Академический Документы
Профессиональный Документы
Культура Документы
1 Argus 1 to 6 (Numeric); 2TJM10 (Electro- The internal burden of the c.t. (eg. Its secondary
mechanical): I.D.M.T.L., Definite Time and resistance) must be taken into account if a true
Instantaneous Overcurrent and Earth Fault equivalent overcurrent factor is to be established
Protection for a lower burden of the load.
A protection class c.t. must be used, eg in Typically, c.t. requirements vary dependent on
accordance with IEC 185 or BS3938. the project specific requirements. The following
considerations must be made.
Typically the c.t. is specified by means of an
accuracy factor and an overcurrent factor up to A) C.T. Rating – should be chosen at least equal to
which the c.t. remains accurate with the maximum the maximum continuous load current of the
specified burden connected to its secondary, eg: circuit. This includes any emergency rating, eg.
of a power transformer where typically one
5P10 : 5VA hour) one hour or two hour overload ratings are
often provided.
Note: Overcurrent factors do not need to be high for Class ‘X’ current transformers to BS 3938 (or class TPS
definite time protection because once the setting is to IEC 44-6) can be specified to meet the above
exceeded accuracy is not important. Often, however requirements and this type are recommended.
there is also the need to consider instantaneous
overcurrent protection as part of the same protection 3. B3/5B3 (Electro-mechanical);DAD (Static): High
system and the settings would normally be of the order Impedance Differential and Restricted Earth
of 10x the c.t. rating or higher. If they are higher than Fault Circulating Current Protection
10x then the overcurrent factor must be raised
accordingly, eg. to P20. The basic requirements are:
1 .All the current transformers should have identical
• Earth Fault Protection turns ratios.
Class ‘X’ current transformers to BS 3938 (or class Vk = k x X/R x If/N x (Rct + 2Rl + Rb)
TPS to IEC 44-6) can be specified to meet the above
requirements and this type are recommended.
where: Rl = Lead resistance between the current
k = stability transformers and the relay (ohms)
X/R = the X/R ratio for the maximum through Rb = Burden of relay (ohms)
fault conditions. The value of this
transient factor depends upon the sum It is not recommended that any other burdens should be
of the source and transmission circuit included in the current transformer circuit, but where this
impedance’s. cannot be avoided the additional burden should be
If = primary current under maximum added to those listed when determining the current
through fault conditions (amps) transformer output voltage required. In addition to the
N = current transformer ratio above, the secondary magnetising currents of the
Rct = secondary resistance of the current current transformers at opposite ends of the feeder
transformer (ohms) should not differ by more than In/20 amperes for output
Re = lead resistance between the current voltages up to 50/In volts.
transformers and the relay ohms)
Rb = burden of relay (ohms)The ac burden To ensure good balance of the protection the current
of the relay per phase is transformers at the two ends should have equal ratios.
0.05V at 1A for 1A tap = 0.05 ohm Close balance of ratios is provided by current
0.3VA at 5A for %a tap = 0.012 ohm transformers to IEC44-6, Class TPS, ratio error limited
to ±0.25%, and these are recommended.
It is not recommended that any other burden should
be included in the current transformer circuit, but • Relay AC Burden per phase
where this cannot be avoided the additional burden 0.05VA at 1A for 1A tap = 0.05 ohm
should be added to those listed when determining the 0.3VA at 5A for %a tap = 0.012 ohm
current transformer output voltage required.
• Stability
In addition to the above, the secondary magnetising Under through fault conditions the relay will be
currents of the current transformers at opposite ends stable with fault current equivalent to 50 times the
of the feeder should not differ by more than In/20A for normal current rating in use.
output voltages up to 50/InV.
8 THR (Static): Distance (Impedance) Protection
For example, consider a 33kV feeder with a worst for Transmission Circuits
case through fault of 8kA with a X/R of 10. The
minimum current transformer knee point required, For high speed operation and accurate impedance
given a turns ratio of 1/400, secondary CT resistance measurement the c.t’s should be Class TPS to IEC44-6
of 2Ω, and lead burden of 1Ω, is :- (Class X to BS3938) and have a knee point voltage (Vk)
equal to or greater than the following:-
Vk ≥ 0.3 x 10 x 8000/400 x (2 + 2x1 + 0.03)
Vk ≥ If [R1 + R2 + X (R3 + R2)]
Vk ≥ 242volts R
Where:
7 Microphase-FM (Numeric): Current If = Secondary fault current for fault at end of Zone
Differential Telephase Protection 1
R1 = Resistive burden of THR relay (See table
The minimum knee point voltage for the line current below)
transformers is given by: R2 = Resistance of connecting loads plus resistance
of the C.T. secondary winding
Vk = k x X x If x (Rct + 2Rl + Rb) X = Ratio of reactance to resistance of the system
R N for R a fault at the end of Zone 1
R3 = Constant depending on impedance setting of
Where: Zone 1
k = Stability factor = 0.8
X/R = The X/R ratio for the maximum through To calculate values of R1 and R3 for 2A or 5A relays,
fault condition. The value of this divide values in the following table by 4 and 25
transient factor depends upon the sum respectively.
of the source and transmission circuit
impedance’s.
If = Primary current under maximum steady
state through fault conditions (amps).
N = Current transformer ratio
Rct = Secondary resistance of the current
transformer (ohms)
Relay Setting R1 R3 For satisfactory operation of all functions except the
nominal of Earth Phase
low impedance biased differential function, the use of
rating Zone 1 a class 5P20 to IEC60185, or any equivalent, would be
Fault Fault satisfactory for any application since the fault levels
(A)
never exceed 20 x the c.t. rating. The VA rating is
1 0.8 to 4 0.3 0.3 0.2 chosen to allow for all the circuit burden (eg. c.t.
4 to 8 0.4 0.4 0.3 secondary cabling and relay burden).
8 to 16 0.8 0.6 0.5
16 to 24 1.5 0.9 0.5 For stability of the low impedance biased differential
24 to 48 3.8 1.2 0.9 function it may be necessary to provide a design which
ensures neither of the two 3-phase sets of c.t’s are
9 Ohmega (Numeric): Distance (Impedance) overfluxed in the event of re-occurring high magnitude
Protection for Transmission Circuits faults with high X/R ratio source impedance. In these
circumstances, where high levels of d.c. component
For high speed operation and accurate impedance current, long time constants and a long operating time
measurement the c.t’s should be Class TPS to IEC44- for the network protection may occur, the c.t’s can be
6 (Class X to BS3928) and have a knee point voltage left with a high level of remnant flux. Any subsequent
(Vk) equal or greater than the higher of the following faults may then cause one of the c.t’s to fully saturate
two expressions: and the differential function mal-operate.
1) Vk ≥ K • Ip (1+ Xp) (0.03 + Rct + Rl) If this is possible, e.g. for a directly connected
N Rp generator (no generator transformer), where the two
For phase-phase faults sets of c.t’s may be supplied by different
manufacturers, where there is a multi-shot delayed
2) Vk ≥ K • Ie (1+ Xe) (0.06 + Rct + Rl) auto-reclose scheme on feeders local to the grid
N Re connection, and the differential setting chosen is very
For phase-earth faults sensitive, it is recommended that any low reactance
c.t’s (ie with high remanance factor) should have knee
Where: point voltages compliant with the following formula:-
Ip =Phase fault current calculated for Xp/Rp
ratio at the end of zone 1 Vk = 50ln (RCT + 2RL + RR) where maximum through
le =earth fault current calculated for Xe/ Re fault current = 10 x ln with maximum X/R = 120.
ratio at the end of zone 1 Minimum Vk to be 60 Volts.
N =C.T. ratio
Xp/Rp =power system reactance to resistance ratio Vk = 30ln (RCT + 2RL + RR) where maximum through
for the total plant including the feeder line fault current = 10 x ln with maximum X/R = 60.
parameters calculated for a phase fault at Minimum Vk to be 60 Volts.
the end of zone 1
Xe/Re =similar ratio to above but calculated for an Where:
earth fault at the end of zone 1 Vk = Knee point voltage
Rct =C.T. internal resistance ln = Rated current
RI =lead burden, C.T. to Ohmega terminals X/R = The X/R ratio for the maximum through fault
K =Factor chosen to ensure adequate condition.
operating speed and is <1. K is usually 0.5 RCT = Secondary resistance of the current
for distribution systems, a higher value is transformer (ohms)
chosen for primary transmission systems. RL = Lead resistance between the current
Reyrolle Protection should be consulted. transformers and the relay (ohms)
RR = Resistance of any other protection functions
Both Vk values should be calculated and the higher sharing the current transformer (ohms)
value chosen for the c.t. to be used.
Where all the onerous conditions described above are
10 GAMMA (Numeric): Generator Protection not required to be met and the c.t. accommodation
facility is limited, the requirements can be reduced, in
a) Two off 3 phase Inputs (Line end and Neutral these circumstances contact VA Tech Reyrolle -
End): Protection for advice.
11 RHO (Numeric): Motor Protection and The class and rating are selected as per the phase input
Electrical Plant Thermal Overload c.t’s. The rated burden is establish from:-
11.1 RHO for low voltage 3 phase A.C. motors VA ≤ (In)² (2Rl + R1 ) [References as before]
For the earth fault c.t. input Rb ≤ 300 ohm
The RHO 0 relay is compatible with CT’s having
either 25mA or 5A secondaries.
If the residual connection mode is employed the e.f. c.t.
input burden should be added to the phase c.t. burden
25mA rated output c.t’s are recommended for motor
since this is a significant value. For this form of
currents up to 100A and 5A up to 3000A
connection a stabilising resistor may be required in the
earth fault c.t. input, e.g. if the setting is instantaneous.
For 5 amp relay input rating some motor control
This resistance must be included in the value for R1.
systems result in high multiples of rated current
However residual connection is not recommended.
flowing during the start up period, and for some
motors the run-up time may be very long (eg 60
11.2 RHO 3 for high voltage 3 phase A.C. motors
seconds). Because of this there are some limitations
and electrical plant
on the motor rating that can be utilised with a
particular c.t. rating due to the thermal capacity of the
Thermal Overload
relay c.t. input terminals. If the motor rating is limited
to less than 75% of the c.t. rating there is unlikely to
The c.t. class recommended is 5P10. This provides
be any problem with overheating no matter how
accurate measurement (maximum error of 5%) for
onerous the starting current, starting time or number
overloads and also for high current magnitudes beyond
of starts in a period of time for practical
typical motor stall current (eg. 6 x full load current).
considerations.
The rated burden is established by selecting a value in
The c.t. classification should be 10P10 or better (eg.
excess of the c.t. secondary circuit loading, eg:-
5P10 for improved accuracy) and have a rating to suit
the c.t. secondary total burdens, ie. C.t. leads, RHO
Rated VA ≥ (In)² (2Rl+ Rb + R1)
0 relay and any equipment connected in series with
the relay.
Where:
In = Rated secondary current
Rl = Secondary lead burdens per phase
Rb = Relay circuit burden (See table
below)
R1 = Other equipment burden per phase
AC Impedance
Burden
5A Phase £ 0.2VA £ 0.01 W
1A Phase £ 0.05VA £ 0.05 W
5A Earth £ 0.4VA £ 0.02 W
1A Earth £ 0.2VA £ 0.2 W