Вы находитесь на странице: 1из 20

Advantages

Range of standard sizes

High efficiency

Rigid design concept

Suitable for turbulent airflow

TIFICAT
ER

Application: Air conditioning applications.


Type: Rigid pleated filter.
Case: Galvanised steel.
Media: Glass fibre.
EN 779:2002 efficiency: F5 (40-45%), F6 (55-65%), F7 (80-85%), F8 (90-95%).
Eurovent 4/5 efficiency: EU5, EU6, EU7, EU8.
Recommended final pressure drop: 450 Pa (suggested economical change point 250 Pa).
Temperature: 70C maximum in continuous service.
Holding frames: Front and side access housings and frames are available.

EN 779:2002
DI

IE

IN

VI

DU

ALLY CER

TI

Reference

Type

Model

Dimensions (WxHxD) mm

Filter classification EN
779:2002

Media surface
m2

060558-007

Riga Flo

Riga Flo 10

594x594x292

F5

5.4

3420/65

7.70

060558-012

Riga Flo

Riga Flo 10

492x594x292

F5

4.4

2790/65

5.77

0.11

060558-008

Riga Flo

Riga Flo 10

289x594x292

F5

2.6

1710/65

4.55

0.06

078367-007

Riga Flo

Riga Flo 10

594x594x152

F5

2.7

2070/55

3.42

0.06

078367-016

Riga Flo

Riga Flo 10

492x594x152

F5

2.2

1710/55

2.57

0.06

078367-008

Riga Flo

Riga Flo 10

289x594x152

F5

1.3

990/55

2.21

0.03

060558-001

Riga Flo

Riga Flo 15

594x594x292

F6

5.4

3420/70

7.70

0.11

060558-009

Riga Flo

Riga Flo 15

492x594x292

F6

4.4

2790/70

5.77

0.11

060558-004

Riga Flo

Riga Flo 15

289x594x292

F6

2.6

1710/70

4.55

0.06

078367-001

Riga Flo

Riga Flo 15

594x594x152

F6

2.7

2070/65

3.42

0.06

078367-013

Riga Flo

Riga Flo 15

492x594x152

F6

2.2

1710/65

2.57

0.06

078367-004

Riga Flo

Riga Flo 15

289x594x152

F6

1.3

990/65

2.21

0.03

060558-002

Riga Flo

Riga Flo 100

594x594x292

F7

5.4

3420/90

7.70

0.11

060558-010

Riga Flo

Riga Flo 100

492x594x292

F7

4.4

2790/90

5.77

0.11

060558-005

Riga Flo

Riga Flo 100

289x594x292

F7

2.6

1710/90

4.55

0.06

078367-002

Riga Flo

Riga Flo 100

594x594x152

F7

2.7

2070/90

3.42

0.06

078367-014

Riga Flo

Riga Flo 100

492x594x152

F7

2.2

1710/90

2.57

0.06

078367-005

Riga Flo

Riga Flo 100

289x594x152

F7

1.3

990/90

2.21

0.03

060558-003

Riga Flo

Riga Flo 200

594x594x292

F8

5.4

3420/130

7.70

0.11

060558-011

Riga Flo

Riga Flo 200

492x594x292

F8

4.4

2790/130

5.77

0.11

060558-006

Riga Flo

Riga Flo 200

289x594x292

F8

2.6

1710/130

4.55

0.06

078367-003

Riga Flo

Riga Flo 200

594x594x152

F8

2.7

2070/175

3.42

0.06

078367-015

Riga Flo

Riga Flo 200

492x594x152

F8

2.2

1710/175

2.57

0.06

078367-006

Riga Flo

Riga Flo 200

289x594x152

F8

1.3

990/175

2.21

0.03

Air flow/presure drop at m 3 / Unit weight kg


Unit volume m 3
h/Pa

Filter Frames and Housings

Carbon and Chemical Filters

0.11

Other sizes are available on request - PH version also available (with header frame)

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

39

A i r F i l t e r Te c h n o l o g y

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

EFFICIENCY
GUARANTEE

Bag and Compact Filters,


Class F5 to F9

Riga-Flo

H E PA / U L PA F i l t e r s , C l a s s
H10 to U17

Pleated Compact Filter

Pre-Filtration, Class G3 to F5

Camfil Farr Solutions

Bag and Compact Filters, Class F5 to F9

Bag and Compact Filters, Class F5 to F9


Pleated Compact Filter

OpakAir

TIFICAT
ER

Advantages

EN 779:2002
DI

IE

IN

VI

DU

ALLY CER

TI

Large surface area

Less frequent changes

Up to 6000 m 3 /hr air flow

Low pressure drop

Application: High air flow air conditioning and process air applications.
Type: High capacity compact filter.
Case: Galvanised steel.
Gasket: Half round EDPM.
Media: Glass fibre paper.
Separator: Hot-melt beads.
Sealant: Polyurethane.
EN 779:2002 efficiency: F8.
Opacimetric efficiency: 95%.
Recommended final pressure drop: 450 Pa (suggested economical change point 250 Pa).
Temperature: 70C maximum in continuous service.
Mounting System: Front and side access housings and safechange systems are available.

EFFICIENCY
GUARANTEE

1514.13.05 OPAKAIR -95

OPR-E-F8

610x610x292

F8

4500/110

19,0

18,00

0,11

1514.53.05 OPAKAIR -95

OPR-E-F8

305x610x292

F8

2250/110

10,0

9,00

0,06

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

40

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

Unit
Unit
weight kg volume m 3

Dimensions
(WxHxD) mm

Type

Filter classification Air flow/pressure drop


EN 779:2002
m/hr/Pa

Media
area m 2

Model

Reference

Advantages
Low pressure drop

Large surface area

Robust metal header frame

Rigid design concept

High dust holding capacity

Application: Air conditioning applications and preparatory filtration in clean rooms.


Type: High efficiency compact filter, HF model with header frame.
Case: Galvanised steel.
Media: Glass fibre paper.
Separator: Hot-melt beads.
Sealant: Polyurethane.
EN 779:2002 efficiency: F7.
Opacimetric efficiency: 85%.
Recommended final pressure drop: 450 Pa (suggested economical change point 250 Pa).
Temperature: 70C maximum in continuous service.
Mounting system: Front and side access housing and frames are available, type 8, type L and
FC housings.

Media area
Unit
Unit
weight kg volume m 3
m2

Reference

Type

Model

Dimensions
(WxHxD) mm

Air flow/nominal
pressure drop m/h/Pa

Energy
Rating

304215

Airopac-90

3GGM-24246-90

610x610x150

3600/105

12,3

6,8

0,06

304219

Airopac-90

3GGM-12246-90

305x610x150

1800/110

6,1

4,0

0,03

Airopac-HF-90 3GGMHF-24245-90

592x592x135

3600/135

10,3

6,8

0,05

301739

Airopac-HF-90 3GGMHF-12245-90

287x592x135

1800/160

4,5

3,8

0,02

Filter Frames and Housings

Carbon and Chemical Filters

301732

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

41

A i r F i l t e r Te c h n o l o g y

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

EFFICIENCY
GUARANTEE

Bag and Compact Filters,


Class F5 to F9

Airopac

H E PA / U L PA F i l t e r s , C l a s s
H10 to U17

Pleated Compact Filter

Pre-Filtration, Class G3 to F5

Camfil Farr Solutions

Bag and Compact Filters, Class F5 to F9

Bag and Compact Filters, Class F5 to F9

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

42

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

Notes

Page 46

Page 47

Page 48

HEPA/ULPA Panels
Megalam MD, MX, MG

HEPA/ULPA Panels
Megalam MX & MG - H14

HEPA/ULPA Panels
Megalam MD - H10 & H14

HEPA/ULPA Panels
Megalam MD & MG - U15

Page 49

Page 50

Page 51

Page 52

HEPA/ULPA Panels
Megalam (Laminator) MDL &
MXL - U15 & U16

HEPA/ULPA Panels
Silent Hood Diffuser - H14

HEPA/ULPA Panels
HEPA/ULPA Panels
Megalam U (Gel) - H14 & U15 Megalam T (Gel) - H14 & U15

Page 55

Page 56

Filter Frames and Housings

Page 53

Carbon and Chemical Filters

Page 54

H E PA / U L PA F i l t e r s , C l a s s
H10 to U17

Page 45

HEPA/ULPA Panels
Megalam MD & MX e-PTFE U15

Page 57

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

43

A i r F i l t e r Te c h n o l o g y

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

Filters for High Efficiency Filters for High Efficiency Filters for High Efficiency Filters for High Efficiency
Sofilair - H10 to H14
Sofilair Green
Close Pleat - H13
Opakfil G Micretain - H10

Bag and Compact Filters,


Class F5 to F9

Summary HEPA / ULPA Filters, Class H10 to U17

Pre-Filtration, Class G3 to F5

Camfil Farr Solutions

H E PA / U L PA F i l t e r s , C l a s s H 1 0 t o U 1 7

HEPA / ULPA Filters, Class H 10 to U 1 7

European Standard EN 1822

EN1822

SOFILAIR and MEGALAM what you can


expect: 100% control of everything we
produce.
Qualified personnel responsible for testing.
Unique serial number for each filter.
Clear, unambiguous control procedures specifying test

conditions, target values and actual performance of


our filters.
Complete traceability of materials and operations.
Equipment and systems certified by accredited
bodies.
Tested performance verified by installation testing
and validation.

The CAMFIL extra:


Individual test results are recorded on a unique

product label. The label has a detachable copy which


can be used to record the position of the individual
filters within your process.
It can also be used as part of the validation process
ensuring regulatory compliance of your installation.

In short EN 1822 means:


Individually certified filters
Tested using MPPS (Most Penetrating Particle Size)

challenge.
Explicit, standardised test procedures.
Full traceability of materials and test data.
NB: the filter grades EU13 etc, are incompatible with

EN 1822.

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

44

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

All HEPA / ULPA filters produced by


Camfil are supplied fully in accordance
with the European Standard EN 1822

Advantages

Type

Application: Very high efficiency final filtration in air conditioning systems, housings and
diffusers.
Type: High air flow HEPA filter.
Frame: Galvanised steel.
Media: Glass fibre paper.
Separator: Hot-melt beads.
Sealant: Polyurethane.
Gasket: One piece half round continuous gasket.
EN 1822 efficiency: H10, H12, H13, and H14.
MPPS efficiency: H10:>85%, H12:>99.5%, H13:>99.95%, H14:> 99.995%.
Recommended final pressure drop: 600 Pa.
Maximum air flow rate: See table, use nominal values otherwise a reduction in efficiency may
occur.
Temperature: 80C maximum in continuous service.
Mounting systems: Front and side access filter frames, FC Housings, terminal housings and
safe change systems.

Dimensions
(WxHxD) mm

Model

with filter changes

Filter classification Media


EN 1822
area m 3

Air flow/preassure
drop m 3 /h/Pa

Unit
Unit
weight kg volume m 3

1575.02.00 Sofilair H10 SFR-E-2000-H10

305x610x292

H10

14

2000/230

0,06

1573.02.00 Sofilair H10 SFR-E-4000-H10

610x610x292

H10

21

4000/230

13

0,11

1570.01.00 Sofilair H10 SFR-E-5000-H10

610x610x292

H10

35

5000/230

16,5

0,11

1585.01.00 Sofilair H12 SFR-E-1500-H12

305x610x292

H12

16

1500/250

8,5

0,06

1580.01.00 Sofilair H12 SFR-E-3400-H12

610x610x292

H12

33

3400/250

16,5

0,11

1580.02.00 Sofilair H12 SFR-E-4000-H12

610x610x292

H12

40

4000/250

16,5

0,11

1568.01.00 Sofilair H13 SFR-E-1300-H13

289x595x292

H13

16

1300/250

8,5

0,06

1565.01.00 Sofilair H13 SFR-E-1500-H13

305x610x292

H13

16

1500/250

8,5

0,06

1567.01.00 Sofilair H13 SFR-E-3200-H13

595x595x292

H13

38

3200/250

15,5

0,11

1560.01.00 Sofilair H13 SFR-E-3400-H13

610x610x292

H13

33

3400/250

16,5

0,11

1560.02.00 Sofilair H13 SFR-E-4000-H13

610x610x292

H13

40

4000/250

16,5

0,11

1560.02.20 Sofilair H13 SFR-E-5000-H13

610x610x292

H13

40

5000/400

16,5

0,11

1565.01.02 Sofilair H14 SFR-E-1400-H14

610x305x292

H14

16

1400/280
1500/310*

8,5

0,06

1560.02.06 Sofilair H14 SFR-E-3500-H14

610x610x292

H14

40

3500/270
4000/310*

16,5

0,11

Carbon and Chemical Filters

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

Reference

Low pressure drop

Filter Frames and Housings

New ergonomic handle to assist

m 3 /hr
Tested in accordance with
EN 1822

*Maximum airflow

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

45

A i r F i l t e r Te c h n o l o g y

EN1822

High air flow rates, up to 5000

Bag and Compact Filters,


Class F5 to F9

Sofilair - H10 to H14

H E PA / U L PA F i l t e r s , C l a s s
H10 to U17

Filters for High Efficiency

Pre-Filtration, Class G3 to F5

Camfil Farr Solutions

H E PA / U L PA F i l t e r s , C l a s s H 1 0 t o U 1 7

HEPA / ULPA Filters, Class H 10 to U 1 7


Filters for High Efficiency

Sofilair Green
Advantages
Totally incinerable

New ergonomic handle to assist

with filter changes

High air flow rates

Corrosion resistant

Light weight construction

Unit
weight
kg

Unit
volume
m3

2000/230

0,06

5000/230

12

0,11

1500/250

10

0,06

4000/250

13,5

0,11

1500/250

0,06

4000/250

12

0,11

15

1400/280
1500/310*

0,06

38

3500/270
4000/310*

12

0,11

Model

Dimensions
(LxHxD)
mm

1575.82.00 Sofilair Green H10

SFRG-P-2000-H10

305x610x292

H10

13

1570.81.00 Sofilair Green H10

SFRG-P-5000-H10

610x610x292

H10

33

1585.81.00 Sofilair Green H12

SFRG-P-1500-H12

305x610x292

H12

15

1580.82.00 Sofilair Green H12

SFRG-P-4000-H12

610x610x292

H12

38

1565.81.00 Sofilair Green H13

SFRG-P-1500-H13

305x610x292

H13

15

1560.82.00 Sofilair Green H13

SFRG-P-4000-H13

610x610x292

H13

38

1565.81.02 Sofilair Green H14

SFRG-P-1400-H14

305x610x292

H14

1560.82.06 Sofilair Green H14

SFRG-P-3500-H14

610x610x292

H14

Reference

Type

Filter
Media area
classification
m2
EN 1822

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

46

Airflow/pressure
drop m 3 /h/Pa

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

EN1822

Application: High efficiency final filtration in air conditioning systems, extraction from corrosive
or hazardous environments.
Type: High air flow incinerable HEPA filter.
Frame: ABS.
Media: Glass fibre paper.
Separator: Hot-melt beads.
Sealant: Polyurethane.
Gasket: One piece half round continuous gasket.
EN 1822 efficiency: H10, H12, H13, H14.
MPPS efficiency: H10:>85%, H13:>99.95 & H14:>99.995%.
Recommended final pressure drop: 600 Pa.
Maximum air flow rate: See table, use nominal values otherwise a reduction in efficiency may
occur.
Temperature: 60C maximum in continuous service.
Mounting systems: Front and side access filter frames. Terminal housings and safe change
systems.

Camfil Farr Solutions

H E PA / U L PA F i l t e r s , C l a s s H 1 0 t o U 1 7
Filters for High Efficiency

Close Pleat - H13


Advantages

Type

Model

Dimensions
(WxHxD) mm

Unit
Filter classification Air flow/pressure drop Media area
Unit
EN 1822
m/hr/Pa
weight kg volume m 3
m2

229004A1

Steel case HEPA TREA-1000

610x610x292

H13

2700 / 250

229002A1

Steel case HEPA

TREA-450

305x610x292

H13

1350 / 250

231007A1

Steel case HEPA

MXEA-600

610x610x150

H13

1625 / 250

231004A1

Steel case HEPA

MXEA-220

305x610x150

H13

820 / 250

226001A1

MDF case HEPA TRSA-1000

610x610x292

H13

2450 / 250

226003A1

MDF case HEPA

TRSA-450

305x610x292

H13

1160 / 250

225006A1

MDF case HEPA

MXSA-600

610x610x150

H13

1475 / 250

225007A1

MDF case HEPA

MXSA-220

305x610x150

H13

690 / 250

23,5

13

0,13

11,7

0,07

13,4

12

0,07

6,7

0,04

21,4

13

0,13

10,1

0,07

12,1

12

0,07

5,7

Filter Frames and Housings

Alternative models, sizes and constructions are available.

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

47

A i r F i l t e r Te c h n o l o g y

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

Reference

Bag and Compact Filters,


Class F5 to F9

Carbon and Chemical Filters

EN1822

Application: Very high efficiency final filtration in air conditioning systems, housings, ducts and
diffusers.
Type: Close pleated very high efficiency filter.
Frame: Galvanised steel / MDF.
Gasket: Half round continuous expanded polyurethane.
Media: Pleated glass paper.
Separator: Hot melt beads.
Sealant: Polyurethane.
EN 1822 efficiency: H13.
MPPS efficiency: 99.95%.
DOP efficiency 0.3 m: 99.99%.
Recommended final pressure drop: 600 Pa.
Maximum flow rate: See table, use nominal values otherwise a reduction in efficiency may
occur.
Temperature: 70C maximum in continuous service.
Mounting systems: FCB Housings, Ducts, Diffusers, CAMSAFE.

Pre-Filtration, Class G3 to F5

Very high efficiency

Compact design concept

H E PA / U L PA F i l t e r s , C l a s s
H10 to U17

Range of standard sizes

HEPA / ULPA Filters, Class H 10 to U 1 7


Filters for High Efficiency

Opakfil G Micretain - H10


Advantages
Easy to install

Up to 4000 m 3 /hr air flow

Incinerable

Air flow /
Filter
Media pressure
drop
classification EN
2
area m
1822
m 3 /hr/Pa

Unit
weight
kg

Unit
volume
m3

1700/250

0.06

4000/250

0.11

9.0

1700/250

0.06

19.0

4000/250

0.11

Reference

Type

Model

Dimensions
(WxHxD) mm

1511.36.51

70PGHF-241212

Opakfil-G Micretain

592x287x290-01

H10

9.0

1511.35.51

70PGHF-242412

Opakfil-G Micretain

592x592x290-01

H10

19.0

1511.36.52

70PGHF-241212

Opakfil-G Micretain

592x287x290-10

H10

1511.35.52

70PGHF-242412

Opakfil-G Micretain

592x592x290-10

H10

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

48

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

Application: Final filtration in air conditioning systems, industrial processes.


Type: Very high efficiency, incinerable, compact filter.
Frame: 25 mm thick flange, polypropylene and ABS.
Gasket: Half round continuous expanded polyurethane. Position: 01- rear, 10- front.
Media: Glass fibre paper.
Separator: Hot-melt beads.
Sealant: Polyurethane.
EN 1822 efficiency: H10.
MPPS efficiency: 85%.
Recommended final pressure drop: 450 Pa.
Maximum flow rate: See table, use nominal values otherwise a reduction in efficiency may
occur.
Temperature: 70C maximum in continuous service.
Holding Frames: Front and side access housings and frames are available. Type 8, Type L and
FC housings.

Megalam MD, MX, MG


Advantages
Less pressure drop

Longer operating life

Quieter

Higher flow rate

Example: Megalam H14 / 6P6

Filter area

Maximum pressure drop


W

MX

MG

18m2

90 Pa (-25%)

70 Pa (-40%)

10m

Pressure drop 0.45 m/s (600m3/h)


EN1822

MD

120 Pa
3

900 m /h (190 Pa)

Energy

600 m /h (90 Pa)

2000 m3/h (250 Pa)

-25%

-42%

x 1.5

x 2.5

Less pressure loss

More Flow

Carbon and Chemical Filters


Filter Frames and Housings

Lower pressure drop


Higher airflow rate
More energy savings
Longer operating life

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

49

A i r F i l t e r Te c h n o l o g y

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

H E PA / U L PA F i l t e r s , C l a s s
H10 to U17

Lifespan

12.5m

Bag and Compact Filters,


Class F5 to F9

H E PA / U L PA P a n e l s

Pre-Filtration, Class G3 to F5

Camfil Farr Solutions

H E PA / U L PA F i l t e r s , C l a s s H 1 0 t o U 1 7

HEPA / ULPA Filters, Class H 10 to U 1 7


H E PA / U L PA P a n e l s

Megalam MX & MG - H14


Advantages
Low pressure drop

Longer operating life

Quiet: LW = 35dB

Individually scanned in

accordance with EN 1822

Higher flow rate

Med
Filter
classifica ia
tion EN area
1822
m2

Air flow/
Unit
pressure Unit volu
weig
drop max
me
ht kg
m 3 /h/Pa
m3

Type

Model

Dimensions
(WxHxD) mm

3440.00.20

MEGALAM MXA

3P6

305x610x90

H14

6.3

300/90

650/195

3.0

0.02

3440.00.30

MEGALAM MXA

6P6

610x610x90

H14

12.7

600/90

1300/195

6.0

0.05

3440.00.40

MEGALAM MXA

9P6

915x610x90

H14

19.1

900/90

1950/195

9.0

0.05

3440.00.50

MEGALAM MXA

12P6

1220x610x90

H14

28.3

1200/90

2500/195

12.0

0.07

3444.00.20

MEGALAM MGA

3P6

305x610x110

H14

9.8

300/70

1000/220

5.0

0.02

3444.00.30

MEGALAM MGA

6P6

610x610x110

H14

19.8

600/70

2000/220

8.0

0.04

3444.00.40

MEGALAM MGA

9P6

915x610x110

H14

27.0

900/70

3000/220

10.0

0.06

3444.00.50

MEGALAM MGA

12P6

1220x610x110

H14

36.3

1200/70

4000/220

13.0

0.08

Other dimensions available on request - Also available with laminator

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

50

Air flow/
pressure
drop m/s
m 3 /h/Pa

Reference

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

EN1822

Application: Final or return filtration for clean rooms with turbulent flow.
Type: HEPA filtering panel with seal for mechanical clamping systems.
Frame: Extruded and anodised aluminium.
Gasket: Half round continuous expanded polyurethane.
Media: Glass fibre paper.
Separator: Hot-melt beads.
Sealant: Polyurethane.
Grid: Mild steel painted grille upstream and downstream.
EN 1822 efficiency: H14.
MPPS efficiency: 99.995%.
Recommended final pressure drop: 600 Pa.
Maximum flow rate: see table, use nominal values otherwise a reduction in efficiency may
occur.
Temperature: 70C maximum in continuous service.
Test: 100% individually scanned to EN 1822.
Mounting system: Mechanical clamping structure, Terminal housing.

Camfil Farr Solutions

H E PA / U L PA F i l t e r s , C l a s s H 1 0 t o U 1 7
H E PA / U L PA P a n e l s

Megalam MD - H10 & H14


Advantages

Pre-Filtration, Class G3 to F5

Guaranteed performance

Protection via 2 grids

Reference

Type

Model

Dimensions
(WxHxD) mm

Filter
classification EN
1822

Media
area m 2

Air flow / pressure


drop at 0.45 m/s
m 3 /h/Pa

Unit
weight
kg

Unit
volume
m3

3401.61.11

MEGALAM MDM

3P6

305x610x66

H10

4.6

300/70

2.0

0.02

3401.62.08

MEGALAM MDM

6P6

610x610x66

H10

9.3

600/70

4.0

0.03

3401.63.01

MEGALAM MDM

9P6

915x610x66

H10

14.0

900/70

6.0

0.05

3401.64.07

MEGALAM MDM

12P6

1220x610x66

H10

18.5

1200/70

9.0

0.07

3423.00.10

MEGALAM MDA

3P3

305x305x66

H14

2.4

150/140

1.0

0.01

3423.00.20

MEGALAM MDA

3P6

305x610x66

H14

4.8

300/130

3.0

0.02

3423.00.30

MEGALAM MDA

6P6

610x610x66

H14

10.0

600/120

5.0

0.03

3423.00.90

MEGALAM MDA

7P6

762x610x66

H14

12.3

750/120

5.0

0.04

3423.00.40

MEGALAM MDA

9P6

915x610x66

H14

14.8

900/120

6.0

0.05

3423.00.50

MEGALAM MDA

12P6

1220x610x66

H14

19.8

1200/120

9.0

0.07

3423.00.60

MEGALAM MDA

15P6

1525x610x66

H14

24.9

1500/120

10.0

0.07

3423.01.00

MEGALAM MDA

9P7

915x762x66

H14

18.6

1125/120

7.5

0.06

3423.01.10

MEGALAM MDA

12P7

1220x762x66

H14

24.9

1500/120

10.0

0.07

3423.01.20

MEGALAM MDA

15P7

1525x762x66

H14

31.0

1875/120

12.5

0.09

3423.01.30

MEGALAM MDA

18P7

1830x762x66

H14

37.2

2250/120

12.5

0.12

3423.01.40

MEGALAM MDA

3P9

305x915x66

H14

7.4

450/120

3.0

0.03

3423.01.50

MEGALAM MDA

9P9

915x915x66

H14

22.3

1350/120

9.0

0.06

3423.01.60

MEGALAM MDA

12P9

1220x915x66

H14

30.0

1800/120

12.0

0.08

Bag and Compact Filters,


Class F5 to F9
H E PA / U L PA F i l t e r s , C l a s s
H10 to U17

Carbon and Chemical Filters

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

Filter Frames and Housings

EN1822

Application: Final or return filtration for clean rooms with turbulent flow.
Type: HEPA filtering panel with seal for mechanical clamping mounting systems.
Frame: Extruded and anodised aluminium.
Gasket: Half round continuous expanded polyurethane.
Media: Glass fibre paper.
Separator: Hot-melt beads.
Sealant: Polyurethane.
Grid: Mild steel painted grille upstream and downstream.
EN 1822 efficiency: H10 / H14.
MPPS efficiency: H10: 85%, H14: 99.995%.
DOP efficiency: H10: 95%, H14: 99.999%.
Recommended final pressure drop: 600 Pa.
Maximum flow rate: See table, use nominal values otherwise a reduction in efficiency may
occur.
Temperature: 70C maximum in continuous service.
Test: : 100% individually scanned to EN 1822.
Mounting system: Mechanical clamping structure, Terminal housings.

Other dimensions available on request

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

51

A i r F i l t e r Te c h n o l o g y

Low pressure drop

HEPA / ULPA Filters, Class H 10 to U 1 7


H E PA / U L PA P a n e l s

Megalam MD & MG - U15


Advantages
Guaranteed performance

Protection via 2 grids

100% individual scanning test

Very high efficiency

according to standard EN 1822

Filter classification Media


EN 1822
area m 2

Air flow /
pressure drop
m 3 /hr/Pa

Unit
weight
kg

Unit
volume
m3

Reference

Type

Model

Dimensions
(WxHxD) mm

3445.00.30

MEGALAM MGGS

6P6

610x610x110

U15

3418.00.10

MEGALAM MDGS

3P3

305x305x66

U15

2,8

150/140

1.0

0,01

3418.00.20

MEGALAM MDGS

3P6

305x610x66

U15

5,5

300/140

2.0

0,02

3418.00.30

MEGALAM MDGS

6P6

610x610x66

U15

11,2

600/140

4.0

0,03

3418.00.90

MEGALAM MDGS

7P6

762x610x66

U15

14

750/140

5.0

0,04

3418.00.40

MEGALAM MDGS

9P6

915x610x66

U15

16,9

900/140

6.0

0,05

3418.00.50

MEGALAM MDGS

12P6

1220x610x66

U15

22,5

1200/140

8.0

0,07

3418.00.60

MEGALAM MDGS

15P6

1525x610x66

U15

28,3

1500/140

10.0

0,07

3418.00.80

MEGALAM MDGS

3P7

305x762x66

U15

375/140

2.5

0,02

3418.01.00

MEGALAM MDGS

9P7

915x762x66

U15

21,1

1125/140

7.5

0,06

3418.01.10

MEGALAM MDGS

12P7

1220x762x66

U15

28,3

1500/140

10.0

0,07

3418.01.20

MEGALAM MDGS

15P7

1525x762x66

U15

35,3

1875/140

12.5

0,09

3418.01.40

MEGALAM MDGS

3P9

305x915x66

U15

8,3

450/140

3.0

0,03

3418.01.50

MEGALAM MDGS

9P9

915x915x66

U15

25,3

1350/140

9.0

0,06

3418.01.60

MEGALAM MDGS

12P9

1220x915x66

U15

33,9

1800/140

12.0

0,08

8.0

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

52

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

EN1822

Application: Final or return filtration for clean rooms with turbulent flow.
Type: ULPA filtering panel with seal for mechanical clamping systems.
Frame: Extruded and anodised aluminium.
Gasket: Half round continuous expanded polyurethane.
Media: Glass fibre paper.
Separator: Hot-melt beads.
Sealant: Polyurethane.
Grid: Mild steel painted grille upstream and downstream.
EN 1822 efficiency: U15.
MPPS efficiency: 99.9995%.
Recommended final pressure drop: 600 Pa.
Maximum flow rate: See table, use nominal values otherwise a reduction in efficiency may
occur.
Temperature: 70C maximum in continuous service.
Test: 100% individually scanned to EN 1822.
Mounting system: Mechanical clamping structure, Terminal housings.

Camfil Farr Solutions

H E PA / U L PA F i l t e r s , C l a s s H 1 0 t o U 1 7
H E PA / U L PA P a n e l s

Megalam (Laminator) MDL & MXL - U15 & U16

Integrated laminator screen

100% individual scanning test

ULPA U15 and U16

according to standard EN 1822

Unit weight
kg

Unit
volume
m3

16.9

900/150

6.0

0.05

16.9

900/150

6.0

0.05

U15

22.5

1200/150

8.0

0.07

U15

22.5

1200/150

8.0

0.07

915x610x66

U16

18.4

900/165

6.0

0.05

915x610x66

U16

18.4

900/165

6.0

0.05

12P6-01

1220x610x66

U16

24.5

1200/165

8.0

0.07

12P6-01

1220x610x66

U16

24.5

1200/165

8.0

0.07

MEGALAM MXLGS

6P6-01

610x610x90

U15

15.4

600/120

5.6

0.05

MEGALAM MXLGS

6P6-10

610x610x90

U15

15.4

600/120

5.6

0.05

Type

Model

Dimensions
(WxHxD) mm

3449.20.40

MEGALAM MDLGS

9P6-01

915x610x66

U15

3449.00.40

MEGALAM MDLGS

9P6-10

915x610x66

U15

3449.20.50

MEGALAM MDLGS

12P6-01

1220x610x66

3449.00.50

MEGALAM MDLGS

12P6-10

1220x610x66

3450.20.40 MEGALAM MDLSGS

9P6-01

3450.00.40 MEGALAM MDLSGS

9P6-10

3450.00.50 MEGALAM MDLSGS


3450.20.50 MEGALAM MDLSGS
3425.20.30
3425.00.30

Carbon and Chemical Filters

Air flow/pressure
drop m/h/Pa

Filter
Media
classification EN area
m
1822

Reference

Filter Frames and Housings

Other dimensions available on request

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

53

A i r F i l t e r Te c h n o l o g y

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

Bag and Compact Filters,


Class F5 to F9

EN1822

Application: Final filtration for clean rooms, clean devices and units with laminar flow.
Type: ULPA filtering panel with laminator and gasket for mechanical clamping systems.
Frame: Extruded and anodised aluminium.
Gasket: Half round continuous expanded polyurethane.
Media: Glass fibre paper.
Separator: Hot-melt beads.
Sealant: Polyurethane.
Laminator: Screen bonded downstream for laminar diffusion.
Grid: Mild steel painted grille placed upstream.
EN 1822 efficiency: U15 / U16.
MPPS efficiency: U15: 99.9995%, U16: 99.99995%.
Recommended final pressure drop: 600 Pa.
Maximum flow rate: See table, use nominal values otherwise a reduction in efficiency may
occur.
Temperature: 70C maximum in continuous service.
Test: 100% individually scanned to EN 1822.
Mounting system: Mechanical clamping structure, Terminal housings.

H E PA / U L PA F i l t e r s , C l a s s
H10 to U17

Laminarity better than +/- 20%

Pre-Filtration, Class G3 to F5

Advantages

HEPA / ULPA Filters, Class H 10 to U 1 7


H E PA / U L PA P a n e l s

Silent Hood Diffuser - H14


Advantages
H14 compact filter-diffuser for

Quiet: LW = 35 dB

clean room
Ready to install

Laminarity +/- 20%

Application: Final filtration for clean rooms.


Type: Ready to install HEPA/ULPA filter diffuser.
Frame: Extruded and anodised aluminium, galvanised steel cover.
Gasket: 10x5mm neoprene, self adhesive ready for installation.
Media: Glass fibre paper.
Separator: Hot melt beads.
Sealant: Polyurethane.
Connection: Spigot with outer dia. 315mm or 250mm depending on the model.
Grid: Downstream in painted mild steel.
EN 1822 efficiency: H14.
MPPS efficiency: 99.995%.
Recommended final pressure drop: 600 Pa.
Maximum flow rate: See table, use nominal values otherwise a reduction in efficiency may
occur.
Temperature: 70C maximum in continuous service.
Test: 100% individually scanned in accordance with EN 1822.
Mounting system: Mechanical clamping structures.

Type

Dimensions (WxHxD) Filter classification media


mm
EN 1822
area m 2

Model

Air flow/nominal
pressure drop
m/h/Pa

Unit volume
Unit
weight kg
m3

5970.00.21

Silent Hood MDSHA RF1

300x600x116/250

H14

4.2

300/140

10

0.03

5975.00.31

Silent Hood MDSHA RF1

600x600x116/315

H14

9.2

600/140

13

0.06

5975.00.41

Silent Hood

MDSHA RF

905x600x116/335

H14

14

900/140

16

0.09

5975.00.51

Silent Hood MDSHA RF1

1210x600x116/315

H14

19

1200/140

19

0.13

5975.00.20

Silent Hood MDSHA RF1

305x610x116/250

H14

4.3

300/140

10

0.03

5975.00.30

Silent Hood MDSHA RF1

610x610x116/315

H14

9.4

600/140

13

0.06

5975.00.40

Silent Hood

MDSHA RF

915x610x116/315

H14

14.6

900/140

16

0.09

5975.00.50

Silent Hood

MDSHA RF

1220x610x116/315

H14

19.5

1200/140

19

0.13

Other dimensions available on request. Available in other grades and with a laminator

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

54

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

Reference

Camfil Farr Solutions

H E PA / U L PA F i l t e r s , C l a s s H 1 0 t o U 1 7
H E PA / U L PA P a n e l s

Megalam U (Gel) - H14 & U15


Advantages

Pre-Filtration, Class G3 to F5

Reference

Type

Filter
classification
EN 1822

Dimensions
(WxHxD)mm

Media
area m

Air flow/pressure
drop m/h/Pa

Air flow /
Unit
pressure drop
max m/h/Pa volume m

Unit
weight
kg

3413.08.96

MEGALAM MDA U

H14

305x305x78

2.4

150/120

250/200

0.01

2.0

3413.08.89

MEGALAM MDA U

H14

305x610x78

4.8

300/120

300/200

0.02

4.0

3413.08.79

MEGALAM MDA U

H14

610x610x78

10.0

600/120

1000/200

0.03

6.0

3413.08.87

MEGALAM MDA U

H14

915x610x78

14.8

900/120

1500/200

0.05

8.0

3413.08.90

MEGALAM MDA U

H14

1220x610x78

19.8

1200/120

2000/200

0.06

11.0

3413.08.97

MEGALAM MDA U

H14

305x762x78

6.1

375/120

625/200

0.02

4.5

3413.08.98

MEGALAM MDA U

H14

915x762x78

18.6

1125/120

1875/200

0.05

9.0

3413.08.91

MEGALAM MDA U

H14

1220x762x78

24.9

1500/120

2500/200

0.07

13.0

3413.08.88

MEGALAM MDA U

H14

915x915x78

22.3

1350/120

2250/200

0.06

12.0

3413.08.95

MEGALAM MDA U

H14

1220x915x78

29.0

1800/120

3000/200

0.08

15.0

3413.08.82

MEGALAM MDGS U

U15

762x610x78

14.0

750/140

0.04

6.5

3413.08.81

MEGALAM MDGS U

U15

915x610x78

16.9

900/140

0.05

8.0

3413.18.02

MEGALAM MDGS U

U15

915x762x78

21.1

1125/140

0.05

9.0

3413.08.84

MEGALAM MDGS U

U15

1220x762x78

28.3

1500/140

0.07

13.0

3413.08.80

MEGALAM MDGS U

U15

915x915x78

25.3

1350/140

0.06

12.0

H E PA / U L PA F i l t e r s , C l a s s
H10 to U17

Filter Frames and Housings

Other dimensions available on request.

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

55

A i r F i l t e r Te c h n o l o g y

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

Application: Final filtration for clean rooms and housings.


Type: HEPA/ULPA filter with gel seal.
Frame: Anodized aluminium.
Gasket: PU gel.
Media: Glass fibre paper.
Separator: Hot melt beads.
Sealant: Polyurethane.
Grid: Mild steel white epoxy paint upstream and downstream.
EN 1822 efficiency: H14 and U15.
MPPS efficiency: H14 = 99.995%, U15 = 99.9995%.
Temperature: 70C maximum in continuous service.
Test: 100% individually scanned in accordance with EN 1822.

Carbon and Chemical Filters

EN1822

Can be assembled without

clamping

100% individual control

Bag and Compact Filters,


Class F5 to F9

Leaktightness by means of gel

HEPA / ULPA Filters, Class H 10 to U 1 7


H E PA / U L PA P a n e l s

Megalam T (Gel) - H14 & U15


Advantages
Compact design

100% individually scann tested

in accordance with EN 1822

Secure protection of the filter

media

Application: Gel seal filter for terminal housings and laminar flow environments.
Type: HEPA/ULPA filter with gel seal.
Frame: Extruded anodised aluminium.
Media: Glass fibre paper.
Separator: Hot-melt beads.
Sealant: Polyurethane.
Gasket: PU Gel.
EN 1822 efficiency: H14 and U15.
MPPS efficiency: H14 = 99.995%, U15 = 99.9995%.
Recommended final pressure drop: 600 Pa.
Maximum air flow rate: See table, use nominal values otherwise a reduction in efficiency may
occur.
Temperature: 70C maximum in continuous service.
Test: 100% individually scanned in accordance with EN 1822.
Mounting systems: Ceiling mounted grid systems and terminal housings.

Reference

Type

Model

Dimensions
(WxHxD)
mm

Filter classification
EN 1822

Media
area
m2

Air flow/pressure
drop m 3 /h/Pa

Unit weight
kg

Unit volume m 3

3471.x0.10

MEGALAM

MDT14 U-305x305x71-2G

305x305x71

H14

2,4

150/120

0,01

3471.x0.20

MEGALAM

MDT14 U-305x610x71-2G

305x610x71

H14

4,8

300/120

0,02

3471.x0.30

MEGALAM

MDT14 U-610x610x71-2G

610x610x71

H14

10

600/120

0,03

3471.x0.90

MEGALAM

MDT14 U-762x610x71-2G

762X610X71

H14

12,3

750/120

0,04

3471.x0.40

MEGALAM

MDT14 U-915x610x71-2G

915x610x71

H14

14,8

900/120

0,05

3471.x0.50

MEGALAM

MDT14 U-1220x610x71-2G

1220x610x71

H14

19,8

1200/120

0,06

3471.x0.80

MEGALAM

MDT14 U-305x762x71-2G

305x762x71

H14

375/120

2,5

0,02

3471.x1.00

MEGALAM

MDT14 U-915x762x71-2G

915x762x71

H14

18,6

1125/120

7,5

0,06

3471.x1.10

MEGALAM

MDT14 U-1220x762x71-2G

1220x762x71

H14

24,9

1500/120

10

0,07

3471.x1.50

MEGALAM

MDT14 U-915x915x71-2G

915x915x71

H14

22,3

1350/120

0,06

3471.x1.60

MEGALAM

MDT14 U-1220x915x71-2G

1220x915x71

H14

30

1800/120

12

0,08

3472.x0.20

MEGALAM

MDT15 U-305x610x71-2G

305x610x71

U15

5,5

300/140

0,017

3472.x0.30

MEGALAM

MDT15 U-610x610x71-2G

610x610x71

U15

11,2

600/140

0,034

3472.x0.90

MEGALAM

MDT15 U-762x610x71-2G

762X610X71

U15

14

750/140

0,042

3472.x0.40

MEGALAM

MDT15 U-915x610x71-2G

915x610x71

U15

16,9

900/140

0,051

3472.x0.50

MEGALAM

MDT15 U-1220x610x71-2G

1220x610x71

U15

22,5

1200/140

0,068

3472.x0.80

MEGALAM

MDT15 U-305x762x71-2G

305x762x71

U15

375/140

2,5

0,021

3472.x1.00

MEGALAM

MDT15 U-915x762x71-2G

915x762x71

U15

21,1

1125/140

7,5

0,064

3472.x1.10

MEGALAM

MDT15 U-1220x762x71-2G

1220x762x71

U15

28,3

1500/140

10

0,069

3472.x1.50

MEGALAM

MDT15 U-915x915x71-2G

915x915x71

U15

25,3

1200/140

0,062

Please Note:
Seal Position "01" : x = 2
Seal Position "10" : x = 3
Other dimensions available on request

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

56

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

EN1822

Laminar air flow distribution

Type

No outgassing

Application: Very high efficiency final filter for clean environments and LAF benches.
Type: ULPA filter.
Frame: Extruded anodised aluminium.
Media: e PTFE (Teflon).
Separator: Hot-melt beads.
Sealant: Polyurethane.
Gasket: Half round continuous expanded polyurethane.
EN 1822 efficiency: U15
MPPS efficiency: > 99.9995%
Maximum air flow rate: See table, use nominal values otherwise a reduction in efficiency may
occur.
Temperature: 70C maximum in continuous service.
Test: 100% individually scanned in accordance with EN 1822.
Mounting system: Ceiling mounted grid systems, terminal housings and clean devices.

Filter classification
EN 1822

Dimensions
(WxHxD)mm

Media
area m

Air flow/Preassure
drop m/h/Pa

Unit
Unit
volume m weight kg

305x610x66

4,80

300/105

0,017

2,00

1645020Z

MD15/PTFE-305610

U15

1645050B

MD15/PTFE-610610

U15

610x610x66

9,70

605/100

0,034

4,00

1645150

MD15/PTFE-1220610

U15

1220x610x66

19,50

1205/100

0,068

8,00

164550P1

MD15/PTFE-1220915

U15

1220x915x66

29,20

1810/100

0,083

12,00

164902

MX15/PTFE-305610

U15

305x610x90

6,60

300/85

0,023

2,80

164907

MX15/PTFE-610610

U15

610x610x90

13,20

605/80

0,046

5,60

1649000

MX15/PTFE-1220610

U15

1220x610x90

26,60

1205/80

0,092

11,20

16490000

MX15/PTFE-1220915

U15

1220x915x90

40,10

1810/80

0,112

16,80

Filter Frames and Housings

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

Reference

Chemical resistance

High mechanical strength

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

57

A i r F i l t e r Te c h n o l o g y

EN1822

Very high efficiency

Bag and Compact Filters,


Class F5 to F9

Advantages

H E PA / U L PA F i l t e r s , C l a s s
H10 to U17

Megalam MD & MX e-PTFE - U15

Carbon and Chemical Filters

H E PA / U L PA P a n e l s

Pre-Filtration, Class G3 to F5

Camfil Farr Solutions

H E PA / U L PA F i l t e r s , C l a s s H 1 0 t o U 1 7

HEPA / ULPA Filters, Class H 10 to U 1 7

Knowsley Road, Haslingden, Lancashire, BB4 4EG


Tel: +44 (0) 1706 238000, Fax: +44 (0) 1706 226736
www.camfilfarr.co.uk

58

As part of our continuous improvement, Camfil Farr reserve the right to change specifications without notice.

Notes

Вам также может понравиться