29C614E
Instructions for The Digitrip RMS 310 3-Pole and 4-Pole Trip Unit
Installation and Operation with K-Frame Series C Circuit Breakers
TABLE OF CONTENTS
Description
Page
1.0
General Information ..........................................1
1.1
Protection ..........................................................1
2.0
UL Listed Devices ..............................................2
3.0
Installation..........................................................2
3.1
Preparation ........................................................2
3.2
Four Pole Trip Unit Installation ..........................3
3.3
Ground Fault Trip Unit Installation ....................5
3.3.1 General Information ..........................................5
3.3.2 Installation..........................................................6
3.3.3 Accessory Installation with Ground ....................
Fault Trip Units ..................................................7
3.4
Three Pole (Non-Ground Fault),
Trip Unit Installation ..........................................7
3.5
Final Installation Instructions
(All Trip Units) ....................................................7
4.0
Principle of Operation ......................................10
4.1
General ............................................................10
4.2
Overload Trip ..................................................10
4.3
Short Delay/Instantaneous Trip ......................10
4.4
Ground Fault Protection ..................................10
5.0
Protection Settings ..........................................10
5.1
General ............................................................10
5.2
Short Delay Pickup Settings ............................10
5.3
Short Delay Time Settings ..............................10
5.4
Instantaneous Pickup ......................................11
5.5
Ground Fault Pickup Settings ..........................11
5.6
Ground Fault Time Settings ............................11
6.0
Testing ............................................................11
6.1
Functional Field Testing ..................................11
6.2
Performance Testing for Ground
Fault Trip Units ................................................11
6.2.1 Code Requirements ........................................11
6.2.2 Standards Requirements ................................11
6 2 3 General Test Instructions ................................11
7.0
Rating Plug ......................................................13
8.0
References ......................................................13
8.1
Series C K-Frame Molded Case
Circuit Breakers ..............................................13
8.2
Internal Accessories ......................................15
8.3
Attachment and Ground Fault
Alarm Unit Catalog Numbers ..........................15
WARNING
Page 2
I.L. 29C614E
Figure 1a Digitrip RMS 310 Trip Unit for 3-Pole KFrame Series C Circuit Breaker
Figure 1b Digitrip RMS 310 Trip Unit for 4-Pole KFrame Series C Circuit Breaker
3.0 INSTALLATION
3.1 PREPARATION (ALL TRIP UNITS)
NOTICE
Type
KESxxxxLS, LSE
KESxxxxLSI, LSIE
KESxxxxLSG
KESxxxxLSlG
NOTICE
3-pole KES trip units may be used in 4-pole circuit
breakers if the fourth pole is unprotected. A 4-pole
I.L. 29C614E
Page 3
Circuit
Breaker
Base
Shunt
Plate
Inserts
Conductor
Bar
Shunt
Plates
Conductor
Barriers
Conductor
Barriers
Base
Base
Conductors
To continue installation, proceed to the section applicable to the trip unit being installed:
NOTICE
If installing a 4-pole trip unit, remove conductor bar
from the right-hand (fourth) pole (Figure 2). Discard
the conductor but keep the retaining screw.
Make sure circuit breaker base conductors are positioned in slots in base. (See Figure 3)
Remove screws from shunt plate inserts. (See Figure 3)
NOTICE
The trip unit outer screws may be placed in the trip
unit conductor holes at this time. If preferred, a
magnetic screwdriver may be used to position the
screws when the trip unit is in the base.
Effective 2/2009
Section
3.2
3.3
3.4
NOTICE
Secondary winding connector is not polarized.
I.L. 29C614E
Page 4
Bend Tab
at Scored Line
and Break Out
Line End
Latch Bracket
Pin
Trip Unit
and Current
Sensor
Retaining
Screws
Latch
Side
Plate
Trip Unit
Retaining
Screws
Notch is
Positioned
Towards Load
End of Circuit
Breaker and
is Closer to
Base than Cover
Side
Plate
Fourth
Pole
Current
Sensor
Trip Unit
Load End
Barrier
Secondary
Winding
Connector
Barrier
Current Sensor
Retaining Screw
Place the barrier with the notch between the trip unit
and the current sensor. The notch must fit around the
secondary winding connector.
Position trip unit together with the barrier and current
sensor in the circuit breaker. (See Figure 6) Make sure
latch bracket pin is properly seated in slots in side
plates. If necessary, latch may be moved toward load
end of circuit breaker to seat trip unit.
Trip Unit
Secondary
Winding
Connector
CAUTION
Effective 2/2009
Effective 6/98
I.L. 29C614E
Page 5
1.50 AT TOP
[38,1]
.03
[0,76]
2X .280
[7,11]
THRU HOLE
.50
4X R .36
[9,14]
[12,70]
POLARITY MARKINGS
.31
[7,87]
( 2.000 )
([50,80])
.25
[6,35]
( .617 )
([15.67])
( 1.000 )
([25,40])
1.47
[37,34]
1.44
[36.58]
4X R .28
[7,11]
( 4.376 )
([111,13])
5.610
[142.49]
1/2" BOLTS
(NOT INCLUDED)
.50
12,70]
2.188
[55,58]
T/POTTING
T/CONDUCTOR
5.69 AT TOP
[144,53]
1.188
[30,18]
1.17
[29,72]
5.75 AT BASE
[146,05]
2.25
[57,15]
2.25 AT TOP
[57,15]
2.33 AT BASE
[59,18]
2.91 AT BASE
[73,91]
Effective 2/2009
NOTICE
The polarity of the sensor connections is critical.
Always observe the polarity markings on the installation drawings. The polarity markings are identified
as white dots on the transformers. To insure correct
ground fault equipment performance, conduct field
Page 6
I.L. 29C614E
tests to comply with National Electric Code requirements under Article 230-95(C). See Section 6.2 for
testing instructions.
Source
L
3.3.2 INSTALLATION
C Black
Grey
White
Neutral
Sensor
G.F. Alarm Relay
(Optional)
Yellow
Green
L1
NO
L2
NC
120
Vac
Remote
Reset Test
(Optional)
Load
CAUTION
Connector
Insert
Connector,
Then Push
Down
PC Board
To install the ground fault alarm and neutral current sensor connector printed circuit board, an accessory switch
must be installed in order to provide a support bracket. If
the auxiliary switch supplied with the trip unit will be
used, install it in the right pole of the breaker per IL
29C122.
NOTICE
See wiring instructions in Section 3.3.3 for special
restrictions on accessory wiring for ground fault
breakers.
Next, insert the four-position connector on the printed
circuit board into the receptacle in the trip unit and push
the board down onto the bracket. (See Figure 9)
View from right side of breaker
I.L. 29C614E
Page 7
Finish installation of the ground fault trip unit by following the instructions in Section 3.5.
NOTICE
See wiring instructions below for special restrictions on accessory wiring for ground fault breakers.
Then install the ground fault alarm and neutral current sensor connector printed circuit board as
described above.
CAUTION
Effective 2/2009
CAUTION
CAUTION
NOTICE
When the trip unit is installed in a new circuit breaker frame, the remaining cover mounting hard ware is
supplied in a plastic bag with the frame.
I.L. 29C614E
Page 8
Install circuit breaker cover and pan-head screws followed by thread forming screws as shown in Figure 10.
An additional label is included with each four pole trip
unit. Position the label marked Fourth Pole Protected
in the location shown in Figure 10.
!
Fourth
Pole
Protected
Label
CAUTION
NOTICE
Screw, .190-32 x 3.125 Inch, Pan Head, Cross-Recessed.
Screw, No. 8 x 1.63 Inch, Flat Head, Cross-Recessed,
Thread Forming.
En
ga
Re
Pu
ge
mo
ve
Pins
Trip
Unit
sh
-to
-Tr
ip
Rating Plug
Press Push-to-Trip button (in rating plug) to check manual tripping of the circuit breaker.
Plunger
NOTICE
Receptacles
Slot
I.L. 29C614E
Page 9
4 x IG
3 x IG
6
1x
3
2
5 x IG
2 x IG
1 x IG
5x
Time
Time
300
500
300
500
150
150
Time ms
Ground Current IG
Current In
In
D
C
6
7
400A
2
8
Short Delay Pick-up
(Multiples of Rated Current)
300
200
100
200
300
100
I
Time
Time
2x-8x
2x-8x
2x-8x
2x-8x
Current In
Effective 2/2009
Current In
I.L. 29C614E
Page 10
CAUTION
For ambient conditions above 40C and where the maximum ampere rating plug has been installed, derating of
the circuit breaker frame should be considered to avoid
exceeding a safe terminal temperature operating range.
Consult Cutler-Hammer for recommendations.
4.1 GENERAL
I.L. 29C614E
Page 11
NOTICE
These ampere values are always the same no matter
what rating plug is installed in the circuit breaker.
Available on Catalog Nos. KES3xxxLSG and LSIG.
5.6 GROUND FAULT TIME SETTINGS
Effective 2/2009
I.L. 29C614E
Page 12
Low
Voltage
Source
Low
Voltage
Source
Line Side
Line Side
L
L
Polarity
Marks
Polarity
Marks
Load Side
Load Side
Current-Limiting
Resistor
(if required)
WARNING
Current-Limiting
Resistor
(if required)
NOTICE
Since the Digitrip RMS 310 Trip Units derive their
operating power from the phase currents, and not
from the neutral current, passing current through
the neutral sensor will not properly test the ground
fault feature.
When testing the lowest Ground Fault Pick Up (GFPU)
setting, 1xIG, the indicated connections in Figure 15-4a
must be used. For single phase currents that are
20% of the sensor current rating, the trip unit will not
power up. Therefore, Ground Fault testing cannot be
performed in the usual manner.
The connections displayed in Figure 15-4a and 15-4b
effectively multiply the power up current by a factor of 3.
With this setup, two of the three currents will cancel and
the third current should cause the breaker to trip at the
lowest setting.
Effective 2/2009
I.L. 29C614E
Page 13
Low
Voltage
Source
I
Line Side
Source
L
Low
Voltage
Source
I
Polarity
Marks
Current-Limiting
Resistor
(if required)
Load Side
Current-Limiting
Resistor
(if required)
Low
Voltage
Source
Source
I
I
Current-Limiting
Resistor
(if required)
CAUTION
FIELD TESTING SHOULD BE USED FOR FUNCTIONAL TESTING AND NOT FIELD CALIBRATION OF
THE DIGITRIP RMS 310 GROUND FAULT TRIP UNIT.
ANY TEMPORARY CONNECTION MADE FOR THE
PURPOSE OF CONDUCTING TESTS SHOULD BE
RESTORED TO PROPER OPERATING CONDITIONS
BEFORE RETURNING THE BREAKER TO SERVICE.
Effective 2/2009
I.L. 29C614E
Page 14
Test Date
Circuit Breaker
Number
Results
Tested By:
For adjustable rating plugs (Table 1-2), the primary current carrying conductors used with the breaker must be
sized to correspond with the maximum setting of the rating plug, in accordance with National Electrical Code
requirements.
The Long Delay protection function of the trip unit is set
at the rating plug value (In).The Short Delay and
Instantaneous protection functions are set as a multiple
of In. The Ground Fault protection function is independent of In.
Pins
Plunger
Push-to-Trip Button
8.0 REFERENCES
8.1 SERIES C K-FRAME MOLDED CASE CIRCUIT
BREAKERS
Effective 2/2009
I.L. 29C614E
29C104
AD 29-167K
Page 15
Additional
Components
A1X3PK
A1X3RTK
AAL3RPK
AAL3RTK
GFAU
Table 1-1 Digitrip RMS 310 Trip Unit Type Catalog Numbers
Trip Unit Functions
Long
Delay
Short
Delay
4 POLE
KES3125LS
KES3250LS
KES3400LS
KES3125LSI
KES3250LSI
KES3400LSI
KES3125LSG
KES3250LSG
KES3400LSG
KES3125LSIG
KES3250LSIG
KES3400LSIG
KES4400LS
KES4250LS
KES4400LSI
KES4250LSI
KES4400LSE
KES4250LSE
KES4400LSIE
KES4250LSIE
Fixed Ampere
Rating with
Fixed Long Delay
Adjustable Ampere
Setting with Fixed
Long Delay
Adjustable Short
Delay Pick-up with
Short Delay Time
I2t Ramp
Adjustable Short
Delay Time with
Adjustable Short
Delay Pick-up, or
Adjustable
Instantaneous
Pick-up
Instant.
Fixed
Instantaneous
(Override)
Ground
Fault
Adjustable Ground
Fault Pick-up with
Adjustable Ground
Fault Time
Fourth
Pole
Protection
100% Rating
for Fourth Pole
50% Rating
for Fourth Pole
3 POLE
Effective 2/2009
I.L. 29C614E
Page 16
Table 1-2 Digitrip RMS 310 Trip Unit Trip Function and Rating Settings
Trip Function
Rating/Setting Description
Ampere Rating
Fixed at 100%
Trip Unit
Ampere Rating
125A
250A
400A
125A
70A-90A-100A-125A (In)
63A-80A-100A-125A (In)
125A-150A-200A-250A (In)
125A-160A-225A-250A (In)
200A-250A-300A-400A (In)
200A-250A-315A-400A (In)
250A-300A-350A-400A (In)
250A
400A
Instantaneous
Pick-up
Ground Fault
Pick-up
(Adjustable)
Trip Unit
Ampere Rating
Settings
400A
250A
125A
Not UL Listed
Occurs with short delay time adjustment set at I.
Eaton Corporation
Electrical Group
1000 Cherrington Parkway
Moon Township, PA 15108-4312
USA
tel: 1-800-525-2000
www.etn.ch.com
Effective 6/98 (ISI)
Style 6612C36H04
Printed in U.S.A.
Effective 2/2009
Style #6612C36H06
Printed in USA/TC