Академический Документы
Профессиональный Документы
Культура Документы
ATS 01
Catalogue
May
07
General contents
Soft starters
for asynchronous motors
1 Altistart 01
2 Altistart U01
Contents
1/1
Presentation
Soft starters
for asynchronous motors
Altistart 01
1
2
536594
536593
Presentation
1
The Altistart 01 soft starter operates either as a torque limiter on starting, or as a soft
start/soft stop unit for asynchronous motors.
Using the Altistart 01 starter enhances the starting performance of asynchronous
motors by allowing them to start gradually, smoothly and in a controlled manner. It
prevents mechanical shocks, which lead to wear and tear, and subsequent
maintenance work and production downtime.
The Altistart 01 limits the starting torque and current peaks on starting on machines
which do not require a high starting torque.
It is designed for the following simple applications:
b Conveyors
b Conveyor belts
b Pumps
b Fans
b Compressors
b Automatic doors and gates
b Small cranes
b Belt-driven machinery, etc.
The Altistart 01 is compact, easy to install and can be mounted side-by-side. It
complies with standards IEC/EN 60947-4-2, carries UL, CSA, C-Tick, CCC
certifications and e marking.
The Altistart 01 soft start/soft stop unit offer comprises 3 ranges:
b 1 ATS 01N1ppp soft starters
v Control one phase of the motor power supply (single phase or three phase) to limit
the starting torque
v Internal bypass relay
v Motor power ratings ranging from 0.37 kW to 11 kW
v Motor supply voltages ranging from 110 V to 480 V, 50/60 Hz. An external power
supply is required for controlling the starter.
A contactor is always required to switch off the motor.
4
5
6
7
8
Description
b Altistart 01 soft starters (ATS 01N1ppp) are equipped with:
v A potentiometer 1 for setting the starting time
v A potentiometer 2 for adjusting the start voltage threshold according to the motor
load
v Two inputs 3:
- One 24 V z input or one 110240 V a for powering the control part that
controls the motor
b Altistart 01 soft start/soft stop units (ATS 01N2ppp) are equipped with:
v A potentiometer 6 for setting the starting time
v A potentiometer 8 for setting the deceleration time
v A potentiometer 7 for adjusting the start voltage threshold according to the motor
load
v 1 green LED 4 to indicate that the unit is switched on
v 1 yellow LED 5 to indicate that the motor is powered at nominal voltage, if it
is connected to the starter
v A connector 9:
- 2 logic inputs for Run/Stop commands
- 1 logic input for the BOOST function
- 1 logic output to indicate the end of starting
- 1 relay output to indicate the motor has reached a standstill at the end of the
deceleration stage
Characteristics:
pages 1/4 and 1/5
1/2
References:
page 1/6
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/15
Presentation (continued)
Soft starters
for asynchronous motors
Altistart 01
Description (continued)
Equivalence table for contact references
ATS 01N2ppLU/QN/RT
R1A
R1C
External power supply 0 V C0M
Stop command
LI1
Run command
LI2
LI + (+ 24 V positive
Control section power
supply
logic)
BOOST
BOOST
End of starting
LO1
115 V external power
supply
Functions
Relay outputs
ATS 01N2ppLY
04
05
02
03
01 (0 V negative
logic)
06
07
ATS 01N2ppQ
04
05
02
03
01 (0 V negative
logic)
Functions
b 2-wire control
The run and stop commands are controlled by a single logic input. State 1 of logic
input LI2 controls starting and state 0 controls stopping.
ATS 01N2ppLU/QN/RT
ATS 01N2ppLY/Q
LI +
LI1
LI2
01
02
03
b 3-wire control
The run and stop commands are controlled by 2 different logic inputs.
Stopping is achieved when logic input LI1 opens (state 0).
The pulse on input LI2 is stored until input LI1 opens.
Altistart 01 control terminals
LI +
LI1
LI2
01
02
03
536537
b Starting time
Controlling the starting time means that the time of the voltage ramp applied to the
motor can be adjusted to obtain a gradual starting time, dependent on the motor load.
U
100%
Un
Voltage ramp
50%
Un
b End of starting
v Application function via logic output LO1
Soft start/soft stop units ATS 01N206pp to ATS 01N232pp are equipped with an
open collector logic output LO, which indicates the end of starting when the motor
has reached nominal speed.
v Application function via an option
For ATS 01N2ppLY/Q soft start/soft stop units, end of starting information can be
obtained by adding the option LAD 8N11 with N/O+N/C contacts.
The option can be connected easily to the bypass contactor of the electronic(s) unit
without dismantling the product.
Characteristics:
pages 1/4 and 1/5
Dimensions:
page 1/7
Initial voltage
t
200 ms
References:
page 1/6
Schemes:
pages 1/8 to 1/15
1/3
Characteristics
Soft starters
for asynchronous motors
Altistart 01
Environment characteristics
Type of starter
Conforming to standards
Electromagnetic
compatibility EMC
e marking
Product certifications
Degree of protection
Degree of pollution
Vibration resistance
Shock resistance
Relative humidity
Ambient air
temperature around
the device
Storage
Operation
C
C
IEC 61000-4-11
IEC 61000-4-12 level 3
Bear e marking in accordance with the European low voltage directives IEC/EN
60947-4-2
UL, CSA, C-Tick and CCC
B44.1-96/ASME A17.5 for starter wired to the motor delta terminal
IP 20
IP 20 on front panel
2 conforming to IEC/EN 60947-4-2
3 conforming to IEC 60664-1 and UL 508
1.5 mm peak to peak from 3 to 13 Hz,
2 gn
1 gn from 13 to 150 Hz conforming to
IEC/EN 60068-2-6
15 gn for 11 ms conforming to
8 gn for 11 ms conforming to
IEC/EN 60068-2-27
IEC/EN 60068-2-27
5...95% without condensation or dripping water, conforming to IEC/EN 60068-2-3
- 25+ 70 conforming to IEC/EN 60947-4-2
- 10+ 40 without derating,
0+ 55
up to 50C with current derating of
2% per C above 40C
1000 without derating (above this, derate 2000 without derating (above this, derate
the current by 2.2% per additional 100 m) the current by 0.5% per additional 100 m)
Operating position
Maximum permanent angle in relation to the normal vertical
mounting position
10
10
Electrical characteristics
Type of starter
Category of use
Rated operating voltage
ATS
Conforming to IEC 60947-4-2
Three-phase voltage
V
Frequency
Output voltage
Control power supply voltage
Hz
A
s
s
%
Type of starter
ATS
01N1ppFT
01N2ppLU 01N2ppQN 01N2ppRT 01N2ppLY
Ac-53b
110 - 10% to 200 - 10% to 380 - 10% to 440 - 10% to 230 - 15% to
480 + 10%
240 + 10%
415 + 10%
480 + 10%
690 + 10%
50 - 5% to 60 + 5%
Maximum 3-phase voltage equal to line supply voltage.
a 110...220 Built into the starter
a 110
10%
10%
z 24 10%
3...25
6...32
32...85
1...5
1...10
1...25
1...10
1...25
30...80% of starting torque of motor connected directly on the line supply
01N1ppFT
1
100
1
100
01N2ppQ
400
-15+ 10%
01N2ppLY,
01N2ppQ
Use
I
Starting time
Maximum number of cycles per
hour
Starting time
5
20
5
20
10
10
t
Operating cycle
Presentation:
pages 1/2 and 1/3
1/4
References:
page 1/6
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/15
1
50
5
10
10
5
1
360
12
30
Characteristics (continued)
Soft starters
for asynchronous motors
Altistart 01
Power dissipated
ATS 01N1
W
W
A
W
W
A
W
W
A
03FT
06FT
09FT
z 24 V, 25 mA,
z 24 V, 30 mA,
a 110 V, 30 mA
a 110 V, 35 mA,
a 240 V, 65 mA
a 240 V, 80 mA
4
1
1
19
31
46
15
30
45
06LU/QN/RT
09LU/QN/RT
12LU/QN/RT
4
4
4
64
94
124
30
45
60
30LY/Q
44LY/Q
72LY/Q
22
22
23
184
268
436
90
132
216
ppLU/QN/RT
24 V power supply
Max. current available 10 mA.
No short-circuit and overload protection
Logic inputs with impedance 27 k
24 V power supply (U max. 40 V)
Max. current consumption 8 mA
State 0 if U < 5 V and I < 0.2 mA
State 1 if U > 13 V and I > 0.5 mA
Open collector logic output
External 24 V power supply (min. 6 V, max. 30 V)
Max. current 200 mA
Normally open (N/O) contact
Minimum switching capacity: 10 mA for c 6 V
Max. switching capacity on inductive load
(cos = 0.5 and L/R = 20 ms): 2 A for a 250 V or
c 30 V (AC-15)
Max. operating voltage 440 V
12FT
25FT
1
61
60
22LU/QN/RT
4.5
224.5
110
85LY/Q
23
514
255
ppLY/Q
1
126
125
32LU/QN/RT
4.5
324.5
160
Operating category
AC-15: Ie 3 A, Ue 250 V,
DC-13: Ie 2 A, Ue 24 V,
Minimum switching capacity:
10 mA for c 17 V
Maximum operating voltage
250 V
LED signalling
Green LED
Starter powered up
Yellow LED
Nominal voltage reached
(1) Acceleration current complying with the maximum conditions of use (see page 1/4).
ATS
Power circuit
mm2
mm2
mm2
mm2
mm2
mm2
N.m
2.5 14 AWG
1
17 AWG
2.5 14 AWG
0.75 18 AWG
2.5 14 AWG
1
17 AWG
0.8
Cage type connector
1.510 8 AWG
1.56 10 AWG
16
10 AWG
16
10 AWG
110
8 AWG
16
10 AWG
1.92.5
Screw connector
6...25
6...25
4...25
4...16
6...35
6...25
5
mm2
mm2
mm2
mm2
mm2
mm2
2.5
1
2.5
0.75
2.5
1
0.52.5
0.51.5
0.51.5
0.51.5
0.52.5
0.51
Tightening torque
N.m
0.8
0.75...1.5
0.75...1.5
0.75...1.5
0.75...1.5
0.75...1.5
0.75...1.5
Tinned connector. Fixed
using 6 screws
0.7
Control circuit
14 AWG
17 AWG
14 AWG
18 AWG
14 AWG
17 AWG
14 AWG
16 AWG
16 AWG
16 AWG
14 AWG
17 AWG
0.5
U
3 Tn
0,85 U
2 Tn
0,6 U
Tn
Tr
N/Ns
0
0,25
Presentation:
pages 1/2 and 1/3
0,5
0,75
References:
page 1/6
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/15
1/5
References
Soft starters
for asynchronous motors
Altistart 01
DF563901
Motor
Motor power (1)
Single phase 3-phase
230 V
210 V 230 V 230 V 400 V 460 V
kW
HP
kW
HP kW
HP
Starter
Nominal
current
Reference (2)
Weight
kg
0.37
0.55
0.75
1.1
1.5
0.5
1
1.5
2
1.1
2.2
3
4
0.5
1.5
2
3
5
ATS 01N103FT
0.160
ATS 01N106FT
0.160
1.1
0.5
ATS 01N109FT
0.280
1.5
1.5
2.2
5.5
7.5
12
ATS 01N112FT
0.280
2.2
2
3
3
4
5.5
5
7.5
7.5
9
11
10
15
25
ATS 01N125FT
0.350
0.75
ATS 01N103FT
DF563902
kW
Starter
Nominal
current
A
HP
Reference (2)
Weight
kg
1/1.5
ATS 01N206LU
0.420
1.5
ATS 01N209LU
0.420
2.2/3
3/
12
ATS 01N212LU
0.420
4/5.5
5/7.5
22
ATS 01N222LU
0.560
7.5
10
32
ATS 01N232LU
0.560
ATS 01N206QN
0.420
ATS 01N209QN
0.420
5.5
12
ATS 01N212QN
0.420
7.5/11
22
ATS 01N222QN
0.560
15
32
ATS 01N232QN
0.560
2/3
ATS 01N206RT
0.420
ATS 01N209RT
0.420
7.5
12
ATS 01N212RT
0.420
10/15
22
ATS 01N222RT
0.560
20
32
ATS 01N232RT
0.560
DF563903
Starter
Nominal
current
A
32
ATS 01N230LY
kg
2.400
11
15
22
25
30
40
37
44
ATS 01N244LY
2.400
18.5
25
37
40
50
60
55
72
ATS 01N272LY
3.800
22
30
45
50
60
75
75
85
ATS 01N285LY
3.800
Reference (2)
Weight
HP
25
Starter
Nominal
current
A
44
37
40
45
50
Reference (2)
Weight
ATS 01N244Q
kg
2.400
72
ATS 01N272Q
3.800
85
ATS 01N285Q
3.800
ATS 01N230LY
(1) Standard power ratings of motors, HP power ratings indicated according to standard UL 508.
(2) For thermal protection of the motor, please use a thermal circuit-breaker GVp ME, GV3 P or
GV7 RE (see combinations pages 1/16 and 1/17).
(3) Control power supply built into the starter.
Presentation:
pages 1/2 and 1/3
1/6
Characteristics:
pages 1/4 and 1/5
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/15
Soft starters
for asynchronous motors
References (continued)
Dimensions
1
Altistart 01
References (continued)
Accessories
Description
Plate for quick mounting on DIN rail
Adaptor for mounting on 4 DZ5 MB rail
Auxiliary contact, provides information that
the motor is at full voltage
Reference
ATS 01N230LY,
ATS 01N244p
ATS 01N103FT,
ATS 01N106FT
ATS 01N2pppLY,
ATS 01N2pppQ
VY1 H4101
Weight
kg
RHZ 66
0.005
LAD 8N11
Dimensions
ATS 01N103FT, ATS 01N106FT
Screw fixing
130,7
30,2
112,8
100,4
45
(1)
145
132,5
100
124
50
52,7
22,5
(1)
Screw fixing
Screw fixing
130,7
30,2
(1)
175
154
145
124
132,5
52,7
72,2
45
(1)
162,5
112,8
30,2
45
112,8
130,7
(1)
(1)
76
Quick mounting on 5 rail (35 or 70 mm) using plate VY1 H4101 (1)
132
146
76
97
(1)
References:
page 1/7
4xM4
180
126
180
Characteristics:
pages 1/4 and 1/5
156
97
156
126
Presentation:
pages 1/2 and 1/3
242
254,5
4xM4
Schemes:
pages 1/8 to 1/15
1/7
Schemes
Soft starters
for asynchronous motors
Altistart 01
For 0.37 to 11 kW motors
a 110 V, 220 V
5/L3
3/L2
1/L1
200480 V
Q1
S1
F2
F1
KM1
3/L2
5/L3
6/T3
A1
S2
4/T2
KM1
1/L1
13
(1)
14
24 V
CL2
CL1/0
KM1
2/T1
M1
3
Note: For single-phase motors, use the ATS 01N1ppFT without connecting the 2nd phase 3/L2, 4/T2.
Wait 5 seconds after switching the soft starter off before switching it on again.
(1) A line contactor must be used in the sequence.
Compatible components (for full references, see pages 1/16 and 1/17 or refer to our catalogue: Motor starter solutions - Control and protection components.)
Code
A1
Q1
KM1
F1, F2
S1, S2
Description
Soft starter
GV2 ME circuit-breaker
LC1 ppp + LA4 DA2U
Control protection fuses
XB4 B or XB5 B pushbuttons
Function chart
Green LED
Yellow LED
Motor voltage
Presentation:
pages 1/2 and 1/3
1/8
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
Schemes (continued)
Soft starters
for asynchronous motors
Altistart 01
For 0.75 to 15 kW motors
5/L3
3/L2
Q1
5/L3
1/L1
1/L1
Q1
a 110 V, 220 V
F1
F2
F3 (1)
F3 (1)
LO1
LI +
KM3
KM2
LI1
KM2
A1
KM3
M1
3
R1A
KM2
LO1
KM3
BOOST
KM2
S2
5/L3
KM3
3/L2
LI2
S3
1/L1
COM
LI +
LI1
COM
R1C
6/T3
ATS 01N2pppp
4/T2
6/T3
4/T2
R1C
2/T1
ATS 01N2pppp
2/T1
R1A
BOOST
6/T3
5/L3
3/L2
1/L1
A1
4/T2
2/T1
S1
LI2
M1
3
Description
Soft start/soft stop unit
GV2 ME circuit-breaker
LC1 ppp + LA4 DA2U
Control protection fuses
3 fast-acting fuses
XB4 B or XB5 B pushbuttons
Presentation:
pages 1/2 and 1/3
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
1/9
Schemes (continued)
Soft starters
for asynchronous motors
Altistart 01
For 0.75 to 15 kW motors
3/L2
5/L3
6/T3
5/L3
3/L2
z 250 V max.
4/T2
2/T1
1/L1
Q1
F2
F1
Q2
KM1
R1A
S3
LO1
BOOST
5/L3
A1
3/L2
S1
S1
LI +
KM1
COM
S2
6/T3
R1C
LI2
S3
LI1
S2
4/T2
LI1
COM
6/T3
4/T2
F4
F4
LI +
ATS 01N2pppp
R1C
2-wire
control
2/T1
BOOST
R1A
LO1
6/T3
5/L3
3/L2
1/L1
A1
4/T2
2/T1
Q2
3-wire
control (1)
1/L1
F3 (2)
2/T1
S2
LI2
M1
3
M1
3
Description
Soft start/soft stop unit
GV2 ME circuit-breaker
Fuse switches
Thermal overload relay
LC1 ppp + LA4 DA2U
Control protection fuses
3 fast-acting fuses
XB4 B or XB5 B pushbuttons
Function charts
2-wire control with deceleration
Power supply
voltage
Green LED
Green LED
Logic input LI2
Logic input LI2
Logic input LI1
Relay output R1
Relay output R1
Logic output
LO1
Motor voltage
Motor voltage
10 s
10 s
Yellow LED
Yellow LED
Presentation:
pages 1/2 and 1/3
1/10
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
Schemes (continued)
Soft starters
for asynchronous motors
Altistart 01
For 0.75 to 15 kW motors
5/L3
6/T3
1/L1
3/L2
4/T2
Q1
z 250 V max.
F3 (1)
F1
F2
R1A
LO1
BOOST
5/L3
A1
LI +
LI1
COM
6/T3
R1C
4/T2
ATS 01N2pppp
S2
2/T1
KM1
1/L1
2/T1
S1
3/L2
KM1
LI2
KM1
M1
3
Description
Soft start/soft stop unit
GV2 ME circuit-breaker
LC1 ppp + LA4 DA2U
Control protection fuses
3 fast-acting fuses
XB4 B or XB5 B pushbuttons
Presentation:
pages 1/2 and 1/3
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
1/11
Schemes (continued)
Soft starters
for asynchronous motors
Altistart 01
For 15 to 75 kW motors
ATS 01N2ppLY and ATS 01N2ppQ soft start/soft stop units (compatible components, see page 1/13)
Manual control without deceleration (freewheel), with GV3 and GV7 motor circuit-breakers
ATS 01N230LY to ATS 01N285LY
1/L1
3/L2
5/L3
400 V
5/L3
F2
3/L2
F1
230690 V
1/L1
115 V
Q1
Q1
F3 (1)
02
05
6/T3
5/L3
3/L2
ATS 01N2ppQ 02
4/T2
03
01
6/T3
04
4/T2
2/T1
01
2/T1
6/T3
06
07
1/L1
6/T3
5/L3
3/L2
A1
00
ATS 01N2ppLY
4/T2
05
1/L1
A1
04
4/T2
2/T1
F3 (1)
2/T1
03
F1
1/L1
F2
F2
5/L3
400 V
5/L3
3/L2
1/L1
F1
a 110 V, 220 V
230690 V
115 V
3/L2
Q1
Q1
S1
F3 (1)
F3
(1)
S1
S3
KM2
01
04
05
03
1/12
References:
page 1/6
Dimensions:
page 1/7
01
ATS 01N2ppQ 02
6/T3
02
5/L3
A1
00
3/L2
5/L3
3/L2
ATS 01N2ppLY
06
07
KM2
2/T1
05
6/T3
KM2
1/L1
A1
04
4/T2
KM3
KM3
KM3
KM2
KM3
4/T2
S2
KM2
1/L1
KM3
S2
KM2
KM2
S3
KM3
KM3
2/T1
03
Schemes (continued)
Soft starters
for asynchronous motors
Altistart 01
For 15 to 75 kW motors
5/L3
1/L1
5/L3
3/L2
F2
Q1
Q1
ATS 01N2ppLY
01
5/L3
A1
00
3/L2
5/L3
3/L2
1/L1
A1
04
04
S1
S3
02
05
01
ATS 01N2ppQ 02
6/T3
03
4/T2
2/T1
2/T1
S1
S3
S2
S2
06
07
6/T3
05
F3 (2)
(2)
4/T2
F3
1/L1
F1
1/L1
115 V
03
Compatible components (for full references, see pages 1/16 and 1/17 or refer to our catalogue: Motor starter solutions - Control and protection components.)
Code
A1
Q1
KM2, KM3
F1, F2
F3
S1, S2, S3
Description
Soft start/soft stop unit
GV3 or GV7 circuit-breaker
LC1 ppp + LA4 DA2U
Control protection fuses
3 fast-acting fuses
XB4 B or XB5 B pushbuttons
Presentation:
pages 1/2 and 1/3
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
1/13
Schemes (continued)
Soft starters
for asynchronous motors
Altistart 01
For 15 to 75 kW motors
ATS 01N2ppLY and ATS 01N2ppQ soft start/soft stop units (continued)
Automatic control with or without deceleration (freewheel), with contactor
1/L1
5/L3
F2
F1
3/L2
1/L1
115 V
5/L3
F2
F1
Q1
Q1
KM1
KM1
F4
F4
F4
F4
ATS 01N2ppLY 02
S3
05
5/L3
3/L2
ATS 01N2ppQ
S3
02
S2
S2
KM1
03
6/T3
06
07
01
01
4/T2
5/L3
3/L2
A1
04
2/T1
05
6/T3
KM1
KM1
00
S2
4/T2
S2
KM1
1/L1
KM1
A1
04
1/L1
S1
S1
2/T1
03
Compatible components (for full references, see pages 1/16 and 1/17 or refer to our catalogue: Motor starter solutions - Control and protection components.)
Code
A1
Q1
KM1
F1, F2
F4
S1, S2, S3
Description
Soft start/soft stop unit
GK1 disconnector
LC1 ppp + LA4 DA2U
Control protection fuses
LRD thermal overload relay
XB4 B or XB5 B pushbuttons
Presentation:
pages 1/2 and 1/3
Characteristics:
pages 1/4 and 1/5
1/14
References:
page 1/6
Dimensions:
page 1/7
Schemes (continued)
Soft starters
for asynchronous motors
Altistart 01
For 15 to 75 kW motors
ATS 01N2ppLY and ATS 01N2ppQ soft start/soft stop units (continued)
Automatic control without deceleration (freewheel), with a maintaining function
F1
5/L3
1/L1
F2
3/L2
5/L3
1/L1
115 V
F1
F2
Q1
Q1
F3
F3
(1)
KM1
KM1
S1
(1)
KM1
5/L3
3/L2
1/L1
5/L3
3/L2
ATS 01N2ppLY 02
01
04
ATS 01N2ppQ
S2
05
03
KM1
6/T3
KM1
01
4/T2
06
07
A1
00
2/T1
05
6/T3
KM1
4/T2
S2
2/T1
KM1
1/L1
S1
A1
04
02
03
Description
Soft starter
GV3 circuit-breaker
LC1 ppp + LA4 DA2U
Control protection fuses
3 fast-acting fuses
XB4 B or XB5 B pushbuttons
Presentation:
pages 1/2 and 1/3
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
1/15
Combinations
Soft starters
for asynchronous motors
Altistart 01
400 V power supply, type 1 coordination
Components to be combined in accordance with standards IEC 60947-1 and IEC 60947-4-2
Combine either circuit-breaker (light blue columns), contactor, starter, or switch/fuse (dark blue columns), contactor, starter
Motor
kW
M1
0.37
Starter
Class 10
Type of circuit-breaker
Telemecanique
Rating
Type of
contactor
0.98
0.55
1.5
ATS 01N103FT
GV2 ME06
1.6
0.75
ATS 01N103FT
GV2 ME07
2.5
1.1
2.5
ATS 01N103FT
GV2 ME08
ATS 01N106FT
GV2 ME08
ATS 01N106FT
GV2 ME10
6.3
6.3
ATS 01N106FT
GV2 ME14
ATS 01N109FT
GV2 ME14
ATS 01N112FT
GV2 ME16
13
13
ATS 01N125FT
GV2 ME20
17
17
ATS 01N125FT
GV2 ME21
2.2
3.5
6.5
8.4
5.5
7.5
11
14.8
18.1
11
21
I 2t
Rating
A1
Q1
ATS 01N103FT GV2 ME05
1.5
Thermal
overload relay
A2 s
Q2
LS1 D2531
DF2 CA02
265
LS1 D2531
DF2 CA02
265
LS1 D2531
DF2 CA02
265
LS1 D2531
DF2 CA04
265
LS1 D2531
DF2 CA04
265
LS1 D2531
DF2 CA06
265
LS1 D2531
DF2 CA06
265
LS1 D2531
DF2 CA08
265
LS1 D2531
DF2 CA08
265
LS1 D2531
DF2 CA12
12
265
LS1 D2531
DF2 CA12
12
265
LS1 D2531
DF2 CA12
12
610
LS1 D2531
DF2 CA12
12
610
LS1 D2531
DF2 CA16
16
610
LS1 D2531
DF2 CA16
16
610
LS1 D2531
DF2 CA20
20
6050
F4
LR2 K0306
LRD 05
LR2 K0307
LRD 06
LR2 K0308
LRD 07
LR2 K0308
LRD 08
LR2 K0308
LRD 08
LR2 K0310
LRD 08
LR2 K0310
LRD 08
LR2 K0312
LRD 10
LR2 K0312
LRD 10
LR2 K0314
LRD 12
LR2 K0314
LRD 12
LR2 K0316
LRD 14
LR2 K0316
LRD 14
LR2 K0321
LRD 16
LR2 K0321
LRD 16
LRD 21
LC1 D18
LS1 D2531
DF2 CA20
20
6050
LRD 21
21
LC1 D25
LS1 D2531
DF2 CA25
25
6050
LRD 21
21
LC1 D25
LS1 D2531
DF2 CA25
25
6050
LRD 21
ATS 01N125FT
GV2 ME22
23
LC1 D25
LS1 D2531
DF2 CA25
25
6050
LRD 22
23
LC1 D25
LS1 D2531
DF2 CA25
25
6050
LRD 22
15
28.5
32
LC1 D32
GK1 EM
DF2 EA40
40
7200
LRD 3353
18.5
35
ATS 01N244Q
GV3 P40
40
LC1 D38
GK1 EM
DF2 EA40
40
8000
LRD 3355
22
42
ATS 01N244Q
GV3 P50
50
LC1 D50
GK1 FM
DF2 FA63
63
8000
LRD 3357
30
57
ATS 01N272Q
GV3 P65
65
LC1 D65
GK1 FM
DF2 FA63
63
9000
LRD 3359
37
69
ATS 01N272Q
GV3 ME80
80
LC1 D80
GK1 FM
DF2 FA80
80
9000
LRD 3363
45
81
ATS 01N285Q
GV7 RE100
100
LC1 D95
GK1 FM
DF2 FA100
100
9000
LRD 3365
Presentation:
pages 1/2 and 1/3
1/16
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/11
Combinations (continued)
Soft starters
for asynchronous motors
Altistart 01
690 V power supply, type 1 coordination
Components to be combined in accordance with standards IEC 60947-1 and IEC 60947-4-2
Combine either circuit-breaker (light blue columns), contactor, starter, or switch/fuse (dark blue columns), contactor, starter
Motor
Starter
Class 10
kW
M1
30
33
A1
ATS 01N230LY
37
40
ATS 01N244LY
55
58
ATS 01N272LY
75
75.7
ATS 01N285LY
Type of circuit-breaker
Telemecanique
Rating
Type of
contactor
Type of switch
or switch
disconnector
(base unit)
3040
KM1
LC1 D50
Q2
GK1 EM
4865
LC1 D65
5680
60100
Am fuses
Reference
Presentation:
pages 1/2 and 1/3
Characteristics:
pages 1/4 and 1/5
Thermal
overload relay
A2 s
DF2 EA40
40
7200
F4
LRD 3355
GK1 FM
DF2 FA63
63
8000
LRD 3359
LC1 D115
GK1 FM
DF2 FA80
80
9000
LRD 3363
LC1 D150
GK1 FM
DF2 FA100
100
9000
LRD 3365
A
Q1
GV3 P40 +
GV AN11
GV3 P65 +
GV AN11
GV3 ME80 +
GV3 A01
GV7 RE100 +
GV7 AE11
I 2t
Rating
References:
page 1/6
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/11
1/17
Contents
2/1
Presentation
Soft starters
for asynchronous motors
536566
Presentation
The Altistart U01 is a soft start/soft stop unit for asynchronous motors. It is designed
primarily for combinations with TeSys U controller-starters.
The Altistart U01 is compact and easy to install. It complies with standards IEC/EN
60947-4-2, carries UL, CSA, C-Tick, CCC certifications and e marking.
4
5
6
7
8
Description
Characteristics:
pages 2/4 and 2/5
2/2
References:
page 2/6
Dimensions:
page 2/7
Schemes:
pages 2/8 to 2/11
Presentation (continued)
Soft starters
for asynchronous motors
Altistart U01 and TeSys U
b 3-wire control
The run and stop commands are controlled by 2 different logic inputs.
Stopping is achieved when logic input LI1 opens (state 0).
The pulse on input LI2 is stored until input LI1 opens.
Altistart U01 control terminals
+ 24 V
LI1
LI2
b Starting time
Controlling the starting time means that the time of the voltage ramp applied to the
motor can be adjusted to obtain a gradual starting time, dependent on the motor load.
b Voltage boost function via logic input
Activating the BOOST logic input enables the function for supplying a starting
overtorque capable of overcoming any mechanical friction.
When the input is at state 1, the function is active (input connected to the + 24 V) and
the starter applies a fixed voltage to the motor for a limited time before starting.
U
100%
Un
Voltage ramp
50%
Un
Initial voltage
t
200 ms
Application of a voltage boost equal to 100% of the nominal
motor voltage
b End of starting
v Application function for logic output LO1
ATSU 01N2ppLT soft start/soft stop units are equipped with an open collector logic
output LO, which indicates the end of starting when the motor has reached nominal
speed.
Characteristics:
pages 2/4 and 2/5
References:
page 2/6
Dimensions:
page 2/7
Schemes:
pages 2/8 to 2/11
2/3
Characteristics
Soft starters
for asynchronous motors
Altistart U01 and TeSys U
Environmental characteristics
Type of starter
Conformity to standards
ATSU 01N2ppLT
Altistart U01 electronic starters have been developed to conform to the strictest
international standards and the recommendations relating to electrical industrial
control devices (IEC, EN), in particular standard IEC/EN 60947-4-2.
Product certifications
Degree of protection
Degree of pollution
Vibration resistance
Shock resistance
Relative humidity
Ambient temperature around
the unit
Storage
Operation
C
C
m
10
Electrical characteristics
Type of starter
Category of use
Conforming to IEC 60947-4-2
Rated operating voltage
3-phase a voltage
Frequency
Output voltage
Control supply voltage
Rated operating current
Adjustable starting time
Adjustable deceleration time
Starting torque
Type of starter
ATSU
Control power supply consumption
Power dissipated
At full load at end of starting
In transient state at 5 times the
rated operating current
Type of starter
Use
I
Starting time
Starting time
Maximum number of cycles per
hour
V
Hz
A
s
s
%
W
W
ATSU 01N2ppLT
Ac-53b
200 - 10% to 480 + 10%
50 - 5% to 60 + 5%
Maximum 3-phase voltage equal to line supply voltage
24 V c, 100 mA 10%
6...32
1...10
1...10
30.... 80% of DOL motor starting torque
01N206LT
01N209LT
01N212LT
01N222LT
01N232LT
24 V c, 65 mA
24 V c, 100 mA
1.5
1.5
1.5
2.5
2.5
61.5
91.5
121.5
222.5
322.5
ATSU 01N206LT to ATSU 01N222LT
ATSU 01N232LT
1
100
1
50
5
20
10
10
t
Operating cycle
Presentation:
pages 2/2 and 2/3
2/4
References:
page 2/6
Dimensions:
page 2/7
Schemes:
pages 2/8 to 2/11
5
10
10
5
Characteristics (continued)
Soft starters
for asynchronous motors
Altistart U01 and TeSys U
24 V 10%
Isolated
Max. current 100 mA
Logic inputs with impedance 27 k; 24 V power supply (U max 40 V)
Max. current 8 mA
State 0 if U < 5 V and I < 0.2 mA
State 1 if U > 13 V and I > 0.5 mA
Open collector logic output:
External 24 V power supply (minimum 6 V, maximum 30 V)
Max. current 200 mA
Normally open (N/O) contact
Minimum switching capacity: 10 mA for 6 V c
Maximum switching capacity on inductive load (cos = 0.5 and L/R = 20 ms): 2 A for
250 V a or 30 V c (AC-15)
Maximum operating voltage 440 V
Starter powered up
Nominal voltage reached
LED signalling
Green LED
Yellow LED
1 conductor
2 conductors
1 conductor
2 conductors
1 conductor
2 conductors
mm2
mm2
mm2
mm2
mm2
mm2
N.m
1 conductor
2 conductors
1 conductor
2 conductors
1 conductor
2 conductors
mm2
mm2
mm2
mm2
mm2
mm2
N.m
Tightening torque
Control circuit
1.510
1.56
16
16
110
16
1.92.5
8 AWG
10 AWG
10 AWG
10 AWG
8 AWG
10 AWG
Screw connector
0.52.5
0.51.5
0.51.5
0.51.5
0.52.5
0.51
0.5
14 AWG
16 AWG
16 AWG
16 AWG
14 AWG
17 AWG
The diagram opposite shows the torque/speed characteristic of a cage motor in relation to the
supply voltage.
The torque varies in line with the square of the voltage at a fixed frequency. The gradual increase
in the voltage prevents the instantaneous current peak on power-up.
U
3 Tn
0,85 U
2 Tn
0,6 U
Tn
Tr
N/Ns
0
0,25
Presentation:
pages 2/2 and 2/3
0,5
0,75
References:
page 2/6
Dimensions:
page 2/7
Schemes:
pages 2/8 to 2/11
2/5
References
Soft starters
for asynchronous motors
400 V
kW
460 V
HP
Starter
Nominal
current
Reference
Weight
kg
ATSU 01N222LT
0.75
1.1
1
1.5
2
3
ATSU 01N206LT
0.340
1.5
2.2
3
1.5
ATSU 01N209LT
0.340
2.2
3
5.5
7.5
12
ATSU 01N212LT
0.340
4
5.5
5
7.5
7.5
11
10
15
22
ATSU 01N222LT
0.490
7.5
10
15
20
32
ATSU 01N232LT
0.490
Accessorie
1
Description
Reference
ATSU 01N2ppLT
VW3 G4104
DF510362
LUBp2BL
Power connector between
ATSU 01N2ppLT and
TeSys U
Weight
kg
0.020
LUCM ppBL
460 V
HP
2
3
7.5
10
15
20
ATSU 01N206LT
ATSU 01N206LT
ATSU 01N209LT
ATSU 01N209LT
ATSU 01N212LT
ATSU 01N212LT
ATSU 01N222LT
ATSU 01N222LT
ATSU 01N232LT
TeSys U
Power base
LUB 12
LUB 12
LUB 12
LUB 12
LUB 12
LUB 32
LUB 32
LUB 32
LUB 32
LUCp 05BL
LUCp 12BL
LUCp 12BL
LUCp 12BL
LUCp 12BL
LUCp 18BL
LUCp 18BL
LUCp 32BL
LUCp 32BL
(1) Standard motor power ratings, HP power ratings indicated according to standard UL 508.
(2) Depending on the configuration of the chosen TeSys U starter, replace the p with A for
standard, B for expandable, and M for multifunction.
ATSU 01N2ppLT
2/6
Soft starter
Presentation:
pages 2/2 and 2/3
Motor power
Voltage
230 V
400 V
kW/HP
kW
0.75/1
1.5
1.1/1.5
2.2/3
1.5/2
4
2.2/3
3/
5.5
4/5
7.5
5.5/7.5
11
7.5/10
15
Characteristics:
pages 2/4 and 2/5
Dimensions:
page 2/7
Schemes:
pages 2/8 to 2/11
Dimensions
Soft starters
for asynchronous motors
45
135
124
150
284
154
72,2
99
135
99
314
170
154
72,2
45
46,6
44,8
28
20
Presentation:
pages 2/2 and 2/3
Characteristics:
pages 2/4 and 2/5
References:
page 2/6
Schemes:
pages 2/8 to 2/11
2/7
Schemes
Soft starters
for asynchronous motors
3/L2
1/L1
5/L3
1/L1
Power wiring
QF1
QF1
TeSys U
CU
TeSys U
with
reversing
unit
CU
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
Tesys U
Tesys U
2/T1
4/T2
6/T3
3/L2
5/L3
6/T3
A1
2/T1
6/T3
ATSU 01N2ppLT
M1
3
4/T2
4/T2
2/T1
ATSU 01N2ppLT
1/L1
A1
M1
3
Compatible components (For full references, see pages 1/16 and 1/17 or refer to our catalogue: Motor starter solutions - Control and protection components)
Code
A1
QF1
CU
Presentation:
pages 2/2 and 2/3
2/8
Description
Soft start/soft stop unit
TeSys U controller-starter
TeSys U control unit
Characteristics:
pages 2/4 and 2/5
References:
page 2/6
Dimensions:
page 2/7
Schemes (continued)
Soft starters
for asynchronous motors
c 24 V
S1
BOOST
LI2
+ 24 V
R1C
R1A
A1
Stop
Run
S1
S2
A1
A2
QF1
ATSU 01N2ppLT
17
18
Stop
Run
LO1
+ 24 V
LI2
COM
LI1
R1C
R1A
18
LUA1 C20
BOOST
17
ATSU 01N2ppLT
LUA1 C20
A1
LI1
A1
COM
c 24 V
LO1
Without deceleration
A2
QF1
Functional diagrams
Power supply
voltage
Green LED
Power supply
voltage
Green LED
Yellow LED
Yellow LED
U1
U1
10 s
10 s
Motor voltage
Motor voltage
t1
t1
t2
c 24 V
17
ATSU 01N2ppLT
A1
14
13
+ 24 V
LI2
LI1
QF1
14
QF1
A2
A1
QF1
S1
QF1
A2
R1C
13
S2
S2
COM
18
LUA1 C20
LO1
+ 24 V
LI2
LI1
COM
R1C
R1A
18
S1
BOOST
17
ATSU 01N2ppLT
LUA1 C20
A1
BOOST
A1
R1A
c 24 V
LO1
Without deceleration
Functional diagrams
Power supply
voltage
Green LED
Power supply
voltage
Green LED
500 ms
Pushbutton S1
Pushbutton S2
U1
Yellow LED
Yellow LED
10 s
Motor voltage
10 s
Motor voltage
t1
t1
Characteristics:
pages 2/4 and 2/5
References:
page 2/6
Dimensions:
page 2/7
2/9
Schemes (continued)
Soft starters
for asynchronous motors
Run
direction 2
Run
direction 2
S2
Run
direction 1
S1
S2
Stop
S3
17
17
Stop
S3
LUA1 C20
18
18
LUA1 C20
+
c 24 V
c 24 V
LO1
BOOST
LI2
+ 24 V
LI1
COM
R1C
R1A
ATSU 01N2ppLT
To PLC
Presentation:
pages 2/2 and 2/3
2/10
Characteristics:
pages 2/4 and 2/5
References:
page 2/6
Dimensions:
page 2/7
LO1
+ 24 V
BOOST
LI2
LI1
COM
ATSU 01N2ppLT
R1C
B1
A1
B3
A3
LI2
+ 24 V
BOOST
LO1
LI1
COM
R1C
R1A
A2
Run
direction 1
S1
A1
LU2B p2BL
ATSU 01N2ppLT
B1
A1
B3
A3
LU2B p2BL
QF1
A1
R1A
QF1
A2
Without deceleration
Schemes (continued)
Soft starters
for asynchronous motors
LO1
COM
OA3
COM
OA1
c 24 V 24 V Aux.
D(B)
D(A)
Gnd
Modbus Module
LUL C031
BOOST
+ 24 V
LI2
4 5 8
LI1
COM
R1A
c 24 V 24 V Aux.
D(B)
D(A)
Gnd
LO1
COM
LO1
BOOST
+ 24 V
LI2
LU9B N11C
Pre-wired coil
ATSU 01N2ppLT
Modbus Module
LUL C031
4 5 8
13
LI1
COM
R1A
R1C
ATSU 01N2ppLT
A1
A1
R1C
A1
LO1
c 24 V
14
+
c 24 V
QF1
Function
Register
Bit
Powering down TeSys U and ATSU
704
0
Value
A2
B1
A1
Function
Register
Bit
Value
Powering up TeSys U and ATSU
Forward
704
0
1
Reverse
704
1
1
Powering down TeSys U and ATSU
Forward
704
0
0
Reverse
704
1
0
Automatic control without deceleration
Run
700
0
1
Stop forward
704
0
0
Stop reverse
704
1
0
Automatic control with deceleration (forward or reverse)
Run
700
0
1
Soft stop
700
0
0
A1: Soft start/soft stop unit
QF1: TeSys U controller-starter with reversing unit
B3
A3
LU2B p2BL
1
0
1
0
A1
OA3
COM
OA1
LO1
BOOST
+ 24 V
LI2
LI1
ASI LUFC5
A2
B1
A1
A3
B3
LU2B p2BL
c 24 V AS-Interface
LU9B N11C
+
Pre-wired coil +
c 24 V AS-Interface
c 24 V
c 24 V
Function
Bit
Value
Power-up and automatic control without deceleration
Run
D0
1
Stop
D0
0
Function
Bit
Value
Power-up and automatic control without deceleration
Run forward
D0
1
Stop
D0
0
Run reverse
D1
1
Stop
D1
0
A1: Soft start/soft stop unit
QF1: TeSys U controller-starter with reversing unit
Presentation:
pages 2/2 and 2/3
R1C
QF1
14
ASI LUFC5
COM
R1A
13
LO1
BOOST
ATSU 01N2ppLT
+ 24 V
LI2
LI1
COM
R1C
R1A
ATSU 01N2ppLT
Characteristics:
pages 2/4 and 2/5
References:
page 2/6
Dimensions:
page 2/7
2/11
A worldwide presence
Constantly available
b More than 5 000 points of sale in 190 countries.
b You can be sure to find the range of products that are right for you and which
complies fully with the standards in the country where they are used.
Technical assistance wherever you are
b Our technicians are at your disposal to assist you in finding the optimum
solution for your particular needs.
b Schneider Electric provides you with all necessary technical assistance,
throughout the world.
ART. 071789
Simply Smart !
Due to evolution of standards and equipment, the characteristics indicated in texts and images of this
document do not constitute a commitment on our part without confirmation.
Design: Schneider Electric
Photos: Schneider Electric
Printed by:
05/2007-V2.0
DIA2ED2040201EN
www.telemecanique.com