account if a true
Instantaneous Overcurrent and Earth Fault equivalent overcurrent factor is to be established
Protection for a lower burden of the load.

A protection class c.t. must be used, eg in Typically, c.t. requirements vary dependent on
accordance with IEC 185 or BS3938. the project specific requirements. The following
considerations must be made.
Typically the c.t. is specified by means of an
accuracy factor and an overcurrent factor up to A) C.T. Rating – should be chosen at least equal to
which the c.t. remains accurate with the maximum the maximum continuous load current of the
specified burden connected to its secondary, eg: circuit. This includes any emergency rating, eg.
of a power transformer where typically one
5P10 : 5VA hour) one hour or two hour overload ratings are
often provided.

B) Accuracy Factor – Typically standard values of


Accuracy Overcurrent Maximum burden 5% or 10% are employed. 5% where current
Limit Factor (at c.t. secondary level) grading requirement are onerous eg. where the
circuits being graded have similar ratings and
there are several stages of grading. In these
The accuracy limit is in percent, and although circumstances an accuracy of 5% assists in
termed a composite error (which takes account of allowing small grading steps. Accuracy levels of
polarity error and magnitude error) is effectively 10% are acceptable where large grading steps
the maximum ratio error. The c.t. is more can be tolerated and only a small number of
accurate at current values up to full load. Beyond grading steps are required.
full load, up to the overcurrent factor, the error will
not exceed the specified value. C) Overcurrent Factor – The factor should be
chosen to ensure:-
The overcurrent factor is a multiple of the c.t.
rating up to which the c.t. remains within the i I.d.m.t.l. relay performance is not
accuracy limit. undermined by the c.t’s inability to transform
all the current into the secondary circuit.
Thus in the example of a 5P10, 5VA c.t., this will
transform primary current within the accuracy limit ii That any a.c. saturation due to a very large
of 5% when a burden of 5VA (at rated current) is primary current is not so sever as to result in
connected to the c.t. secondary, for a primary insufficient energy in the secondary
current up to 10x its rating. waveform to prevent the relay from
operating.
If the load burden is less than the rated burden a
higher overcurrent factor can be tolerated, Provided the above criterion are met it is not
although not necessarily exactly in inverse necessary to select an overcurrent factor
proportion, i.e. half the burden, twice the which ensures the maximum fault current
overcurrent factor does not necessarily apply. can be accurately transformed.
d) Burden – this is the load burden in VA, at the rated The accuracy and overcurrent factors are therefore
c.t. secondary current, of all equipment connected already fixed and for both these factors the earth fault
to the c.t. secondary, including all pilot burden. protection requirements are normally less onerous than
Pilot burden can be significant, particularly for 5 for overcurrent.
amp rated c.t’s. Most modern protection relays
(static or numeric) represent a fixed burden no A major consideration for an electro-mechanical relay is
matter what the setting. However, for electro- its burden at relay setting. Employing a low earth fault
mechanical relays, the burden may be dependent setting usually results in a high burden. In these
on the setting of the relay. circumstances the rated burden of the c.t. must be
chosen on the basis of the requirements of the earth
Examples of typical applications are as follows. fault element.

• I.D.M.T.L. Overcurrent 2. Duobias 4C21 (Electro-Mechanical):


Transformer Differential Protection
a) For industrial systems with relatively low fault
current and no onerous grading requirements – a All CT’s should be of the low reactance type and the
class 10P10 with rated burden to suit the load. knee point voltage (Vk) should be equal to, or exceed
twice the maximum steady state working voltage under
b) For utility distribution networks with relatively high any through fault condition. To assess the steady state
fault current and several grading stages - a class working voltage the impedance’s of the Duobias relays
5P20, with rated burden to suit the load. are ignored and only the c.t. winding and
interconnecting lead resistance’s considered.
Note: Where the maximum fault level is considerably
higher than the overcurrent factor and therefore the c.t. As a general guide the knee point voltage Vk should
secondary current could be significantly lower than equal or exceed:-
that equivalent to the primary current (due to a.c.
saturation), it is necessary to consider any effect on For Star connected CT’s - Vk equal or greater than
the protection system performance, eg. grading 2I(A+C)
margins. For Delta connected CT’s -Vk equal or greater than
2I(B+3D)
For i.d.m.t.l. applications, because the operating time Where:
at high fault current is approaching a definite minimum I = Maximum through fault current referred to the
value, partial saturation of the c.t. at values beyond the secondary winding of the star connected c.t’s
overcurrent factor has only a limited effect. However, with a three phase system fault.
this must be taken into account in establishing the A = Secondary winding resistance of each of the star
appropriate setting to ensure proper grading. connected c.t’s.
B = Secondary winding resistance of each delta
• Definite Time and Instantaneous Overcurrent connected c.t.
C = Resistance of each lead between the star
a) For industrial systems with requirements as for connected c.t. terminals and the relay terminals.
i.d.m.t.l. relays item (a) above, a class 10P 10. D = Resistance of each lead between the delta
b) For utilites as for (b) above – a class 5P 10. connected terminals and the relay terminals.

Note: Overcurrent factors do not need to be high for Class ‘X’ current transformers to BS 3938 (or class TPS
definite time protection because once the setting is to IEC 44-6) can be specified to meet the above
exceeded accuracy is not important. Often, however requirements and this type are recommended.
there is also the need to consider instantaneous
overcurrent protection as part of the same protection 3. B3/5B3 (Electro-mechanical);DAD (Static): High
system and the settings would normally be of the order Impedance Differential and Restricted Earth
of 10x the c.t. rating or higher. If they are higher than Fault Circulating Current Protection
10x then the overcurrent factor must be raised
accordingly, eg. to P20. The basic requirements are:
1 .All the current transformers should have identical
• Earth Fault Protection turns ratios.

Considerations and requirements for earth fault


protection are the same as for overcurrent. Usually
the relay employs the same c.t’s eg. three phase
mounted c.t’s connected in residual to establish the
earth fault current.
2 The Knee point voltage of the current 5. Solkor R/Rf (Electro-mechanical): Pilot Wire,
transformers should be at least twice the relay Feeder Current Differential Protection
setting voltage. The knee point voltage is
expressed as the voltage at fundamental The minimum knee point voltage of the line current
frequency applied to the secondary circuit of the transformers is given by:
current transformer which when increased in
magnitude by 10% causes the magnetising Vk = 50 + If (Rct + 2Rl)
current to increase by 50%. In N

3 The current transformers should be of the low Where


leakage reactance type. Generally most modern In = Rated current of relay, amps
current transformers are of this type and there If = Primary current under maximum steady state
should be no difficulty in meeting this through fault conditions
requirement. Low leakage reactance current N = Current transformer ratio
transformers have a jointless core with the Rct = Secondary resistance of the current transformer
secondary winding evenly distributed along the in ohms
whole length of the magnetic circuit, and the Rl = Cable/wiring resistance between the current
primary conductor passes through the centre of transformers and the relay summation
the core. transformer, for each single wire (route length),
in ohms
Class ‘X’ current transformers to BS 3938 (or class
TPS to IEC 44-6) can be specified to meet the above Generally it is not recommended that any other
requirements and this type are recommended. equipment burdens should be included in the current
transformer circuit in order to avoid any possible mal-
4. Duobias M (Numeric): Transformer operation due to through faults. However, in some
Differential and Restricted Earth Fault instances the protection design often requires the
inclusion of starting relays for the Solkor protection and
For high speed operation under all fault conditions occasionally the addition of i.d.m.t.l. protection to the
the minimum current transformer knee point voltage same c.t’s for backup protection. In such cases the extra
should equal or exceed: Vk = 4I(A+C). burden should be carefully established and included in
the calculation. The additional burden on each phase
Where: should be reasonably balanced.
I = Either the maximum three phase through fault
current (as limited by the transformer The secondary magnetising currents of the current
impedance) or the high-set setting, whichever transformer at opposite ends of the feeder should not
is greater differ by more than In/20 amperes for output voltage up to
A = The secondary winding resistance of each 50/In volts.
star connected c.t.
C = The c.t. secondary loop lead resistance for To ensure good balance of the protection the current
internal earth faults transformers at the two ends should have equal ratios.
Close balance of ratio is provided by current transformers
For restricted earth fault protection it is to IEC44-6, Class TPS (BS3938, Class X), where ratio
recommended that all c.t’s should have an equal error is limited to ±0.25% and these are recommended.
number of secondary turns. Line c.t’s are normally
star connected and standard ratios can be selected 6 Solkor-M (Numeric): Feeder Current Differential
according to the transformer rating, ratios need not Protection
be exact provided they are within the range of the
Duobias-M relay current setting ranges and do not The current transformers at the two ends should have
cause the c.t. or relay thermal ratings to be similar design parameters and performance
exceeded. characteristics. In addition the secondary burden of the
two current transformers should be kept similar. This will
Ideally the line c.t. ratios should be selected to allow then allow a low value of stability factor to be used, hence
Duobias-M relay settings for c.t. ratio correction reducing the knee point voltage requirements of the
factors to be employed in order to balance the current transformers.
secondary current to normal relay current. This
allows maximum sensitivity to be achieved for The minimum knee point voltage for the line current
internal faults. transformer is given by:

Class ‘X’ current transformers to BS 3938 (or class Vk = k x X/R x If/N x (Rct + 2Rl + Rb)
TPS to IEC 44-6) can be specified to meet the above
requirements and this type are recommended.
where: Rl = Lead resistance between the current
k = stability transformers and the relay (ohms)
X/R = the X/R ratio for the maximum through Rb = Burden of relay (ohms)
fault conditions. The value of this
transient factor depends upon the sum It is not recommended that any other burdens should be
of the source and transmission circuit included in the current transformer circuit, but where this
impedance’s. cannot be avoided the additional burden should be
If = primary current under maximum added to those listed when determining the current
through fault conditions (amps) transformer output voltage required. In addition to the
N = current transformer ratio above, the secondary magnetising currents of the
Rct = secondary resistance of the current current transformers at opposite ends of the feeder
transformer (ohms) should not differ by more than In/20 amperes for output
Re = lead resistance between the current voltages up to 50/In volts.
transformers and the relay ohms)
Rb = burden of relay (ohms)The ac burden To ensure good balance of the protection the current
of the relay per phase is transformers at the two ends should have equal ratios.
0.05V at 1A for 1A tap = 0.05 ohm Close balance of ratios is provided by current
0.3VA at 5A for %a tap = 0.012 ohm transformers to IEC44-6, Class TPS, ratio error limited
to ±0.25%, and these are recommended.
It is not recommended that any other burden should
be included in the current transformer circuit, but • Relay AC Burden per phase
where this cannot be avoided the additional burden 0.05VA at 1A for 1A tap = 0.05 ohm
should be added to those listed when determining the 0.3VA at 5A for %a tap = 0.012 ohm
current transformer output voltage required.
• Stability
In addition to the above, the secondary magnetising Under through fault conditions the relay will be
currents of the current transformers at opposite ends stable with fault current equivalent to 50 times the
of the feeder should not differ by more than In/20A for normal current rating in use.
output voltages up to 50/InV.
8 THR (Static): Distance (Impedance) Protection
For example, consider a 33kV feeder with a worst for Transmission Circuits
case through fault of 8kA with a X/R of 10. The
minimum current transformer knee point required, For high speed operation and accurate impedance
given a turns ratio of 1/400, secondary CT resistance measurement the c.t’s should be Class TPS to IEC44-6
of 2Ω, and lead burden of 1Ω, is :- (Class X to BS3938) and have a knee point voltage (Vk)
equal to or greater than the following:-
Vk ≥ 0.3 x 10 x 8000/400 x (2 + 2x1 + 0.03)
Vk ≥ If [R1 + R2 + X (R3 + R2)]
Vk ≥ 242volts R
Where:
7 Microphase-FM (Numeric): Current If = Secondary fault current for fault at end of Zone
Differential Telephase Protection 1
R1 = Resistive burden of THR relay (See table
The minimum knee point voltage for the line current below)
transformers is given by: R2 = Resistance of connecting loads plus resistance
of the C.T. secondary winding
Vk = k x X x If x (Rct + 2Rl + Rb) X = Ratio of reactance to resistance of the system
R N for R a fault at the end of Zone 1
R3 = Constant depending on impedance setting of
Where: Zone 1
k = Stability factor = 0.8
X/R = The X/R ratio for the maximum through To calculate values of R1 and R3 for 2A or 5A relays,
fault condition. The value of this divide values in the following table by 4 and 25
transient factor depends upon the sum respectively.
of the source and transmission circuit
impedance’s.
If = Primary current under maximum steady
state through fault conditions (amps).
N = Current transformer ratio
Rct = Secondary resistance of the current
transformer (ohms)
Relay Setting R1 R3 For satisfactory operation of all functions except the
nominal of Earth Phase
low impedance biased differential function, the use of
rating Zone 1 a class 5P20 to IEC60185, or any equivalent, would be
Fault Fault satisfactory for any application since the fault levels
(A)
never exceed 20 x the c.t. rating. The VA rating is
1 0.8 to 4 0.3 0.3 0.2 chosen to allow for all the circuit burden (eg. c.t.
4 to 8 0.4 0.4 0.3 secondary cabling and relay burden).
8 to 16 0.8 0.6 0.5
16 to 24 1.5 0.9 0.5 For stability of the low impedance biased differential
24 to 48 3.8 1.2 0.9 function it may be necessary to provide a design which
ensures neither of the two 3-phase sets of c.t’s are
9 Ohmega (Numeric): Distance (Impedance) overfluxed in the event of re-occurring high magnitude
Protection for Transmission Circuits faults with high X/R ratio source impedance. In these
circumstances, where high levels of d.c. component
For high speed operation and accurate impedance current, long time constants and a long operating time
measurement the c.t’s should be Class TPS to IEC44- for the network protection may occur, the c.t’s can be
6 (Class X to BS3928) and have a knee point voltage left with a high level of remnant flux. Any subsequent
(Vk) equal or greater than the higher of the following faults may then cause one of the c.t’s to fully saturate
two expressions: and the differential function mal-operate.

1) Vk ≥ K • Ip (1+ Xp) (0.03 + Rct + Rl) If this is possible, e.g. for a directly connected
N Rp generator (no generator transformer), where the two
For phase-phase faults sets of c.t’s may be supplied by different
manufacturers, where there is a multi-shot delayed
2) Vk ≥ K • Ie (1+ Xe) (0.06 + Rct + Rl) auto-reclose scheme on feeders local to the grid
N Re connection, and the differential setting chosen is very
For phase-earth faults sensitive, it is recommended that any low reactance
c.t’s (ie with high remanance factor) should have knee
Where: point voltages compliant with the following formula:-
Ip =Phase fault current calculated for Xp/Rp
ratio at the end of zone 1 Vk = 50ln (RCT + 2RL + RR) where maximum through
le =earth fault current calculated for Xe/ Re fault current = 10 x ln with maximum X/R = 120.
ratio at the end of zone 1 Minimum Vk to be 60 Volts.
N =C.T. ratio
Xp/Rp =power system reactance to resistance ratio Vk = 30ln (RCT + 2RL + RR) where maximum through
for the total plant including the feeder line fault current = 10 x ln with maximum X/R = 60.
parameters calculated for a phase fault at Minimum Vk to be 60 Volts.
the end of zone 1
Xe/Re =similar ratio to above but calculated for an Where:
earth fault at the end of zone 1 Vk = Knee point voltage
Rct =C.T. internal resistance ln = Rated current
RI =lead burden, C.T. to Ohmega terminals X/R = The X/R ratio for the maximum through fault
K =Factor chosen to ensure adequate condition.
operating speed and is <1. K is usually 0.5 RCT = Secondary resistance of the current
for distribution systems, a higher value is transformer (ohms)
chosen for primary transmission systems. RL = Lead resistance between the current
Reyrolle Protection should be consulted. transformers and the relay (ohms)
RR = Resistance of any other protection functions
Both Vk values should be calculated and the higher sharing the current transformer (ohms)
value chosen for the c.t. to be used.
Where all the onerous conditions described above are
10 GAMMA (Numeric): Generator Protection not required to be met and the c.t. accommodation
facility is limited, the requirements can be reduced, in
a) Two off 3 phase Inputs (Line end and Neutral these circumstances contact VA Tech Reyrolle -
End): Protection for advice.

The current transformer minimum requirements b) Neutral Earth C.T. Inputs:


depend on the protection application, the functions
employed and the primary circuit configuration. For solid earthed (eg. direct connected
generator), use the same as (a) above
For impedance earthed neutral, a lower specification The RHO c.t. input circuit burden is fixed and is no
can be employed eg 5P5. greater than 0.25VA, eg 0.01 ohm at 5 amp and the rated
burden is therefore established by selecting a value in
Use of C.T’s Common to More Than One Relay excess of the c.t. secondary circuit loading eg. for phase
inputs:-
Generally the c.t’s employed for generator protection
should be dedicated to that one duty, for security of Rated VA ≥ (In)² (2Rl + Rb + R1)
the protection.
Where:
Technically however there is no reason why other In = Rated secondary current
equipment may not share the same c.t’s, except that Rl = Secondary lead burdens per phase (ohm)
the additional burden should be taken into account Rb = Relay circuit burden ≤ 0.015 ohm for 5 amp
and also that the c.t’s for the three phase inputs ≤ 11 ohm for 25 Ma
should have a reasonably balanced burden on each R1 = Other equipment burden (ohm) per phase
phase. This ensures no possibility of mal-operation
of the differential function. For earth fault detection RHO 0 has a separate input
which can be employed either from a residual connection
For the requirement of redundancy, there is no of the phase inputs or a separate core balance c.t. (the
problem with the performance of either relay when preferred option). The relay is set to the selected mode
connecting two Gamma relays in series. However, eg. Residual Connection or CBCT. In residual
we recommend that the redundancy philosophy be connection the trip setting and primary c.t. rating setting
extended to include the c.t’s, ie. use separate c.t. establish the pick-up level.
secondaries.
In CBCT mode the setting range is 30mA to 3000mA,
Use of duplicate Gamma relays, particularly on high and the CBCT ratio is chosen with this in mind to
rated generator units (eg over 15 MW) provides a establish a required primary trip current. The actual
high level of security and integrity which is still cost current input range at the relay terminals is 0.06 to 6.0
effective. MA.

11 RHO (Numeric): Motor Protection and The class and rating are selected as per the phase input
Electrical Plant Thermal Overload c.t’s. The rated burden is establish from:-

11.1 RHO for low voltage 3 phase A.C. motors VA ≤ (In)² (2Rl + R1 ) [References as before]
For the earth fault c.t. input Rb ≤ 300 ohm
The RHO 0 relay is compatible with CT’s having
either 25mA or 5A secondaries.
If the residual connection mode is employed the e.f. c.t.
input burden should be added to the phase c.t. burden
25mA rated output c.t’s are recommended for motor
since this is a significant value. For this form of
currents up to 100A and 5A up to 3000A
connection a stabilising resistor may be required in the
earth fault c.t. input, e.g. if the setting is instantaneous.
For 5 amp relay input rating some motor control
This resistance must be included in the value for R1.
systems result in high multiples of rated current
However residual connection is not recommended.
flowing during the start up period, and for some
motors the run-up time may be very long (eg 60
11.2 RHO 3 for high voltage 3 phase A.C. motors
seconds). Because of this there are some limitations
and electrical plant
on the motor rating that can be utilised with a
particular c.t. rating due to the thermal capacity of the
Thermal Overload
relay c.t. input terminals. If the motor rating is limited
to less than 75% of the c.t. rating there is unlikely to
The c.t. class recommended is 5P10. This provides
be any problem with overheating no matter how
accurate measurement (maximum error of 5%) for
onerous the starting current, starting time or number
overloads and also for high current magnitudes beyond
of starts in a period of time for practical
typical motor stall current (eg. 6 x full load current).
considerations.
The rated burden is established by selecting a value in
The c.t. classification should be 10P10 or better (eg.
excess of the c.t. secondary circuit loading, eg:-
5P10 for improved accuracy) and have a rating to suit
the c.t. secondary total burdens, ie. C.t. leads, RHO
Rated VA ≥ (In)² (2Rl+ Rb + R1)
0 relay and any equipment connected in series with
the relay.
Where:
In = Rated secondary current
Rl = Secondary lead burdens per phase
Rb = Relay circuit burden (See table
below)
R1 = Other equipment burden per phase

RHO 3 C.T. Input Burdens

AC Impedance
Burden
5A Phase £ 0.2VA £ 0.01 W
1A Phase £ 0.05VA £ 0.05 W
5A Earth £ 0.4VA £ 0.02 W
1A Earth £ 0.2VA £ 0.2 W

For earth fault detection RHO3 has a separate input


which can be employed either from a residual
connection of the phase inputs or a separate core
balance c.t. (the preferred option). There is no
selection made within the relay, the primary current
setting is a function only of the relay current setting
and the c.t. ratio.

If a residual connection is employed and the earth


fault setting chosen is both sensitive (e.g. less than
0.5In) and instantaneous, it is recommended that a
stabilising resistor be employed in the earth fault
input circuit. This must then be taken into account in
establishing R1.

For residual connection arrangement, Rb will be a


summation of the phase fault and earth fault input
burdens.

12 PHI (Numeric): Point-on-Wave Circuit


Breaker Controller

The current transformer inputs do not need to be


employed for the point-on-wave function and can be
left unconnected. If connected to the c.t’s the PHI
unit enables the current profile to be monitored for
continuous load and switching conditions. The class
of c.t. is not important and either instrument or
protection class c.t’s can be employed, eg any c.t’s
already employed for another function. Dedicated
ct’s are not necessary. It is only necessary to
ensure the additional small burden of the PHI relay
is included in the requirements of the c.t’s being
employed.

Вам также может понравиться