Академический Документы
Профессиональный Документы
Культура Документы
A cooling tower is a device commonly used to cool condenser water in power and refrigerating plants.
SYSTEMS USING COOLING TOWER
1. Cooling Towers for Refrigeration
An important device used in any refrigeration or air conditioning system is a condenser. A condenser
is used in the high pressure side of a refrigeration or air conditioning system to convert the high-pressure
vapour refrigerant from the compressor into liquid refrigerant. The medium used in a condenser may be
water or air, depending upon the application. In the case of water cooled condensers, the warm water being
pumped by the condenser should be cooled with the help of cooling towers so that the same water may be
re-circulated to the condenser.
Water-cooled chillers are normally more energy efficient than air-cooled chillers due to heat rejection to
tower water at or near wet-bulb temperatures.
2. Industrial Cooling Towers
Industrial cooling towers can be used to remove heat from various sources such as machinery or heated
process material. The primary use of large, industrial cooling towers is to remove the heat absorbed in the
circulating cooling water systems used in power plants, petroleum refineries, petrochemical plants, natural
gas processing plants, food processing plants, semi-conductor plants, and for other industrial facilities
such as in condensers of distillation columns, for cooling liquid in crystallization, etc.
Disadvantages
Higher investment costs
Requires large areas for tower installation
For the same capacity used, the mechanical draft cooling towers are much smaller than the natural draft
cooling towers. This is because of the increase in cooling capacity due to increase in volume of the air
being forced out by fan.
Capacity control is possible in mechanical draft cooling tower. By controlling the speed of the fan, the
volume of air can be controlled, which in turn controls the capacity.
The natural draft cooling towers can be located only in open space. As they do not depend upon the
atmospheric air, the mechanical draft cooling towers shall be located even inside the building.
According to the location of the fan, they are further classified as:
1. Forced draft cooling towers, and
2. Induced draft cooling towers.
Forced Draft Cooling Towers
In this system, fan is located near the bottom and on the side. This fan forces
the air from bottom to top. An eliminator is used to prevent loss of water
droplets along with the forced air.
Induced Draft Cooling Towers
In this system, a centrally located fan at the top, takes suction from the tower
and discharges it to the atmosphere. The only difference between the induced
draft cooling tower and forced draft cooling tower is that the fan is located at
the top in the induced draft cooling tower.
Figure 52 Forced Draft Cooling Tower
Comparison between Induced Draft Counter Flow and Cross Flow Cooling Towers
Figure 54 Induced draft counter flow and cross flow cooling towers.
Counter flow
In a counter flow design, the air flow is directly opposite to the water flow (see Figure 54 upper diagram). Air flow
first enters an open area beneath the fill media, and is then drawn up vertically. The water is sprayed through pressurized
nozzles near the top of the tower, and then flows downward through the fill, opposite to the air flow.
Advantages of the counter flow design:
Breakup of water in spray makes heat transfer more efficient.
The coldest water comes in contact with the coolest and most dry air, optimizing the heat transfer and
obtaining the maximum performance
Disadvantages of the counter flow design:
Typically higher initial and long-term cost, primarily due to pump requirements.
Difficult to use variable water flow, as spray characteristics may be negatively affected.
Cross flow
Cross flow is a design in which the air flow is directed perpendicular to the water flow (see Figure 54 lower diagram).
Air flow enters one or more vertical faces of the cooling tower to meet the fill material. Water flows (perpendicular to the
air) through the fill by gravity.
A distribution or hot water basin consisting of a deep pan with holes or nozzles in its bottom is located near the top of
a cross flow tower. Gravity distributes the water through the nozzles uniformly across the fill material.
Advantages of the cross flow design:
Gravity water distribution allows smaller pumps and maintenance while in use.
Typically lower initial and long-term cost, mostly due to pump requirements.
Disadvantages of the cross flow design:
The air flows horizontally and the water falling downwards meets the air at different
temperatures. Therefore the heat transfer is not always optimized
Low pressure head on the distribution pan may encourage orifice clogging and less water breakup at spray
nozzle.
Energy balance:
m3h3 + mah1 = m4h4 + mah2
m3h3 m4h4 = ma(h2 h1)
where: m3 = mass of water entering
m4 = mass of cooled water received by cold water basin
h3 = enthalpy of water entering, kJ/kg = hf at t3
h4 = enthalpy of water leaving, kJ/kg = hf at t4
h1 = enthalpy of air entering, kJ/kg d.a
h2 = enthalpy of air leaving, kJ/kg d.a
Mass balance:
m3 + mmoist air1 = m4 + mmoist air2
m3 + ma + mv1 = m4 + ma + mv2
m3 + maW1 = m4 + maW2
m3 m4 = ma (W2 W1) = mass of water evaporated (or mass of make-up water)
where: W1 = humidity ratio of air entering, kg/kgd.a
W2 = humidity ratio of air leaving, kg/kgd.a
Approach Cooling Range, ACR = (also simply Approach) difference between the temperature of the
cooled tower water, t4 and the atmospheric wet bulb temperature, tw1. Approach is the most important
indicator of cooling tower performance. It dictates the theoretical limit to the leaving cold-water
temperature. The approach temperatures generally fall between 5 and 20F implying that the leaving
cooled water temperature shall be 5 to 20oF above the ambient WBT.
ACR = t4 tw1
Actual Cooling Range, CRA = difference between the raw water temperature at the entrance, t3 and
the cooled water at the basin, t4. It is the actual temperature drop of
water.
CRA = t3 t4
Theoretical Cooling Range, CRT = difference between the raw water temperature at the entrance, t3
and the atmospheric wet bulb temperature, tw1. It is the maximum
temperature drop)
CRT = t3 tw1
Cooling Tower Efficiency =
Sample Problems
1.) In a cooling tower 28.34 m3/min of air at 32oC DB and
24oC WB enter the tower and leave saturated at 29oC.
(a) To what temperature can the air stream cool a spray
of water which enters at 38oC, with a flow of 34 kg/min
of water? (b) Cooling tower efficiency and (c) How
many kg per hour of make-up water is needed to
compensate for the water that is evaporated?
Solution:
Point 1:
m3 m4 = ma(W2 W1)
34 m4 = (32.06) (0.0256 0.0156)
m4 = 33.68 kg/min
Energy balance:
m3h3 m4h4 = ma(h2 h1)
(34) (159.21) 33.68h4 = (32.06) (95 72.5)
h4 = 139.3 kJ/kg = hf at t4
t4 = tsat at hf (139.3 kJ/kg)
Using steam table No. 1, by interpolation: t4 = tsat at hf t4 = 33.2oC
(b) Cooling Tower Efficiency =
(c) Make-up water = ma (W2 W1) = (32.060) (0.0256 0.0156) = 0.3206 kg/min or 19.24 kg/h
2.) Fifty gallons per minute of water enters a cooling tower at
46oC. Atmospheric air at 16oC DB and 55% RH enters
the tower at 2.85 m3/sec and leaves at 32oC saturated.
Determine (a) the volume flow rate of water receives by
cold water basin, and (b) the exit temperature of the
water.
Solution:
Point 1: At td1 = 16oC and 1 = 55%,
h1 = 32 kJ/kg v1 = 0.828 m3/kg
W1 = 0.0056 kg/kgd.a
ma = V1 = 2.85 m3/min = 3.442 kg/min
v1
0.828 m3/kg
Point 2: At td2 = 32oC and 2 = 100% RH (saturated air),
Point 3: Using Steam Table No.1: h3 = hf at 46oC = 192.62 kJ/kg, v3 = vf at 46oC = 0.0010103 m3/kg
m3 = V3 = (50 gal/min x 1 min/60 sec) (3.7854 L/gal x 1 m3 /1000L) = 3.122 kg/sec
v3
(0.0010103 m3/kg)
(a) Mass balance:
m3 m4 = ma(W2 W1)
3.122 m4 = (3.442) (0.0307 0.0056)
m4 = 3.036 kg/min
Energy balance:
m3h3 m4h4 = ma(h2 h1)
(3.122) (192.62) 3.036h4 = (3.442) (111 32)
h4 = 108.51 kJ/kg = hf at t4
t4 = tsat at hf (108.51 kJ/kg)
Using steam table No. 1, by interpolation: t4 = tsat at hf(108.51 kJ/kg) t4 = 25.9oC
Specific volume of water leaving, v4 = vf at hf(108.51 kJ/kg)
v4 = 0.0010031 m3/kg
Volume flow rate of water leaving = m4v4 = (3.036 kg/sec) (0.0010031 m3/kg) = 0.003045 m3/sec
3.) Water at 55oC is cooled in a cooling tower which has an efficiency of 65%. The temperature of the
surrounding air is 32oC DB and 70% RH. The heat dissipated from the condenser is 2,300,000 kJ/h. Find
the capacity in liters per second of the pump used in the cooling tower.
Solution:
t3 t4 x 100% = 55 t4 x 100%
t3 tw1
55 27.4
t4 = 37.1oC
Heat balance about condenser,
mwh4 = mwh3 + Q
Capacity of pump = mw v4 = (8.54 kg/sec) (1.00674 x 10-3 m3/kg) = 0.00859 m3/sec or 8.59 L/s
Problems:
(1) In a cooling tower water enters at 52oC and leaves at 27oC. Air at 29oC and 47% RH also enters the cooling
tower and leaves at 46oC fully saturated with moisture. It is desired to determine (a) the volume and mass
of air necessary to cool one kg of water, and (b) the quantity of water that can be cooled with 142 m 3/min
at atmospheric air. Ans: (a) 0.5742 m3, 0.66 kg; (b) 247.3 kg
(2) A cooling tower receives 6 kg/s of water of 60oC. Air enters the tower at 32oC DB and 27oC WB
temperatures and leaves at 50oC and 90 per cent relative humidity. The cooling efficiency is 60.6 per cent.
Determine (a) the mass flow rate of air entering, and (b) the quantity of make-up water required. Ans: (a)
3.253 kg/s, (b) 0.1818 kg/s
(3)
A mechanical-draft cooling tower receives 115 m3/sec of atmospheric air at 103 kPa, 32oC DB
temperature, 55%RH and discharges the air saturated at 36oC. If the tower receives 200 kg/sec of water at
40oC, what will be the exit temperature of the cooled water? Ans: 31.2oC