Epoxy & Cycloaliphatic

EPOXY RESIN
MEDIUM VOLTAGE BUSHINGS
Indoor epoxy resin
Raw material

Aromatic epoxy resin, hardened with dicarboxylic acid anhydrides filled with silanised silica

Tensile strength

79,28 N/mm

ISO R 527

Flexural strength

102,45 N/mm

ISO R 178

Impact strength

9,2 kJ/m

ISO 179

Noth impact strength

1,2 kJ/m

ISO 179

Compressive Strength

130 - 150 N/mm

ISO R 604

Critical stress intensity factor (K ic)

1.9 - 2.1 Mpa.m1/2

CG 216-0/89

Specific energy at break (Gic)

300 - 340 J/m

CG 216-0/89

Glass transition point

115 +5/-10 C

ISO 11357-1 (DSC)

Class of flammability

V1 >12mm

UL 94

Water absorbtion

0,018% by wt.

ISO 62

Coeff. of linear thermal expansion

31-36*10-6 K-1

DIN 53752 (20 - 80C)

Tracking resistance

CTI >600 -0.0

IEC 60112

Dielectric constant

4,2 (23 C, 50 Hz)

DIN 53483

Dissipation factor

0,0309 % (23C - 50 Hz)

IEC 60250

Dielectric strength

17 - 20 kV/mm

IEC 60243 - 1

HV arc resistance

182 - 189 seconds

ASTM D 495

1.9 g/cm

ISO 1183-1

Density
Color

brown

Outdoor Cycloaliphatic resin


Raw material

Cycloaliphatic epoxy resin, hardened with dicarboxylic acid anhydrides filled with silanised
silica

Tensile strength

85,1 N/mm

ISO 527

Flexural strength

134,8 N/mm

ISO 178

Impact strength

12,6 kJ/m

ISO 179

Notch impact strength

1,5 kJ/m

Critical stress intensity factor (K ic)

2.15-2.35 Mpa.m

ISO 179
1/2

CG 216-0/89

Specific energy at break (Gic)

470-500 J/m

CG 216-0/89

Class of flammability

V1 (>12 mm)

UL 94

Glass transition point

110 +/-5 C

ISO 11357-1 (DSC)

Tracking resistance

CTI <600-0.0

IEC 60112

Volume resistance

8,89+15 Ohm.cm

IEC 60093

1.5 - 5.0 % (23 - 100C)

DIN 53483

35-38*10-6 K-1

DIN 53752

4,12 (23 C, 50 Hz)

IEC 60250

Dielectric strength

18 - 20 kV/mm

IEC 60243 - 1

Dissipation factor

0,0101 % (23 C, 50 Hz)

IEC 60250

Water absorption

0,026% by wt.

ISO 62

1.9 g/cm

ISO 1183-1

Loss factor
Coeff. of linear thermal expansion
Dielectric constant

Density
Color

E-50

brown

sprl BINAME bvba Robert Dansaertlaan, 250 1702 Groot-Bijgaarden Belgium


Tel : +32 (0)2 466 25 08 Fax : +32 (0)2 466 59 90 info@biname.be www.insulators.be

Epoxy busbar passing insulator for indoor use


Isolateurs de traverse en poxy intrieur - intrieur
Doorvoerisolatoren in epoxy voor binnendienst
Recommended service voltage
Tension asignee demploi
Aanbevolen dienstspanning

Widths for EPDM


BUSBARS spacers

55

1x40x5mm
1x40x10mm

75

1x50x10mm
2x50x10mm
1x60x10mm
2x60x10mm

95

1x80x10mm
2x80x10mm

115

1x100x10mm
2x100x10mm

145

1x120x10mm
2x120x10mm

REF.
B740
B707
B708
B4054
B4055
B741
B742
B709
B4056
B4057

12-24-36 kV

Epoxy & Cycloaliphatic

Type : GD 12 kV - GD 24/36 kV
Screwable bushing / Vissable / Schroefbaar
Indoor / Intrieur / Binnendienst
Option : EPDM spacer / Obturateur / Doppen

S
(mm)
2-4-6-8-12
2-4-6-8-12
2-4-6-8-12
2-4-6-8-12
2-4-6-8-12
2-4-6-8-12
2-4-6-8-12
2-4-6-8-12
2-4-6-8-12
2-4-6-8-12

A
(kV)

B
(kV)

2
(kV)

3
(kV)

(A)

Rated Highest voltage for equipment (Um) - On metal panel


Tension assigne la plus leve pour le matriel (Um) - Sur parois mtal
Toegekende Maximale systeemspanning (Um) - Op metalen wand

(B)

Rated Highest voltage for equipment (Um) - On metal panel


Tension assigne la plus leve pour le matriel (Um) - Sur parois mtal
Toegekende Maximale systeemspanning (Um) - Op metalen wand

(2)

Rated Power Frequency Withstand Voltage, dry (50 Hz, 1 min)


Tension de tenue assigne frquence industrielle, sec (50 Hz, 1 min)
Toegekende overspanning bij industriele frekwentie, droog (50 Hz, 1 min)

(3)

Rated Lightning impulse withstand (1.2/50 s)


Tension de tenue assigne au choc de foudre (1.2/50 s)
Toegekende Stootspanningsniveau (1,2/50 s)

Cr

Creepage distance / Ligne de fuite / Kruipafstand.

Flexion resistance / Rsistance la flexion / Buigweerstand

Cr
mm

120
140
160
180
210
140
160
180
200
230

55
75
95
115
145
55
75
95
115
145

95
115
135
155
185
102
127
145
165
195

12

28

75

120

7500
7500
7500
10000
10000

12

24/36

50

125

230

12500

120

150

c
50
50
50
50
50
65,5
70,5
65
65
65

sprl BINAME bvba Robert Dansaertlaan, 250 1702 Groot-Bijgaarden Belgium


Tel : +32 (0)2 466 25 08 Fax : +32 (0)2 466 59 90 info@biname.be www.insulators.be

Z
(kg)
1,1
1,3
1,6
1,8
2,2
1,65
1,96
2,3
2,6
3,0

E-51

Epoxy busbar passing insulator for indoor use


Isolateurs de traverse en poxy intrieur - intrieur
Doorvoerisolatoren in epoxy voor binnendienst

Epoxy & Cycloaliphatic

Type : RDIG 12 kV
Bar passing bushing
Indoor / Intrieur / binnendienst
Option : EPDM spacer / Obturateur / Doppen

12 kV

art. 2019624
art. 2022359

Widths for EPDM


BUSBARS spacers

55

1x40x5mm
1x40x10mm

75

1x50x10mm
2x50x10mm
1x60x10mm
2x60x10mm

95

1x80x10mm
2x80x10mm

115

1x100x10mm
2x100x10mm

145

1x120x10mm
2x120x10mm

REF.
2022326
2019624
2022355
2022357
2022359
2019672

E-52

Recommended service voltage


Tension asignee demploi
Aanbevolen dienstspanning

1 (kV)

12

2 (kV)

28

3 (kV)

75

Cr
mm
170
170
170
170
170
190

(1)

Rated Highest voltage for equipment (Um)


Tension assigne la plus leve pour le matriel (Um)
Toegekende Maximale systeemspanning (Um)

(2)

Rated Power Frequency Withstand Voltage, dry (50 Hz, 1 min)


Tension de tenue assigne frquence industrielle, sec (50 Hz, 1 min)
Toegekende overspanning bij industriele frekwentie, droog (50 Hz, 1 min)

(3)

Rated Lightning impulse withstand (1.2/50 s)


Tension de tenue assigne au choc de foudre (1.2/50 s)
Toegekende Stootspanningsniveau (1,2/50 s)

Cr

Creepage distance / Ligne de fuite / Kruipafstand.

Flexion resistance / Rsistance la flexion / Buigweerstand

7500
10000
10000
10000
10000
10000

95
115
140
160
185
260

55
75
95
115
145
195

14
14
14
14
17
17

100
120
145
165
190
270

145
160
185
205
235
225

185
200
230
250
290
280

120
132
160
180
205
280

20
20
20
20
22,5
28

55

sprl BINAME bvba Robert Dansaertlaan, 250 1702 Groot-Bijgaarden Belgium


Tel : +32 (0)2 466 25 08 Fax : +32 (0)2 466 59 90 info@biname.be www.insulators.be

Z
(kg)
2,18
2,51
3,91
4,80
6,30
11,50

Epoxy busbar passing insulator for indoor use


Isolateurs de traverse en poxy intrieur - intrieur
Doorvoerisolatoren in epoxy voor binnendienst
Recommended service voltage
Tension asignee demploi
Aanbevolen dienstspanning

24/36 kV

The metal fittings are electrically


connected.The bushing flange is provided with a
tapped hole M12.

Widths for aluminium


BUSBAR spacers

55

1x40x5mm
1x40x10mm

75

1x50x10mm
2x50x10mm
1x60x10mm
2x60x10mm

95

1x80x10mm
2x80x10mm

115

1x100x10mm
2x100x10mm

145

1x120x10mm
2x120x10mm

REF.
2022411
2022416
2022500
2022507
2022512
2022586
2022589
2022595

1 (kV)

2 (kV)

2022512

3 (kV)

Cr
mm

24

50

125

310

36

70

170

380

7500
7500
12500
12500
7500
7500
12500
12500

105
125
145
165
118
140
155
175

58
80
98
118
58
80
98
118

(1)

Rated Highest voltage for equipment (Um)


Tension assigne la plus leve pour le matriel (Um)
Toegekende Maximale systeemspanning (Um)

(2)

Rated Power Frequency Withstand Voltage, dry (50 Hz, 1 min)


Tension de tenue assigne frquence industrielle, sec (50 Hz, 1 min)
Toegekende overspanning bij industriele frekwentie, droog (50 Hz, 1 min)

(3)

Rated Lightning impulse withstand (1.2/50 s)


Tension de tenue assigne au choc de foudre (1.2/50 s)
Toegekende Stootspanningsniveau (1,2/50 s)

Cr

Creepage distance / Ligne de fuite / Kruipafstand.

Flexion resistance / Rsistance la flexion / Buigweerstand

L1

L2

515

240

645

300

22
22
22
28
28
28
28
28

120
140
160
180
135
160
180
200

170
190
210
230
170
200
220
240

215
235
255
280
220
245
265
285

130
150
170
190
140
165
185
205

sprl BINAME bvba Robert Dansaertlaan, 250 1702 Groot-Bijgaarden Belgium


Tel : +32 (0)2 466 25 08 Fax : +32 (0)2 466 59 90 info@biname.be www.insulators.be

145

220

Epoxy & Cycloaliphatic

Type : RDIG 20/24 - 30/36 kV


Bar passing bushing
Indoor / Intrieur / binnendienst
Option : Spacer / Obturateur / Doppen

Z
(kg)
6,84
7,46
9,13
10,85
9,30
12,46
13,78
16,20

E-53

Epoxy bushings for indoor use


Isolateurs de traverse en poxy intrieur - intrieur
Doorvoerisolatoren in epoxy voor binnendienst
Type : RDBG 12 kV
Bolt bushing
Indoor / Intrieur / binnendienst

Epoxy & Cycloaliphatic

Recommended service voltage


Tension asignee demploi
Aanbevolen dienstspanning

art. 2019598

REF.
2019598
2019599
2019600
2019601

E-54

12 kV

1 (kV)

2 (kV)

3 (kV)

(Cr) mm

12

28

75

170

3750

A
200
400
630
800

(1)

Rated Highest voltage for equipment (Um)


Tension assigne la plus leve pour le matriel (Um)
Toegekende Maximale systeemspanning (Um)

(2)

Rated Power Frequency Withstand Voltage, dry (50 Hz, 1 min)


Tension de tenue assigne frquence industrielle, sec (50 Hz, 1 min)
Toegekende overspanning bij industriele frekwentie, droog (50 Hz, 1 min)

(3)

Rated Lightning impulse withstand (1.2/50 s)


Tension de tenue assigne au choc de foudre (1.2/50 s)
Toegekende Stootspanningsniveau (1,2/50 s)

Cr

Creepage distance / Ligne de fuite / Kruipafstand.

Flexion resistance / Rsistance la flexion / Buigweerstand

Rated current / Intensit nominale / Nominale Stroom


L
395
415
435
455

L3
50
60
70
80

d
M12
M16
M20
M24 x2

h
62

sprl BINAME bvba Robert Dansaertlaan, 250 1702 Groot-Bijgaarden Belgium


Tel : +32 (0)2 466 25 08 Fax : +32 (0)2 466 59 90 info@biname.be www.insulators.be

Z (kg)
1,70
2,05
2,60
3,40

Epoxy bushings for indoor use


Isolateurs de traverse en poxy intrieur - intrieur
Doorvoerisolatoren in epoxy voor binnendienst
Recommended service voltage
Tension asignee demploi
Aanbevolen dienstspanning

24/36 kV

Epoxy & Cycloaliphatic

Type : RDBG 20/24 - 30/36 kV


Bolt bushing
Indoor / Intrieur / binnendienst

The metal fittings are electrically


connected.The bushing flange is provided with a
tapped hole M12.

art. 2022322 + 2037717

REF.

Bolts+
fittings
2037717
2037718
2022322
2037119
2019605 - bolts & fit. Incl.
2037721
2037722
2037723
2022323
2037724
2037725
2037726
2037727

1 (kV)

2 (kV)

3 (kV)

Cr

24

50

125

280

7500

36

70

170

400

7500

(1)

Rated Highest voltage for equipment (Um)


Tension assigne la plus leve pour le matriel (Um)
Toegekende Maximale systeemspanning (Um)

(2)

Rated Power Frequency Withstand Voltage, dry (50 Hz, 1 min)


Tension de tenue assigne frquence industrielle, sec (50 Hz, 1 min)
Toegekende overspanning bij industriele frekwentie, droog (50 Hz, 1 min)

(3)

Rated Lightning impulse withstand (1.2/50 s)


Tension de tenue assigne au choc de foudre (1.2/50 s)
Toegekende Stootspanningsniveau (1,2/50 s)

Cr

Creepage distance / Ligne de fuite / Kruipafstand.

Flexion resistance / Rsistance la flexion / Buigweerstand

Rated current / Intensit nominale / Nominale Stroom

200
400
630
800
200
400
630
800
1000
1250
1600

615
635
655
675
840
860
880
900
960
1000
1030

L1

L2

515

240

740

350

L3

d1

50
60
70
80
50
60
70
80
110
130
145

M12
M16
M20
M24 x 2
M12
M16
M20
M24 x 2
M30 x 2
M33 x 2
M36 x 3

d2

70

157

80

22

100 237 110

28

Z
(kg)
4,45
4,85
130 185 100
5,60
6,50
11,90
12,60
13,50
150 200 120 15,50
17,50
19,00
20,50
u

sprl BINAME bvba Robert Dansaertlaan, 250 1702 Groot-Bijgaarden Belgium


Tel : +32 (0)2 466 25 08 Fax : +32 (0)2 466 59 90 info@biname.be www.insulators.be

E-55

Epoxy bushings - indoor - outdoor


Isolateurs de traverse en poxy - Intrieur-Extrieur
Doorvoerisolatoren in epoxy - binnen - buiten

Epoxy & Cycloaliphatic

Type : FDBG 12 - 20/24 - 30/36kV


- Bolt bushing
- Indoor / outdoor
- intrieur/extrieur
- Binnen-/buitendienst

Bolts +
fittings
2037732
2021837
2037733
2037734
2019789 bolts & fit. Incl.
2037728
2021839
2037729
2037730
2019793 bolts & fit. Incl.
2037668
2037669
2037670
2021841
2037671
2037672
2037673
REF.

E-56

1 (kV)

2 (kV)

3 (kV)

Cr
mm

12

28

75

280

7500

24

50

125

610

7500

36

70

170

750

7500

200
400
630
800
200
400
630
800
200
400
630
800
1000
1250

450
470
490
510
665
685
705
725
860
880
900
920
980
1020

(1)

Rated Highest voltage for equipment (Um)


Tension assigne la plus leve pour le matriel (Um)
Toegekende Maximale systeemspanning (Um)

(2)

Rated Power Frequency Withstand Voltage, dry (50 Hz, 1 min)


Tension de tenue assigne frquence industrielle, sec (50 Hz, 1 min)
Toegekende overspanning bij industriele frekwentie, droog (50 Hz, 1 min)

(3)

Rated Lightning impulse withstand (1.2/50 s)


Tension de tenue assigne au choc de foudre (1.2/50 s)
Toegekende Stootspanningsniveau (1,2/50 s)

Cr

Creepage distance / Ligne de fuite / Kruipafstand.

Flexion resistance / Rsistance la flexion / Buigweerstand

Rated current / Intensit nominale / Nominale Stroom

L1

L2

L3

d1

d2

50
60
140 62
70
80
50
60
565 295
150 70
70
80
50
60
70
760 360
170 100
80
110
130
350 175

d3

90

80

110

d4
M12
M16
M20
M24 x 2
M12
M16
M20
M24 x 2
M12
M16
M20
M24 x 2
M30 x 2
M33 x 2

d5

70

96

165 115

22

80

190 175 125

28

110 270 190 140

35

sprl BINAME bvba Robert Dansaertlaan, 250 1702 Groot-Bijgaarden Belgium


Tel : +32 (0)2 466 25 08 Fax : +32 (0)2 466 59 90 info@biname.be www.insulators.be

Z
(kg)
3,40
4,00
4,50
5,00
7,15
7,70
8,60
9,40
12,70
13,50
14,50
15,55
18,00
20,00