ACS550

Users Manual
ACS550-01 Drives (0.75160 kW)
ACS550-U1 Drives (1200 hp)

List of related manuals


GENERAL MANUALS
ACS550-01/U1 User's Manual (0.75160 kW) /
(1200 hp)
3AFE64804588 (3AUA0000001418) (English)
Flange Mounting Instructions
Kit, IP21 / UL type 1
Frame size Code (English)
FMK-A-R1
R1
100000982
FMK-A-R2
R2
100000984
FMK-A-R3
R3
100000986
FMK-A-R4
R4
100000988
R5
AC8-FLNGMT-R5 1
ACS800R6
AC8-FLNGMT-R6 1
PNTG01U-EN
1. Not available for ACS550-01 series

Kit, IP54 / UL type 12


FMK-B-R1
FMK-B-R2
FMK-B-R3
FMK-B-R4

Frame size
R1
R2
R3
R4

Code (English)
100000990
100000992
100000994
100000996

RPBA-01 PROFIBUS DP Adapter User's Manual


3AFE64504215 (English)
SREA-01 Ethernet Adapter User's Manual
3AUA0000042896 (English)
Typical contents
Safety
Installation
Programming/Start-up
Diagnostics
Technical data
MAINTENANCE MANUALS
Guide for Capacitor Reforming in ACS50, ACS55,
ACS150, ACS310, ACS350, ACS355, ACS550, ACH550
and R1-R4 OINT-/SINT-boards
3AFE68735190 (English)
ACS550-01 manuals

OPTION MANUALS
(delivered with optional equipment)
MFDT-01 FlashDrop User's Manual
3AFE68591074 (English)
OHDI-01 115/230 V Digital Input Module User's Manual
3AUA0000003101 (English)
OREL-01 Relay Output Extension Module User's
Manual
3AUA0000001935 (English)
OTAC-01 Users Manual Pulse Encoder Interface
Module Users Manual
3AUA0000001938 (English)
RCAN-01 CANopen Adapter User's Manual
3AFE64504231 (English)
RCNA-01 ControlNet Adapter User's Manual
3AFE64506005 (English)
RDNA-01 DeviceNet Adapter User's Manual
3AFE64504223 (English)
RECA-01 EtherCAT Adapter Module User's Manual
3AUA0000043520 (English)
REPL-01 Ethernet POWERLINK Adapter Module
User's Manual
3AUA0000052289 (English)
REPL-02 Ethernet POWERLINK Adapter Module
User's Manual
3AUA0000090411 (English)
RETA-01 Ethernet Adapter Module User's Manual
3AFE64539736 (English)
RETA-02 Ethernet Adapter Module User's Manual
3AFE68895383 (English)

CANopen is a registered trademark of CAN in Automation


e.V.
ControlNet is a trademark of ODVA.
DeviceNet is a trademark of ODVA.
DRIVECOM is a registered trademark of DRIVECOM User
Group e.V.
EtherCAT is registered trademark and patented
technology, licensed by Beckhoff Automation GmbH,
Germany.
EtherNet/IP is a trademark of ODVA.
ETHERNET POWERLINK is a trademark of Bernecker +
Rainer Industrie-ElektronikGes.m.b.H.
Modbus and Modbus/TCP are registered trademarks of
Schneider Automation Inc.
PROFIBUS, PROFIBUS DP and PROFINET IO are
registered trademarks of Profibus International.

ACS550-01/U1 Drives
0.75160 kW
1200 hp
Users Manual

3AFE64804588 (3AUA0000001418) Rev H


EN
EFFECTIVE: 2014-07-04
SUPERSEDES: 3AFE64804588 (3AUA0000001418) Rev G 2009-07-07
2014 ABB Oy. All Rights Reserved.

ACS550-01/U1 Users Manual

Safety instructions
Use of warnings and notes
There are two types of safety instructions throughout this manual:
Notes draw attention to a particular condition or fact, or give information on a
subject.
Warnings caution you about conditions which can result in serious injury or death
and/or damage to the equipment. They also tell you how to avoid the danger. The
warning symbols are used as follows:
Electricity warning warns of hazards from electricity which can cause physical
injury and/or damage to the equipment.
General warning warns about conditions, other than those caused by electricity,
which can result in physical injury and/or damage to the equipment.

General safety
WARNING! Obey these instructions. If you ignore them, injury or death, or damage
to the equipment can occur.
Use safety shoes to avoid foot injury.
Handle the drive carefully.
Beware of hot surfaces. Some parts, such as heatsinks, remain hot for a while
after disconnection of the electrical supply. See chapter Technical data on page
277.
Keep the drive in its package or protect it otherwise from dust and burr from
drilling and grinding until you install it. Protect also the installed drive against dust
and burr. Electrically conductive debris inside the drive can cause damage or
malfunction.

Electrical safety
WARNING! The ACS550 adjustable speed AC drive should ONLY be installed by a
qualified electrician.

WARNING! Even when the motor is stopped, dangerous voltage is present at the
power circuit terminals U1, V1, W1 and U2, V2, W2 and, depending on the frame
size, UDC+ and UDC-, or BRK+ and BRK-.

Safety instructions

ACS550-01/U1 Users Manual

WARNING! Dangerous voltage is present when input power is connected. After


disconnecting the supply, wait at least 5 minutes (to let the intermediate circuit
capacitors discharge) before removing the cover.

WARNING! Even when power is switched off from the input terminals of the
ACS550, there may be dangerous voltage (from external sources) on the terminals
of the relay outputs RO1RO3.

WARNING! When the control terminals of two or more drives are connected in
parallel, the auxiliary voltage for these control connections must be taken from a
single source which can either be one of the drives or an external supply.

WARNING! If you install the drive on an IT system (an ungrounded power system or
a high-resistance-grounded [over 30 ohms] power system), disconnect the internal
EMC filter, otherwise the system will be connected to ground potential through the
EMC filter capacitors. This can cause danger or damage the drive.
If you install the drive on a corner-grounded TN system, disconnect the internal EMC
filter, otherwise the system will be connected to ground potential through the EMC
filter capacitors. This will damage the drive.
Note: Disconnecting the internal EMC filter increases the conducted emission and
reduces the drive EMC compatibility considerably.
See section Disconnecting the internal EMC filter on page 27. Also see sections IT
systems on page 286 and Corner-grounded TN systems on page 285.

WARNING! Do not attempt to install or remove EM1, EM3, F1 or F2 screws while


power is applied to the drives input terminals.

Maintenance
WARNING! The ACS550-01/U1 is not field repairable. Never attempt to repair a
malfunctioning drive; contact your local ABB representative for replacement.

Safety instructions

ACS550-01/U1 Users Manual

Control of the drive and motor


WARNING! Do not control the motor with the disconnecting device (disconnecting
means); instead, use the control panel start and stop keys
and
, or
commands via the I/O board of the drive. The maximum allowed number of charging
cycles of the DC capacitors (i.e. power-ups by applying power) is five in ten minutes.

WARNING! The ACS550 will start up automatically after an input voltage interruption
if the external run command is on.

Note: For more technical information, contact your local ABB representative.

Safety instructions

Safety instructions

ACS550-01/U1 Users Manual

ACS550-01/U1 Users Manual

Table of contents
List of related manuals
Safety instructions
Use of warnings and notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control of the drive and motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5
5
5
6
7

Table of contents
Contents of this manual
Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Intended audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Installation
Installation flow chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Preparing for installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Installing the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Start-up, control with I/O and ID Run
How to start up the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
How to control the drive through the I/O interface . . . . . . . . . . . . . . . . . . . . . . 44
How to perform the ID Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Control panels
About control panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Assistant Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Basic Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

47
47
48
68

Application macros
ABB Standard macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-wire macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alternate macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Potentiometer macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hand-Auto macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PID Control macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PFC macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Torque Control macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection examples of two-wire and three-wire sensors . . . . . . . . . . . . . . . .
Connection for obtaining 010 V from analog outputs . . . . . . . . . . . . . . . . . .
User parameter sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

78
79
80
81
82
83
84
85
86
87
88

Table of contents

10

ACS550-01/U1 Users Manual

Macro default values for parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89


Parameters
Complete parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Complete parameter descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Embedded fieldbus
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical and electrical installation EFB . . . . . . . . . . . . . . . . . . . . . . . . .
Communication set-up EFB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Activate drive control functions EFB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Feedback from the drive EFB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostics EFB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus protocol technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ABB control profiles technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

203
204
204
205
207
211
212
215
224

Fieldbus adapter
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical and electrical installation FBA . . . . . . . . . . . . . . . . . . . . . . . . .
Communication set-up FBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Activate drive control functions FBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Feedback from the drive FBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostics FBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ABB Drives profile technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generic profile technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

237
239
240
241
241
244
245
248
256

Diagnostics
Diagnostic displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Correcting faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
Correcting alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266

Table of contents

Maintenance
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main fan replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Internal enclosure fan replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

271
271
272
274
275
275

Technical data
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Brake components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Losses, cooling data and noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

277
281
289
295
299
300
301

ACS550-01/U1 Users Manual

11

Dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Degrees of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Applicable standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IEC/EN 61800-3:2004 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compliance with the IEC/EN 61800-3:2004 +A1:2012 . . . . . . . . . . . . . . . . .

303
306
307
308
309
309
311
311

Index
Further information
Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . . . . . . . . . . . .
Document library on the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

325
325
325
325

Table of contents

12

Table of contents

ACS550-01/U1 Users Manual

ACS550-01/U1 Users Manual

13

Contents of this manual


Compatibility
This manual covers ACS550-01/U1 drives. The manual is compatible with the
ACS550-01/U1 drive firmware version 3.14e or later. See parameter 3301
FIRMWARE on page 155.

Intended use
The ACS550-01/U1 is a general purpose drive. The macros should only be applied
to the applications defined in the respective section.

Intended audience
This manual is intended for personnel who install, commission, operate and service
the drive. Read the manual before working on the drive. The reader is expected to
know the fundamentals of electricity, wiring, electrical components and electrical
schematic symbols.

Contents of this manual

14

Contents of this manual

ACS550-01/U1 Users Manual

ACS550-01/U1 Users Manual

15

Installation
Study these installation instructions carefully before proceeding. Failure to observe
the warnings and instructions may cause a malfunction or personal hazard.
WARNING! Before you begin read chapter Safety instructions on page 5.
Note: The installation must always be designed and made according to applicable
local laws and regulations. ABB does not assume any liability whatsoever for any
installation which breaches the local laws and/or other regulations. Furthermore, if
the recommendations given by ABB are not followed, the drive may experience
problems that the warranty does not cover.

Installation flow chart


The installation of the ACS550 adjustable speed AC drive follows the outline below.
The steps must be carried out in the order shown. At the right of each step are
references to the detailed information needed for the correct installation of the drive.
Task

See

PREPARE for installation

Preparing for installation on page 16

PREPARE the mounting location

Prepare the mounting location on page 20

REMOVE the front cover

Remove the front cover on page 21

MOUNT the drive

Mount the drive on page 22

INSTALL wiring

Wiring overview on page 23 and


Check the insulation of the assembly on page 30

CHECK installation

Check installation on page 35

REINSTALL the cover

Reinstall the cover on page 36

START-UP

How to start up the drive on page 37

Installation

16

ACS550-01/U1 Users Manual

Preparing for installation


Lifting the drive
Lift the drive only by the metal
chassis.
Unpacking the drive
1. Unpack the drive.
2. Check for any damage and
notify the shipper immediately
if damaged components are
found.

IP2040

3. Check the contents against


the order and the shipping label to verify that all parts have been received.
Drive identification
Drive labels
To determine the type of drive you are installing, refer to either:
serial number label attached on upper part of the choke plate between the
mounting holes, or
Type designation

Serial number

type designation label attached on the heat sink on the right side of the drive
cover. Two examples of the type designation label are given below.

Serial number
Type designation

Serial number

Type designation

Installation

ACS550-01/U1 Users Manual

17

The labels contain information on the Type designation (page 17), Ratings and frame
size (page 17), Serial number (page 17), degree of protection (see also Degrees of
protection on page 306) and valid markings (see also Markings on page 309).
Type designation
Use the following chart to interpret the type designation found on both the type
designation and the serial number label.
ACS550-01-08A8-4+J404+
AC, Standard Drive 550 product series
Construction (region specific)
01 = Setup and parts specific to IEC installation and compliance
U1 = Setup and parts specific to US installation and NEMA compliance
Output current rating
e.g. 08A8 = 8.8 A, see section Ratings on page 277 for details
Voltage rating
2 = 208240 V AC
4 = 380480 V AC
6 = 500600 V AC
Options
Examples of options:
B055 = IP54 / UL type 12 (no specification = IP21 / UL type 1).
UL type 12 is not available for type ACS550-01-290A-4.
0J400 = No control panel
J404 = ACS-CP-C Basic Control Panel
L511 = OREL-01 Relay output extension
K451 = RDNA-01 DeviceNet
K454 = RPBA-01 PROFIBUS DP

Ratings and frame size


The chart in section Ratings on page 277 lists technical specifications and identifies
the drives frame size significant, since some instructions in this document vary,
depending on the drives frame size. To read the ratings table, you need the Output
current rating entry from the type designation. Also, when using the ratings table,
note that the table is broken into sections based on the drives Voltage rating.
Serial number
The format of the drive serial number shown on the labels is described below.
Serial number is of format CYYWWXXXXX, where
C:
Country of manufacture
YY:
Year of manufacture
WW:
Week of manufacture; 01, 02, 03, for week 1, week 2, week 3,
XXXXX: Integer starting every week from 00001.

Installation

18

ACS550-01/U1 Users Manual

Motor compatibility
The motor, drive and supply power must be compatible:
Motor
specification

Verify

Reference

Motor type

3-phase induction motor

Nominal current

Motor value is within this


range: 0.22.0 I2hd
(I2hd = drive heavy duty
current)

Type designation label on drive, entry for


Output I2hd, or
Type designation on drive and rating table in
chapter Technical data on page 277.

Nominal frequency

10500 Hz

Voltage range

Motor is compatible with


208240 V (for ACS550-X1-XXXX-2) or
the ACS550 voltage range. 380480 V (for ACS550-X1-XXXX-4) or
500600 V (for ACS550-U1-XXXX-6)

Insulation

500600 V drives: Either


the motor complies with
NEMA MG1 Part 31, or a
du/dt filter is used between
the motor and drive.

For ACS550-U1-XXXX-6

Tools required
To install the ACS550 you need the following:
screwdrivers (as appropriate for the mounting hardware used)
wire stripper
tape measure
drill
for installations involving ACS550-U1, frame sizes R5 or R6 and IP54 / UL type
12 enclosures: punch for creating conduit mounting holes
for installations involving ACS550-U1, frame size R6: appropriate crimping tool
for power cable lugs. See section Power terminal considerations R6 frame size
on page 287.
mounting hardware: screws or nuts and bolts, four each. The type of hardware
depends on the mounting surface and the frame size. For the dimensions and
weights of the frames, see Dimensions and weights on page 303.
Frame size

Mounting hardware

R1R4

M5

#10

R5

M6

1/4 in

R6

M8

5/16 in

Suitable environment and enclosure


Confirm that the site meets the environmental requirements. To prevent damage
prior to installation, store and transport the drive according to the environmental
requirements specified for storage and transportation. See section Ambient
conditions on page 307.

Installation

ACS550-01/U1 Users Manual

19

Confirm that the enclosure is appropriate, based on the site contamination level:
IP21 / UL type 1 enclosure: The site must be free of airborne dust, corrosive
gases or liquids, and conductive contaminants such as dripping water,
condensation, carbon dust and metallic particles.
IP54 / UL type 12 enclosure: This enclosure provides protection from airborne
dust and light sprays or splashing water from all directions.
If, for some reason, an IP21 drive needs to be installed without the conduit box or
cover, or an IP54 drive without the conduit plate or hood, see the note in chapter
Technical data, page 310.
Suitable mounting location
Confirm that the mounting location meets the following constraints:
The drive must be mounted vertically on a smooth, solid surface, and in a suitable
environment as defined above. For horizontal installation, contact your local ABB
representative for more information.
The minimum space requirements for the drive are the outside dimensions (see
section Outside dimensions on page 304), plus air flow space around the drive
(see section Losses, cooling data and noise on page 301).
The distance between the motor and the drive is limited by the maximum motor
cable length. See section Motor connection specifications on page 289.
The mounting site must support the drives modest weight. See section Weight on
page 306.

Installation

20

ACS550-01/U1 Users Manual

Installing the drive


WARNING! Before installing the ACS550, ensure the input power supply to the drive
is off.
For flange mounting (mounting the drive in a cooling air duct), see the appropriate
Flange Mounting Instructions:
IP21 / UL type 1

Frame size

Kit

IP54 / UL type 12

Code (English)

Kit

Code (English)

R1

FMK-A-R1

100000982

FMK-B-R1

100000990

R2

FMK-A-R2

100000984

FMK-B-R2

100000992

R3

FMK-A-R3

100000986

FMK-B-R3

100000994

R4

FMK-A-R4

100000988

FMK-B-R4

100000996

R5
R6

AC8-FLNGMT-R5

AC8-FLNGMT-R6

ACS800-PNTG01U- EN
-

1. Not available in ACS550-01 series.

Prepare the mounting location


The ACS550 should only be mounted where all of the
requirements defined in section Preparing for installation
on page 16 are met.
1. Mark the position of the mounting holes with the help of
the mounting template provided with the drive.

1
X0002

2. Drill the holes.


Note: Frame sizes R3 and R4 have four holes along the top. Use only two. If
possible, use the two outside holes (to allow room to remove the fan for
maintenance).

Note: ACS400 drives can be replaced using the original mounting holes. For R1 and
R2 frame sizes, the mounting holes are identical. For R3 and R4 frame sizes, the
inside mounting holes on the top of ACS550 drives match ACS400 mounts.

Installation

ACS550-01/U1 Users Manual

21

Remove the front cover


3

IP21 / UL type 1
1. Remove the control panel, if attached.

2. Loosen the captive screw at the top.


3. Pull near the top to remove the cover.

IP2000

IP54 / UL type 12
1. If hood is present: Remove screws
(2) holding hood in place.
2. If hood is present: Slide hood up and
off of the cover.

R1R5

R6
1

3. Loosen the captive screws around


the edge of the cover.
4. Remove the cover.
3

4
FM

Installation

22

ACS550-01/U1 Users Manual

Mount the drive

IP21 / UL type 1
1. Position the ACS550 onto the mounting screws or
bolts and securely tighten in all four corners.
Note: Lift the ACS550 by its metal chassis (frame
size R6 by the lifting holes on both sides at the top).

2. Non-English speaking locations: Add a warning


sticker in the appropriate language over the existing
warning on the top of the module.

IP2002

IP54 / UL type 12
For the IP54 / UL type 12 enclosures, rubber plugs are required in the holes
provided for access to the drive mounting slots.
1. As required for access, remove the rubber plugs.
Push plugs out from the back of the drive.
2. R5 & R6: Align the sheet metal hood (not shown) in
front of the drives top mounting holes. (Attach as
part of next step.)

1, 4

3. Position the ACS550 onto the mounting screws or


bolts and securely tighten in all four corners.
5

Note: Lift the ACS550 by its metal chassis (frame


size R6 by the lifting holes on both sides at the top).
4. Reinstall the rubber plugs.

FM

5. Non-English speaking locations: Add a warning sticker in the appropriate language


over the existing warning on the top of the module.

Installation

ACS550-01/U1 Users Manual

23

Wiring overview
Conduit/Gland kit
Wiring drives with the IP21 / UL type 1 enclosure requires a conduit/gland kit with the
following items:
conduit/gland box
five (5) cable clamps (ACS550-01 only)
screws
cover.
The kit is included with IP21 / UL type 1 enclosures.
Wiring requirements
WARNING! Ensure the motor is compatible for use with the ACS550. The drive must
be installed by a competent person in accordance with the considerations defined in
section Preparing for installation on page 16. If in doubt, contact your local ABB
representative.
As you install the wiring, observe the following:
There are four sets of wiring instructions one set for each combination of drive
enclosure type (IP21 / UL type and IP54 / UL type 12) and wiring type (conduit or
cable). Be sure to select the appropriate procedure.
Determine electro-magnetic compliance (EMC) requirements per local codes.
See section Motor cable requirements for CE & C-Tick compliance on page 293.
In general:
Follow local codes for cable size.
Keep these four classes of wiring separated: input power wiring, motor wiring,
control/communications wiring and braking unit wiring.
When installing input power and motor wiring, refer to the following, as
appropriate:
Terminal

Description

Specifications and notes

3-phase power supply input

Input power connections on page 281

PE

Protective Ground

Ground connections on page 285

U2, V2, W2

Power output to motor

Motor connections on page 289

U1, V1,

W11

The ACS550 -x1-xxxx-2 (208240 V series) can be used with a single phase supply, if output
current is derated by 50%. For single phase supply voltage, connect power at U1 and W1.

To locate input power and motor connection terminals, see section Power
connection diagrams on page 25. For specifications on power terminals, see
section Drives power connection terminals on page 286.
For corner-grounded TN systems, see section Corner-grounded TN systems on
page 285.
For IT systems, see section IT systems on page 286.

Installation

24

ACS550-01/U1 Users Manual

For frame size R6, see section Power terminal considerations R6 frame size on
page 287 to install the appropriate cable lugs.
For drives using braking (optional), refer to the following, as appropriate:
Frame size

Terminal

Description

Braking accessory

R1, R2

BRK+, BRK-

Braking resistor

Braking resistor. See section Brake


components on page 295.

R3, R4, R5, R6

UDC+, UDC-

DC bus

Contact your ABB representative to


order either:
braking unit or
chopper and resistor

When installing control wiring, refer to the following chapters or sections, as


appropriate:

Installation

Control terminals table on page 28


Control connections on page 299
Application macros on page 77
Complete parameter descriptions on page 106
Embedded fieldbus on page 203
Fieldbus adapter on page 237.

ACS550-01/U1 Users Manual

25

Power connection diagrams


The following diagram shows the terminal layout for frame size R3, which, in
general, applies to frame sizes R1R6, except for the R5/R6 power and ground
terminals.

ON

ON

1 2

ON

J1 DIP switches for analog inputs (two types can be used)


J1
J1
AI1: (in voltage position)

Diagram shows the R3 frame.


Other frames have similar layouts.

AI2: (in current position)


Panel connector

X1 Analog inputs and outputs


(and 10 V ref. voltage output)
FlashDrop option

X1 Digital inputs

Power LED (green)


Fault LED (red)

(and 24 V aux. voltage output)


X1 Relay outputs

J2 DIP switch
for RS485 termination
J2

Optional module 1

J2

X1 Communications
(RS485)

ON
ON

off position

Frame sizes
R5/R6 differ.
See
next page.

Optional module 2

on position

Power input
(U1, V1, W1)

Power output to motor


(U2, V2, W2)
EM3

EM1

GND

PE
3AUA0000001571

Optional braking
Frame
Terminal
Brake options
size
labels
R1, R2 BRK+, BRK- Brake resistor
R3, R4 UDC+, UDC- Braking unit
Chopper and resistor

WARNING! To avoid danger, or damage to the drive, on IT systems and cornergrounded TN systems, see section Disconnecting the internal EMC filter on page 27.

Installation

26

ACS550-01/U1 Users Manual

The following diagram shows the power and ground terminal layout for frame sizes
R5 and R6end
R5

R6

F2

F1

F2

PE

GND
GND

Power input
(U1, V1, W1)

X0011

Power output to motor


(U2, V2, W2)

F1

Optional braking
Frame
Terminal
Brake options
size
labels
R5, R6 UDC+, UDC- Braking unit
Chopper and resistor

PE
Power input
(U1, V1, W1)

GND

X0013

Power output to motor


(U2, V2, W2)

WARNING! To avoid danger, or damage to the drive, on IT systems and cornergrounded TN systems, see section Disconnecting the internal EMC filter on page 27.

Installation

ACS550-01/U1 Users Manual

27

Disconnecting the internal EMC filter


On certain types of systems, you must disconnect the internal EMC filter, otherwise
the system will be connected to ground potential through the EMC filter capacitors,
which might cause danger, or damage the drive.
Note: Disconnecting the internal EMC filter increases the conducted emission and
reduces the drive EMC compatibility considerably.
The following table shows the installation rules for the EMC filter screws in order to
connect or disconnect the filter, depending on the system type and the frame size.
For more information on the different system types, see IT systems on page 286 and
Corner-grounded TN systems on page 285.
The locations of screws EM1 and EM3 are shown in the diagram on page 25. The
locations of screws F1 and F2 are shown in the diagram on page 26.
Frame
sizes
R1R3

R4
R5R6

IT systems (ungrounded
or high-resistancegrounded [> 30 ohm])

Screw

Symmetrically
grounded TN systems
(TN-S systems)

Corner-grounded
TN systems

EM1

EM31

EM1

F1

F2

EM3

x = Install the screw. (EMC filter will be connected.)


= Replace the screw with the provided polyamide screw. (EMC filter will be disconnected.)
= Remove the screw. (EMC filter will be disconnected.)
1 ACS550-U1 drives are shipped with screw EM3 already removed.

Installation

28

ACS550-01/U1 Users Manual

Control terminals table


The following provides information for connecting control wiring at X1 on the drive.
X1

Hardware description

SCR

Terminal for signal cable shield (screen). (Connected internally to chassis ground.)

AI1

Analog input channel 1, programmable. Default2 = frequency reference. Resolution


0.1%, accuracy 1%.
Two different DIP switch types can be used.

Analog I/O

AGND

Analog input circuit common (connected internally to chassis gnd. through 1 Mohm).

+10 V

Potentiometer reference source: 10 V 2%, max. 10 mA (1 kohm < R < 10 kohm).

AI2

Analog input channel 2, programmable. Default2 = not used. Resolution 0.1%,


accuracy 1%.
Two different DIP switch types can be used.

ON

ON ON

ON

J1: AI2 ON: 020 mA (Ri = 100 ohm)

Digital inputs1

ON ON

J1: AI2 OFF: 010 V (Ri = 312 kohm)

Installation

ON

J1: AI1 ON: 020 mA (Ri = 100 ohm)

ON

J1: AI1 OFF: 010 V (Ri = 312 kohm)

AGND

Analog input circuit common (connected internally to chassis gnd. through 1 Mohm).

AO1

Analog output, programmable. Default2 = frequency. 020 mA (load < 500 ohm).
Accuracy 3%.

AO2

Analog output, programmable. Default2 = current. 020 mA (load < 500 ohm).
Accuracy 3%.

AGND

Analog output circuit common (connected internally to chassis gnd. through 1 Mohm).

10 +24V

Auxiliary voltage output 24 V DC / 250 mA (reference to GND), short circuit


protected.

11

Auxiliary voltage output common (connected internally as floating).

GND

12 DCOM

Digital input common. To activate a digital input, there must be 10 V


(or -10 V) between that input and DCOM. The 24 V may be provided by the
ACS550 (X1-10) or by an external 1224 V source of either polarity.

13 DI1

Digital input 1, programmable. Default2 = start/stop.

14 DI2

Digital input 2, programmable. Default2 = fwd/rev.

15 DI3

Digital input 3, programmable. Default2 = constant speed sel (code).

16 DI4

Digital input 4, programmable. Default2 = constant speed sel (code).

17 DI5

Digital input 5, programmable. Default2 = ramp pair selection (code).

18 DI6

Digital input 6, programmable. Default2 = not used.

ACS550-01/U1 Users Manual

29

X1

Hardware description
Relay output 1, programmable. Default2 = Ready
Maximum: 250 V AC / 30 V DC, 2 A
Minimum: 500 mW (12 V, 10 mA)

19 RO1C
20 RO1A
Relay outputs

21 RO1B

Relay output 2, programmable. Default2 = Running


Maximum: 250 V AC / 30 V DC, 2 A
Minimum: 500 mW (12 V, 10 mA)

22 RO2C
23 RO2A
24 RO2B

Relay output 3, programmable. Default2 = Fault (-1)


Maximum: 250 V AC / 30 V DC, 2 A
Minimum: 500 mW (12 V, 10 mA)

25 RO3C
26 RO3A
27 RO3B

1
2

Digital input impedance 1.5 kohm. Maximum voltage for digital inputs is 30 V.
Default values depend on the macro used. Values specified are for the default macro. See chapter
Application macros on page 77.

Note: Terminals 3, 6 and 9 are at the same potential.

Note: For safety reasons the fault relay signals a fault when the ACS550 is
powered down.

WARNING! All ELV (Extra Low Voltage) circuits connected to the drive must be used
within a zone of equipotential bonding, i.e. within a zone where all simultaneously
accessible conductive parts are electrically connected to prevent hazardous voltages
appearing between them. This is accomplished by a proper factory grounding.
The terminals on the control board as well as on the optional modules attachable to
the board fulfil the Protective Extra Low Voltage (PELV) requirements stated in
EN 50178, provided that the external circuits connected to the terminals also fulfil
the requirements and the installation site is below 2000 m (6562 ft).
You can wire the digital input terminals in either a PNP or NPN configuration.
PNP connection (source)
X1

10
11
12
13
14
15
16
17
18

+24V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6

NPN connection (sink)


X1
10 +24V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6

Installation

30

ACS550-01/U1 Users Manual

Check the insulation of the assembly


Drive
Do not make any voltage tolerance or insulation resistance tests on any part of the
drive as testing can damage the drive. Every drive has been tested for insulation
between the main circuit and the chassis at the factory. Also, there are voltagelimiting circuits inside the drive which cut down the testing voltage automatically.
Supply cable
Check the insulation of the supply (input) cable according to local regulations before
connecting to the drive.
Motor and motor cable
Check the insulation of the motor and motor cable as follows:
1. Check that the motor cable is connected to the motor, and disconnected from the
drive output terminals U2, V2 and W2.
2. Measure the insulation resistance between phase
U1
conductors and between each phase conductor and
M
V1
3~
the Protective Earth conductor using a measuring
ohm
W1
PE
voltage of 1000 V DC. The insulation resistance of an
ABB motor must exceed 100 Mohm (reference value
at 25 C or 77 F). For the insulation resistance of
other motors, please consult the manufacturers instructions. Note: Moisture inside
the motor casing will reduce the insulation resistance. If moisture is suspected, dry
the motor and repeat the measurement.
Install the wiring
Wiring IP21 / UL type 1 enclosure with cables
1. Open the appropriate knockouts in the conduit/gland
box. (See section Conduit/Gland kit on page 23.)
2. Install the cable clamps for the power/motor cables.

2
1

Installation

X0004

ACS550-01/U1 Users Manual

31

3. On the input power cable, strip the sheathing back far


enough to route individual wires.
4. On the motor cable, strip the sheathing back far
enough to expose the copper wire shield so that the
shield can be twisted into a bundle (pig-tail). Keep the
bundle not longer than five times its width to minimize
noise radiation.
360 grounding under the clamp is recommended for
the motor cable to minimize noise radiation. In this
case, remove the sheathing at the cable clamp.
5. Route both cables through the clamps.
6. Strip and connect the power/motor wires and the
power ground wire to the drive terminals. See the
table on the right for tightening torques.
Note: For R6 frame size, refer to section Power
terminal considerations R6 frame size on page 287.

6
7
6

3
8

IP2001

Frame
Tightening torque
size Nm
lbft
1
R1, R2 1.4
R3
2.5
1.8
R4
5.6; PE: 2 4; PE 1.5
11
R5
15
30; PE: 6
R6
40; PE: 8

7. Connect the bundle (pig-tail) created from the motor


cable shield to the GND terminal.
8. Install conduit/gland box and tighten the cable clamps.

X0005

9. Install the cable clamp(s) for the control cable(s).


(Power/motor cables and clamps not shown in the
figure.)
9

X0006

10. Strip control cable sheathing and twist the copper


shield into a bundle (pig-tail).
11. Route control cable(s) through clamp(s) and tighten
clamp(s).

12
13

12. Connect the ground shield bundle (pig-tail) for digital and
analog I/O cables at X1-1. (Ground only at the drive end.)
13. Strip and connect the individual control wires to the
drive terminals. See section Control terminals table
on page 28. Use a tightening torque of 0.4 Nm
(0.3 lbft).

11

14. Install the conduit/gland box cover (1 screw).


IP2003

Installation

32

ACS550-01/U1 Users Manual

Wiring IP21 / UL type 1 enclosure with conduit


1. Open the appropriate knockouts in the conduit/gland
box. (See section Conduit/Gland kit on page 23.)
2. Install thin-wall conduit clamps (not supplied).

X0007

3. Install conduit/gland box.


4. Connect conduit runs to box.

X0005

5. Route input power and motor wiring through


conduits (must be separate conduit runs).
6. Strip wires.
7. Connect power, motor and ground wires to the drive
terminals. See the table on the right for tightening
torques.
Note: For R6 frame size, refer to section Power
terminal considerations R6 frame size on page
287.

7
5
4

IP2004

Frame
Tightening torque
size Nm
lbft
R1, R2 1.4
1
1.8
R3
2.5
R4
5.6; PE: 2 4; PE 1.5
R5
15
11
R6
40; PE: 8
30; PE: 6

8. Route the control cable through the conduit (must be


separate from input power and motor conduit runs).
9. Strip the control cable sheathing and twist the copper
shield into a bundle (pig-tail).

10
11

10. Connect the ground shield bundle (pig-tail) for digital


and analog I/O cables at X1-1. (Ground only at the
drive end.)
11. Strip and connect the individual control wires to the
drive terminals. See section Control terminals table
on page 28. Use a tightening torque of 0.4 Nm
(0.3 lbft).

12. Install the conduit/gland box cover (1 screw).


IP2005

Installation

ACS550-01/U1 Users Manual

33

Wiring IP54 / UL type 12 enclosure with cables


1. Cut the cable seals as needed for the power, motor
and control cables. The cable seals are coneshaped, rubber seals on the bottom of the drive.
The conical part of the seals must face downwards
when the seals are inserted in the lead-through
plate holes.

2. On the input power cable, strip the sheathing back


far enough to route individual wires.
3. On the motor cable, strip the sheathing back far
enough to expose the copper wire shield so that
the shield can be twisted into a bundle (pig-tail).
Keep the bundle not longer than five times its width
to minimize noise radiation.
360 grounding under the clamp is recommended
for the motor cable to minimize noise radiation. In
this case, remove the sheathing at the cable
clamp.
4. Route both cables through the clamps and tighten
the clamps.
5. Strip and connect the power/motor wires and the
power ground wire to the drive terminals. See the
table on the right for tightening torques.

IP5003

1
5
2
4

3
4

IP5004

Frame
Tightening torque
size Nm
lbft
R1, R2 1.4
1
1.8
R3
2.5
R4
5.6; PE: 2 4; PE 1.5
R5
15
11
30; PE: 6
R6
40; PE: 8

Note: For R6 frame size, refer to section Power terminal considerations R6 frame
size on page 287.
6. Connect the bundle (pig-tail) created from the
motor cable shield to the GND terminal.
7. Strip control cable sheathing and twist the copper
shield into a bundle (pig-tail).
8. Route control cable(s) through clamp(s) and
tighten clamp(s).

9, 10

9. Connect the ground shield bundle (pig-tail) for


digital and analog I/O cables at X1-1. (Ground only
at the drive end.)
10. Strip and connect the individual control wires to the
drive terminals. See section Control terminals table
on page 28. Use a tightening torque of 0.4 Nm
(0.3 lbft).

IP5005

Installation

34

ACS550-01/U1 Users Manual

Wiring IP54 / UL type 12 enclosure with conduit


1. Remove and discard the cable seals where conduit
will be installed. (The cable seals are cone-shaped,
rubber seals on the bottom of the drive.)

2. For each conduit run, install water tight conduit


connectors (not supplied).

IP5013

3. Route the power wiring through the conduit.

IP5016

4. Route the motor wiring through the conduit.


5. Strip the wires.
6. Connect the power, motor and ground wires to the
drive terminals. See the table on the right for
tightening torques.
Note: For R6 frame size, refer to section Power
terminal considerations R6 frame size on page
287.
7. Route the control cable through the conduit.

4
IP5007

Frame
Tightening torque
size Nm
lbft
1
R1, R2 1.4
R3
2.5
1.8
R4
5.6; PE: 2 4; PE 1.5
11
R5
15
R6
40; PE: 8
30; PE: 6

8. Strip the control cable sheathing and twist the


copper shield into a bundle (pig-tail).
9. Connect the ground shield bundle (pig-tail) for digital and analog I/O cables at X1-1.
(Ground only at the drive end.)
10. Strip and connect the individual control wires to the drive terminals. See section
Control terminals table on page 28. Use a tightening torque of 0.4 Nm (0.3 lbft).

Installation

ACS550-01/U1 Users Manual

35

Check installation
Before applying power, perform the following checks.
Check
Installation environment conforms to the drives specifications for ambient conditions.
The drive is mounted securely.
Space around the drive meets the drives specifications for cooling.
The motor and driven equipment are ready for start.
For IT systems and corner-grounded TN systems: The internal EMC filter is disconnected (see
section Disconnecting the internal EMC filter on page 27).
The drive is properly grounded.
The input power (mains) voltage matches the drive nominal input voltage.
The input power (mains) connections at U1, V1 and W1 are connected and tightened as
specified.
The input power (mains) fuses are installed.
The motor connections at U2, V2 and W2 are connected and tightened as specified.
The motor cable is routed away from other cables.
NO power factor compensation capacitors are in the motor cable.
The control connections are connected and tightened as specified.
NO tools or foreign objects (such as drill shavings) are inside the drive.
NO alternate power source for the motor (such as a bypass connection) is connected no
voltage is applied to the output of the drive.

Installation

36

ACS550-01/U1 Users Manual

Reinstall the cover


1

IP21 / UL type 1
1. Align the cover and slide it on.
2

2. Tighten the captive screw.


3. Reinstall the control panel.
4. Continue with start-up. See chapter Start-up,
control with I/O and ID Run on page 37.

IP2009

IP54 / UL type 12

R6

R1R5

1. Align the cover and slide it on.


2. Tighten the captive screws around
the edge of the cover.

3. Slide the hood down over the top


of the cover. (Only needed for UL
type 12 installations.)
4. Install the two screws that attach
the hood. (Only needed for UL
type 12 installations.)

5
6

5. Install the control panel.


Note: The control panel window
must be closed to comply with
IP54 / UL type 12.

1
2

FM

6. Optional: Add a lock (not supplied) to secure the control panel window.
7. Continue with start-up. See chapter Start-up, control with I/O and ID Run on page
37.

Installation

ACS550-01/U1 Users Manual

37

Start-up, control with I/O and ID Run


The chapter instructs how to:
perform the start-up
start, stop, change the direction of rotation and adjust the speed of the motor
through the I/O interface
perform an Identification Run for the drive.
Using the control panel to do these tasks is explained briefly in this chapter. For
details on how to use the control panel, refer to chapter Control panels starting on
page 47.

How to start up the drive


How you start up the drive depends on the control panel you have.
If you have an Assistant Control Panel, you can either run the Start-up
Assistant (see section How to perform the guided start-up on page 42) or perform
a limited start-up (see section How to perform the limited start-up on page 37).
The Start-up Assistant, which is included in the Assistant Control Panel only,
guides you through all essential settings to be done. In the limited start-up, the
drive gives no guidance; you go through the very basic settings by following the
instructions given in the manual.
If you have a Basic Control Panel, follow the instructions given in section How
to perform the limited start-up on page 37.
How to perform the limited start-up
For the limited start-up, you can use the Basic Control Panel or the Assistant Control
Panel. The instructions below are valid for both control panels, but the displays
shown are the Basic Control Panel displays, unless the instruction applies to the
Assistant Control Panel only.
Before you start, ensure that you have the motor nameplate data on hand.
SAFETY
The start-up may only be carried out by a qualified electrician.
The safety instructions given in chapter Safety instructions must be followed during
the start-up procedure.
The drive will start up automatically at power up, if the external run command is on.
Check the installation. See the checklist in chapter Installation, page 35.

Start-up, control with I/O and ID Run

38

ACS550-01/U1 Users Manual

Check that the starting of the motor does not cause any danger.
De-couple the driven machine if:
there is a risk of damage in case of incorrect direction of rotation, or
an ID Run needs to be performed during the drive start-up. ID Run is essential only in
applications that require the ultimate in motor control accuracy.
POWER-UP
Apply input power.
The Basic Control Panel powers up into the Output mode.

00
.

REM
OUTPUT

The Assistant Control Panel asks if you want to run the Startup Assistant. If you press EXIT , the Start-up Assistant is not
run, and you can continue with manual start-up in a similar
manner as described below for the Basic Control Panel.

Hz

FWD

CHOICE
Do you want to
use the start-up
assistant?
Yes
No
00:00
OK
EXIT

REM

MANUAL ENTRY OF START-UP DATA (Group 99: START-UP DATA)


If you have an Assistant Control Panel, select the language
(the Basic Control Panel does not support languages). See
parameter 9901 for the values of the available language
alternatives. You find parameter descriptions in section
Complete parameter descriptions starting on page 106.

REM

PAR EDIT

9901 LANGUAGE

ENGLISH

[0]
CANCEL

00:00

SAVE

The general parameter setting procedure is described below for the Basic
Control Panel. You find more detailed instructions for the Basic Control Panel
on page 73. Instructions for the Assistant Control Panel are on page 55.
The general parameter setting procedure:
1. To go to the Main menu, press
if the bottom line shows OUTPUT;
otherwise press
repeatedly until you see MENU at the bottom.
2. Press keys

until you see PAr and press

REM

rEF

MENU

REM

-01PAR

3. Find the appropriate parameter group with keys


.

and press

REM

REM

REM

FWD

2002
PAR

5. Press and hold


for about two seconds until the parameter value is
shown with SET under the value.

FWD

2001
PAR

4. Find the appropriate parameter in the group with keys

FWD

FWD

1500

rpm

1600

rpm

PAR SET FWD

6. Change the value with keys


you keep the key pressed down.

. The value changes faster while

REM

PAR SET FWD

7. Save the parameter value by pressing

REM

2002
PAR

Start-up, control with I/O and ID Run

FWD

ACS550-01/U1 Users Manual

39

Select the application macro (parameter 9902). The general


parameter setting procedure is given above.

REM

9902
PAR

The default value 1 (ABB STANDARD) is suitable in most cases.

Select the motor control mode (parameter 9904).


1 (VECTOR:SPEED) is suitable in most cases. 2 (VECTOR:TORQ) is suitable for
torque control applications. 3 (SCALAR:FREQ) is recommended

REM

FWD

9904
PAR

FWD

for multimotor drives when the number of the motors connected to the
drive is variable
when the nominal current of the motor is less than 20% of the nominal
current of the drive
when the drive is used for test purposes with no motor connected.

Enter the motor data from the motor nameplate:

ABB Motors
3

motor

V
690 Y
400 D
660 Y
380 D
415 D
440 D
Cat. no

M2AA 200 MLA 4


IEC 200 M/L 55
No
Ins.cl. F
IP 55
kW
r/min
A
cos
IA/IN t E/s
30
1475 32.5 0.83
0.83
56
1475
30
0.83
34
1470
30
30
0.83
59
1470
1475
0.83
54
30
35 1770
0.83
59

Hz
50
50
50
50
50
60
3GAA 202 001 - ADA

6312/C3

6210/C3

380 V
supply
voltage

Note: Set the motor data to


exactly the same value as on
the motor nameplate. For
example, if the motor nominal
speed is 1470 rpm on the
nameplate, setting the value of
parameter 9908 MOTOR NOM
SPEED to 1500 rpm results in the
wrong operation of the drive.

180
IEC 34-1

motor nominal voltage (parameter 9905)

REM

9905
PAR

motor nominal current (parameter 9906)


Allowed range: 0.22.0 I2hd A

motor nominal frequency (parameter 9907)

REM

9906
PAR

REM

REM

REM

FWD

9908
PAR

motor nominal power (parameter 9909)

FWD

9907
PAR

motor nominal speed (parameter 9908)

FWD

FWD

9909
PAR

FWD

Start-up, control with I/O and ID Run

40

ACS550-01/U1 Users Manual

Select the motor identification method (parameter 9910).


The default value 0 (OFF/IDMAGN) using the identification magnetization is suitable for most
applications. It is applied in this basic start-up procedure. Note however that this requires
that:
parameter 9904 is set to 1 (VECTOR:SPEED) or 2 (VECTOR:TORQ), or
parameter 9904 is set to 3 (SCALAR:FREQ) and parameter 2101 is set to 3 (SCALAR FLYST)
or 5 (FLY + BOOST).
If your selection is 0 (OFF/IDMAGN), move to the next step.
Value 1 (ON), which performs a separate ID Run, should be selected if:
vector control mode is used [parameter 9904 = 1 (VECTOR:SPEED) or 2 (VECTOR:TORQ)],
and/or
the operation point is near zero speed, and/or
operation at torque range above the motor nominal torque over a wide speed range and
without any measured speed feedback is required.
If you decide to do the ID Run [value 1 (ON)], continue by following the separate instructions
given on page 45 in section How to perform the ID Run and then return to step DIRECTION
OF THE MOTOR ROTATION on page 40.
IDENTIFICATION MAGNETIZATION WITH ID RUN SELECTION 0 (OFF/IDMAGN)
As stated above, the identification magnetization is performed only if:
parameter 9904 is set to 1 (VECTOR:SPEED) or 2 (VECTOR:TORQ), or
parameter 9904 is set to 3 (SCALAR:FREQ) and parameter 2101 is set to 3 (SCALAR FLYST)
or 5 (FLY + BOOST).
Press key LOC
REM to switch to local control (LOC shown on the left).
Press
to start the drive. The motor model is now calculated by magnetizing the motor
for 10 to 15 s at zero speed (motor not rotating).
DIRECTION OF THE MOTOR ROTATION
Check the direction of the motor rotation.
If the drive is in remote control (REM shown on the left),
switch to local control by pressing LOC
REM .
To go to the Main menu, press
if the bottom line shows
OUTPUT; otherwise press
repeatedly until you see
MENU at the bottom.
Press keys
/
until you see rEF and press
.
Increase the frequency reference from zero to a small value
.
with key
Press
to start the motor.
Check that the actual direction of the motor is the same as
indicated on the display (FWD means forward and REV
reverse).
Press
to stop the motor.

Start-up, control with I/O and ID Run

LOC

xxx
.

SET FWD

Hz

ACS550-01/U1 Users Manual

41

To change the direction of the motor rotation:


Disconnect input power from the drive, and wait 5 minutes
for the intermediate circuit capacitors to discharge. Measure
the voltage between each input terminal (U1, V1 and W1)
and earth with a multimeter to ensure that the drive is
discharged.
Exchange the position of two motor cable phase conductors
at the drive output terminals or at the motor connection box.
Verify your work by applying input power and repeating the
check as described above.

forward
direction

reverse
direction

SPEED LIMITS AND ACCELERATION/DECELERATION TIMES


Set the minimum speed (parameter 2001).

LOC

2001
PAR

Set the maximum speed (parameter 2002).

LOC

2002
PAR

Set the acceleration time 1 (parameter 2202).


Note: Check also acceleration time 2 (parameter 2205) if two
acceleration times will be used in the application.

LOC

Set the deceleration time 1 (parameter 2203).


Note: Set also deceleration time 2 (parameter 2206) if two
deceleration times will be used in the application.

LOC

FWD

FWD

2202
PAR

FWD

2203
PAR

FWD

SAVING A USER PARAMETER SET AND FINAL CHECK


The start-up is now completed. However, it might be useful at
this stage to set the parameters required by your application
and save the settings as a user parameter set as instructed in
section User parameter sets on page 88.

LOC

9902
PAR

FWD

Check that the drive state is OK.


Basic Control Panel: Check that there are no faults or alarms
shown on the display. If you want to check the LEDs on the
front of the drive, switch first to remote control (otherwise a
fault is generated) before removing the panel and verifying that
the red LED is not lit and the green LED is lit but not blinking.
Assistant Control Panel: Check that there are no faults or
alarms shown on the display and that the panel LED is green
and does not blink.
The drive is now ready for use.

Start-up, control with I/O and ID Run

42

ACS550-01/U1 Users Manual

How to perform the guided start-up


To be able to perform the guided start-up, you need the Assistant Control Panel.
Before you start, ensure that you have the motor nameplate data on hand.
SAFETY
The start-up may only be carried out by a qualified electrician.
The safety instructions given in chapter Safety instructions must be followed during
the start-up procedure.
The drive will start up automatically at power up, if the external run command is on.
Check the installation. See the checklist in chapter Installation, page 35.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if:
there is a risk of damage in case of incorrect direction of rotation, or
an ID Run needs to be performed during the drive start-up. ID Run is essential only in
applications that require the ultimate in motor control accuracy.
POWER-UP
Apply input power. The control panel first asks if you want to use
the Start-up Assistant.
Press OK (when Yes is highlighted) to run the Start-up
Assistant.
Press EXIT if you do not want to run the Start-up Assistant.

REM
CHOICE
Do you want to
use the start-up
assistant?
Yes
No
00:00
OK
EXIT

to highlight No and then press OK if you want to


Press key
make the panel ask (or not ask) the question about running the
Start-up Assistant again the next time you switch on the power to
the drive.

REM
CHOICE
Show start-up
assistant on
next boot?
Yes
No
00:00
EXIT

OK

SELECTING THE LANGUAGE


If you decided to run the Start-up Assistant, the display then asks
you to select the language. Scroll to the desired language with
keys
/
and press SAVE to accept.
If you press EXIT , the Start-up Assistant is stopped.

REM

PAR EDIT

9901 LANGUAGE

ENGLISH

[0]
EXIT

00:00

SAVE

STARTING THE GUIDED SET-UP


The Start-up Assistant now guides you through the set-up tasks,
starting with the motor set-up. Set the motor data to exactly the
same value as on the motor nameplate.
Scroll to the desired parameter value with keys
/
and
press SAVE to accept and continue with the Start-up Assistant.
Note: At any time, if you press EXIT , the Start-up Assistant is
stopped and the display goes to the Output mode.

Start-up, control with I/O and ID Run

REM

PAR EDIT

9905 MOTOR NOM VOLT

220 V

EXIT

00:00

SAVE

ACS550-01/U1 Users Manual

43

After completing a set-up task, the Start-up Assistant suggests the


next one.
Press OK (when Continue is highlighted) to continue with the
suggested task.
to highlight Skip and then press OK to move to
Press key
the following task without doing the suggested task.
Press EXIT to stop the Start-up Assistant.

REM
CHOICE
Do you want to
continue with
application setup?
Continue
Skip
00:00
OK
EXIT

SAVING A USER PARAMETER SET AND FINAL CHECK


The start-up is now completed. However, it might be useful at this
stage to set the parameters required by your application and save
the settings as a user parameter set as instructed in section User
parameter sets on page 88.
After the whole set-up is completed, check there are no faults or
alarms shown on the display and the panel LED is green and does
not blink.
The drive is now ready for use.

Start-up, control with I/O and ID Run

44

ACS550-01/U1 Users Manual

How to control the drive through the I/O interface


The table below instructs how to operate the drive through the digital and analog
inputs when:
the motor start-up is performed, and
the default (standard) parameter settings are valid.
Displays of the Basic Control Panel are shown as an example.
PRELIMINARY SETTINGS
If you need to change the direction of rotation, check that parameter
1003 is set to 3 (REQUEST).
Ensure that the control connections are wired according to the
connection diagram given for the ABB Standard macro.

See section ABB Standard


macro on page 78.

Ensure that the drive is in remote control. Press key


between remote and local control.

In remote control, the panel


display shows text REM.

LOC
REM

to switch

STARTING AND CONTROLLING THE SPEED OF THE MOTOR


Start by switching digital input DI1 on.
Assistant Control Panel: The arrow starts rotating. It is dotted until the
setpoint is reached.
Basic Control Panel: Text FWD starts flashing fast and stops after the
setpoint is reached
Regulate the drive output frequency (motor speed) by adjusting the
voltage of analog input AI1.

REM
OUTPUT

REM
OUTPUT

00
.

Hz

500
.

Hz

500
.

Hz

500
.

Hz

00
.

Hz

FWD

FWD

CHANGING THE DIRECTION OF ROTATION OF THE MOTOR


Reverse direction: Switch digital input DI2 on.

REM
OUTPUT

Forward direction: Switch digital input DI2 off.

REM
OUTPUT

REV

FWD

STOPPING THE MOTOR


Switch digital input DI1 off. The motor stops.
Assistant Control Panel: The arrow stops rotating.
Basic Control Panel: Text FWD starts flashing slowly.

Start-up, control with I/O and ID Run

REM
OUTPUT

FWD

ACS550-01/U1 Users Manual

45

How to perform the ID Run


The drive estimates motor characteristics automatically using identification
magnetization when the drive is started for the first time and after any motor
parameter (Group 99: START-UP DATA) is changed. This is valid when parameter
9910 ID RUN has value 0 (OFF/IDMAGN), and
parameter 9904 = 1 (VECTOR:SPEED) or 2 (VECTOR:TORQ), or
parameter 9904 = 3 (SCALAR:FREQ) and parameter 2101 = 3 (SCALAR FLYST) or
5 (FLY + BOOST).
In most applications there is no need to perform a separate ID Run [9910 ID RUN =
1 (ON)]. The ID Run should be selected if:
vector control mode is used [parameter 9904 = 1 (VECTOR:SPEED) or
2 (VECTOR:TORQ)], and/or
the operation point is near zero speed, and/or
operation at torque range above the motor nominal torque over a wide speed
range and without any measured speed feedback is required.
Note: If motor parameters (Group 99: START-UP DATA) are changed after the ID
Run, it must be repeated.
ID Run procedure
The general parameter setting procedure is not repeated here. For Assistant Control
Panel see page 55 and for Basic Control Panel page 73 in chapter Control panels.
PRE-CHECK
WARNING! The motor will run at up to approximately 5080% of the nominal speed
during the ID Run. The motor will rotate in the forward direction. Ensure that it is
safe to run the motor before performing the ID Run!
De-couple the motor from the driven equipment.
Check that the values of the motor data parameters 99059909 are equivalent to those on
the motor nameplate, as shown in the steps on page 39.
If parameter values (Group 01: OPERATING DATA to Group 98: OPTIONS) are changed
before the ID Run, check that the new settings meet the following conditions:
< 0 rpm

2001

MINIMUM SPEED

2002

MAXIMUM SPEED

2003

MAXIMUM CURRENT

> 80% of the motor rated speed


> I2hd

2017 MAX TORQUE 1 > 50% or 2018 MAX TORQUE 2 > 50%, depending on which limit is in
use according to parameter 2014 MAX TORQUE SEL.
Check that the Run Enable signal is on (parameter 1601).
Ensure that the panel is in local control (LOC shown on the left / at the top). Press key
switch between local and remote control.

LOC
REM

to

Start-up, control with I/O and ID Run

46

ACS550-01/U1 Users Manual

ID RUN WITH THE ASSISTANT CONTROL PANEL


Change parameter 9910 ID RUN to 1 (ON). Save the new setting
by pressing SAVE .

LOC

PAR EDIT

9910 ID RUN

ON

[1]
CANCEL

If you want to monitor actual values during the ID Run, go to


the Output mode by pressing EXIT repeatedly until you get
there.

00:00

LOC

50.0Hz

0.0 Hz
0.0 A
0.0 %
00:00

DIR

Press
to start the ID Run. The panel keeps switching
between the display that was shown when you started the ID
Run and the alarm display presented on the right.
In general, it is recommended not to press any control panel
keys during the ID Run. However, you can stop the ID Run at
any time by pressing
.

LOC

After the ID Run is completed, the alarm display is not shown


any more.
If the ID Run fails, the fault display presented on the right is
shown.

LOC

SAVE

MENU

ALARM

ALARM 2019
ID run
00:00

FAULT

FAULT 11
ID RUN FAIL
00:00

ID RUN WITH THE BASIC CONTROL PANEL


Change parameter 9910 ID RUN to 1 (ON). Save the new setting
by pressing
.

9910
1

LOC

PAR

LOC

FWD

PAR SET FWD

If you want to monitor actual values during the ID Run, go to


the Output mode by pressing
repeatedly until you get
there.

LOC

Press
to start the ID Run. The panel keeps switching
between the display that was shown when you started the ID
Run and the alarm display presented on the right.
In general, it is recommended not to press any control panel
keys during the ID Run. However, you can stop the ID Run at
any time by pressing
.

LOC

After the ID Run is completed, the alarm display is not shown


any more.
If the ID Run fails, the fault display presented on the right is
shown.

LOC

Start-up, control with I/O and ID Run

OUTPUT

00
.

FWD

A2019

FWD

F0011

FWD

Hz

ACS550-01/U1 Users Manual

47

Control panels
About control panels
Use a control panel to control the drive, read status data and adjust parameters. The
drive works with either of two different control panel types:
Basic Control Panel This panel (described in section Basic Control Panel on
page 68) provides basic tools for manual entry of parameter values.
Assistant Control Panel This panel (described below) includes pre-programmed
assistants to automate the most common parameter setups. The panel provides
language support. It is available with different language sets.

Compatibility
The manual is compatible with the following panel versions:
Basic Control Panel: ACS-CP-C Rev. M or later
Assistant Control Panel (Area 1): ACS-CP-A Rev. F or later
(new panel series manufactured since 2007 with serial number XYYWWRXXXX,
where year YY = 07 or greater and revision R = F, G, E, )
Assistant Control Panel (Asia): ACS-CP-D Rev. Q or later
See page 51 for how to find out the version of your Assistant Control Panel. See
parameter 9901 LANGUAGE to see the languages supported by the different Assistant
Control Panels.

Control panels

48

ACS550-01/U1 Users Manual

Assistant Control Panel


Features
The Assistant Control Panel features:
alphanumeric control panel with an LCD display
language selection for the display
Start-up Assistant to ease drive commissioning
copy function parameters can be copied to the control panel memory for later
transfer to other drives or for backup of a particular system.
context sensitive help
real time clock.
Overview
The following table summarizes the key functions and displays on the Assistant
Control Panel.
No. Use

1
2a LOC
LOC
2b
2c
3
7

49.1Hz
400RPM

49.RPM
1 Hz
1200
12.40A
.5 A
405
10.dm3/s
7 %

DIR
DIR

12:45
00:00

5
6

Status LED Green for normal operation. If LED is flashing, or red, see
section Diagnostic displays on page 259.

LCD display Divided into three main areas:


a. Status line variable, depending on the mode of operation, see section
Status line on page 49.
b. Center variable; in general, shows signal and parameter values, menus or
lists. Shows also faults and alarms.
c. Bottom line shows current functions of the two soft keys and, if enabled,
the clock display.

MENU
MENU

4
8
10

Soft key 1 Function depends on the context. The text in the lower left corner
of the LCD display indicates the function.

Soft key 2 Function depends on the context. The text in the lower right
corner of the LCD display indicates the function.

Up
Scrolls up through a menu or list displayed in the center of the LCD display.
Increments a value if a parameter is selected.
Increments the reference value if the upper right corner is highlighted.
Holding the key down changes the value faster.

Down
Scrolls down through a menu or list displayed in the center of the LCD
display.
Decrements a value if a parameter is selected.
Decrements the reference value if the upper right corner is highlighted.
Holding the key down changes the value faster.

LOC/REM Changes between local and remote control of the drive.

Help Displays context sensitive information when the key is pressed. The
information displayed describes the item currently highlighted in the center of
the display.

STOP Stops the drive in local control.

10 START Starts the drive in local control.

Control panels

ACS550-01/U1 Users Manual

49

Status line
The top line of the LCD display shows the basic status information of the drive.
LOC
1
No. Field
1

Control location

49.1Hz

LOC

MAIN MENU
2

1
4

Alternatives

Significance

LOC

Drive control is local, that is, from the control


panel.

REM

Drive control is remote, such as the drive I/O or


fieldbus.

State

Forward shaft direction


Reverse shaft direction

Panel operation
mode

Rotating arrow

Drive is running at setpoint.

Dotted rotating arrow

Drive is running but not at setpoint.

Stationary arrow

Drive is stopped.

Dotted stationary arrow

Start command is present, but the motor is not


running, e.g. because start enable is missing.
Name of the current mode
Name of the list or menu shown
Name of the operation state, e.g. PAR EDIT.

Reference value
or number of the
selected item

Reference value in the Output mode


Number of the highlighted item, e.g mode,
parameter group or fault.

Operation
You operate the control panel with menus and keys. The keys include two contextsensitive soft keys, whose current function is indicated by the text shown in the
display above each key.
and
You select an option, e.g. operation mode or parameter, by scrolling the
arrow keys until the option is highlighted (in reverse video) and then pressing
the relevant soft key. With the right soft key you usually enter a mode, accept an
option or save the changes. The left soft key is used to cancel the made changes
and return to the previous operation level.
The Assistant Control Panel has nine panel modes: Output, Parameters, Assistants,
Changed Parameters, Fault Logger, Time and Date, Parameter Backup, I/O Settings
and Fault. The operation in the first eight modes is described in this chapter. When a
fault or alarm occurs, the panel goes automatically to the Fault mode showing the
fault or alarm. You can reset it in the Output or Fault mode (see chapter
Diagnostics).

Control panels

50

ACS550-01/U1 Users Manual

Initially, the panel is in the Output mode, where you can


start, stop, change the direction, switch between local and
remote control, modify the reference value and monitor up
to three actual values. To do other tasks, go first to the
Main menu and select the appropriate mode on the menu.
The status line (see section Status line on page 49) shows
the name of the current menu, mode, item or state.

LOC

49.1Hz

49.1 Hz
0.5 A
10.7 %
00:00

DIR
LOC

MENU

MAIN MENU

PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT

How to do common tasks

00:00

ENTER

The table below lists common tasks, the mode in which you can perform them and
the page number where the steps to do the task are described in detail.
Task

Mode

How to get help

Any

51

How to find out the panel version

At power up

51

How to adjust the display contrast

Output

54

How to switch between local and remote control

Any

52

How to start and stop the drive

Any

52

How to change the direction of the motor rotation

Output

53

How to set the speed, frequency or torque reference

Output

54

How to change the value of a parameter

Parameters

55

How to select the monitored signals

Parameters

56

How to do guided tasks (specification of related parameter sets)


with assistants

Assistants

57

How to view and edit changed parameters

Changed Parameters

60

How to view faults

Fault Logger

61

How to reset faults and alarms

Output, Fault

265

How to show/hide the clock, change date and time formats, set the Time and Date
clock and enable/disable automatic clock transitions according to
the daylight saving changes

62

How to copy parameters from the drive to the control panel

Parameter Backup

65

How to restore parameters from the control panel to the drive

Parameter Backup

65

How to view backup information

Parameter Backup

66

How to edit and change parameter settings related to I/O terminals I/O Settings

Control panels

Page

67

ACS550-01/U1 Users Manual

51

How to get help


Step
1.

Action

Display

Press ? to read the context-sensitive help text for the item that is highlighted.

LOC
PAR GROUPS
10
01 OPERATING DATA
03 FB ACTUAL SIGNALS
04 FAULT HISTORY
10 START/STOP/DIR
11 REFERENCE SELECT
00:00
SEL
EXIT

If help text exists for the item, it is shown on the display.

LOC
HELP
This group defines
external sources
(EXT1 and EXT2) for
commands that enable
start, stop and
EXIT
00:00

2.

If the whole text is not visible, scroll the lines with keys

and

3.

After reading the text, return to the previous display by pressing

EXIT

LOC
HELP
external sources
(EXT1 and EXT2) for
commands that enable
start, stop and
direction changes.
EXIT
00:00
LOC
PAR GROUPS
10
01 OPERATING DATA
03 FB ACTUAL SIGNALS
04 FAULT HISTORY
10 START/STOP/DIR
11 REFERENCE SELECT
00:00
SEL
EXIT

How to find out the panel version


Step

Action

1.

If the power is switched on, switch it off.

2.

Keep key ? pressed down while you switch on the power and read the
information. The display shows the following panel information:
Panel FW: panel firmware version
ROM CRC: panel ROM check sum
Flash Rev: flash content version
Flash content comment.

Display

PANEL VERSION INFO


Panel FW:
x.xx
ROM CRC:
xxxxxxxxxx
Flash Rev:
x.xx
xxxxxxxxxxxxxxxxxxxxx

When you release the ? key, the panel goes to the Output mode.

Control panels

52

ACS550-01/U1 Users Manual

How to start, stop and switch between local and remote control
You can start, stop and switch between local and remote control in any mode. To be
able to start or stop the drive, the drive must be in local control.
Step
1.

Action

Display

To switch between remote control (REM shown on the status line) and local
control (LOC shown on the status line), press LOC
REM .

LOC
MESSAGE
Switching to the
local control mode.

Note: Switching to local control can be disabled with parameter 1606 LOCAL
LOCK.

00:00

The very first time the drive is powered up, it is in remote control (REM) and
controlled through the drive I/O terminals. To switch to local control (LOC) and
control the drive using the control panel, press LOC
REM . The result depends on
how long you press the key:
If you release the key immediately (the display flashes Switching to the local
control mode), the drive stops. Set the local control reference as instructed
on page 54.
If you press the key for about two seconds, the drive continues as before.
The drive copies the current remote values for the run/stop status and the
reference, and uses them as the initial local control settings.
To stop the drive in local control, press

The arrow ( or ) on the


status line stops rotating.

To start the drive in local control, press

The arrow ( or ) on the


status line starts rotating. It
is dotted until the drive
reaches the setpoint.

Control panels

ACS550-01/U1 Users Manual

53

Output mode
In the Output mode, you can:
monitor actual values of up to three signals in Group 01: OPERATING DATA
change the direction of the motor rotation
set the speed, frequency or torque reference
adjust the display contrast
start, stop, change the direction and switch between local and remote control.
You get to the Output mode by pressing

EXIT

repeatedly.

The top right corner of the


LOC
49.1Hz LOC
5.0Hz
HZ
50%
display shows the reference
49.1 Hz
value. The center can be
0.5 A
0.4 A
configured to show up to three
10.7 %
24.4 %
00:00
MENU
00:00
MENU
DIR
DIR
signal values or bar graphs. If
just one or two signals are
selected for display, the number and name of each displayed signal are shown in
addition to the value or bar graph. See page 56 for instructions on selecting and
modifying the monitored signals.
How to change the direction of the motor rotation
Step
1.

Action
If you are not in the Output mode, press

Display
EXIT

repeatedly until you get there.

REM

49.1Hz

49.1 Hz
0.5 A
10.7 %

DIR
2.

If the drive is in remote control (REM shown on the status line), switch to local
control by pressing LOC
REM . The display briefly shows a message about changing
the mode and then returns to the Output mode.

To change the direction from forward ( shown on the status line) to reverse (
DIR
shown on the status line), or vice versa, press
.

Note: Parameter 1003 DIRECTION must be set to 3 (REQUEST).

MENU

49.1Hz

LOC

49.1 Hz
0.5 A
10.7 %

DIR
3.

00:00

00:00

MENU

49.1Hz

LOC

49.1 Hz
0.5 A
10.7 %

DIR

00:00

MENU

Control panels

54

ACS550-01/U1 Users Manual

How to set the speed, frequency or torque reference


Step
1.

Action

Display

If you are not in the Output mode, press

EXIT

repeatedly until you get there.

REM

49.1Hz

49.1 Hz
0.5 A
10.7 %

DIR
2.

If the drive is in remote control (REM shown on the status line), switch to local
control by pressing LOC
REM . The display briefly shows a message about changing
the mode and then returns to the Output mode.
Note: With Group 11: REFERENCE SELECT, you can allow the reference
modification in remote control.

3.

To increase the highlighted reference value shown in the top right corner of the
display, press
. The value changes immediately. It is stored in the drive
permanent memory and restored automatically after power switch-off.
To decrease the value, press

00:00

MENU

49.1Hz

LOC

49.1 Hz
0.5 A
10.7 %

DIR

00:00

LOC

MENU

50.0Hz

50.0 Hz
0.5 A
10.7 %

DIR

00:00

MENU

How to adjust the display contrast


Step
1.

Action

Display

If you are not in the Output mode, press

EXIT

repeatedly until you get there.

LOC

49.1Hz

49.1 Hz
0.5 A
10.7 %

DIR
2.

To increase the contrast, press keys


To decrease the contrast, press keys

MENU
MENU

and
and

simultaneously.
simultaneously.

LOC

MENU

49.1Hz

49.1 Hz
0.5 A
10.7 %

DIR

Control panels

00:00

00:00

MENU

ACS550-01/U1 Users Manual

55

Parameters mode
In the Parameters mode, you can:
view and change parameter values
start, stop, change the direction and switch between local and remote control.
How to select a parameter and change its value
Step
1.

Action

Display
MENU

Go to the Main menu by pressing


if you are in the Output mode, otherwise
EXIT
by pressing
repeatedly until you get to the Main menu.

LOC

MAIN MENU

PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT

00:00

ENTER

2.

Go to the Parameters mode by selecting PARAMETERS on the menu with keys


ENTER
and
, and pressing
.

LOC
PAR GROUPS
01
01 OPERATING DATA
03 FB ACTUAL SIGNALS
04 FAULT HISTORY
10 START/STOP/DIR
11 REFERENCE SELECT
00:00
SEL
EXIT

3.

Select the appropriate parameter group with keys

LOC
PAR GROUPS
99
99 START-UP DATA
01 OPERATING DATA
03 FB ACTUAL SIGNALS
04 FAULT HISTORY
10 START/STOP/DIR
00:00
SEL
EXIT

Press

4.

SEL

and

LOC
PARAMETERS
9901 LANGUAGE
ENGLISH
9902 APPLIC MACRO
9904 MOTOR CTRL MODE
9905 MOTOR NOM VOLT
00:00
EDIT
EXIT

Select the appropriate parameter with keys


and
. The current
value of the parameter is shown below the selected parameter.

Press

EDIT

LOC
PARAMETERS
9901 LANGUAGE
9902 APPLIC MACRO
ABB STANDARD
9904 MOTOR CTRL MODE
9905 MOTOR NOM VOLT
00:00
EDIT
EXIT
LOC

PAR EDIT

9902 APPLIC MACRO

ABB STANDARD

[1]
CANCEL
5.

Specify a new value for the parameter with keys

and

Pressing the key once increments or decrements the value. Holding the key
down changes the value faster. Pressing the keys simultaneously replaces the
displayed value with the default value.
6.

To save the new value, press

SAVE

To cancel the new value and keep the original, press

CANCEL

LOC

00:00

SAVE

PAR EDIT

9902 APPLIC MACRO

3-WIRE

[2]
CANCEL

00:00

SAVE

LOC
PARAMETERS
9901 LANGUAGE
9902 APPLIC MACRO
3-WIRE
9904 MOTOR CTRL MODE
9905 MOTOR NOM VOLT
00:00
EDIT
EXIT

Control panels

56

ACS550-01/U1 Users Manual

How to select the monitored signals


Step
1.

Action
You can select which signals are monitored in the Output mode and how they
are displayed with Group 34: PANEL DISPLAY parameters. See page 55 for
detailed instructions on changing parameter values.

LOC

By default, the display shows three signals. The particular default signals
depend on the value of parameter 9902 APPLIC MACRO: For macros whose
default value of parameter 9904 MOTOR CTRL MODE is 1 (VECTOR:SPEED), the
default for signal 1 is 0102 SPEED, otherwise 0103 OUTPUT FREQ. The defaults
for signals 2 and 3 are always 0104 CURRENT and 0105 TORQUE, respectively.

[103]
CANCEL
LOC

To change the default signals, select up to three signals from Group 01:
OPERATING DATA to be shown.

[104]
CANCEL

Signal 1: Change the value of parameter 3401 SIGNAL1 PARAM to the index of
the signal parameter in Group 01: OPERATING DATA (= number of the
parameter without the leading zero), e.g. 105 means parameter 0105 TORQUE.
Value 100 means that no signal is displayed.
Repeat for signals 2 (3408 SIGNAL2 PARAM) and 3 (3415 SIGNAL3 PARAM).
2.

Select how you want the signals to be displayed: as a decimal number or a bar
graph. For decimal numbers, you can specify the decimal point location, or use
the decimal point location and unit of the source signal [setting (9 (DIRECT)]. For
details, see parameter 3404.
Signal 1: parameter 3404 OUTPUT1 DSP FORM
Signal 2: parameter 3411 OUTPUT2 DSP FORM
Signal 3: parameter 3418 OUTPUT3 DSP FORM.

3.

Select the units to be displayed for the signals. This has no effect if parameter
3404/3411/3418 is set to 9 (DIRECT). For details, see parameter 3405.
Signal 1: parameter 3405 OUTPUT1 UNIT
Signal 2: parameter 3412 OUTPUT2 UNIT
Signal 3: parameter 3419 OUTPUT3 UNIT.

4.

Display

Select the scalings for the signals by specifying the minimum and maximum
display values. This has no effect if parameter 3404/3411/3418 is set to 9
(DIRECT). For details, see parameters 3406 and 3407.
Signal 1: parameters 3406 OUTPUT1 MIN and 3407 OUTPUT1 MAX
Signal 2: parameters 3413 OUTPUT2 MIN and 3414 OUTPUT2 MAX
Signal 3: parameters 3420 OUTPUT3 MIN and 3421 OUTPUT3 MAX.

PAR EDIT

3401 SIGNAL1 PARAM

OUTPUT FREQ
00:00

SAVE

PAR EDIT

3408 SIGNAL2 PARAM

CURRENT

LOC

00:00

SAVE

PAR EDIT

3415 SIGNAL3 PARAM

TORQUE

[105]
CANCEL
LOC

00:00

SAVE

PAR EDIT

3404 OUTPUT1 DSP FORM

DIRECT

[9]
CANCEL

LOC

00:00

SAVE

PAR EDIT

3405 OUTPUT1 UNIT


[3]
CANCEL
LOC

Hz

00:00

SAVE

PAR EDIT

3406 OUTPUT1 MIN

0.0 Hz

CANCEL
LOC

00:00

SAVE

PAR EDIT

3407 OUTPUT1 MAX

500.0 Hz

CANCEL

Control panels

00:00

SAVE

ACS550-01/U1 Users Manual

57

Assistants mode
When the drive is first powered up, the Start-up Assistant guides you through the
setup of the basic parameters. The Start-up Assistant is divided into assistants, each
of which guides you through the task of specifying a related parameter set, for
example Motor Set-up or PID Control. You can activate the assistants one after the
other as the Start-up Assistant suggests, or independently. The tasks of the
assistants are listed in the table on page 58.
In the Assistants mode, you can:
use assistants to guide you through the specification of a set of basic parameters
start, stop, change the direction and switch between local and remote control.
How to use an assistant
The table below shows the basic operation sequence which leads you through
assistants. The Motor Set-up Assistant is used as an example.
Step
1.

Action

Display
MENU

Go to the Main menu by pressing


if you are in the Output mode, otherwise
EXIT
by pressing
repeatedly until you get to the Main menu.

LOC

EXIT
2.

Go to the Assistants mode by selecting ASSISTANTS on the menu with keys


ENTER
and
, and pressing
.

3.

Select the assistant with keys

4.

and

, and press

SEL

MAIN MENU

PARAMETERS
ASSISTANTS
CHANGED PAR
00:00

ENTER

LOC
ASSISTANTS
1
Start-up assistant
Motor Set-up
Application
Speed control EXT1
Speed control EXT2
00:00
SEL
EXIT
LOC

PAR EDIT

If you select any other assistant than the Start-up Assistant, it guides you
through the task of specification of its parameter set as shown in steps 4. and 5.
below. After that you can select another assistant on the Assistants menu or exit
the Assistants mode. The Motor Set-up Assistant is used here as an example.

9905 MOTOR NOM VOLT

If you select the Start-up Assistant, it activates the first assistant, which guides
you through the task of specification of its parameter set as shown in steps 4.
and 5. below. The Start-up Assistant then asks if you want to continue with the
next assistant or skip it select the appropriate answer with keys
and
SEL
, and press
. If you choose to skip, the Start-up Assistant asks the
same question about the next assistant, and so on.

LOC
CHOICE
Do you want to
continue with
application setup?
Continue
Skip
00:00
OK
EXIT

To specify a new value, press keys

LOC

and

220 V

EXIT

00:00

SAVE

PAR EDIT

9905 MOTOR NOM VOLT

240 V

EXIT
To ask for information on the requested parameter, press key ? . Scroll the
EXIT
help text with keys
and
. Close the help by pressing
.

00:00

SAVE

LOC
HELP
Set as given on the
motor nameplate.
Voltage value must
correspond to motor
D/Y connection.
EXIT
00:00

Control panels

58

ACS550-01/U1 Users Manual

Step
5.

Action

Display

To accept the new value and continue to the setting of the next parameter,
SAVE
press
.
To stop the assistant, press

EXIT

LOC

PAR EDIT

9906 MOTOR NOM CURR

1.2 A

.
EXIT

00:00

SAVE

The table below lists the tasks of the assistants and the relevant drive parameters.
Depending on the selection made in the Application task (parameter 9902 APPLIC
MACRO), the Start-up Assistant decides, which consequent tasks it suggests.
Name

Description

Set parameters

Language select

Selecting the language

9901

Motor set-up

Setting the motor data


Performing the motor identification. (If the speed limits are not in
the allowed range: Setting the limits.)

99049909
9910

Application

Selecting the application macro

9902, parameters associated to


the macro

Option modules

Activating the option modules

Group 35: MOTOR TEMP MEAS


Group 52: PANEL COMM
9802

Speed control
EXT1

Selecting the source for the speed reference

1103

(If AI1 is used: Setting analog input AI1 limits, scale, inversion)

(13011303, 3001)

Setting the reference limits

1104, 1105

Setting the speed (frequency) limits

2001, 2002, (2007, 2008)

Setting the acceleration and deceleration times

2202, 2203

Selecting the source for the speed reference

1106

(If AI1 is used: Setting analog input AI1 limits, scale, inversion)

(13011303, 3001)

Setting the reference limits

1107, 1108

Speed control
EXT2
Torque control

PID control

Selecting the source for the torque reference

1106

(If AI1 is used: Setting analog input AI1 limits, scale, inversion)

(13011303, 3001)

Setting the reference limits

1107, 1108

Setting the torque ramp up and ramp down times

2401, 2402

Selecting the source for the process reference

1106

(If AI1 is used: Setting analog input AI1 limits, scale, inversion)

(13011303, 3001)

Setting the reference limits

1107, 1108

Setting the speed (reference) limits

2001, 2002, (2007, 2008)

Setting the source and limits for the process actual value

4016, 4018, 4019

Start/Stop control Selecting the source for start and stop signals of the two external
control locations, EXT1 and EXT2

Timed functions

1001, 1002

Selecting between EXT1 and EXT2

1102

Defining the direction control

1003

Defining the start and stop modes

21012103

Selecting the use of Run Enable signal

1601

Setting the timed functions

Group 36: TIMED FUNCTIONS

Selecting the timed start/stop control for external control locations 1001, 1002
EXT1 and EXT2

Control panels

Selecting timed EXT1/EXT2 control

1102

Activation of timed constant speed 1

1201

ACS550-01/U1 Users Manual


Name

Description

59
Set parameters

Selecting timed function status indicated through relay output RO 1401


Selecting timed PID1 parameter set 1/2 control

4027

Protections

Setting the current and torque limits

2003, 2017

Output signals

Selecting the signals indicated through relay output RO

Group 14: RELAY OUTPUTS

Selecting the signals indicated through analog output AO

Group 15: ANALOG OUTPUTS

Setting the minimum, maximum, scaling and inversion

Control panels

60

ACS550-01/U1 Users Manual

Changed Parameters mode


In the Changed Parameters mode, you can:
view a list of all parameters that have been changed from the macro default
values
change these parameters
start, stop, change the direction and switch between local and remote control.
How to view and edit changed parameters
Step
1.

Action

Display
MENU

Go to the Main menu by pressing


if you are in the Output mode, otherwise
EXIT
by pressing
repeatedly until you get to the Main menu.

LOC

MAIN MENU

PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT

00:00

ENTER

2.

Go to the Changed Parameters mode by selecting CHANGED PAR on the


ENTER
menu with keys
and
, and pressing
.

LOC
CHANGED PAR
1202 CONST SPEED 1
10.0 Hz
1203 CONST SPEED 2
1204 CONST SPEED 3
9902 APPLIC MACRO
00:00
EDIT
EXIT

3.

Select the changed parameter on the list with keys


and
. The
EDIT
value of the selected parameter is shown below it. Press
to modify the
value.

LOC

PAR EDIT

1202 CONST SPEED 1

10.0 Hz

CANCEL
4.

Specify a new value for the parameter with keys

and

Pressing the key once increments or decrements the value. Holding the key
down changes the value faster. Pressing the keys simultaneously replaces the
displayed value with the default value.
5.

SAVE

To accept the new value, press


. If the new value is the default value, the
parameter is removed from the list of changed parameters.
To cancel the new value and keep the original, press

Control panels

CANCEL

LOC

00:00

SAVE

PAR EDIT

1202 CONST SPEED 1

15.0 Hz

CANCEL

00:00

SAVE

LOC
CHANGED PAR
1202 CONST SPEED 1
15.0 Hz
1203 CONST SPEED 2
1204 CONST SPEED 3
9902 APPLIC MACRO
00:00
EDIT
EXIT

ACS550-01/U1 Users Manual

61

Fault Logger mode


In the Fault Logger mode, you can:
view the drive fault history of maximum ten faults (after a power off, only the three
latest faults are kept in the memory)
see the details of the three latest faults (after a power off, the details of only the
most recent fault is kept in the memory)
read the help text for the fault
start, stop, change the direction and switch between local and remote control.
How to view faults
Step
1.

Action

Display
MENU

Go to the Main menu by pressing


if you are in the Output mode, otherwise
EXIT
by pressing
repeatedly until you get to the Main menu.

LOC

EXIT
2.

Go to the Fault Logger mode by selecting FAULT LOGGER on the menu with
ENTER
keys
and
, and pressing
. The display shows the fault log
starting with the latest fault.
The number on the row is the fault code according to which the causes and
corrective actions are listed in chapter Diagnostics.

3.

To see the details of a fault, select it with keys


.

and

To show the help text, press


.

DIAG

After reading the help, press

OK

00:00

ENTER

LOC
FAULT LOGGER
10: PANEL LOSS
19.03.05 13:04:57
6:
DC UNDERVOLT
6:
AI1 LOSS
EXIT

00:00

DETAIL

, and press

LOC
PANEL LOSS
FAULT
10
FAULT TIME 1
13:04:57
FAULT TIME 2
00:00
DIAG
EXIT

and

LOC
DIAGNOSTICS
Check: Comm lines
and connections,
parameter 3002,
parameters in groups
10 and 11.
EXIT
OK
00:00

DETAIL

4.

MAIN MENU

PARAMETERS
ASSISTANTS
CHANGED PAR

. Scroll the help text with keys


to return to the previous display.

Control panels

62

ACS550-01/U1 Users Manual

Time and Date mode


In the Time and Date mode, you can:
show or hide the clock
change date and time display formats
set the date and time
enable or disable automatic clock transitions according to the daylight saving
changes
start, stop, change the direction and switch between local and remote control.
The Assistant Control Panel contains a battery to ensure the function of the clock
when the panel is not powered by the drive.
How to show or hide the clock, change display formats, set the date and time and enable
or disable clock transitions due to daylight saving changes
Step
1.

Action

Display
MENU

Go to the Main menu by pressing


if you are in the Output mode, otherwise
EXIT
by pressing
repeatedly until you get to the Main menu.

LOC

MAIN MENU

PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT

00:00

ENTER

2.

Go to the Time and Date mode by selecting TIME & DATE on the menu with
ENTER
keys
and
, and pressing
.

LOC
TIME & DATE
1
CLOCK VISIBILITY
TIME FORMAT
DATE FORMAT
SET TIME
SET DATE
00:00
SEL
EXIT

3.

To show (hide) the clock, select CLOCK VISIBLILITY on the menu, press
SEL
SEL
, select Show clock (Hide clock) and press
, or, if you want to return
EXIT
to the previous display without making changes, press
.

LOC
CLOCK VISIB
Show clock
Hide clock

00:00

EXIT
SEL

To specify the date format, select DATE FORMAT on the menu, press
OK
CANCEL
and select a suitable format. Press
to save or
to cancel your
changes.

To specify the time format, select TIME FORMAT on the menu, press
OK
CANCEL
and select a suitable format. Press
to save or
to cancel your
changes.

To set the time, select SET TIME on the menu and press
. Specify the
OK
hours with keys
and
, and press
.Then specify the minutes.
OK
CANCEL
Press
to save or
to cancel your changes.

LOC

00:00

OK

15:41
00:00

OK

SET TIME

CANCEL

Control panels

00:00

LOC
TIME FORMAT
24-hour
12-hour

CANCEL
SEL

SEL

LOC
DATE FORMAT
dd.mm.yy
mm/dd/yy
dd.mm.yyyy
mm/dd/yyyy
CANCEL

SEL

OK

ACS550-01/U1 Users Manual

Step

63

Action

Display
SEL

To set the date, select SET DATE on the menu and press
. Specify the
first part of the date (day or month depending on the selected date format) with
OK
keys
and
, and press
. Repeat for the second part. After
OK
CANCEL
specifying the year, press
. To cancel your changes, press
.

LOC

SET DATE

19.03.05
CANCEL

To enable or disable the automatic clock transitions according to the daylight


SEL
saving changes, select DAYLIGHT SAVING on the menu and press
.
Pressing ? opens the help that shows the beginning and end dates of the
period during which daylight saving time is used in each country or area
whose daylight saving changes you can select to be followed.

00:00

OK

LOC
DAYLIGHT SAV 1
Off
EU
US
Australia1:NSW,Vict..
Australia2:Tasmania..
00:00
SEL
EXIT

To disable automatic clock transitions according to the daylight saving


SEL
changes, select Off and press
.

LOC
HELP
EU:
On: Mar last Sunday
Off: Oct last Sunday

To enable automatic clock transitions, select the country or area whose


SEL
daylight saving changes are followed and press
.

US:
EXIT

To return to the previous display without making changes, press

EXIT

00:00

Control panels

64

ACS550-01/U1 Users Manual

Parameter Backup mode


The Parameter Backup mode is used to export parameters from one drive to another
or to make a backup of the drive parameters. Uploading to the panel stores all drive
parameters, including up to two user sets, to the Assistant Control Panel. The full
set, partial parameter set (application) and user sets can then be downloaded from
the control panel to another drive or the same drive. Uploading and downloading can
be performed in local control.
The control panel memory is non-volatile and does not depend on the panel battery.
In the Parameter Backup mode, you can:
copy all parameters from the drive to the control panel (UPLOAD TO PANEL).
This includes all defined user sets of parameters and internal (not adjustable by
the user) parameters such as those created by the ID Run.
view the information about the backup stored to the control panel with UPLOAD
TO PANEL (BACKUP INFO). This includes e.g. the type and rating of the drive
where the backup was made. It is useful to check this information when you are
going to copy the parameters to another drive with DOWNLOAD FULL SET to
ensure that the drives match.
restore the full parameter set from the control panel to the drive (DOWNLOAD
FULL SET). This writes all parameters, including the internal non-user-adjustable
motor parameters, to the drive. It does not include the user sets of parameters.
Note: Only use this function to restore a drive from a backup or to transfer
parameters to systems that are identical to the original system.
copy a partial parameter set (part of the full set) from the control panel to a drive
(DOWNLOAD APPLICATION). The partial set does not include user sets, internal
motor parameters, parameters 99059909, 1605, 1607, 5201, nor any Group
51: EXT COMM MODULE and Group 53: EFB PROTOCOL parameters.
The source and target drives and their motor sizes do not need to be the same.
copy USER S1 parameters from the control panel to the drive (DOWNLOAD
USER SET1). A user set includes Group 99: START-UP DATA parameters and
the internal motor parameters.
The function is only shown on the menu when User Set 1 has been first saved
using parameter 9902 APPLIC MACRO (see section User parameter sets on page
88) and then uploaded to the control panel with UPLOAD TO PANEL.
copy USER S2 parameters from the control panel to the drive (DOWNLOAD
USER SET2). As DOWNLOAD USER SET1 above.
start, stop, change the direction and switch between local and remote control.

Control panels

ACS550-01/U1 Users Manual

65

How to upload and download parameters


For the upload and download functions available, see above. Note that the drive has
to be in local control for uploading and downloading.
Step
1.

Action

Display
MENU

Go to the Main menu by pressing


if you are in the Output mode, otherwise
EXIT
by pressing
repeatedly until you get to the Main menu. If REM is shown
on the status line, press LOC
REM to switch to local control.

LOC

MAIN MENU

PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT

00:00

ENTER

2.

Go to the Par Backup mode by selecting PAR BACKUP on the menu with keys
ENTER
and
, and pressing
.

LOC
PAR BACKUP
1
UPLOAD TO PANEL
BACKUP INFO
DOWNLOAD FULL SET
DOWNLOAD APPLICATION
DOWNLOAD USER SET1
00:00
SEL
EXIT

3.

To copy all parameters (including user sets and internal parameters) from the
drive to the control panel, select UPLOAD TO PANEL on the Par Backup
SEL
menu with keys
and
, and press
. During the transfer, the
ABORT
display shows the transfer status as a percentage of completion. Press
if
you want to stop the operation.

LOC
PAR BACKUP
Copying parameters
50%

After the upload is completed, the display shows a message about the
OK
completion. Press
to return to the Par Backup menu.

ABORT

LOC
MESSAGE
Parameter upload
successful.

OK
To perform downloads, select the appropriate operation (here DOWNLOAD
FULL SET is used as an example) on the Par Backup menu with keys
SEL
and
, and press
. The display shows the transfer status as a
ABORT
percentage of completion. Press
if you want stop the operation.

00:00

LOC
PAR BACKUP
Downloading
parameters (full
set)
ABORT

After the download is completed, the display shows a message about the
OK
completion. Press
to return to the Par Backup menu.

00:00

50%

00:00

LOC
MESSAGE
Parameter download
successfully
completed.
OK

00:00

Control panels

66

ACS550-01/U1 Users Manual

How to view information about the backup


Step
1.

Action

Display
MENU

Go to the Main menu by pressing


if you are in the Output mode, otherwise
EXIT
by pressing
repeatedly until you get to the Main menu.

LOC

MAIN MENU

PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT

00:00

ENTER

2.

Go to the Par Backup mode by selecting PAR BACKUP on the menu with keys
ENTER
and
, and pressing
.

LOC
PAR BACKUP
1
UPLOAD TO PANEL
BACKUP INFO
DOWNLOAD FULL SET
DOWNLOAD APPLICATION
DOWNLOAD USER SET1
00:00
SEL
EXIT

3.

Select BACKUP INFO on the Par Backup menu with keys


and
,
SEL
and press
. The display shows the following information about the drive
where the backup was made:

LOC
BACKUP INFO
DRIVE TYPE
ACS550
3304 DRIVE RATING
4A62i
3301 FIRMWARE
EXIT
00:00

DRIVE TYPE:
DRIVE RATING:

FIRMWARE:

type of the drive


rating of the drive in format XXXYZ, where
XXX: nominal current rating. If present, an A indicates
a decimal point, e.g. 4A6 means 4.6 A.
Y:
2 = 200 V
4 = 400 V
6 = 600 V
Z:
i = European loading package
n = US loading package
firmware version of the drive.

You can scroll the information with keys


4.

Press

Control panels

EXIT

and

to return to the Par Backup menu.

LOC
BACKUP INFO
ACS550
3304 DRIVE RATING
4A62i
3301 FIRMWARE
300F hex
EXIT
00:00

.
LOC
PAR BACKUP
1
UPLOAD TO PANEL
BACKUP INFO
DOWNLOAD FULL SET
DOWNLOAD APPLICATION
DOWNLOAD USER SET1
00:00
SEL
EXIT

ACS550-01/U1 Users Manual

67

I/O Settings mode


In the I/O Settings mode, you can:
check the parameter settings related to any I/O terminal
edit the parameter setting. For example, if 1103: REF1 is listed under Ain1
(Analog input 1), that is, parameter 1103 REF1 SELECT has value AI1, you can
change its value to e.g. AI2. You cannot, however, set the value of parameter 1106
REF2 SELECT to AI1.
start, stop, change the direction and switch between local and remote control.
How to edit and change parameter settings related to I/O terminals
Step
1.

Action

Display
MENU

Go to the Main menu by pressing


if you are in the Output mode, otherwise
EXIT
by pressing
repeatedly until you get to the Main menu.

LOC

MAIN MENU

PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT

00:00

ENTER

2.

Go the I/O Settings mode by selecting I/O SETTINGS on the menu with keys
ENTER
and
, and pressing
.

LOC
I/O SETTINGS 1
DIGITAL INPUTS (DI)
ANALOG INPUTS (AI)
RELAY OUTPUTS (ROUT)
ANALOG OUTPUTS (AOUT)
PANEL
00:00
SEL
EXIT

3.

Select the I/O group, e.g. DIGITAL INPUTS, with keys


and
, and
SEL
press
. After a brief pause, the display shows the current settings for the
selection.

LOC
I/O SETTINGS
DI1
1001:START/STOP (E1)
DI2
DI3
EXIT

4.

Select the setting (line with a parameter number) with keys


EDIT
and press
.

and

LOC

00:00
PAR EDIT

1001 EXT1 COMMANDS

DI1

[1]
CANCEL
5.

Specify a new value for the setting with keys

and

Pressing the key once increments or decrements the value. Holding the key
down changes the value faster. Pressing the keys simultaneously replaces the
displayed value with the default value.
6.

To save the new value, press

SAVE

To cancel the new value and keep the original, press

CANCEL

LOC

00:00

SAVE

PAR EDIT

1001 EXT1 COMMANDS

DI1,2

[2]
CANCEL

00:00

SAVE

LOC
I/O SETTINGS
DI1
1001:START/STOP (E1)
DI2
1001:DIR (E1)
DI3
00:00
EXIT

Control panels

68

ACS550-01/U1 Users Manual

Basic Control Panel


Features
The Basic Control Panel features:
numeric control panel with an LCD display
copy function parameters can be copied to the control panel memory for later
transfer to other drives or for backup of a particular system.
Overview
The following table summarizes the key functions and displays on the Basic Control
Panel.
No. Use
1
1a LOC

1c

1d OUTPUT
RESET
EXIT

2
6

4
5

Control panels

11
.

FWD

LCD display Divided into five areas:


a. Upper left Control location:
LOC: drive control is local, that is, from the control panel
REM: drive control is remote, such as the drive I/O or fieldbus.

1b
1e

b. Upper right Unit of the displayed value.


c. Center Variable; in general, shows parameter and signal values, menus or
lists. Shows also fault and alarm codes.

MENU
ENTER

d. Lower left and center Panel operation state:


OUTPUT: Output mode
PAR: Parameter mode
MENU: Main menu
FAULT : Fault mode.

3
7
9

e. Lower right Indicators:


FWD (forward) / REV (reverse): direction of the motor rotation
Flashing slowly: stopped
Flashing rapidly: running, not at setpoint
Steady: running, at setpoint
SET : Displayed value can be modified (in the Parameter and Reference
modes).
2

RESET/EXIT Exits to the next higher menu level without saving changed
values. Resets faults in the Output and Fault modes.

MENU/ENTER Enters deeper into menu level. In the Parameter mode,


saves the displayed value as the new setting.

Up
Scrolls up through a menu or list.
Increases a value if a parameter is selected.
Increases the reference value in the Reference mode.
Holding the key down changes the value faster.

Down
Scrolls down through a menu or list.
Decreases a value if a parameter is selected.
Decreases the reference value in the Reference mode.
Holding the key down changes the value faster.

LOC/REM Changes between local and remote control of the drive.

DIR Changes the direction of the motor rotation.

STOP Stops the drive in local control.

START Starts the drive in local control.

ACS550-01/U1 Users Manual

69

Operation
You operate the control panel with menus and keys. You select an option, e.g.
and
arrow keys until the
operation mode or parameter, by scrolling the
option is visible in the display and then pressing the
key.
With the
changes.

key, you return to the previous operation level without saving the made

The Basic Control Panel has five panel modes: Output, Reference, Parameter, Copy
and Fault. The operation in the first four modes is described in this chapter. When a
fault or alarm occurs, the panel goes automatically to the Fault mode showing the
fault or alarm code. You can reset the fault or alarm in the Output or Fault mode (see
chapter Diagnostics).
After the power is switched on, the panel is in the
Output mode, where you can start, stop, change the
direction, switch between local and remote control and
monitor up to three actual values (one at a time). To do
other tasks, go first to the Main menu and select the
appropriate mode.

REM
OUTPUT
REM

491
.
PAr

Hz

FWD

MENU

FWD

How to do common tasks


The table below lists common tasks, the mode in which you can perform them and
the page number where the steps to do the task are described in detail.
Task

Mode

Page

How to switch between local and remote control

Any

70

How to start and stop the drive

Any

70

How to change the direction of the motor rotation

Any

70

How to browse the monitored signals

Output

71

How to set the speed, frequency or torque reference

Reference

72

How to change the value of a parameter

Parameter

73

How to select the monitored signals

Parameter

74

How to reset faults and alarms

Output, Fault

265

How to copy parameters from the drive to the control panel

Copy

76

How to restore parameters from the control panel to the drive

Copy

76

Control panels

70

ACS550-01/U1 Users Manual

How to start, stop and switch between local and remote control
You can start, stop and switch between local and remote control in any mode. To be
able to start or stop the drive, the drive must be in local control.
Step
1.

Action

Display

To switch between remote control (REM shown on the left) and local
control (LOC shown on the left), press LOC
REM .
Note: Switching to local control can be disabled with parameter 1606

LOC
OUTPUT

491
.

Hz

FWD

LOCAL LOCK.

After pressing the key, the display briefly shows message LoC or rE,
as appropriate, before returning to the previous display.

LOC

LoC

FWD

The very first time the drive is powered up, it is in remote control (REM)
and controlled through the drive I/O terminals. To switch to local control
(LOC) and control the drive using the control panel, press LOC
REM . The result
depends on how long you press the key:
If you release the key immediately (the display flashes LoC), the drive
stops. Set the local control reference as instructed on page 72.
If you press the key for about two seconds (release when the display
changes from LoC to LoC r), the drive continues as before. The drive
copies the current remote values for the run/stop status and the
reference, and uses them as the initial local control settings.
To stop the drive in local control, press

Text FWD or REV on the bottom


line starts flashing slowly.

To start the drive in local control, press

Text FWD or REV on the bottom


line starts flashing rapidly. It
stops flashing when the drive
reaches the setpoint.

How to change the direction of the motor rotation


You can change the direction of the motor rotation in any mode.
Step
1.

2.

Action

Display

If the drive is in remote control (REM shown on the left), switch to local
control by pressing LOC
REM . The display briefly shows message LoC before
returning to the previous display.

LOC

To change the direction from forward (FWD shown at the bottom) to


reverse (REV shown at the bottom), or vice versa, press
.

LOC

OUTPUT

OUTPUT

Note: Parameter 1003 DIRECTION must be set to 3 (REQUEST).

Control panels

491
.

Hz

491
.

Hz

FWD

REV

ACS550-01/U1 Users Manual

71

Output mode
In the Output mode, you can:
monitor actual values of up to three Group 01: OPERATING DATA signals, one
signal at a time
start, stop, change the direction and switch between local and remote control.
You get to the Output mode by pressing
the bottom.

until the display shows text OUTPUT at

The display shows the value of one Group 01:


OPERATING DATA signal. The unit is shown on the
right. Page 74 tells how to select up to three signals to
be monitored in the Output mode. The table below
shows how to view them one at a time.

REM
OUTPUT

491
.

Hz

FWD

How to browse the monitored signals


Step
1.

Action

Display

If more than one signals have been selected to be monitored (see page
74), you can browse them in the Output mode.
To browse the signals forward, press key
them backward, press key
repeatedly.

repeatedly. To browse

REM
OUTPUT
REM
OUTPUT
REM
OUTPUT

491
.
05
.
107
.

Hz

FWD
A

FWD
%

FWD

Control panels

72

ACS550-01/U1 Users Manual

Reference mode
In the Reference mode, you can:
set the speed, frequency or torque reference
start, stop, change the direction and switch between local and remote control.
How to set the speed, frequency or torque reference
Step
1.

Action

Display

Go to the Main menu by pressing


if you are in the Output mode,
otherwise by pressing
repeatedly until you see MENU at the bottom.

REM

PAr

MENU

2.

If the drive is in remote control (REM shown on the left), switch to local
control by pressing LOC
REM . The display briefly shows LoC before switching
to local control.

LOC

PAr

MENU

FWD

FWD

Note: With Group 11: REFERENCE SELECT, you can allow the reference
modification in remote control (REM).
3.

If the panel is not in the Reference mode (rEF not visible), press key
or
until you see rEF and then press
. Now the display
shows the current reference value with SET under the value.

LOC

rEF
491
.

MENU
LOC

FWD
Hz

SET FWD

4.

To increase the reference value, press


To decrease the reference value, press

LOC

The value changes immediately when you press the key. It is stored in the
drive permanent memory and restored automatically after power switch-off.

Control panels

500
.

SET FWD

Hz

ACS550-01/U1 Users Manual

73

Parameter mode
In the Parameter mode, you can:
view and change parameter values
select and modify the signals shown in the Output mode
start, stop, change the direction and switch between local and remote control.
How to select a parameter and change its value
Step
1.

Action

Display

Go to the Main menu by pressing


if you are in the Output mode,
otherwise by pressing
repeatedly until you see MENU at the bottom.

LOC

rEF

MENU

2.

If the panel is not in the Parameter mode (PAr not visible), press key
or
until you see PAr and then press
. The display
shows the number of one of the parameter groups.

LOC

PAr
-01-

MENU
LOC

FWD

PAR

3.

Use keys

and

to find the desired parameter group.

LOC

Press
group.

. The display shows one of the parameters in the selected

LOC

Use keys

and

to find the desired parameter.

LOC

Press and hold


for about two seconds until the display shows the
value of the parameter with SET underneath indicating that changing of the
value is now possible.

FWD

1103
PAR

6.

FWD

1101
PAR

5.

FWD

-11PAR

4.

FWD

FWD

LOC

PAR SET FWD

Note: When SET is visible, pressing keys


and
simultaneously changes the displayed value to the default value of the
parameter.
7.

Use keys
and
to select the parameter value. When you have
changed the parameter value, SET starts flashing.

LOC

2
1103

PAR SET FWD

To save the displayed parameter value, press

To cancel the new value and keep the original, press

LOC

PAR

FWD

Control panels

74

ACS550-01/U1 Users Manual

How to select the monitored signals


Step
1.

Action

Display

You can select which signals are monitored in the Output mode and how
they are displayed with Group 34: PANEL DISPLAY parameters. See page
55 for detailed instructions on changing parameter values.

LOC

By default, you can monitor three signals by browsing (see page 71). The
particular default signals depend on the value of parameter 9902 APPLIC
MACRO: For macros whose default value of parameter 9904 MOTOR CTRL
MODE is 1 (VECTOR:SPEED), the default for signal 1 is 0102 SPEED, otherwise
0103 OUTPUT FREQ. The defaults for signals 2 and 3 are always 0104
CURRENT and 0105 TORQUE, respectively.

LOC

103
104
105

PAR SET FWD

PAR SET FWD


LOC

PAR SET FWD

To change the default signals, select from Group 01: OPERATING DATA
up to three signals to be browsed.
Signal 1: Change the value of parameter 3401 SIGNAL1 PARAM to the index
of the signal parameter in Group 01: OPERATING DATA (= number of the
parameter without the leading zero), e.g. 105 means parameter 0105
TORQUE. Value 100 means that no signal is displayed.
Repeat for signals 2 (3408 SIGNAL2 PARAM) and 3 (3415 SIGNAL3 PARAM).
For example, if 3401 = 0 and 3415 = 0, browsing is disabled and only the
signal specified by 3408 appears in the display. If all three parameters are
set to 0, i.e. no signals are selected for monitoring, the panel displays text
n.A.
2.

Specify the decimal point location, or use the decimal point location and
unit of the source signal [setting (9 (DIRECT)]. Bar graphs are not available
for Basic Operation Panel. For details, see parameter 3404.

LOC

PAR SET FWD

Signal 1: parameter 3404 OUTPUT1 DSP FORM


Signal 2: parameter 3411 OUTPUT2 DSP FORM
Signal 3: parameter 3418 OUTPUT3 DSP FORM.
3.

Select the units to be displayed for the signals. This has no effect if
parameter 3404/3411/3418 is set to 9 (DIRECT). For details, see
parameter 3405.

LOC

PAR SET FWD

Signal 1: parameter 3405 OUTPUT1 UNIT


Signal 2: parameter 3412 OUTPUT2 UNIT
Signal 3: parameter 3419 OUTPUT3 UNIT.
4.

Select the scalings for the signals by specifying the minimum and
maximum display values. This has no effect if parameter 3404/3411/3418 is
set to 9 (DIRECT). For details, see parameters 3406 and 3407.

LOC

Signal 1: parameters 3406 OUTPUT1 MIN and 3407 OUTPUT1 MAX


Signal 2: parameters 3413 OUTPUT2 MIN and 3414 OUTPUT2 MAX
Signal 3: parameters 3420 OUTPUT3 MIN and 3421 OUTPUT3 MAX.

LOC

Control panels

00
.
5000
.

Hz

PAR SET FWD

PAR SET FWD

Hz

ACS550-01/U1 Users Manual

75

Copy mode
The Basic Control Panel can store a full set of drive parameters and up to two user
sets of drive parameters to the control panel. The control panel memory is nonvolatile.
In the Copy mode, you can:
copy all parameters from the drive to the control panel (uL Upload). This
includes all defined user sets of parameters and internal (not adjustable by the
user) parameters such as those created by the ID Run.
restore the full parameter set from the control panel to the drive (dL A Download
All). This writes all parameters, including the internal non-user-adjustable motor
parameters, to the drive. It does not include the user sets of parameters.
Note: Only use this function to restore a drive, or to transfer parameters to
systems that are identical to the original system.
copy a partial parameter set from the control panel to a drive (dL P Download
Partial). The partial set does not include user sets, internal motor parameters,
parameters 99059909, 1605, 1607, 5201, nor any Group 51: EXT COMM
MODULE and Group 53: EFB PROTOCOL parameters.
The source and target drives and their motor sizes do not need to be the same.
copy USER S1 parameters from the control panel to the drive (dL u1 Download
User Set 1). A user set includes Group 99: START-UP DATA parameters and the
internal motor parameters.
The function is only shown on the menu when User Set 1 has been first saved
using parameter 9902 APPLIC MACRO (see section User parameter sets on page
88) and then uploaded to panel.
copy USER S2 parameters from the control panel to the drive (dL u2 Download
User Set 2). As dL u1 Download User Set 1 above.
start, stop, change the direction and switch between local and remote control.

Control panels

76

ACS550-01/U1 Users Manual

How to upload and download parameters


For the upload and download functions available, see above.
Step
1.

Action

Display

Go to the Main menu by pressing


if you are in the Output mode,
otherwise by pressing
repeatedly until you see MENU at the bottom.

LOC

PAr

MENU

2.

If the panel is not in the Copy mode (CoPY not visible), press key
or
until you see CoPY.
Press

3.

To upload all parameters (including user sets) from the drive to the control
panel, step to uL with keys
and
.

LOC

LOC

LOC

CoPY
dL u1
MENU

FWD

MENU

FWD

uL
uL 50
dL A
dL 50
MENU

Press
. During the transfer, the display shows the transfer status as a
percentage of completion.

LOC

FWD

FWD
%

FWD

To perform downloads, step to the appropriate operation (here dL A,


Download All, is used as an example) with keys
and
.

LOC

MENU

Press
. During the transfer, the display shows the transfer status as a
percentage of completion.

LOC

FWD
%

FWD

Basic Control Panel alarm codes


In addition to the faults and alarms generated by the drive (see chapter Diagnostics),
the Basic Control Panel indicates control panel alarms with a code of form A5xxx.
See section Alarm codes (Basic Control Panel) on page 269 for a list of the alarm
codes and descriptions.

Control panels

ACS550-01/U1 Users Manual

77

Application macros
Macros change a group of parameters to new, predefined values. Use macros to
minimize the need for manual editing of parameters. Selecting a macro sets all other
parameters to their default values, except:
Group 99: START-UP DATA parameters (except parameter 9904)
1602 PARAMETER LOCK
1607 PARAM

SAVE

3018 COMM FAULT FUNC and 3019

COMM FAULT TIME

9802 COMM PROT SEL


Group 50: ENCODER Group 53: EFB PROTOCOL parameters
Group 29: MAINTENANCE TRIG parameters.
After selecting a macro, you can make additional parameter changes manually with
the control panel.
You enable application macros by setting the value for parameter 9902
By default, 1, ABB STANDARD, is the enabled macro.

APPLIC

MACRO.

The following sections describe each of the application macros and provide a
connection example for each macro.
The last section in this chapter, Macro default values for parameters, lists the
parameters that the macros change and the default values established by each
macro.

Application macros

78

ACS550-01/U1 Users Manual

ABB Standard macro


This is the default macro. It provides a general purpose, 2-wire I/O configuration,
with three (3) constant speeds. Parameter values are the default values defined in
section Complete parameter list on page 91.
Connection example:
X1
110 kohm 1

SCR
AI1
AGND
10V
AI2
AGND
AO1
AO2
AGND

Signal cable shield (screen)


External frequency reference 1: 010 V1
Analog input circuit common
Reference voltage 10 V DC
Not used
Analog input circuit common
Output frequency: 020 mA
Output current: 020 mA
Analog output circuit common

10
11
12
13
14
15
16
17
18

24V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6

Auxiliary voltage output +24 V DC


Auxiliary voltage output common
Digital input common for all
Start/Stop: Activate to start
Fwd/Rev: Activate to reverse rotation direction
Constant speed selection2
Constant speed selection2
Ramp pair selection: Activate to select 2nd acc/dec ramp pair
Not used

19
20
21
22
23
24
25
26
27

RO1C
RO1A
RO1B
RO2C
RO2A
RO2B
RO3C
RO3A
RO3B

Relay output 1, programmable


Default operation:
Ready =>19 connected to 21
Relay output 2, programmable
Default operation:
Running =>22 connected to 24
Relay output 3, programmable
Default operation:
Fault (-1) =>25 connected to 27
(Fault => 25 connected to 26)

DI3
0
1
0
1

DI4
0
0
1
1

Output signals
Jumper setting
Analog output AO1: Frequency
J1
Analog output AO2: Current
AI1: 010 V
Relay output 1: Ready
AI2: 0(4)20 mA
Relay output 2: Running
or
J1
Relay output 3: Fault (-1)
AI1: 010 V
ON

1 2

Application macros

Output
Reference through AI1
CONST SPEED 1 (1202)
CONST SPEED 2 (1203)
CONST SPEED 3 (1204)

ON

Input signals
Analog reference (AI1)
Start, stop and direction (DI1,2)
Constant speed selection (DI3,4)
Ramp pair (1 of 2) selection (DI5)

Note 1. The external reference is


used as a speed reference if a vector
mode is selected.
Note 2. Code:
0 = open, 1 = connected

ON

2
3
4
5
6
7
8
9

AI2: 0(4)20 mA

ACS550-01/U1 Users Manual

79

3-wire macro
This macro is used when the drive is controlled using momentary push-buttons. It
provides three (3) constant speeds. To enable, set the value of parameter 9902 to
2 (3-WIRE).
Note: When the stop input (DI2) is deactivated (no input), the control panel start/stop
buttons are disabled.
Connection example:
X1
110 kohm 1

2
3
4
5
6
7
8
9

SCR
AI1
AGND
10V
AI2
AGND
AO1
AO2
AGND

Signal cable shield (screen)


External speed reference 1: 010 V
Analog input circuit common
Reference voltage 10 V DC
Not used
Analog input circuit common
Motor output speed: 020 mA
Output current: 020 mA
Analog output circuit common

10
11
12
13
14
15
16
17
18

24V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6

Auxiliary voltage output +24 V DC


Auxiliary voltage output common
Digital input common for all
Start: Momentary activation with DI2 activated starts the drive
Stop: Momentary deactivation stops the drive
Fwd/Rev: Activation reverses rotation direction
Constant speed selection1
Constant speed selection1
Not used

19
20
21
22
23
24
25
26
27

RO1C
RO1A
RO1B
RO2C
RO2A
RO2B
RO3C
RO3A
RO3B

Relay output 1, programmable


Default operation:
Ready =>19 connected to 21
Relay output 2, programmable
Default operation:
Running =>22 connected to 24
Relay output 3, programmable
Default operation:
Fault (-1) =>25 connected to 27
(Fault => 25 connected to 26)

Output signals
Analog output AO1: Speed
Analog output AO2: Current
Relay output 1: Ready
Relay output 2: Running
Relay output 3: Fault (-1)

DI5
0
0
1
1

Output
Reference through AI1
CONST SPEED 1 (1202)
CONST SPEED 2 (1203)
CONST SPEED 3 (1204)
Jumper setting
J1
AI1: 010 V
AI2: 0(4)20 mA

ON

DI4
0
1
0
1

ON

Input signals
Analog reference (AI1)
Start, stop and direction (DI1,2,3)
Constant speed selection (DI4,5)

Note 1. Code:
0 = open, 1 = connected

or
J1
ON

1 2

AI1: 010 V
AI2: 0(4)20 mA

Application macros

80

ACS550-01/U1 Users Manual

Alternate macro
This macro provides an I/O configuration adopted to a sequence of DI control
signals used when alternating the rotation direction of the motor. To enable, set the
value of parameter 9902 to 3 (ALTERNATE).
Connection example:
X1
2
3
4
5
6
7
8
9

SCR
AI1
AGND
10V
AI2
AGND
AO1
AO2
AGND

Signal cable shield (screen)


External speed reference 1: 010 V
Analog input circuit common
Reference voltage 10 V DC
Not used
Analog input circuit common
Motor output speed: 020 mA
Output current: 020 mA
Analog output circuit common

10
11
12
13
14
15
16
17
18

24V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6

Auxiliary voltage output +24 V DC


Auxiliary voltage output common
Digital input common for all
Start fwd: If DI1 state is the same as DI2, the drive stops
Start reverse
Constant speed selection1
Constant speed selection1
Ramp pair selection: Activation selects 2nd acc/dec ramp pair
Run enable: Deactivation always stops the drive

19
20
21
22
23
24
25
26
27

RO1C
RO1A
RO1B
RO2C
RO2A
RO2B
RO3C
RO3A
RO3B

110 kohm 1

DI3
0
1
0
1

Output signals
Analog output AO1: Speed
Analog output AO2: Current
Relay output 1: Ready
Relay output 2: Running
Relay output 3: Fault (-1)

DI4
0
0
1
1

Output
Reference through AI1
CONST SPEED 1 (1202)
CONST SPEED 2 (1203)
CONST SPEED 3 (1204)

or
J1
ON

1 2

Application macros

Jumper setting
J1
AI1: 010 V
AI2: 0(4)20 mA

ON

Input signals
Analog reference (AI1)
Start, stop and direction (DI1,2)
Constant speed selection (DI3,4)
Ramp pair 1/2 selection (DI5)
Run enable (DI6)

Note 1. Code:
0 = open, 1 = connected

ON

Relay output 1, programmable


Default operation:
Ready =>19 connected to 21
Relay output 2, programmable
Default operation:
Running =>22 connected to 24
Relay output 3, programmable
Default operation:
Fault (-1) =>25 connected to 27
(Fault => 25 connected to 26)

AI1: 010 V
AI2: 0(4)20 mA

ACS550-01/U1 Users Manual

81

Motor Potentiometer macro


This macro provides a cost-effective interface for PLCs that vary the speed of the
motor using only digital signals. To enable, set the value of parameter 9902 to
4 (MOTOR POT).
Connection example:
SCR
AI1
AGND
10V
AI2
AGND
AO1
AO2
AGND

Signal cable shield (screen)


Not used
Analog input circuit common
Reference voltage 10 V DC
Not used
Analog input circuit common
Motor output speed: 020 mA
Output current: 020 mA
Analog output circuit common

10
11
12
13
14
15
16
17
18

24V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6

Auxiliary voltage output +24 V DC


Auxiliary voltage output common
Digital input common for all
Start/stop: Activation starts the drive.
Forward/reverse: Activation reverses rotation direction.
Reference up: Activation increases the reference1
Reference down: Activation decreases the reference1
Constant speed 1: 1202
Run enable: Deactivation always stops the drive.

19
20
21
22
23
24
25
26
27

RO1C
RO1A
RO1B
RO2C
RO2A
RO2B
RO3C
RO3A
RO3B

Relay output 1, programmable


Default operation:
Ready =>19 connected to 21
Relay output 2, programmable
Default operation:
Running =>22 connected to 24
Relay output 3, programmable
Default operation:
Fault (-1) =>25 connected to 27
(Fault => 25 connected to 26)

Output signals
Analog output AO1: Speed
Analog output AO2: Current
Relay output 1: Ready
Relay output 2: Running
Relay output 3: Fault (-1)

Jumper setting
J1
AI1: 010 V
AI2: 0(4)20 mA

ON

Input signals
Start, stop and direction (DI1,2)
Reference up/down (DI3,4)
Constant speed selection (DI5)
Run enable (DI6)

Note 1. For DI3 and DI4:


If both are active or inactive the
speed reference is unchanged.
The existing speed reference is
stored during stop or power down.
Note 2.
Settings of the ramp times with
acceleration and deceleration time
2 (parameters 2205 and 2206).

ON

X1
1
2
3
4
5
6
7
8
9

or

J1
ON

1 2

AI1: 010 V
AI2: 0(4)20 mA

Application macros

82

ACS550-01/U1 Users Manual

Hand-Auto macro
This macro provides an I/O configuration that is typically used in HVAC applications.
To enable, set the value of parameter 9902 to 5 (HAND/AUTO).
Note: Parameter 2108

START INHIBIT

must remain in the default setting, 0 (OFF).

Connection example:
X1
2
3
4
5
6
7
8
9

SCR
AI1
AGND
10V
AI2
AGND
AO1
AO2
AGND

Signal cable shield (screen)


External reference 1: 010 V (Hand Control)
Analog input circuit common
Reference voltage 10 V DC
External reference 2: 020 mA (Auto Control)
Analog input circuit common
Motor output speed: 020 mA
Output current: 0 20 mA
Analog output circuit common

10
11
12
13
14
15
16
17
18

24V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6

Auxiliary voltage output +24 V DC


Auxiliary voltage output common
Digital input common for all
Start/Stop (Hand): Activation starts the drive
Forward/Reverse (Hand): Activation reverses rotation direction
EXT1/EXT2 Selection: Activation selects auto control
Run enable: Deactivation always stops the drive
Forward/Reverse (Auto): Activation reverses rotation direction
Start/Stop (Auto): Activation starts the drive

19
20
21
22
23
24
25
26
27

RO1C
RO1A
RO1B
RO2C
RO2A
RO2B
RO3C
RO3A
RO3B

110 kohm 1

Output signals
Analog output AO1: Speed
Analog output AO2: Current
Relay output 1: Ready
Relay output 2: Running
Relay output 3: Fault (-1)

AI2: 0(4)20 mA

or
J1
ON

1 2

Application macros

Jumper setting
J1
AI1: 010 V
ON

Input signals
Two analog references (AI1, 2)
Start/stop hand/auto (DI1, 6)
Direction hand/auto (DI2, 5)
Control location selection (DI3)
Run enable (DI4)

Note 1.
The sensor for AI2 is powered
externally. See the manufacturers
instructions. To use sensors
supplied by the drive aux. voltage
output, see page 86.

ON

Relay output 1, programmable


Default operation:
Ready =>19 connected to 21
Relay output 2, programmable
Default operation:
Running =>22 connected to 24
Relay output 3, programmable
Default operation:
Fault (-1) =>25 connected to 27
(Fault => 25 connected to 26)

AI1: 010 V
AI2: 0(4)20 mA

ACS550-01/U1 Users Manual

83

PID Control macro


This macro provides parameter settings for closed-loop control systems such as
pressure control, flow control, etc. To enable, set the value of parameter 9902 to
6 (PID CONTROL).
Note: Parameter 2108 START INHIBIT must remain in the default setting, 0 (OFF).
Connection example:
X1
110 kohm 1

SCR
AI1
AGND
10V
AI2
AGND
AO1
AO2
AGND

10
11
12
13
14
15
16
17
18

24V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6

19
20
21
22
23
24
25
26
27

RO1C
RO1A
RO1B
RO2C
RO2A
RO2B
RO3C
RO3A
RO3B

Signal cable shield (screen)


External ref. 1 (Manual) or Ext ref. 2 (PID): 010 V1
Analog input circuit common
Note 1.
Reference voltage 10 V DC
Manual: 010V => speed reference
Actual signal (PID): 420 mA
PID: 010V => 0100% PID
Analog input circuit common
setpoint
Motor output speed: 020 mA
Note 3.
Output current: 020 mA
The sensor for AI2 is powered exterAnalog output circuit common
nally. See the manufacturers instructions. To use sensors supplied by the
Auxiliary voltage output +24 V DC
drive aux. voltage output, see page 86.
Auxiliary voltage output common
Digital input common for all
Start/Stop (Hand): Activation starts the drive
EXT1/EXT2 selection: Activation selects PID control
Constant speed selection 1: (Not used in PID control)2
Constant speed selection 2: (Not used in PID control)2
Run enable: Deactivation always stops the drive
Start/Stop (PID): Activation starts the drive
Relay output 1, programmable
Default operation:
Ready =>19 connected to 21
Relay output 2, programmable
Default operation:
Running =>22 connected to 24
Relay output 3, programmable
Default operation:
Fault (-1) =>25 connected to 27
(Fault => 25 connected to 26)

DI3
0
1
0
1

Output signals
Analog output AO1: Speed
Analog output AO2: Current
Relay output 1: Ready
Relay output 2: Running
Relay output 3: Fault (-1)

DI4
0
0
1
1

Output
Reference through AI1
CONST SPEED 1 (1202)
CONST SPEED 2 (1203)
CONST SPEED 3 (1204)

Jumper setting
J1
AI1: 010 V
AI2: 0(4)20 mA

ON

or

J1
ON

1 2

Input signals
Analog reference (AI1)
Actual value (AI2)
Start/stop hand/PID (DI1, 6)
EXT1/EXT2 selection (DI2)
Constant speed selection (DI3, 4)
Run enable (DI5)

Note 2. Code:
0 = open, 1 = connected

ON

2
3
4
5
6
7
8
9

AI1: 010 V
AI2: 0(4)20 mA

Note: Use the following switch-on order:


1. EXT1/EXT2
2. Run Enable
3. Start.

Application macros

84

ACS550-01/U1 Users Manual

PFC macro
This macro provides parameter settings for pump and fan control (PFC) applications.
To enable, set the value of parameter 9902 to 7 (PFC CONTROL).
Note: Parameter 2108

START INHIBIT

must remain in the default setting, 0 (OFF).

Connection example:
X1
2
3
4
5
6
7
8
9

SCR
AI1
AGND
10V
AI2
AGND
AO1
AO2
AGND

Signal cable shield (screen)


External ref. 1 (Manual) or Ext ref. 2 (PID/PFC): 010 V1
Analog input circuit common
Note 1.
Reference voltage 10 V DC
Manual: 0 10V => 050 Hz
Actual signal (PID): 4 20 mA
PID/PFC: 0 10V => 0100% PID
Analog input circuit common
setpoint
Output frequency: 020 mA
Actual 1 (PI controller actual value): 0(4)20 mA
Analog output circuit common

10
11
12
13
14
15
16
17
18

24V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6

19
20
21
22
23
24
25
26
27

RO1C
RO1A
RO1B
RO2C
RO2A
RO2B
RO3C
RO3A
RO3B

Auxiliary voltage output +24 V DC


Auxiliary voltage output common
Digital input common for all
Start/Stop (Manual): Activation starts the drive
Run enable: Deactivation always stops the drive
EXT1/EXT2 selection: Activation selects PFC control
Interlock: Deactivation always stops the drive
Interlock: Deactivation stops constant speed motor
Start/Stop (PFC): Activation starts the drive
Note 2.
Relay output 1, programmable
The sensor for AI2 is powered exterDefault operation:
nally. See the manufacturers instrucRunning =>19 connected to 21 tions. To use sensors supplied by the
Relay output 2, programmable
drive aux. voltage output, see page 86.
Default operation:
Fault (-1) =>22 connected to 24 (Fault => 22 connected to 23)

110 kohm 1

Output signals
Jumper setting
Analog output AO1: Frequency
J1
Analog output AO2: Actual 1
AI1: 010 V
Relay output 1: Running
AI2: 0(4)20 mA
Relay output 2: Fault (-1)
or
J1
Relay output 3: Aux. motor ON
AI1: 010 V
ON

Input signals
Analog ref. and actual (AI1, 2)
Start/stop manual/PFC (DI1, 6)
Run enable (DI2)
EXT1/EXT2 selection (DI3)
Interlock (DI4, 5)

ON

Relay output 3, programmable


Default operation:
Auxiliary motor switched on=>25 connected to 27

2. Run Enable
3. Start.

Application macros

ON

1 2

Note: Use the following switch-on order:


1. EXT1/EXT2

AI2: 0(4)20 mA

ACS550-01/U1 Users Manual

85

Torque Control macro


This macro provides parameter settings for applications that require torque control of
the motor. Control can also be switched to speed control. To enable, set the value of
parameter 9902 to 8 (TORQUE CTRL).
Connection example:
X1
110 kohm 1
2
3
4
2
5
6
7
8
9

SCR
AI1
AGND
10V
AI2
AGND
AO1
AO2
AGND

Signal cable shield (screen)


External speed reference 1: 010 V
Analog input circuit common
Reference voltage 10 V DC
External torque reference: 420 mA
Analog input circuit common
Motor output speed: 020 mA
Note 1.
Output current: 020 mA
Reverses rotation direction in
Analog output circuit common
speed control.

10
11
12
13
14
15
16
17
18

24V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6

Reverses torque direction in


Auxiliary voltage output +24 V DC
torque control.
Auxiliary voltage output common
Digital input common for all
Start/stop: Activation starts the drive.
Forward/reverse: Activation reverses direction1
Speed/torque control: Activation selects torque control
Constant speed 1: 1202
Ramp pair selection: Activate to select 2nd acc/dec ramp pair
Run enable: Deactivation always stops the drive

19
20
21
22
23
24
25
26
27

RO1C
RO1A
RO1B
RO2C
RO2A
RO2B
RO3C
RO3A
RO3B

Output signals
Analog output AO1: Speed
Analog output AO2: Current
Relay output 1: Ready
Relay output 2: Running
Relay output 3: Fault (-1)

Jumper setting
J1
AI1: 010 V
AI2: 0(4)20 mA

ON

or

J1
ON

1 2

Input signals
Two analog references (AI1, 2)
Start/stop and direction (DI1, 2)
Speed/torque control (DI3)
Constant speed selection (DI4)
Ramp pair 1/2 selection (DI5)
Run enable (DI6)

Note 2.
The sensor for AI2 is powered
externally. See the manufacturers
instructions. To use sensors supplied
by the drive aux. voltage output, see
page 86.

ON

Relay output 1, programmable


Default operation:
Ready =>19 connected to 21
Relay output 2, programmable
Default operation:
Running =>22 connected to 24
Relay output 3, programmable
Default operation:
Fault (-1) =>25 connected to 27
(Fault => 25 connected to 26)

AI1: 010 V
AI2: 0(4)20 mA

Application macros

86

ACS550-01/U1 Users Manual

Connection examples of two-wire and three-wire sensors


Many applications use process PI(D) and need a feedback signal from the process.
The feedback signal is typically connected to analog input 2 (AI2).
The macro wiring diagrams for each macro earlier in this chapter use an externally
powered sensor (connections not shown). The figures below give examples of
connections using a two-wire or three-wire sensor/transmitter supplied by the drive
auxiliary voltage output.
Two-wire sensor/transmitter
P
I

420 mA

X1 / control board
5 AI2
Process actual value measurement,
6 AGND 0(4) 20 mA, Rin = 100 ohm

X1 / control board
10 +24 V Auxiliary voltage output, non-isolated,
11 GND 24 V DC, 250 mA

Note: The sensor is supplied through its current output and the drive feeds the supply voltage (+24 V).
Thus the output signal must be 420 mA, not 020 mA

Three-wire sensor/transmitter

P
I

Application macros

OUT

0(4)20 mA

X1 / control board
5 AI2
Process actual value measurement,
6 AGND 0(4) 20 mA, Rin = 100 ohm

X1 / control board
10 +24 V Auxiliary voltage output, non-isolated,
11 GND 24 V DC, 250 mA

ACS550-01/U1 Users Manual

87

Connection for obtaining 010 V from analog outputs


To obtain 010 V from analog outputs, connect a 500 ohm resistor (or two 1 kohm
resistors in parallel) between the analog output and analog output circuit common
AGND.
Examples for analog output 2 AO2 are shown in the figure below.

010 V

X1
8

AO2

Analog output 2. Default output 020 mA.

AGND

Analog input circuit common. Internally connected to chassis


through a 1 Mohm resistor.

500 ohm

010 V

X1

1 kohm

AO2

Analog output 2. Default output 020 mA.

AGND

Analog input circuit common. Internally connected to chassis


through a 1 Mohm resistor.

1 kohm

Application macros

88

ACS550-01/U1 Users Manual

User parameter sets


In addition to the standard application macros, it is possible to save two user
parameter sets into the permanent memory and load them at a later time. A user
parameter set consists of the user parameter settings, including Group 99: STARTUP DATA, and the results of the motor identification. The panel reference is also
saved if the user parameter set is saved and loaded in local control. The remote
control setting is saved into the user parameter set, but the local control setting is
not.
The steps below show how to save and load User Parameter Set 1. The procedure
for User Parameter Set 2 is identical, only the parameter 9902 values are different.
To save User Parameter Set 1:
Adjust the parameters. Perform the motor identification if it is needed in the
application but it is not done yet.
Save the parameter settings and the results of the motor identification to the
permanent memory by changing parameter 9902 to -1 (USER S1 SAVE).
Press

SAVE

(Assistant Control Panel) or

MENU
ENTER

(Basic Control Panel).

To load User Parameter Set 1:


Change parameter 9902 to 0 (USER S1 LOAD).
Press

SAVE

(Assistant Control Panel) or

MENU
ENTER

(Basic Control Panel) to load.

The user parameter set can also be switched through digital inputs (see parameter
1605).
Note: Loading the user parameter set restores the parameter settings including
Group 99: START-UP DATA and the results of the motor identification. Check that
the settings correspond to the motor used.
Hint: The user can for example switch the drive between two motors without having
to adjust the motor parameters and to repeat the motor identification every time the
motor is changed. The user needs only to adjust the settings and perform the motor
identification once for each motor and then to save the data as two user parameter
sets. When the motor is changed, only the corresponding user parameter set needs
to be loaded, and the drive is ready to operate.

Application macros

ACS550-01/U1 Users Manual

89

Macro default values for parameters


Parameter default values are listed in section Complete parameter list on page 91.
Changing from the default macro (ABB Standard), that is, editing the value of
parameter 9902, changes the parameter default values as defined in the following
tables.
Note: There are two sets of values because the defaults are configured for 50 Hz/
IEC compliance (ACS550-01) and 60 Hz/NEMA compliance (ACS550-U1).
ACS550-01
Parameter
9902 APPLIC MACRO
9904 MOTOR CTRL
1001
1002
1003
1102
1103
1106
1201
1304
1401
1402
1403
1501

Motor
PID
PFC
Torque
Potenti- Hand-auto
Control
Control
Control
ometer
1=
2=
3=
4=
5=
6=
7=
8=
ABB STANDARD 3-WIRE
ALTERNATE MOTOR POT HAND/AUTO PID CONTROL PFC CONTROL TORQUE CTRL
3 = SCALAR: 1 = VECTOR: 1 = VECTOR: 1 = VECTOR: 1 = VECTOR: 1 = VECTOR: 3 = SCALAR: 2 = VECTOR:
ABB
Standard

MODE

FREQ

EXT1 COMMANDS
EXT2 COMMANDS

2 = DI1,2
0 = NOT SEL
3 = REQUEST
0 = EXT1
1 = AI1

3-wire

SPEED

OUTPUT FREQ SPEED

SPEED

SPEED

SPEED

FREQ

TORQUE

SPEED

SPEED

SPEED

SPEED

104 =

104 =

104 =

104 =

104 =

CURRENT

CURRENT

CURRENT

CURRENT

CURRENT

SPEED

SPEED

SPEED

SPEED

OUTPUT FREQ SPEED

130 =
104 =
PID 1 FBK
CURRENT
MINIMUM AO2
0.0 mA
0.0 mA
0.0 mA
0.0 mA
0.0 mA
0.0 mA
4.0 mA
0.0 mA
RUN ENABLE
0 = NOT SEL 0 = NOT SEL 6 = DI6
6 = DI6
4 = DI4
5 = DI5
2 = DI2
6 = DI6
ACC/DEC 1/2 SEL 5 = DI5
0 = NOT SEL 5 = DI5
0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 5 = DI5
SUPERV 1 PARAM 103 = 0103 102 = 0102 102 = 0102 102 = 0102 102 = 0102 102 = 0102 103 = 0103 102 = 0102
CURRENT

OUTPUT FREQ SPEED

3401 SIGNAL1 PARAM

1.0
INTEGRATION TIME 60.0 s
GAIN
1.0
INTEGRATION TIME 60.0 s
PFC ENABLE
0 = NOT SEL
GAIN

OUTPUT FREQ SPEED

103 = 0103 102 = 0102 102 = 0102 102 = 0102 102 = 0102 102 = 0102 103 = 0103 102 = 0102
OUTPUT FREQ SPEED

4001
4002
4101
4102
8123

SPEED

4 = DI1P,2P,3 9 = DI1F,2 R 2 = DI1,2


2 = DI1,2
1 = DI1
1 = DI1
2 = DI1,2
0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 7 = DI6,5
6 = DI6
6 = DI6
2 = DI1,2
DIRECTION
3 = REQUEST 3 = REQUEST 3 = REQUEST 3 = REQUEST 1 = FORWARD 1 = FORWARD 3 = REQUEST
EXT1/EXT2 SEL
0 = EXT1
0 = EXT1
0 = EXT1
3 = DI3
2 = DI2
3 = DI3
3 = DI3
REF1 SELECT
1 = AI1
1 = AI1
12 =
1 = AI1
1 = AI1
1 = AI1
1 = AI1
DI3U,4D(NC)
REF2 SELECT
2 = AI2
2 = AI2
2 = AI2
2 = AI2
2 = AI2
19 = PID1OUT 19 = PID1OUT 2 = AI2
CONST SPEED SEL 9 = DI3,4
10 = DI4,5 9 = DI3,4
5 = DI5
0 = NOT SEL 9 = DI3,4
0 = NOT SEL 4 = DI4
MINIMUM AI2
0.0%
0.0%
0.0%
0.0%
20.0%
20.0%
20.0%
20.0%
RELAY OUTPUT 1 1 = READY
1 = READY 1 = READY 1 = READY 1 = READY 1 = READY 2 = RUN
1 = READY
RELAY OUTPUT 2 2 = RUN
2 = RUN
2 = RUN
2 = RUN
2 = RUN
2 = RUN
3 = FAULT(-1) 2 = RUN
RELAY OUTPUT 3 3 = FAULT(-1) 3 = FAULT(-1) 3 = FAULT(-1) 3 = FAULT(-1) 3 = FAULT(-1) 3 = FAULT(-1) 31 = PFC
3 = FAULT(-1)
AO1 CONTENT SEL 103 = 0103 102 = 0102 102 = 0102 102 = 0102 102 = 0102 102 = 0102 103 = 0103 102 = 0102

1507 AO2 CONTENT SEL 104 =


1510
1601
2201
3201

Alternate

SPEED

SPEED

SPEED

SPEED

OUTPUT FREQ SPEED

1.0
1.0
1.0
1.0
1.0
2.5
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
3.0 s
1.0
1.0
1.0
1.0
1.0
2.5
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
3.0 s
0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 1 = ACTIVE

1.0
60.0 s
1.0
60.0 s
0 = NOT SEL

Application macros

90

ACS550-01/U1 Users Manual

ACS550-U1
Parameter
9902 APPLIC MACRO
9904 MOTOR CTRL
1001
1002
1003
1102
1103
1106
1201
1304
1401
1402
1403
1501

Motor
PID
PFC
Torque
Potenti- Hand-auto
Control
Control
Control
ometer
1=
2=
3=
4=
5=
6=
7=
8=
ABB STANDARD 3-WIRE
ALTERNATE MOTOR POT HAND/AUTO PID CONTROL PFC CONTROL TORQUE CTRL
3 = SCALAR: 1 = VECTOR: 1 = VECTOR: 1 = VECTOR: 1 = VECTOR: 1 = VECTOR: 3 = SCALAR: 2 = VECTOR:
ABB
Standard

MODE
FREQ
EXT1 COMMANDS 2 = DI1,2
EXT2 COMMANDS

3-wire

SPEED
SPEED
SPEED
4 = DI1P,2P,3 9 = DI1F,2R 2 = DI1,2

SPEED
1 = DI1

FREQ
1 = DI1

TORQUE
2 = DI1,2

0 = NOT SEL
3 = REQUEST
0 = EXT1
1 = AI1

OUTPUT FREQ SPEED

SPEED

SPEED

SPEED

SPEED

104 =

104 =

104 =

104 =

104 =

CURRENT

CURRENT

CURRENT

CURRENT

CURRENT

SPEED

SPEED

SPEED

SPEED

OUTPUT FREQ SPEED

130 =
104 =
PID 1 FBK
CURRENT
MINIMUM AO2
0.0 mA
0.0 mA
0.0 mA
0.0 mA
0.0 mA
0.0 mA
4.0 mA
0.0 mA
RUN ENABLE
0 = NOT SEL 0 = NOT SEL 6 = DI6
6 = DI6
4 = DI4
5 = DI5
2 = DI2
6 = DI6
ACC/DEC 1/2 SEL 5 = DI5
0 = NOT SEL 5 = DI5
0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 5 = DI5
SUPERV 1 PARAM 103 = 0103 102 = 0102 102 = 0102 102 = 0102 102 = 0102 102 = 0102 103 = 0103 102 = 0102
CURRENT

OUTPUT FREQ SPEED

3401 SIGNAL1 PARAM

1.0
INTEGRATION TIME 60.0 s
GAIN
1.0
INTEGRATION TIME 60.0 s
PFC ENABLE
0 = NOT SEL
GAIN

Application macros

OUTPUT FREQ SPEED

103 = 0103 102 = 0102 102 = 0102 102 = 0102 102 = 0102 102 = 0102 103 = 0103 102 = 0102
OUTPUT FREQ SPEED

4001
4002
4101
4102
8123

SPEED
2 = DI1,2

0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 7 = DI6,5


6 = DI6
6 = DI6
2 = DI1,2
3 = REQUEST 3 = REQUEST 3 = REQUEST 3 = REQUEST 1 = FORWARD 1 = FORWARD 3 = REQUEST
EXT1/EXT2 SEL
0 = EXT1
0 = EXT1
0 = EXT1
3 = DI3
2 = DI2
3 = DI3
3 = DI3
REF1 SELECT
1 = AI1
1 = AI1
12 =
1 = AI1
1 = AI1
1 = AI1
1 = AI1
DI3U,4D(NC)
REF2 SELECT
2 = AI2
2 = AI2
2 = AI2
2 = AI2
2 = AI2
19 = PID1OUT 19 = PID1OUT 2 = AI2
CONST SPEED SEL 9 = DI3,4
10 = DI4,5 9 = DI3,4
5 = DI5
0 = NOT SEL 9 = DI3,4
0 = NOT SEL 4 = DI4
MINIMUM AI2
0.0%
0.0%
0.0%
0.0%
20.0%
20.0%
20.0%
20.0%
RELAY OUTPUT 1 1 = READY
1 = READY 1 = READY 1 = READY 1 = READY 1 = READY 2 = RUN
1 = READY
RELAY OUTPUT 2 2 = RUN
2 = RUN
2 = RUN
2 = RUN
2 = RUN
2 = RUN
3 = FAULT(-1) 2 = RUN
RELAY OUTPUT 3 3 = FAULT(-1) 3 = FAULT(-1) 3 = FAULT(-1) 3 = FAULT(-1) 3 = FAULT(-1) 3 = FAULT(-1) 31 = PFC
3 = FAULT(-1)
AO1 CONTENT SEL 103 = 0103 102 = 0102 102 = 0102 102 = 0102 102 = 0102 102 = 0102 103 = 0103 102 = 0102
DIRECTION

1507 AO2 CONTENT SEL 104 =


1510
1601
2201
3201

Alternate

SPEED

SPEED

SPEED

SPEED

OUTPUT FREQ SPEED

1.0
1.0
1.0
1.0
1.0
2.5
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
3.0 s
1.0
1.0
1.0
1.0
1.0
2.5
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
3.0 s
0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 1 = ACTIVE

1.0
60.0 s
1.0
60.0 s
0 = NOT SEL

ACS550-01/U1 Users Manual

91

Parameters
Complete parameter list
The following table lists all parameters. Table header abbreviations are:
S = Parameters can be modified only when the drive is stopped.
User = Space to enter desired parameter values.
Some values depend on the construction as indicated in the table by
-01: = Setup and parts specific to IEC installation and compliance or
-U1: = Setup and parts specific to US installation and NEMA compliance.
Refer to the type designation on the drive, for example ACS550-01-08A8-4.
Code

Name

Range

Resolution

Default

User

Group 99: START-UP DATA


9901

LANGUAGE

016 / 03

0 (ENGLISH)

9902

APPLIC MACRO

-38, 31

1 (ABB STANDARD)

9904

MOTOR CTRL MODE

1 = VECTOR:SPEED, 2 = VECTOR:TORQUE, 1
3 = SCALAR:FREQ

3 (SCALAR:FREQ)

9905

MOTOR NOM VOLT

-01-yyyy-2: 115345 V /
-U1-yyyy-2: 115345 V

-01-yyyy-2: 230 V /
-U1-yyyy-2: 230 V

1V

-01-yyyy-4: 200600 V /
-U1-yyyy-4: 230690 V

-01:-yyyy-4 400 V /
-U1-yyyy-4: 460 V

-U1-yyyy-6: 288862 V

-U1-yyyy-6: 575 V

9906

MOTOR NOM CURR

0.2 I2hd 2.0 I2hd

0.1 A

1.0 I2hd

9907

MOTOR NOM FREQ

10.0500.0 Hz

0.1 Hz

-01: 50.0 Hz /
-U1: 60.0 Hz

9908

MOTOR NOM SPEED

5030000 rpm

1 rpm

Size dependent

9909

MOTOR NOM POWER

0.23.0 Phd

-01: 0.1 kW /
-U1: 0.1 hp

1.0 Phd

9910

ID RUN

0 = OFF/IDMAGN, 1 = ON

0 (OFF/IDMAGN)

9915

MOTOR COSPHI

0 = IDENTIFIED, 0.010.97

0.01

0 (IDENTIFIED)

-3000030000 rpm

1 rpm

Group 01: OPERATING DATA


& DIR

0101

SPEED

0102

SPEED

030000 rpm

1 rpm

0103

OUTPUT FREQ

0.0500.0 Hz

0.1 Hz

0104

CURRENT

0.02.0 I2hd

0.1 A

0105

TORQUE

-200.0200.0%

0.1%

0106

POWER

-2.02.0 Phd

0.1 kW

0107

DC BUS VOLTAGE

02.5 VdN

1V

0109

OUTPUT VOLTAGE

02.0 VdN

1V

0110

DRIVE TEMP

0.0150.0 C

0.1 C

0.1 Hz / 1 rpm -

0111

EXTERNAL REF

0.0500.0 Hz / 030000 rpm

0112

EXTERNAL REF

0.0100.0% (0.0600.0% for torque) 0.1%

0113

CTRL LOCATION

0 = LOCAL, 1 = EXT1, 2 = EXT2

Parameters

92

ACS550-01/U1 Users Manual

Code

Name

Range

Resolution

Default

0114

RUN TIME (R)

0115

KWH COUNTER (R)

09999 h

1h

065535 kWh

1 kWh

0116

APPL BLK OUTPUT

0118

DI

0119
0120

0.0100.0% (0.0600.0% for torque) 0.1%

1-3 STATUS

000111 (07 decimal)

DI

4-6 STATUS

000111 (07 decimal)

AI

0.0100.0%

0.1%

0121

AI

0122

RO

0123
0124

0.0100.0%

0.1%

1-3 STATUS

000111 (07 decimal)

RO

4-6 STATUS

000111 (07 decimal)

AO

0.020.0 mA

0.1 mA

0125

AO

0.020.0 mA

0.1 mA

0126

PID

1 OUTPUT

-1000.01000.0%

0.1%

0127

PID

2 OUTPUT

-100.0100.0%

0.1%

0128

PID

1 SETPNT

Unit and scale defined by par. 4006/


4106 and 4007/4107

0129

PID

2 SETPNT

Unit and scale defined by par. 4206 and


4207

0130

PID

1 FBK

Unit and scale defined by par. 4006/


4106 and 4007/4107

0131

PID

2 FBK

Unit and scale defined by par. 4206 and 4207

0132

PID

1 DEVIATION

Unit and scale defined by par. 4006/


4106 and 4007/4107

0133

PID

2 DEVIATION

Unit and scale defined by par. 4206 and 4207

0134

COMM RO WORD

065535

0135

COMM VALUE

-32768+32767

0136

COMM VALUE

-32768+32767

0137

PROCESS VAR

0138

PROCESS VAR

0139

PROCESS VAR

0140

RUN TIME

0.00499.99 kh

0.01 kh

0141

MWH COUNTER

065535 MWh

1 MWh

0142

REVOLUTION CNTR

065535 Mrev

1 Mrev

0143

DRIVE ON TIME HI

065535 days

1 day

0144

DRIVE ON TIME LO

00:00:0023:59:58

1=2s

0145

MOTOR TEMP

Par. 3501 = 13: -10200 C


Par. 3501 = 4: 05000 ohm
Par. 3501 = 56: 01

0146

MECH ANGLE

032768

0147

MECH REVS

-32768 +32767

0148

Z PLS DETECTED

0 = NOT DETECTED, 1 = DETECTED

0150

CB TEMP

-20.0150.0 C

1.0 C

0153

MOT THERM STRESS

0.0100.0%

0.1%

0158

PID COMM VALUE

-32768 +32767

0159

PID COMM VALUE

-32768 +32767

0174

SAVED KWH

0.0999.9 kWh

0.1 kWh

Parameters

User

ACS550-01/U1 Users Manual


Code

Name

0175

SAVED MWH

0176

SAVED AMOUNT

0177

SAVED AMOUNT

0178

SAVED CO2

93

Range

Resolution

Default

065535 MWh

1 MWh

0.0999.9

0.1

065535

0.06553.5 tn

0.1 tn

User

Group 03: FB ACTUAL SIGNALS


1

FB CMD WORD

FB STS WORD

0304

FB STS WORD

0305

FAULT WORD

0306

FAULT WORD

0307

FAULT WORD

0308

ALARM WORD

0309

ALARM WORD

Fault codes (panel displays as text)

0301

FB CMD WORD

0302
0303

Group 04: FAULT HISTORY


0401

LAST FAULT

0402

FAULT TIME

Date dd.mm.yy / power-on time in days 1 day

0403

FAULT TIME

Time hh.mm.ss

0404

SPEED AT FLT

-32768+32767

1 rpm

0405

FREQ AT FLT

-3276.8+3276.7

0.1 Hz

0406

VOLTAGE AT FLT

0.06553.5

0.1 V

0407

CURRENT AT FLT

0.06553.5

0.1 A

0408

TORQUE AT FLT

-3276.8+3276.7

0.1%

0409

STATUS AT FLT

0000FFFF hex

0410

DI

1-3 AT FLT

000111 (07 decimal)

0411

DI

4-6 AT FLT

000111 (07 decimal)

0412

PREVIOUS FAULT

As par. 0401

0413

PREVIOUS FAULT

As par. 0401

2s

Group 10: START/STOP/DIR


1001

EXT1 COMMANDS

014

2 (DI1,2)

1002

EXT2 COMMANDS

014

0 (NOT SEL)

1003

DIRECTION

1 = FORWARD, 2 = REVERSE,
3 = REQUEST

3 (REQUEST)

1004

JOGGING SEL

-66

0 (NOT SEL)

1 [REF1(Hz/rpm)]

Group 11: REFERENCE SELECT


1101

KEYPAD REF SEL

1 = REF1(Hz/rpm), 2 = REF2(%)

1102

EXT1/EXT2 SEL

-612

0 (EXT1)

1103

REF1 SELECT

017, 2021

1 (AI1)

1104

REF1 MIN

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm 0.0 Hz / 0 rpm

1105

REF1 MAX

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm -01: 50.0 (52.0) Hz /


1500 rpm
-U1: 60.0 (62.0) Hz /
1800 rpm
1

1106

REF2 SELECT

017, 1921

1107

REF2 MIN

0.0100.0% (0.0600.0% for torque) 0.1%

0.0%

2 (AI2)

1108

REF2 MAX

0.0100.0% (0.0600.0% for torque) 0.1%

100.0%

Parameters

94
Code

ACS550-01/U1 Users Manual


Name

Range

Resolution

Default

-14 19

9 (DI3,4)

User

Group 12: CONSTANT SPEEDS


1201

CONST SPEED SEL

1202

CONST SPEED

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm -01: 5.0 Hz / 300 rpm


-U1: 6.0 Hz / 360 rpm

1203

CONST SPEED

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm -01: 10.0 Hz / 600 rpm


-U1: 12.0 Hz / 720 rpm

1204

CONST SPEED

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm -01: 15.0 Hz / 900 rpm


-U1: 18.0 Hz / 1080 rpm

1205

CONST SPEED

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm -01: 20.0 Hz / 1200 rpm


-U1: 24.0 Hz / 1440 rpm

1206

CONST SPEED

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm -01: 25.0 Hz / 1500 rpm


-U1: 30.0 Hz / 1800 rpm

1207

CONST SPEED

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm -01: 40.0 Hz / 2400 rpm


-U1: 48.0 Hz / 2880 rpm

1208

CONST SPEED

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm -01: 50.0 Hz / 3000 rpm


-U1: 60.0 Hz / 3600 rpm

1209

TIMED MODE SEL

1 = EXT/CS1/2/3, 2 = CS1/2/3/4

2 (CS1/2/3/4)

Group 13: ANALOG INPUTS


1301

MINIMUM AI1

0.0100.0%

0.1%

0.0%

1302

MAXIMUM AI1

0.0100.0%

0.1%

100.0%

1303

FILTER AI1

0.010.0 s

0.1 s

0.1 s

1304

MINIMUM AI2

0.0100.0%

0.1%

0.0%

1305

MAXIMUM AI2

0.0100.0%

0.1%

100.0%

1306

FILTER AI2

0.010.0 s

0.1 s

0.1 s

Group 14: RELAY OUTPUTS


1401

RELAY OUTPUT

044, 46, 47, 52

1 (READY)

1402

RELAY OUTPUT

044, 46, 47, 52

2 (RUN)

1403

RELAY OUTPUT

044, 46, 47, 52

3 [FAULT(-1)]

1404

RO

1 ON DELAY

0.03600.0 s

0.1 s

0.0 s

1405

RO

1 OFF DELAY

0.03600.0 s

0.1 s

0.0 s

1406

RO

2 ON DELAY

0.03600.0 s

0.1 s

0.0 s

1407

RO

2 OFF DELAY

0.03600.0 s

0.1 s

0.0 s

1408

RO

3 ON DELAY

0.03600.0 s

0.1 s

0.0 s

1409

RO

3 OFF DELAY

0.03600.0 s

0.1 s

0.0 s

1410

RELAY OUTPUT

044, 46, 47, 52

0 (NOT SEL)

1411

RELAY OUTPUT

044, 46, 47, 52

0 (NOT SEL)

1412

RELAY OUTPUT

044, 46, 47, 52

0 (NOT SEL)

1413

RO

4 ON DELAY

0.03600.0 s

0.1 s

0.0 s

1414

RO

4 OFF DELAY

0.03600.0 s

0.1 s

0.0 s

1415

RO

5 ON DELAY

0.03600.0 s

0.1 s

0.0 s

1416

RO

5 OFF DELAY

0.03600.0 s

0.1 s

0.0 s

1417

RO

6 ON DELAY

0.03600.0 s

0.1 s

0.0 s

1418

RO

6 OFF DELAY

0.03600.0 s

0.1 s

0.0 s

103 (parameter 0103


OUTPUT FREQ)

Group 15: ANALOG OUTPUTS


1501

AO1 CONTENT SEL

Parameters

99178

ACS550-01/U1 Users Manual

95

Code

Name

Range

Resolution

Default

User

1502

AO1 CONTENT MIN

Depends on the signal


selected with par. 1501

1503

AO1 CONTENT MAX

Depends on the signal


selected with par. 1501

1504

MINIMUM AO1

0.020.0 mA

0.1 mA

0.0 mA

1505

MAXIMUM AO1

0.020.0 mA

0.1 mA

20.0 mA

1506

FILTER AO1

0.010.0 s

0.1 s

0.1 s

1507

AO2 CONTENT SEL

99178

104 (parameter 0104


CURRENT)

1508

AO2 CONTENT MIN

Depends on the signal


selected with par. 1507

1509

AO2 CONTENT MAX

Depends on the signal


selected with par. 1507

1510

MINIMUM AO2

0.020.0 mA

0.1 mA

0.0 mA

1511

MAXIMUM AO2

0.020.0 mA

0.1 mA

20.0 mA

1512

FILTER AO2

0.010.0 s

0.1 s

0.1 s

0 (NOT SEL)

Group 16: SYSTEM CONTROLS


1601

RUN ENABLE

-67

1602

PARAMETER LOCK

0 = LOCKED, 1 = OPEN, 2 = NOT SAVED

1 (OPEN)

1603

PASS CODE

065535

1604

FAULT RESET sEL

-68

0 (KEYPAD)

1605

USER PAR SET CHG

-66

0 (NOT SEL)

1606

LOCAL LOCK

-68

0 (NOT SEL)

1607

PARAM SAVE

0 = DONE, 1 = SAVE

0 (DONE)

1608

START ENABLE

-67

0 (NOT SEL)

1609

START ENABLE

-67

0 (NOT SEL)

1610

DISPLAY ALARMS

0 = NO, 1 = YES

0 (NO)

1611

PARAMETER VIEW

0 = DEFAULT, 1 = FLASHDROP

0 (DEFAULT)

1612

FAN CONTROL

0 = AUTO,1 = ON

0 (AUTO)

1613

FAULT RESET

0 = DEFAULT, 1 = RESET NOW

0 (DEFAULT)

Group 20: LIMITS


2001

MINIMUM SPEED

-3000030000 rpm

1 rpm

0 rpm

2002

MAXIMUM SPEED

030000 rpm

1 rpm

-01: 1500 rpm /


-U1: 1800 rpm

2003

MAX CURRENT

0 1.8 I2hd

0.1 A

1.8 I2hd

2005

OVERVOLT CTRL

0 = DISABLE, 1 = ENABLE

1 (ENABLE)

2006

UNDERVOLT CTRL

0 = DISABLE, 1 = ENABLE(TIME),
2 = ENABLE

1 [ENABLE(TIME)]

2007

MINIMUM FREQ

-500.0500.0 Hz

0.1 Hz

0.0 Hz

2008

MAXIMUM FREQ

0.0500.0 Hz

0.1 Hz

-01: 50.0 (52.0) Hz /


-U1: 60.0 (62.0) Hz

2013

MIN TORQUE SEL

-67

0 (MIN TORQUE 1)

2014

MAX TORQUE SEL

-67

0 (MAX TORQUE 1)

2015

MIN TORQUE

-600.00.0%

0.1%

-300.0%

2016

MIN TORQUE

-600.00.0%

0.1%

-300.0%

2017

MAX TORQUE

0.0600.0%

0.1%

300.0%

2018

MAX TORQUE

0.0600.0%

0.1%

300.0%

Parameters

96
Code

ACS550-01/U1 Users Manual


Name

Range

Resolution

Default

User

Group 21: START/STOP


2101

START FUNCTION

Vector control modes: 1, 2, 8


Scalar control mode: 15, 8

8 (RAMP)

2102

STOP FUNCTION

1 = COAST, 2 = RAMP

1 (COAST)

2103

DC MAGN TIME

0.0010.00 s

0.01 s

0.30 s

2104

DC HOLD CTL

0 = NOT SEL, 1 = DC HOLD,


2 = DC BRAKING

0 (NOT SEL)

2105

DC HOLD SPEED

0360 rpm

1 rpm

5 rpm

2106

DC CURR REF

0100%

1%

30%

2107

DC BRAKE TIME

0.0250.0 s

0.1 s

0.0 s

2108

START INHIBIT

0 = OFF, 1 = ON

0 (OFF)

2109

EMERG STOP SEL

-66

0 (NOT SEL)

2110

TORQ BOOST CURR

15300%

1%

100%

2112

ZERO SPEED DELAY

0.0 = NOT SEL, 0.160.0 s

0.1 s

0.0 s (NOT SEL)

2113

START DELAY

0.0060.00 s

0.01 s

0.00 s

Group 22: ACCEL/DECEL


2201

ACC/DEC

2202

ACCELER TIME

1/2 SEL
1

2203

DECELER TIME

2204

RAMP SHAPE

-67

5 (DI5)

0.01800.0 s

0.1 s

5.0 s

0.01800.0 s

0.1 s

5.0 s

0.0 = LINEAR, 0.11000.0 s

0.1 s

0.0 s

2205

ACCELER TIME

0.01800.0 s

0.1 s

60.0 s

2206

DECELER TIME

0.01800.0 s

0.1 s

60.0 s

2207

RAMP SHAPE

2208

EMERG DEC TIME

2209

RAMP INPUT

0.0 = LINEAR, 0.11000.0 s

0.1 s

0.0 s

0.01800.0 s

0.1 s

1.0 s

-67

0 (NOT SEL)

Group 23: SPEED CONTROL


2301

PROP GAIN

0.00200.00

0.01

5.00

2302

INTEGRATION TIME

0.00600.00 s

0.01 s

0.50 s

2303

DERIVATION TIME

010000 ms

1 ms

0 ms

2304

ACC COMPENSATION

0.00600.00 s

0.01 s

0.00 s

2305

AUTOTUNE RUN

0 = OFF, 1 = ON

0 (OFF)

Group 24: TORQUE CONTROL


2401

TORQ RAMP UP

0.00120.00 s

0.01 s

0.00 s

2402

TORQ RAMP DOWN

0.00120.00 s

0.01 s

0.00 s

0 = OFF, 1 = ON

0 (OFF)

Group 25: CRITICAL SPEEDS


2501

CRIT SPEED SEL

2502

CRIT SPEED

1 LO

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm 0.0 Hz / 0 rpm

2503

CRIT SPEED

1 HI

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm 0.0 Hz / 0 rpm

2504

CRIT SPEED

2 LO

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm 0.0 Hz / 0 rpm

2505

CRIT SPEED

2 HI

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm 0.0 Hz / 0 rpm

2506

CRIT SPEED

3 LO

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm 0.0 Hz / 0 rpm

2507

CRIT SPEED

3 HI

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm 0.0 Hz / 0 rpm

Group 26: MOTOR CONTROL


2601

FLUX OPT ENABLE

0 = OFF, 1 = ON

0 (OFF)

2602

FLUX BRAKING

0 = OFF, 1 = ON

0 (OFF)

Parameters

ACS550-01/U1 Users Manual

97

Code

Name

Range

Resolution

Default

2603

IR COMP VOLT

0.0100.0 V

0.1 V

Size dependent

2604

IR COMP FREQ

0100%

1%

80%

2605

U/F RATIO

1 = LINEAR, 2 = SQUARED

1 (LINEAR)

2606

SWITCHING FREQ

1, 2, 4, 8, 12 kHz

4 kHz

2607

SWITCH FREQ CTRL

0 = OFF, 1 = ON

1 (ON)

2608

SLIP COMP RATIO

0200%

1%

0%

2609

NOISE SMOOTHING

0 = DISABLE, 1 = ENABLE

0 (DISABLE)

2619

DC STABILIZER

0 = DISABLE, 1 = ENABLE

0 (DISABLE)

2625

OVERMODULATION

0 = DISABLE, 1 = ENABLE

0 (DISABLE)

User

Group 29: MAINTENANCE TRIG


2901

COOLING FAN TRIG

0.06553.5 kh, 0.0 disables

0.1 kh

0.0 kh

2902

COOLING FAN ACT

0.06553.5 kh

0.1 kh

0.0 kh

2903

REVOLUTION TRIG

065535 Mrev, 0 disables

1 Mrev

0 Mrev

2904

REVOLUTION ACT

065535 Mrev

1 Mrev

0 Mrev

2905

RUN TIME TRIG

0.06553.5 kh, 0.0 disables

0.1 kh

0.0 kh

2906

RUN TIME ACT

0.06553.5 kh

0.1 kh

0.0 kh

2907

USER

MWh TRIG

0.06553.5 MWh, 0.0 disables

0.1 MWh

0.0 MWh

2908

USER

MWh ACT

0.06553.5 MWh

0.1 MWh

0.0 MWh

0 (NOT SEL)

Group 30: FAULT FUNCTIONS


3001

AI<MIN FUNCTION

03

3002

PANEL COMM ERR

13

1 (FAULT)

3003

EXTERNAL FAULT

-66

0 (NOT SEL)

3004

EXTERNAL FAULT

-66

0 (NOT SEL)

3005

MOT THERM PROT

0 = NOT SEL, 1 = FAULT, 2 = ALARM

1 (FAULT)

3006

MOT THERM TIME

2569999 s

1s

500 s

3007

MOT LOAD CURVE

50150%

1%

100%

3008

ZERO SPEED LOAD

25150%

1%

70%

3009

BREAK POINT FREQ

1250 Hz

1 Hz

35 Hz

3010

STALL FUNCTION

0 = NOT SEL, 1 = FAULT, 2 = ALARM

0 (NOT SEL)

3011

STALL FREQUENCY

0.550.0 Hz

0.1 Hz

20.0 Hz

3012

STALL TIME

10400 s

1s

20 s

3017

EARTH FAULT

0 = DISABLE, 1 = ENABLE

1 (ENABLE)

3018

COMM FAULT FUNC

0 = NOT SEL, 1 = FAULT, 2 = CONST SP 7, 1


3 = LAST SPEED

3019

COMM FAULT TIME

0.0600.0 s

0.1 s

3.0 s

3021

AI1 FAULT LIMIT

0.0100.0%

0.1%

0.0%

3022

AI2 FAULT LIMIT

0.0100.0%

0.1%

0.0%

3023

WIRING FAULT

0 = DISABLE, 1 = ENABLE

1 (ENABLE)

3024

CB TEMP FAULT

0 = DISABLE, 1 = ENABLE

1 (ENABLE)

3028

EARTH FAULT LVL

13

-01: 2 (MEDIUM)
-U1: 1 (LOW)

0 (NOT SEL)

Group 31: AUTOMATIC RESET


3101

NUMBER OF TRIALS

05

3102

TRIAL TIME

1.0600.0 s

0.1 s

30.0 s

3103

DELAY TIME

0.0120.0 s

0.1 s

0.0 s

Parameters

98

ACS550-01/U1 Users Manual

Code

Name

Range

Resolution

Default

3104

AR OVERCURRENT

0 = DISABLE, 1 = ENABLE

0 (DISABLE)

3105

AR OVERVOLTAGE

0 = DISABLE, 1 = ENABLE

0 (DISABLE)

3106

AR UNDERVOLTAGE

0 = DISABLE, 1 = ENABLE

0 (DISABLE)

3107

AR AI<MIN

0 = DISABLE, 1 = ENABLE

0 (DISABLE)

3108

AR EXTERNAL FLT

0 = DISABLE, 1 = ENABLE

0 (DISABLE)

Group 32: SUPERVISION


3201

SUPERV

1 PARAM

100 = NOT SELECTED, 101178

103 (parameter 0103


OUTPUT FREQ)

3202

SUPERV

1 LIM LO

Depends on the signal


selected with par. 3201

3203

SUPERV

1 LIM HI

Depends on the signal


selected with par. 3201

3204

SUPERV

2 PARAM

100 = NOT SELECTED, 101178

104 (parameter 0104


CURRENT)

3205

SUPERV

2 LIM LO

Depends on the signal


selected with par. 3204

3206

SUPERV

2 LIM HI

Depends on the signal


selected with par. 3204

3207

SUPERV

3 PARAM

100 = NOT SELECTED, 101178

105 (parameter 0105


TORQUE)

3208

SUPERV

3 LIM LO

Depends on the signal


selected with par. 3207

3209

SUPERV

3 LIM HI

Depends on the signal


selected with par. 3207

Firmware version

Group 33: INFORMATION


3301

FIRMWARE

0000FFFF hex

3302

LOADING PACKAGE

0000FFFF hex

Type dependent

3303

TEST DATE

yy.ww

0.01

3304

DRIVE RATING

Type dependent

3305

PARAMETER TABLE

0000FFFF hex

Type dependent

Group 34: PANEL DISPLAY


3401

SIGNAL1 PARAM

100 = NOT SELECTED, 101178

103 (parameter 0103


OUTPUT FREQ)

3402

SIGNAL1 MIN

Depends on the signal


selected with par. 3401

3403

SIGNAL1 MAX

Depends on the signal


selected with par. 3401

3404

OUTPUT1 DSP FORM

09

9 (DIRECT)

3405

OUTPUT1 UNIT

0127

Depends on the signal


selected with par. 3401

3406

OUTPUT1 MIN

Depends on the signal


selected with par. 3401

3407

OUTPUT1 MAX

Depends on the signal


selected with par. 3401

3408

SIGNAL2 PARAM

100 = NOT SELECTED, 101178

104 (parameter 0104


CURRENT)

3409

SIGNAL2 MIN

Depends on the signal


selected with par. 3408

3410

SIGNAL2 MAX

Depends on the signal


selected with par. 3408

Parameters

User

ACS550-01/U1 Users Manual

99

Code

Name

Range

Resolution

Default

User

3411

OUTPUT2 DSP FORM

09

9 (DIRECT)

3412

OUTPUT2 UNIT

0127

Depends on the signal


selected with par. 3408

3413

OUTPUT2 MIN

Depends on the signal


selected with par. 3408

3414

OUTPUT2 MAX

Depends on the signal


selected with par. 3408

3415

SIGNAL3 PARAM

100 = NOT SELECTED, 101178

105 (parameter 0105


TORQUE)

3416

SIGNAL3 MIN

Depends on the signal


selected with par. 3415

3417

SIGNAL3 MAX

Depends on the signal


selected with par. 3415

3418

OUTPUT3 DSP FORM

09

9 (DIRECT)

3419

OUTPUT3 UNIT

0127

Depends on the signal


selected with par. 3415

3420

OUTPUT3 MIN

Depends on the signal


selected with par. 3415

3421

OUTPUT3 MAX

Depends on the signal


selected with par. 3415

Group 35: MOTOR TEMP MEAS


3501

SENSOR TYPE

06

0 (NONE)

3502

INPUT SELECTION

18

1 (AI1)

3503

ALARM LIMIT

Par. 3501 = 13: -10200 C


Par. 3501 = 4: 05000 ohm
Par. 3501 = 56: 01

110 C / 1500 ohm / 0

3504

FAULT LIMIT

Par. 3501 = 13: -10200 C


Par. 3501 = 4: 05000 ohm
Par. 3501 = 56: 01

130 C / 4000 ohm / 0

Group 36: TIMED FUNCTIONS


3601

TIMERS ENABLE

3602

START TIME

-67

0 (NOT SEL)

00:00:0023:59:58

2s

00:00:00

3603

STOP TIME

00:00:0023:59:58

2s

00:00:00

3604

START DAY

17

1 (MONDAY)

3605

STOP DAY

3606

START TIME

1
2

17

1 (MONDAY)

00:00:0023:59:58

2s

00:00:00

3607

STOP TIME

00:00:0023:59:58

2s

00:00:00

3608

START DAY

17

1 (MONDAY)

3609

STOP DAY

3610

START TIME

2
3

17

1 (MONDAY)

00:00:0023:59:58

2s

00:00:00

3611

STOP TIME

00:00:0023:59:58

2s

00:00:00

3612

START DAY

17

1 (MONDAY)

3613

STOP DAY

3614

START TIME

3
4

17

1 (MONDAY)

00:00:0023:59:58

2s

00:00:00

3615

STOP TIME

00:00:0023:59:58

2s

00:00:00

3616

START DAY

17

1 (MONDAY)

3617

STOP DAY

17

1 (MONDAY)

3622

BOOSTER SEL

-66

0 (NOT SEL)

3623

BOOSTER TIME

00:00:0023:59:58

2s

00:00:00

Parameters

100

ACS550-01/U1 Users Manual

Code

Name

Range

3626

3629

TIMED FUNC

14 SRC 031

Resolution

Default

0 (NOT SEL)

User

Group 37: USER LOAD CURVE


3701

USER LOAD C MODE

03

0 (NOT SEL)

3702

USER LOAD C FUNC

1 = FAULT, 2 = ALARM

1 (FAULT)

10400 s

1s

20 s

0500 Hz

1 Hz

5 Hz

3703

USER LOAD C TIME

3704

LOAD FREQ

3705

LOAD TORQ LOW

0600%

1%

10%

3706

LOAD TORQ HIGH

0600%

1%

300%

0500 Hz

1 Hz

25 Hz

0600%

1%

15%

3707

LOAD FREQ

3708

LOAD TORQ LOW

2
2

0600%

1%

300%

0500 Hz

1 Hz

43 Hz

3709

LOAD TORQ HIGH

3710

LOAD FREQ

3711

LOAD TORQ LOW

0600%

1%

25%

3712

LOAD TORQ HIGH

0600%

1%

300%

0500 Hz

1 Hz

50 Hz

0600%

1%

30%

3713

LOAD FREQ

3714

LOAD TORQ LOW

4
4

0600%

1%

300%

0500 Hz

1 Hz

500 Hz

3715

LOAD TORQ HIGH

3716

LOAD FREQ

3717

LOAD TORQ LOW

0600%

1%

30%

3718

LOAD TORQ HIGH

0600%

1%

300%

Group 40: PROCESS PID SET 1


4001

GAIN

0.1100.0

0.1

1.0

4002

INTEGRATION TIME

0.0 = NOT SEL, 0.13600.0 s

0.1 s

60.0 s

4003

DERIVATION TIME

0.010.0 s

0.1 s

0.0 s

4004

PID DERIV FILTER

0.010.0 s

0.1 s

1.0 s

4005

ERROR VALUE INV

0 = NO, 1 = YES

0 (NO)

4006

UNITS

0127

4 (%)

4007

UNIT SCALE

04

4008

0% VALUE

Unit and scale defined by par. 4006 and 4007

0.0

4009

100% VALUE

Unit and scale defined by par. 4006 and 4007

100.0
1 (AI1)

4010

SET POINT SEL

02, 817, 1920

4011

INTERNAL SETPNT

Unit and scale defined by par. 4006 and 4007

40.0

4012

SETPOINT MIN

-500.0500.0%

0.1%

0.0%

4013

SETPOINT MAX

-500.0500.0%

0.1%

100.0%

4014

FBK SEL

113

1 (ACT1)

4015

FBK MULTIPLIER

0.000 = NOT SEL, -32.76832.767

0.001

0.000 (NOT SEL)

4016

ACT1 INPUT

17

2 (AI2)

4017

ACT2 INPUT

17

2 (AI2)

4018

ACT1 MINIMUM

-10001000%

1%

0%

4019

ACT1 MAXIMUM

-10001000%

1%

100%

4020

ACT2 MINIMUM

-10001000%

1%

0%

Parameters

ACS550-01/U1 Users Manual

101

Code

Name

Range

Resolution

Default

4021

ACT2 MAXIMUM

-10001000%

1%

100%

4022

SLEEP SELECTION

-67

0 (NOT SEL)

4023

PID SLEEP LEVEL

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm 0.0 Hz / 0 rpm

4024

PID SLEEP DELAY

0.03600.0 s

0.1 s

4025

WAKE-UP DEV

Unit and scale defined by par. 4006 and 4007

0.0

4026

WAKE-UP DELAY

0.0060.00 s

0.01 s

0.50 s

4027

PID

-614

0 (SET 1)

1 PARAM sET

User

60.0 s

Group 41: PROCESS PID SET 2


4101

GAIN

0.1100.0

0.1

1.0

4102

INTEGRATION TIME

0.0 = NOT SEL, 0.13600.0 s

0.1 s

60.0 s

4103

DERIVATION TIME

0.010.0 s

0.1 s

0.0 s

4104

PID DERIV FILTER

0.010.0 s

0.1 s

1.0 s

4105

ERROR VALUE INV

0 = NO, 1 = YES

0 (NO)

4106

UNITS

0127

4 (%)

4107

UNIT SCALE

04

4108

0% VALUE

Unit and scale defined by par. 4106 and 4107

0.0

4109

100% VALUE

Unit and scale defined by par. 4106 and 4107

100.0
1 (AI1)

4110

SET POINT SEL

02, 817, 1920

4111

INTERNAL SETPNT

Unit and scale defined by par. 4106 and 4107

40.0

4112

SETPOINT MIN

-500.0500.0%

0.1%

0.0%

4113

SETPOINT MAX

-500.0500.0%

0.1%

100.0%

4114

FBK SEL

113

1 (ACT1)

4115

FBK MULTIPLIER

0.000 = NOT SEL, -32.76832.767

0.001

0.000 (NOT SEL)

4116

ACT1 INPUT

17

2 (AI2)

4117

ACT2 INPUT

17

2 (AI2)

4118

ACT1 MINIMUM

-10001000%

1%

0%

4119

ACT1 MAXIMUM

-10001000%

1%

100%

4120

ACT2 MINIMUM

-10001000%

1%

0%

4121

ACT2 MAXIMUM

-10001000%

1%

100%

4122

SLEEP SELECTION

-67

0 (NOT SEL)

4123

PID SLEEP LEVEL

0.0500.0 Hz / 030000 rpm

0.1 Hz / 1 rpm 0.0 Hz / 0 rpm

4124

PID SLEEP DELAY

0.03600.0 s

0.1 s

4125

WAKE-UP DEV

Unit and scale defined by par. 4106 and 4107

0.0

4126

WAKE-UP DELAY

0.0060.00 s

0.01 s

0.50 s

60.0 s

Group 42: EXT / TRIM PID


4201

GAIN

0.1100.0

0.1

1.0

4202

INTEGRATION TIME

0.0 = NOT SEL, 0.13600.0 s

0.1 s

60.0 s

4203

DERIVATION TIME

0.010.0 s

0.1 s

0.0 s

4204

PID DERIV FILTER

0.010.0 s

0.1 s

1.0 s

4205

ERROR VALUE INV

0 = NO, 1 = YES

0 (NO)

4206

UNITS

0127

4 (%)

Parameters

102
Code

ACS550-01/U1 Users Manual


Name

Range

Resolution

Default

4207

UNIT SCALE

04

4208

0% VALUE

Unit and scale defined by par. 4206 and 4207

0.0

4209

100% VALUE

Unit and scale defined by par. 4206 and 4207

100.0

4210

SET POINT SEL

02, 817, 1920

1 (AI1)

4211

INTERNAL SETPNT

Unit and scale defined by par. 4206 and 4207

40.0

4212

SETPOINT MIN

-500.0500.0%

0.1%

0.0%

4213

SETPOINT MAX

-500.0500.0%

0.1%

100.0%

4214

FBK SEL

113

1 (ACT1)

4215

FBK MULTIPLIER

0.000 = NOT SEL, -32.76832.767

0.001

0.000 (NOT SEL)

User

4216

ACT1 INPUT

17

2 (AI2)

4217

ACT2 INPUT

17

2 (AI2)

4218

ACT1 MINIMUM

-10001000%

1%

0%

4219

ACT1 MAXIMUM

-10001000%

1%

100%

4220

ACT2 MINIMUM

-10001000%

1%

0%

4221

ACT2 MAXIMUM

-10001000%

1%

100%

4228

ACTIVATE

-612

0 (NOT SEL)

4229

OFFSET

0.0100.0%

0.1%

0.0%

4230

TRIM MODE

0 = NOT SEL, 1 = PROPORTIONAL,


3 = DIRECT

0 (NOT SEL)

4231

TRIM SCALE

-100.0100.0%

0.1%

0.0%

4232

CORRECTION SRC

1 = PID2REF, 2 = PID2OUTPUT

1 (PID2REF)

0.01

0.00

Group 45: ENERGY SAVING


4502

ENERGY PRICE

0.00655.35

4507

CO2 CONV FACTOR

0.010.0 tn/MWh

0.1 tn/MWh

0.5 tn/MWh

4508

PUMP POWER

0.01000.0%

0.1%

100.0%

4509

ENERGY RESET

0 = DONE, 1 = RESET

0 (DONE)

Group 50: ENCODER


5001

PULSE NR

5016384

1024

5002

ENCODER ENABLE

0 = DISABLE, 1 = ENABLE

0 (DISABLE)

5003

ENCODER FAULT

1 = FAULT, 2 = ALARM

1 (FAULT)

5010

Z PLS ENABLE

0 = DISABLE, 1 = ENABLE

0 (DISABLE)

5011

POSITION RESET

0 = DISABLE, 1 = ENABLE

0 (DISABLE)

Group 51: EXT COMM MODULE


-

0 (NOT DEFINED)

5102 FB PAR 226


5126

065535

5127

FBA PAR REFRESH

0 = DONE, 1 = REFRESH

0 (DONE)

5101

FBA TYPE

5128

FILE CPI FW REV

0000FFFF hex

5129

FILE CONFIG ID

0000FFFF hex

5130

FILE CONFIG REV

0000FFFF hex

5131

FBA STATUS

06

0 (IDLE)

5132

FBA CPI FW REV

0000FFFF hex

5133

FBA APPL FW REV

0000FFFF hex

Parameters

ACS550-01/U1 Users Manual


Code

Name

103

Range

Resolution

Default

User

Group 52: PANEL COMM


5201

STATION ID

1247

5202

BAUD RATE

9.6, 19.2, 38.4, 57.6, 115.2 kbits/s

9.6 kbits/s

5203

PARITY

0 = 8 NONE 1, 1 = 8 NONE 2,
2 = 8 EVEN 1, 3 = 8 ODD 1

0 (8 NONE 1)

5204

OK MESSAGES

065535

5205

PARITY ERRORS

065535

5206

FRAME ERRORS

065535

5207

BUFFER OVERRUNS

065535

5208

CRC ERRORS

065535

Group 53: EFB PROTOCOL


5301

EFB PROTOCOL ID

00xFFFF

5302

EFB STATION ID

065535

5303

EFB BAUD RATE

1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, 76.8 kbits/s

9.6 kbits/s

5304

EFB PARITY

0 = 8 NONE 1, 1 = 8 NONE 2,
2 = 8 EVEN 1, 3 = 8 ODD 1

0 (8 NONE 1)

5305

EFB CTRL PROFILE

0 = ABB DRV LIM, 1 = DCU PROFILE,


2 = ABB DRV FULL

0 (ABB DRV LIM)

5306

EFB OK MESSAGES

065535

5307

EFB CRC ERRORS

065535

5308

EFB UART ERRORS

065535

07

0 (IDLE)

065535

5309

EFB STATUS

5310

EFB PAR

10

5311

EFB PAR

11

065535

5312

EFB PAR

12

065535

5313

EFB PAR

13

065535

5314

EFB PAR

14

065535

5315

EFB PAR

15

065535

5316

EFB PAR

16

065535

5317

EFB PAR

17

065535

5318

EFB PAR

18

065535

5319

EFB PAR

19

0000FFFF hex

5320

EFB PAR

20

0000FFFF hex

Group 64: LOAD ANALYZER


6401

PVL SIGNAL

100178

103 (parameter 0103


OUTPUT FREQ)

6402

PVL FILTER TIME

0.0120.0 s

0.1 s

0.1 s

6403

LOGGERS RESET

-67

0 (NOT SEL)

6404

AL2 SIGNAL

101178

103 (parameter 0103


OUTPUT FREQ)

6405

AL2 SIGNAL BASE

Depends on the signal


selected with par. 6404.

6406

PEAK VALUE

6407

PEAK TIME

Date dd.mm.yy / power-on time in days 1 d

6408

PEAK TIME

Time hh.mm.ss

2s

6409

CURRENT AT PEAK

0.06553.5 A

0.1 A

Parameters

104

ACS550-01/U1 Users Manual

Code

Name

Range

Resolution

Default

6410

UDC AT PEAK

065535 V

1V

6411

FREQ AT PEAK

0.06553.5 Hz

0.1 Hz

6412

TIME OF RESET

Date dd.mm.yy / power-on time in days 1 d

6413

TIME OF RESET

Time hh.mm.ss

2s

6414

AL1RANGE0TO10

0.0100.0%

0.1%

6415

AL1RANGE10TO20

0.0100.0%

0.1%

6416

AL1RANGE20TO30

0.0100.0%

0.1%

6417

AL1RANGE30TO40

0.0100.0%

0.1%

6418

AL1RANGE40TO50

0.0100.0%

0.1%

6419

AL1RANGE50TO60

0.0100.0%

0.1%

6420

AL1RANGE60TO70

0.0100.0%

0.1%

6421

AL1RANGE70TO80

0.0100.0%

0.1%

6422

AL1RANGE80TO90

0.0100.0%

0.1%

6423

AL1RANGE90TO

0.0100.0%

0.1%

6424

AL2RANGE0TO10

0.0100.0%

0.1%

6425

AL2RANGE10TO20

0.0100.0%

0.1%

6426

AL2RANGE20TO30

0.0100.0%

0.1%

6427

AL2RANGE30TO40

0.0100.0%

0.1%

6428

AL2RANGE40TO50

0.0100.0%

0.1%

6429

AL2RANGE50TO60

0.0100.0%

0.1%

6430

AL2RANGE60TO70

0.0100.0%

0.1%

6431

AL2RANGE70TO80

0.0100.0%

0.1%

6432

AL2RANGE80TO90

0.0100.0%

0.1%

6433

AL2RANGE90TO

0.0100.0%

0.1%

User

Group 81: PFC CONTROL


8103

REFERENCE STEP

0.0100.0%

0.1%

0.0%

8104

REFERENCE STEP

0.0100.0%

0.1%

0.0%

8105

REFERENCE STEP

0.0100.0%

0.1%

0.0%

8109

START FREQ

0.0500.0 Hz

0.1 Hz

-01: 50.0 Hz /
-U1: 60.0 Hz

8110

START FREQ

0.0500.0 Hz

0.1 Hz

-01: 50.0 Hz /
-U1: 60.0 Hz

8111

START FREQ

0.0500.0 Hz

0.1 Hz

-01: 50.0 Hz /
-U1: 60.0 Hz

8112

LOW FREQ

0.0500.0 Hz

0.1 Hz

-01: 25.0 Hz /
-U1: 30.0 Hz

8113

LOW FREQ

0.0500.0 Hz

0.1 Hz

-01: 25.0 Hz /
-U1: 30.0 Hz

8114

LOW FREQ

0.0500.0 Hz

0.1 Hz

-01: 25.0 Hz /
-U1: 30.0 Hz

8115

AUX MOT START D

0.03600.0 s

0.1 s

5.0 s

8116

AUX MOT STOP D

0.03600.0 s

0.1 s

3.0 s

8117

NR OF AUX MOT

04

8118

AUTOCHNG INTERV

-0.1 = TEST MODE, 0.0 = NOT SEL,


0.1336.0 h

0.1 h

0.0 h (NOT SEL)

8119

AUTOCHNG LEVEL

0.0100.0%

0.1%

50.0%

8120

INTERLOCKS

06

4 (DI4)

Parameters

ACS550-01/U1 Users Manual


Code

Name

Range

105
Resolution

Default

8121

REG BYPASS CTRL

0 = NO, 1 = YES

0 (NO)

8122

PFC START DELAY

0.0010.00 s

0.01 s

0.50 s

User

8123

PFC ENABLE

0 = NOT SEL, 1 = ACTIVE

0 (NOT SEL)

8124

ACC IN AUX STOP

0.0 = NOT SEL, 0.11800.0 s

0.1 s

0.0 s (NOT SEL)

8125

DEC IN AUX START

0.0 = NOT SEL, 0.11800.0 s

0.1 s

0.0 s (NOT SEL)

8126

TMED AUTOCHNG

04

0 (NOT SEL)

8127

MOTORS

17

8128

AUX START ORDER

1 = EVEN RUNTIME, 2 = RELAY ORDER

1 (EVEN RUNTIME)

0 = NOT SEL, 1 = STD MODBUS,


4 = EXT FBA

0 (NOT SEL)

Group 98: OPTIONS


9802

COMM PROT SEL

Parameters

106

ACS550-01/U1 Users Manual

Complete parameter descriptions


This section describes the actual signals and parameters for ACS550.
Group 99: START-UP DATA
This group defines special start-up data required to:
set up the drive
enter motor information.
Code Description
9901 LANGUAGE
Selects the display language. There are two different Assistant Control Panels, each supporting a different language
set. (Panel ACS-CP-L supporting languages 0, 2, 1115 has been integrated into ACS-CP-A.)
Assistant Control Panel ACS-CP-A:
1 = ENGLISH (AM)
0 = ENGLISH
5 = PORTUGUES
6 = NEDERLANDS
10 = SVENSKA
11 = RUSSKI
15 = MAGYAR
16 = ELLINIKA
Assistant Control Panel ACS-CP-D (Asia):
0 = ENGLISH
1 = CHINESE

2 = DEUTSCH
7 = FRANAIS
12 = POLSKI

3 = ITALIANO
8 = DANSK
13 = TRKE

2 = KOREAN

3 = JAPANESE

4 = ESPAOL
9 = SUOMI
14 = CZECH

9902 APPLIC MACRO


Selects an application macro. Application macros automatically edit parameters to configure the ACS550 for a
particular application.
1 = ABB STANDARD
6 = PID CONTROL
0 = USER S1 LOAD

2 = 3-WIRE
7 = PFC CONTROL
-1 = USER S1 SAVE

3 = ALTERNATE
8 = TORQUE CTRL
-2 = USER S2 LOAD

4 = MOTOR POT
5 = HAND/AUTO
31 = LOAD FD SET
-3 = USER S2 SAVE

31 = LOAD FD SET FlashDrop parameter values as defined by the FlashDrop file. Parameter view is selected by
parameter 1611 PARAMETER VIEW.
FlashDrop is an optional device for fast copying of parameters to unpowered drives. FlashDrop allows easy
customization of the parameter list, e.g. selected parameters can be hidden. For more information, see MFDT-01
FlashDrop Users Manual (3AFE68591074 [English]).
-1 = USER S1 SAVE, -3 = USER S2 SAVE With these it is possible to save two different user parameter sets into the
drive permanent memory for later use. Each set contains parameter settings, including Group 99: START-UP
DATA, and the results of the motor identification run.
0 = USER S1 LOAD, -2 = USER S2 LOAD With these the user parameter sets can be taken back in use.
9904 MOTOR CTRL MODE
Selects the motor control mode.
1 = VECTOR:SPEED sensorless vector control mode.
Reference 1 is speed reference in rpm.
Reference 2 is speed reference in % (100% is absolute maximum speed, equal to the value of parameter 2002
MAXIMUM SPEED, or 2001 MINIMUM SPEED if the absolute value of the minimum speed is greater than the maximum
speed).
2 = VECTOR:TORQ.
Reference 1 is speed reference in rpm.
Reference 2 is torque reference in % (100% is nominal torque.)
3 = SCALAR:FREQ scalar control mode.
Reference 1 is frequency reference in Hz.
Reference 2 is frequency reference in % (100% is absolute maximum frequency, equal to the value of parameter
2008 MAXIMUM FREQ, or 2007 MINIMUM FREQ if the absolute value of the minimum speed is greater than the
maximum speed).

Parameters

ACS550-01/U1 Users Manual

107

Code Description
9905 MOTOR NOM VOLT
Defines the nominal motor voltage.
Must equal the value on the motor rating plate.
The ACS550 cannot supply the motor with a voltage greater than the input
power (mains) voltage.
9906 MOTOR NOM CURR
Defines the nominal motor current.
Must equal the value on the motor rating plate.
Range allowed: 0.22.0 I2hd (where I2hd is drive current).
9907 MOTOR NOM FREQ
Defines the nominal motor frequency.
Range: 10500 Hz (typically 50 or 60 Hz)
Sets the frequency at which output voltage equals the MOTOR NOM VOLT.
Field weakening point = Nom Freq Supply Volt / Mot Nom Volt

Output voltage

P 9905

Output
frequency
P 9907

9908 MOTOR NOM SPEED


Defines the nominal motor speed.
Must equal the value on the motor rating plate.
9909 MOTOR NOM POWER
Defines the nominal motor power.
Must equal the value on the motor rating plate.
9910 ID RUN
This parameter controls a self-calibration process called the Motor ID Run. During this process, the drive operates
the motor (motor rotating) and makes measurements in order to identify motor characteristics and create a model
used for internal calculations. An ID Run is especially effective when:
vector control mode is used [parameter 9904 = 1 (VECTOR:SPEED) or 2 (VECTOR:TORQ)], and/or
operation point is near zero speed, and/or
operation requires a torque range above the motor nominal torque, over a wide speed range, and without any
measured speed feedback (i.e. without a pulse encoder).
0 = OFF/IDMAGN The Motor ID Run process is not run. Identification magnetization is performed, depending on
parameter 9904 and 2101 settings. In identification magnetization, the motor model is calculated at first start by
magnetizing the motor for 10 to 15 s at zero speed (motor not rotating). The model is recalculated always at start
after motor parameter changes.
Parameter 9904 = 1 (VECTOR:SPEED) or 2 (VECTOR:TORQ): Identification magnetization is performed.
Parameter 9904 = 3 (SCALAR:FREQ) and parameter 2101 = 3 (SCALAR FLYST) or 5 (FLY + BOOST): Identification
magnetization is performed.
Parameter 9904 = 3 (SCALAR:FREQ) and parameter 2101 has other value than 3 (SCALAR FLYST) or 5 (FLY +
BOOST): Identification magnetization is not performed.
1 = ON Enables the Motor ID Run, during which the motor is rotating, at the next start command. After run
completion, this value automatically changes to 0.
Note: The motor must be de-coupled from the driven equipment.
Note: If motor parameters are changed after ID Run, repeat the ID Run.
WARNING! The motor will run at up to approximately 5080% of the nominal speed during the ID Run. The
motor will rotate in the forward direction.
Ensure that it is safe to run the motor before performing the ID Run!
See also section How to perform the ID Run on page 45.
9915 MOTOR COSPHI
Defines the nominal motor cos phi (power factor). The parameter improves performance especially with high
efficiency motors.
0 = IDENTIFIED Drive identifies the cos phi automatically by estimation.
0.010.97 Value entered used as the cos phi.

Parameters

108

ACS550-01/U1 Users Manual

Group 01: OPERATING DATA


This group contains drive operating data, including actual signals. The drive sets the
values for actual signals, based on measurements or calculations. You cannot set
these values.
Code Description
0101 SPEED & DIR
The calculated signed speed of the motor (rpm). The absolute value of 0101 SPEED & DIR is the same as the value of
0102 SPEED.
The value of 0101 SPEED & DIR is positive if the motor runs in the forward direction.
The value of 0101 SPEED & DIR is negative if the motor runs in the reverse direction.
0102 SPEED
The calculated speed of the motor (rpm). (Parameter 0102 or 0103 is shown by default in the control panel Output
mode.)
0103 OUTPUT FREQ
The frequency (Hz) applied to the motor. (Parameter 0102 or 0103 is shown by default in the control panel Output
mode.)
0104 CURRENT
The motor current, as measured by the ACS550. (Shown by default in the control panel Output mode.)
0105 TORQUE
Output torque. Calculated value of torque on motor shaft in % of motor nominal torque. (Shown by default in the
control panel Output mode.)
0106 POWER
The measured motor power in kW.
0107 DC BUS VOLTAGE
The DC bus voltage in V DC, as measured by the ACS550.
0109 OUTPUT VOLTAGE
The voltage applied to the motor.
0110 DRIVE TEMP
The temperature of the drive power transistors in degrees Celsius.
0111 EXTERNAL REF 1
External reference, REF1, in rpm or Hz units determined by parameter 9904.
0112 EXTERNAL REF 2
External reference, REF2, in %.
0113 CTRL LOCATION
Active control location. Alternatives are:
0 = LOCAL
1 = EXT1
2 = EXT2
0114 RUN TIME (R)
The drives accumulated running time in hours (h).
Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0115 KWH COUNTER (R)
The drives accumulated power consumption in kilowatt hours.
The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0116 APPL BLK OUTPUT
Application block output signal. Value is from either:
PFC control, if PFC Control is active, or
Parameter 0112 EXTERNAL REF 2.

Parameters

ACS550-01/U1 Users Manual

109

Code Description
0118 DI 1-3 STATUS
Status of the three digital inputs.
Status is displayed as a binary number.
1 indicates that the input is activated.
0 indicates that the input is deactivated.
DI

0119 DI 4-6 STATUS


Status of the three digital inputs.
See parameter 0118 DI 1-3 STATUS.

DI

DI

0120 AI 1
The relative value of analog input 1 in %.
0121 AI 2
The relative value of analog input 2 in %.
0122 RO 1-3 STATUS
Status of the three relay outputs.
1 indicates that the relay is energized.
0 indicates that the relay is de-energized.
0123 RO 4-6 STATUS
Status of the three relay outputs. Available if OREL-01 Relay Output
Extension Module is installed.
See parameter 0122.

1 STATUS
2 STATUS
RELAY 3 STATUS
RELAY

RELAY

0124 AO 1
The analog output 1 value in milliamperes.
0125 AO 2
The analog output 2 value in milliamperes.
0126 PID 1 OUTPUT
The PID controller 1 output value in %.
0127 PID 2 OUTPUT
The PID controller 2 output value in %.
0128 PID 1 SETPNT
The PID 1 controller setpoint signal.
Units and scale defined by PID parameters.
0129 PID 2 SETPNT
The PID 2 controller setpoint signal.
Units and scale defined by PID parameters.
0130 PID 1 FBK
The PID 1 controller feedback signal.
Units and scale defined by PID parameters.
0131 PID 2 FBK
The PID 2 controller feedback signal.
Units and scale defined by PID parameters.
0132 PID 1 DEVIATION
The difference between the PID 1 controller reference value and actual value.
Units and scale defined by PID parameters.
0133 PID 2 DEVIATION
The difference between the PID 2 controller reference value and actual value.
Units and scale defined by PID parameters.
0134 COMM RO WORD
Free data location that can be written from serial link.
Used for relay output control.
See parameter 1401.
0135 COMM VALUE 1
Free data location that can be written from serial link.

Parameters

110

ACS550-01/U1 Users Manual

Code Description
0136 COMM VALUE 2
Free data location that can be written from serial link.
0137 PROCESS VAR 1
Process variable 1
Defined by parameters in Group 34: PANEL DISPLAY.
0138 PROCESS VAR 2
Process variable 2
Defined by parameters in Group 34: PANEL DISPLAY.
0139 PROCESS VAR 3
Process variable 3
Defined by parameters in Group 34: PANEL DISPLAY.
0140 RUN TIME
The drives accumulated running time in thousands of hours (kh).
Cannot be reset.
0141 MWH COUNTER
The drives accumulated power consumption in megawatt hours.
The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
Cannot be reset.
0142 REVOLUTION CNTR
The motors accumulated revolutions in millions of revolutions.
Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0143 DRIVE ON TIME HI
The drives accumulated power-on time in days.
Cannot be reset.
0144 DRIVE ON TIME LO
The drives accumulated power-on time in 2 second ticks (30 ticks = 60 seconds).
Shown in format hh.mm.ss.
Cannot be reset.
0145 MOTOR TEMP
Motor temperature in degrees Celsius / PTC resistance in ohms.
Applies only if motor temperature sensor is set up.
See parameter 3501.
0146 MECH ANGLE
Defines the motor shafts angular position to about 0.01 (32,768 divisions for 360). The position is defined as 0 at
power up.
During operation the zero position can be set by:
a Z-pulse input, if parameter 5010 Z PLS ENABLE = 1 (ENABLE)
parameter 5011 POSITION RESET, if parameter 5010 Z PLS ENABLE = 2 (DISABLE)
any status change of parameter 5002 ENCODER ENABLE.
0147 MECH REVS
A signed integer that counts full revolutions of the motor shaft. The value:
increments when parameter 0146 MECH ANGLE changes from 32767 to 0
decrements when parameter 0146 MECH ANGLE changes from 0 to 32767.
0148 Z PLS DETECTED
Encoder zero pulse detector. When a Z-pulse defines the zero position, the shaft must pass through the zero position
to trigger a Z-pulse. Until then, the shaft position is unknown (the drive uses the shaft position at power up as zero).
This parameter signals when parameter 0146 MECH ANGLE is valid. The parameter starts at 0 = NOT DETECTED on
power-up and changes to 1 = DETECTED only if:
parameter 5010 Z PLS ENABLE = 1 (ENABLE) and
an encoder Z-pulse has been detected.
0150 CB TEMP
Temperature of the drive control board in degrees Celsius.
Note: Some drives have a control board (OMIO) that does not support this feature. These drives always show the
constant value of 25.0 C.

Parameters

ACS550-01/U1 Users Manual

111

Code Description
0153 MOT THERM STRESS
Estimated rise of the motor temperature. Value equals to the estimated motor thermal stress as a percentage of the
motor temperature trip level.
0158 PID COMM VALUE 1
Data received from fieldbus for PID control (PID1 and PID2).
0159 PID COMM VALUE 2
Data received from fieldbus for PID control (PID1 and PID2).
0174 SAVED KWH
Energy saved in kWh compared to the energy used when the pump is connected directly to the supply. See the note
on page 180.
The counter value is accumulated till it reaches 999.9 after which the counter rolls over and starts again from 0.0
and the counter value of signal 0175 is incremented by one. Can be reset with parameter 4509 ENERGY RESET
(resets all energy calculators at the same time).
See Group 45: ENERGY SAVING.
0175 SAVED MWH
Energy saved in MWh compared to the energy used when the pump is connected directly to the supply. See the note
on page 180.
The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time).
See Group 45: ENERGY SAVING.
0176 SAVED AMOUNT 1
Energy saved in local currency (remainder when the total saved energy is divided by 1000). See the note on page
180.
To find out the total saved energy in currency units, add the value of parameter 0177 multiplied by 1000 to the
value of parameter 0176.
Example:
0176 SAVED AMOUNT 1 = 123.4
0177 SAVED AMOUNT 2 = 5
Total saved energy = 5 1000 + 123.4 = 5123.4 currency units.
The counter value is accumulated till it reaches 999.9 after which the counter rolls over and starts again from 0.0
and the counter value of signal 0177 is incremented by one.
Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time).
Local energy price is set with parameter 4502 ENERGY PRICE.
See Group 45: ENERGY SAVING.
0177 SAVED AMOUNT 2
Energy saved in local currency in thousand currency units. Eg value 5 means 5000 currency units. See the note on
page 180.
The counter value is accumulated till it reaches 65535 (the counter does not roll over).
See parameter 0176 SAVED AMOUNT 1.
0178 SAVED CO2
Reduction on carbon dioxide emissions in tn. See the note on page 180.
The counter value is accumulated till it reaches 6553.5 (the counter does not roll over).
Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time).
CO2 conversion factor is set with parameter 4507 CO2 CONV FACTOR.
See Group 45: ENERGY SAVING.

Parameters

112

ACS550-01/U1 Users Manual

Group 03: FB ACTUAL SIGNALS


This group monitors fieldbus communications.
Code Description
0301 FB CMD WORD 1
Read-only copy of the Fieldbus
Command Word 1.
The fieldbus command is the principal
means for controlling the drive from a
fieldbus controller. The command
consists of two Command Words. Bitcoded instructions in the Command
Words switch the drive between
states.
To control the drive, using the
Command Words, an external location
(EXT1 or EXT2) must be active and set
to COMM. (See parameters 1001 and
1002.)
The control panel displays the word in
hex. For example, all zeros and a 1 in
Bit 0 displays as 0001. All zeros and a
1 in Bit 15 displays as 8000.
0302 FB CMD WORD 2
Read-only copy of the Fieldbus
Command Word 2.
See parameter 0301.
0303 FB STS WORD 1
Read-only copy of the Status Word 1.
The drive sends status information to
the fieldbus controller. The status
consists of two Status Words.
The control panel displays the word in
hex. For example, all zeros and a 1 in
Bit 0 displays as 0001. All zeros and a
1 in Bit 15 displays as 8000.
0304 FB STS WORD 2
Read-only copy of the Status Word 2.
See parameter 0303.

Parameters

Bit #

0301, FB CMD WORD 1

0302, FB CMD WORD 2

STOP

FBLOCAL_CTL

START

FBLOCAL_REF

REVERSE

START_DISABLE1

LOCAL

START_DISABLE2

RESET

Reserved

EXT2

Reserved

RUN_DISABLE

Reserved

STPMODE_R

Reserved

STPMODE_EM

Reserved

STPMODE_C

Reserved

10

RAMP_2

Reserved

11

RAMP_OUT_0

REF_CONST

12

RAMP_HOLD

REF_AVE

13

RAMP_IN_0

LINK_ON

14

RREQ_LOCALLOC

REQ_STARTINH

15

TORQLIM2

OFF_INTERLOCK

Bit #

0303, FB STS WORD 1

0304, FB STS WORD 2

READY

ALARM

ENABLED

NOTICE

STARTED

DIRLOCK

RUNNING

LOCALLOCK

ZERO_SPEED

CTL_MODE

ACCELERATE

Reserved

DECELERATE

Reserved

AT_SETPOINT

CPY_CTL

LIMIT

CPY_REF1

SUPERVISION

CPY_REF2

10

REV_REF

REQ_CTL

11

REV_ACT

REQ_REF1

12

PANEL_LOCAL

REQ_REF2

13

FIELDBUS_LOCAL

REQ_REF2EXT

14

EXT2_ACT

ACK_STARTINH

15

FAULT

ACK_OFF_ILCK

ACS550-01/U1 Users Manual

113

Code Description
0305 FAULT WORD 1
Read-only copy of the Fault Word 1.
When a fault is active, the
corresponding bit for the active fault is
set in the Fault Words.
Each fault has a dedicated bit
allocated within Fault Words.
See section Fault listing on page 260
for a description of the faults.
The control panel displays the word in
hex. For example, all zeros and a 1 in
Bit 0 displays as 0001. All zeros and a
1 in Bit 15 displays as 8000.
0306 FAULT WORD 2
Read-only copy of the Fault Word 2.
See parameter 0305.
0307 FAULT WORD 3
Read-only copy of the Fault Word 3.
See parameter 0305.

0308 ALARM WORD 1


When an alarm is active, the
corresponding bit for the active alarm
is set in the Alarm Words.
Each alarm has a dedicated bit
allocated within Alarm Words.
Bits remain set until the whole alarm
word is reset. (Reset by writing zero to
the word.)
The control panel displays the word in
hex. For example, all zeros and a 1 in
Bit 0 displays as 0001. All zeros and a
1 in Bit 15 displays as 8000.
0309 ALARM WORD 2
See parameter 0308.

Bit # 0305, FAULT WORD 1 0306, FAULT WORD 2 0307, FAULT WORD 3
0

OVERCURRENT

Obsolete

EFB 1

DC OVERVOLT

THERM FAIL

EFB 2

DEV OVERTEMP

OPEX LINK

EFB 3

SHORT CIRC

OPEX PWR

INCOMPATIBLE SW

Reserved

CURR MEAS

USER LOAD CURVE

DC UNDERVOLT

SUPPLY PHASE

Reserved

AI1 LOSS

ENCODER ERR

Reserved

AI2 LOSS

OVERSPEED

Reserved

MOT OVERTEMP

Reserved

Reserved

PANEL LOSS

DRIVE ID

Reserved

10

ID RUN FAIL

CONFIG FILE

System error

11

MOTOR STALL

SERIAL 1 ERR

System error

12

CB OVERTEMP

EFB CON FILE

System error

13

EXT FAULT 1

FORCE TRIP

System error

14

EXT FAULT 2

MOTOR PHASE

System error

15

EARTH FAULT

OUTP WIRING

Param. setting fault

Bit #

0308, ALARM WORD 1

0309, ALARM WORD 2

OVERCURRENT

Reserved

OVERVOLTAGE

PID SLEEP

UNDERVOLTAGE

ID RUN

DIR LOCK

Reserved

IO COMM

START ENABLE 1 MISSING

AI1 LOSS

START ENABLE 2 MISSING

AI2 LOSS

EMERGENCY STOP

PANEL LOSS

ENCODER ERROR

DEVICE OVERTEMP

FIRST START

MOTOR TEMP

Reserved

10

Reserved

USER LOAD CURVE

11

MOTOR STALL

START DELAY

12

AUTORESET

Reserved

13

AUTOCHANGE

Reserved

14

PFC I LOCK

Reserved

15

Reserved

Reserved

Parameters

114

ACS550-01/U1 Users Manual

Group 04: FAULT HISTORY


This group stores a recent history of the faults reported by the drive.
Code Description
0401 LAST FAULT
0 Clear the fault history (on panel = NO RECORD).
n Fault code of the last recorded fault. The fault code is displayed as a name. See section Fault listing on page 260
for the fault codes and names. The fault name shown for this parameter may be shorter than the corresponding
name in the fault listing, which shows the names as they are shown in the fault display.
0402 FAULT TIME 1
The day on which the last fault occurred. Either as:
A date if real time clock is operating.
The number of days after power on if real time clock is not used, or was not set.
0403 FAULT TIME 2
The time at which the last fault occurred. Either as:
Real time, in format hh:mm:ss if real time clock is operating.
The time since power on (minus the whole days reported in 0402), in format hh:mm:ss if real time clock is not
used, or was not set.
Format on the Basic Control Panel: The time since power on in 2-second ticks (minus the whole days reported in
0402). 30 ticks = 60 seconds. E.g. Value 514 equals 17 minutes and 8 seconds (= 514/30).
0404 SPEED AT FLT
The motor speed (rpm) at the time the last fault occurred.
0405 FREQ AT FLT
The frequency (Hz) at the time the last fault occurred.
0406 VOLTAGE AT FLT
The DC bus voltage (V) at the time the last fault occurred.
0407 CURRENT AT FLT
The motor current (A) at the time the last fault occurred.
0408 TORQUE AT FLT
The motor torque (%) at the time the last fault occurred.
0409 STATUS AT FLT
The drive status (hex code word) at the time the last fault occurred.
0410 DI 1-3 AT FLT
The status of digital inputs 13 at the time the last fault occurred.
0411 DI 4-6 AT FLT
The status of digital inputs 46 at the time the last fault occurred.
0412 PREVIOUS FAULT 1
Fault code of the second last fault. Read-only.
0413 PREVIOUS FAULT 2
Fault code of the third last fault. Read-only.

Parameters

ACS550-01/U1 Users Manual

115

Group 10: START/STOP/DIR


This group:
defines external sources (EXT1 and EXT2) for commands that enable start, stop
and direction changes
locks direction or enables direction control.
To select between the two external locations use the next group (parameter 1102).
Code Description
1001 EXT1 COMMANDS
Defines external control location 1 (EXT1) the configuration of start, stop and direction commands.
0 = NOT SEL No external start, stop and direction command source.
1 = DI1 Two-wire Start/Stop.
Start/Stop is through digital input DI1 (DI1 activated = Start; DI1 de-activated = Stop).
Parameter 1003 defines the direction. Selecting 1003 = 3 (REQUEST) is the same as 1003 = 1 (FORWARD).
2 = DI1,2 Two-wire Start/Stop, Direction.
Start/Stop is through digital input DI1 (DI1 activated = Start; DI1 de-activated = Stop).
Direction control [requires parameter 1003 = 3 (REQUEST)] is through digital input DI2
(DI2 activated = Reverse; de-activated = Forward).
3 = DI1P,2P Three-wire Start/Stop.
Start/Stop commands are through momentary push-buttons (the P stands for pulse).
Start is through a normally open push-button connected to digital input DI1. In order to start the drive, the digital
input DI2 must be activated prior to the pulse in DI1.
Connect multiple Start push-buttons in parallel.
Stop is through a normally closed push-button connected to digital input DI2.
Connect multiple Stop push-buttons in series.
Parameter 1003 defines the direction. Selecting 1003 = 3 (REQUEST) is the same as 1003 = 1 (FORWARD).
4 = DI1P,2P,3 Three-wire Start/Stop, Direction.
Start/Stop commands are through momentary push-buttons, as described for DI1P,2P.
Direction control [requires parameter 1003 = 3 (REQUEST)] is through digital input DI3
(DI3 activated = Reverse; de-activated = Forward).
5 = DI1P,2P,3P Start Forward, Start Reverse and Stop.
Start and Direction commands are given simultaneously with two separate momentary push-buttons (the P stands
for pulse).
Start Forward command is through a normally open push-button connected to digital input DI1. In order to start the
drive, the digital input DI3 must be activated prior to the pulse in DI1.
Start Reverse command is through a normally open push-button connected to digital input DI2. In order to start
the drive, the digital input DI3 must be activated during the pulse in DI2.
Connect multiple Start push-buttons in parallel.
Stop is through a normally closed push-button connected to digital input DI3.
Connect multiple Stop push-buttons in series.
Requires parameter 1003 = 3 (REQUEST).
6 = DI6 Two-wire Start/Stop.
Start/Stop is through digital input DI6 (DI6 activated = Start; DI6 de-activated = Stop).
Parameter 1003 defines the direction. Selecting 1003 = 3 (REQUEST) is the same as 1003 = 1 (FORWARD).
7 = DI6,5 Two-wire Start/Stop/Direction.
Start/Stop is through digital input DI6 (DI6 activated = Start; DI6 de-activated = Stop).
Direction control [requires parameter 1003 = 3 (REQUEST)] is through digital input DI5.
(DI5 activated = Reverse; de-activated = Forward).
8 = KEYPAD Control Panel.
Start/Stop and Direction commands are through the control panel when EXT1 is active.
Direction control requires parameter 1003 = 3 (REQUEST).
9 = DI1F,2R Start/Stop/Direction commands through DI1 and DI2 combinations.
Start forward = DI1 activated and DI2 de-activated.
Start reverse = DI1 de-activated and DI2 activated.
Stop = both DI1 and DI2 activated, or both de-activated.
Requires parameter 1003 = 3 (REQUEST).
10 = COMM Assigns the fieldbus Command Word as the source for the start/stop and direction commands.
Bits 0,1, 2 of Command Word 1 (parameter 0301) activates the start/stop and direction commands.
See Fieldbus users manual for detailed instructions.

Parameters

116

ACS550-01/U1 Users Manual

Code Description
11 = TIMED FUNC 1. Assigns Start/Stop control to Timed Function 1 (Timed Function activated = START; Timed
Function de-activated = STOP). See Group 36: TIMED FUNCTIONS.
1214 = TIMED FUNC 24 Assigns Start/Stop control to Timed Function 24. See TIMED FUNC 1 above.
1002 EXT2 COMMANDS
Defines external control location 2 (EXT2) the configuration of start, stop and direction commands.
See parameter 1001 EXT1 COMMANDS above.
1003 DIRECTION
Defines the control of motor rotation direction.
1 = FORWARD Rotation is fixed in the forward direction.
2 = REVERSE Rotation is fixed in the reverse direction.
3 = REQUEST Rotation direction can be changed on command.
1004 JOGGING SEL
Defines the signal that activates the jogging function. Jogging uses Constant Speed 7 (parameter 1208) for speed
reference and ramp pair 2 (parameters 2205 and 2206) for accelerating and decelerating. When the jogging
activation signal is lost, the drive uses ramp stop to decelerate to zero speed, even if coast stop is used in normal
operation (parameter 2102). The jogging status can be parameterized to relay outputs (parameter 1401). The jogging
status is also seen in DCU Profile status bit 21.
0 = NOT SEL Disables the jogging function.
1 = DI1 Activates/de-activates jogging based on the state of DI1 (DI1 activated = jogging active; DI1 de-activated =
jogging inactive).
26 = DI2DI6 Activates jogging based on the state of the selected digital input. See DI1 above.
-1 = DI1(INV) Activates jogging based on the state of DI1 (DI1 activated = jogging inactive; DI1 de-activated = jogging
active).
-2-6 = DI2(INV)DI6(INV) Activates jogging based on the state of the selected digital input. See DI1(INV) above.

Parameters

ACS550-01/U1 Users Manual

117

Group 11: REFERENCE SELECT


This group defines:
how the drive selects between command sources
characteristics and sources for REF1 and

REF2.

Code Description
1101 KEYPAD REF SEL
Selects the reference controlled in local control mode.
1 = REF1(Hz/rpm) Reference type depends on parameter 9904 MOTOR CTRL MODE.
Speed reference (rpm) if 9904 = 1 (VECTOR:sPEED) or 2 (VECTOR:TORQ).
Frequency reference (Hz) if 9904 = 3 (SCALAR:FREQ).
2 = REF2(%)
1102 EXT1/EXT2 SEL
Defines the source for selecting between the two external control locations EXT1 or EXT2. Thus, defines the source for
Start/Stop/Direction commands and reference signals.
0 = EXT1 Selects external control location 1 (EXT1).
See parameter 1001 EXT1 COMMANDS for EXT1s Start/Stop/Dir definitions.
See parameter 1103 REF1 SELECT for EXT1s reference definitions.
1 = DI1 Assigns control to EXT1 or EXT2 based on the state of DI1 (DI1 activated = EXT2; DI1 de-activated = EXT1).
26 = DI2DI6 Assigns control to EXT1 or EXT2 based on the state of the selected digital input. See DI1 above.
7 = EXT2 Selects external control location 2 (EXT2).
See parameter 1002 EXT2 COMMANDS for EXT2s Start/Stop/Dir definitions.
See parameter 1106 REF2 SELECT for EXT2s reference definitions.
8 = COMM Assigns control of the drive via external control location EXT1 or EXT2 based on the fieldbus control word.
Bit 5 of the Command Word 1 (parameter 0301) defines the active external control location (EXT1 or EXT2).
See Fieldbus users manual for detailed instructions.
9 = TIMED FUNC 1 Assigns control to EXT1 or EXT2 based on the state of the Timed Function (Timed Function
activated = EXT2; Timed Function de-activated = EXT1). See Group 36: TIMED FUNCTIONS.
1012 = TIMED FUNC 24 Assigns control to EXT1 or EXT2 based on the state of the Timed Function. See TIMED
FUNC 1 above.
-1 = DI1(INV) Assigns control to EXT1 or EXT2 based on the state of DI1 (DI1 activated = EXT1; DI1 de-activated =
EXT2).
-2-6 = DI2(INV)DI6(INV) Assigns control to EXT1 or EXT2 based on the state of the selected digital input. See
DI1(INV) above.
1103 REF1 SELECT
EXT REF 1 MAX
Selects the signal source for external reference REF1.
0 = KEYPAD Defines the control panel as the reference
source.
EXT REF 1 MIN
1 = AI1 Defines analog input 1 (AI1) as the reference
source.
2 = AI2 Defines analog input 2 (AI2) as the reference
- EXT REF 1 MIN
source.
10 V /
3 = AI1/JOYST Defines analog input 1 (AI1), configured for
20 mA
joystick operation, as the reference source.
- EXT REF 1 MAX
The minimum input signal runs the drive at the maximum
2 V / 4 mA
reference in the reverse direction. Define the minimum
0 V / 0 mA
using parameter 1104.
EXT REF 1 MIN
-2%
+2%
The maximum input signal runs the drive at maximum
reference in the forward direction. Define the maximum
- EXT REF 1 MIN
using parameter 1105.
Hysteresis 4% of full scale
Requires parameter 1003 = 3 (REQUEST).
WARNING! Because the low end of the reference
range commands full reverse operation, do not use 0 V as the lower end of the reference range. Doing so
means that if the control signal is lost (which is a 0 V input) the result is full reverse operation. Instead, use
the following set-up so that loss of the analog input triggers a fault, stopping the drive:
Set parameter 1301 MINIMUM AI1 (1304 MINIMUM AI2) at 20% (2 V or 4 mA).
Set parameter 3021 AI1 FAULT LIMIT to a value 5% or higher.
Set parameter 3001 AI<MIN FUNCTION to 1 (FAULT).
4 = AI2/JOYST Defines analog input 2 (AI2), configured for joystick operation, as the reference source.
See above (AI1/JOYST) description.

Parameters

118

ACS550-01/U1 Users Manual

Code Description
5 = DI3U,4D(R) Defines digital inputs as the speed reference source (motor potentiometer control).
Digital input DI3 increases the speed (the U stands for up).
Digital input DI4 decreases the speed (the D stands for down).
A Stop command resets the reference to zero (the R stands for reset).
Parameter 2205 ACCELER TIME 2 controls the reference signals rate of change.
6 = DI3U,4D Same as above (DI3U,4D(R)), except:
A Stop command does not reset the reference to zero. The reference is stored.
When the drive restarts, the motor ramps up (at the selected acceleration rate) to the stored reference.
7 = DI5U,6D Same as above (DI3U,4D), except that DI5 and DI6 are the digital inputs used.
8 = COMM Defines the fieldbus as the reference source.
9 = COMM+AI1 Defines a fieldbus and analog input 1 (AI1) combination as the reference source. See Analog input
reference correction below.
10 = COMM*AI1 Defines a fieldbus and analog input 1 (AI1) combination as the reference source. See Analog input
reference correction below.
11 = DI3U,4D(RNC) Same as DI3U,4D(R) above, except that:
Changing the control source (EXT1 to EXT2, EXT2 to EXT1, LOC to REM) does not copy the reference.
12 = DI3U,4D(NC) Same as DI3U,4D above, except that:
Changing the control source (EXT1 to EXT2, EXT2 to EXT1, LOC to REM) does not copy the reference.
Stop command resets reference to zero.
13 = DI5U,6D(NC) Same as DI5U,6D above, except that:
Changing the control source (EXT1 to EXT2, EXT2 to EXT1, LOC to REM) does not copy the reference.
14 = AI1+AI2 Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See
Analog input reference correction below.
15 = AI1*AI2 Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See
Analog input reference correction below.
16 = AI1-AI2 Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See
Analog input reference correction below.
17 = AI1/AI2 Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See
Analog input reference correction below.
20 = KEYPAD(RNC) Defines the control panel as the reference source.
A Stop command resets the reference to zero (the R stands for reset.).
Changing the control source (EXT1 to EXT2, EXT2 to EXT1) does not copy the reference.
21 = KEYPAD(NC) Defines the control panel as the reference source.
A Stop command does not reset the reference to zero. The reference is stored.
Changing the control source (EXT1 to EXT2, EXT2 to EXT1) does not copy the reference.
Analog input reference correction
Parameter values 9, 10 and 1417 use the formula in the following table.
Value setting
C+B
C*B
C-B
C/B

Calculation of the AI reference


C value + (B value - 50% of reference value)
C value (B value / 50% of reference value)
(C value + 50% of reference value) - B value
(C value 50% of reference value) / B value

Where:
C = Main reference value
( = COMM for values 9, 10 and
= AI1 for values 1417).
B = Correcting reference
( = AI1 for values 9, 10 and
= AI2 for values 1417).
Example:
The figure shows the reference source curves for value
settings 9, 10 and 1417, where:
C = 25%.
P 4012 SETPOINT MIN = 0.
P 4013 SETPOINT MAX = 0.
B varies along the horizontal axis.

Parameters

120

17 (/)

100
80
60

9, 14 (+)

40

10, 15 (*)

20
0

16 (-)
100% B

ACS550-01/U1 Users Manual

119

Code Description
1104 REF1 MIN
Sets the minimum for external reference 1.
The minimum analog input signal (as a percent of the full
signal in volts or amperes) corresponds to REF1 MIN in
Hz/rpm.
Parameter 1301 MINIMUM AI1 or 1304 MINIMUM AI2 sets
the minimum analog input signal.
These parameters (reference and analog min. and max.
settings) provide scale and offset adjustment for the
reference.
1105 REF1 MAX
Sets the maximum for external reference 1.
The maximum analog input signal (as a percent of full
the signal in volts or amperes) corresponds to REF1 MAX
in Hz/rpm.
Parameter 1302 MAXIMUM AI1 or 1305 MAXIMUM AI2 sets
the maximum analog input signal.

Ext ref
P 1105
(MAX)

Analog
input signal

P 1104
(MIN)
P 1301
or 1304

P 1302
or 1305

Ext ref
P 1104
(MIN)

P 1105
(MAX)

Analog
P 1301
or 1304

P 1302
or 1305

input signal

1106 REF2 SELECT


Selects the signal source for external reference REF2.
017 Same as for parameter 1103 REF1 SELECT.
19 = PID1OUT The reference is taken from the PID1 output. See Group 40: PROCESS PID SET 1 and Group 41:
PROCESS PID SET 2.
2021 Same as for parameter 1103 REF1 SELECT.
19= PID1

REF2
SELECT

117
2021

If PFC is used

LIMIT
MAX
MIN

(1107, 1108)

PFC

(1107, 1108)

1107 REF2 MIN


Sets the minimum for external reference 2.
The minimum analog input signal (in volts or amperes) corresponds to REF2 MIN in %.
Parameter 1301 MINIMUM AI1 or 1304 MINIMUM AI2 sets the minimum analog input signal.
This parameter sets the minimum frequency reference.
The value is a percentage of the:
maximum frequency or speed
maximum process reference
nominal torque.
1108 REF2 MAX
Sets the maximum for external reference 2.
The maximum analog input signal (in volts or amperes) corresponds to REF2 MAX in %.
Parameter 1302 MAXIMUM AI1 or 1305 MAXIMUM AI2 sets the maximum analog input signal.
This parameter sets the maximum frequency reference.
The value is a percentage of the:
maximum frequency or speed
maximum process reference
nominal torque.

Parameters

120

ACS550-01/U1 Users Manual

Group 12: CONSTANT SPEEDS


This group defines a set of constant speeds. In general:
You can program up to 7 constant speeds, ranging from 0500 Hz or
030000 rpm.
Values must be positive (No negative speed values for constant speeds).
Constant speed selections are ignored if:

the torque control is active, or


the process PID reference is followed, or
the drive is in local control mode, or
PFC (Pump-Fan Control) is active.

Note: Parameter 1208 CONST SPEED 7 acts also as a so-called fault speed which
may be activated if the control signal is lost. For example, see parameters 3001
AI<MIN FUNCTION, 3002 PANEL COMM ERR and 3018 COMM FAULT FUNC.
Code Description
1201 CONST SPEED SEL
Defines the digital inputs used to select Constant Speeds. See general comments in introduction.
0 = NOT SEL Disables the constant speed function.
1 = DI1 Selects Constant Speed 1 with digital input DI1.
Digital input activated = Constant Speed 1 activated.
26 = DI2DI6 Selects Constant Speed 1 with digital input DI2DI6. See above.
7 = DI1,2 Selects one of three Constant Speeds (13) using DI1 and DI2.
Uses two digital inputs, as defined below (0 = DI de-activated, 1 = DI activated):
DI1

DI2

0
1
0
1

0
0
1
1

Function
No constant speed
Constant speed 1 (1202)
Constant speed 2 (1203)
Constant speed 3 (1204)

Can be set up as a so-called fault speed, which is activated if the control signal is lost. Refer to parameter 3001
AI<MIN function and parameter 3002 PANEL COMM ERR.
8 = DI2,3 Selects one of three Constant Speeds (13) using DI2 and DI3.
See above (DI1,2) for code.
9 = DI3,4 Selects one of three Constant Speeds (13) using DI3 and DI4.
See above (DI1,2) for code.
10 = DI4,5 Selects one of three Constant Speeds (13) using DI4 and DI5.
See above (DI1,2) for code.
11 = DI5,6 Selects one of three Constant Speeds (13) using DI5 and DI6.
See above (DI1,2) for code.
12 = DI1,2,3 Selects one of seven Constant Speeds (17) using DI1, DI2 and DI3.
Uses three digital inputs, as defined below (0 = DI de-activated, 1 = DI activated):
DI1
0
1
0
1
0
1
0
1

Parameters

DI2
0
0
1
1
0
0
1
1

DI3
0
0
0
0
1
1
1
1

Function
No constant speed
Constant speed 1 (1202)
Constant speed 2 (1203)
Constant speed 3 (1204)
Constant speed 4 (1205)
Constant speed 5 (1206)
Constant speed 6 (1207)
Constant speed 7 (1208)

ACS550-01/U1 Users Manual

121

Code Description
13 = DI3,4,5 Selects one of seven Constant Speeds (17) using DI3, DI4 and DI5.
See above (DI1,2,3) for code.
14 = DI4,5,6 Selects one of seven Constant Speeds (17) using DI4, DI5 and DI6.
See above (DI1,2,3) for code.
1518 = TIMED FUNC 14 Selects Constant Speed 1, Constant Speed 2 or the external reference, depending on
the state of the Timed Function (14) and constant speed mode. See parameter 1209 TIMED MODE SEL and Group
36: TIMED FUNCTIONS.
19 = TIMED FUN1&2 Selects a constant speed or the external reference, depending on the state of Timed Functions
1 & 2 and constant speed mode. See parameter 1209 TIMED MODE SEL and Group 36: TIMED FUNCTIONS.
-1 = DI1(INV) Selects Constant Speed 1 with digital input DI1.
Inverse operation: Digital input de-activated = Constant Speed 1 activated.
-2- 6 = DI2(INV)DI6(INV) Selects Constant Speed 1 with digital input. See above.
-7 = DI1,2(INV) Selects one of three Constant Speeds (13) using DI1 and DI2.
Inverse operation uses two digital inputs, as defined below (0 = DI de-activated, 1 = DI activated):
DI1 DI2

1
0
1
0

1
1
0
0

Function
No constant speed
Constant speed 1 (1202)
Constant speed 2 (1203)
Constant speed 3 (1204)

-8 = DI2,3(INV) Selects one of three Constant Speeds (13) using DI2 and DI3.
See above (DI1,2(INV)) for code.
-9 = DI3,4(INV) Selects one of three Constant Speeds (13) using DI3 and DI4.
See above (DI1,2(INV)) for code.
-10 = DI4,5(INV) Selects one of three Constant Speeds (13) using DI4 and DI5.
See above (DI1,2(INV)) for code.
-11 = DI5,6(INV) Selects one of three Constant Speeds (13) using DI5 and DI6.
See above (DI1,2(INV)) for code.
-12 = DI1,2,3(INV) Selects one of seven Constant Speeds (17) using DI1, DI2 and DI3.
Inverse operation uses three digital inputs, as defined below (0 = DI de-activated, 1 = DI activated):
DI1 DI2

1
0
1
0
1
0
1
0

1
1
0
0
1
1
0
0

DI3

1
1
1
1
0
0
0
0

Function
No constant speed
Constant speed 1 (1202)
Constant speed 2 (1203)
Constant speed 3 (1204)
Constant speed 4 (1205)
Constant speed 5 (1206)
Constant speed 6 (1207)
Constant speed 7 (1208)

-13 = DI3,4,5(INV) Selects one of seven Constant Speeds (17) using DI3, DI4 and DI5.
See above (DI1,2,3(INV)) for code.
-14 = DI4,5,6(INV) Selects one of seven Constant Speeds (17) using DI4, DI5 and DI6.
See above (DI1,2,3(INV)) for code.
1202 CONST SPEED 1
Sets value for Constant Speed 1.
The range and units depend on parameter 9904 MOTOR CTRL MODE.
Range: 030000 rpm when 9904 = 1 (VECTOR:SPEED) or 2 (VECTOR:TORQ).
Range: 0500 Hz when 9904 = 3 (SCALAR:FREQ).
1203 CONST SPEED 2CONST SPEED 7
Each sets a value for a Constant Speed. See CONST SPEED 1 above.

1208 Constant Speed 7 is used also as jogging speed. See parameter 1004 JOGGING SEL.

Parameters

122

ACS550-01/U1 Users Manual

Code Description
1209 TIMED MODE SEL
Defines timed function activated constant speed mode. Timed function can be used to change between the external
reference and constant speeds when parameter 1201 CONST SPEED SEL = 1518 (TIMED FUNC 14) or 19 (TIMED
FUN1&2).
1 = EXT/CS1/2/3
If parameter 1201 = 1518 (TIMED FUNC 14), selects an external speed when this timed function (14) is not
active and selects Constant speed 1 when it is active.
TIMED FUNCTION

14

0
1

Function
External reference
Constant speed 1 (1202)

If parameter 1201 = 19 (TIMED FUN1&2), selects an external speed when neither timed function is active, selects
Constant speed 1 when only Timed function 1 is active, selects Constant speed 2 when only Timed function 2 is
active and selects Constant speed 3 when both Timed functions 1 and 2 are active.
TIMED FUNCTION

0
1
0
1

TIMED FUNCTION

0
0
1
1

Function
External reference
Constant speed 1 (1202)
Constant speed 2 (1203)
Constant speed 3 (1204)

2 = CS1/2/3/4
If parameter 1201 = 1518 (TIMED FUNC 14), selects Constant speed 1 when this timed function (14) is not
active and selects Constant speed 2 when it is active.
TIMED FUNCTION

14

0
1

Function
Constant speed 1 (1202)
Constant speed 2 (1203)

If parameter 1201 = 19 (TIMED FUN1&2), selects Constant speed 1 when neither timed function is active, selects
Constant speed 2 when only Timed function 1 is active, selects Constant speed 3 when only Timed function 2 is
active and selects Constant speed 4 when both Timed functions 1 and 2 are active.
TIMED FUNCTION

0
1
0
1

Parameters

TIMED FUNCTION

0
0
1
1

Function
Constant speed 1 (1202)
Constant speed 2 (1203)
Constant speed 3 (1204)
Constant speed 4 (1205)

ACS550-01/U1 Users Manual

123

Group 13: ANALOG INPUTS


This group defines the limits and the filtering for analog inputs.
Code Description
1301 MINIMUM AI1
Defines the minimum value of the analog input.
Define value as a percent of the full analog signal range. See example below.
The minimum analog input signal corresponds to 1104 REF1 MIN or 1107 REF2 MIN.
MINIMUM AI cannot be greater than MAXIMUM AI.
These parameters (reference and analog min. and max. settings) provide scale and offset adjustment for the
reference.
See the figure at parameter 1104.
Example: To set the minimum analog input value to 4 mA:
Configure the analog input for 020 mA current signal.
Calculate the minimum (4 mA) as a percent of full range (20 mA) = 4 mA / 20 mA 100% = 20%
1302 MAXIMUM AI1
Defines the maximum value of the analog input.
Define value as a percent of the full analog signal range.
The maximum analog input signal corresponds to 1105 REF1 MAX or 1108 REF2 MAX.
See the figure at parameter 1104.
1303 FILTER AI1
Defines the filter time constant for analog input 1 (AI1).
The filtered signal reaches 63% of a step change within the time
specified.

Unfiltered signal

100
63

Filtered signal

t
Time constant
1304 MINIMUM AI2
Defines the minimum value of the analog input.
See MINIMUM AI1 above.
1305 MAXIMUM AI2
Defines the maximum value of the analog input.
See MAXIMUM AI1 above.
1306 FILTER AI2
Defines the filter time constant for analog input 2 (AI2).
See FILTER AI1 above.

Parameters

124

ACS550-01/U1 Users Manual

Group 14: RELAY OUTPUTS


This group defines the condition that activates each of the relay outputs. Relay
outputs 46 are only available if OREL-01 Relay Output Extension Module is
installed.
Code Description
1401 RELAY OUTPUT 1
Defines the event or condition that activates relay 1 what relay output 1 means.
0 = NOT SEL Relay is not used and is de-energized.
1 = READY Energize relay when drive is ready to function. Requires:
Run enable signal present.
No faults exist.
Supply voltage is within range.
Emergency Stop command is not on.
2 = RUN Energize relay when the drive is running.
3 = FAULT(-1) Energize relay when power is applied. De-energizes when a fault occurs.
4 = FAULT Energize relay when a fault is active.
5 = ALARM Energize relay when an alarm is active.
6 = REVERSED Energize relay when motor rotates in reverse direction.
7 = STARTED Energize relay when drive receives a start command (even if Run Enable signal is not present). Deenergized relay when drive receives a stop command or a fault occurs.
8= SUPRV1 OVER Energize relay when first supervised parameter (3201) exceeds the limit (3203).
See Group 32: SUPERVISION starting on page 153.
9 = SUPRV1 UNDER Energize relay when first supervised parameter (3201) drops below the limit (3202).
See Group 32: SUPERVISION starting on page 153.
10 = SUPRV2 OVER Energize relay when second supervised parameter (3204) exceeds the limit (3206).
See Group 32: SUPERVISION starting on page 153.
11 = SUPRV2 UNDER Energize relay when second supervised parameter (3204) drops below the limit (3205).
See Group 32: SUPERVISION starting on page 153.
12 = SUPRV3 OVER Energize relay when third supervised parameter (3207) exceeds the limit (3209).
See Group 32: SUPERVISION starting on page 153.
13 = SUPRV3 UNDER Energize relay when third supervised parameter (3207) drops below the limit (3208).
See Group 32: SUPERVISION starting on page 153.
14 = AT SET POINT Energize relay when the output frequency is equal to the reference frequency.
15 = FAULT(RST) Energize relay when the drive is in a fault condition and will reset after the programmed auto-reset
delay.
See parameter 3103 DELAY TIME.
16 = FLT/ALARM Energize relay when fault or alarm occurs.
17 = EXT CTRL Energize relay when external control is selected.
18 = REF 2 SEL Energize relay when EXT2 is selected.
19 = CONST FREQ Energize relay when a constant speed is selected.
20 = REF LOSS Energize relay when reference or active control place is lost.
21 = OVERCURRENT Energize relay when an overcurrent alarm or fault occurs.
22 = OVERVOLTAGE Energize relay when an overvoltage alarm or fault occurs.
23 = DRIVE TEMP Energize relay when a drive or control board overtemperature alarm or fault occurs.
24 = UNDERVOLTAGE Energize relay when an undervoltage alarm or fault occurs.
25 = AI1 LOSS Energize relay when AI1 signal is lost.
26 = AI2 LOSS Energize relay when AI2 signal is lost.
27 = MOTOR TEMP Energize relay when a motor overtemperature alarm or fault occurs.
28 = STALL Energize relay when a stall alarm or fault exists.
30 = PID SLEEP Energize relay when the PID sleep function is active.
31 = PFC Use relay to start/stop motor in PFC control (See Group 81: PFC CONTROL).
Use this option only when PFC control is used.
Selection activated / deactivated when drive is not running.
32 = AUTOCHANGE Energize relay when PFC autochange operation is performed.
Use this option only when PFC control is used.
33 = FLUX READY Energize relay when the motor is magnetized and able to supply nominal torque (motor has
reached nominal magnetizing).
34 = USER MACRO 2 Energize relay when User Parameter Set 2 is active.

Parameters

ACS550-01/U1 Users Manual

125

Code Description
35 = COMM Energize relay based on input from fieldbus communication.
Fieldbus writes binary code in parameter 0134 that can energize relay 1relay 6 according to the following:
Par. 0134
0
1
2
3
4
562
63

Binary
000000
000001
000010
000011
000100

111111

RO6
0
0
0
0
0

RO5 RO4 RO3 RO2 RO1


0
0
0
0
0
0
0
0
0
1
0
0
0
1
0
0
0
0
1
1
0
0
1
0
0

1
1
1
1
1

0 = De-energize relay, 1 = Energize relay.


36 = COMM(-1) Energize relay based on input from fieldbus communication.
Fieldbus writes binary code in parameter 0134 that can energize relay 1relay 6 according to the following:
Par. 0134 Binary
RO6
0
000000
1
1
000001
1
2
000010
1
3
000011
1
4
000100
1
562

63
111111
0

RO5 RO4 RO3 RO2 RO1


1
1
1
1
1
1
1
1
1
0
1
1
1
0
1
1
1
1
0
0
1
1
0
1
1

0
0
0
0
0

0 = De-energize relay, 1 = Energize relay.


37 = TIMED FUNC 1 Energize relay when Timed Function 1 is active. See Group 36: TIMED FUNCTIONS.
3840 = TIMED FUNC 24 Energize relay when Timed Function 24 is active. See TIMED FUNC 1 above.
41 = MNT TRIG FAN Energize relay when cooling fan counter is triggered. See Group 29: MAINTENANCE TRIG.
42 = MNT TRIG REV Energize relay when revolutions counter is triggered. See Group 29: MAINTENANCE TRIG.
43 = MNT TRIG RUN Energize relay when run time counter is triggered. See Group 29: MAINTENANCE TRIG.
44 = MNT TRIG MWH Energize relay when MWh counter is triggered. See Group 29: MAINTENANCE TRIG.
46 = START DELAY Energize relay when a start delay is active.
47 = USER LOAD C Energize relay when a user load curve fault or alarm occurs.
52 = JOG ACTIVE Energize relay when the jogging function is active.
1402 RELAY OUTPUT 2
Defines the event or condition that activates relay 2 what relay output 2 means.
See 1401 RELAY OUTPUT 1.
1403 RELAY OUTPUT 3
Defines the event or condition that activates relay 3 what relay output 3 means.
See 1401 RELAY OUTPUT 1.
1404 RO 1 ON DELAY
Control event
Defines the switch-on delay for relay 1.
On / off delays are ignored when relay output 1401 is set to PFC.
1405 RO 1 OFF DELAY
Defines the switch-off delay for relay 1.
On / off delays are ignored when relay output 1401 is set to PFC.

Relay status
1404 ON DELAY 1405 OFF DELAY

1406 RO 2 ON DELAY
Defines the switch-on delay for relay 2.
See RO 1 ON DELAY.
1407 RO 2 OFF DELAY
Defines the switch-off delay for relay 2.
See RO 1 OFF DELAY.
1408 RO 3 ON DELAY
Defines the switch-on delay for relay 3.
See RO 1 ON DELAY.

Parameters

126

ACS550-01/U1 Users Manual

Code Description
1409 RO 3 OFF DELAY
Switch-off delay for relay 3.
See RO 1 OFF DELAY.
1410 RELAY OUTPUT 46

Defines the event or condition that activates relay 46 what relay output 46 means. Available if OREL-01 Relay
1412 Output Extension Module is installed.
See 1401 RELAY OUTPUT 1.
1413 RO 4 ON DELAY
Defines the switch-on delay for relay 4.
See RO 1 ON DELAY.
1414 RO 4 OFF DELAY
Defines the switch-off delay for relay 4.
See RO 1 OFF DELAY.
1415 RO 5 ON DELAY
Defines the switch-on delay for relay 5.
See RO 1 ON DELAY.
1416 RO 5 OFF DELAY
Defines the switch-off delay for relay 5.
See RO 1 OFF DELAY.
1417 RO 6 ON DELAY
Defines the switch-on delay for relay 6.
See RO 1 ON DELAY.
1418 RO 6 OFF DELAY
Defines the switch-off delay for relay 6.
See RO 1 OFF DELAY.

Parameters

ACS550-01/U1 Users Manual

127

Group 15: ANALOG OUTPUTS


This group defines the drives analog (current signal) outputs. The drives analog
outputs can be:
any parameter in Group 01: OPERATING DATA
limited to programmable minimum and maximum values of output current
scaled (and/or inverted) by defining the minimum and maximum values of the
source parameter (or content). Defining an maximum value (parameter 1503 or
1509) that is less than the content minimum value (parameter 1502 or 1508)
results in an inverted output.
filtered.
Code Description
1501 AO1 CONTENT SEL
Defines the content for analog output AO1.
99 = EXCITE PTC Provides a current source for sensor type PTC. Output = 1.6 mA. See Group 35: MOTOR TEMP
MEAS.
100 = EXCITE PT100 Provides a current source for sensor type PT100. Output = 9.1 mA. See Group 35: MOTOR
TEMP MEAS.
101178 Output corresponds to a parameter in Group 01: OPERATING DATA.
Parameter defined by value (value 102 = parameter 0102)
1502 AO1 CONTENT MIN
Sets the minimum content value.
Content is the parameter selected by parameter 1501.
Minimum value refers to the minimum content value that will be
converted to an analog output.
These parameters (content and current min. and max. settings)
provide scale and offset adjustment for the output. See the
figure.
1503 AO1 CONTENT MAX
Sets the maximum content value
Content is the parameter selected by parameter 1501.
Maximum value refers to the maximum content value that will
be converted to an analog output.
1504 MINIMUM AO1
Sets the minimum output current.
1505 MAXIMUM AO1
Sets the maximum output current.
1506 FILTER AO1
Defines the filter time constant for AO1.
The filtered signal reaches 63% of a step change within the time
specified.
See the figure in parameter 1303.

AO (mA)
P 1505 /
P 1511

P 1504 /
P 1510

AO CONTENT

P 1502 / 1508
P 1505 /
P 1511

P 1503 / 1509

AO (mA)

P 1504 /
P 1510

AO CONTENT

P 1503 / 1509

P 1502 / 1508

1507 AO2 CONTENT SEL


Defines the content for analog output AO2. See AO1 CONTENT SEL above.
1508 AO2 CONTENT MIN
Sets the minimum content value. See AO1 CONTENT MIN above.
1509 AO2 CONTENT MAX
Sets the maximum content value. See AO1 CONTENT MAX above.
1510 MINIMUM AO2
Sets the minimum output current. See MINIMUM AO1 above.

Parameters

128
Code Description
1511 MAXIMUM AO2
Sets the maximum output current. See MAXIMUM AO1 above.
1512 FILTER AO2
Defines the filter time constant for AO2. See FILTER AO1 above.

Parameters

ACS550-01/U1 Users Manual

ACS550-01/U1 Users Manual

129

Group 16: SYSTEM CONTROLS


This group defines a variety of system level locks, resets and enables.
Code Description
1601 RUN ENABLE
Selects the source of the run enable signal.
0 = NOT SEL Allows the drive to start without an external run enable signal.
1 = DI1 Defines digital input DI1 as the run enable signal.
This digital input must be activated for run enable.
If the voltage drops and de-activates this digital input, the drive will coast to stop and not start until the run enable
signal resumes.
26 = DI2DI6 Defines digital input DI2DI6 as the run enable signal.
See DI1 above.
7 = COMM Assigns the fieldbus Command Word as the source for the run enable signal.
Bit 6 of the Command Word 1 (parameter 0301) activates the run disable signal.
See fieldbus users manual for detailed instructions.
-1 = DI1(INV) Defines an inverted digital input DI1 as the run enable signal.
This digital input must be de-activated for run enable.
If this digital input activates, the drive will coast to stop and not start until the run enable signal resumes.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the run enable signal.
See DI1(INV) above.
1602 PARAMETER LOCK
Determines if the control panel can change parameter values.
This lock does not limit parameter changes made by macros.
This lock does not limit parameter changes written by fieldbus inputs.
This parameter value can be changed only if the correct pass code is entered. See parameter 1603 PASS CODE.
0 = LOCKED You cannot use the control panel to change parameter values.
The lock can be opened by entering the valid pass code to parameter 1603.
1 = OPEN You can use the control panel to change parameter values.
2 = NOT SAVED You can use the control panel to change parameter values, but they are not stored in permanent
memory.
Set parameter 1607 PARAM SAVE to 1 (SAVE) to store changed parameter values to memory.
1603 PASS CODE
Entering the correct pass code allows you to change the parameter lock.
See parameter 1602 above.
The code 358 allows you to change the value of the parameter 1602 once.
This entry reverts back to 0 automatically.
1604 FAULT RESET SEL
Selects the source for the fault reset signal. The signal resets the drive after a fault trip if the cause of the fault no
longer exists.
0 = KEYPAD Defines the control panel as the only fault reset source.
Fault reset is always possible with control panel.
1 = DI1 Defines digital input DI1 as a fault reset source.
Activating the digital input resets the drive.
26 = DI2DI6 Defines digital input DI2DI6 as a fault reset source.
See DI1 above.
7 = START/STOP Defines the Stop command as a fault reset source.
Do not use this option when fieldbus communication provides the start, stop and direction commands.
8 = COMM Defines the fieldbus as a fault reset source.
The Command Word is supplied through fieldbus communication.
The bit 4 of the Command Word 1 (parameter 0301) resets the drive.
-1 = DI1(INV) Defines an inverted digital input DI1 as a fault reset source.
De-activating the digital input resets the drive.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as a fault reset source.
See DI1(INV) above.

Parameters

130

ACS550-01/U1 Users Manual

Code Description
1605 USER PAR SET CHG
Defines control for changing the user parameter set.
See parameter 9902 APPLIC MACRO.
The drive must be stopped to change User Parameter Sets.
During a change, the drive will not start.
Note: Always save the User Parameter Set after changing any parameter settings, or performing a motor
identification.
Whenever the power is cycled, or parameter 9902 APPLIC MACRO is changed, the drive loads the last settings
saved. Any unsaved changes to a user parameter set are lost.
Note: The value of this parameter (1605) is not included in the User Parameter Sets, and it does not change if User
Parameter Sets change.
Note: You can use a relay output to supervise the selection of User Parameter Set 2.
See parameter 1401.
0 = NOT SEL Defines the control panel (using parameter 9902) as the only control for changing User Parameter
Sets.
1 = DI1 Defines digital input DI1 as a control for changing User Parameter Sets.
The drive loads User Parameter Set 1 on the falling edge of the digital input.
The drive loads User Parameter Set 2 on the rising edge of the digital input.
The User Parameter Set changes only when the drive is stopped.
26 = DI2DI6 Defines digital input DI2DI6 as a control for changing User Parameter Sets.
See DI1 above.
-1 = DI1(INV) Defines an inverted digital input DI1 as a control for changing User Parameter Sets.
The drive loads User Parameter Set 1 on the rising edge of the digital input.
The drive loads User Parameter Set 2 on the falling edge of the digital input.
The User Parameter Set changes only when the drive is stopped.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as a control for changing User Parameter Sets.
See DI1(INV) above.
1606 LOCAL LOCK
Defines control for the use of the LOC mode. The LOC mode allows drive control from the control panel.
When LOCAL LOCK is active, the control panel cannot change to LOC mode.
0 = NOT SEL Disables the lock. The control panel can select LOC and control the drive.
1 = DI1 Defines digital input DI1 as the control for setting the local lock.
Activating the digital input locks out local control.
De-activating the digital input enable the LOC selection.
26 = DI2DI6 Defines digital input DI2DI6 as the control for setting the local lock.
See DI1 above.
7 = ON Sets the lock. The control panel cannot select LOC and cannot control the drive.
8 = COMM Defines bit 14 of the Command Word 1 as the control for setting the local lock.
The Command Word is supplied through fieldbus communication.
The Command Word is 0301.
-1 = DI1(INV) Defines an inverted digital input DI1 as the control for setting the local lock.
De-activating the digital input locks out local control.
Activating the digital input enable the LOC selection.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the control for setting the local lock.
See DI1(INV) above.
1607 PARAM SAVE
Saves all altered parameters to permanent memory.
Parameters altered through a fieldbus are not automatically saved to permanent memory. To save, you must use
this parameter.
If 1602 PARAMETER LOCK = 2 (NOT SAVED), parameters altered from the control panel are not saved. To save, you
must use this parameter.
If 1602 PARAMETER LOCK = 1 (OPEN), parameters altered from the control panel are stored immediately to
permanent memory.
0 = DONE Value changes automatically when all parameters are saved.
1 = SAVE Saves altered parameters to permanent memory.

Parameters

ACS550-01/U1 Users Manual

131

Code Description
1608 START ENABLE 1
Selects the source of the start enable 1 signal.
Note: Start enable functionality differs from the run enable functionality.
0 = NOT SEL Allows the drive to start without an external start enable signal.
1 = DI1 Defines digital input DI1 as the start enable 1 signal.
This digital input must be activated for start enable 1 signal.
If the voltage drops and de-activates this digital input, the drive will coast to stop and show alarm 2021 on the
panel display. The drive will not start until start enable 1 signal resumes.
26 = DI2DI6 Defines digital input DI2DI6 as the start enable 1 signal.
See DI1 above.
7 = COMM Assigns the fieldbus Command Word as the source for the start enable 1 signal.
Bit 2 of the Command word 2 (parameter 0302) activates the start disable 1 signal.
See fieldbus users manual for detailed instructions.
-1 = DI1(INV) Defines an inverted digital input DI1 as the start enable 1 signal.
-2-6 = DI2 (INV)DI6(INV) Defines an inverted digital input DI2DI6 as the start enable 1 signal.
See DI1 (INV) above.
Drive started

START/STOP
COMMAND
(Group 10)
START ENABLE
SIGNAL
(Parameters
1608 & 1609)

Relay
de-energized

Relay energized

STARTED
RELAY STATUS
(Group 14)
Damper open
Damper
closed DAMPER
STATUS
Damper
closing
time

Damper
closed
Damper
opening
time

RUN ENABLE SIGNAL


from the damper end
switch when the
damper is fully opened.
(Parameter 1601)
MOTOR STATUS
Acceleration
time
(Par 2202)

Drive coasts
to stop

Parameters

132

ACS550-01/U1 Users Manual

Code Description
1609 START ENABLE 2
Selects the source of the start enable 2 signal.
Note: Start enable functionality differs from the run enable functionality.
0 = NOT SEL Allows the drive to start without an external start enable signal.
1 = DI1 Defines digital input DI1 as the start enable 2 signal.
This digital input must be activated for start enable 2 signal.
If the voltage drops and de-activates this digital input, the drive will coast to stop and show alarm 2022 on the
panel display. The drive will not start until start enable 2 signal resumes.
26 = DI2DI6 Defines digital input DI2DI6 as the start enable 2 signal.
See DI1 above.
7 = COMM Assigns the fieldbus Command Word as the source for the start enable 2 signal. Bit 3 of the Command
word 2 (parameter 0302) activates the start disable 2 signal.
See fieldbus users manual for detailed instructions.
-1 = DI1(INV) Defines an inverted digital input DI1 as the start enable 2 signal.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the start enable 2 signal.
See DI1 (INV) above.
1610 DISPLAY ALARMS
Controls the visibility of the following alarms:
2001, Overcurrent alarm
2002, Overvoltage alarm
2003, Undervoltage alarm
2009, Device overtemperature alarm.
For more information, see section Alarm listing on page 267.
0 = NO The above alarms are suppressed.
1 = YES All of the above alarms are enabled.
1611 PARAMETER VIEW
Selects the parameter view, i.e. which parameters are shown.
Note: This parameter is visible only when it is activated by the optional FlashDrop device. FlashDrop is designed for
fast copying of parameters to unpowered drives. It allows easy customization of the parameter list, e.g. selected
parameters can be hidden. For more information, see MFDT-01 FlashDrop Users Manual (3AFE68591074
[English]).
FlashDrop parameter values are activated by setting parameter 9902 to 31 (LOAD FD SET).
0 = DEFAULT Complete long and short parameter lists are shown.
1 = FLASHDROP FlashDrop parameter list is shown. Does not include short parameter list. Parameters that are
hidden by the FlashDrop device are not visible.
1612 FAN CONTROL
Selects drive cooling fan control. Can be used to mitigate DC voltage fluctuations.
0 = AUTO Fan is controlled automatically (default).
1 = ON Fan is always forced on.
1613 FAULT RESET
Allows to reset faults with a parameter. Can be used to reset faults from remote monitoring systems that have access
to drive parameters.
0 = DEFAULT Fault is not reset (default)
1 = RESET NOW Resets fault.

Parameters

ACS550-01/U1 Users Manual

133

Group 20: LIMITS


This group defines minimum and maximum limits to follow in driving the motor
speed, frequency, current, torque, etc.
Code Description
2001 MINIMUM SPEED
Defines the minimum speed (rpm) allowed.
A positive (or zero) minimum speed value defines two ranges,
one positive and one negative.
A negative minimum speed value defines one speed range.
See the figure.

Speed
P 2002

2001 value is < 0

Speed range allowed

Time

P 2001
2002 MAXIMUM SPEED
Defines the maximum speed (rpm) allowed.

Speed

2001 value is > 0

P 2002
Speed range allowed
P 2001
0
-(P 2001)

Time
Speed range allowed

-(P 2002)
2003 MAX CURRENT
Defines the maximum output current (A) supplied by the drive to the motor.
2005 OVERVOLT CTRL
Sets the DC overvoltage controller on or off.
Fast braking of a high inertia load causes the DC bus voltage to rise to the overvoltage control limit. To prevent the
DC voltage from exceeding the trip limit, the overvoltage controller automatically decreases the braking torque by
increasing output frequency.
0 = DISABLE Disables controller.
1 = ENABLE Enables controller
Note: If a braking chopper or a braking resistor is connected to the drive, this parameter value must be set to
0 (DISABLE) to ensure proper operation of the chopper.
2006 UNDERVOLT CTRL
Sets the DC undervoltage controller on or off. When on:
If the DC bus voltage drops due to loss of input power, the undervoltage controller decreases the motor speed in
order to keep the DC bus voltage above the lower limit.
When the motor speed decreases, the inertia of the load causes regeneration back into the drive, keeping the DC
bus charged and preventing an undervoltage trip.
The DC undervoltage controller increases power loss ride-through on systems with a high inertia, such as a
centrifuge or a fan.
0 = DISABLE Disables controller.
1 = ENABLE(TIME) Enables controller with 500 ms time limit for operation.
2 = ENABLE Enables controller without maximum time limit for operation.

Parameters

134

ACS550-01/U1 Users Manual

Code Description
2007 MINIMUM FREQ
Defines the minimum limit for the drive output frequency.
A positive or zero minimum frequency value defines two
ranges, one positive and one negative.
A negative minimum frequency value defines one speed range.
See the figure.
Note: Keep MINIMUM FREQ MAXIMUM FREQ.
2008 MAXIMUM FREQ
Defines the maximum limit for the drive output frequency.

Freq
P 2008

2007 value is < 0

Frequency range allowed

Time

P 2007
2007 value is > 0

Freq
P 2008

Frequency range allowed


P 2007
0
-(P 2007)

Time
Frequency range allowed

-(P 2008)
2013 MIN TORQUE SEL
Defines control of the selection between two minimum torque limits (2015 MIN TORQUE 1 and 2016 MIN TORQUE 2).
0 = MIN TORQUE 1 Selects 2015 MIN TORQUE 1 as the minimum limit used.
1 = DI1 Defines digital input DI1 as the control for selecting the minimum limit used.
Activating the digital input selects MIN TORQUE 2 value.
De-activating the digital input selects MIN TORQUE 1 value.
26 = DI2DI6 Defines digital input DI2DI6 as the control for selecting the minimum limit used.
See DI1 above.
7 = COMM Defines bit 15 of the Command Word 1 as the control for selecting the minimum limit used.
The Command Word is supplied through fieldbus communication.
The Command Word is parameter 0301.
-1 = DI1(INV) Defines an inverted digital input DI1 as the control for selecting the minimum limit used.
Activating the digital input selects MIN TORQUE 1 value.
De-activating the digital input selects MIN TORQUE 2 value.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the control for selecting the minimum limit
used.
See DI1(INV) above.
2014 MAX TORQUE SEL
Defines control of the selection between two maximum torque limits (2017 MAX TORQUE 1 and 2018 MAX TORQUE 2).
0 = MAX TORQUE 1 Selects 2017 MAX TORQUE 1 as the maximum limit used.
1 = DI1 Defines digital input DI1 as the control for selecting the maximum limit used.
Activating the digital input selects MAX TORQUE 2 value.
De-activating the digital input selects MAX TORQUE 1 value.
26 = DI2DI6 Defines digital input DI2DI6 as the control for selecting the maximum limit used.
See DI1 above.
7 = COMM Defines bit 15 of the Command Word 1 as the control for selecting the maximum limit used.
The Command Word is supplied through fieldbus communication.
The Command Word is parameter 0301.
-1 = DI1(INV) Defines an inverted digital input di1 as the control for selecting the maximum limit used.
Activating the digital input selects MAX TORQUE 1 value.
De-activating the digital input selects MAX TORQUE 2 value.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the control for selecting the maximum limit
used.
See DI1(INV) above.
2015 MIN TORQUE 1
Sets the first minimum limit for torque (%). Value is a percent of the motor nominal torque.
2016 MIN TORQUE 2
Sets the second minimum limit for torque (%). Value is a percent of the motor nominal torque.

Parameters

ACS550-01/U1 Users Manual

135

Code Description
2017 MAX TORQUE 1
Sets the first maximum limit for torque (%). Value is a percent of the motor nominal torque.
2018 MAX TORQUE 2
Sets the second maximum limit for torque (%). Value is a percent of the motor nominal torque.

Parameters

136

ACS550-01/U1 Users Manual

Group 21: START/STOP


This group defines how the motor starts and stops. The ACS550 supports several
start and stop modes.
Code Description
2101 START FUNCTION
Selects the motor start method. The valid options depend on the value of parameter 9904 MOTOR CTRL MODE.
1 = AUTO Selects the automatic start mode.
Vector control modes: Optimal start in most cases. The drive automatically selects the correct output frequency to
start a rotating motor.
SCALAR:FREQ mode: Immediate start from zero frequency. Identical to selection 8 = RAMP.
2 = DC MAGN Selects the DC Magnetizing start mode.
Note: The DC Magnetizing start mode cannot start a rotating motor.
Note: The drive starts when the set pre-magnetizing time (parameter 2103 DC MAGN TIME) has passed, even if motor
magnetization is not complete.
Vector control modes: Magnetizes the motor within the time determined by the parameter 2103 DC MAGN TIME
using DC current. The normal control is released exactly after the magnetizing time. This selection guarantees
the highest possible break-away torque.
SCALAR:FREQ mode: Magnetizes the motor within the time determined by the parameter 2103 DC MAGN TIME using
DC current. The normal control is released exactly after the magnetizing time.
3 = SCALAR FLYST Selects the flying start mode.
Vector control modes: Not applicable.
SCALAR:FREQ mode: The drive automatically selects the correct output frequency to start a rotating motor useful
if the motor is already rotating and if the drive will start smoothly at the current frequency.
Cannot be used in multimotor systems.
4 = TORQ BOOST Selects the automatic torque boost mode (SCALAR:FREQ mode only).
May be necessary in drives with high starting torque.
Torque boost is only applied at start, ending when output frequency exceeds 20 Hz or when output frequency is
equal to reference.
In the beginning the motor magnetizes within the time determined by the parameter 2103 DC MAGN TIME using DC
current.
See parameter 2110 TORQ BOOST CURR.
5 = FLY + BOOST Selects both the flying start and the torque boost mode (SCALAR:FREQ mode only).
Flying start routine is performed first and the motor is magnetized. If the speed is found to be zero, the torque
boost is done.
8 = RAMP Immediate start from zero frequency.
2102 STOP FUNCTION
Selects the motor stop method.
1 = COAST Selects cutting off the motor power as the stop method. The motor coasts to stop.
2 = RAMP Selects using a deceleration ramp.
Deceleration ramp is defined by 2203 DECELER TIME 1 or 2206 DECELER TIME 2 (whichever is active).
2103 DC MAGN TIME
Defines the pre-magnetizing time for the DC Magnetizing start mode.
Use parameter 2101 to select the start mode.
After the start command, the drive pre-magnetizes the motor for the time defined here and then starts the motor.
Set the pre-magnetizing time just long enough to allow full motor magnetization. Too long a time heats the motor
excessively.
2104 DC HOLD CTL
Motor
speed
Selects whether DC current is used for braking or DC Hold.
0 = NOT SEL Disables the DC current operation.
1 = DC HOLD Enables the DC Hold function. See the diagram.
Requires parameter 9904 MOTOR CTRL MODE = 1 (VECTOR:SPEED)
Stops generating sinusoidal current and injects DC into the motor when
both the reference and the motor speed drop below the value of parameter
Ref
2105.
When the reference rises above the level of parameter 2105 the drive
DC hold
resumes normal operation.
speed
2 = DC BRAKING Enables the DC Injection Braking after modulation has
stopped.
If parameter 2102 STOP FUNCTION is 1 (COAST), braking is applied after start is removed.
If parameter 2102 STOP FUNCTION is 2 (RAMP), braking is applied after ramp.

Parameters

DC hold
T

ACS550-01/U1 Users Manual

137

Code Description
2105 DC HOLD SPEED
Sets the speed for DC Hold. Requires that parameter 2104 DC HOLD CTL = 1 (DC HOLD).
2106 DC CURR REF
Defines the DC current control reference as a percentage of parameter 9906 MOTOR NOM CURR.
2107 DC BRAKE TIME
Defines the DC brake time after modulation has stopped, if parameter 2104 is 2 (DC BRAKING).
2108 START INHIBIT
Sets the Start inhibit function on or off. If the drive is not actively started and running, the Start inhibit function ignores
a pending start command in any of the following situations and a new start command is required:
A fault is reset.
Run Enable (parameter 1601) activates while start command is active.
Mode changes from local to remote.
Control switches from EXT1 to EXT2.
Control switches from EXT2 to EXT1.
0 = OFF Disables the Start inhibit function.
1 = ON Enables the Start inhibit function.
2109 EMERG STOP SEL
Defines control of the Emergency stop command. When activated:
Emergency stop decelerates the motor using the emergency stop ramp (parameter 2208 EMERG DEC TIME).
Requires an external stop command and removal of the emergency stop command before drive can restart.
0 = NOT SEL Disables the Emergency stop function through digital inputs.
1 = DI1 Defines digital input DI1 as the control for Emergency stop command.
Activating the digital input issues an Emergency stop command.
De-activating the digital input removes the Emergency stop command.
26 = DI2DI6 Defines digital input DI2DI6 as the control for Emergency stop command.
See DI1 above.
-1 = DI1(INV) Defines an inverted digital input DI1 as the control for Emergency stop command.
De-activating the digital input issues an Emergency stop command.
Activating the digital input removes the Emergency stop command.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the control for Emergency stop command.
See DI1(INV) above.
2110 TORQ BOOST CURR
Sets the maximum supplied current during torque boost.
See parameter 2101 START FUNCTION.

Parameters

138

ACS550-01/U1 Users Manual

Code Description
2112 ZERO SPEED DELAY
Defines the delay for the Zero Speed Delay function. If parameter value is set to zero, the Zero Speed Delay function
is disabled.
The function is useful in applications where a smooth and quick restarting is essential. During the delay the drive
knows accurately the rotor position.
No Zero Speed Delay
With Zero Speed Delay
Speed

Speed
Speed controller switched off:
Motor coasts to stop.

Zero Speed

Speed controller remains live.


Motor is decelerated to true 0 speed.

Zero Speed

t
Delay
Zero speed delay can be used e.g. with jogging function or mechanical brake.
No Zero Speed Delay
The drive receives a stop command and decelerates along a ramp. When the motor actual speed falls below an
internal limit (called Zero Speed), the speed controller is switched off. The drive modulation is stopped and the motor
coasts to standstill.
With Zero Speed Delay
The drive receives a stop command and decelerates along a ramp. When the motor actual speed falls below an
internal limit (called Zero Speed), the zero speed delay function activates. During the delay the functions keeps the
speed controller live: The drive modulates, motor is magnetized and drive is ready for a quick restart.
Note: Parameter 2102 STOP FUNCTION must be 2 = RAMP for zero speed delay to operate.
0.0 = NOT SEL Disables the Zero Speed Delay function.
2113 START DELAY
Defines the Start delay. After the conditions for start have been fulfilled, the drive waits until the delay has elapsed
and then starts the motor. Start delay can be used with all start modes.
If START DELAY = zero, the delay is disabled.
During the Start delay, alarm 2028 START DELAY is shown.

Parameters

ACS550-01/U1 Users Manual

139

Group 22: ACCEL/DECEL


This group defines ramps that control the rate of acceleration and deceleration. You
define these ramps as a pair, one for acceleration and one for deceleration. You can
define two pairs of ramps and use a digital input to select one or the other pair.
Code Description
2201 ACC/DEC 1/2 SEL
Defines control for selection of acceleration/deceleration ramps.
Ramps are defined in pairs, one each for acceleration and deceleration.
See below for the ramp definition parameters.
0 = NOT SEL Disables selection, the first ramp pair is used.
1 = DI1 Defines digital input DI1 as the control for ramp pair selection.
Activating the digital input selects ramp pair 2.
De-activating the digital input selects ramp pair 1.
26 = DI2DI6 Defines digital input DI2DI6 as the control for ramp pair selection.
See DI1 above.
7 = COMM Defines bit 10 of the Command Word 1 as the control for ramp pair selection.
The Command Word is supplied through fieldbus communication.
The Command Word is parameter 0301.
-1 = DI1(INV) Defines an inverted digital input DI1 as the control for ramp pair selection.
De-activating the digital input selects ramp pair 2
Activating the digital input selects ramp pair 1.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the control for ramp pair selection.
See DI1(INV) above.
2202 ACCELER TIME 1
Sets the acceleration time for zero to maximum frequency for ramp pair 1. See A in
the figure.
Actual acceleration time also depends on 2204 RAMP SHAPE 1.
See 2008 MAXIMUM FREQ.
2203 DECELER TIME 1
Sets the deceleration time for maximum frequency to zero for ramp pair 1.
Actual deceleration time also depends on 2204 RAMP SHAPE 1.
See 2008 MAXIMUM FREQ.
2204 RAMP SHAPE 1
Selects the shape of the acceleration/deceleration ramp for ramp pair 1. See B in
the figure.
Shape is defined as a ramp, unless additional time is specified here to reach the
maximum frequency. A longer time provides a softer transition at each end of the
slope. The shape becomes an s-curve.
Rule of thumb: 1/5 is a suitable relation between the ramp shape time and the
acceleration ramp time.
0.0 = LINEAR Specifies linear acceleration/deceleration ramps for ramp pair 1.
0.11000.0 = S-CURVE Specifies s-curve acceleration/deceleration ramps for
ramp pair 1.

MAX
FREQ

Linear

B (=0)
T
MAX
FREQ

S-curve

A
A = 2202 ACCELER TIME 1
B = 2204 RAMP SHAPE 1

2205 ACCELER TIME 2


Sets the acceleration time for zero to maximum frequency for ramp pair 2.
See 2202 ACCELER TIME 1.
Used also as jogging acceleration time. See 1004 JOGGING SEL.
2206 DECELER TIME 2
Sets the deceleration time for maximum frequency to zero for ramp pair 2.
See 2203 DECELER TIME 1.
Used also as jogging deceleration time. See 1004 JOGGING SEL.
2207 RAMP SHAPE 2
Selects the shape of the acceleration/deceleration ramp for ramp pair 2.
See 2204 RAMP SHAPE 1.

Parameters

140

ACS550-01/U1 Users Manual

Code Description
2208 EMERG DEC TIME
Sets the deceleration time for maximum frequency to zero for an emergency.
See parameter 2109 EMERG STOP SEL.
Ramp is linear.
2209 RAMP INPUT 0
Defines control for forcing the speed to 0 with the currently used deceleration ramp (see parameters 2203 DECELER
TIME 1 and 2206 DECELER TIME 2).
0 = NOT SEL Not selected.
1 = DI1 Defines digital input DI1 as the control for forcing the speed to 0.
Activating the digital input forces the speed to zero, after which the speed will stay at 0.
De-activating the digital input: speed control resumes normal operation.
26 = DI2DI6 Defines digital input DI2DI6 as the control for forcing the speed to 0.
See DI1 above.
7 = COMM Defines bit 13 of the Command Word 1 as the control for forcing the speed to 0.
The Command Word is supplied through fieldbus communication.
The Command Word is parameter 0301.
-1 = DI1(INV) Defines inverted digital input DI1 as the control for forcing the speed to 0.
De-activating the digital input forces the speed to 0.
Activating the digital input: speed control resumes normal operation.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the control for forcing the speed to 0.
See DI1(INV) above.

Parameters

ACS550-01/U1 Users Manual

141

Group 23: SPEED CONTROL


This group defines variables used for speed control operation.
Code Description
2301 PROP GAIN
Sets the relative gain for the speed controller.
Larger values may cause speed oscillation.
The figure shows the speed controller output
after an error step (error remains constant).
Note: You can use parameter 2305 AUTOTUNE
RUN to automatically set the proportional gain.

2302 INTEGRATION TIME


Sets the integration time for the speed
controller.
The integration time defines the rate at which
the controller output changes for a constant
error value.
Shorter integration times correct continuous
errors faster.
Control becomes unstable if the integration
time is too short.
The figure shows the speed controller output
after an error step (error remains constant).
Note: You can use parameter 2305 AUTOTUNE
RUN to automatically set the integration time.

Controller
output =
Kp e

Gain = Kp = 1
TI = Integration time = 0
TD= Derivation time = 0
Error value
Controller output
e = Error value
t
Controller output
Gain = Kp = 1
TI = Integration time > 0
TD= Derivation time = 0

Kp e

e = Error value

Kp e

t
TI

2303 DERIVATION TIME


Sets the derivation time for the speed controller.
Derivative action makes the control more responsive to error value changes.
The longer the derivation time, the more the speed controller output is boosted during the change.
If the derivation time is set to zero, the controller works as a PI controller, otherwise as a PID controller.
The figure below shows the speed controller output after an error step when the error remains constant.
%

Kp TD

Controller output

e
Ts

Kp e
Error value

Gain = Kp = 1
TI = Integration time > 0
TD= Derivation time > 0
Ts= Sample time period = 2 ms
e = Error value change between two samples

e = Error value

Kp e

t
TI

Parameters

142

ACS550-01/U1 Users Manual

Code Description
2304 ACC COMPENSATION
Sets the derivation time for acceleration compensation.
Adding a derivative of the reference to the output of the speed controller compensates for inertia during
acceleration.
2303 DERIVATION TIME describes the principle of derivative action.
Rule of thumb: Set this parameter between 50 and 100% of the sum of the mechanical time constants for the motor
and the driven machine.
The figure shows the speed responses when a high inertia load is accelerated along a ramp.
* No acceleration compensation

Acceleration compensation

Speed reference
Actual speed
t

*Note: You can use parameter 2305 AUTOTUNE RUN to automatically set acceleration compensation.
2305 AUTOTUNE RUN
Starts automatic tuning of the speed controller.
0 = OFF Disables the Autotune creation process. (Does not disable the operation of Autotune settings.)
1 = ON Activates speed controller autotuning. Automatically reverts to OFF.
Procedure:
Note: The motor load must be connected.
Run the motor at a constant speed of 20 to 40% of the rated speed.
Change the autotuning parameter 2305 to ON.
The drive:
Accelerates the motor.
Calculates values for proportional gain, integration time and acceleration compensation.
Changes parameters 2301, 2302 and 2304 to these values.
Resets 2305 to OFF.

Parameters

ACS550-01/U1 Users Manual

143

Group 24: TORQUE CONTROL


This group defines variables used for torque control operation.
Code Description
2401 TORQ RAMP UP
Defines the torque reference ramp up time The minimum time for the reference to increase from zero to the
nominal motor torque.
2402 TORQ RAMP DOWN
Defines the torque reference ramp down time The minimum time for the reference to decrease from the nominal
motor torque to zero.

Parameters

144

ACS550-01/U1 Users Manual

Group 25: CRITICAL SPEEDS


This group defines up to three critical speeds or ranges of speeds that are to be
avoided due, for example, to mechanical resonance problems at certain speeds.
Code Description
2501 CRIT SPEED SEL
Sets the critical speeds function on or off. The critical speed
function avoids specific speed ranges.
0 = OFF Disables the critical speeds function.
1 = ON Enables the critical speeds function.
Example: To avoid speeds at which a fan system vibrates badly:
Determine problem speed ranges. Assume they are found to
be: 1823 Hz and 4652 Hz.
Set 2501 CRIT SPEED SEL = 1.
Set 2502 CRIT SPEED 1 LO = 18 Hz.
Set 2503 CRIT SPEED 1 HI = 23 Hz.
Set 2504 CRIT SPEED 2 LO = 46 Hz.
Set 2505 CRIT SPEED 2 HI = 52 Hz.

foutput
52
46
23
18

f1L f1H
18 23

2502 CRIT SPEED 1 LO


Sets the minimum limit for critical speed range 1.
The value must be less than or equal to 2503 CRIT SPEED 1 HI.
Units are rpm, unless 9904 MOTOR CTRL MODE = 3 (SCALAR:FREQ), then units are Hz.
2503 CRIT SPEED 1 HI
Sets the maximum limit for critical speed range 1.
The value must be greater than or equal to 2502 CRIT SPEED 1 LO.
Units are rpm, unless 9904 MOTOR CTRL MODE = 3 (SCALAR:FREQ), then units are Hz.
2504 CRIT SPEED 2 LO
Sets the minimum limit for critical speed range 2.
See parameter 2502.
2505 CRIT SPEED 2 HI
Sets the maximum limit for critical speed range 2.
See parameter 2503.
2506 CRIT SPEED 3 LO
Sets the minimum limit for critical speed range 3.
See parameter 2502.
2507 CRIT SPEED 3 HI
Sets the maximum limit for critical speed range 3.
See parameter 2503.

Parameters

f2L f2H
46 52

fREF (Hz)

ACS550-01/U1 Users Manual

145

Group 26: MOTOR CONTROL


This group defines variables used for motor control.
Code Description
2601 FLUX OPT ENABLE
Changes the magnitude of the flux depending on the actual load. Flux Optimization can reduce the total energy
consumption and noise, and it should be enabled for drives that usually operate below nominal load.
0 = OFF Disables the feature.
1 = ON Enables the feature.
2602 FLUX BRAKING
Provides faster deceleration by raising the level of
magnetization in the motor when needed, instead of
limiting the deceleration ramp. By increasing the flux in
the motor, the energy of the mechanical system is
changed to thermal energy in the motor.
Requires parameter 9904 MOTOR CTRL MODE =
1 (VECTOR:sPEED) OR 2 (VECTOR:TORQ).
0 = OFF Disables the feature.
1 = ON Enables the feature.

Braking
torque (%)
120%

Rated motor power


1 2.2 kW
Without flux braking
2 15 kW
3 37 kW
4 75 kW
1
5 250 kW
3
4
5

80
40
2
0

10

120%

40

50
f (Hz)

30

40

50
f (Hz)

With flux braking

80

40
0

30

20

2
5
5

3
10

20

IR compensation
2603 IR COMP VOLT
When enabled, IR compensation provides an extra
Sets the IR compensation voltage used for 0 Hz.
voltage boost to the motor at low speeds. Use IR
Requires parameter 9904 MOTOR CTRL MODE =
compensation, for example, in applications that require a
3 (SCALAR:FREQ).
high breakaway torque.
Keep IR compensation as low as possible to prevent
overheating.
Motor
Typical IR compensation values are:
voltage
380480 V drives
3
PN (kW)
IR comp (V)
18

A
7.5
15

15
12

37
8

132
3

A = IR compensated
B = No compensation

P 2603
2604 IR COMP FREQ
Sets the frequency at which IR compensation is 0 V (in
% of motor frequency).

f (Hz)

P 2604

2605 U/F RATIO


Selects the form for the U/f (voltage to frequency) ratio below field weakening point.
1 = LINEAR Preferred for constant torque applications.
2 = SQUARED Preferred for centrifugal pump and fan applications. (SQUARED is more silent for most operating
frequencies.)

Parameters

146

ACS550-01/U1 Users Manual

Code Description
2606 SWITCHING FREQ
Sets the switching frequency for the drive. Also see parameter 2607 SWITCH FREQ CTRL and section Switching
frequency derating on page 280.
Higher switching frequencies mean less noise.
In multimotor systems, do not change the switching frequency from the default value.
12 kHz switching frequency is available in scalar control mode, that is when parameter 9904 MOTOR CTRL MODE = 3
(SCALAR:FREQ).
See the availability of switching frequencies for different drive types in the table below.
1, 2, 4 and 8 kHz
208240 V All types
380480 V All types
500600 V All types

12 kHz
Frame sizes R1R4 in scalar control mode
Frame sizes R1R4 (except ACS550-01-097A-4) in scalar control mode
Frame sizes R2R4 in scalar control mode

2607 SWITCH FREQ CTRL


The switching frequency may be reduced if the ACS550
internal temperature rises above a limit. See the figure.
This function allows the highest possible switching
frequency to be used based on operating conditions.
Higher switching frequency results in lower acoustic
noise.
In multimotor systems, do no disable (set OFF) the
function.
0 = OFF The function is disabled.
1 = ON The switching frequency is limited according to
the figure.

fsw
limit

R1R4 drives, see par 2606


R5R6 drives, see par 2606

12 kHz
8 kHz

Drive
temperature

4 kHz
80 C

90 C

100 C

2608 SLIP COMP RATIO


Sets gain for slip compensation (in %).
A squirrel-cage motor slips under load. Increasing the frequency as the motor torque increases compensates for
the slip.
Requires parameter 9904 MOTOR CTRL MODE = 3 (SCALAR:FREQ).
0 No slip compensation.
1200 Increasing slip compensation. 100% means full slip compensation.
2609 NOISE SMOOTHING
This parameter introduces a random component to the switching frequency. Noise smoothing distributes the acoustic
motor noise over a range of frequencies instead of a single tonal frequency resulting in lower peak noise intensity.
The random component has an average of 0 Hz. It is added to the switching frequency set by parameter 2606
SWITCHING FREQ. This parameter has no effect if parameter 2606 = 12 kHz.
0 = DISABLE
1 = ENABLE.
2619 DC STABILIZER
Enables or disables the DC voltage stabilizer. The DC stabilizer is used in scalar control mode to prevent possible
voltage oscillations in the drive DC bus caused by motor load or weak supply network. In case of voltage variation the
drive tunes the frequency reference to stabilize the DC bus voltage and therefore the load torque oscillation.
0 = DISABLE Disables DC stabilizer.
1 = ENABLE Enables DC stabilizer.
2625 OVERMODULATION
Enables or disables overmodulation. Disabling overmodulation can help in some applications in field weakening
area.
0 = DISABLE Disables overmodulation.
1 = ENABLE Enables overmodulation.

Parameters

ACS550-01/U1 Users Manual

147

Group 29: MAINTENANCE TRIG


This group contains usage levels and trigger points. When usage reaches the set
trigger point, a notice displayed on the control panel signals that maintenance is due.
Code Description
2901 COOLING FAN TRIG
Sets the trigger point for the drives cooling fan counter.
Value is compared to parameter 2902 value.
0.0 Disables the trigger.
2902 COOLING FAN ACT
Defines the actual value of the drives cooling fan counter.
When parameter 2901 has been set to a non-zero value, the counter starts.
When the actual value of the counter exceeds the value defined by parameter 2901, a maintenance notice is
displayed on the panel.
0.0 Resets the parameter.
2903 REVOLUTION TRIG
Sets the trigger point for the motors accumulated revolutions counter.
Value is compared to parameter 2904 value.
0 Disables the trigger.
2904 REVOLUTION ACT
Defines the actual value of the motors accumulated revolutions counter.
When parameter 2903 has been set to a non-zero value, the counter starts.
When the actual value of the counter exceeds the value defined by parameter 2903, a maintenance notice is
displayed on the panel.
0 Resets the parameter.
2905 RUN TIME TRIG
Sets the trigger point for the drives run time counter.
Value is compared to parameter 2906 value.
0.0 Disables the trigger.
2906 RUN TIME ACT
Defines the actual value of the drives run time counter.
When parameter 2905 has been set to a non-zero value, the counter starts.
When the actual value of the counter exceeds the value defined by parameter 2905, a maintenance notice is
displayed on the panel.
0.0 Resets the parameter.
2907 USER MWh TRIG
Sets the trigger point for the drives accumulated power consumption (in megawatt hours) counter.
Value is compared to parameter 2908 value.
0.0 Disables the trigger.
2908 USER MWh ACT
Defines the actual value of the drives accumulated power consumption (in megawatt hours) counter.
When parameter 2907 has been set to a non-zero value, the counter starts.
When the actual value of the counter exceeds the value defined by parameter 2907, a maintenance notice is
displayed on the panel.
0.0 Resets the parameter.

Parameters

148

ACS550-01/U1 Users Manual

Group 30: FAULT FUNCTIONS


This group defines situations that the drive should recognize as potential faults and
defines how the drive should respond if the fault is detected.
Code Description
3001 AI<MIN FUNCTION
Defines the drive response if the analog input (AI) signal drops below the fault limits and AI is used
as the active reference source (Group 11: REFERENCE SELECT)
as the Process or External PID controllers' feedback or setpoint source (Group 40: PROCESS PID SET 1, Group
41: PROCESS PID SET 2 or Group 42: EXT / TRIM PID) and the corresponding PID controller is active.
3021 AI1 FAULT LIMIT and 3022 AI2 FAULT LIMIT set the fault limits.
0 = NOT SEL No response.
1 = FAULT Displays a fault (7, AI1 LOSS or 8, AI2 LOSS) and the drive coasts to stop.
2 = CONST SP 7 Displays an alarm (2006, AI1 LOSS or 2007, AI2 LOSS) and sets speed using 1208 CONST SPEED 7.
3 = LAST SPEED Displays an alarm (2006, AI1 LOSS or 2007, AI2 LOSS) and sets speed using the last operating level.
This value is the average speed over the last 10 seconds.
WARNING! If you select CONST SP 7 or LAST SPEED, make sure that continued operation is safe when the
analog input signal is lost.
3002 PANEL COMM ERR
Defines the drive response to a control panel communication error.
1 = FAULT Displays a fault (10, PANEL LOSS) and the drive coasts to stop.
2 = CONST SP 7 Displays an alarm (2008, PANEL LOSS) and sets speed using 1208 CONST SPEED 7.
3 = LAST SPEED Displays an alarm (2008, PANEL LOSS) and sets speed using the last operating level. This value is
the average speed over the last 10 seconds.
Note: When either of the two external control locations are active, and start, stop and/or direction are through the
control panel 1001 EXT1 COMMANDS / 1002 EXT2 COMMANDS = 8 (KEYPAD) the drive follows speed/frequency
reference according to the configuration of the external control locations, instead of the value of the last speed or
parameter 1208 CONST SPEED 7.
WARNING! If you select CONST SP 7 or LAST SPEED, make sure that continued operation is safe when the
control panel communication is lost.
3003 EXTERNAL FAULT 1
Defines the External Fault 1 signal input and the drive response to an external fault.
0 = NOT SEL External fault signal is not used.
1 = DI1 Defines digital input DI1 as the external fault input.
Activating the digital input indicates a fault. The drive displays a fault (14, EXT FAULT 1) and the drive coasts to
stop.
26 = DI2DI6 Defines digital input DI2DI6 as the external fault input.
See DI1 above.
-1 = DI1(INV) Defines an inverted digital input DI1 as the external fault input.
De-activating the digital input indicates a fault. The drive displays a fault (14, EXT FAULT 1) and the drive coasts to
stop.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the external fault input.
See DI1(INV) above.
3004 EXTERNAL FAULT 2
Defines the External Fault 2 signal input and the drive response to an external fault.
See parameter 3003 above.
3005 MOT THERM PROT
Defines the drive response to motor overheating.
0 = NOT SEL No response and/or motor thermal protection not set up.
1 = FAULT When the calculated motor temperature exceeds 90 C, displays an alarm (2010, MOTOR TEMP). When
the calculated motor temperature exceeds 110 C, displays a fault (9, MOT OVERTEMP) and the drive coasts to stop.
2 = ALARM When the calculated motor temperature exceeds 90 C, displays an alarm (2010, MOTOR TEMP).

Parameters

ACS550-01/U1 Users Manual

149

Code Description
Motor load
t
Temp. rise
100%
63%
t
}

3006 MOT THERM TIME


Sets the motor thermal time constant for the motor temperature
model.
This is the time required for the motor to reach 63% of the final
temperature with steady load.
For thermal protection according to UL requirements for NEMA
class motors, use the rule of thumb: MOTOR THERM TIME equals
35 times t6, where t6 (in seconds) is specified by the motor
manufacturer as the time that the motor can safely operate at six
times its rated current.
The thermal time for a Class 10 trip curve is 350 s, for a Class
20 trip curve 700 s, and for a Class 30 trip curve 1050 s.

P 3006

3007 MOT LOAD CURVE


Sets the maximum allowable operating load of the motor.
With the default value 100%, motor overload protection is functioning
150
when the constant current exceeds 127% of the parameter 9906
MOTOR NOM CURR value.
The default overloadability is at the same level as what motor
P 3007 100 =
manufacturers typically allow below 30 C (86 F) ambient
127%
temperature and below 1000 m (3300 ft) altitude. When the ambient
temperature exceeds 30 C (86 F) or the installation altitude is over P 3008 50
1000 m (3300 ft), decrease the parameter 3007 value according to
the motor manufacturers recommendation.
Example: If the constant protection level needs to be 115% of
the motor nominal current, set parameter 3007 value to 91%
(= 115/127100%).

Output current relative to


9906 MOTOR NOM CURR

Frequency
P 3009

3008 ZERO SPEED LOAD


Sets the maximum allowable current at zero speed.
Value is relative to 9906 MOTOR NOM CURR.
3009 BREAK POINT FREQ
Sets the break point frequency for the motor load curve.
Example: Thermal protection trip times when parameters 3006 MOT THERM TIME, 3007 MOT LOAD CURVE and 3008
ZERO SPEED LOAD have default values.
IO/IN
A
3.5
3.0

60 s

2.5

90 s

2.0

180 s

1.5

300 s

IO = Output current
IN = Nominal motor current
fO = Output frequency
fBRK = Break point frequency
A = Trip time

600 s

1.0
0.5

fO/fBRK

0
0

0.2

0.4

0.6

0.8

1.0

1.2

Parameters

150

ACS550-01/U1 Users Manual

Code Description
3010 STALL FUNCTION
This parameter defines the operation of the Stall function. This
protection is active if the drive operates in the stall region (see the
figure) for the time defined by 3012 STALL TIME. The User Limit is
defined in Group 20: LIMITS by 2017 MAX TORQUE 1, 2018 MAX TORQUE
2, or the limit on the COMM input.
0 = NOT SEL Stall protection is not used.
1 = FAULT When the drive operates in the stall region for the time set
by 3012 STALL TIME:
The drive coasts to stop.
A fault indication is displayed.
2 = ALARM When the drive operates in the stall region for the time set
by 3012 STALL TIME:
An alarm indication is displayed.
The alarm disappears when the drive is out of the stall region for
half the time set by parameter 3012 STALL TIME.
3011 STALL FREQUENCY
This parameter sets the frequency value for the Stall function. Refer to
the figure.

Torque/
Current
Stall region
95%

User
limit

f
P 3011
Stall frequency

3012 STALL TIME


This parameter sets the time value for the Stall function.
3017 EARTH FAULT
Defines the drive response if the drive detects a ground fault in the motor or motor cables. The drive monitors for
ground faults while the drive is running, and while the drive is not running. See also parameter 3023 WIRING FAULT
and 3028 EARTH FAULT LVL.
Note: Disabling earth fault (ground fault) may void the warranty.
0 = DISABLE No drive response to ground faults.
1 = ENABLE Ground faults display fault 16 (EARTH FAULT), and (if running) the drive coasts to stop.
3018 COMM FAULT FUNC
Defines the drive response if the fieldbus communication is lost.
0 = NOT SEL No response.
1 = FAULT Displays a fault (28, SERIAL 1 ERR) and the drive coasts to stop.
2 = CONST SP 7 Displays an alarm (2005, I/O COMM) and sets speed using 1208 CONST SPEED 7. This alarm speed
remains active until the fieldbus writes a new reference value.
3 = LAST SPEED Displays an alarm (2005, I/O COMM) and sets speed using the last operating level. This value is the
average speed over the last 10 seconds. This alarm speed remains active until the fieldbus writes a new
reference value.
WARNING! If you select CONST SP 7, or LAST SPEED, make sure that continued operation is safe when
fieldbus communication is lost.
3019 COMM FAULT TIME
Sets the communication fault time used with 3018 COMM FAULT FUNC.
Brief interruptions in the fieldbus communication are not treated as faults if they are less than the COMM FAULT TIME
value.
3021 AI1 FAULT LIMIT
Sets a fault level for analog input 1.
See 3001 AI<MIN FUNCTION.
3022 AI2 FAULT LIMIT
Sets a fault level for analog input 2.
See 3001 AI<MIN FUNCTION.

Parameters

ACS550-01/U1 Users Manual

151

Code Description
3023 WIRING FAULT
Defines the drive response to cross wiring faults and to ground faults detected when the drive is NOT running. When
the drive is not running it monitors for:
Improper connections of input power to the drive output (the drive can display fault 35, OUTPUT WIRING if improper
connections are detected).
Ground faults (the drive can display fault 16, EARTH FAULT if a ground fault is detected). Also, see parameter 3017
EARTH FAULT.
Note: Disabling wiring fault (ground fault) may void the warranty.
0 = DISABLE No drive response to either of the above monitoring results.
1 = ENABLE The drive displays faults when this monitoring detects problems.
3024 CB TEMP FAULT
Defines the drive response to control board overheating. Not for drives with an OMIO control board.
0 = DISABLE No response.
1 = ENABLE Displays fault 37 (CB OVERTEMP) and the drive coasts to stop.
3028 EARTH FAULT LVL
Defines detection level for earth fault. See Correcting faults, fault 16, EARTH FAULT.
Note: Parameter 3017 EARTH FAULT has to be enabled.
1 = LOW Low level leakage current, high sensitivity. The drive trips to low ground (earth) leakage current (default in
the USA software version).
2 = MEDIUM Medium sensitivity to ground (earth) fault current (default in the European software version).
3 = HIGH High level leakage current, low sensitivity. The drive trips to higher ground (earth) leakage current.

Parameters

152

ACS550-01/U1 Users Manual

Group 31: AUTOMATIC RESET


This group defines conditions for automatic resets. An automatic reset occurs after a
particular fault is detected. The drive holds for a set delay time, then automatically
restarts. You can limit the number of resets in a specified time period and set up
automatic resets for a variety of faults.
Code Description
3101 NUMBER OF TRIALS
Sets the number of allowed automatic resets within a trial period defined
by 3102 TRIAL TIME.
If the number of automatic resets exceeds this limit (within the trial
time), the drive prevents additional automatic resets and remains
stopped.
Starting then requires a successful reset performed from the control
panel or from a source selected by 1604 FAULT RESET SEL.
3102 TRIAL TIME
Sets the time period used for counting and limiting the number of resets.
See 3101 NUMBER OF TRIALS.

Example: Three faults have occurred in


the trial time. The last is reset only if the
value for 3101 NUMBER OF TRIALS is 3 or
more.
Trial time
X

X X

Time

x = Automatic reset

3103 DELAY TIME


Sets the delay time between a fault detection and attempted drive restart.
If DELAY TIME = zero, the drive resets immediately.
3104 AR OVERCURRENT
Sets the automatic reset for the overcurrent function on or off.
0 = DISABLE Disables automatic reset.
1 = ENABLE Enables automatic reset.
Automatically resets the fault (OVERCURRENT) after the delay set by 3103 DELAY TIME, and the drive resumes
normal operation.
3105 AR OVERVOLTAGE
Sets the automatic reset for the overvoltage function on or off.
0 = DISABLE Disables automatic reset.
1 = ENABLE Enables automatic reset.
Automatically resets the fault (DC OVERVOLT) after the delay set by 3103 DELAY TIME, and the drive resumes
normal operation.
3106 AR UNDERVOLTAGE
Sets the automatic reset for the undervoltage function on or off.
0 = DISABLE Disables automatic reset.
1 = ENABLE Enables automatic reset.
Automatically resets the fault (DC UNDERVOLT) after the delay set by 3103 DELAY TIME, and the drive resumes
normal operation.
3107 AR AI<MIN
Sets the automatic reset for the analog input less than minimum value function on or off.
0 = DISABLE Disables automatic reset.
1 = ENABLE Enables automatic reset.
Automatically resets the fault (AI<MIN) after the delay set by 3103 DELAY TIME, and the drive resumes normal
operation.
WARNING! When the analog input signal is restored, the drive may restart, even after a long stop. Make
sure that automatic, long delayed starts will not cause physical injury and/or damage equipment.
3108 AR EXTERNAL FLT
Sets the automatic reset for external faults function on or off.
0 = DISABLE Disables automatic reset.
1 = ENABLE Enables automatic reset.
Automatically resets the fault (EXT FAULT 1 or EXT FAULT 2) after the delay set by 3103 DELAY TIME, and the drive
resumes normal operation.

Parameters

ACS550-01/U1 Users Manual

153

Group 32: SUPERVISION


This group defines supervision for up to three signals from Group 01: OPERATING
DATA. Supervision monitors a specified parameter and energizes a relay output if
the parameter passes a defined limit. Use Group 14: RELAY OUTPUTS to define the
relay and whether the relay activates when the signal is too low or too high.
Code Description
3201 SUPERV 1 PARAM
Selects the first supervised parameter.
Must be a parameter number from Group 01: OPERATING
DATA.
LO HI
100 = NOT SELECTED No parameter selected.
Note: Case LO HI represents a normal hysteresis.
101178 Selects parameter 01010178.
If the supervised parameter passes a limit, a relay output is
Value of supervised parameter
energized.
The supervision limits are defined in this group.
HI (3203)
The relay outputs are defined in Group 14: RELAY
LO (3202)
OUTPUTS (definition also specifies which supervision limit
t
is monitored).
LO HI
Case A
Operating data supervision using relay outputs, when LOHI.
Energized (1)
Case A = Parameter 1401 RELAY OUTPUT 1 (or 1402 RELAY
t
OUTPUT 2, etc.) value is SUPRV1 OVER or SUPRV2 OVER. Use
0
for monitoring when/if the supervised signal exceeds a
Case B
given limit. The relay remains active until the supervised
value drops below the low limit.
Energized (1)
t
Case B = Parameter 1401 RELAY OUTPUT 1 (or 1402 RELAY
0
OUTPUT 2, etc.) value is SUPRV1 UNDER or SUPRV2 UNDER.
Use for monitoring when/if the supervised signal falls
LO > HI
below a given limit. The relay remains active until the
Note: Case LO>HI represents a special hysteresis with
supervised value rises above the high limit.
two separate supervision limits.
LO HI
Operating data supervision using relay outputs, when LO>HI. Value of supervised parameter
Active limit
The lowest limit (HI 3203) is active initially and remains active
until the supervised parameter goes above the highest limit
LO (3202)
(LO 3202), making that limit the active limit. That limit remains
HI (3203)
active until the supervised parameter goes below the lowest
t
limit (HI 3203), making that limit active.
Case A = Parameter 1401 RELAY OUTPUT 1 (or 1402 RELAY
Case A
OUTPUT 2, etc.) value is SUPRV1 OVER or SUPRV2 OVER.
Initially the relay is de-energized. It is energized whenever Energized (1)
t
the supervised parameter goes above the active limit.
0
Case B = Parameter 1401 RELAY OUTPUT 1 (or 1402 RELAY
OUTPUT 2, etc.) value is SUPRV1 UNDER or SUPRV2 UNDER.
Case B
Initially the relay is energized. It is de-energized whenever
Energized (1)
the supervised parameter goes below the active limit.
t
0
3202 SUPERV 1 LIM LO
Sets the low limit for the first supervised parameter. See
3201 SUPERV 1 PARAM above.
3203 SUPERV 1 LIM HI
Sets the high limit for the first supervised parameter. See
3201 SUPERV 1 PARAM above.
3204 SUPERV 2 PARAM
Selects the second supervised parameter. See 3201 SUPERV 1 PARAM above.
3205 SUPERV 2 LIM LO
Sets the low limit for the second supervised parameter. See 3204 SUPERV 2 PARAM above.
3206 SUPERV 2 LIM HI
Sets the high limit for the second supervised parameter. See 3204 SUPERV 2 PARAM above.

Parameters

154

ACS550-01/U1 Users Manual

Code Description
3207 SUPERV 3 PARAM
Selects the third supervised parameter. See 3201 SUPERV 1 PARAM above.
3208 SUPERV 3 LIM LO
Sets the low limit for the third supervised parameter. See 3207 SUPERV 3 PARAM above.
3209 SUPERV 3 LIM HI
Sets the high limit for the third supervised parameter. See 3207 SUPERV 3 PARAM above.

Parameters

ACS550-01/U1 Users Manual

155

Group 33: INFORMATION


This group provides access to information about the drives current programs:
versions and test date.
Code Description
3301 FIRMWARE
Contains the version of the drives firmware.
3302 LOADING PACKAGE
Contains the version of the loading package.
3303 TEST DATE
Contains the test date (yy.ww).
3304 DRIVE RATING
Indicates the drives current and voltage rating. The format is XXXY, where:
XXX = The nominal current rating of the drive in amperes. If present, an A indicates a decimal point in the rating
for the current. For example XXX = 8A8 indicates a nominal current rating of 8.8 A.
Y = The voltage rating of the drive, where Y = :
2 indicates a 208240 V rating.
4 indicates a 380480 V rating.
6 indicates a 500600 V rating.
3305 PARAMETER TABLE
Contains the version of the parameter table used in the drive.

Parameters

156

ACS550-01/U1 Users Manual

Group 34: PANEL DISPLAY


This group defines the content for control panel display (middle area), when the
control panel is in the Output mode.
Code Description
3401 SIGNAL1 PARAM
P 3404 P 3405
Selects the first parameter (by number) displayed on the control
LOC
49.1Hz
panel.
Definitions in this group define display content when the control
P 3401 (=137)
panel is in the control mode.
P 3408 (=138)
Any parameter number in Group 01: OPERATING DATA can be
P 3415 (=139)
selected.
00:00
MENU
DIR
Using the following parameters, the display value can be scaled,
converted to convenient units and/or displayed as a bar graph.
LOC
5.0Hz
The figure identifies selections made by parameters in this group.
HZ
50%
If just one or two parameters are selected for display, that is just
one or two of the values of parameters 3401 SIGNAL1 PARAM, 3408
P 3404
SIGNAL2 PARAM and 3415 SIGNAL3 PARAM are other than 100 (NOT
SELECTED), the number and name of each displayed parameter are
00:00
MENU
DIR
shown in addition to the value.
100 = NOT SELECTED First parameter not displayed.
101178 Displays parameter 01010178. If parameter does not
exist, the display shows n.a..

49.1 Hz
0.5 A
10.7 %

0.4 A
24.4 %

3402 SIGNAL1 MIN


Defines the minimum expected value for the first display parameter.
Use parameters 3402, 3403, 3406 and 3407, for example to convert
a Group 01: OPERATING DATA parameter, such as 0102 SPEED (in
rpm) to the speed of a conveyor driven by the motor (in ft/min). For
such a conversion, the source values in the figure are the min. and
max. motor speed, and the display values are the corresponding min.
and max. conveyor speed. Use parameter 3405 to select the proper
units for the display.
Note: Selecting units does not convert values. Parameter is not
effective if parameter 3404 OUTPUT1 DSP FORM = 9 (DIRECT).

Display
value
P 3407

P 3406
P3402

3403 SIGNAL1 MAX


Defines the maximum expected value for the first display parameter.
Note: Parameter is not effective if parameter 3404 OUTPUT1 DSP
FORM = 9 (DIRECT).
3404 OUTPUT1 DSP FORM
Defines the decimal point location for the first display parameter.
07 Defines the decimal point location.
Enter the number of digits desired to the right of the decimal
point.
See the table for an example using pi (3.14159).
8 = BAR METER Specifies a bar meter display.
9 = DIRECT Decimal point location and units of measure are
identical to the source signal. See Group 01: OPERATING DATA
parameter listing in section Complete parameter list on page 91
for resolution (which indicates the decimal point location) and the
units of measure.

Parameters

3404 value
0
1
2
3
4
5
6
7
8
9

P 3403
Source value

Display
Range
-32768+32767
+3
(Signed)
+ 3.1
+ 3.14
+ 3.142
3
065535
(Unsigned)
3.1
3.14
3.142
Bar meter displayed.
Decimal point location and
units as for the source
signal.

ACS550-01/U1 Users Manual

157

Code Description
3405 OUTPUT1 UNIT
Selects the units used with the first display parameter.
Note: Parameter is not effective if parameter 3404 OUTPUT1 DSP FORM = 9 (DIRECT).
0 = NO UNIT
1=A
2=V
3 = Hz
4=%
5=s
6=h
7 = rpm
8 = kh

9 = C
10 = lb ft
11 = mA
12 = mV
13 = kW
14 = W
15 = kWh
16 = F
17 = hp

18 = MWh
19 = m/s
20 = m 3/h
21 = dm 3/s
22 = bar
23 = kPa
24 = GPM
25 = PSI
26 = CFM

27
28
29
30
31
32
33
34
35

= ft
= MGD
= inHg
= FPM
= kb/s
= kHz
= ohm
= ppm
= pps

36 = l/s
37 = l/min
38 = l/h
39 = m3/s
40 = m3/m
41 = kg/s
42 = kg/m
43 = kg/h
44 = mbar

45
46
47
48
49
50
51
52
53

= Pa
= GPS
= gal/s
= gal/m
= gal/h
= ft3/s
= ft3/m
= ft3/h
= lb/s

The following units are useful for the bar display.


117 = %ref
119 = %dev 121 = % SP 123 = Iout
118 = %act 120 = % LD 122 = %FBK 124 = Vout

125 = Fout
126 = Tout

127 = Vdc

54 =
55 =
56 =
57 =
58 =
59 =
60 =
61 =
62 =

lb/m
lb/h
FPS
ft/s
inH2O
in wg
ft wg
lbsi
ms

63 = Mrev
64 = d
65 = inWC
66 = m/min
67 = Nm
68 = Km 3/h

3406 OUTPUT1 MIN


Sets the minimum value displayed for the first display parameter.
Note: Parameter is not effective if parameter 3404 OUTPUT1 DSP FORM = 9 (DIRECT).
3407 OUTPUT1 MAX
Sets the maximum value displayed for the first display parameter.
Note: Parameter is not effective if parameter 3404 OUTPUT1 DSP FORM = 9 (DIRECT).
3408 SIGNAL2 PARAM
Selects the second parameter (by number) displayed on the control panel. See parameter 3401.
3409 SIGNAL2 MIN
Defines the minimum expected value for the second display parameter. See parameter 3402.
3410 SIGNAL2 MAX
Defines the maximum expected value for the second display parameter. See parameter 3403.
3411 OUTPUT2 DSP FORM
Defines the decimal point location for the second display parameter. See parameter 3404.
3412 OUTPUT2 UNIT
Selects the units used with the second display parameter. See parameter 3405.
3413 OUTPUT2 MIN
Sets the minimum value displayed for the second display parameter. See parameter 3406.
3414 OUTPUT2 MAX
Sets the maximum value displayed for the second display parameter. See parameter 3407.
3415 SIGNAL3 PARAM
Selects the third parameter (by number) displayed on the control panel. See parameter 3401.
3416 SIGNAL3 MIN
Defines the minimum expected value for the third display parameter. See parameter 3402.
3417 SIGNAL3 MAX
Defines the maximum expected value for the third display parameter. See parameter 3403.
3418 OUTPUT3 DSP FORM
Defines the decimal point location for the third display parameter. See parameter 3404.
3419 OUTPUT3 UNIT
Selects the units used with the third display parameter. See parameter 3405.
3420 OUTPUT3 MIN
Sets the minimum value displayed for the third display parameter. See parameter 3406.

Parameters

158

ACS550-01/U1 Users Manual

Code Description
3421 OUTPUT3 MAX
Sets the maximum value displayed for the third display parameter. See parameter 3407.

Parameters

ACS550-01/U1 Users Manual

159

Group 35: MOTOR TEMP MEAS


This group defines the detection and reporting for a particular potential fault motor
overheating, as detected by a temperature sensor. Typical connections are shown
below.
One sensor

Three sensors
AI1

AI1

Motor

Motor

AGND

AGND

AO1

AO1

AGND
AGND

3.3 nF

3.3 nF

WARNING! IEC 60664 requires double or reinforced insulation between live parts
and the surface of accessible parts of electrical equipment which are either nonconductive or conductive but not connected to the protective earth.
To fulfil this requirement, connect a thermistor (and other similar components) to the
drives control terminals using any of these alternatives:
Separate the thermistor from live parts of the motor with double reinforced
insulation.
Protect all circuits connected to the drives digital and analog inputs. Protect
against contact, and insulate from other low voltage circuits with basic insulation
(rated for the same voltage level as the drives main circuit).
Use an external thermistor relay. The relay insulation must be rated for the same
voltage level as the drives main circuit.
The figure below shows thermistor relay and PTC sensor connections using a digital
input. At the motor end, the cable shield should be earthed through, eg a 3.3 nF
capacitor. If this is not possible, leave the shield unconnected.

Thermistor relay
3501 SENSOR TYPE = 5 (THERM(0)) or 6 (THERM(1))
Thermistor
relay

PTC sensor
3501 SENSOR TYPE = 5 (THERM(0))

Control board
Control board

DI6

DI6

+24 V DC
T
T
Motor

+24 V DC
Motor

3.3 nF

Parameters

160

ACS550-01/U1 Users Manual

For other faults, or for anticipating motor overheating using a model, see Group 30:
FAULT FUNCTIONS.
Code Description
3501 SENSOR TYPE
Identifies the type of the motor temperature sensor used, PT100 (C), PTC (ohm) or thermistor.
See parameters 1501 AO1 CONTENT SEL and 1507 AO2 CONTENT SEL.
0 = NONE
1 = 1 x PT100 Sensor configuration uses one PT100 sensor.
Analog output AO1 or AO2 feeds constant current through the sensor.
The sensor resistance increases as the motor temperature rises, as does the voltage over the sensor.
The temperature measurement function reads the voltage through analog input AI1 or AI2 and converts it to
degrees Celsius.
2 = 2 x PT100 Sensor configuration uses two PT100 sensors.
Operation is the same as for above 1 x PT100.
3 = 3 x PT100 Sensor configuration uses three PT100 sensors.
Operation is the same as for above 1 x PT100.
4 = PTC Sensor configuration uses one PTC.
The analog output feeds a constant current through the sensor.
The resistance of the sensor increases sharply as the motor
temperature rises over the PTC reference temperature (Tref), as
does the voltage over the resistor. The temperature measurement
Excessive
function reads the voltage through analog input AI1 and converts it
into ohms.
The table below and the graph show typical PTC sensor resistance
as a function of the motor operating temperature.
Temperature
Resistance
Normal
Normal
< 1.5 kohm
Excessive
> 4 kohm
5 = THERM(0) Sensor configuration uses a thermistor.
Motor thermal protection is activated through a digital input. Connect
T
either a PTC sensor or a normally closed thermistor relay to a digital
input.
When the digital input is 0, the motor is overheated.
See the connection figure on page 159.
The table below and the graph show the resistance requirements for a PTC sensor connected between 24 V and
a digital input as a function of the motor operating temperature.
Temperature
Resistance
Normal
< 3 kohm
Excessive
> 28 kohm
6 = THERM(1) Sensor configuration uses a thermistor.
Motor thermal protection is activated through a digital input. Connect a normally open thermistor relay to a digital
input.
When the digital input is 1, the motor is overheated.
See the connection figure on page 159.
3502 INPUT SELECTION
Defines the input used for the temperature sensor.
1 = AI1 PT100 and PTC.
2 = AI2 PT100 and PTC.
38 = DI1DI6 Thermistor and PTC
3503 ALARM LIMIT
Defines the alarm limit for motor temperature measurement.
At motor temperatures above this limit, the drive displays an alarm (2010, MOTOR TEMP)
For thermistors or PTC connected to a digital input:
0 de-activated
1 activated

Parameters

ACS550-01/U1 Users Manual

161

Code Description
3504 FAULT LIMIT
Defines the fault limit for motor temperature measurement.
At motor temperatures above this limit, the drive displays a fault (9, MOT OVERTEMP) and stops the drive.
For thermistors or PTC connected to a digital input:
0 de-activated
1 activated

Parameters

162

ACS550-01/U1 Users Manual

Group 36: TIMED FUNCTIONS


This group defines the timed functions. The timed functions include:
four daily start and stop times
four weekly start, stop and boost times
four timers for collecting selected periods together.
A timer can be connected to multiple time periods and a time period can be in
multiple timers.
Time Period 1
3602 START TIME 1
3603 STOP TIME 1
3604 START DAY 1
3605 STOP DAY 1
Time Period 2
3606 START TIME 2
3607 STOP TIME 2
3608 START DAY 2
3609 STOP DAY 2
Time Period 3
3610 START TIME 3
3611 STOP TIME 3
3612 START DAY 3
3613 STOP DAY 3
Time Period 4
3614 START TIME 4
3615 STOP TIME 4
3616 START DAY 4
3617 STOP DAY 4

Timer 1
3626 TIMED FUNC 1 SRC
Timer 2
3627 TIMED FUNC 2 SRC
Timer 3
3628 TIMED FUNC 3 SRC
Timer 4
3629 TIMED FUNC 4 SRC

Booster
3622 BOOSTER SEL
3623 BOOSTER TIME

A parameter can be connected to only one timer.


Timer 1
3626 TIMED FUNC 1 SRC
Timer 2
3627 TIMED FUNC 2 SRC

1001 EXT1 COMMANDS


1002 EXT2 COMMANDS
1102 EXT1/EXT2 SEL
1201 CONST SPEED SEL
1401 RELAY OUTPUT 11403 RELAY OUTPUT 3
1410 RELAY OUTPUT 41412 RELAY OUTPUT 6
(Available if OREL-01 is installed.)
4027 PID 1 PARAM SET
4228 ACTIVATE
8126 TIMED AUTOCHNG

You can use the Timed functions assistant for easy configuring. For more information
on the assistants, see section Assistants mode on page 57.

Parameters

ACS550-01/U1 Users Manual

163

Code Description
3601 TIMERS ENABLE
Selects the source for the timer enable signal.
0 = NOT SEL Timed functions are disabled.
1 = DI1 Defines digital input DI1 as the timed function enable signal.
The digital input must be activated to enable the timed function.
26 = DI2DI6 Defines digital input DI2DI6 as the timed function enable signal.
7 = ACTIVE Timed functions are enabled.
-1 = DI1(INV) Defines an inverted digital input DI1 as the timed function enable signal.
This digital input must be de-activated to enable the timed function.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the timed function enable signal.
3602 START TIME 1
Defines the daily start time.
The time can be changed in steps of 2 seconds.
If parameter value is 07:00:00, the timer is activated
at 7 a.m.
The figure shows multiple timers on different
weekdays.

20:30:00

Time period 2

17:00:00
Time period 4

15:00:00
13:00:00

Time period 3

12:00:00
10:30:00

Time period 1

09:00:00
00:00:00
Mon Tue Wed Thu Fri Sat Sun
3603 STOP TIME 1
Defines the daily stop time.
The time can be changed in steps of 2 seconds.
If the parameter value is 09:00:00, the timer is deactivated at 9 a.m.
3604 START DAY 1
Defines the weekly start day.
1 = MONDAY7 = SUNDAY
If parameter value is 1, timer 1 weekly is active from Monday midnight (00:00:00).
3605 STOP DAY 1
Defines weekly stop day.
1 = MONDAY7 = SUNDAY
If parameter value is 5, timer 1 weekly is deactivated on Friday midnight (23:59:58).
3606 START TIME 2
Defines timer2 daily start time.
See parameter 3602.
3607 STOP TIME 2
Defines timer 2 daily stop time.
See parameter 3603.
3608 START DAY 2
Defines timer 2 weekly start day.
See parameter 3604.
3609 STOP DAY 2
Defines timer 2 weekly stop day.
See parameter 3605.
3610 START TIME 3
Defines timer 3 daily start time.
See parameter 3602.
3611 STOP TIME 3
Defines timer 3 daily stop time.
See parameter 3603.

Parameters

164

ACS550-01/U1 Users Manual

Code Description
3612 START DAY 3
Defines timer 3 weekly start day.
See parameter 3604.
3613 STOP DAY 3
Defines timer 3 weekly stop day.
See parameter 3605.
3614 START TIME 4
Defines timer 4 daily start time.
See parameter 3602.
3615 STOP TIME 4
Defines timer 4 daily stop time.
See parameter 3603.
3616 START DAY 4
Defines timer 4 weekly start day.
See parameter 3604.
3617 STOP DAY 4
Defines timer 4 weekly stop day.
See parameter 3605.
3622 BOOSTER SEL
Selects the source for the booster signal.
0 = NOT SEL Booster signal is disabled.
1 = DI1 Defines DI1 as the booster signal.
26 = DI2DI6 Defines DI2DI6 as the booster signal.
-1 = DI1(INV) Defines an inverted digital input DI1 as the booster signal.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the booster signal.
3623 BOOSTER TIME
Defines the booster ON time. Time is started when booster sel
signal is released. If parameter value is 01:30:00, booster is
active for 1 hour and 30 minutes after activation DI is released.

Booster active

Activation DI
Booster time
3626 TIMED FUNC 1 SRC
Defines the time periods used by the timer.
0 = NOT SEL No time periods have been selected.
1 = T1 Time Period 1 selected in the timer.
2 = T2 Time Period 2 selected in the timer.
3 = T1+T2 Time Periods 1 and 2 selected in the timer.
4 = T3 Time Period 3 selected in the timer.
5 = T1+T3 Time Periods 1 and 3 selected in the timer.
6 = T2+T3 Time Periods 2 and 3 selected in the timer.
7 = T1+T2+T3 Time Periods 1, 2 and 3 selected in the timer.
8 = T4 Time Period 4 selected in the timer.
9 = T1+T4 Time Periods 1 and 4 selected in the timer.
10 = T2+T4 Time Periods 2 and 4 selected in the timer.
11 = T1+T2+T4 Time Periods 1, 2 and 4 selected in the timer.
12 = T3+T4 Time Periods 3 and 4 selected in the timer.
13 = T1+T3+T4 Time Periods 1, 3 and 4 selected in the timer.
14 = T2+T3+T4 Time Periods 2, 3 and 4 selected in the timer.
15 = T1+T2+T3+T4 Time Periods 1, 2, 3 and 4 selected in the timer.
16 = BOOSTER Booster selected in the timer.
17 = T1+B Booster and Time Period 1 selected in the timer.
18 = T2+B Booster and Time Period 2 selected in the timer.
19 = T1+T2+B Booster and Time Periods 1 and 2 selected in the timer.
20 = T3+B Booster and Time Period 3 selected in the timer.

Parameters

ACS550-01/U1 Users Manual

165

Code Description
21 = T1+T3+B Booster and Time Periods 1 and 3 selected in the timer.
22 = T2+T3+B Booster and Time Periods 2 and 3 selected in the timer.
23 = T1+T2+T3+B Booster and Time Periods 1, 2 and 3 selected in the timer.
24 = T4+B Booster and Time Period 4 selected in the timer.
25 = T1+T4+B Booster and Time Periods 1 and 4 selected in the timer.
26 = T2+T4+B Booster and Time Periods 2 and 4 selected in the timer.
27 = T1+T2+T4+B Booster and Time Periods 1, 2 and 4 selected in the timer.
28 = T3+T4+B Booster and Time Periods 3 and 4 selected in the timer.
29 = T1+T3+T4+B Booster and Time Periods 1, 3 and 4 selected in the timer.
30 = T2+T3+T4+B Booster and Time Periods 2, 3 and 4 selected in the timer.
31 = T1+2+3+4+B Booster and Time Periods 1, 2, 3 and 4 selected in the timer.
3627 TIMED FUNC 2 SRC
See parameter 3626.
3628 TIMED FUNC 3 SRC
See parameter 3626.
3629 TIMED FUNC 4 SRC
See parameter 3626.

Parameters

166

ACS550-01/U1 Users Manual

Group 37: USER LOAD CURVE


This group defines supervision of user adjustable load curves (motor torque as a
function of frequency). The curve is defined by five points.
Code Description
3701 USER LOAD C MODE
Supervision mode for the user adjustable load
curves.
This functionality replaces the former underload
supervision in Group 30: FAULT FUNCTIONS. To
emulate it, see section Correspondence with the
obsolete underload supervision on page 167.
0 = NOT SEL Supervision is not active.
1 = UNDERLOAD Supervision for the torque
dropping below the underload curve.
2 = OVERLOAD Supervision for the torque
exceeding the overload curve.
3 = BOTH Supervision for the torque dropping
below the underload curve or exceeding the
overload curve.

Motor torque (%)


Overload area
P3706

P3709

P3712

P3715
P3714

P3718
P3717

Allowed operating area


P3711
P3705

Underload area
P3708
P3704

P3707

P3710 P3713

P3716

Output frequency (Hz)


3702 USER LOAD C FUNC
Action wanted during load supervision.
1 = FAULT A fault is generated when the condition defined by 3701 USER LOAD C MODE has been valid longer than
the time set by 3703 USER LOAD C TIME.
2 = ALARM An alarm is generated when the condition defined by 3701 USER LOAD C MODE has been valid longer than
half of the time defined by 3703 USER LOAD C TIME.
3703 USER LOAD C TIME
Defines the time limit for generating a fault.
Half of this time is used as the limit for generating an alarm.
3704 LOAD FREQ 1
Defines the frequency value of the first load curve definition point.
Must be smaller than 3707 LOAD FREQ 2.
3705 LOAD TORQ LOW 1
Defines the torque value of the first underload curve definition point.
Must be smaller than 3706 LOAD TORQ HIGH 1.
3706 LOAD TORQ HIGH 1
Defines the torque value of the first overload curve definition point.
3707 LOAD FREQ 2
Defines the frequency value of the second load curve definition point.
Must be smaller than 3710 LOAD FREQ 3.
3708 LOAD TORQ LOW 2
Defines the torque value of the second underload curve definition point.
Must be smaller than 3709 LOAD TORQ HIGH 2.
3709 LOAD TORQ HIGH 2
Defines the torque value of the second overload curve definition point.
3710 LOAD FREQ 3
Defines the frequency value of the third load curve definition point.
Must be smaller than 3713 LOAD FREQ 4.
3711 LOAD TORQ LOW 3
Defines the torque value of the third underload curve definition point.
Must be smaller than 3712 LOAD TORQ HIGH 3.
3712 LOAD TORQ HIGH 3
Defines the torque value of the third overload curve definition point.

Parameters

ACS550-01/U1 Users Manual

167

Code Description
3713 LOAD FREQ 4
Defines the frequency value of the fourth load curve definition point.
Must be smaller than 3716 LOAD FREQ 5
3714 LOAD TORQ LOW 4
Defines the torque value of the fourth underload curve definition point.
Must be smaller than 3715 LOAD TORQ HIGH 4.
3715 LOAD TORQ HIGH 4
Defines the torque value of the fourth overload curve definition point.
3716 LOAD FREQ 5
Defines the frequency value of fifth load curve definition point.
3717 LOAD TORQ LOW 5
Defines the torque value of the fifth underload curve definition point.
Must be smaller than 3718 LOAD TORQ HIGH 5.
3718 LOAD TORQ HIGH 5
Defines the torque value of the fifth overload curve definition point.

Correspondence with the obsolete underload supervision


The now obsolete parameter 3015 UNDERLOAD CURVE provided five selectable
curves shown in the figure. The parameter characteristics were as described below.
If the load drops below the
set curve for longer than
the time set by parameter
3014 UNDERLOAD TIME
(obsolete), the underload
protection is activated.
Curves 13 reach
maximum at the motor
rated frequency set by
parameter 9907 MOTOR
NOM FREQ.
TM = nominal torque of the
motor.

TM
(%)
80

Underload curve types

3
70%

60

2
50%
1

40

5
30%

20

4
f

2.4 N

N = nominal frequency of
the motor.
If you want to emulate the behavior of an old underload curve with parameters as in
the shaded columns, set the new parameters as in the white columns in the two
tables below:
Obsolete parameters
New parameters
Underload supervision with
3013
3014
3701
3702
3703
parameters 30133015 (obsolete) UNDERLOAD UNDERLOAD USER LOAD USER LOAD USER LOAD
FUNCTION

TIME

C MODE

C FUNC

C TIME

No underload functionality

Underload curve, fault generated

Underload curve, alarm generated

2t

Parameters

168

ACS550-01/U1 Users Manual

Obs.
par.

Parameters

New parameters

3015

3704

3705

3707

3708

3710

3711

3713

3714

3716

3717

UNDER
LOAD
CURVE

LOAD
FREQ 1

LOAD
TORQ
LOW 1

LOAD
FREQ 2

LOAD
TORQ
LOW 2

LOAD
FREQ 3

LOAD
TORQ
LOW 3

LOAD
FREQ 4

LOAD
TORQ
LOW 4

LOAD
FREQ 5

LOAD
TORQ
LOW 5

(Hz)

(%)

(Hz)

(%)

(Hz)

(%)

(Hz)

(%)

(Hz)

(%)

EU

US

EU

US

EU

US

10

32

38

20

31

30

EU

US

17

41

50

37

30

42

31

37

43

10

73

88

20

71

86

EU

US

23

50

60

30

500 500

30

50

40

50

60

50

500 500

50

42

50

57

50

60

70

500 500

70

17

98

117

23

120 144

30

500 500

30

30

99

119

40

120 144

50

500 500

50

ACS550-01/U1 Users Manual

169

Group 40: PROCESS PID SET 1


This group defines a set of parameters used with the Process PID (PID1) controller.
Typically only parameters in this group are needed.
PID controller Basic set-up
In PID control mode, the drive compares a reference signal (setpoint) to an actual
signal (feedback) and automatically adjusts the speed of the drive to match the two
signals. The difference between the two signals is the error value.
Typically PID control mode is used, when the speed of a motor needs to be
controlled based on pressure, flow or temperature. In most cases when there is
only 1 transducer signal wired to the ACS550 only parameter group 40 is needed.
The following is a schematic of setpoint/feedback signal flow using parameter group
40.
Panel REF1
Panel REF 2
Panel REF2
AI
Current
Torque
Power

P4016

AI
Current
Torque
Power

P4017

P4014

Panel REF 1
DI
AI
Comm REF 1
Panel REF 2
DI
AI
Comm REF 2
Panel REF2 P4010
AI1
AI2
Comm
Internal
AI P4016
Current
Torque
Power
P4014
AI P4017
Current
Torque
Power

500% PID Setpoint


-500%
G40
PID1

P1106

P1106
017,
2021
19

P1101
REF1
REF2

PANEL
LOC/REM
selection
LOC

P4015
PID Act Value

P1103

G12
Const
Speed

REM

P1104
P1105

P1102
EXT 1
EXT 2

G12
Const
Speed

PID Setpoint
P4012
P4013
G40
PID1

P1106
017,
2021
19

P1107
P1108

PID1 Out

P4015
PID Act Value

Note: In order to activate and use the PID controller, parameter 1106 must be set to
value 19.

Parameters

170

ACS550-01/U1 Users Manual

PID controller Advanced


The ACS550 has two separate PID controllers:
Process PID (PID1) and
External PID (PID2)
Process PID (PID1) has 2 separate sets of parameters:
Process PID (PID1) SET1, defined in Group 40: PROCESS PID SET 1 and
Process PID (PID1) SET2, defined in Group 41: PROCESS PID SET 2
You can select between the two different sets by using parameter 4027.
Typically two different PID controller sets are used when the load of the motor
changes considerably from one situation to another.
You can use External PID (PID2), defined in Group 42: EXT / TRIM PID, in two
different ways:
Instead of using additional PID controller hardware, you can set outputs of the
ACS550 to control a field instrument like a damper or a valve. In this case, set
parameter 4230 to value 0. (0 is the default value.)
You can use External PID (PID2) to trim or fine-tune the speed of the ACS550.
Code Description
4001 GAIN
Defines the PID controllers gain.
The setting range is 0.1 100.
At 0.1, the PID controller output changes one-tenth as much as the error value.
At 100, the PID controller output changes one hundred times as much as the error value.
Use the proportional gain and integration time values to adjust the responsiveness of the system.
A low value for proportional gain and a high value for integral time ensures stable operation, but provides sluggish
response.
If the proportional gain value is too large or the integral time too short, the system can become unstable.
Procedure:
Initially, set:
4001 GAIN = 0.1.
4002 INTEGRATION TIME = 20 seconds.
Start the system and see if it reaches the setpoint quickly while maintaining stable operation. If not, increase GAIN
(4001) until the actual signal (or drive speed) oscillates constantly. It may be necessary to start and stop the drive to
induce this oscillation.
Reduce GAIN (4001) until the oscillation stops.
Set GAIN (4001) to 0.4 to 0.6 times the above value.
Decrease the INTEGRATION TIME (4002) until the feedback signal (or drive speed) oscillates constantly. It may be
necessary to start and stop the drive to induce this oscillation.
Increase INTEGRATION TIME (4002) until the oscillation stops.
Set INTEGRATION TIME (4002) to 1.15 to 1.5 times the above value.
If the feedback signal contains high frequency noise, increase the value of parameter 1303 FILTER AI1 or 1306
FILTER AI2 until the noise is filtered from the signal.

Parameters

ACS550-01/U1 Users Manual

171

Code Description
4002 INTEGRATION TIME
Defines the PID controllers integration time.
Integration time is, by definition, the time required to increase the
output by the error value:
Error value is constant and 100%.
Gain = 1.
Integration time of 1 second denotes that a 100% change is
achieved in 1 second.
0.0 = NOT SEL Disables integration (I-part of controller).
0.13600.0 Integration time (seconds).
See 4001 for adjustment procedure.

A
B
D (P 4001 = 10)
C (P 4001 = 1)
t
P 4002
A = Error
B = Error value step
C = Controller output with Gain = 1
D = Controller output with Gain = 10

4003 DERIVATION TIME


Defines the PID controllers derivation time.
You can add the derivative of the error to the PID controller
output. The derivative is the error values rate of change. For
example, if the process error value changes linearly, the
derivative is a constant added to the PID controller output.
The error-derivative is filtered with a 1-pole filter. The time
constant of the filter is defined by parameter 4004 PID DERIV
FILTER.
0.010.0 Derivation time (seconds).

Process error value

Error
100%

0%

PID output

D-part of controller output

Gain
P 4001
P 4003

4004 PID DERIV FILTER


Defines the filter time constant for the error-derivative part of the PID controller output.
Before being added to the PID controller output, the error-derivative is filtered with a 1-pole filter.
Increasing the filter time smooths the error-derivative, reducing noise.
0.010.0 Filter time constant (seconds).
4005 ERROR VALUE INV
Selects either a normal or inverted relationship between the feedback signal and the drive speed.
0 = NO Normal, a decrease in feedback signal increases drive speed. Error = Ref - Fbk
1 = YES Inverted, a decrease in feedback signal decreases drive speed. Error = Fbk - Ref
4006 UNITS
Selects the unit for the PID controller actual values. (PID1 parameters 0128, 0130 and 0132).
See parameter 3405 for list of available units.
4007 UNIT SCALE
Defines the decimal point location in PID controller actual values.
Enter the decimal point location counting in from the right end of the
entry.
See the table for an example using pi (3.14159).

4007 value
0
1
2
3
4

Entry
00003
00031
00314
03142
31416

Display
3
3.1
3.14
3.142
3.1416

Parameters

172

ACS550-01/U1 Users Manual

Code Description
4008 0% VALUE
Defines (together with the next parameter) the scaling applied to
the PID controllers actual values (PID1 parameters 0128, 0130
and 0132).
Units and scale are defined by parameters 4006 and 4007.
4009 100% VALUE
Defines (together with the previous parameter) the scaling applied
to the PID controllers actual values.
Units and scale are defined by parameters 4006 and 4007.

Units (P4006)
Scale (P4007)

+1000.0%

P 4009

P 4008

-1000.0%

0%

100%
Internal scale (%)

4010 SET POINT SEL


Defines the reference signal source for the PID controller.
Parameter has no significance when the PID regulator is by-passed (see 8121 REG BYPASS CTRL).
0 = KEYPAD Control panel provides reference.
1 = AI1 Analog input 1 provides reference.
2 = AI2 Analog input 2 provides reference.
8 = COMM Fieldbus provides reference.
9 = COMM+AI1 Defines a fieldbus and analog input 1 (AI1) combination as the reference source. See Analog input
reference correction below.
10 = COMM*AI1 Defines a fieldbus and analog input 1 (AI1) combination as the reference source. See Analog input
reference correction below.
11 = DI3U,4D(RNC) Digital inputs, acting as a motor potentiometer control, provide reference.
DI3 increases the speed (the U stands for up)
DI4 decreases the reference (the D stands for down).
Parameter 2205 ACCELER TIME 2 controls the reference signals rate of change.
R = Stop command resets the reference to zero.
NC = Reference value is not copied.
12 = DI3U,4D(NC) Same as DI3U,4D(RNC) above, except:
Stop command does not reset reference to zero. At restart the motor ramps up, at the selected acceleration rate,
to the stored reference.
13 = DI5U,6D(NC) Same as DI3U,4D(NC) above, except:
Uses digital inputs DI5 and DI6.
14 = AI1+AI2 Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See
Analog input reference correction below.
15 = AI1*AI2 Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See
Analog input reference correction below.
16 = AI1-AI2 Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See
Analog input reference correction below.
17 = AI1/AI2 Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See
Analog input reference correction below.
19 = INTERNAL A constant value set using parameter 4011 provides reference.
20 = PID2OUT Defines PID controller 2 output (parameter 0127 PID 2 OUTPUT) as the reference source.

Parameters

ACS550-01/U1 Users Manual

173

Code Description
Analog input reference correction
Parameter values 9, 10 and 1417 use the formula in the following table.
Value setting
C+B
C*B
C-B
C/B

Calculation of the AI reference


C value + (B value - 50% of reference value)
C value (B value / 50% of reference value)
(C value + 50% of reference value) - B value
(C value 50% of reference value) / B value

Where:
C = Main reference value
( = COMM for values 9, 10 and
= AI1 for values 1417)
B = Correcting reference
( = AI1 for values 9, 10 and
= AI2 for values 1417).
Example:
The figure shows the reference source curves for
value settings 9, 10 and 1417, where:
C = 25%.
P 4012 SETPOINT MIN = 0.
P 4013 SETPOINT MAX = 0.
B varies along the horizontal axis.

120

17 (/)

100
80
60

9, 14 (+)

40

10, 15 (*)

20
0

16 (-)
0

100%

4011 INTERNAL SETPNT


Sets a constant value used for the process reference.
Units and scale are defined by parameters 4006 and 4007.
4012 SETPOINT MIN
Sets the minimum value for the reference signal source.
See parameter 4010.
4013 SETPOINT MAX
Sets the maximum value for the reference signal source.
See parameter 4010.
4014 FBK SEL
Defines the PID controller feedback (actual signal).
You can define a combination of two actual values (ACT1 and ACT2) as the feedback signal.
Use parameter 4016 to define the source for actual value 1 (ACT1).
Use parameter 4017 to define the source for actual value 2 (ACT2).
1 = ACT1 Actual value 1 (ACT1) provides the feedback signal.
2 = ACT1-ACT2 ACT1 minus ACT2 provides the feedback signal.
3 = ACT1+ACT2 ACT1 plus ACT2 provides the feedback signal.
4 = ACT1*ACT2 ACT1 times ACT2 provides the feedback signal.
5 = ACT1/ACT2 ACT1 divided by ACT2 provides the feedback signal.
6 = MIN(ACT1,2) The smaller of ACT1 or ACT2 provides the feedback signal.
7 = MAX(ACT1,2) The greater of ACT1 or ACT2 provides the feedback signal.
8 = sqrt(ACT1-2) Square root of the value for ACT1 minus ACT2 provides the feedback signal.
9 = sqA1+sqA2 Square root of ACT1 plus the square root of ACT2 provides the feedback signal.
10 = sqrt(ACT1) Square root of ACT1 provides the feedback signal.
11 = COMM FBK 1 Signal 0158 PID COMM VALUE 1 provides the feedback signal.
12 = COMM FBK 2 Signal 0159 PID COMM VALUE 2 provides the feedback signal.
13 = AVE(ACT1,2) The average of ACT1 and ACT2 provides the feedback signal.
4015 FBK MULTIPLIER
Defines an extra multiplier for the PID feedback value FBK defined by parameter 4014.
Used mainly in applications where the flow is calculated from the pressure difference.
0.000 = NOT SEL The parameter has no effect (1.000 used as the multiplier).
-32.76832.767 Multiplier applied to the signal defined by parameter 4014 FBK SEL.
Example: FBK = Multiplier A1 A2

Parameters

174

ACS550-01/U1 Users Manual

Code Description
4016 ACT1 INPUT
Defines the source for actual value 1 (ACT1). See also parameter 4018 ACT1 MINIMUM.
1 = AI1 Uses analog input 1 for ACT1.
2 = AI2 Uses analog input 2 for ACT1.
3 = CURRENT Uses current for ACT1.
4 = TORQUE Uses torque for ACT1.
5 = POWER Uses power for ACT1.
6 = COMM ACT 1 Uses value of signal 0158 PID COMM VALUE 1 for ACT1.
7 = COMM ACT 2 Uses value of signal 0159 PID COMM VALUE 2 for ACT1.
4017 ACT2 INPUT
Defines the source for actual value 2 (ACT2). See also parameter 4020 ACT2 MINIMUM.
1 = AI1 Uses analog input 1 for ACT2.
2 = AI2 Uses analog input 2 for ACT2.
3 = CURRENT Uses current for ACT2.
4 = TORQUE Uses torque for ACT2.
5 = POWER Uses power for ACT2.
6 = COMM ACT 1 Uses value of signal 0158 PID COMM VALUE 1 for ACT2.
7 = COMM ACT 2 Uses value of signal 0159 PID COMM VALUE 2 for ACT2.
4018 ACT1 MINIMUM
Sets the minimum value for ACT1.
Scales the source signal used as the actual value ACT1 (defined
by parameter 4016 ACT1 INPUT). For parameter 4016 values
6 (COMM ACT 1) and 7 (COMM ACT 2) scaling is not done.
Par 4016
1
2
3
4
5

Source
Analog input 1
Analog input 2
Current
Torque
Power

Source min.
1301 MINIMUM AI1
1304 MINIMUM AI2
0
-2 nominal torque
-2 nominal power

Source max.
1302 MAXIMUM AI1
1305 MAXIMUM AI2
2 nominal current
2 nominal torque
2 nominal power

See the figure: A= Normal; B = Inversion (ACT1 MINIMUM > ACT1


MAXIMUM)
4019 ACT1 MAXIMUM
Sets the maximum value for ACT1.
See 4018 ACT1 MINIMUM.
4020 ACT2 MINIMUM
Sets the minimum value for ACT2.
See 4018 ACT1 MINIMUM.
4021 ACT2 MAXIMUM
Sets the maximum value for ACT2.
See 4018 ACT1 MINIMUM.

ACT1

(%)

P 4019

P 4018
Source min. Source max.
Source signal
ACT1

(%)

P 4018

P 4019
Source min.
Source max.
Source signal

4022 SLEEP SELECTION


Defines the control for the PID sleep function.
0 = NOT SEL Disables the PID sleep control function.
1 = DI1 Defines digital input DI1 as the control for the PID sleep function.
Activating the digital input activates the sleep function.
De-activating the digital input restores PID control.
26 = DI2DI6 Defines digital input DI2DI6 as the control for the PID sleep function.
See DI1 above.
7 = INTERNAL Defines the output rpm/frequency, process reference and process actual value as the control for the
PID sleep function. Refer to parameters 4025 WAKE-UP DEV and 4023 PID SLEEP LEVEL.
-1 = DI1(INV) Defines an inverted digital input DI1 as the control for the PID sleep function.
De-activating the digital input activates the sleep function.
Activating the digital input restores PID control.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the control for the PID sleep function.
See DI1(INV) above.

Parameters

ACS550-01/U1 Users Manual

175

Code Description
4023 PID SLEEP LEVEL
Sets the motor speed / frequency that enables the PID sleep
function a motor speed / frequency below this level, for at least
the time period 4024 PID SLEEP DELAY enables the PID sleep
function (stopping the drive).
Requires 4022 = 7 (INTERNAL).
See the figure: A = PID output level; B = PID process feedback.
4024 PID SLEEP DELAY
Sets the time delay for the PID sleep function a motor speed /
frequency below 4023 PID SLEEP LEVEL for at least this time period
enables the PID sleep function (stopping the drive).
See 4023 PID SLEEP LEVEL above.
4025 WAKE-UP DEV
Defines the wake-up deviation a deviation from the setpoint
greater than this value, for at least the time period 4026 WAKE-UP
DELAY, re-starts the PID controller.
Parameters 4006 and 4007 define the units and scale.
Parameter 4005 = 0,
Wake-up level = Setpoint - Wake-up deviation.
Parameter 4005 = 1,
Wake-up level = Setpoint + Wake-up deviation.
Wake-up level can be above or below setpoint.
See the figures:
C = Wake-up level when parameter 4005 = 1
D = Wake-up level when parameter 4005 = 0
E = Feedback is above wake-up level and lasts longer than 4026
WAKE-UP DELAY PID function wakes up.
F = Feedback is below wake-up level and lasts longer than 4026
WAKE-UP DELAY PID function wakes up.
4026 WAKE-UP DELAY
Defines the wake-up delay a deviation from the setpoint greater
than 4025 WAKE-UP DEV, for at least this time period, re-starts the
PID controller.

t < P 4024
t > P 4024
P 4023

t
B
P 4026

Setpoint
P 4025

t
Stop
Start
C
4005 = 1

}
=0
}4005
D

P 4025
Setpoint
P 4025

t
E
P 4025
Setpoint
P 4025

C
P 4026
D

P 4026
F

Parameters

176

ACS550-01/U1 Users Manual

Code Description
4027 PID 1 PARAM SET
Process PID (PID1) has two separate sets of parameters, PID set 1 and PID set 2.
PID set 1 uses parameters 40014026.
PID set 2 uses parameters 41014126.
PID 1 PARAM SET defines which set is selected.
0 = SET 1 PID Set 1 (parameters 40014026) is active.
1 = DI1 Defines digital input DI1 as the control for PID Set selection.
Activating the digital input selects PID Set 2.
De-activating the digital input selects PID Set 1.
26 = DI2DI6 Defines digital input DI2DI6 as the control for PID Set selection.
See DI1 above.
7 = SET 2 PID Set 2 (parameters 41014126) is active.
811 = TIMED FUNC 14 Defines the Timed function as the control for the PID Set selection (Timed function deactivated = PID Set 1; Timed function activated = PID Set 2)
See Group 36: TIMED FUNCTIONS.
12 = 2-ZONE MIN The drive calculates the difference between setpoint 1 and feedback 1 as well as setpoint 2 and
feedback 2. The drive will control the zone (and select the set) that has a larger difference.
A positive difference (a setpoint higher than the feedback) is always larger than a negative difference. This keeps
feedback values at or above the setpoint.
Controller does not react to the situation of feedback above setpoint if another zone's feedback is closer to its
setpoint.
13 = 2-ZONE MAX The drive calculates the difference between setpoint 1 and feedback 1 as well as setpoint 2 and
feedback 2. The drive will control the zone (and select the set) that has a smaller difference.
A negative difference (a setpoint lower than the feedback) is always smaller than a positive difference. This keeps
feedback values at or below the setpoint.
Controller does not react to the situation of feedback below setpoint if another zone's feedback is closer to its
setpoint.
14 = 2-ZONE AVE The drive calculates the difference between setpoint 1 and feedback 1 as well as setpoint 2 and
feedback 2. In addition, it calculates the average of the deviations and uses it to control zone 1. Therefore one
feedback is kept above its setpoint and another is kept as much below its setpoint.
-1 = DI1(INV) Defines an inverted digital input DI1 as the control for PID Set selection.
Activating the digital input selects PID Set 1.
De-activating the digital input selects PID Set 2.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the control for PID Set selection.
See DI1(INV) above.

Parameters

ACS550-01/U1 Users Manual

177

Group 41: PROCESS PID SET 2


Parameters of this group belong to PID parameter set 2. The operation of
parameters 41014126 is analogous with set 1 parameters 40014026.
PID parameter set 2 can be selected by parameter 4027 PID 1 PARAM SET.
Code Description
4101

4126

See 4001 4026

Parameters

178

ACS550-01/U1 Users Manual

Group 42: EXT / TRIM PID


This group defines the parameters used for the second PID controller (PID2), which
is used for the External / Trimming PID.
The operation of parameters 42014221 is analogous with Process PID set 1
(PID1) parameters 40014021.
Code Description
4201 See 4001 4021

4221
4228 ACTIVATE
Defines the source for enabling the external PID function.
Requires 4230 TRIM MODE = 0 (NOT SEL).
0 = NOT SEL Disables external PID control.
1 = DI1 Defines digital input DI1 as the control for enabling external PID control.
Activating the digital input enables external PID control.
De-activating the digital input disables external PID control.
26 = DI2DI6 Defines digital input DI2DI6 as the control for enabling external PID control.
See DI1 above.
7 = DRIVE RUN Defines the start command as the control for enabling external PID control.
Activating the start command (drive is running) enables external PID control.
8 = ON Defines the power-on as the control for enabling external PID control.
Activating power to the drive enables external PID control.
912 = TIMED FUNC 14 Defines the Timed function as the control for enabling external PID control (Timed
function active enables external PID control).
See Group 36: TIMED FUNCTIONS.
-1 = DI1(INV) Defines an inverted digital input DI1 as the control for enabling external PID control.
Activating the digital input disables external PID control.
De-activating the digital input enables external PID control.
-2-6 = DI2(INV)DI6(INV) Defines an inverted digital input DI2DI6 as the control for enabling external PID control.
See DI1(INV) above.
4229 OFFSET
Defines the offset for the PID output.
When PID is activated, output starts from this value.
When PID is deactivated, output resets to this value.
Parameter is active when 4230 TRIM MODE = 0 (trim mode is not active).
4230 TRIM MODE
Selects the type of trim, if any. Using the trim it is possible to combine a corrective factor to the drive reference.
0 = NOT SEL Disables the trim function.
1 = PROPORTIONAL Adds a trim factor that is proportional to the rpm/Hz reference.
2 = DIRECT Adds a trim factor based on the control loops maximum limit.
4231 TRIM SCALE
Defines the multiplier (as a percent, plus or minus) used in the trim mode.

Parameters

ACS550-01/U1 Users Manual

179

Code Description
4232 CORRECTION SRC
Defines the trimming reference for the correction source.
1 = PID2REF Uses appropriate REF MAX (S WITCH A OR B):
1105 REF1 MAX when REF1 is active (A).
1108 REF2 MAX when REF2 is active (B).
2 = PID2OUTPUT Uses the absolute maximum speed or frequency (Switch C):
2002 MAXIMUM SPEED if 9904 MOTOR CTRL MODE = 1 (VECTOR:sPEED) or 2 (VECTOR:TORQ).
2008 MAXIMUM FREQ if 9904 MOTOR CTRL MODE = 3 (SCALAR:FREQ).
Add
Ramped ref
Switch

Select
(par. 4230)

Ext ref 1 max (A)

off

Ext ref 2 max (B)

proportional

Abs max speed/


freq (C)

direct

Trimmed ref
Trim scale

Mul.
X

Mul.

Select
(par. 4232)
Trimming PID2 ref

PID2 ref

PID 2

Trimming PID2 out

Parameters

180

ACS550-01/U1 Users Manual

Group 45: ENERGY SAVING


This group defines the setup of calculation and optimization of energy savings.
Note: The values of saved energy parameters 0174 SAVED KWH, 0175 SAVED MWH,
0176 SAVED AMOUNT 1, 0177 SAVED AMOUNT 2 and 0178 SAVED CO2 are derived from
subtracting the drive's energy consumed from the direct-on-line (DOL) consumption
calculated on the basis of parameter 4508 PUMP POWER. As such, the accuracy of
the values is dependent on the accuracy of the power estimate entered in that
parameter.
Code Description
4502 ENERGY PRICE
Price of energy per kWh.
Used for reference when energy savings are calculated.
See parameters 0174 SAVED KWH, 0175 SAVED MWH, 0176 SAVED AMOUNT 1, 0177 SAVED AMOUNT 2 and 0178
SAVED CO2 (reduction on carbon dioxide emissions in tn).
4507 CO2 CONV FACTOR
Conversion factor for converting energy into CO2 emissions (kg/kWh or tn/MWh). Used for multiplying the saved
energy in MWh to calculate the value of parameter 0178 SAVED CO2 (reduction on carbon dioxide emissions in tn).
4508 PUMP POWER
Pump power (as a percentage of the nominal motor power) when connected directly to supply (DOL).
Used for reference when energy savings are calculated.
See parameters 0174 SAVED KWH, 0175 SAVED MWH, 0176 SAVED AMOUNT 1, 0177 SAVED AMOUNT 2 and 0178
SAVED CO2.
It is possible to use this parameter as the reference power also for other applications than pumps. The reference
power can also be some other constant power than a motor connected directly online.
4509 ENERGY RESET
Resets energy calculators 0174 SAVED KWH, 0175 SAVED MWH, 0176 SAVED AMOUNT 1, 0177 SAVED AMOUNT 2 and
0178 SAVED CO2.

Parameters

ACS550-01/U1 Users Manual

181

Group 50: ENCODER


This group defines the setup for encoder use:
Sets the number of encoder pulses per shaft revolution.
Enables the encoder operation.
Defines how mechanical angle and revolution data is reset.
See also Users Manual for Pulse Encoder Interface Module OTAC-01
(3AUA0000001938 [English]).
Code Description
5001 PULSE NR
Sets the number of pulses provided by an optional encoder for each full motor shaft revolution (ppr).
5002 ENCODER ENABLE
Enables/disables an optional encoder.
0 = DISABLE Drive uses speed feedback derived from the internal motor model (applies for any setting of parameter
9904 MOTOR CTRL MODE).
1 = ENABLE Drive uses feedback from an optional encoder. This function requires the Pulse Encoder Interface
Module (OTAC-01) and an encoder. Operation depends on the setting of parameter 9904 MOTOR CTRL MODE:
9904 = 1 (VECTOR:SPEED): The encoder provides improved speed feedback and improved low speed torque
accuracy.
9904 = 2 (VECTOR:TORQ): The encoder provides improved speed feedback and improved low speed torque
accuracy.
9904 = 3 (SCALAR:SPEED): The encoder provides speed feedback. (This is not closed loop speed regulation.
However, using parameter 2608 SLIP COMP RATIO and an encoder improves steady state speed accuracy.)
5003 ENCODER FAULT
Defines the drive operation if a failure is detected in communication between the encoder and the encoder interface
module, or between the module and the drive.
1 = FAULT The drive generates fault ENCODER ERR, and the motor coasts to a stop.
2 = ALARM The drive generates alarm ENCODER ERR and operates as if parameter 5002 ENCODER ENABLE =
0 (DISABLE), that is, speed feedback is derived from the internal motor model.
5010 Z PLS ENABLE
Enables/disables the use of an encoders Z-pulse to define the motor shafts zero position. When enabled, a Z-pulse
input resets parameter 0146 MECH ANGLE to zero to define the shafts zero position. This function requires an encoder
that provides Z-pulse signals.
0 = DISABLE Z-pulse input is not present or ignored if present.
1 = ENABLE A Z-pulse input resets parameter 0146 MECH ANGLE to zero.
5011 POSITION RESET
Resets the encoders position feedback. This parameter is self-clearing.
0 = DISABLE Inactive.
1 = ENABLE Resets the encoder position feedback. Parameters reset depends on the state of parameter 5010 Z PLS
ENABLE:
5010 = 0 (DISABLE) Reset applies to parameters 0147 MECH REVS and 0146 MECH ANGLE.
5010 = 1 (ENABLE) Reset applies only to parameter 0147 MECH REVS.

Parameters

182

ACS550-01/U1 Users Manual

Group 51: EXT COMM MODULE


This group defines set-up variables for a fieldbus adapter (FBA) communication
module. For more information on these parameters, refer to the users manual
supplied with the FBA module.
Code Description
5101 FBA TYPE
Displays the type of the connected fieldbus adapter module.
0 = NOT DEFINED Module not found, or not properly connected, or parameter 9802 is not set to 4 (EXT FBA).
1 = PROFIBUS-DP
21 = LONWORKS
32 = CANopen
37 = DEVICENET
101 = CONTROLNET
128 = ETHERNET
132 = PROFINET
135 = EtherCAT
136 = EPL Ethernet POWERLINK
5102 FB PAR 2FB PAR 26

Refer to communication module documentation for more information on these parameters.


5126
5127 FBA PAR REFRESH
Validates any changed fieldbus parameter settings.
0 = DONE Refreshing done.
1 = REFRESH Refreshing.
After refreshing, the value reverts automatically to DONE.
5128 FILE CPI FW REV
Displays the CPI firmware revision of the drives fieldbus adapter configuration file. Format is xyz where:
x = major revision number
y = minor revision number
z = correction number
Example: 107 = revision 1.07
5129 FILE CONFIG ID
Displays the revision of the drives fieldbus adapter modules configuration file identification.
File configuration information is drive application program-dependent.
5130 FILE CONFIG REV
Contains the revision of the drives fieldbus adapter module configuration file.
Example: 1 = revision 1
5131 FBA STATUS
Contains the status of the adapter module.
0 = IDLE Adapter not configured.
1 = EXECUT INIT Adapter is initializing.
2 = TIME OUT A timeout has occurred in the communication between the adapter and the drive.
3 = CONFIG ERROR Adapter configuration error.
The revision code of the adapters CPI firmware revision is older than required CPI firmware version defined in
the drives configuration file (parameter 5132 < 5128).
4 = OFF-LINE Adapter is off-line.
5 = ON-LINE Adapter is on-line.
6 = RESET Adapter is performing a hardware reset.
5132 FBA CPI FW REV
Contains the revision of the modules CPI program. Format is xyz where:
x = major revision number
y = minor revision number
z = correction number
Example: 107 = revision 1.07
5133 FBA APPL FW REV
Contains the revision of the modules application program. Format is xyz (see parameter 5132).

Parameters

ACS550-01/U1 Users Manual

183

Group 52: PANEL COMM


This group defines the communication settings for the control panel port on the drive.
Normally, when using the supplied control panel, there is no need to change settings
in this group.
In this group, parameter modifications take effect on the next power-up.
Code Description
5201 STATION ID
Defines the address of the drive.
Two units with the same address are not allowed on-line.
Range: 1247
5202 BAUD RATE
Defines the communication speed of the drive in kbits per second (kb/s).
9.6 kb/s
19.2 kb/s
38.4 kb/s
57.6 kb/s
115.2 kb/s
5203 PARITY
Sets the character format to be used with the panel communication.
0 = 8 NONE 1 8 data bits, no parity, one stop bit.
1 = 8 NONE 2 8 data bits, no parity, two stop bits.
2 = 8 EVEN 1 8 data bits, even parity, one stop bit.
3 = 8 ODD 1 8 data bits, odd parity, one stop bit.
5204 OK MESSAGES
Contains a count of valid Modbus messages received by the drive.
During normal operation, this counter is increasing constantly.
5205 PARITY ERRORS
Contains a count of the characters with a parity error that is received from the bus. For high counts, check:
Parity settings of devices connected on the bus they must not differ.
Ambient electro-magnetic noise levels high noise levels generate errors.
5206 FRAME ERRORS
Contains a count of the characters with a framing error that the bus receives. For high counts, check:
Communication speed settings of devices connected on the bus they must not differ.
Ambient electro-magnetic noise levels high noise levels generate errors.
5207 BUFFER OVERRUNS
Contains a count of the characters received that cannot be placed in the buffer.
Longest possible message length for the drive is 128 bytes.
Received messages exceeding 128 bytes overflow the buffer. The excess characters are counted.
5208 CRC ERRORS
Contains a count of the messages with a CRC error that the drive receives. For high counts, check:
Ambient electro-magnetic noise levels high noise levels generate errors.
CRC calculations for possible errors.

Parameters

184

ACS550-01/U1 Users Manual

Group 53: EFB PROTOCOL


This group defines set-up variables used for an embedded fieldbus (EFB)
communication protocol. The standard EFB protocol in the ACS550 is Modbus. See
chapter Embedded fieldbus page 203.
Code Description
5301 EFB PROTOCOL ID
Contains the identification and program revision of the protocol.
Format: XXYY, where xx = protocol ID, and YY = program revision.
5302 EFB STATION ID
Defines the node address of the RS485 link.
The node address on each unit must be unique.
5303 EFB BAUD RATE
Defines the communication speed of the RS485 link in kbits per second (kb/s).
1.2 kb/s
2.4 kb/s
4.8 kb/s
9.6 kb/s
19.2 kb/s
38.4 kb/s
57.6 kb/s
76.8 kb/s
5304 EFB PARITY
Defines the data length, parity and stop bits to be used with the RS485 link communication.
The same settings must be used in all on-line stations.
0 = 8 NONE 1 8 data bits, no parity, one stop bit.
1 = 8 NONE 2 8 data bits, no parity, two stop bits.
2 = 8 EVEN 1 8 data bits, even parity, one stop bit.
3 = 8 ODD 1 8 data bits, odd parity, one stop bit.
5305 EFB CTRL PROFILE
Selects the communication profile used by the EFB protocol.
0 = ABB DRV LIM Operation of Control/Status Words conforms to ABB Drives Profile, as used in ACS400.
1 = DCU PROFILE Operation of Control/Status Words conforms to 32-bit DCU Profile.
2 = ABB DRV FULL Operation of Control/Status Words conforms to ABB Drives Profile, as used in ACS600/800.
5306 EFB OK MESSAGES
Contains a count of valid messages received by the drive.
During normal operation, this counter is increasing constantly.
5307 EFB CRC ERRORS
Contains a count of the messages with a CRC error received by the drive. For high counts, check:
Ambient electro-magnetic noise levels high noise levels generate errors.
CRC calculations for possible errors.
5308 EFB UART ERRORS
Contains a count of the messages with a character error received by the drive.
5309 EFB STATUS
Contains the status of the EFB protocol.
0 = IDLE EFB protocol is configured, but not receiving any messages.
1 = EXECUT INIT EFB protocol is initializing.
2 = TIME OUT A timeout has occurred in the communication between the network master and the EFB protocol.
3 = CONFIG ERROR EFB protocol has a configuration error.
4 = OFF-LINE EFB protocol is receiving messages that are NOT addressed to this drive.
5 = ON-LINE EFB protocol is receiving messages that are addressed to this drive.
6 = RESET EFB protocol is performing a hardware reset.
7 = LISTEN ONLY EFB protocol is in listen-only mode.
5310 EFB PAR 10
Specifies the parameter mapped to Modbus Register 40005.

Parameters

ACS550-01/U1 Users Manual

185

Code Description
5311 EFB PAR 11
Specifies the parameter mapped to Modbus Register 40006.
5312 EFB PAR 12
Specifies the parameter mapped to Modbus Register 40007.
5313 EFB PAR 13
Specifies the parameter mapped to Modbus Register 40008.
5314 EFB PAR 14
Specifies the parameter mapped to Modbus Register 40009.
5315 EFB PAR 15
Specifies the parameter mapped to Modbus Register 40010.
5316 EFB PAR 16
Specifies the parameter mapped to Modbus Register 40011.
5317 EFB PAR 17
Specifies the parameter mapped to Modbus Register 40012.
5318 EFB PAR 18
For Modbus: Sets additional delay in milliseconds before the ACS550 begins transmitting response to the master
request.
5319 EFB PAR 19
ABB Drives profile (ABB DRV LIM or ABB DRV FULL) Control Word. Read only copy of the Fieldbus Control Word.
5320 EFB PAR 20
ABB Drives profile (ABB DRV LIM or ABB DRV FULL) Status Word. Read only copy of the Fieldbus Status Word.

Parameters

186

ACS550-01/U1 Users Manual

Group 64: LOAD ANALYZER


This group defines the load analyzer, which can be used for analyzing the
customers process and sizing the drive and the motor.
The peak value is logged at 2 ms level, and the distribution loggers are updated on
0.2 s (200 ms) time level. Three different values can be logged.
1. Amplitude logger 1: The measured current is logged continuously. The
distribution as a percentage of the nominal current I2N is shown in ten classes.
2. Peak value logger: One signal in group 1 can be logged for the peak (maximum)
value. The peak value of the signal, peak time (time when the peak value was
detected) as well the frequency, current and DC voltage at the peak time are shown.
3. Amplitude logger 2: One signal in group 1 can be logged for amplitude
distribution. The base value (100% value) can be set by the user.
The first logger cannot be reset. The other two loggers can be reset by a userdefined method. They are also reset if either of the signals or the peak value filter
time is changed.
Code Description
6401 PVL SIGNAL
Defines (by number) the signal logged for the peak value.
Any parameter number in Group 01: OPERATING DATA can be selected. Eg 102 = parameter 0102 SPEED.
100 = NOT SELECTED No signal (parameter) logged for the peak value.
101178 Logs parameter 01010178.
6402 PVL FILTER TIME
Defines the filter time for peak value logging.
0.0120.0 Filter time (seconds).
6403 LOGGERS RESET
Defines the source for the reset of peak value logger and amplitude logger 2.
0 = NOT SEL No reset selected.
1 = DI1 Reset loggers on the rising edge of digital input DI1.
26 = DI2DI6 Reset loggers on the rising edge of digital input DI2DI6.
7 = RESET Reset loggers. Parameter is set to NOT SEL.
-1 = DI1(INV) Reset loggers on the falling edge of digital input DI1.
-2-6 = DI2(INV) DI6(INV) Reset loggers on the falling edge of digital input DI2DI6.
6404 AL2 SIGNAL
Defines the signal logged for amplitude logger 2.
Any parameter number in Group 01: OPERATING DATA can be selected. Eg 102 = parameter 0102 SPEED.
100 = NOT SELECTED No signal (parameter) logged for amplitude distribution (amplitude logger 2).
101178 Logs parameter 01010178.
6405 AL2 SIGNAL BASE
Defines the base value from which the percentage distribution is calculated.
Representation and default value depends on the signal selected with parameter 6404 AL2 SIGNAL.
6406 PEAK VALUE
Detected peak value of the signal selected with parameter 6401 PVL SIGNAL.
6407 PEAK TIME 1
Date of the peak value detection.
Format: Date if the real time clock is operating (dd.mm.yy). / The number of days elapsed after the power-on if the
real time clock is not used, or was not set (xx d).
6408 PEAK TIME 2
Time of the peak value detection.
Format: hours:minutes:seconds.

Parameters

ACS550-01/U1 Users Manual

187

Code Description
6409 CURRENT AT PEAK
Current at the moment of the peak value (amperes).
6410 UDC AT PEAK
DC voltage at the moment of the peak value (volts).
6411 FREQ AT PEAK
Output frequency at the moment of the peak value (herzes).
6412 TIME OF RESET 1
Last reset date of the peak logger and amplitude logger 2.
Format: Date if the real time clock is operating (dd.mm.yy). / The number of days elapsed after the power-on if the
real time clock is not used, or was not set (xx d).
6413 TIME OF RESET 2
Last reset time of the peak logger and amplitude logger 2.
Format: hours:minutes:seconds.
6414 AL1RANGE0TO10
Amplitude logger 1 (current in percent of nominal current I2N) 010% distribution.
6415 AL1RANGE10TO20
Amplitude logger 1 (current in percent of nominal current I2N) 1020% distribution.
6416 AL1RANGE20TO30
Amplitude logger 1 (current in percent of nominal current I2N) 2030% distribution.
6417 AL1RANGE30TO40
Amplitude logger 1 (current in percent of nominal current I2N) 3040% distribution.
6418 AL1RANGE40TO50
Amplitude logger 1 (current in percent of nominal current I2N) 4050% distribution.
6419 AL1RANGE50TO60
Amplitude logger 1 (current in percent of nominal current I2N) 5060% distribution.
6420 AL1RANGE60TO70
Amplitude logger 1 (current in percent of nominal current I2N) 6070% distribution.
6421 AL1RANGE70TO80
Amplitude logger 1 (current in percent of nominal current I2N) 7080% distribution.
6422 AL1RANGE80TO90
Amplitude logger 1 (current in percent of nominal current I2N) 8090% distribution.
6423 AL1RANGE90TO
Amplitude logger 1 (current in percent of nominal current I2N) over 90% distribution.
6424 AL2RANGE0TO10
Amplitude logger 2 (signal selection with parameter 6404) 010% distribution.
6425 AL2RANGE10TO20
Amplitude logger 2 (signal selection with parameter 6404) 1020% distribution.
6426 AL2RANGE20TO30
Amplitude logger 2 (signal selection with parameter 6404) 2030% distribution.
6427 AL2RANGE30TO40
Amplitude logger 2 (signal selection with parameter 6404) 3040% distribution.
6428 AL2RANGE40TO50
Amplitude logger 2 (signal selection with parameter 6404) 4050% distribution.
6429 AL2RANGE50TO60
Amplitude logger 2 (signal selection with parameter 6404) 5060% distribution.
6430 AL2RANGE60TO70
Amplitude logger 2 (signal selection with parameter 6404) 6070% distribution.
6431 AL2RANGE70TO80
Amplitude logger 2 (signal selection with parameter 6404) 7080% distribution.

Parameters

188
Code Description
6432 AL2RANGE80TO90
Amplitude logger 2 (signal selection with parameter 6404) 8090% distribution.
6433 AL2RANGE90TO
Amplitude logger 2 (signal selection with parameter 6404) over 90% distribution.

Parameters

ACS550-01/U1 Users Manual

ACS550-01/U1 Users Manual

189

Group 81: PFC CONTROL


This group defines a Pump-Fan Control (PFC) mode of operation. The major
features of PFC control are:
The ACS550 controls the motor of pump no. 1, varying the motor speed to control
the pump capacity. This motor is the speed regulated motor.
Direct line connections power the motor of pump no. 2 and pump no.3, etc. The
ACS550 switches pump no. 2 (and then pump no. 3, etc.) on and off as needed.
These motors are auxiliary motors.
The ACS550 PID control uses two signals: a process reference and an actual
value feedback. The PID controller adjusts the speed (frequency) of the first
pump such that the actual value follows the process reference.
When demand (defined by the process reference) exceeds the first motors
capacity (user defined as a frequency limit), the PFC control automatically starts
an auxiliary pump. The PFC also reduces the speed of the first pump to account
for the auxiliary pumps addition to total output. Then, as before, the PID controller
adjusts the speed (frequency) of the first pump such that the actual value follows
the process reference. If demand continues to increase, PFC adds additional
auxiliary pumps, using the same process.
When demand drops, such that the first pump speed falls below a minimum limit
(user defined by a frequency limit), the PFC control automatically stops an
auxiliary pump. The PFC also increases the speed of the first pump to account for
the auxiliary pumps missing output.
An Interlock function (when enabled) identifies off-line (out of service) motors, and
the PFC control skips to the next available motor in the sequence.
An Autochange function (when enabled and with the appropriate switchgear)
equalizes duty time between the pump motors. Autochange periodically
increments the position of each motor in the rotation the speed regulated motor
becomes the last auxiliary motor, the first auxiliary motor becomes the speed
regulated motor, etc.
Code Description
8103 REFERENCE STEP 1
Sets a percentage value that is added to the process reference.
Applies only when at least one auxiliary (constant speed) motor is running.
Default value is 0%.
Example: An ACS550 operates three parallel pumps that maintain water pressure in a pipe.
4011 INTERNAL SETPNT sets a constant pressure reference that controls the pressure in the pipe.
The speed regulated pump operates alone at low water consumption levels.
As water consumption increases, first one constant speed pump operates, then, the second.
As flow increases, the pressure at the output end of the pipe drops relative to the pressure measured at the input
end. As auxiliary motors step in to increase the flow, the adjustments below correct the reference to more closely
match the output pressure.
When the first auxiliary pump operates, increase the reference with parameter 8103 REFERENCE STEP 1.
When two auxiliary pumps operate, increase the reference with parameter 8103 REFERENCE STEP 1 + parameter
8104 REFERENCE STEP 2.
When three auxiliary pumps operate, increase the reference with parameter 8103 REFERENCE STEP 1 + parameter
8104 REFERENCE STEP 2 + parameter 8105 REFERENCE STEP 3.

Parameters

190

ACS550-01/U1 Users Manual

Code Description
8104 REFERENCE STEP 2
Sets a percentage value that is added to the process reference.
Applies only when at least two auxiliary (constant speed) motors are running.
See parameter 8103 REFERENCE STEP 1.
8105 REFERENCE STEP 3
Sets a percentage value that is added to the process reference.
Applies only when at least three auxiliary (constant speed) motors are running.
See parameter 8103 REFERENCE STEP 1.
8109 START FREQ 1
Sets the frequency limit used to start the first auxiliary motor. The first auxiliary motor starts if:
No auxiliary motors are running.
f (Hz)
ACS550 output frequency exceeds the limit:
P 8115
8109 + 1 Hz.
Output frequency stays above a relaxed limit
fMAX
(8109 - 1 Hz) for at least the time: 8115 AUX MOT START D.
(P 8109)+1
After the first auxiliary motor starts:
P 8109
Output frequency decreases by the value =
A
(8109 START FREQ 1) - (8112 LOW FREQ 1).
P 8112
In effect, the output of the speed regulated motor drops to
fMIN
compensate for the input from the auxiliary motor.
See the figure, where:
A = (8109 START FREQ 1) - (8112 LOW FREQ 1)
B = Output frequency increase during the start delay.
C
C = Diagram showing auxiliary motors run status as frequency
1
increases (1 = On).
0
Note: 8109 START FREQ 1 value must be between:
8112 LOW FREQ 1
(2008 MAXIMUM FREQ) -1.

B A

8110 START FREQ 2


Sets the frequency limit used to start the second auxiliary motor.
See 8109 START FREQ 1 for a complete description of the operation.
The second auxiliary motor starts if:
One auxiliary motor is running.
ACS550 output frequency exceeds the limit: 8110 + 1.
Output frequency stays above the relaxed limit (8110 - 1 Hz) for at least the time: 8115 AUX MOT START D.
8111 START FREQ 3
Sets the frequency limit used to start the third auxiliary motor.
See 8109 START FREQ 1 for a complete description of the operation.
The third auxiliary motor starts if:
Two auxiliary motors are running.
ACS550 output frequency exceeds the limit: 8111 + 1 Hz.
Output frequency stays above the relaxed limit (8111 - 1 Hz) for at least the time: 8115 AUX MOT START D.

Parameters

ACS550-01/U1 Users Manual

191

Code Description
8112 LOW FREQ 1
Sets the frequency limit used to stop the first auxiliary motor. The first auxiliary motor stops if:
Only one (the first) auxiliary motor is running.
f (Hz)
ACS550 output frequency drops below the limit:
8112 - 1.
Output frequency stays below the relaxed limit
P 8109
(8112 + 1 Hz) for at least the time: 8116 AUX MOT STOP D.
fMAX
After the first auxiliary motor stops:
A
Output frequency increases by the value =
P 8112
(8109 START FREQ 1) - (8112 LOW FREQ 1).
(P 8112)-1
In effect, the output of the speed regulated motor increases to
fMIN
compensate for the loss of the auxiliary motor.
See the figure, where:
P 8116
A = (8109 START FREQ 1) - (8112 LOW FREQ 1)
B = Output frequency decrease during the stop delay.
C = Diagram showing auxiliary motors run status as frequency
C
decreases (1 = On).
1
Grey path = Shows hysteresis if time is reversed, the path
backwards is not the same. For details on the path for starting,
0
see the diagram at 8109 START FREQ 1.
Note: 8112 LOW FREQ 1 value must be between:
(2007 MINIMUM FREQ) +1.
8109 START FREQ 1

A
t

8113 LOW FREQ 2


Sets the frequency limit used to stop the second auxiliary motor.
See 8112 LOW FREQ 1 for a complete description of the operation.
The second auxiliary motor stops if:
Two auxiliary motors are running.
ACS550 output frequency drops below the limit: 8113 - 1.
Output frequency stays below the relaxed limit (8113 + 1 Hz) for at least the time: 8116 AUX MOT STOP D.
8114 LOW FREQ 3
Sets the frequency limit used to stop the third auxiliary motor.
See 8112 LOW FREQ 1 for a complete description of the operation.
The third auxiliary motor stops if:
Three auxiliary motors are running.
ACS550 output frequency drops below the limit: 8114 - 1.
Output frequency stays below the relaxed limit (8114 + 1 Hz) for at least the time: 8116 AUX MOT STOP D.
8115 AUX MOT START D
Sets the Start Delay for the auxiliary motors.
The output frequency must remain above the start frequency limit (parameter 8109, 8110, or 8111) for this time
period before the auxiliary motor starts.
See 8109 START FREQ 1 for a complete description of the operation.
8116 AUX MOT STOP D
Sets the Stop Delay for the auxiliary motors.
The output frequency must remain below the low frequency limit (parameter 8112, 8113, or 8114) for this time
period before the auxiliary motor stops.
See 8112 LOW FREQ 1 for a complete description of the operation.

Parameters

192

ACS550-01/U1 Users Manual

Code Description
8117 NR OF AUX MOT
Sets the number of auxiliary motors.
Each auxiliary motor requires a relay output, which the drive uses to send start/stop signals.
The Autochange function, if used, requires an additional relay output for the speed regulated motor.
The following describes the set-up of the required relay outputs.
Relay outputs
As noted above, each auxiliary motor requires a relay output, which the drive uses to send start/stop signals. The
following describes how the drive keeps track of motors and relays.
The ACS550 provides relay outputs RO1RO3.
An external digital output module (OREL-01) can be added to provide relay outputs RO4RO6.
Parameters 14011403 and 14101412 define, respectively, how relays RO1RO6 are used the parameter
value 31 PFC defines the relay as used for PFC.
The ACS550 assigns auxiliary motors to relays in ascending order. If the Autochange function is disabled, the first
auxiliary motor is the one connected to the first relay with a parameter setting = 31 PFC, and so on. If the
Autochange function is used, the assignments rotate. Initially, the speed regulated motor is the one connected to
the first relay with a parameter setting = 31 PFC, the first auxiliary motor is the one connected to the second relay
with a parameter setting = 31 PFC, and so on.
Relay logic
ACS550
ACS550

Standard PFC mode


PFC with Autochange mode
The fourth auxiliary motor uses the same reference step, low frequency and start frequency values as the third
auxiliary motor.

Parameters

ACS550-01/U1 Users Manual

193

Code Description
The table below shows the ACS550 PFC motor assignments for some typical settings in the Relay Output
parameters (14011403 and 14101412), where the settings are either =31 (PFC), or =X (anything but 31), and
where the Autochange function is disabled (8118 AUTOCHNG INTERV = 0.0).
Parameter setting
ACS550 Relay assignment
1 1 1 1 1 1 8
Autochange disabled
4 4 4 4 4 4 1
RO1
RO2
RO3
RO4
RO5
RO6
0 0 0 1 1 1 1
1 2 3 0 1 2 7
31 X X X X X 1
Aux.
X
X
X
X
X
31 31 X X X X 2
Aux.
Aux.
X
X
X
X
31 31 31 X X X 3
Aux.
Aux.
Aux.
X
X
X
X 31 31 X X X 2
X
Aux.
Aux.
X
X
X
X X X 31 X 31 2
X
X
X
Aux.
X
Aux.
31 31 X X X X 1* Aux.
Aux.
X
X
X
X
* = One additional relay output for the PFC that is in use. One motor is in sleep
when the other is rotating.
The table below shows the ACS550 PFC motor assignments for some typical settings in the Relay Output
parameters (14011403 and 14101412), where the settings are either =31 (PFC), or =X (anything but 31), and
where the Autochange function is enabled (8118 AUTOCHNG INTERV = value > 0.0).
Parameter setting
ACS550 Relay assignment
1 1 1 1 1 1 8
Autochange enabled
4 4 4 4 4 4 1
RO1
RO2
RO3
RO4
RO5
RO6
0 0 0 1 1 1 1
1 2 3 0 1 2 7
31 31 X X X X 1
PFC
PFC
X
X
X
X
31 31 31 X X X 2
PFC
PFC
PFC
X
X
X
X 31 31 X X X 1
X
PFC
PFC
X
X
X
X X X 31 X 31 1
X
X
X
PFC
X
PFC
31 31 X X X X 0** PFC
PFC
X
X
X
X
** = No auxiliary motors, but the autochange function is in use. Working as a
standard PID-control.
8118 AUTOCHNG INTERV
Controls operation of the Autochange function and sets the
interval between changes.
The Autochange time interval only applies to the time when
the speed regulated motor is running.
See parameter 8119 AUTOCHNG LEVEL for an overview of the
Autochange function.
The drive always coasts to stop when autochange is
performed.
Autochange enabled requires parameter 8120 INTERLOCKS =
value > 0.
-0.1 = TEST MODE Forces the interval to value 3648 s.
0.0 = NOT SEL Disables the Autochange function.
0.1336 The operating time interval (the time when the start
signal is on) between automatic motor changes.
WARNING! When enabled, the Autochange function
requires the interlocks (8120 INTERLOCKS = value > 0)
enabled. During autochange the power output is
interrupted and the drive coasts to stop, preventing
damage to the contacts.

Relay logic
ACS550

PFC with Autochange mode

Parameters

194

ACS550-01/U1 Users Manual

Code Description
8119 AUTOCHNG LEVEL
Sets an upper limit, as a percent of output capacity, for the autochange logic. When the output from the PID/PFC
control block exceeds this limit, autochange is prevented. For example, use this parameter to deny autochange when
the Pump-Fan system is operating near maximum capacity.
Autochange overview
The purpose of the autochange operation is to equalize duty time between multiple motors used in a system. At each
autochange operation:
A different motor takes a turn connected to the ACS550 output the speed regulated motor.
The starting order of the other motors rotates.
The Autochange function requires:
External switchgear for changing the drives output power connections.
Parameter 8120 INTERLOCKS = value > 0.
Autochange is performed when:
The running time since the previous autochange reaches the time set by 8118 AUTOCHNG INTERV.
The PFC input is below the level set by this parameter, 8119 AUTOCHNG LEVEL.
Note: The ACS550 always coasts to stop when autochange is performed.
In an autochange, the Autochange function does all of the
PID output
A
following (see the figure):
4PFC
Initiates a change when the running time, since the last
100%
autochange, reaches 8118 AUTOCHNG INTERV, and PFC
2PFC
input is below limit 8119 AUTOCHNG LEVEL.
P
8119
Stops the speed regulated motor.
3PFC
Switches off the contactor of the speed regulated motor.
3PFC
Increments the starting order counter, to change the
4PFC
starting order for the motors.
2PFC
Identifies the next motor in line to be the speed regulated
t
1PFC
motor.
Switches off the above motors contactor, if the motor was
P 8122
running. Any other running motors are not interrupted.
P 8118
P 8118
Switches on the contactor of the new speed regulated
B
motor. The autochange switchgear connects this motor to
A = Area above 8119 AUTOCHNG LEVEL
the ACS550 power output.
autochange not allowed.
Delays motor start for the time 8122 PFC START DELAY.
B = Autochange occurs.
Starts the speed regulated motor.
1PFC, etc. = PID output associated with each motor.
Identifies the next constant speed motor in the rotation.
Switches the above motor on, but only if the new speed
regulated motor had been running (as a constant speed
motor) This step keeps an equal number of motors running before and after autochange.
Continues with normal PFC operation.
Output
Starting order counter
frequency
The operation of the starting-order counter:
2 aux
No aux
1 aux
motors
motors
motor
The relay output parameter definitions (14011403 and
fMAX
14101412) establish the initial motor sequence. (The lowest
parameter number with a value 31 (PFC) identifies the relay
connected to 1PFC, the first motor, and so on.)
Initially, 1PFC = speed regulated motor, 2PFC = 1st auxiliary
motor, etc.
The first autochange shifts the sequence to: 2PFC = speed
regulated motor, 3PFC = 1st auxiliary motor, , 1PFC = last
Area
auxiliary motor.
Autochange
The next autochange shifts the sequence again, and so on.
is allowed
PID output
If the autochange cannot start a needed motor because all
inactive motors are interlocked, the drive displays an alarm
100%
P 8119
(2015, PFC I LOCK).
When ACS550 power supply is switched off, the counter
preserves the current Autochange rotation positions in permanent memory. When power is restored, the
Autochange rotation starts at the position stored in memory.
If the PFC relay configuration is changed (or if the PFC enable value is changed), the rotation is reset. (See the first
bullet above.)

Parameters

ACS550-01/U1 Users Manual

195

Code Description
8120 INTERLOCKS
Defines operation of the Interlock function. When the Interlock function is enabled:
An interlock is active when its command signal is absent.
An interlock is inactive when its command signal is present.
The ACS550 will not start if a start command occurs when the speed regulated motors interlock is active the
control panel displays an alarm (2015, PFC I LOCK).
Wire each Interlock circuit as follows:
Wire a contact of the motors On/Off switch to the Interlock circuit the drives PFC logic can then recognize that
the motor is switched off and start the next available motor.
Wire a contact of the motor thermal relay (or other protective device in the motor circuit) to the Interlock input the
drives PFC logic can then recognize that a motor fault is activated and stop the motor.
0 = NOT SEL Disables the Interlock function. All digital inputs are available for other purposes.
Requires 8118 AUTOCHNG INTERV = 0.0 (The Autochange function must be disabled if Interlock function is
disabled.)
1 = DI1 Enables the Interlock function and assigns a digital input (starting with DI1) to the interlock signal for each
PFC relay. These assignments are defined in the following table and depend on:
the number of PFC relays [number of parameters 14011403 and 14101412 with value = 31 (PFC)]
the Autochange function status (disabled if 8118 AUTOCHNG INTERV = 0.0, and otherwise enabled).
No. PFC
Autochange disabled
relays
(P 8118)
0
DI1: Speed Reg Motor
DI2DI6: Free
DI1: Speed Reg Motor
1
DI2: First PFC Relay
DI3DI6: Free
2
DI1: Speed Reg Motor
DI2: First PFC Relay
DI3: Second PFC Relay
DI4DI6: Free
3
DI1: Speed Reg Motor
DI2: First PFC Relay
DI3: Second PFC Relay
DI4: Third PFC Relay
DI5DI6: Free
4
DI1: Speed Reg Motor
DI2: First PFC Relay
DI3: Second PFC Relay
DI4: Third PFC Relay
DI5: Fourth PFC Relay
DI6: Free
5
DI1: Speed Reg Motor
DI2: First PFC Relay
DI3: Second PFC Relay
DI4: Third PFC Relay
DI5: Fourth PFC Relay
DI6: Fifth PFC Relay
6
Not allowed

Autochange enabled
(P 8118)
Not allowed
DI1: First PFC Relay
DI2DI6: Free
DI1: First PFC Relay
DI2: Second PFC Relay
DI3DI6: Free
DI1: First PFC Relay
DI2: Second PFC Relay
DI3: Third PFC Relay
DI4DI6: Free
DI1: First PFC Relay
DI2: Second PFC Relay
DI3: Third PFC Relay
DI4: Fourth PFC Relay
DI5DI6: Free
DI1:
DI2:
DI3:
DI4:
DI5:
DI6:

First PFC Relay


Second PFC Relay
Third PFC Relay
Fourth PFC Relay
Fifth PFC Relay
Free
DI1: First PFC Relay
DI2: Second PFC Relay
DI3: Third PFC Relay
DI4: Fourth PFC Relay
DI5: Fifth PFC Relay
DI6: Sixth PFC Relay

Parameters

196

ACS550-01/U1 Users Manual

Code Description
2 = DI2 Enables the Interlock function and assigns a digital input (starting with DI2) to the interlock signal for each
PFC relay. These assignments are defined in the following table and depend on:
the number of PFC relays [number of parameters 14011403 and 14101412 with value = 31 (PFC)]
the Autochange function status (disabled if 8118 AUTOCHNG INTERV = 0.0, and otherwise enabled).
No. PFC
Autochange disabled
relays
(P 8118)
0
DI1: Free
DI2: Speed Reg Motor
DI3 DI6: Free
DI1: Free
1
DI2: Speed Reg Motor
DI3: First PFC Relay
DI4 DI6: Free
2
DI1: Free
DI2: Speed Reg Motor
DI3: First PFC Relay
DI4: Second PFC Relay
DI5 DI6: Free
3
DI1: Free
DI2: Speed Reg Motor
DI3: First PFC Relay
DI4: Second PFC Relay
DI5: Third PFC Relay
DI6: Free
4
DI1: Free
DI2: Speed Reg Motor
DI3: First PFC Relay
DI4: Second PFC Relay
DI5: Third PFC Relay
DI6: Fourth PFC Relay
5
Not allowed

Parameters

Not allowed

Autochange enabled
(P 8118)
Not allowed
DI1: Free
DI2: First PFC Relay
DI3 DI6: Free
DI1: Free
DI2: First PFC Relay
DI3: Second PFC Relay
DI4 DI6: Free
DI1: Free
DI2: First PFC Relay
DI3: Second PFC Relay
DI4: Third PFC Relay
DI5 DI6: Free
DI1:
DI2:
DI3:
DI4:
DI5:
DI6:

Free
First PFC Relay
Second PFC Relay
Third PFC Relay
Fourth PFC Relay
Free
DI1: Free
DI2: First PFC Relay
DI3: Second PFC Relay
DI4: Third PFC Relay
DI5: Fourth PFC Relay
DI6: Fifth PFC Relay
Not allowed

ACS550-01/U1 Users Manual

197

Code Description
3 = DI3 Enables the Interlocks function and assigns a digital input (starting with DI3) to the interlock signal for each
PFC relay. These assignments are defined in the following table and depend on:
the number of PFC relays [number of parameters 14011403 and 14101412 with value = 31 (PFC)]
the Autochange function status (disabled if 8118 AUTOCHNG INTERV = 0.0, and otherwise enabled).
No. PFC
Autochange disabled
relays
(P 8118)
0
DI1DI2: Free
DI3: Speed Reg Motor
DI4DI6: Free
DI1DI2: Free
1
DI3: Speed Reg Motor
DI4: First PFC Relay
DI5DI6: Free
2
DI1DI2: Free
DI3: Speed Reg Motor
DI4: First PFC Relay
DI5: Second PFC Relay
DI6: Free
3
DI1DI2: Free
DI3: Speed Reg Motor
DI4: First PFC Relay
DI5: Second PFC Relay
DI6: Third PFC Relay
4
Not allowed

56

Not allowed

Autochange enabled
(P 8118)
Not allowed
DI1DI2: Free
DI3: First PFC Relay
DI4DI6: Free
DI1DI2: Free
DI3: First PFC Relay
DI4: Second PFC Relay
DI5DI6: Free
DI1DI2: Free
DI3: First PFC Relay
DI4: Second PFC Relay
DI5: Third PFC Relay
DI6: Free
DI1DI2: Free
DI3: First PFC Relay
DI4: Second PFC Relay
DI5: Third PFC Relay
DI6: Fourth PFC Relay

Not allowed

4 = DI4 Enables the Interlock function and assigns a digital input (starting with DI4) to the interlock signal for each
PFC relay. These assignments are defined in the following table and depend on:
the number of PFC relays [number of parameters 14011403 and 14101412 with value = 31 (PFC)]
the Autochange function status (disabled if 8118 AUTOCHNG INTERV = 0.0, and otherwise enabled).
No. PFC
Autochange disabled
relays
(P 8118)
DI1 DI3: Free
0
DI4: Speed Reg Motor
DI5 DI6: Free
DI1 DI3: Free
1
DI4: Speed Reg Motor
DI5: First PFC Relay
DI6: Free
2
DI1 DI3: Free
DI4: Speed Reg Motor
DI5: First PFC Relay
DI6: Second PFC Relay
3
Not allowed

46

Not allowed

Autochange enabled
(P 8118)
Not allowed
DI1 DI3: Free
DI4: First PFC Relay
DI5 DI6: Free
DI1 DI3: Free
DI4: First PFC Relay
DI5: Second PFC Relay
DI6: Free
DI1 DI3: Free
DI4: First PFC Relay
DI5: Second PFC Relay
DI6: Third PFC Relay

Not allowed

Parameters

198

ACS550-01/U1 Users Manual

Code Description
5 = DI5 Enables the Interlock function and assigns a digital input (starting with DI5) to the interlock signal for each
PFC relay. These assignments are defined in the following table and depend on:
the number of PFC relays [number of parameters 14011403 and 14101412 with value = 31 (PFC)]
the Autochange function status (disabled if 8118 AUTOCHNG INTERV = 0.0, and otherwise enabled).
No. PFC
Autochange disabled
relays
(P 8118)
0
DI1DI4: Free
DI5: Speed Reg Motor
DI6: Free
DI1DI4: Free
1
DI5: Speed Reg Motor
DI6: First PFC Relay
2
Not allowed
36

Not allowed

Autochange enabled
(P 8118)
Not allowed
DI1 DI4: Free
DI5: First PFC Relay
DI6: Free
DI1 DI4: Free
DI5: First PFC Relay
DI6: Second PFC Relay

Not allowed

6 = DI6 Enables the Interlock function and assigns digital input DI6 to the interlock signal for the speed regulated
motor.
Requires 8118 AUTOCHNG INTERV = 0.0.
No. PFC
Autochange disabled
relays
0
DI1 DI5: Free
DI6: Speed Reg Motor
1
Not allowed
26

Parameters

Not allowed

Autochange enabled
Not allowed
DI1DI5: Free
DI6: First PFC Relay

Not allowed

ACS550-01/U1 Users Manual

199

Code Description
8121 REG BYPASS CTRL
Selects Regulator by-pass control. When enabled, Regulator by-pass control provides a simple control mechanism
without a PID regulator.
Use Regulator by-pass control only in special
fOUT
applications.
0 = NO Disables Regulator by-pass control. The drive
fMAX
uses the normal PFC reference: 1106 REF2 SELECT.
1 = YES Enables Regulator by-pass control.
The process PID regulator is bypassed.
Actual value of PID is used as the PFC reference
P 8110
(input). Normally EXT REF2 is used as the PFC
P 8109
reference.
The drive uses the feedback signal defined by 4014
FBK SEL (or 4114) for the PFC frequency reference.
P 8113
The figure shows the relation between the control
signal 4014 FBK SEL (OR 4114) and the speed
P 8112
regulated motors frequency in a three-motor
fMIN
system.
Example: In the diagram below, the pumping stations
P 4014
outlet flow is controlled by the measured inlet flow (A).
(%)
C
A
B

Mains 3~

3
3

3
ACS550 P1
P2
P3
A

A = No auxiliary motors running


B = One auxiliary motor running
C = Two auxiliary motors running

Contactors
3
3

3
P1

Sewage
tank

M
3~
Outlet pipe1

M
3~
P2

Inlet pipe

Outlet pipe2

M
3~
P3

Outlet pipe3

8122 PFC START DELAY


Sets the start delay for speed regulated motors in the system. Using the delay, the drive works as follows:
Switches on the contactor of the speed regulated motor connecting the motor to the ACS550 power output.
Delays motor start for the time 8122 PFC START DELAY.
Starts the speed regulated motor.
Starts auxiliary motors. See parameter 8115 for delay.
WARNING! Motors equipped with star-delta starters require a PFC Start Delay.
After the ACS550 relay output switches a motor on, the star-delta starter must switch to the star-connection and
then back to the delta-connection before the drive applies power.
So, the PFC Start Delay must be longer than the time setting of the star-delta starter.
8123 PFC ENABLE
Selects PFC control. When enabled, PFC control:
Switches in, or out, auxiliary constant speed motors as output demand increases or decreases. Parameters 8109
START FREQ 1 to 8114 LOW FREQ 3 define the switch points in terms of the drive output frequency.
Adjusts the speed regulated motor output down, as auxiliary motors are added, and adjusts the speed regulated
motor output up, as auxiliary motors are taken off line.
Provides Interlock functions, if enabled.
Requires 9904 MOTOR CTRL MODE = 3 (SCALAR:FREQ).
0 = NOT SEL Disables PFC control.
1 = ACTIVE Enables PFC control.

Parameters

200

ACS550-01/U1 Users Manual

Code Description
8124 ACC IN AUX STOP
Sets the PFC acceleration time for a zero-to-maximum
frequency ramp. This PFC acceleration ramp:
Applies to the speed regulated motor, when an auxiliary
motor is switched off.
Replaces the acceleration ramp defined in Group 22:
ACCEL/DECEL.
Applies only until the output of the regulated motor
increases by an amount equal to the output of the
switched off auxiliary motor. Then the acceleration ramp
defined in Group 22: ACCEL/DECEL applies.
0 = NOT SEL.
0.11800 Activates this function using the value
entered as the acceleration time.
8125 DEC IN AUX START
Sets the PFC deceleration time for a maximum-to-zero
frequency ramp. This PFC deceleration ramp:
Applies to the speed regulated motor, when an auxiliary
motor is switched on.
Replaces the deceleration ramp defined in Group 22:
ACCEL/DECEL.
Applies only until the output of the regulated motor
decreases by an amount equal to the output of the
auxiliary motor. Then the deceleration ramp defined in
Group 22: ACCEL/DECEL applies.
0 = NOT SEL.
0.11800 Activates this function using the value
entered as the deceleration time.

fOUT
A

P 8125

P 8124

Aux.
motor
1

t
0
A = speed regulated motor accelerating using Group 22:
ACCEL/DECEL parameters (2202 or 2205).
B = speed regulated motor decelerating using Group
22: ACCEL/DECEL parameters (2203 or 2206).
At aux. motor start, speed regulated motor decelerates
using 8125 DEC IN AUX START.
At aux. motor stop, speed regulated motor accelerates
using 8124 ACC IN AUX STOP.

8126 TIMED AUTOCHNG


Sets the autochange using a Timed function. See parameter 8119 AUTOCHNG LEVEL.
0 = NOT SEL.
1 = TIMED FUNC 1 Enables autochange when Timed function 1 is active.
24 = TIMED FUNC 24 Enables autochange when Timed function 24 is active.
8127 MOTORS
Sets the actual number of PFC controlled motors (maximum 7 motors, 1 speed regulated, 3 connected direct-on-line
and 3 spare motors).
This value includes also the speed regulated motor.
This value must be compatible with the number of relays allocated to PFC if the Autochange function is used.
If Autochange function is not used, the speed regulated motor does not need to have a relay output allocated to
PFC but it needs to be included in this value.
8128 AUX START ORDER
Sets the start order of the auxiliary motors.
1 = EVEN RUNTIME Time sharing is active. Evens out the cumulative run time of the auxiliary motors. The start order
depends on the run time: The auxiliary motor whose cumulative run time is shortest is started first, then the motor
whose cumulative run time is the second shortest etc. When the demand drops, the first motor to be stopped is the
one whose cumulative run time is longest.
2 = RELAY ORDER The start order is fixed to be the order of the relays.

Parameters

ACS550-01/U1 Users Manual

201

Group 98: OPTIONS


This group configures for options, in particular, enabling serial communication with
the drive.
Code Description
9802

COMM PROT SEL


Selects the communication protocol.
0 = NOT SEL No communication protocol selected.
1 = STD MODBUS The drive communicates with Modbus via the RS485 channel (X1-communications, terminal).
See also Group 53: EFB PROTOCOL.
4 = EXT FBA The drive communicates via a fieldbus adapter module in option slot 2 of the drive.
See also Group 51: EXT COMM MODULE.

Parameters

202

Parameters

ACS550-01/U1 Users Manual

ACS550-01/U1 Users Manual

203

Embedded fieldbus
Overview
The ACS550 can be set up to accept control from an external system using standard
serial communication protocols. When using serial communication, the ACS550 can
either:
receive all of its control information from the fieldbus, or
be controlled from some combination of fieldbus control and other available
control locations, such as digital or analog inputs and the control panel.
Fieldbus controller
Fieldbus

Other devices

Connect using either:


standard embedded fieldbus (EFB) at
terminals X1:2832
fieldbus adapter (FBA) module mounted
in slot 2 (option Rxxx).

Two basic serial communications configurations are available:


embedded fieldbus (EFB) Using the RS485 interface at terminals X1:2832 on
the control board, a control system can communicate with the drive using the
Modbus protocol. (For protocol and profile descriptions, see sections Modbus
protocol technical data and ABB control profiles technical data later in this
chapter.)
fieldbus adapter (FBA) See chapter Fieldbus adapter on page 237.
Control interface
In general, the basic control interface between Modbus and the drive consists of:
Output words
Control Word
Reference1
Reference2
Input words
Status Word
Actual value 1
Actual value 2

Embedded fieldbus

204

ACS550-01/U1 Users Manual

Actual value 3
Actual value 4
Actual value 5
Actual value 6
Actual value 7
Actual value 8
The content of these words is defined by profiles. For details on the profiles used,
sees section ABB control profiles technical data on page 224.
Note: The words output and input are used as seen from the fieldbus controller
point of view. For example an output describes data flow from the fieldbus controller
to the drive and appears as an input from the drive point of view.

Planning
Network planning should address the following questions:
What types and quantities of devices must be connected to the network?
What control information must be sent down to the drives?
What feedback information must be sent from the drives to the controlling
system?

Mechanical and electrical installation EFB


WARNING! Connections should be made only while the drive is disconnected from
the power source.
Drive terminals 2832 are for RS485 communications.
Use Belden 9842 or equivalent. Belden 9842 is a dual twisted, shielded pair cable
with a wave impedance of 120 ohm.
Use one of these twisted shielded pairs for the RS485 link. Use this pair to
connect all A (-) terminals together and all B (+) terminals together.
Use one of the wires in the other pair for the logical ground (terminal 31), leaving
one wire unused.
Do not directly ground the RS485 network at any point. Ground all devices on the
network using their corresponding earthing terminals.
As always, the grounding wires should not form any closed loops, and all the
devices should be earthed to a common ground.
Connect the RS485 link in a daisy-chained bus, without dropout lines.

Embedded fieldbus

ACS550-01/U1 Users Manual

205

To reduce noise on the network, terminate the RS485 network using 120
resistors at both ends of the network. Use the DIP switch to connect or disconnect
the termination resistors. See the following diagram.
Terminated
station

Station

Terminated
station

Station

Drive RS485:

B
B ++ Positive
Positive

Negative
A - Negative

AGND
AGND

SCR Screen
SCR
Screen

See

See
Note1
2
Note

SCR
Screen
SCR Screen

ACH 550
RS485:
Terminal
block X1
Terminal Block -X1

28

29

30

31

32
PREFERRED WIRING:
3 Conductor with Shield

See Note 2: Shield


See Note 3: Shield
Notes:
NOTES:
1. Set switch
to OFF.
ON
position
make the
1. Use 3 J2
Conductor
Cable - Tie
3rd Wire
to AGND: would
X1-31.
See
Note
3:
R
G
See Note
4: Ground
network
active
pull down
[BIAS]
2. Set
switch J2(pull
to OFF. up
BUS &
termination
is an active
network: resistors
Ground
Pull Up & Pull
(BIAS) resistors are on board the ACH550 Drive!
are on board
theDown
drive).
See Note 5: Reference/Common
3. Tie shield wires together at Drive See Note 4: Reference/
Do Not
terminate
at SCR!
2. Tie shield
wires
together
at the drive Do NOT
4. Terminate
shield ONLY at "Ground" terminal
Common
terminate
at SCR.
in the Building Automation Controller!

5. Terminate
wire at "Reference"
terminal
3. Terminate
theAGN
shield
ONLY at
the Ground terminal
in the Building Automation Controller!
in the controller.
4. Terminate the AGND wire at the Reference
terminal in the controller.

Building Automation
Controller

Controller

For configuration information see the following sections:


Communication set-up EFB on page 205
Activate drive control functions EFB on page 207
The appropriate EFB protocol specific technical data. For example, Modbus
protocol technical data on page 215.

Communication set-up EFB


Serial communication selection
To activate the serial communication, set parameter 9802 COMM
1 (STD MODBUS).

PROT SEL

Note: If you cannot see the desired selection on the panel, your drive does not have
that protocol software in the application memory.

Embedded fieldbus

206

ACS550-01/U1 Users Manual

Serial communication configuration


Setting 9802 automatically sets the appropriate default values in parameters that
define the communication process. These parameters and descriptions are defined
below. In particular, note that the station Id may require adjustment.
Protocol reference

Code

Description

5301

EFB PROTOCOL ID
Contains the identification and program revision of
the protocol.

Do not edit. Any non-zero value entered


for parameter 9802 COMM PROT SEL,
sets this parameter automatically. The
format is: XXYY, where XX = protocol ID,
and YY = program revision.

5302

EFB STATION ID
Defines the node address of the RS485 link.

Set each drive on the network with a


unique value for this parameter.
When this protocol is selected, the
default value for this parameter is: 1

Modbus

Note: For a new address to take affect, the drive power must be cycled or 5302 must first be
set to 0 before selecting a new address. Leaving 5302 = 0 places the RS485 channel in reset,
disabling communication.
5303

EFB BAUD RATE


Defines the communication speed of the RS485
link in kbits per second (kbits/s).
1.2
2.4
4.8
9.6

kb/s
kb/s
kb/s
kb/s

When this protocol is selected, the


default value for this parameter is: 9.6

19.2 kb/s
38.4 kb/s
57.6 kb/s
76.8 kb/s

5304

When this protocol is selected, the


EFB PARITY
default value for this parameter is: 1
Defines the data length, parity and stop bits to be
used with the RS485 communication.
The same settings must be used in all on-line
stations.
0 = 8 NONE 1 8 data bits, no parity, one stop bit.
1 = 8 NONE 2 8 data bits, no parity, two stop bits.
2 = 8 EVEN 1 8 data bits, even parity, one stop bit.
3 = 8 ODD 1 8 data bits, odd parity, one stop bit.

5305

EFB CTRL PROFILE


Selects the communication profile used by the
EFB protocol.
0 = ABB DRV LIM Operation of Control/Status
Words conforms to ABB Drives Profile, as used
in ACS400.
1 = DCU PROFILE Operation of Control/Status
Words conforms to 32-bit DCU Profile.
2 = ABB DRV FULL Operation of Control/Status
Words conforms to ABB Drives Profile, as used
in ACS600/800.

When this protocol is selected, the


default value for this parameter is: 0

Note: After any changes to the communication settings, the protocol must be
reactivated by either cycling the drive power, or by clearing and then restoring the
station Id (5302).

Embedded fieldbus

ACS550-01/U1 Users Manual

207

Activate drive control functions EFB


Controlling the drive
Fieldbus control of various drive functions requires configuration to:
tell the drive to accept fieldbus control of the function
define as a fieldbus input, any drive data required for control
define as a fieldbus output, any control data required by the drive.
The following sections describe, at a general level, the configuration required for
each control function. For the protocol-specific details, see the document supplied
with the FBA module.
Start/Stop Direction control
Using the fieldbus for start/stop/direction control of the drive requires:
drive parameter values set as defined below
fieldbus controller supplied command(s) in the appropriate location. (The location
is defined by the Protocol Reference, which is protocol dependent.)
Drive parameter

Value

Description

Modbus1 protocol reference


ABB DRV

DCU PROFILE

1001 EXT1 COMMANDS

10 (COMM)

Start/Stop by fieldbus
with Ext1 selected.

40001 bits 03

40031 bits 0, 1

1002 EXT2 COMMANDS

10 (COMM)

Start/Stop by fieldbus
with Ext2 selected.

40001 bits 03

40031 bits 0, 1

1003 DIRECTION

3 (REQUEST) Direction by fieldbus.

4002/40032

40031 bit 3

For Modbus, the protocol reference can depend on the profile used, hence two columns in these
tables. One column refers to the ABB Drives profile, selected when parameter 5305 = 0 (ABB DRV
LIM) or 5305 = 2 (ABB DRV FULL). The other column refers to the DCU profile selected when
parameter 5305 = 1 (DCU PROFILE). See section ABB control profiles technical data on page 224.
2 The reference provides direction control a negative reference provides reverse rotation.

Embedded fieldbus

208

ACS550-01/U1 Users Manual

Input reference select


Using the fieldbus to provide input references to the drive requires:
drive parameter values set as defined below
fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Drive parameter

Value

Description

Modbus protocol
reference
ABB DRV

DCU PROFILE

1102

EXT1/EXT2 SEL

8 (COMM)

Reference set selection by fieldbus.

40001 bit 11

40031 bit 5

1103

REF1 SELECT

8 (COMM)

Input reference 1 by fieldbus.

40002

1106

REF2 SELECT

8 (COMM)

Input reference 2 by fieldbus.

40003

Reference Scaling
Where required,

REFERENCES

can be scaled. See the following, as appropriate:

Modbus Register 40002 in section Modbus protocol technical data on page 215
Reference scaling in section ABB control profiles technical data on page 224.
Miscellaneous drive control
Using the fieldbus for miscellaneous drive control requires:
drive parameter values set as defined below
fieldbus controller supplied command(s) in the appropriate location. (The location
is defined by the Protocol Reference, which is protocol dependent.)
Drive parameter

Value

Description

Modbus protocol
reference
ABB DRV

DCU PROFILE

1601

RUN ENABLE

7 (COMM) Run enable by fieldbus.

40001 bit 3

40031 bit 6
(inverted)

1604

FAULT RESET SEL

8 (COMM) Fault reset by fieldbus.

40001 bit 7

40031 bit 4

1606

LOCAL LOCK

8 (COMM) Source for local lock selection is


the fieldbus.

Does not
apply

40031 bit 14

1607

PARAM SAVE

1 (SAVE)

1608

START ENABLE

7 (COMM) Source for start enable 1 is the


fieldbus Command word.

1609

START ENABLE

7 (COMM) Source for start enable 2 is the


fieldbus Command word.

40032 bit 3

2013

MIN TORQUE SEL

7 (COMM) Source for minimum torque


selection is the fieldbus.

40031 bit 15

2014

MAX TORQUE SEL

7 (COMM) Source for maximum torque


selection is the fieldbus.

2201

ACC/DEC

7 (COMM) Source for ramp pair selection is


the fieldbus.

Embedded fieldbus

1/2 SEL

Saves altered parameters to


memory (then value returns to 0).

41607
Does not
apply.

40032 bit 2

40031 bit 10

ACS550-01/U1 Users Manual

209

Relay output control


Using the fieldbus for relay output control requires:
drive parameter values set as defined below
fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location. (The location is defined by the Protocol Reference, which is protocol
dependent.)
Drive parameter

Value

Description

Modbus protocol reference


ABB DRV

DCU PROFILE

1401

RELAY OUTPUT

35 (COMM)

Relay Output 1 controlled


by fieldbus.

40134 bit 0 or 00033

1402

RELAY OUTPUT

35 (COMM)

Relay Output 2 controlled


by fieldbus.

40134 bit 1 or 00034

1403

RELAY OUTPUT

35 (COMM)

Relay Output 3 controlled


by fieldbus.

40134 bit 2 or 00035

14101

RELAY OUTPUT

35 (COMM)

Relay Output 4 controlled


by fieldbus.

40134 bit 3 or 00036

14111

RELAY OUTPUT

35 (COMM)

Relay Output 5 controlled


by fieldbus.

40134 bit 4 or 00037

14121

RELAY OUTPUT

35 (COMM)

Relay Output 6 controlled


by fieldbus.

40134 bit 5 or 00038

More than 3 relays requires the addition of a relay extension module.

Note: Relay status feedback occurs without configuration as defined below.

Drive parameter

Description

Modbus protocol
reference
ABB DRV

DCU PROFILE

0122

RO

1-3 STATUS

Relay 13 status.

40122

0123

RO

4-6 STATUS

Relay 46 status.

40123

Analog output control


Using the fieldbus for analog output control (e.g. PID setpoint) requires:
drive parameter values set as defined below
fieldbus controller supplied analog value(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Drive parameter

Value

Description

Modbus protocol
reference
ABB DRV

1501 AO1 CONTENT SEL


0135 COMM VALUE 1
1507 AO2 CONTENT SEL
0136 COMM VALUE 2

135 (COMM VALUE 1) Analog Output 1


controlled by writing to

parameter 0135.
136 (COMM VALUE 2) Analog Output 2
controlled by writing to

parameter 0136.

DCU PROFILE

40135

40136

Embedded fieldbus

210

ACS550-01/U1 Users Manual

PID control setpoint source


Using the following settings to select the fieldbus as the setpoint source for PID
loops:
Drive parameter

Value

Modbus protocol
reference

Description

ABB DRV

4010 SET POINT SEL


(Set 1)
4110

SET POINT SEL

(Set 2)

8 (COMM VALUE 1) Setpoint is input reference 2


(+/-/* AI1)
9 (COMM+AI1)
10 (COMM*AI1)

DCU PROFILE

40003

4210 SET POINT SEL


(Ext/Trim)

Communication fault
When using fieldbus control, specify the drives action if serial communication is lost.
Drive parameter

Value

Description

3018 COMM FAULT FUNC

0 (NOT SEL)
1 (FAULT)
2 (CONST SP7)
3 (LAST SPEED)

3019 COMM FAULT TIME

Set time delay before acting on a communication loss.

Embedded fieldbus

Set for appropriate drive response.

ACS550-01/U1 Users Manual

211

Feedback from the drive EFB


Pre-defined feedback
Inputs to the controller (drive outputs) have pre-defined meanings established by the
protocol. This feedback does not require drive configuration. The following table lists
a sample of feedback data. For a complete listing, see input word/point/object
listings in the technical data for the appropriate protocol starting on page 215.
Modbus protocol reference

Drive parameter

ABB DRV

DCU PROFILE

0102

SPEED

40102

0103

OUTPUT FREQ

40103

0104

CURRENT

40104

0105

TORQUE

40105

0106

POWER

40106

0107

DC BUS VOLTAGE

40107

0109

OUTPUT VOLTAGE

40109

0301

FB CMD WORD1

bit 0 (STOP)

40301 bit 0

0301

FB CMD WORD1

1 bit 2 (REV)

40301 bit 2

0118

DI

1-3 STATUS bit 0 (DI3)

40118

Note: With Modbus, any parameter can be accessed using the format: 4 followed
by the parameter number.
Actual value scaling
The scaling of actual values can be protocol dependent. In general, for Actual
Values, scale the feedback integer using the parameters resolution. (See section
Complete parameter list on page 91 for parameter resolutions.) For example:
Feedback
integer

Parameter
resolution

(Feedback integer) (Parameter resolution) = Scaled value

0.1 mA

1 0.1 mA = 0.1 mA

10

0.1%

10 0.1% = 1%

Where parameters are in percent, the Complete parameter descriptions section


specifies what parameter corresponds to 100%. In such cases, to convert from
percent to engineering units, multiply by the value of the parameter that defines
100% and divide by 100%.

Embedded fieldbus

212

ACS550-01/U1 Users Manual

For example:
Feedback
integer
10

0.1%

100

Value of the
parameter that
defines 100%

Parameter
resolution

0.1%

(Feedback integer) (Parameter resolution)


(Value of 100% ref.) / 100% = Scaled value

1500 rpm1
500

10 0.1% 1500 RPM / 100% = 15 rpm

Hz2

100 0.1% 500 Hz / 100% = 50 Hz

Assuming, for the sake of this example, that the Actual Value uses parameter 9908 MOT NOM SPEED
as the 100% reference and that 9908 = 1500 rpm.
2
Assuming, for the sake of this example, that the Actual Value uses parameter 9907 MOT NOM FREQ
as the 100% reference and that 9907 = 500 Hz.

Diagnostics EFB
Fault queue for drive diagnostics
For general ACS550 diagnostics information, see chapter Diagnostics on page 259.
The three most recent ACS550 faults are reported to the fieldbus as defined below.
Drive parameter

Modbus protocol reference


ABB DRV

DCU PROFILE

0401 LAST FAULT

40401

0412 PREVIOUS FAULT 1

40412

0413 PREVIOUS FAULT 2

40413

Serial communication diagnostics


Network problems can be caused by multiple sources. Some of these sources are:
loose connections
incorrect wiring (including swapped wires)
bad grounding
duplicate station numbers
incorrect setup of drives or other devices on the network.
The major diagnostic features for fault tracing on an EFB network include Group 53:
EFB PROTOCOL parameters 53065309. Section Complete parameter
descriptions on page 106 describes these parameters in detail.

Embedded fieldbus

ACS550-01/U1 Users Manual

213

Diagnostic situations
The sub-sections below describe various diagnostic situations the problem
symptoms and corrective actions.
Normal operation
During normal network operation, 53065309 parameter values act as follows at
each drive:
5306 EFB OK MESSAGES advances (advances for each message properly received
and addressed to this drive).
5307 EFB CRC ERRORS does not advance at all (advances when an invalid
message CRC is received).
5308 EFB UART ERRORS does not advance at all (advances when character format
errors are detected, such as parity or framing errors).
5309 EFB STATUS value varies depending on network traffic.
Loss of communication
The ACS550 behavior, if communication is lost, was configured earlier in section
Communication fault on page 210. The parameters are 3018 COMM FAULT FUNC and
3019 COMM FAULT TIME. Section Complete parameter descriptions on page 106
describes these parameters in detail.
No master station on line
If no master station is on line: Neither the EFB OK MESSAGES nor the errors (5307 EFB
CRC ERRORS and 5308 EFB UART ERRORS) increase on any of the stations.
To correct:
Check that a network master is connected and properly programmed on the
network.
Verify that the cable is connected and that it is not cut or short circuited.
Duplicate stations
If two or more stations have duplicate numbers:
Two or more drives cannot be addressed.
Every time there is a read or write to one particular station, the value for 5307 EFB
CRC ERRORS or 5308 EFB UART ERRORS advances.
To correct: Verify the station numbers of all stations. Change conflicting station
numbers.
Swapped wires
If the communication wires are swapped (terminal A on one drive is connected to
terminal B on another):
The value of 5306 EFB OK
The values of 5307

MESSAGES

EFB CRC ERRORS

does not advance.


and 5308

EFB UART ERRORS

are advancing.

To correct: Check that the RS-485 lines are not swapped.

Embedded fieldbus

214

ACS550-01/U1 Users Manual

Fault 28 Serial 1 Err


If the drives control panel shows fault code 28,
following:

SERIAL

1 ERR, check for either of the

The master system is down. To correct, resolve problem with master system.
The communication connection is bad. To correct, check communication
connection at the drive.
The time-out selection for the drive is too short for the given installation. The
master is not polling the drive within the specified time-out delay. To correct,
increase the time set by parameter 3019 COMM FAULT TIME.
Faults 3133 EFB1EFB3
The three EFB fault codes listed for the drive in chapter Diagnostics on page 259
(fault codes 3133) are not used.
Intermittent off-line occurrences
The problems described above are the most common problems encountered with
ACS550 serial communication. Intermittent problems might also be caused by:
marginally loose connections
wear on wires caused by equipment vibrations
insufficient grounding and shielding on both the devices and on the
communication cables.

Embedded fieldbus

ACS550-01/U1 Users Manual

215

Modbus protocol technical data


Overview
The Modbus protocol was introduced by Modicon, Inc. for use in control
environments featuring Modicon programmable controllers. Due to its ease of use
and implementation, this common PLC language was quickly adopted as a de-facto
standard for integration of a wide variety of master controllers and slave devices.
Modbus is a serial, asynchronous protocol. Transactions are half-duplex, featuring a
single Master controlling one or more Slaves. While RS232 can be used for point-topoint communication between a single Master and a single Slave, a more common
implementation features a multi-drop RS485 network with a single Master controlling
multiple Slaves. The ACS550 features RS485 for its Modbus physical interface.
RTU
The Modbus specification defines two distinct transmission modes: ASCII and RTU.
The ACS550 supports RTU only.
Feature summary
The following Modbus function codes are supported by the ACS550.
Function

Code (Hex)

Description

Read Coil Status

0x01

Read discrete output status. For the ACS550, the individual bits
of the control word are mapped to Coils 116. Relay outputs are
mapped sequentially beginning with Coil 33 (e.g. RO1=Coil 33).

Read Discrete Input


Status

0x02

Read discrete inputs status. For the ACS550, the individual bits
of the status word are mapped to Inputs 116 or 132,
depending on the active profile. Terminal inputs are mapped
sequentially beginning with Input 33 (e.g. DI1=Input 33).

Read Multiple
Holding Registers

0x03

Read multiple holding registers. For the ACS550, the entire


parameter set is mapped as holding registers, as well as
command, status and reference values.

Read Multiple Input


Registers

0x04

Read multiple input registers. For the ACS550, the 2 analog input
channels are mapped as input registers 1 & 2.

Force Single Coil

0x05

Write a single discrete output. For the ACS550, the individual bits
of the control word are mapped to Coils 116. Relay outputs are
mapped sequentially beginning with Coil 33 (e.g. RO1=Coil 33).

Write Single
Holding Register

0x06

Write single holding register. For the ACS550, the entire


parameter set is mapped as holding registers, as well as
command, status and reference values.

Diagnostics

0x08

Perform Modbus diagnostics. Subcodes for Query (0x00),


Restart (0x01) & Listen Only (0x04) are supported.

Force Multiple Coils

0x0F

Write multiple discrete outputs. For the ACS550, the individual


bits of the control word are mapped to Coils 116. Relay outputs
are mapped sequentially beginning with Coil 33 (e.g. RO1=Coil
33).

Write Multiple
Holding Registers

0x10

Write multiple holding registers. For the ACS550, the entire


parameter set is mapped as holding registers, as well as
command, status and reference values.

Read/Write Multiple
Holding Registers

0x17

This function combines functions 0x03 and 0x10 into a single


command.

Embedded fieldbus

216

ACS550-01/U1 Users Manual

Mapping summary
The following table summarizes the mapping between the ACS550 (parameters and
I/0) and Modbus reference space. For details, see Modbus addressing below.
ACS550

Modbus reference

Supported function codes

Control Bits
Relay Outputs

Coils(0xxxx)

01 Read Coil Status


05 Force Single Coil
15 Force Multiple Coils

Status Bits
Discrete Inputs

Discrete Inputs(1xxxx)

02 Read Input Status

Analog Inputs

Input Registers(3xxxxx)

04 Read Input Registers

Parameters
Holding Registers(4xxxx)
Control/Status Words
References

03
06
16
23

Read 4X Registers
Preset Single 4X Register
Preset Multiple 4X Registers
Read/Write 4X Registers

Communication profiles
When communicating by Modbus, the ACS550 supports multiple profiles for control
and status information. Parameter 5305 EFB CTRL PROFILE selects the profile used.
The primary (and default) profile is the ABB DRV LIM profile. This
implementation of the ABB Drives profile standardizes the control interface with
ACS400 drives. The ABB Drives profile is based on the PROFIBUS interface. It is
discussed in detail in the following sections.

ABB DRV LIM

DCU PROFILE The DCU PROFILE profile extends the control and status interface to
32 bits. It is the internal interface between the main drive application and the
embedded fieldbus environment.

ABB DRV FULL

ABB DRV FULL is the implementation of the ABB Drives profile that
standardizes the control interface with ACS600 and ACS800 drives. This
implementation supports two control word bits not supported by the ABB DRV LIM
implementation.

Modbus addressing
With Modbus, each function code implies access to a specific Modbus reference set.
Thus, the leading digit is not included in the address field of a Modbus message.
Note: The ACS550 supports the zero-based addressing of the Modbus
specification. Holding register 40002 is addressed as 0001 in a Modbus message.
Similarly, coil 33 is addressed as 0032 in a Modbus message.
Refer again to the Mapping summary above. The following sections describe, in
detail, the mapping to each Modbus reference set.
0xxxx Mapping Modbus coils. The drive maps the following information to the
0xxxx Modbus set called Modbus Coils:
bit-wise map of the CONTROL WORD (selected using parameter 5305 EFB CTRL
PROFILE). The first 32 coils are reserved for this purpose.

Embedded fieldbus

ACS550-01/U1 Users Manual

217

relay output states, numbered sequentially beginning with coil 00033.


The following table summarizes the 0xxxx reference set:
Modbus
ref.
00001

Internal location
(all profiles)
Bit 0

CONTROL WORD

ABB DRV LIM

DCU PROFILE

(5305 = 0)

(5305 = 1)

ABB DRV FULL

(5305 = 2)

STOP

OFF1

OFF1

00002

CONTROL WORD

Bit 1

OFF2

START

OFF21

00003

CONTROL WORD

Bit 2

OFF31

REVERSE

OFF31

00004

CONTROL WORD

Bit 3

START

LOCAL

START

00005

CONTROL WORD

Bit 4

N/A

RESET

RAMP_OUT_ZERO1

00006

CONTROL WORD

Bit 5

RAMP_HOLD1

EXT2

RAMP_HOLD1

00007

CONTROL WORD

Bit 6

RAMP_IN_ZERO1

RUN_DISABLE

RAMP_IN_ZERO1

00008

CONTROL WORD

Bit 7

RESET

STPMODE_R

RESET

00009

CONTROL WORD

Bit 8

N/A

STPMODE_EM

N/A

00010

CONTROL WORD

Bit 9

N/A

STPMODE_C

N/A

00011

CONTROL WORD

Bit 10 N/A

RAMP_2

REMOTE_CMD1

00012

CONTROL WORD

Bit 11 EXT2

RAMP_OUT_0

EXT2

00013

CONTROL WORD

Bit 12 N/A

RAMP_HOLD

N/A

00014

CONTROL WORD

Bit 13 N/A

RAMP_IN_0

N/A

00015

CONTROL WORD

Bit 14 N/A

REQ_LOCALLOCK

N/A

00016

CONTROL WORD

Bit 15 N/A

TORQLIM2

N/A

00017

CONTROL WORD

Bit 16 Does not apply

FBLOCAL_CTL

Does not apply

00018

CONTROL WORD

Bit 17

FBLOCAL_REF

00019

CONTROL WORD

Bit 18

START_DISABLE1

00020

CONTROL WORD

Bit 19

START_DISABLE2

00021
00032

Reserved

00033

RELAY OUTPUT

00034

Reserved

Reserved

Reserved

Relay Output 1

Relay Output 1

Relay Output 1

RELAY OUTPUT

Relay Output 2

Relay Output 2

Relay Output 2

00035

RELAY OUTPUT

Relay Output 3

Relay Output 3

Relay Output 3

00036

RELAY OUTPUT

Relay Output 4

Relay Output 4

Relay Output 4

00037

RELAY OUTPUT

Relay Output 5

Relay Output 5

Relay Output 5

00038

RELAY OUTPUT

Relay Output 6

Relay Output 6

Relay Output 6

= Active low

For the 0xxxx registers:


Status is always readable.
Forcing is allowed by user configuration of the drive for fieldbus control.
Additional relay outputs are added sequentially.

Embedded fieldbus

218

ACS550-01/U1 Users Manual

The ACS550 supports the following Modbus function codes for coils:
Function code

Description

01

Read coil status

05

Force single coil

15 (0x0F Hex)

Force multiple coils

1xxxx Mapping Modbus discrete inputs. The drive maps the following
information to the 1xxxx Modbus set called Modbus Discrete Inputs:
bit-wise map of the STATUS WORD (selected using parameter 5305 EFB CTRL
PROFILE). The first 32 inputs are reserved for this purpose.
discrete hardware inputs, numbered sequentially beginning with input 33.
The following table summarizes the 1xxxx reference set:
Modbus
ref.

Internal location
(all profiles)

ABB DRV

DCU PROFILE

(5305 = 0 OR 2)

(5305 = 1)

10001

STATUS WORD

Bit 0

RDY_ON

READY

10002

STATUS WORD

Bit 1

RDY_RUN

ENABLED

10003

STATUS WORD

Bit 2

RDY_REF

STARTED

10004

STATUS WORD

Bit 3

TRIPPED

RUNNING

Bit 4

OFF_2_STA1

ZERO_SPEED
ACCELERATE

10005

STATUS WORD

10006

STATUS WORD

Bit 5

OFF_3_STA1

10007

STATUS WORD

Bit 6

SWC_ON_INHIB

DECELERATE

10008

STATUS WORD

Bit 7

ALARM

AT_SETPOINT

10009

STATUS WORD

Bit 8

AT_SETPOINT

LIMIT

10010

STATUS WORD

Bit 9

REMOTE

SUPERVISION

10011

STATUS WORD

Bit 10

ABOVE_LIMIT

REV_REF

10012

STATUS WORD

Bit 11

EXT2

REV_ACT

10013

STATUS WORD

Bit 12

RUN_ENABLE

PANEL_LOCAL

10014

STATUS WORD

Bit 13

N/A

FIELDBUS_LOCAL

10015

STATUS WORD

Bit 14

N/A

EXT2_ACT

10016

STATUS WORD

Bit 15

N/A

FAULT

10017

STATUS WORD

Bit 16

Reserved

ALARM

10018

STATUS WORD

Bit 17

Reserved

REQ_MAINT

10019

STATUS WORD

Bit 18

Reserved

DIRLOCK

10020

STATUS WORD

Bit 19

Reserved

LOCALLOCK

10021

STATUS WORD

Bit 20

Reserved

CTL_MODE

10022

STATUS WORD

Bit 21

Reserved

Reserved

10023

STATUS WORD

Bit 22

Reserved

Reserved

10024

STATUS WORD

Bit 23

Reserved

Reserved

10025

STATUS WORD

Bit 24

Reserved

Reserved

10026

STATUS WORD

Bit 25

Reserved

Reserved

10027

STATUS WORD

Bit 26

Reserved

REQ_CTL

Embedded fieldbus

ACS550-01/U1 Users Manual

Modbus
ref.

219

Internal location
(all profiles)

ABB DRV

DCU PROFILE

(5305 = 0 OR 2)

(5305 = 1)

10028

STATUS WORD

Bit 27

Reserved

REQ_REF1

10029

STATUS WORD

Bit 28

Reserved

REQ_REF2

10030

STATUS WORD

Bit 29

Reserved

REQ_REF2EXT

10031

STATUS WORD

Bit 30

Reserved

ACK_STARTINH

10032

STATUS WORD

Bit 31

Reserved

ACK_OFF_ILCK

10033

DI1

DI1

DI1

10034

DI2

DI2

DI2

10035

DI3

DI3

DI3

10036

DI4

DI4

DI4

10037

DI5

DI5

DI5

10038

DI6

DI6

DI6

= Active low

For the 1xxxx registers:


Additional discrete inputs are added sequentially.
The ACS550 supports the following Modbus function codes for discrete inputs:
Function code
02

Description
Read input status

3xxxx Mapping Modbus inputs. The drive maps the following information to the
3xxxx Modbus addresses called Modbus input registers:
any user defined analog inputs.
The following table summarizes the input registers:
Modbus
reference

ACS550
all profiles

Remarks

30001

AI1

This register shall report the level of Analog Input 1 (0100%).

30002

AI2

This register shall report the level of Analog Input 2 (0100%).

The ACS550 supports the following Modbus function codes for 3xxxx registers:
Function code
04

Description
Read 3xxxx input status

4xxxx Register mapping. The drive maps its parameters and other data to the
4xxxx holding registers as follows:
4000140099 map to drive control and actual values. These registers are
described in the table below.
4010149999 map to drive parameters 01019999. Register addresses that do
not correspond to drive parameters are invalid. If there is an attempt to read or
write outside the parameter addresses, the Modbus interface returns an
exception code to the controller.

Embedded fieldbus

220

ACS550-01/U1 Users Manual

The following table summarizes the 4xxxx drive control registers 4000140099 (for
4xxxx registers above 40099, see the drive parameter list, e.g. 40102 is parameter
0102):
Modbus register

Access

Remarks

40001

CONTROL WORD

R/W

Maps directly to the profileS CONTROL WORD. Supported only


if 5305 = 0 or 2 (ABB Drives profile). Parameter 5319 holds
a copy in hex format.
If 5305 = 1 (DCU profile selected), the register remains
empty.

40002

Reference 1

R/W

Range = 0+20000 (scaled to 01105 REF1 MAX), or


-200000 (scaled to 1105 REF1 MAX0).

40003

Reference 2

R/W

Range = 0+10000 (scaled to 01108 REF2 MAX), or


-100000 (scaled to 1108 REF2 MAX0).

40004

STATUS WORD

Maps directly to the profileS STATUS WORD. Supported only if


5305 = 0 or 2 (ABB Drives profile). Parameter 5320 holds a
copy in hex format.
If 5305 = 1 (DCU profile selected), the register remains
empty.

40005

Actual 1
(select using 5310)

By default, stores a copy of 0103 OUTPUT FREQ. Use


parameter 5310 to select a different actual value for this
register.

40006

Actual 2
(select using 5311)

By default, stores a copy of 0104 CURRENT. Use parameter


5311 to select a different actual value for this register.

40007

Actual 3
(select using 5312)

By default, stores nothing. Use parameter 5312 to select an


actual value for this register.

40008

Actual 4
(select using 5313)

By default, stores nothing. Use parameter 5313 to select an


actual value for this register.

40009

Actual 5
(select using 5314)

By default, stores nothing. Use parameter 5314 to select an


actual value for this register.

40010

Actual 6
(select using 5315)

By default, stores nothing. Use parameter 5315 to select an


actual value for this register.

40011

Actual 7
(select using 5316)

By default, stores nothing. Use parameter 5316 to select an


actual value for this register.

40012

Actual 8
(select using 5317)

By default, stores nothing. Use parameter 5317 to select an


actual value for this register.

40031

ACS550 CONTROL
WORD LSW

R/W

Maps directly to the Least Significant Word of the DCU


profiles CONTROL WORD. Supported only if 5305 = 1.
See parameter 0301.

40032

ACS550 CONTROL
WORD MSW

Maps directly to the Most Significant Word of the DCU


profiles CONTROL WORD. Supported only if 5305 = 1.
See parameter 0302.

40033

ACS550 STATUS
WORD LSW

Maps directly to the Least Significant Word of the DCU


profiles STATUS WORD. Supported only if 5305 = 1.
See parameter 0303.

40034

ACS550 STATUS
WORD MSW

Maps directly to the Most Significant Word of the DCU


profiles STATUS WORD. Supported only if 5305 = 1.
See parameter 0304.

40045

REFERENCE

R/W

The least significant word of reference 1. Supported only by


the DCU profile i.e. when 5305 ECB CTRL PROFILE setting is
DCU profile.

Embedded fieldbus

1 LSW

ACS550-01/U1 Users Manual

221

Modbus register

Access

Remarks

40046

REFERENCE

1 MSW

R/W

The most significant word of reference 1. Supported only by


the DCU profile i.e. when 5305 ECB CTRL PROFILE setting is
DCU profile.

40047

REFERENCE

2 LSW

R/W

The least significant word of reference 2. Supported only by


the DCU profile i.e. when 5305 ECB CTRL PROFILE setting is
DCU profile.

40048

REFERENCE

2 MSW

R/W

The most significant word of reference 2. Supported only by


DCU profile i.e. when 5305 ECB CTRL PROFILE setting is DCU
profile.

Embedded fieldbus

222

ACS550-01/U1 Users Manual

For the Modbus protocol, drive parameters in Group 53: EFB PROTOCOL report the
parameter mapping to 4xxxx Registers.
Code

Description

5310

EFB PAR 10
Specifies the parameter mapped to Modbus register 40005.

5311

EFB PAR 11
Specifies the parameter mapped to Modbus register 40006.

5312

EFB PAR 12
Specifies the parameter mapped to Modbus register 40007.

5313

EFB PAR 13
Specifies the parameter mapped to Modbus register 40008.

5314

EFB PAR 14
Specifies the parameter mapped to Modbus register 40009.

5315

EFB PAR 15
Specifies the parameter mapped to Modbus register 40010.

5316

EFB PAR 16
Specifies the parameter mapped to Modbus register 40011.

5317

EFB PAR 17
Specifies the parameter mapped to Modbus register 40012.

5318

EFB PAR 18
Sets additional delay in milliseconds before the ACS550 begins
transmitting response to the master request.

5319

EFB PAR 19
Holds a copy (in hex) of the CONTROL WORD, Modbus register 40001.

5320

EFB PAR 20
Holds a copy (in hex) of the STATUS WORD, Modbus register 40004.

Except where restricted by the drive, all parameters are available for both reading
and writing. The parameter writes are verified for the correct value and for a valid
register addresses.
Note: Parameter writes through standard Modbus are always volatile i.e. modified
values are not automatically stored to permanent memory. Use parameter 1607
PARAM SAVE to save all altered values.
The ACS550 supports the following Modbus function codes for 4xxxx registers:
Function code

Description

03

Read holding 4xxxx registers

06

Preset single 4xxxx register

16 (0x10 Hex)

Preset multiple 4xxxx registers

23 (0x17 Hex)

Read/write 4xxxx registers

Embedded fieldbus

ACS550-01/U1 Users Manual

223

Actual values
The contents of the register addresses 4000540012 are ACTUAL VALUES and are:
specified using parameters 53105317
Read-only values containing information on the operation of the drive
16-bit words containing a sign bit and a 15-bit integer
when negative values, written as the twos complement of the corresponding
positive value
scaled as described earlier in section Actual value scaling on page 211.
Exception codes
Exception codes are serial communication responses from the drive. The ACS550
supports the standard Modbus exception codes defined below.
Exception
code

Name

Meaning

01

ILLEGAL FUNCTION

Unsupported Command

02

ILLEGAL DATA ADDRESS

The data address received in the query is not allowable. It is not


a defined parameter/group.

03

ILLEGAL DATA VALUE

A value contained in the query data field is not an allowable


value for the ACS550, because it is one of the following:
Outside min. or max. limits.
Parameter is read-only.
Message is too long.
Parameter write not allowed when start is active.
Parameter write not allowed when factory macro is selected.

Embedded fieldbus

224

ACS550-01/U1 Users Manual

ABB control profiles technical data


Overview
ABB Drives profile
The ABB Drives profile provides a standard profile that can be used on multiple
protocols, including Modbus and the protocols available on the FBA module. Two
implementations of the ABB Drives profile are available:
This implementation standardizes the control interface with
ACS600 and ACS800 drives.

ABB DRV FULL

ABB DRV LIM This implementation standardizes the control interface with
ACS400 drives. This implementation does not support two control word bits
supported by ABB DRV FULL.

Except as noted, the following ABB Drives Profile descriptions apply to both
implementations.
DCU profile
The DCU profile extends the control and status interface to 32 bits. It is the internal
interface between the main drive application and the embedded fieldbus
environment.
Control Word
The CONTROL WORD is the principal means for controlling the drive from a fieldbus
system. The fieldbus master station sends the CONTROL WORD to the drive. The drive
switches between states according to the bit-coded instructions in the CONTROL
WORD. Using the CONTROL WORD requires that:
The drive is in remote (REM) control.
The serial communication channel is defined as the source for controlling
commands (set using parameters such as 1001 EXT1 COMMANDS, 1002 EXT2
COMMANDS and 1102 EXT1/EXT2 SEL).
The serial communication channel used is configured to use an ABB control
profile. For example, to use the control profile ABB DRV FULL requires both
parameter 9802 COMM PROT SEL = 1 (STD MODBUS) and parameter 5305 EFB CTRL
PROFILE = 2 (ABB DRV FULL).

Embedded fieldbus

ACS550-01/U1 Users Manual

225

ABB Drives profile


The following table and the state diagram later in this sub-section describe the
CONTROL WORD content for the ABB Drives profile.
ABB Drives profile CONTROL WORD (See parameter 5319)
Bit
0

Name
OFF1
CONTROL

OFF2
CONTROL

OFF3
CONTROL

INHIBIT
OPERATION

Value

Commanded
state

Comments

READY TO OPERATE

Enter READY TO OPERATE

EMERGENCY OFF

Drive ramps to stop according to currently


active deceleration ramp (2203 or 2205)
Normal command sequence:
Enter OFF1 ACTIVE
Proceed to READY TO SWITCH ON, unless
other interlocks (OFF2, OFF3) are active.

OPERATING

Continue operation (OFF2 inactive)

EMERGENCY OFF

Drive coasts to stop.


Normal command sequence:
Enter OFF2 ACTIVE
Proceed to SWITCHON INHIBITED

OPERATING

Continue operation (OFF3 inactive)

EMERGENCY STOP

Drive stops within time specified by parameter


2208.
Normal command sequence:
Enter OFF3 ACTIVE
Proceed to SWITCH ON INHIBITED
WARNING! Be sure motor and driven
equipment can be stopped using this
mode.

OPERATION
ENABLED

Enter OPERATION ENABLED (Note the Run


enable signal must be active. See 1601. If
1601 is set to COMM, this bit also actives the
Run Enable signal.)

OPERATION
INHIBITED

Inhibit operation. Enter OPERATION INHIBITED

NORMAL OPERATION

Enter RAMP FUNCTION GENERATOR:

Unused (ABB DRV LIM)


RAMP_OUT_
ZERO
(ABB DRV FULL)

1
0

RFG OUT ZERO

Force ramp function generator output to Zero.


Drive ramps to stop (current and DC voltage
limits in force).

RAMP_HOLD

RFG OUT ENABLED

Enable ramp function.


Enter RAMP FUNCTION GENERATOR:

ACCELERATION ENABLED

ACCELERATOR ENABLED

RAMP_IN_
ZERO

RFG OUT HOLD

Halt ramping (Ramp Function Generator


output held)

RFG INPUT ENABLED

Normal operation. Enter OPERATING

RFG INPUT ZERO

Force Ramp Function Generator input to zero.

Embedded fieldbus

226

ACS550-01/U1 Users Manual

ABB Drives profile CONTROL WORD (See parameter 5319)


Bit
7

Name
RESET

Value

Commanded
state

Comments

0=>1

RESET

Fault reset if an active fault exists (Enter


SWITCH-ON INHIBITED). Effective if 1604 =
COMM.

OPERATING

Continue normal operation

89 Unused
10

11

Unused (ABB DRV LIM)


REMOTE_CMD
(ABB DRV FULL)

Fieldbus control enabled.

CW =/ 0 or Ref =/ 0: Retain last CW and Ref.


CW = 0 and Ref = 0: Fieldbus control
enabled.
Ref and deceleration/acceleration ramp are
locked.

EXT CTRL LOC

EXT2 SELECT

Select external control location 2 (EXT2).


Effective if 1102 = COMM.

EXT1 SELECT

Select external control location 1 (EXT1).


Effective if 1102 = COMM.

12 Unused
15

DCU Profile
The following tables describe the CONTROL WORD content for the DCU profile.
DCU profile CONTROL WORD (See parameter 0301)
Bit
0
1

2
3

4
5

6
7

Embedded fieldbus

Name
STOP
START

REVERSE
LOCAL

RESET
EXT2

RUN_DISABLE
STPMODE_R

Value

Command/Req.

Comments

Stop

Stops according to either the stop mode


parameter or the stop mode requests (bits 7
and 8).
Simultaneous STOP and START commands
result in a stop command.

(no op)

Start

(no op)

Reverse direction

Forward direction

Local mode

External mode

When the fieldbus sets this bit, it steals


control and the drive moves to fieldbus local
control mode.

-> 1

Reset

Edge sensitive.

other

(no op)

Switch to EXT2

Switch to EXT1

Run disable

Run enable on

Normal ramp stop


mode

(no op)

This bit XORd with the sign of the reference


defines direction.

Inverted run enable.

ACS550-01/U1 Users Manual

227

DCU profile CONTROL WORD (See parameter 0301)


Bit
8

9
10

11
12

Name
STPMODE_EM

Emergency ramp
stop mode

(no op)

Coast stop mode

(no op)

Ramp pair 2

Ramp pair 1

Ramp output to 0

(no op)

Ramp freeze

(no op)

Ramp input to 0

(no op)

RREQ_LOCALL
OC

Local mode lock

(no op)

TORQLIM2

Torque limit pair 2

Torque limit pair 1

STPMODE_C
RAMP_2

RAMP_OUT_0

RAMP_IN_0

14
15

Command/Req.

RAMP_HOLD

13

Value

Comments

In lock, drive will not switch to local mode.

DCU profile CONTROL WORD (See parameter 0302)


Bit

Name

Value

Function

1626
27

28
29

30

31

Comments

Reserved
REF_CONST

REF_AVE
LINK_ON

REQ_STARTINH

OFF_INTERLOCK

1
0

Constant speed ref. These bits are only for supervision


purposes.
(no op)

Average speed ref.

(no op)

Master is detected
in link

Link is down

Start inhibit request


is pending

Start inhibit request


is OFF

Panel OFF button


pressed

(no op)

For the control panel (or PC tool) this is


the OFF button interlock.

Status Word
The contents of the STATUS WORD is status information, sent by the drive to the
master station.

Embedded fieldbus

228

ACS550-01/U1 Users Manual

ABB Drives profile


The following table and the state diagram later in this sub-section describe the
STATUS WORD content for the ABB Drives profile.
ABB Drives profile (EFB) STATUS WORD (See parameter 5320)
Bit
0
1
2

3
4
5

6
7

9
10

11
12

Name
RDY_ON
RDY_RUN
RDY_REF

TRIPPED
OFF_2_STA
OFF_3_STA

SWC_ON_INHIB
ALARM

AT_SETPOINT

REMOTE
ABOVE_LIMIT

EXT CTRL LOC

Value
1

READY TO SWITCH ON

NOT READY TO SWITCH ON

READY TO OPERATE

OFF1 ACTIVE

OPERATION ENABLED

OPERATION INHIBITED

01

FAULT

No fault

OFF2 INACTIVE

OFF2 ACTIVE

OFF3 INACTIVE

OFF3 ACTIVE

SWITCH-ON INHIBIT ACTIVE

SWITCH-ON INHIBIT NOT ACTIVE

Alarm (See section Alarm listing on page 267 for details on


alarms.)

No alarm

OPERATING.

Actual value is outside tolerance limits (not equal to reference


value).

Drive control location: REMOTE (EXT1 or EXT2)

Drive control location: LOCAL

Supervised parameters value > supervision high limit.


Bit remains 1 until supervised parameters value < supervision
low limit.
See Group 32: SUPERVISION.

Supervised parameters value < supervision low limit.


Bit remains 0 until supervised parameters value > supervision
high limit.
See Group 32: SUPERVISION.

External control location 2 (EXT2) selected

External control location 1 (EXT1) selected

EXT RUN ENABLE 1


0

13
15

Embedded fieldbus

Unused

Description
(Correspond to states/boxes in the state diagram)

Actual value equals (within tolerance limits) the


reference value.

External Run Enable signal received


No External Run Enable signal received

ACS550-01/U1 Users Manual

229

DCU profile
The following tables describe the STATUS WORD content for the DCU profile.
DCU profile STATUS WORD (See parameter 0303)
Bit
0
1

2
3
4

5
6
7

8
9

10
11

12
13
14

15

Name
READY
ENABLED

STARTED
RUNNING
ZERO_SPEED

ACCELERATE
DECELERATE
AT_SETPOINT

LIMIT
SUPERVISION

REV_REF
REV_ACT

PANEL_LOCAL
FIELDBUS_LOCAL
EXT2_ACT

FAULT

Value

Status

Drive is ready to receive start command.

Drive is not ready.

External run enable signal received.

No external run enable signal received.

Drive has received start command.

Drive has not received start command.

Drive is modulating.

Drive is not modulating.

Drive is at zero speed.

Drive has not reached zero speed.

Drive is accelerating.

Drive is not accelerating.

Drive is decelerating.

Drive is not decelerating.

Drive is at setpoint.

Drive has not reached setpoint.

Operation is limited by Group 20: LIMITS settings.

Operation is within Group 20: LIMITS settings.

A supervised parameter (Group 32: SUPERVISION) is outside


its limits.

All supervised parameters are within limits.

Drive reference is in reverse direction.

Drive reference is in forward direction.

Drive is running in reverse direction.

Drive is running in forward direction.

Control is in control panel (or PC tool) local mode.

Control is not in control panel local mode.

Control is in fieldbus local mode (steals control panel local).

Control is not in fieldbus local mode.

Control is in EXT2 mode.

Control is in EXT1 mode.

Drive is in a fault state.

Drive is not in a fault state.

Embedded fieldbus

230

ACS550-01/U1 Users Manual

DCU profile STATUS WORD (See parameter 0304)


Bit
16
17

18
19
20

Name
ALARM
REQ_MAINT

DIRLOCK
LOCALLOCK
CTL_MODE

Value

Status

An alarm is on.

No alarms are on.

A maintenance request is pending.

No maintenance request is pending.

Direction lock is ON. (Direction change is locked out.)

Direction lock is OFF.

Local mode lock is ON. (Local mode is locked out.)

Local mode lock is OFF.

Drive is in vector control mode.

Drive is in scalar control mode.

2125
26

27
28
29

30
31

Embedded fieldbus

Reserved
REQ_CTL

REQ_REF1
REQ_REF2
REQ_REF2EXT

ACK_STARTINH
ACK_OFF_ILCK

Copy the control word

(no op)

Reference 1 requested in this channel.

Reference 1 is not requested in this channel.

Reference 2 requested in this channel.

Reference 2 is not requested in this channel.

External PID reference 2 requested in this channel.

External PID reference 2 is not requested in this channel.

A start inhibit from this channel is granted.

A start inhibit from this channel is not granted.

Start inhibit due to OFF button

Normal operation

ACS550-01/U1 Users Manual

231

State diagram
ABB Drives profile
To illustrate the operation of the state diagram, the following example (ABB DRV LIM
implementation of the ABB Drives profile) uses the control word to start the drive:
First, the requirements for using the CONTROL WORD must be met. See above.
When the power is first connected, the state of the drive is not ready to switch on.
See dotted lined path (
) in the state diagram below.
Use the CONTROL WORD to step through the state machine states until the
OPERATING state is reached, meaning that the drive is running and follows the
given reference. See the table below.
Step
1

CONTROL WORD Value

CW = 0000 0000 0000 0110


bit 15

bit 0

Description
This CW value changes the drive state to READY TO SWITCH
ON.
Wait at least 100 ms before proceeding.

CW = 0000 0000 0000 0111

This CW value changes the drive state to READY TO OPERATE.

CW = 0000 0000 0000 1111

This CW value changes the drive state to OPERATION ENABLED.


The drive starts, but will not accelerate.

CW = 0000 0000 0010 1111

This CW value releases the ramp function generator (RFG)


output and changes the drive state to RFG: ACCELERATOR
ENABLED.

CW = 0000 0000 0110 1111

This CW value releases the ramp function generator (RFG)


output and changes the drive state to OPERATING. The drive
accelerates to the given reference and follows the reference.

Embedded fieldbus

232

ACS550-01/U1 Users Manual

The state diagram below describes the start-stop function of CONTROL WORD (CW)
and STATUS WORD (SW) bits for the ABB Drives profile.
From any state

From any state

Emergency Off
OFF2 (CW Bit1=0)

Emergency Stop
OFF3 (CW Bit2=0)
(SW Bit5=0)

From any state

OFF3
ACTIVE

OFF2
ACTIVE

(SW Bit4=0)

Fault
FAULT

(SW Bit3=1)

(CW Bit7=1)**

n(f)=0 / I=0
From any state
OFF1 (CW Bit0=0)
(SW Bit1=0)

n(f)=0 / I=0

SWITCH-ON
INHIBITED

MAINS OFF

OFF1
ACTIVE

Power ON

(CW Bit0=0)

A B* C D

NOT READY
TO SWITCH ON

OPERATION
INHIBITED

READY TO
SWITCH ON

(SW Bit0=1)

(CW= xxxx x1xx xxxx x111)

OPERATION INHIBITED

B* C* D*

READY TO
OPERATE

(CW Bit4=0)*

OPERATION
ENABLED

(SW Bit2=1)

(CW Bit5=0)

(CW=xxxx x1xx xxx1* 1111


i.e. Bit 4=1)*
RFG OUTPUT
ENABLED*

KEY
State
State change
(CW Bit6=0)
Path described in example
CW = CONTROL WORD
SW = STATUS WORD
RFG = Ramp Function Generator
I = Param. 0104 CURRENT
f = Param. 0103 OUTPUT FREQ
n = Speed
* Indicates the features not in ABB DRV LIM
** This state transition also occurs if the fault is
reset from any other source (e.g. digital input).

(SW Bit1=1)

(CW Bit3=1 and


SW Bit12=1)

C D

Embedded fieldbus

(SW Bit0=0)

(CW xxxx x1xx xxxx x110)

(CW Bit3=0)
(SW Bit2=0)

(SW Bit6=1)

D
B*

(CW=xxxx x1xx xx11* 1111


i.e. Bit 5=1)
RFG: ACCELERATOR
ENABLED
C

(CW=xxxx x1xx x111* 1111


i.e. Bit 6=1)
OPERATING

(SW Bit8=1)

ACS550-01/U1 Users Manual

233

Reference scaling
Fieldbus references REF1 and REF2 are scaled as shown in the following tables.
Fieldbus scaling for ABB Drives profile
Reference

Range

Reference
type

Scaling

Remarks

REF1

-32767

+32767

Speed or
frequency

-20000 = -(par. 1105)


0=0
+20000 = (par. 1105)
(20000 corresponds to 100%)

Final reference limited by


1104/1105. Actual motor
speed limited by 2001/2002
(speed) or 2007/2008
(frequency).

REF2

-32767

+32767

Speed or
frequency

-10000 = -(par. 1108)


0=0
+10000 = (par. 1108)
(10000 corresponds to 100%)

Final reference limited by


1107/1108. Actual motor
speed limited by 2001/2002
(speed) or 2007/2008
(frequency).

Torque

-10000 = -(par. 1108)


0=0
+10000 = (par. 1108)
(10000 corresponds to 100%)

Final reference limited by


2015/2017 (torque1) or 2016/
2018 (torque2).

PID
Reference

-10000 = -(par. 1108)


0=0
+10000 = (par. 1108)
(10000 corresponds to 100%)

Final reference limited by


4012/4013 (PID set1) or
4112/4113 (PID set2).

Note: The setting of parameter 1104 REF1 MIN and 1107


the scaling of references.

REF2 MIN

has no effect on

Fieldbus scaling for DCU profile


Reference

Range

Reference
type

Scaling

Remarks

REF1

-214783648

+214783647

Speed or
frequency

1000 = 1 rpm / 1 Hz

Final reference limited by


1104/1105. Actual motor
speed limited by 2001/2002
(speed) or 2007/2008
(frequency).

REF2

-214783648

+214783647

Speed or
frequency

1000 = 1%

Final reference limited by


1107/1108. Actual motor
speed limited by 2001/2002
(speed) or 2007/2008
(frequency).

Torque

1000 = 1%

Final reference limited by


2015/2017 (torque1) or 2016/
2018 (torque2).

PID
Reference

1000 = 1%

Final reference limited by


4012/4013 (PID set1) or
4112/4113 (PID set2).

Note: The setting of parameter 1104 REF1 MIN and 1107


the scaling of references.

REF2 MIN

has no effect on

Embedded fieldbus

234

ACS550-01/U1 Users Manual

Scaling examples
When parameter 1103 REF1 SELECT or 1106 REF2 SELECT is set to
COMM*AI1, the reference is scaled as follows:

COMM+AI1

or

ABB Drives and DCU profiles


Reference
REF1

Value
setting
COMM+AI1

AI reference scaling
COMM

(%) +(AI (%) - 0.5 REF1 MAX (%))


Fieldbus reference
correction coefficient
(100 + 0.5 (Par. 1105)%

100%

AI1 input signal


(100 - 0.5 (par. 1105))%
0%
REF1

COMM*AI1

COMM

50%

100%

(%) (AI (%) / 0.5 REF1 MAX (%))


Fieldbus reference
correction coefficient
200%

100%

AI1 input signal


(100 - 0.5 (par. 1105))%
0%
REF2

COMM+AI1

COMM

50%

100%

(%) + (AI (%) - 0.5 REF2 MAX (%))


Fieldbus reference
correction coefficient
(100 + 0.5 (Par. 1108)%

100%

AI1 input signal


(100 - 0.5 (par. 1108)%
0%

Embedded fieldbus

50%

100%

ACS550-01/U1 Users Manual

235

ABB Drives and DCU profiles


Reference
REF2

Value
setting
COMM*AI1

AI reference scaling
COMM

(%) (AI (%) / 0.5 REF2 MAX (%))


Fieldbus reference
correction coefficient
200%

100%

AI1input signal
0%
0%

50%

100%

Embedded fieldbus

236

ACS550-01/U1 Users Manual

Reference handling
Use Group 10: START/STOP/DIR parameters to configure for control of rotation
direction for each control location (EXT1 and EXT2). The following diagrams illustrate
how group 10 parameters and the sign of the fieldbus reference interact to produce
REFERENCE values (REF1 and REF2). Note, fieldbus references are bipolar, that is
they can be positive or negative.
ABB Drives profile
Parameter
1003 DIRECTION

Value setting

AI reference scaling

1 (FORWARD)

Resultant ref.
Max. ref

Fieldbus
reference

-163% -100%

100% 163%

-(Max. ref.)
1003 DIRECTION

2 (REVERSE)

Max. ref
Resultant ref.
Fieldbus
reference

-163% -100%

100% 163%

-(Max. ref.)
1003 DIRECTION

3 (REQUEST)

Resultant ref.
Max. ref

Fieldbus
reference

-(Max. ref.)

Embedded fieldbus

-163% -100%
100% 163%

ACS550-01/U1 Users Manual

237

Fieldbus adapter
Overview
The ACS550 can be set up to accept control from an external system using standard
serial communication protocols. When using serial communication, the ACS550 can
either:
receive all of its control information from the fieldbus, or
be controlled from some combination of fieldbus control and other available
control locations, such as digital or analog inputs and the control panel.
Fieldbus controller
Fieldbus

Other devices

Connect using either:


standard embedded fieldbus (EFB) at
terminals X1:2832
fieldbus adapter (FBA) module mounted
in slot 2 (option Rxxx)

Two basic serial communications configurations are available:


embedded fieldbus (EFB) See chapter Embedded fieldbus on page 203.
fieldbus adapter (FBA) With one of the optional FBA modules in the drives
expansion slot 2, the drive can communicate to a control system using one of the
following protocols:
PROFIBUS DP
Ethernet (Modbus/TCP, EtherNet/IP, EtherCAT, PROFINET IO, POWERLINK)
CANopen
DeviceNet
ControlNet.
The ACS550 detects automatically which communication protocol is used by the
plug-in fieldbus adapter. The default settings for each protocol assume that the
profile used is the protocols industry-standard drive profile (e.g. PROFIdrive for
PROFIBUS, AC/DC Drive for DeviceNet). All of the FBA protocols can also be
configured for the ABB Drives profile.
Configuration details depend on the protocol and profile used.These details are
provided in a users manual supplied with the FBA module.
Details for the ABB Drives profile (which apply for all protocols) are provided in
section ABB Drives profile technical data on page 248.

Fieldbus adapter

238

ACS550-01/U1 Users Manual

Control interface
In general, the basic control interface between the fieldbus system and the drive
consists of:
Output Words:
CONTROL WORD
REFERENCE (speed or frequency)
Others: The drive supports a maximum of 15 output words. Protocols limits
may further restrict the total.
Input Words:
STATUS WORD
Actual Value (speed or frequency)
Others: The drive supports a maximum of 15 input words. Protocols limits may
further restrict the total.
Note: The words output and input are used as seen from the fieldbus controller
point of view. For example an output describes data flow from the fieldbus controller
to the drive and appears as an input from the drive point of view.
The meanings of the controller interface words are not restricted by the ACS550.
However, the profile used may set particular meanings.
Fieldbus controller
Fieldbus

Process I/O
(cyclic)

Service
Messages
(Acyclic)

Control Word (CW)


References
Status Word (SW)
Actual Values

Parameter R/W Requests/Responses

Control Word
The CONTROL WORD is the principal means for controlling the drive from a fieldbus
system. The fieldbus controller sends the CONTROL WORD to the drive. The drive
switches between states according to the bit-coded instructions in the CONTROL
WORD. Using the CONTROL WORD requires that:
The drive is in remote (REM) control.
The serial communication channel is defined as the source for controlling
commands from EXT1 (set using parameters 1001 EXT1 COMMANDS and 1102
EXT1/EXT2 SEL).
The external plug-in fieldbus adapter is activated:

Fieldbus adapter

ACS550-01/U1 Users Manual

239

Parameter 9802 COMM PROT SEL = 4 (EXT FBA).


The external plug-in fieldbus adapter is configured to use the drive profile
mode or drive profile objects.
The content of the CONTROL WORD depends on the protocol/profile used. See the
users manual provided with the FBA module and/or section ABB Drives profile
technical data on page 248.
Status Word
The STATUS WORD is a 16-bit word containing status information, sent by the drive to
the fieldbus controller. The content of the STATUS WORD depends on the protocol/
profile used. See the users manual provided with the FBA module and/or section
ABB Drives profile technical data on page 248.
Reference
The contents of each REFERENCE word:
can be used, as speed or frequency reference
is a 16-bit word comprised of a sign bit and a 15-bit integer
Negative references (indicating reversed rotation direction) are indicated by the
twos complement of the corresponding positive reference value.
The use of a second reference (REF2) is supported only when a protocol is
configured for the ABB Drives profile.
Reference scaling is fieldbus type specific. See the users manual provided with the
FBA module and/or the following sections as appropriate:
Reference scaling on page 252 (ABB Drives profile technical data)
Reference scaling on page 256 (Generic profile technical data).
Actual Values
Actual Values are 16-bit words containing information on selected operations of the
drive. Drive Actual Values (for example, Group 10: START/STOP/DIR parameters)
can be mapped to Input Words using Group 51: EXT COMM MODULE parameters
(protocol-dependent, but typically parameters 51045126).

Planning
Network planning should address the following questions:
What types and quantities of devices must be connected to the network?
What control information must be sent down to the drives?
What feedback information must be sent from the drives to the controlling
system?

Fieldbus adapter

240

ACS550-01/U1 Users Manual

Mechanical and electrical installation FBA


WARNING! Connections should be made only while the drive is disconnected from
the power source.
Overview
The FBA (fieldbus adapter) is a plug-in module that fits in the drives expansion slot
2. The module is held in place with plastic retaining clips and two screws. The
screws also ground the shield for the module cable and connect the module GND
signals to the drive control board.
On installation of the module, electrical connection to the drive is automatically
established through the 34-pin connector.
Mounting procedure
1

Note: Install the input power and motor cables first.


1. Insert the module carefully into the drive expansion slot 2
until the retaining clips lock the module into position.

2. Fasten the two screws (included) to the stand-offs.


Note: Correct installation of the screws is essential for
fulfilling the EMC requirements and for proper operation of
the module.
3. Open the appropriate knockout in the conduit box and
install the cable clamp for the network cable.

X00301

4. Route the network cable through the cable clamp.


5. Connect the network cable to the modules network
connector.

5
6

6. Tighten the cable clamp.

7. Install the conduit box cover (1 screw).


8. For configuration information see the following:
section Communication set-up FBA on page 241
section Activate drive control functions FBA on page 241
The protocol specific documentation provided with the module.

Fieldbus adapter

4
X00302

ACS550-01/U1 Users Manual

241

Communication set-up FBA


Serial communication selection
To activate the serial communication, use parameter 9802 COMM PROT SEL. Set 9802
= 4 (EXT FBA).
Serial communication configuration
Setting 9802, together with mounting a particular FBA module, automatically sets the
appropriate default values in parameters that define the communication process.
These parameters and descriptions are defined in the users manual supplied with
the FBA module.
Parameter 5101 is automatically configured.
Parameters 51025126 are protocol-dependent and define, for example, the
profile used and additional I/O words. These parameters are referred to as the
fieldbus configuration parameters. See the users manual provided with the FBA
module for details on the fieldbus configuration parameters.
Parameter 5127 forces the validation of changes to parameters 51025126. If
parameter 5127 is not used, changes to parameters 51025126 take affect only
after the drive power is cycled.
Parameters 51285133 provide data about the FBA module currently installed
(e.g. component versions and status).
See Group 51: EXT COMM MODULE for parameter descriptions.

Activate drive control functions FBA


Fieldbus control of various drive functions requires configuration to:
tell the drive to accept fieldbus control of the function
define as a fieldbus input, any drive data required for control
define as a fieldbus output, any control data required by the drive.
The following sections describe, at a general level, the configuration required for
each control function. The last column in each table below is deliberately blank. See
the users manual supplied with the FBA module for the appropriate entry.
Start/Stop Direction control
Using the fieldbus for start/stop/direction control of the drive requires:
drive parameter values set as defined below
fieldbus controller supplied command(s) in the appropriate location. (The location
is defined by the Protocol Reference, which is protocol dependent.)
Drive parameter
1001 EXT1
COMMANDS

Value
10 (COMM)

Description

Protocol
reference

Start/Stop controlled by fieldbus with


Ext1 selected.

Fieldbus adapter

242

ACS550-01/U1 Users Manual

Drive parameter
1002 EXT2

Value

Description

10 (COMM)

Start/Stop by controlled fieldbus with


Ext2 selected.

3 (REQUEST)

Direction controlled by fieldbus.

COMMANDS

1003 DIRECTION

Protocol
reference

Input reference select


Using the fieldbus to provide input reference to the drive requires:
drive parameter value set as defined below
fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Drive parameter

Value

Description

1102

EXT1/EXT2 SEL

8 (COMM)

Ref. selected by fieldbus.


(Required only if 2 references used.)

1103

REF1 SELECT

Input reference 1supplied by fieldbus.

1106

REF2 SELECT

8 (COMM)
9 (COMM+AI1)
10 (COMM*AI1)
8 (COMM)
9 (COMM+AI)
10 (COMM*AI)

Protocol
reference

Input reference 2 supplied by fieldbus.


(Required only if 2 references used.)

Note: Multiple references are supported only when using the ABB Drives profile.
Scaling
Where required,
appropriate:

REFERENCES

can be scaled. See the following sections, as

Reference scaling on page 252 (ABB Drives profile technical data)


Reference scaling on page 256 (Generic profile technical data).
System control
Using the fieldbus for miscellaneous drive control requires:
drive parameter values set as defined below
fieldbus controller command(s) in the appropriate location. (The location is
defined by the Protocol Reference, which is protocol dependent.)
Drive parameter

Fieldbus adapter

Value

Description

1601

RUN ENABLE

7 (COMM) Run enable by fieldbus.

1604

FAULT RESET SEL

8 (COMM) Fault reset by fieldbus.

1607

PARAM SAVE

1 (SAVE)

Saves altered parameters to memory (then


value returns to 0).

Protocol
reference

ACS550-01/U1 Users Manual

243

Relay output control


Using the fieldbus for relay output control requires:
drive parameter values set as defined below
fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location. (The location is defined by the Protocol Reference, which is protocol
dependent.)
Drive parameter

Value

Protocol
reference

Description

1401

RELAY OUTPUT

1402

RELAY OUTPUT

35 (COMM)
Relay Output 1 controlled by fieldbus.
36 (COMM(-1)) Relay Output 2 controlled by fieldbus.

1403

RELAY OUTPUT

Relay Output 3 controlled by fieldbus.

14101

RELAY OUTPUT

Relay Output 4 controlled by fieldbus.

RELAY OUTPUT

Relay Output 5 controlled by fieldbus.

RELAY OUTPUT

Relay Output 6 controlled by fieldbus.

1411

1412
1

More than 3 relays requires the addition of a relay extension module.

Note: Relay status feedback occurs without configuration as defined below.


Drive parameter

Value

0122

RO

1-3 STATUS

Relay 13 status.

0123

RO

4-6 STATUS

Relay 46 status.

Protocol reference

Analog output control


Using the fieldbus for analog output control (e.g. PID setpoint) requires:
drive parameter values set as defined below
fieldbus controller supplied analog value(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Drive parameter
1501

AO1 CONTENT SEL

0135

COMM VALUE

1502

1505

AO1 CONTENT MIN

1506

FILTER AO1

1507

AO2 CONTENT SEL

0136

COMM VALUE

1508

1511

AO2 CONTENT MIN

1512

FILTER AO2

Protocol
reference

Value

Description

135 (COMM VALUE 1)

Analog Output 1 controlled by


writing to parameter 0135.

Used for scaling

Filter time constant for AO1.

Analog Output 2 controlled by


writing to parameter 0136.

Used for scaling

Filter time constant for AO2.

Set appropriate
values.

MAXIMUM AO1

136 (COMM VALUE 2)

Set appropriate
values.

MAXIMUM AO2

Fieldbus adapter

244

ACS550-01/U1 Users Manual

PID Control setpoint source


Using the following settings to select the fieldbus as the setpoint source for PID
loops:
Drive parameter

Value

4010 SET POINT SEL (Set 1)


4110

SET POINT SEL

(Set 2)

4210 SET POINT SEL (Ext/Trim)

Setting

Protocol
reference

8 (COMM VALUE 1) Setpoint is input reference 2


(+/-/* AI1)
9 (COMM+AI1)
10 (COMM*AI1)

Communication fault
When using fieldbus control, specify the drives action if serial communication is lost.
Drive parameter

Value

Description

3018 COMM FAULT FUNC

0 (NOT SEL)
1 (FAULT)
2 (CONST SP7)
3 (LAST SPEED)

3019 COMM FAULT TIME

Set time delay before acting on a communication loss.

Set for appropriate drive


response.

Feedback from the drive FBA


Inputs to the controller (drive outputs) have pre-defined meanings established by the
protocol. This feedback does not require drive configuration. The following table lists
a sample of feedback data. For a complete listing, see all parameters listed in
section Complete parameter descriptions on page 106.
Drive parameter
0102

SPEED

0103

OUTPUT FREQ

0104

CURRENT

0105

TORQUE

0106

POWER

0107

DC BUS VOLTAGE

0109

OUTPUT VOLTAGE

0301

FB CMD WORD

1 bit 0 (STOP)

0301

FB CMD WORD

1 bit 2 (REV)

0118

DI

Protocol reference

1-3 STATUS bit 0 (DI3)

Scaling
To scale the drive parameter values see the following sections, as appropriate:
Actual Value scaling on page 255 (ABB Drives profile technical data)
Actual Value scaling on page 257 (Generic profile technical data).

Fieldbus adapter

ACS550-01/U1 Users Manual

245

Diagnostics FBA
Fault handling
The ACS550 provides fault information as follows:
The control panel display shows a fault code and text. See chapter Diagnostics
on page 259 for a complete description.
Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT1 and 0413
store the most recent faults.

PREVIOUS FAULT2

For fieldbus access, the drive reports faults as a hexadecimal value, assigned
and coded according to the DRIVECOM specification. See the table below. Not all
profiles support requesting fault codes using this specification. For profiles that
support this specification, the profile documentation defines the proper fault
request process.
Drive fault code

Fieldbus fault code


(DRIVECOM
specification)

OVERCURRENT

2310h

DC OVERVOLT

3210h

DEV OVERTEMP

4210h

sHORT CIRC

2340h

Reserved

FF6Bh

DC UNDERVOLT

3220h

AI1 LOSS

8110h

AI2 LOSS

8110h

MOT OVERTEMP

4310h

10

PANEL LOSS

5300h

11

ID RUN FAIL

FF84h

12

MOTOR STALL

7121h

14

EXT FAULT

9000h

15

EXT FAULT

9001h

16

EARTH FAULT

2330h

17

Obsolete

FF6Ah

18

THERM FAIL

5210h

19

OPEX LINK

7500h

20

OPEX PWR

5414h

21

CURR MEAS

2211h

22

SUPPLY PHASE

3130h

23

ENCODER ERR

7301h

24

OVERSPEED

7310h

25

Reserved

FF80h

26

DRIVE ID

5400h

Fieldbus adapter

246

ACS550-01/U1 Users Manual

Drive fault code

Fieldbus adapter

Fieldbus fault code


(DRIVECOM
specification)

27

CONFIG FILE

28

SERIAL

1 ERR

7510h

29

EFB CON FILE

6306h

30

FORCE TRIP

FF90h

31

EFB

FF92h

32

EFB

FF93h

33

EFB

FF94h

34

MOTOR PHASE

FF56h

35

OUTP WIRING

FF95h

36

INCOMPATIBLE SW

630Fh

37

CB OVERTEMP

4110h

38

USER LOAD CURVE

FF6Bh

101

SERF CORRUPT

FF55h

102

Reserved

FF55h

103

SERF MACRO

FF55h

104

Reserved

FF55h

105

Reserved

FF55h

201

DSP T1 OVERLOAD

6100h

202

DSP T2 OVERLOAD

6100h

203

DSP T3 OVERLOAD

6100h

204

DSP STACK ERROR

6100h

205

Reserved (obsolete)

5000h

206

CB ID ERROR

5000h

207

EFB LOAD ERROR

6100h

1000

PAR HZRPM

6320h

1001

PAR PFC REF NEG

6320h

1002

Reserved (obsolete)

6320h

1003

PAR AI SCALE

6320h

1004

PAR AO SCALE

6320h

1005

PAR PCU

1006

PAR EXT RO

6320h

1007

PAR FIELDBUS MISSING

6320h

1008

PAR PFC MODE

6320h

1009

PAR PCU

1012

PAR PFC IO

6320h

1013

PAR PFC IO

6320h

1014

PAR PFC IO

6320h

1016

PAR USER LOAD C

630Fh

6320h

6320h

6320h

ACS550-01/U1 Users Manual

247

Serial communication diagnostics


Besides the drive fault codes, the FBA module has diagnostic tools. Refer to the
users manual supplied with the FBA module.

Fieldbus adapter

248

ACS550-01/U1 Users Manual

ABB Drives profile technical data


Overview
The ABB Drives profile provides a standard profile that can be used on multiple
protocols, including protocols available on the FBA module. This section describes
the ABB Drives profile implemented for FBA modules.
Control Word
As described earlier in section Control interface on page 238, the CONTROL
the principal means for controlling the drive from a fieldbus system.

WORD

is

The following table and the state diagram later in this sub-section describe the
content for the ABB Drives profile.

CONTROL WORD

ABB Drives profile (FBA) CONTROL WORD


Bit
0

Name

Value

Commanded state

OFF1
CONTROL

READY TO OPERATE

Enter READY TO OPERATE

EMERGENCY OFF

Drive ramps to stop according to currently


active deceleration ramp (2203 or 2205)
Normal command sequence:
Enter OFF1 ACTIVE
Proceed to READY TO SWITCH ON,
unless other interlocks (OFF2, OFF3) are
active.

OFF2
CONTROL

OPERATING

Continue operation (OFF2 inactive)

EMERGENCY OFF

Drive coasts to stop.


Normal command sequence:
Enter OFF2 ACTIVE
Proceed to SWITCHON INHIBITED

OFF3
CONTROL

OPERATING

Continue operation (OFF3 inactive)

EMERGENCY STOP

Drive stops within in time specified by


parameter 2208.
Normal command sequence:
Enter OFF3 ACTIVE
Proceed to SWITCH ON INHIBITED
WARNING! Be sure motor and
driven equipment can be stopped
using this mode.

INHIBIT
OPERATION

OPERATION
ENABLED

Enter OPERATION ENABLED (Note the Run


enable signal must be active. See 1601. If
1601 is set to COMM, this bit also actives
the Run Enable signal.)

OPERATION
INHIBITED

Inhibit operation. Enter OPERATION

NORMAL OPERATION

Enter RAMP FUNCTION GENERATOR:

RAMP_OUT_
ZERO

INHIBITED

ACCELERATION ENABLED

Fieldbus adapter

Comments

RFG OUT ZERO

Force ramp function generator output to


Zero. Drive ramps to stop (current and DC
voltage limits in force).

ACS550-01/U1 Users Manual

249

ABB Drives profile (FBA) CONTROL WORD


Bit
5

Name
RAMP_HOLD

Value

Commanded state

RFG OUT ENABLED

Comments
Enable ramp function.
Enter RAMP FUNCTION GENERATOR:
ACCELERATOR ENABLED

RFG OUT HOLD

Halt ramping (Ramp Function Generator


output held)

RAMP_IN_
ZERO

RFG INPUT ENABLED

Normal operation. Enter OPERATING

RFG INPUT ZERO

Force Ramp Function Generator input to


zero.

RESET

0=>1

RESET

Fault reset if an active fault exists (Enter


SWITCH-ON INHIBITED). Effective if 1604 =
COMM.

OPERATING

Continue normal operation

89

Unused

10

REMOTE_CMD

11

EXT CTRL LOC

1215

Fieldbus control enabled

CW =/ 0 or Ref =/ 0: Retain last CW and


Ref.
CW = 0 and Ref = 0: Fieldbus control
enabled.
Ref and deceleration/acceleration ramp
are locked.

EXT2 SELECT

Select external control location 2 (EXT2).


Effective if 1102 = COMM.

EXT1 SELECT

Select external control location 1 (EXT1).


Effective if 1102 = COMM.

Unused

Status Word
As described earlier in section Control interface on page 238, the contents of the
STATUS WORD is status information, sent by the drive to the master station. The
following table and the state diagram later in this sub-section describe the status
word content.
ABB Drives profile (FBA) STATUS WORD
Bit
0
1

2
3

Name
RDY_ON
RDY_RUN

RDY_REF
TRIPPED

Value

Description
(Correspond to states/boxes in the state diagram)

READY TO SWITCH ON

NOT READY TO SWITCH ON

READY TO OPERATE

OFF1 ACTIVE

OPERATION ENABLED

OPERATION INHIBITED

01

FAULT

No fault

Fieldbus adapter

250

ACS550-01/U1 Users Manual

ABB Drives profile (FBA) STATUS WORD


Bit
4
5
6

10

11
12

Name
OFF_2_STA
OFF_3_STA
SWC_ON_INHIB

ALARM

AT_SETPOINT

REMOTE

ABOVE_LIMIT

EXT CTRL LOC


EXT RUN ENABLE

13 15 Unused

Fieldbus adapter

Value

Description
(Correspond to states/boxes in the state diagram)

OFF2

inactive

OFF2 ACTIVE

OFF3

OFF3 ACTIVE

SWITCH-ON INHIBIT ACTIVE

SWITCH-ON INHIBIT NOT ACTIVE

Alarm (See section Alarm listing on page 267 for details


on alarms.)

No alarm

OPERATING.

Actual value is outside tolerance limits (not equal to


reference value).

Drive control location: REMOTE (EXT1 or EXT2)

Drive control location: LOCAL

Supervised parameters value > supervision high limit.


Bit remains 1 until supervised parameters value <
supervision low limit.
See Group 32: SUPERVISION.

Supervised parameters value < supervision low limit.


Bit remains 0 until supervised parameters value >
supervision high limit.
See Group 32: SUPERVISION.

External control location 2 (EXT2) selected

External control location 1 (EXT1) selected

External Run Enable signal received

No External Run Enable signal received

inactive

Actual value equals (within tolerance limits)


the reference value.

ACS550-01/U1 Users Manual

251

The state diagram below describes the start-stop function of CONTROL


and STATUS WORD (SW) bits.
From any state

From any state

(SW Bit5=0)

OFF3
ACTIVE

OFF2
ACTIVE

(CW)

From any state

Emergency Off
OFF2 (CW Bit1=0)

Emergency Stop
OFF3 (CW Bit2=0)

WORD

(SW Bit4=0)

Fault
FAULT

(SW Bit3=1)

(CW Bit7=1)

n(f)=0 / I=0
From any state
OFF1 (CW Bit0=0)
(SW Bit1=0)

SWITCH-ON
INHIBITED

MAINS OFF

OFF1
ACTIVE

Power ON

n(f)=0 / I=0

(CW Bit0=0)

A B C

NOT READY
TO SWITCH ON

OPERATION
INHIBITED

READY TO
SWITCH ON

B C D

READY TO
OPERATE

(CW Bit4=0)

(SW Bit1=1)

(CW Bit3=1 and


SW Bit12=1)
OPERATION
ENABLED

C D

(SW Bit2=1)

(CW Bit5=0)

(CW=xxxx x1xx xxx1 1111)


RFG OUTPUT
ENABLED

D
B

(CW=xxxx x1xx xx11 1111)

KEY
State
State change
CW = CONTROL WORD
SW = STATUS WORD
RFG = Ramp Function Generator
I = Param. 0104 CURRENT
f = Param. 0103 OUTPUT FREQ
n = Speed

(SW Bit0=1)

(CW= xxxx x1xx xxxx x111)

OPERATION INHIBITED

(CW Bit6=0)

(SW Bit0=0)

(CW xxxx x1xx xxxx x110)

(CW Bit3=0)
(SW Bit2=0)

(SW Bit6=1)

RFG: ACCELERATOR
ENABLED
C

(CW=xxxx x1xx x111 1111)


OPERATING

(SW Bit8=1)

Fieldbus adapter

252

ACS550-01/U1 Users Manual

Reference
As described earlier in section Control interface on page 238, the REFERENCE word is
a speed or frequency reference.
Reference scaling
The following table describes

REFERENCE

scaling for the ABB Drives profile.

ABB Drives Profile (FBA)


Range

Reference
type

REF1

-32767
+32767

REF2

-32767
+32767

Reference

Scaling

Remarks

Speed or
frequency

-20000 = -(par. 1105)


0=0
+20000 = (par. 1105)
(20000 corresponds to 100%)

Final reference limited by


1104/1105. Actual motor
speed limited by 2001/2002
(speed) or 2007/2008
(frequency).

Speed or
frequency

-10000 = -(par. 1108)


0=0
+10000 = (par. 1108)
(10000 corresponds to 100%)

Final reference limited by


1107/1108. Actual motor
speed limited by 2001/2002
(speed) or 2007/2008
(frequency).

Torque

-10000 = -(par. 1108)


0=0
+10000 = (par. 1108)
(10000 corresponds to 100%)

Final reference limited by


2015/2017 (torque1) or
2016/2018 (torque2).

PID
Reference

-10000 = -(par. 1108)


0=0
+10000 = (par. 1108)
(10000 corresponds to 100%)

Final reference limited by


4012/4013 (PID set1) or
4112/4113 (PID set2).

Note: The setting of parameter 1104


the scaling of references.

REF1 MIN

and 1107 REF2 MIN has no effect on

When parameter 1103 REF1 SELECT or 1106 REF2 SELECT is set to


COMM*AI1, the reference is scaled as follows:

COMM+AI1

or

ABB Drives profile (FBA)


Reference
REF1

Value setting
COMM+AI1

AI reference scaling
(%) + (AI (%) - 0.5 REF1 MAX (%))
Fieldbus reference
correction coefficient
(100 + 0.5 (Par. 1105)%

COMM

100%

(100 - 0.5 (par. 1105))%

Fieldbus adapter

AI1 input signal


0%

50%

100%

ACS550-01/U1 Users Manual

253

ABB Drives profile (FBA)


Reference
REF1

Value setting
COMM*AI1

AI reference scaling
COMM

(%) (AI (%) / 0.5 REF1 MAX (%))


Fieldbus reference
correction coefficient
200%

100%

(100 - 0.5 (par. 1105))%


0%
REF2

COMM+AI1

COMM

AI1 input signal


50%

100%

(%) + (AI (%) - 0.5 REF2 MAX (%))


Fieldbus reference
correction coefficient

(100 + 0.5 (Par. 1108)%

100%
AI1 input signal
(100 - 0.5 (par. 1108)%
0%
REF2

COMM*AI1

COMM

50%

100%

(%) (AI (%) / 0.5 REF2 MAX (%))


Fieldbus reference
correction coefficient
200%

100%
AI1 input signal

0%
0%

50%

100%

Fieldbus adapter

254

ACS550-01/U1 Users Manual

Reference handling
Use Group 10: START/STOP/DIR parameters to configure for control of rotation
direction for each control location (EXT1 and EXT2). The following diagrams illustrate
how group 10 parameters and the sign of the fieldbus reference interact to produce
REFERENCE values (REF1 and REF2). Note, fieldbus references are bipolar, that is
they can be positive or negative.
ABB Drives profile
Parameter
1003 DIRECTION

Value setting
1 (FORWARD)

AI reference scaling
Resultant ref.

Max. ref

Fieldbus
reference

-163% -100%

100% 163%

-(Max. ref.)
1003 DIRECTION

2 (REVERSE)

Max. ref
Resultant ref.
Fieldbus -163% -100%
reference

100% 163%

-(Max. ref.)
1003 DIRECTION

3 (REQUEST)

Resultant ref.

Max. ref

Fieldbus
reference

-(Max. ref.)

Fieldbus adapter

-163% -100%
100% 163%

ACS550-01/U1 Users Manual

255

Actual Value
As described earlier in section Control interface on page 238, Actual Values are
words containing drive values.
Actual Value scaling
The scaling of the integers sent to the fieldbus as Actual Values depends on the
resolution of the selected drive parameter. Except as noted for ACT1 and ACT2 below,
scale the feedback integer using the resolution listed for the parameter in section
Complete parameter list on page 91. For example:
Feedback integer

Parameter resolution

Scaled Value

0.1 mA

1 0.1 mA = 0.1 mA

10

0.1%

10 0.1% = 1%

Data words 5 and 6 are scaled as follows:


ABB Drives profile
Contents

Scaling

ACT1

ACTUAL SPEED

-20000 +20000 = -(par. 1105) +(par. 1105)

ACT2

TORQUE

-10000 +10000 = -100% +100%

Virtual addresses of the drive control


The virtual address area of the drive control is allocated as follows:
1

Control Word

Reference 1 (REF1)

Reference 2 (REF2)

Status Word

Actual Value 1 (ACT1)

Actual Value 2 (ACT2)

Fieldbus adapter

256

ACS550-01/U1 Users Manual

Generic profile technical data


Overview
The generic profile aims to fulfill the industry-standard drive profile for each protocol
(e.g. PROFIdrive for PROFIBUS, AC/DC Drive for DeviceNet).
Control Word
As described earlier in section Control interface on page 238, the CONTROL WORD is
the principal means for controlling the drive from a fieldbus system. For specific
CONTROL WORD content, see the users manual provided with the FBA module.
Status Word
As described earlier in section Control interface on page 238, the contents of the
is status information, sent by the drive to the master station. For
specific STATUS WORD content, see the users manual provided with the FBA module.
STATUS WORD

Reference
As described earlier in section Control interface on page 238, the REFERENCE word is
a speed or frequency reference.
Note: REF2 is not supported by the Generic Drive profiles.
Reference scaling
scaling is fieldbus type specific. However, at the drive, the meaning of a
100% REFERENCE value is fixed as described in the table below. For a detailed
description on the range and scaling of the REFERENCE, see the users manual
supplied with the FBA module.
REFERENCE

Generic profile
Reference
REF

Range
Fieldbus
specific

Reference
type

Scaling

Remarks

Speed

-100% = -(par. 9908)


0=0
+100 = (par. 9908)

Final reference limited by


1104/1105.
Actual motor speed limited by 2001/
2002 (speed).

Frequency

-100% = -(par. 9907)


0=0
+100 = (par. 9907)

Final reference limited by


1104/1105.
Actual motor speed limited by 2007/
2008 (frequency).

Actual Values
As described earlier in section Control interface on page 238, Actual Values are
words containing drive values.

Fieldbus adapter

ACS550-01/U1 Users Manual

257

Actual Value scaling


For Actual Values, scale the feedback integer using the parameters resolution. (See
section Complete parameter list on page 91 for parameter resolutions.) For example:
Feedback
integer

(Feedback integer) (Parameter resolution) =


Scaled Value

Parameter resolution

0.1 mA

1 0.1 mA = 0.1 mA

10

0.1%

10 0.1% = 1%

Where parameters are in percent, the Complete parameter list section specifies
what parameter corresponds to 100%. In such cases, to convert from percent to
engineering units, multiply by the value of the parameter that defines 100% and
divide by 100%. For example:
Feedback
integer
10
100

Parameter
resolution
0.1%
0.1%

Value of the
parameter that
defines 100%
1500 rpm1
500

Hz2

(Feedback integer) (Parameter resolution)


(Value of 100% ref.) / 100% =
Scaled Value
10 0.1% 1500 RPM / 100% = 15 rpm
100 0.1% 500 Hz / 100% = 50 Hz

Assuming, for the sake of this example, that the Actual Value uses parameter 9908 MOT NOM SPEED
as the 100% reference and that 9908 = 1500 rpm.
2 Assuming, for the sake of this example, that the Actual Value uses parameter 9907 MOT NOM FREQ
as the 100% reference and that 9907 = 500 Hz.

Actual Value mapping


See the users manual supplied with the FBA module.

Fieldbus adapter

258

Fieldbus adapter

ACS550-01/U1 Users Manual

ACS550-01/U1 Users Manual

259

Diagnostics
WARNING! Do not attempt any measurement, parts replacement or other service
procedure not described in this manual. Such action will void the warranty, may
endanger correct operation and increase downtime and expense.

WARNING! All electrical installation and maintenance work described in this chapter
should only be undertaken by qualified service personnel. The safety instructions in
chapter Safety instructions on page 5 must be followed.

Diagnostic displays
The drive detects error situations and reports them using:
the green and red LED on the body of the drive
the status LED on the control panel (if an Assistant Control Panel is attached to
the drive)
the control panel display (if a control panel is attached to the drive)
the Fault Word and Alarm Word parameter bits (parameters 0305 to 0309). See
Group 03: FB ACTUAL SIGNALS on page 112 for the bit definitions.
The form of the display depends on the severity of the error. You can specify the
severity for many errors by directing the drive to:
ignore the error situation
report the situation as an alarm
report the situation as a fault.
Red Faults
The drive signals that it has detected a severe error, or fault, by:
enabling the red LED on the drive (LED is either steady on or blinking)
showing the steady red status LED on the control panel (if attached to the drive)
setting an appropriate bit in a Fault Word parameter (0305 to 0307)
overriding the control panel display with the display
of a fault code in the Fault mode (figures on the
right)

LOC

FAULT 7
AI1 LOSS

stopping the motor (if it was on).


The fault code on the control panel display is
temporary. Pressing any of the following keys removes
the fault message: MENU, ENTER, UP, or DOWN key.

FAULT

00:00
LOC

F0007

FWD

Diagnostics

260

ACS550-01/U1 Users Manual

The message reappears after a few seconds if the control panel is not touched and
the fault is still active.
Flashing green Alarms
For less severe errors, called alarms, the diagnostic display is advisory. For these
situations, the drive is simply reporting that it had detected something unusual. In
these situations, the drive:
flashes the green LED on the drive (does not apply to alarms that arise from
control panel operation errors)
flashes the green LED on the control panel (if attached to the drive)
sets an appropriate bit in an Alarm Word parameter (0308 or 0309). See Group
03: FB ACTUAL SIGNALS on page 112 for the bit definitions
overrides the control panel display with the display
of an alarm code and/or name in the Fault mode
(figures on the right).
Alarm messages disappear from the control panel
display after a few seconds. The message returns
periodically as long as the alarm condition exists.

LOC

ALARM

ALARM 2008
PANEL LOSS
00:00
LOC

A2008

FWD

Correcting faults
The recommended corrective action for faults is:
Use the table in section Fault listing below to find and address the root cause of
the problem.
Reset the drive. See section Fault resetting on page 265.
Fault listing
The following table lists the faults by code number and describes each. The fault
name is the long form shown in the Fault mode of the Assistant Control Panel when
the fault occurs. The fault names shown (for Assistant Control Panel only) in the
Fault Logger mode (see page 61) and the fault names for parameter 0401 LAST
FAULT may be shorter.

Diagnostics

Fault
code

Fault name in
panel

OVERCURRENT

Description and recommended corrective action


Output current is excessive. Check for and correct:
Excessive motor load.
Insufficient acceleration time (parameters 2202 ACCELER TIME 1 and
2205 ACCELER TIME 2).
Faulty motor, motor cables or connections.

ACS550-01/U1 Users Manual

Fault
code

261

Fault name in
panel

Description and recommended corrective action

DC OVERVOLT

Intermediate circuit DC voltage is excessive. Check for and correct:


Static or transient overvoltages in the input power supply.
Insufficient deceleration time (parameters 2203 DECELER TIME 1 and
2206 DECELER TIME 2).
Undersized brake chopper (if present).
Verify that overvoltage controller is ON (using parameter 2005).

DEV OVERTEMP

Drive heatsink is overheated. Temperature is at or above limit.


R1R4: 115 C (239 F)
R5, R6: 125 C (257 F)
Check for and correct:
Fan failure.
Obstructions in the air flow.
Dirt or dust coating on the heat sink.
Excessive ambient temperature.
Excessive motor load.

SHORT CIRC

Fault current. Check for and correct:


A short-circuit in the motor cable(s) or motor.
Supply disturbances.

RESERVED

Not used.

DC UNDERVOLT

Intermediate circuit DC voltage is not sufficient. Check for and correct:


Missing phase in the input power supply.
Blown fuse.
Undervoltage on mains.

AI1 LOSS

Analog input 1 loss. Analog input value is less than AI1 FAULT LIMIT (3021).
Check for and correct:
Source and connection for analog input.
Parameter settings for AI1 FAULT LIMIT (3021) and 3001 AI<MIN FUNCTION.

AI2 LOSS

Analog input 2 loss. Analog input value is less than AI2 FAULT LIMIT (3022).
Check for and correct:
Source and connection for analog input.
Parameter settings for AI2 FAULT LIMIT (3022) and 3001 AI<MIN FUNCTION.

MOT OVERTEMP

Motor is too hot, based on either the drives estimate or on temperature


feedback.
Check for overloaded motor.
Adjust the parameters used for the estimate (30053009).
Check the temperature sensors and Group 35: MOTOR TEMP MEAS
parameters.

10

PANEL LOSS

Panel communication is lost and either:


Drive is in local control mode (the control panel displays LOC), or
Drive is in remote control mode (REM) and is parameterized to accept
start/stop, direction or reference from the control panel.
To correct check:
Communication lines and connections.
Parameter 3002 PANEL COMM ERR.
Parameters in Group 10: START/STOP/DIR and Group 11:
REFERENCE SELECT (if drive operation is REM).

Diagnostics

262

Diagnostics

ACS550-01/U1 Users Manual

Fault
code

Fault name in
panel

11

ID RUN FAIL

The Motor ID Run was not completed successfully. Check for and correct:
Motor connections.
Motor parameters 99059909.

12

MOTOR STALL

Motor or process stall. Motor is operating in the stall region. Check for and
correct:
Excessive load.
Insufficient motor power.
Parameters 30103012.

13

RESERVED

Not used.

14

EXT FAULT

Digital input defined to report first external fault is active. See parameter
3003 EXTERNAL FAULT 1.

15

EXT FAULT

Digital input defined to report second external fault is active. See parameter
3004 EXTERNAL FAULT 2.

16

EARTH FAULT

Possible ground fault detected in the motor or motor cables. The drive
monitors for ground faults while the drive is running and while the drive is
not running. Detection is more sensitive when the drive is not running and
can produce false positives.
Possible corrections:
Check for/correct faults in the input wiring.
Verify that motor cable does not exceed maximum specified length.
Decrease the detection level for earth fault with parameter 3028 EARTH
FAULT LVL.
A delta grounded input power supply and motor cables with high
capacitance may result in erroneous error reports during non-running
tests. To disable response to fault monitoring when the drive is not
running, use parameter 3023 WIRING FAULT. To disable response to all
ground fault monitoring, use parameter 3017 EARTH FAULT.
Note: Disabling earth fault (ground fault) may void the warranty.

17

OBSOLETE

Not used.

18

THERM FAIL

Internal fault. The thermistor measuring the internal temperature of the


drive is open or shorted. Contact your local ABB representative.

19

OPEX LINK

Internal fault. A communication-related problem has been detected on the


fiber optic link between the control and OINT boards. Contact your local
ABB representative.

20

OPEX PWR

Internal fault. Exceptionally low voltage detected on the OINT power supply.
Contact your local ABB representative.

21

CURR MEAS

Internal fault. Current measurement is out of range. Contact your local ABB
representative.

22

SUPPLY PHASE

Ripple voltage in the DC link is too high. Check for and correct:
Missing mains phase.
Blown fuse.

Description and recommended corrective action

ACS550-01/U1 Users Manual

263

Fault
code

Fault name in
panel

23

ENCODER ERR

The drive is not detecting a valid encoder signal. Check for and correct:
Encoder presence and proper connection (reverse wired = channel A
connected to terminal of channel B or vice versa, loose connection or
short circuit).
Voltage logic levels are outside of the specified range.
A working and properly connected Pulse Encoder Interface Module,
OTAC-01.
Wrong value entered in parameter 5001 PULSE NR. A wrong value will
only be detected if the error is such that the calculated slip is greater
than 4 times the rated slip of the motor.
Encoder is not being used, but parameter 5002 ENCODER ENABLE =
1 (ENABLE).

24

OVERSPEED

Motor speed is greater than 120% of the larger (in magnitude) of 2001
or 2002 MAXIMUM SPEED. Check for and correct:
Parameter settings for 2001 and 2002.
Adequacy of motor braking torque.
Applicability of torque control.
Brake chopper and resistor.

Description and recommended corrective action

MINIMUM SPEED

25

RESERVED

Not used.

26

DRIVE ID

Internal fault. Configuration Block Drive ID is not valid. Contact your local
ABB representative.

27

CONFIG FILE

Internal configuration file has an error. Contact your local ABB


representative.

28

SERIAL

29

EFB CON FILE

Error in reading the configuration file for the embedded fieldbus.

30

FORCE TRIP

Fault trip forced by the fieldbus. See the fieldbus Users Manual.

31

EFB

32

EFB

33

EFB

34

MOTOR PHASE

Fault in the motor circuit. One of the motor phases is lost. Check for and
correct:
Motor fault.
Motor cable fault.
Thermal relay fault (if used).
Internal fault.

35

OUTP WIRING

Incorrect input power and motor cable connection (i.e., input power cable is
connected to drive motor connection). The fault can be erroneously
declared if the drive is faulty or the input power is a delta grounded system
and the motor cable capacitance is large.
This fault can be disabled by using parameter 3023 WIRING FAULT.
Check input power connections. Check grounding.

1 ERR

Fieldbus communication has timed out. Check for and correct:


Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME).
Communication settings (Group 51: EXT COMM MODULE or Group 53:
EFB PROTOCOL as appropriate).
Poor connections and/or noise on line.

Fault code reserved for the embedded fieldbus (EFB) protocol application.
The meaning is protocol dependent.

Diagnostics

264

ACS550-01/U1 Users Manual

Fault
code

Fault name in
panel

36

INCOMPATIBLE
SW

The drive cannot use the software.


Internal fault.
The loaded software is not compatible with the drive.
Call support representative.

37

CB OVERTEMP

Drive control board is overheated. The fault trip limit is 88 C. Check for and
correct:
Excessive ambient temperature.
Fan failure.
Obstructions in the air flow.
Not for drives with an OMIO control board.

38

USER LOAD
CURVE

Condition defined by parameter 3701 USER LOAD C MODE has been valid
longer than the time defined by 3703 USER LOAD C TIME.

101
199

SYSTEM ERROR

Error internal to the drive. Contact your local ABB representative and report
the error number.

201
299

SYSTEM ERROR

Error in the system. Contact your local ABB representative and report the
error number.

UNKNOWN
DRIVE TYPE:

Wrong type of panel, i.e. panel that supports drive X but not the ACS550,
has been connected to the ACS550.

Description and recommended corrective action

ACS550
SUPPORTED
DRIVES: X

Faults that indicate conflicts in the parameter settings are listed below.

Diagnostics

Fault
code

Fault name in
panel

1000

PAR HZRPM

Parameter values are inconsistent. Check for any of the following:


2001 MINIMUM SPEED > 2002 MAXIMUM SPEED.
2007 MINIMUM FREQ > 2008 MAXIMUM FREQ.
2001 MINIMUM SPEED / 9908 MOTOR NOM SPEED is outside proper range
(> 50).
2002 MAXIMUM SPEED / 9908 MOTOR NOM SPEED is outside proper range
(> 50).
2007 MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range
(> 50).
2008 MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range
(> 50).

1001

PAR PFC REF


NEG

Parameter values are inconsistent. Check for the following:


2007 MINIMUM FREQ is negative, when 8123 PFC ENABLE is active.

1002

RESERVED

Not used.

1003

PAR AI SCALE

Parameter values are inconsistent. Check for any of the following:


1301 MINIMUM AI1 > 1302 MAXIMUM AI1.
1304 MINIMUM AI2 > 1305 MAXIMUM AI2.

1004

PAR AO SCALE

Parameter values are inconsistent. Check for any of the following:


1504 MINIMUM AO1 > 1505 MAXIMUM AO1.
1510 MINIMUM AO2 > 1511 MAXIMUM AO2.

Description and recommended corrective action

ACS550-01/U1 Users Manual

265

Fault
code

Fault name in
panel

1005

PAR PCU

1006

PAR EXT RO

Parameter values are inconsistent. Check for the following:


Extension relay module not connected and
14101412 RELAY OUTPUTS 46 have non-zero values.

1007

PAR FIELDBUS
MISSING

Parameter values are inconsistent. Check for and correct:


A parameter is set for fieldbus control (e.g. 1001 EXT1 COMMANDS = 10
(COMM)), but 9802 COMM PROT SEL = 0.

1008

PAR PFC MODE

Parameter values are inconsistent 9904 MOTOR CTRL MODE must be = 3


(SCALAR:FREQ), when 8123 PFC ENABLE is activated.

1009

PAR PCU

1010/
1011

RESERVED

1012

PAR PFC IO

IO configuration is not complete not enough relays are parameterized to


PFC. Or, a conflict exists between Group 14: RELAY OUTPUTS, parameter
8117 NR OF AUX MOT and parameter 8118 AUTOCHNG INTERV.

1013

PAR PFC IO

IO configuration is not complete the actual number of PFC motors


(parameter 8127, MOTORS) does not match the PFC motors in Group 14:
RELAY OUTPUTS and parameter 8118 AUTOCHNG INTERV.

1014

PAR PFC IO

IO configuration is not complete the drive is unable to allocate a digital


input (interlock) for each PFC motor (parameters 8120 INTERLOCKS and
8127 MOTORS).

1015

RESERVED

Not used.

1016

PAR USER LOAD C

Parameter values for the user load curve are inconsistent. Check that the
following conditions are met:
3704 LOAD FREQ 1 < 3707 LOAD FREQ 2 < 3710 LOAD FREQ 3 <
3713 LOAD FREQ 4 < 3716 LOAD FREQ 5.
3705 LOAD TORQ LOW 1 < 3706 LOAD TORQ HIGH 1.
3708 LOAD TORQ LOW 2 < 3709 LOAD TORQ HIGH 2.
3711 LOAD TORQ LOW 3 < 3712 LOAD TORQ HIGH 3.
3714 LOAD TORQ LOW 4 < 3715 LOAD TORQ HIGH 4.
3717 LOAD TORQ LOW 5 < 3718 LOAD TORQ HIGH 5.

Description and recommended corrective action


Parameter values for power control are inconsistent: Improper motor
nominal kVA or motor nominal power. Check for the following:
1.1 < (9906 MOTOR NOM CURR 9905 MOTOR NOM VOLT 1.73 / PN) < 3.0
where: PN = 1000 9909 MOTOR NOM POWER (if units are kW)
or PN = 746 9909 MOTOR NOM POWER (if units are hp, e.g. in US)

Parameter values for power control are inconsistent: Improper motor


nominal frequency or speed. Check for both of the following:
1 < (60 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED < 16
0.8 < 9908 MOTOR NOM SPEED /
(120 9907 MOTOR NOM FREQ / Motor Poles) < 0.992
Not used.

Fault resetting
The ACS550 can be configured to automatically reset certain faults. Refer to
parameter Group 31: AUTOMATIC RESET.
WARNING! If an external source for start command is selected and it is active, the
ACS550 may start immediately after fault reset.

Diagnostics

266

ACS550-01/U1 Users Manual

Flashing red LED


To reset the drive for faults indicated by a flashing red LED:
Turn the power off for 5 minutes.
Red LED
To reset the drive for faults indicated by a red LED (on, not flashing), correct the
problem and do one of the following:
Press RESET from the control panel.
Turn the power off for 5 minutes.
Depending on the value of 1604 FAULT RESET SEL, the following could also be used to
reset the drive:
digital input
serial communication.
When the fault has been corrected, the motor can be started.
History
For reference, the last three fault codes are stored into parameters 0401, 0412,
0413. For the most recent fault (identified by parameter 0401), the drive stores
additional data (in parameters 04020411) to aid in troubleshooting a problem. For
example, parameter 0404 stores the motor speed at the time of the fault.
The Assistant Control Panel provides additional information about the fault history.
See section Fault Logger mode on page 61 for more information.
To clear the fault history (all of the Group 04: FAULT HISTORY parameters):
1. Using the control panel in the Parameters mode, select parameter 0401.
2. Press EDIT (or ENTER on the Basic Control Panel).
3. Press UP and DOWN at the same time.
4. Press SAVE.

Correcting alarms
The recommended corrective action for alarms is:
Determine if the alarm requires any corrective action (action is not always
required).
Use the table in section Alarm listing below to find and address the root cause of
the problem.

Diagnostics

ACS550-01/U1 Users Manual

267

Alarm listing
The following table lists the alarms by code number and describes each.
Alarm
code

Display

Description

2001

OVERCURRENT

Current limiting controller is active. Check for and correct:


Excessive motor load.
Insufficient acceleration time (parameters 2202 ACCELER TIME 1 and
2205 ACCELER TIME 2).
Faulty motor, motor cables or connections.

2002

OVERVOLTAGE

Overvoltage controller is active. Check for and correct:


Static or transient overvoltages in the input power supply.
Insufficient deceleration time (parameters 2203 DECELER TIME 1 and
2206 DECELER TIME 2).

2003

UNDERVOLTAGE

Undervoltage controller is active. Check for and correct:


Undervoltage on mains.

2004

DIR LOCK

The change in direction being attempted is not allowed. Either:


Do not attempt to change the direction of motor rotation, or
Change parameter 1003 DIRECTION to allow direction change (if
reverse operation is safe).

2005

IO COMM

Fieldbus communication has timed out. Check for and correct:


Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME).
Communication settings (Group 51: EXT COMM MODULE or
Group 53: EFB PROTOCOL as appropriate).
Poor connections and/or noise on line.

2006

AI1 LOSS

Analog input 1 is lost, or value is less than the minimum setting.


Check:
Input source and connections.
Parameter that sets the minimum (3021).
Parameter that sets the alarm/fault operation (3001),

2007

AI2 LOSS

Analog input 2 is lost, or value is less than the minimum setting.


Check:
Input source and connections.
Parameter that sets the minimum (3022).
Parameter that sets the alarm/fault operation (3001).

2008

PANEL LOSS

Panel communication is lost and either:


Drive is in local control mode (the control panel displays LOC), or
Drive is in remote control mode (REM) and is parameterized to
accept start/stop, direction or reference from the control panel.
To correct check:
Communication lines and connections.
Parameter 3002 PANEL COMM ERR.
Parameters in Group 10: START/STOP/DIR and Group 11:
REFERENCE SELECT (if drive operation is REM).

Diagnostics

268

ACS550-01/U1 Users Manual

Alarm
code

Diagnostics

Display

Description

2009

DEVICE
OVERTEMP

Drive heatsink is hot. This alarm warns that a DEVICE OVERTEMP fault
may be near.
R1R4: 100 C (212 F)
R5, R6: 110 C (230 F)
Check for and correct:
Fan failure.
Obstructions in the air flow.
Dirt or dust coating on the heat sink.
Excessive ambient temperature.
Excessive motor load.

2010

MOTOR TEMP

Motor is hot, based on either the drives estimate or on temperature


feedback. This alarm warns that a MOT OVERTEMP fault trip may be
near. Check:
Check for overloaded motor.
Adjust the parameters used for the estimate (30053009).
Check the temperature sensors and Group 35: MOTOR TEMP
MEAS.

2011

RESERVED

Not used.

2012

MOTOR STALL

Motor is operating in the stall region. This alarm warns that a MOTOR
STALL fault trip may be near.

2013
(Note 1)

AUTORESET

This alarm warns that the drive is about to perform an automatic fault
reset, which may start the motor.
To control automatic reset, use Group 31: AUTOMATIC RESET.

2014
(Note 1)

AUTOCHANGE

This alarm warns that the PFC autochange function is active.


To control PFC, use Group 81: PFC CONTROL and the PFC macro
on page 84.

2015

PFC I LOCK

This alarm warns that the PFC interlocks are active, which means that
the drive cannot start the following:
Any motor (when Autochange is used).
The speed regulated motor (when Autochange is not used).

2016/
2017

RESERVED

Not used.

2018
(Note 1)

PID SLEEP

This alarm warns that the PID sleep function is active, which means
that the motor could accelerate when the PID sleep function ends.
To control PID sleep, use parameters 40224026 or 41224126.

2019

ID RUN

Performing ID Run.

2020

RESERVED

Not used.

2021

START ENABLE
MISSING

This alarm warns that the Start Enable 1 signal is missing.


To control Start Enable 1 function, use parameter 1608.
To correct, check:
Digital input configuration.
Communication settings.

2022

START ENABLE
MISSING

This alarm warns that the Start Enable 2 signal is missing.


To control Start Enable 2 function, use parameter 1609.
To correct, check:
Digital input configuration.
Communication settings.

ACS550-01/U1 Users Manual

Alarm
code

269

Display

Description

2023

EMERGENCY
STOP

Emergency stop activated.

2024

ENCODER ERROR

The drive is not detecting a valid encoder signal. Check for and
correct:
Encoder presence and proper connection (reverse wired, loose
connection or short circuit).
Voltage logic levels are outside of the specified range.
A working and properly connected Pulse Encoder Interface Module,
OTAC-01.
Wrong value entered in parameter 5001 PULSE NR. A wrong value
will only be detected if the error is such that the calculated slip is
greater than 4 times the rated slip of the motor.
Encoder is not being used, but parameter 5002 ENCODER ENABLE =
1 (ENABLE).

2025

FIRST START

Signals that a the drive is performing a First Start evaluation of motor


characteristics. This is normal the first time the motor is run after motor
parameters are entered or changed. See parameter 9910 ID RUN for a
description of motor models.

2026

RESERVED

Not used.

2027

USER LOAD
CURVE

This alarm warns that the condition defined by parameter 3701 USER
LOAD C MODE has been valid longer than half of the time defined by
3703 USER LOAD C TIME.

2028

START DELAY

Shown during the Start delay. See parameter 2113 START DELAY.

Note 1. Even when the relay output is configured to indicate alarm conditions (e.g. parameter
1401 RELAY OUTPUT 1 = 5 (ALARM) or 16 (FLT/ALARM)), this alarm is not indicated by a relay
output.

Alarm codes (Basic Control Panel)


The Basic Control Panel indicates control panel alarms with a code, A5xxx. The
following table lists the alarm codes and descriptions.
Code

Description

5001

Drive is not responding.

5002

The communication profile is incompatible with the drive.

5010

The panels parameter backup file is corrupted.

5011

Drive is controlled from another source.

5012

Rotation direction is locked.

5013

Button is disabled, because start is inhibited.

5014

Button is disabled, because drive is faulted.

5015

Button is disabled, because local mode lock is on.

5018

Parameter default value cant be found.

5019

Writing a non-zero value is prohibited (can only write a zero value).

5020

Group or parameter does not exist or parameter value is inconsistent.

5021

Group or parameter is hidden.

5022

Group or parameter is write protected.

5023

Modification is not allowed while the drive is running.

Diagnostics

270

ACS550-01/U1 Users Manual

Code

Diagnostics

Description

5024

Drive is busy, try again.

5025

Write is not allowed while upload or download is in progress.

5026

Value is at or below low limit.

5027

Value is at or above high limit.

5028

Value is invalid doesn't match any values in the discrete values list.

5029

Memory is not ready, try again.

5030

Request is invalid.

5031

Drive is not ready, e.g due to low DC voltage.

5032

Parameter error was detected.

5040

Selected parameter set cant be found in the current parameter backup.

5041

Parameter backup doesn't fit into memory.

5042

Selected parameter set cant be found in the current parameter backup.

5043

No start inhibit was granted.

5044

Parameter backup versions do not match.

5050

Parameter upload was aborted.

5051

File error was detected.

5052

Parameter upload attempt has failed.

5060

Parameter download was aborted.

5062

Parameter download attempt has failed.

5070

Panel backup memory write error was detected.

5071

Panel backup memory read error was detected.

5080

Operation is not allowed, because the drive is not in local mode.

5081

Operation is not allowed, because a fault is active.

5083

Operation is not allowed, because parameter lock is not open.

5084

Operation is not allowed, because drive is busy, try again.

5085

Download is not allowed, because drive types are incompatible.

5086

Download is not allowed, because drive models are incompatible.

5087

Download is not allowed, because parameter sets do not match.

5088

Operation failed, because a drive memory error was detected.

5089

Download failed, because a CRC error was detected.

5090

Download failed, because a data processing error was detected.

5091

Operation failed, because a parameter error was detected.

5092

Download failed, because parameter sets do not match.

ACS550-01/U1 Users Manual

271

Maintenance
WARNING! Read chapter Safety instructions on page 5 before performing any
maintenance on the equipment. Ignoring the safety instructions can cause injury or
death.

Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Maintenance

Interval

Instruction

Heatsink temperature check


and cleaning

Depends on the dustiness of the


environment (every 612
months)

See Heatsink on page 271.

Main cooling fan replacement

Every six years

See Main fan replacement on


page 272.

Internal enclosure cooling fan


replacement
(IP54 / UL type 12 drives)

Every three years.

See Internal enclosure fan


replacement on 274.

Capacitor reforming

Every year when stored

See Reforming on page 275.

Capacitor replacement
(frame sizes R5 and R6)

Every nine years

See Replacement on page 275.

Replace battery in the Assistant


Control Panel

Every ten years

See Battery on page 275.

Consult your local ABB representative for more details on the maintenance. On the
Internet, go to www.abb.com/drives and select Service Maintenance.

Heatsink
The heatsink fins accumulate dust from the cooling air. Since a dusty heatsink is less
efficient at cooling the drive, overtemperature faults become more likely. In a
normal environment (not dusty, not clean) check the heatsink annually, in a dusty
environment check more often.
Clean the heatsink as follows (when necessary):
1. Remove power from the drive.
2. Remove the cooling fan (see section Main fan replacement on page 272).
3. Blow clean compressed air (not humid) from bottom to top and simultaneously use a
vacuum cleaner at the air outlet to trap the dust.
Note: If there is a risk of the dust entering adjoining equipment, perform the cleaning
in another room.

Maintenance

272

ACS550-01/U1 Users Manual

4. Reinstall the cooling fan.


5. Restore power.

Main fan replacement


Fan failure can be predicted by the increasing noise from fan bearings and the
gradual rise in the heatsink temperature in spite of heatsink cleaning. If the drive is
operated in a critical part of a process, fan replacement is recommended once these
symptoms start appearing. Replacement fans are available from ABB. Do not use
other than ABB specified spare parts.
Frame sizes R1R4
To replace the fan:

1. Remove power from the drive.

2. Remove drive cover.


3. For frame size:

R1, R2: Press together the retaining clips on the fan


cover sides, and lift.
R3, R4: Press in on the lever located on the left side
of the fan mount, and rotate the fan up and out.
4. Disconnect the fan cable.
5. Reinstall the fan in reverse order.

X0021

6. Restore power.
Frame size R5
To replace the fan:
1. Remove power from drive.
2. Remove the screws attaching the fan.

Bottom view
3

3. Remove the fan: Swing the fan out on its hinges.


4. Disconnect the fan cable.
5. Reinstall the fan in reverse order.
6. Restore power.
Arrows in the fan show the directions of the rotation and air flow.

Maintenance

X5023

ACS550-01/U1 Users Manual

273

Frame size R6
To replace the fan:
1. Remove power from the drive.

2. Remove the screw attaching the fan casing


and let the casing lean down against the
limiters.
3. Slide out the cable connector and disconnect
it.

4. Take off the casing and replace the fan onto


the casings pins.
5. Reinstall the casing in reverse order.
6. Restore power.
4

Maintenance

274

ACS550-01/U1 Users Manual

Internal enclosure fan replacement


IP54 / UL type 12 enclosures have an additional internal fan to circulate air inside the
enclosure.
Frame sizes R1R4
To replace the internal enclosure fan in frame sizes R1 to
R3 (located at the top of the drive) and R4 (located in front
of the drive):
1. Remove power from the drive.

4
3
5

R1R3

2. Remove the front cover.


3. The housing that holds the fan in place has barbed
retaining clips at each corner. Press all four clips toward
the center to release the barbs.
FM

4. When the clips/barbs are free, pull the housing up to


remove from the drive.
5. Disconnect the fan cable.

R4

6. Install the fan in reverse order, noting that:


The fan air flow is up (refer to the arrow on fan).

The fan wire harness is toward the front.


The notched housing barb is located in the right-rear
corner.
The fan cable connects just forward of the fan at the
top of the drive.
Frame sizes R5 and R6
To replace the internal enclosure fan in frame sizes R5 or R6:
1. Remove power from the drive.
2. Remove the front cover.
3. Lift the fan out and disconnect the cable.
4. Install the fan in reverse order.
5. Restore power.

Maintenance

3AUA000000404

ACS550-01/U1 Users Manual

275

Capacitors
Reforming
The drive DC link capacitors need to be reformed (re-aged) if the drive has been
non-operational for more than one year. Without reforming, capacitors may be
damaged when the drive starts to operate. It is therefore recommended to reform the
capacitors once a year. See section Serial number on page 17 for how to check the
date of manufacture from the serial number shown on the drive labels.
For information on reforming the capacitors, refer to Guide for Capacitor Reforming
in ACS50, ACS55, ACS150, ACS310, ACS350, ACS355, ACS550, ACH550 and
R1-R4 OINT-/SINTboards (3AFE68735190 [English]), available on the Internet (go
to www.abb.com and enter the code in the Search field).
Replacement
The drive intermediate circuit employs several electrolytic capacitors. Capacitor life
can be prolonged by lowering the ambient temperature.
It is not possible to predict a capacitor failure. Capacitor failure is usually followed by
a input power fuse failure or a fault trip. Contact ABB if capacitor failure is suspected.
Replacements for frame size R5 and R6 are available from ABB. Do not use other
than ABB specified spare parts.

Control panel
Cleaning
Use a soft damp cloth to clean the control panel. Avoid harsh cleaners which could
scratch the display window.
Battery
A battery is only used in Assistant Control Panels that have the clock function
available and enabled. The battery keeps the clock operating in memory during
power interruptions.
To remove the battery, use a coin to rotate the battery holder on the back of the
control panel. Replace the battery with type CR2032.
Note: The battery is NOT required for any control panel or drive function, except the
clock.

Maintenance

276

Maintenance

ACS550-01/U1 Users Manual

ACS550-01/U1 Users Manual

277

Technical data
Ratings
By type designation, the table below provides ratings for the ACS550 adjustable
speed AC drive, including:
IEC ratings
NEMA ratings (shaded columns)
frame size.
Ratings, 208240 V drives
Abbreviated column headers are described in section Symbols on page 279.
Type

Normal use
I2N
A

ACS550-x1see below

Heavy-duty use

PN
kW

I2hd
A

PN
hp

Phd
kW

Phd
hp

Frame
size

Three-phase supply voltage, 208240 V


-04A6-2

4.6

0.75

-06A6-2

6.6

1.1

1.5

-07A5-2

7.5

1.5

-012A-2

11.8

2.2

-017A-2

16.7

-024A-2

24.2

5.5

-031A-2

30.8

-046A-2

46.2

-059A-2

59.4

3.5

0.55

0.75

R1

4.6

0.75

R1

6.6

1.1

1.5

R1

7.5

1.5

R1

11.8

2.2

R1

7.5

16.7

R2

7.5

10

24.2

5.5

7.5

R2

11

15

30.8

7.5

10

R3

15

20

46.2

11

15

R3

-075A-2

74.8

18.5

25

59.4

15

20

R4

-088A-2

88.0

22

30

74.8

18.5

25

R4

-114A-2

114

30

40

88.0

22

30

R4

-143A-2

143

37

50

114

30

40

R6

-178A-2

178

45

60

150

37

50

R6

-221A-2

221

55

75

178

45

60

R6

-248A-2

248

75

100

192

55

75

R6
00467918.xls C

Technical data

278

ACS550-01/U1 Users Manual

Ratings, 380480 V drives


Abbreviated column headers are described in section Symbols on page 279.
Type

Normal use
I2N
A

ACS550-x1see below

Heavy-duty use

PN
kW

I2hd
A

PN
hp

Phd
kW

Phd
hp

Frame
size

Three-phase supply voltage, 380480 V


-03A3-4

3.3

1.1

1.5

-04A1-4

4.1

1.5

-05A4-4

5.4

2.2

Note 1

-06A9-4

6.9

-08A8-4

8.8

-012A-4

11.9

5.5

-015A-4

15.4

7.5

10

-023A-4

23

11

15

-031A-4

31

15

20

0.75

R1

3.3

1.1

1.5

R1

4.1

1.5

Note 1

R1

5.4

2.2

R1

6.9

R1

7.5

8.8

R1

11.9

5.5

7.5

R2

15.4

7.5

10

R2

23

11

15

R3

-038A-4

38

18.5

25

31

15

20

R3

-045A-4

45

22

30

38

18.5

25

R3

-059A-4

59

30

40

44

22

30

R4

-072A-4

72

37

50

59

30

40

R4

-078A-4

77

Note 2

60

72

Note 2

50

R4

-087A-4

87

45

Note 1

72

37

Note 1

R4

-097A-4

97

Note 2

75

77

Note 2

60

R4

-125A-4

125

55

Note 1

87

45

Note 1

R5

-125A-4

125

Note 2

100

96

Note 2

75

R5

-157A-4

157

75

125

124

55

100

R6

-180A-4

180

90

150

156

75

125

R6

-195A-4

205

110

Note 1

162

90

Note 1

R6

-246A-4

246

132

200

192

110

150

R6

-290A-4

290

160

Note 1

246

132

200

1. Not available in ACS550-U1 series.


2. Not available in ACS550-01 series.

Technical data

2.4

R6
00467918.xls C

ACS550-01/U1 Users Manual

279

Ratings, 500600 V drives


Abbreviated column headers are described in section Symbols on page 279.
Type

Normal use
I2N
A

ACS550-U1see below

Heavy-duty use

PN
kW

I2hd
A

PN
hp

Phd
kW

Phd
hp

Frame
size

Three-phase supply voltage, 500600 V (Note 1)


-02A7-6

2.7

1.5

2.4

1.1

1.5

R2

-03A9-6

3.9

2.2

2.7

1.5

R2

-06A1-6

6.1

3.9

2.2

R2

-09A0-6

9.0

5.5

7.5

6.1

R2

-011A-6

11

7.5

10

9.0

5.5

7.5

R2

-017A-6

17

11

15

11

7.5

10

R2

-022A-6

22

15

20

17

11

15

R3

-027A-6

27

18.5

25

22

15

20

R3

-032A-6

32

22

30

27

18.5

25

R4

-041A-6

41

30

40

32

22

30

R4

-052A-6

52

37

50

41

30

40

R4

-062A-6

62

45

60

52

37

50

R4

-077A-6

77

55

75

62

45

60

R6

-099A-6

99

75

100

77

55

75

R6

-125A-6

125

90

125

99

75

100

R6

-144A-6

144

110

150

125

90

125

1. Not available in ACS550-01 series.

R6
00467918.xls C

Symbols
Typical ratings:
Normal use (10% overload capability)
I2N
continuous rms current. 10% overload is allowed for one minute in ten minutes.
PN
typical motor power in normal use. The kilowatt power ratings apply to most IEC, 4-pole
motors. The horsepower ratings apply to most 4-pole NEMA motors.
Heavy-duty use (50% overload capability)
I2hd
continuous rms current. 50% overload is allowed for one minute in ten minutes.
Phd
typical motor power in heavy duty use. The kilowatt power ratings apply to most IEC, 4-pole
motors. The horsepower ratings apply to most 4-pole NEMA motors.

Sizing
The current ratings are the same regardless of the supply voltage within one voltage
range. To achieve the rated motor power given in the table, the rated current of the
drive must be higher than or equal to the rated motor current. Also note that:
the ratings apply for ambient temperature of 40 C (104 F)
the maximum allowed motor shaft power is limited to 1.5 Phd. If the limit is
exceeded, motor torque and current are automatically restricted. The function
protects the input bridge of the drive against overload.
In multimotor systems, the output current of the drive must be equal to or greater
than the calculated sum of the input currents of all motors.

Technical data

280

ACS550-01/U1 Users Manual

Derating
The load capacity (current and power) decreases for certain situations, as defined
below. In such situations, where full motor power is required, oversize the drive so
that the derated value provides sufficient capacity.
For example, if your application requires 15.4 A of motor current and a 8 kHz
switching frequency, calculate the appropriate drive size requirement as follows:
The minimum size required = 15.4 A / 0.80 = 19.25 A
Where: 0.80 is the derating for 8 kHz switching frequency (see section Switching frequency derating
on page 280).

Referring to I2N in the ratings tables (starting from page 277), the following drives
exceed the I2N requirement of 19.25 A: ACS550-x1-023A-4, or ACS550-x1-024A-2.
Temperature derating
In the temperature range +40 C 50 C (+104 F122 F), the rated output current
is decreased 1% for every 1 C (1.8 F) above +40 C (+104 F). Calculate the
output current by multiplying the current given in the rating table by the derating
factor.
Example If the ambient temperature is 50 C (+122 F), the derating factor is
100% - 1%/C 10 C = 90% or 0.90.
The output current is then 0.90 I2N or 0.90 I2hd.
Altitude derating
In altitudes 10004000 m (330013,200 ft) above sea level, the derating is 1% for
every 100 m (330 ft). If the installation site is higher than 2000 m (6600 ft) above sea
level, contact your local ABB representative for further information.
Single phase supply derating
For 208240 V series drives, a single phase supply can be used. In that case, the
derating is 50%.
Switching frequency derating
When using the 8 kHz switching frequency (parameter 2606),
derate all rated currents and powers (including drive's overload currents) to 80%.
When using the 12 kHz switching frequency (parameter 2606),
derate all rated currents and powers (including drive's overload currents) to 65%
(to 50% for 600 V, R4 frame sizes, that is for ACS550-U1-032A-6 ACS550-U1062A-6),
derate ambient temperature maximum to 30 C (86 F).
Note: The continuous maximum current is limited to I2hd.
Note: Setting parameter 2607 SWITCH FREQ CTRL = 1 (ON) allows the drive to reduce
the switching frequency if/when the drives internal temperature exceeds 80 C (with
12 kHz switching frequency) or 90 C (with 8 kHz switching frequency). See the
parameter description for 2607 for details.

Technical data

ACS550-01/U1 Users Manual

281

Input power connections


WARNING! Do not operate the drive outside the nominal input line voltage range.
Overvoltage can result in permanent damage to the drive.
Input power specifications
Input power (mains) connection specifications

Voltage (U1)

Prospective shortcircuit current


(IEC 629)

208/220/230/240 V AC 3-phase (or 1-phase) -15%+10% for


ACS550-x1-xxxx-2.
380/400/415/440/460/480 V AC 3-phase -15%+10% for ACS550-x1xxxx-4.
500/525/575/600 V AC 3-phase -15%+10% for ACS550-U1-xxxx-6.
Maximum allowed prospective short-circuit current in the supply is 100 kA
providing that the input power cable of the drive is protected with
appropriate fuses. US: 100 000 AIC.

Frequency

4863 Hz

Imbalance

Max. 3% of nominal phase to phase input voltage

Fundamental power
factor (cos phi1)
Cable temperature
rating

0.98 (at nominal load)


90 C (194 F) rating minimum

Disconnecting device for isolation


Install a hand-operated input disconnecting device (disconnecting means) between
the AC power source and the drive. The disconnecting device must be of a type that
can be locked to the open position for installation and maintenance work.
Europe: To meet the European Union Directives, according to standard
EN 60204-1, Safety of Machinery, the disconnecting device must be one of the
following types:
a switch-disconnector of utilization category AC-23B (EN 60947-3)
a disconnector having an auxiliary contact that in all cases causes switching
devices to break the load circuit before the opening of the main contacts of the
disconnector (EN 60947-3)
a circuit breaker suitable for isolation in accordance with EN 60947-2.
Other regions: The disconnecting device must conform to the applicable safety
regulations.
Fuses
Branch circuit protection must be provided by the end user and sized per national
and local electric codes. The following tables provide fuse recommendations for
short circuit protection on the drives input power.
The rated fuse currents given in the tables are the maximums for the
mentioned fuse types. If smaller fuse ratings are used, check that the fuse rms
current rating is larger than the input current.

Technical data

282

ACS550-01/U1 Users Manual

Check that the operating time of the fuse is below 0.5 seconds. The operating
time depends on the fuse type, the supply network impedance as well as the crosssectional area, material and length of the supply cable. In case the 0.5 seconds
operating time is exceeded with the gG or T fuses, ultra rapid (aR) fuses will in most
cases reduce the operating time to an acceptable level.
Fuses, 208240 V drives
ACS550-x1see below

Input current
A

-04A6-2

4.6

-06A6-2

6.6

-07A5-2

7.5

-012A-2

Input power (mains) fuses


IEC 60269 gG (A)

UL Class T (A)

Bussmann type

10

10

JJS-10

11.8

16

15

JJS-15

-017A-2

16.7

25

25

JJS-25

-024A-2

24.2

30

JJS-30

-031A-2

30.8

40

40

JJS-40

-046A-2

46.2

63

60

JJS-60

-059A-2

59.4

80

JJS-80

-075A-2

74.8

80

100

JJS-100

-088A-2

88.0

100

110

JJS-110

-114A-2

114

125

150

JJS-150

-143A-2

143

200

200

JJS-200

-178A-2

178

250

250

JJS-250

-221A-2

221

315

300

JJS-300

-248A-2

248

350

JJS-350
00467918.xls C

Fuses, 380480 V drives


ACS550-x1see below

Technical data

Input current
A

-03A3-4

3.3

-04A1-4

4.1

-05A4-4

5.4

-06A9-4

6.9

-08A8-4

8.8

-012A-4

11.9

-015A-4

15.4

-023A-4

23

-031A-4

31

-038A-4

38

-045A-4

45

-059A-4

59

-072A-4

72

-078A-4

77

Input power (mains) fuses


IEC 60269 gG (A)

UL Class T (A)

Bussmann type

10

JJS-10

15

JJS-15

20

JJS-20

25

30

JJS-30

35

40

JJS-40

50

50

JJS-50

60

JJS-60

63

80

JJS-80

80

90

JJS-90

100

JJS-100

10

16

ACS550-01/U1 Users Manual

ACS550-x1see below
-087A-4

283

Input current
A
87

Input power (mains) fuses


IEC 60269 gG (A)

UL Class T (A)

Bussmann type

125

125

JJS-125

-097A-4

97

-125A-4

125

160

175

JJS-175

-157A-4

157

200

200

JJS-200

-180A-4

180

250

250

JJS-250

315

350

JJS-350

-195A-4

205

-246A-4

246

-290A-4

290
00467918.xls C

Fuses, 500600 V drives


ACS550-U1see below

Input current
A

-02A7-6

2.7

-03A9-6

3.9

-06A1-6

6.1

-09A0-6

9.0

-011A-6

11

Input power (mains) fuses


IEC 60269 gG (A)

UL Class T (A)

Bussmann type

10

10

JJS-10

16

15

JJS-15

25

25

JJS-25

35

40

JJS-40

-017A-6

17

-022A-6

22

-027A-6

27

-032A-6

32

-041A-6

41

50

50

JJS-50

-052A-6

52

60

60

JJS-60

-062A-6

62

80

80

JJS-80

-077A-6

77

100

JJS-100

-099A-6

99

125

150

JJS-150

-125A-6

125

160

175

JJS-175

-144A-6

144

200

200

JJS-200
00467918.xls C

Emergency stop devices


The overall design of the installation must include emergency stop devices and any
other safety equipment that may be needed. Pressing STOP on the drives control
panel does NOT:
generate an emergency stop of the motor
separate the drive from dangerous potential.

Technical data

284

ACS550-01/U1 Users Manual

Input power cables/wiring


Input wiring can be any of:
a four conductor cable (three phases and ground/protective earth). Shielding is
not required.
four insulated conductors routed through conduit.
Size wiring according to local safety regulations, appropriate input voltage and the
drives load current.
Note: The conductor must be less than the maximum limit defined by the terminal
size. Check the maximum wire size according to the table in section Drives power
connection terminals on page 286.
The table below lists copper and aluminium cable types for different load currents.
These recommendations apply only for the conditions listed at the top of the table.
IEC

NEC

Based on:
EN 60204-1 and IEC 60364-5-2
PVC insulation
30 C (86 F) ambient temperature
70 C (158 F) surface temperature
cables with concentric copper shield
not more than nine cables laid on cable ladder
side by side.
Max. load
current
A

Technical data

Cu cable
mm2

Max. load
current
A

Al cable
mm2

Based on:
NEC Table 310-16 for copper wires
90 C (194 F) wire insulation
40 C (104 F) ambient temperature
not more than three current-carrying
conductors in raceway or cable, or earth
(directly buried)
copper cables with concentric copper shield.
Max. load
current
A

Cu wire size
AWG/kcmil

14

31.5

22.8

14

20

32.5

27.3

12

27

34

36.4

10

34

36

50.1

47

310

68.3

62

316

61

3x25

86.5

79

325

75

3x35

100

98

335

91

350

118

119

350

117

370

137

153

370

143

395

155

1/0

186

395

165

3120

178

2/0

215

3120

191

3150

205

3/0

249

3150

218

3185

237

4/0

284

3185

257

3240

264

250 MCM or 2 1

330

3240

274

3 (350)

291

300 MCM or 2 1/0

285

2 (395)

319

350 MCM or 2 2/0

ACS550-01/U1 Users Manual

285

Ground connections
For personnel safety, proper operation and reduction of electromagnetic emission/
pick-up, the drive and the motor must be grounded at the installation site.
Conductors must be adequately sized as required by safety regulations.
Power cable shields must be connected to the drive PE terminal in order to meet
safety regulations.
Power cable shields are suitable for use as equipment grounding conductors only
when the shield conductors are adequately sized as required by safety
regulations.
In multiple drive installations, do not connect drive terminals in series.
Corner-grounded TN systems
WARNING! Do not attempt to install or remove the EMC filter screws EM1, EM3, F1
or F2 while power is applied to the drives input terminals.
Corner-grounded TN systems are defined in the following table. In such systems,
disconnect the internal ground connection through the EMC filter capacitors (do this
also if the grounding configuration of the system is unknown), see section
Disconnecting the internal EMC filter on page 27.
Corner-grounded TN systems EMC filter must be disconnected
Grounded at the
corner of the
delta

L1

Grounded at the
mid point of a
delta leg

L1

L2
L3

L2
L3
Single phase,
grounded at an
end point

L1

Three phase
Variac without
solidly grounded
neutral

L1
L1
L2

L2
L3
L3

The EMC filter capacitors make an internal ground connection


that reduces electro-magnetic emission. Where EMC (electromagnetic compatibility) is a concern, and the system is
symmetrically grounded, the EMC filter may be connected.
For reference, the diagram on the right illustrates a
symmetrically grounded TN system (TN-S system).

L1

L2
L3

Technical data

286

ACS550-01/U1 Users Manual

IT systems
WARNING! Do not attempt to install or remove the EMC filter screws EM1, EM3, F1
or F2 while power is applied to the drives input terminals.
For IT systems (an ungrounded power system or a high-resistance-grounded [over
30 ohm] power system):
Disconnect the ground connection to the internal EMC filter, see section
Disconnecting the internal EMC filter on page 27.
Where EMC requirements exist, check for excessive emission propagated to
neighboring low voltage networks. In some cases, the natural suppression in
transformers and cables is sufficient. If in doubt, use a supply transformer with
static screening between the primary and secondary windings.
Do NOT install an external RFI/EMC filter. Using an EMC filter grounds the input
power through the filter capacitors, which could be dangerous and could damage
the drive.
Drives power connection terminals
The following table provides specifications for the drives power connection
terminals.
Note: See the recommended cable sizes for different load currents in section Input
power cables/wiring on page 284.
U1, V1, W1
U2, V2, W2
BRK+, UDC+ terminals

Frame
size

Maximum
wire size

Tightening
torque

Maximum
wire size

Tightening
torque

mm 2

AWG

mm2

AWG

Nm

lbft

mm2

AWG

Nm

lbft

R1

0.75

18

10

1.4

10

1.4

R2

0.75

18

10

1.4

10

1.4

R3

2.5

14

25

2.5

1.8

16

1.8

1.3

R4

10

50

1/0

5.6

25

1.5

R5

10

70

2/0

15

11

70

2/0

15

11

R6

951

3/01

240

350 MCM

40

30

95

3/0

Technical data

Minimum
wire size

Earthing PE terminal

00467918.xls C

See section Power terminal considerations R6 frame size on page 287.

ACS550-01/U1 Users Manual

287

Power terminal considerations R6 frame size


WARNING! For R6 power terminals, if screw-on terminal lugs are supplied, they can
only be used for wire sizes that are 95 mm2 (3/0 AWG) or larger. Smaller wires will
loosen and may damage the drive. They require crimp-on ring lugs as described
below.
Crimp-on ring lugs
On the R6 frame size, if screw-on terminal lugs are
5
supplied but the cable size used is less than 95
2
3
mm (3/0 AWG), or if no screw-on terminal lugs
are supplied at all, use crimp-on ring lugs
4
according to the following procedure.
1. Select appropriate ring lugs from the following
table.
2. Remove the screw-on terminal lugs, if supplied.
3. Attach the ring lugs to the drive end of the cables.
X60002

4. Isolate the ends of the ring lugs with insulating


tape or shrink tubing.
5. Attach the ring lugs to the drive.
Wire size
mm 2

kcmil/
AWG

16

25

35

50

55

1/0

Manufacturer

Ring lug

Crimping
tool

No. of
crimps

Burndy

YAV6C-L2

MY29-3

Ilsco

CCL-6-38

ILC-10

Burndy

YA4C-L4BOX

MY29-3

Ilsco

CCL-4-38

MT-25

Burndy

YA2C-L4BOX

MY29-3

Ilsco

CRC-2

IDT-12

Ilsco

CCL-2-38

MT-25

Burndy

YA1C-L4BOX

MY29-3

Ilsco

CRA-1-38

IDT-12

Ilsco

CCL-1-38

MT-25

Thomas & Betts

54148

TBM-8

Burndy

YA25-L4BOX

MY29-3

Ilsco

CRB-0

IDT-12

Ilsco

CCL-1/0-38

MT-25

Thomas & Betts

54109

TBM-8

Technical data

288

ACS550-01/U1 Users Manual

Wire size
mm2

70

95

95

kcmil/
AWG

2/0

3/0

3/0

Manufacturer

Ring lug

Crimping
tool

No. of
crimps

Burndy

YAL26T38

MY29-3

Ilsco

CRA-2/0

IDT-12

Ilsco

CCL-2/0-38

MT-25

Thomas & Betts

54110

TBM-8

Burndy

YAL27T38

MY29-3

Ilsco

CRA-3/0

IDT-12

Ilsco

CCL-3/0-38

MT-25

Thomas & Betts

54111

TBM-8

Burndy

YA28R4

MY29-3

Ilsco

CRA-4/0

IDT-12

Ilsco

CCL-4/0-38

MT-25

Thomas & Betts

54112

TBM-8

Screw-on terminal lugs


Use the following procedure to attach cables
if screw-on terminal lugs are supplied and
the cable size is 95 mm2 (3/0 AWG) or
larger.
1. Attach the supplied screw-on lugs to the
drive end of the cables.
2. Attach screw-on lugs to the drive.

Technical data

X60003

X60001

ACS550-01/U1 Users Manual

289

Motor connections
WARNING! Never connect line power to the drive output terminals: U2, V2 or W2.
Line voltage applied to the output can result in permanent damage to the drive. If
frequent bypassing is required, use mechanically interlocked switches or contactors.

WARNING! Do not connect any motor with a nominal voltage less than one half of
the drives nominal input voltage.

WARNING! Disconnect the drive before conducting any voltage tolerance (Hi-Pot)
test or insulation resistance (Megger) test on the motor or motor cables. Do not
conduct these tests on the drive.
Motor connection specifications
Motor connection specifications
Voltage (U 2)

0U1, 3-phase symmetrical, Umax at the field weakening point

Frequency

0500 Hz

Frequency resolution
Current
Field weakening point

0.01 Hz
See section Ratings on page 277.
10500 Hz
Selectable. See the availability in the table below.
1, 2, 4 and 8 kHz
208240 V All types

Switching frequency

380480 V All types


500600 V All types

Cable temperature rating


Maximum motor cable
length

12 kHz
Frame sizes R1R4 in scalar
control mode
Frame sizes R1R4 (except
ACS550-01-097A-4) in scalar
control mode
Frame sizes R2R4 in scalar
control mode

90 C (194 F) rating minimum.


See section Motor cable lengths on page 289.

Motor cable lengths


Maximum motor cable lengths for 400 V and 600 V drives are given in the sections
below.
In multimotor systems, the calculated sum of all motor cable lengths must not
exceed the maximum motor cable length given in the appropriate table below.

Technical data

290

ACS550-01/U1 Users Manual

Motor cable length for 400 V drives


The table below shows the maximum motor cable lengths for 400 V drives with
different switching frequencies. Examples for using the table are also given.
Maximum cable length for 400 V drives
EMC limits
Second environment
(category C31)
Frame
size

1 kHz
m

ft

Operational limits
First environment
(category C21)

Basic unit

4 kHz

8 kHz

1 kHz

4 kHz

8 kHz

1/4 kHz

ft

ft

ft

ft

ft

ft

8/12 kHz
m

ft

With
du/dt
filters
m

ft

R1

300 980 300 980 300 980 300 980 300 980 300 980 100 330 100 330 150 490

R2

300 980 300 980 300 980 300 980 100 330 30

R3

300 980 300 980 300 980 300 980 75 245 75 245 200 660 100 330 250 820

R4

300 980 300 980 300 980 300 980 75 245 75 245 200 660 100 330 300 980

R5

100 330 100 330 100 330 100 330 100 330 100 330 300 980 1502 4902 300 980

R6

100 330 100 330

100 330 100 330

98 200 660 100 330 250 820

300 980 1502 4902 300 980

See the new terms in section IEC/EN 61800-3:2004 Definitions on page 311.

12 kHz switching frequency is not available.

Not tested.

Sine filters further extend the cable lengths.

Under heading Operational limits, the Basic unit columns define the cable lengths
with which the basic drive unit works without problems within the drive specification,
without installing any further options. Column With du/dt filters defines the cable
lengths when an external du/dt filter is used.
The columns under heading EMC limits show the maximum cable lengths with
which the units have been tested for EMC emissions. The factory guarantees that
these cable lengths meet the EMC standard requirements.
If external sine filters are installed, longer cable lengths can be used. With sine filters
the limiting factors are the voltage drop of the cable, which has to be taken into
account in engineering, as well as the EMC limits (where applicable).
The default switching frequency is 4 kHz.
WARNING! Using a motor cable longer than specified in the table above may cause
permanent damage to the drive.
Examples for using the table:
Requirements

Checking and conclusions

R1 frame size,
Check operational limits for R1 and 8 kHz -> for a 150 m (490 ft)
8 kHz fsw,
cable a du/dt filter is needed.
Category C2,
150 m (490 ft) cable Check EMC limits -> EMC requirements for Category C2 are met
with a 150 m (490 ft) cable.

Technical data

ACS550-01/U1 Users Manual

291

Requirements

Checking and conclusions

R3 frame size,
4 kHz fsw,
Category C3,
300 m (980 ft) cable

Check operational limits for R3 and 4 kHz -> a 300 m (980 ft) cable
cannot be used even with a du/dt filter. A sine filter must be used and
the voltage drop of the cable must be taken into account in the
installation.
Check EMC limits -> EMC requirements for Category C3 are met
with a 300 m (980 ft) cable.

R5 frame size,
Check operational limits for R5 and 8 kHz -> for a 150 m (490 ft)
8 kHz fsw,
cable the basic unit is sufficient.
Category C3,
150 m (490 ft) cable Check EMC limits -> EMC requirements for Category C3 cannot be
met with a 300 m (980 ft) cable. The installation configuration is not
possible. An EMC plan is recommended to overcome the situation.
R6 frame size,
4 kHz fsw,
EMC limits not
applicable,
150 m (490 ft) cable

Check operational limits for R6 and 4 kHz -> for a 150 m (490 ft)
cable the basic unit is sufficient.
EMC limits do not need to be checked as there are no EMC
requirements.

Motor cable length for 600 V drives


The table below shows the maximum motor cable lengths for 600 V drives with
different switching frequencies. As the 600 V drives are not CE approved, cable
lengths for EMC limits are not given.
Maximum cable length for 600 V drives
Operational limits

1/4 kHz

8/12 kHz

Frame
size

ft

ft

R2

100

330

100

330

R3R4

200

660

100

330

R6

300

980

1502

4902

12 kHz switching frequency is not available.

WARNING! Using a motor cable longer than specified in the table above may cause
permanent damage to the drive.
Motor thermal protection
According to regulations, the motor must be protected against thermal overload and
the current must be switched off when overload is detected. The drive includes a
motor thermal protection function that protects the motor and switches off the current
when necessary. Depending on a drive parameter value (see parameter 3501
SENSOR TYPE), the function either monitors a calculated temperature value (based on
a motor thermal model, see parameters 3005 MOT THERM PROT 3009 BREAK POINT
FREQ) or an actual temperature indication given by motor temperature sensors (see
Group 35: MOTOR TEMP MEAS). The user can tune the thermal model further by
feeding in additional motor and load data.

Technical data

292

ACS550-01/U1 Users Manual

The most common temperature sensors are:


motor sizes IEC180225: thermal switch (e.g. Klixon)
motor sizes IEC200250 and larger: PTC or PT100.
Ground fault protection
ACS550 internal fault logic detects ground faults in the drive, motor, or motor cable.
This fault logic:
is NOT a personal safety or fire protection feature
can be disabled using parameter 3017 EARTH FAULT
Note: Disabling earth fault (ground fault) may void the warranty.
could be tripped by leakage currents (input power to ground) associated with long
high capacitance motor cables.
Grounding and routing
Motor cable shielding
Motor cables require shielding using conduit, armored cable or shielded cable.
Conduit When using conduit:
Bridge joints with a ground conductor bonded to the conduit on each side of
the joint.
Bond conduit run to the drive enclosure.
Use a separate conduit run for motor cables (also separate input power and
control cables).
Use a separate conduit run for each drive.
Armored cable When using armored cable:
Use six-conductor (3 phases and 3 grounds), type MC continuous corrugated
aluminium armor cable with symmetrical grounds.
Armored motor cable can share a cable tray with input power cables, but not
with control cables.
Shielded cable For shielded cable details, see section Motor cable
requirements for CE & C-Tick compliance on page 293.
Grounding
See section Ground connections on page 285.
For CE compliant installations and installations where EMC emissions must be
minimized, see section Effective motor cable shields on page 294.
Drives motor connection terminals
The drives motor and input power terminals have the same specifications. See
section Drives power connection terminals on page 286.

Technical data

ACS550-01/U1 Users Manual

293

Motor cable requirements for CE & C-Tick compliance


The requirements in this section apply for CE or C-Tick compliance.
Minimum requirement (CE & C-Tick)
The motor cable must be a symmetrical three conductor cable with a concentric PE
conductor or a four conductor cable with a concentric shield, however, a symmetrical
constructed PE conductor is always recommended. The following figure shows the
minimum requirement for the motor cable shield (for example, MCMK, Draka NK
Cables).
Insulation jacket

Copper wire shield

Inner insulation

Cable core

Recommendation for conductor layout


The following figure compares conductor layout features in motor cables.
Recommended (CE & C-Tick)

Allowed (CE & C-Tick)

Symmetrical shielded cable: three phase


conductors and a concentric or otherwise
symmetrically constructed PE conductor, and a
shield
PE
conductor
and shield

Shield

A separate PE conductor is required if the


conductivity of the cable shield is < 50% of the
conductivity of the phase conductor.
Shield

PE

Shield
Not allowed for motor cables (CE & C-Tick)
A four-conductor system: three phase
conductors and a protective conductor, without a
shield.
PE

Allowed for motor cables with phase


conductor cross section up to 10 mm2.

Technical data

294

ACS550-01/U1 Users Manual

Effective motor cable shields


The general rule for cable shield effectiveness is: the better and tighter the cables
shield, the lower the radiated emission level. The following figure shows an example
of an effective construction (for example lflex-Servo-FD 780 CP, Lappkabel or
MCCMK, NK Cables).
Insulation jacket

Braided metallic shield

Inner insulator

L2

L3

L1

EN 61800-3 compliant motor cables


The most efficient EMC filtering can be achieved by following these rules:
Motor cables must have an effective shield as described in section Effective
motor cable shields on page 294.
Motor cable shield wires must be twisted together into a bundle (pig-tail) the
bundle length must be less than five times its width and connected to the
terminal marked
(at the bottom right-hand corner of the drive).
At the motor end, the motor cable shield must be earthed 360 degrees with an
EMC cable gland, or the shield wires must be twisted together into a bundle (pigtail) not longer than five times its width and connected to the PE terminal of the
motor.
See section Motor cable length for 400 V drives, columns EMC limits on page
290 to check the maximum motor cable lengths and the need for filters for 400 V
drives for IEC/EN 61800-3 compliance.
WARNING! Do not use RFI/EMC filters on IT systems.

Technical data

ACS550-01/U1 Users Manual

295

Brake components
Availability
Braking availability for ACS550 drives, by frame size is:
R1 and R2 a built-in brake chopper is standard equipment. Add appropriate
resistor, as determined using the following section. Resistors are available from
ABB.
R3R6 does not include an internal brake chopper. Connect a chopper and a
resistor, or a brake unit to the DC link terminals on the drive. Contact your ABB
representative for appropriate parts.
Selecting the braking resistors (frame sizes R1 and R2)
Braking resistor must meet three requirements:
Resistance must be always higher than the minimum value RMIN defined for the
drive type in the following tables. Never use resistance below this value.
Resistance must be low enough to be able to produce the desired braking torque.
To achieve the maximum braking torque (the larger of 150% of heavy duty or
110% of nominal duty), the resistance must not exceed RMAX. If maximum
braking torque is not necessary, resistor values can exceed RMAX.
The resistor power rating must be high enough to dissipate the braking power.
This requirement involves many factors:
the maximum continuous power rating for the resistor(s)
the rate at which the resistor changes temperature (resistor thermal time
constant)
maximum braking time ON If the regeneration (braking) power is larger than
the resistor rated power, there is a limit to the ON time, or the resistor
overheats before the OFF period begins.
minimum braking time OFF If the regeneration (braking) power is larger than
the resistor rated power, the OFF time must be large enough for the resistor to
cool between ON periods.
Braking ON

Time

Braking OFF
ON time

OFF time
Cycle time

Duty cycle =

ON time
Cycle time

the peak braking power requirement


type of braking (deceleration to zero vs. overhauling load) During
deceleration to zero, the generated power steadily decreases, averaging half
of the peak power. For an overhauling load, the braking is countering an
external force (gravity for example) and the braking power is constant. The
total heat generated from an overhauling load is double the heat generated
from deceleration to zero speed (for the same peak torque and ON time).

Technical data

296

ACS550-01/U1 Users Manual

Power

Deceleration curve

Avg. braking power


overhauling load

Overhauling load
curve

Avg. braking power


during deceleration
to zero

Time

Temperature
2x
x

Time

The many variables in the last requirement above are most easily dealt with using
the following tables.
First, determine your maximum braking time ON (ONMAX), minimum braking time
OFF (OFFMIN) and load type (deceleration or overhauling load).
Calculate duty cycle:
Duty cycle

ON MAX

100%

(ONMAX + OFFMIN)

In the appropriate table, find the column that best matches your data:
ONMAX < column specification and
Duty cycle < column specification
Find the row that matches your drive.
The minimum power rating for deceleration to zero is the value in the selected
row/column.
For overhauling loads, double the rating in the selected row/column, or use the
Continuous ON column.
208240 V drives
Resistor1 minimum continuous power rating

Resistance
Type
ACS55001/U1see below

Deceleration-to-zero rating

Prcont
Pr3
Pr10
Pr30
Pr60
Continuous ON
> 60 s ON
< 10 s ON
< 30 s ON
< 60 s ON
RMAX RMIN < 3 s ON
> 27 s OFF > 50 s OFF > 180 s OFF > 180 s OFF
< 10% Duty < 17% Duty < 14% Duty < 25% Duty > 25% Duty
ohm

ohm

Three-phase supply voltage, 208240 V


-04A6-2

234

80

45

80

120

200

1100

-06A6-2

160

80

65

120

175

280

1500

-07A5-2

117

44

85

160

235

390

2200

-012A-2

80

44

125

235

345

570

3000

-017A-2

48

44

210

390

575

950

4000

-024A-2

32

30

315

590

860

1425

5500

-031A-2

23

22

430

800

1175

1940

7500

Technical data

Resistor time constant specification must be > 85 seconds.

ACS550-01/U1 Users Manual

297

380480 V drives
Resistor1 minimum continuous power rating

Resistance
Type
ACS55001/U1see below

Deceleration-to-zero rating

RMAX

RMIN

ohm

ohm

Prcont
Pr3
Pr10
Pr30
Pr60
Continuous ON
> 60 s ON
< 3 s ON
< 10 s ON
< 30 s ON
< 60 s ON
> 27 s OFF > 50 s OFF > 180 s OFF > 180 s OFF
< 10% Duty < 17% Duty < 14% Duty < 25% Duty > 25% Duty
W

Three-phase supply voltage, 380480 V


-03A3-4

641

120

65

120

175

285

1100

-04A1-4

470

120

90

160

235

390

1500

-05A4-4

320

120

125

235

345

570

2200

-06A9-4

235

80

170

320

470

775

3000

-08A8-4

192

80

210

400

575

950

4000

-012A-4

128

80

315

590

860

1425

5500

-015A-4

94

63

425

800

1175

1950

7500

-023A-4

64

63

625

1175

1725

2850

11000

Resistor time constant specification must be > 85 seconds.

500600 V drives
Resistor1 minimum continuous power rating

Resistance
Type
ACS550U1see below

Deceleration-to-zero rating

Prcont
Pr3
Pr10
Pr30
Pr60
Continuous ON
> 60 s ON
< 10 s ON
< 30 s ON
< 60 s ON
RMAX RMIN < 3 s ON
> 27 s OFF > 50 s OFF > 180 s OFF > 180 s OFF
< 10% Duty < 17% Duty < 14% Duty < 25% Duty > 25% Duty
ohm

ohm

Three-phase supply voltage, 500600 V


-02A7-6

548

80

93

175

257

425

1462

-03A9-6

373

80

137

257

377

624

2144

-06A1-6

224

80

228

429

629

1040

3573

-09A0-6

149

80

342

643

943

1560

5359

-011A-6

110

60

467

877

1286

2127

7308

-017A-6

75

60

685

1286

1886

3119

10718

Resistor time constant specification must be > 85 seconds.

WARNING! Never use a brake resistor with a resistance below the minimum value
specified for the particular drive. The drive and the internal chopper are not able to
handle the overcurrent caused by the low resistance.
Symbols
RMIN Minimum allowed resistance of the braking resistor.
RMAX Maximum resistance allowed if maximum braking torque is necessary.

Technical data

298

ACS550-01/U1 Users Manual

Prx Duty-cycle based resistor power rating in deceleration braking, where x is


ONMAX time.
Installing and wiring resistors
All resistors must be installed outside the drive module in a place where they can
dissipate heat.
WARNING! The surface temperature of the resistor is very high, and air flowing from
the resistor is very hot. Materials near the brake resistor must be non-flammable.
Provide protection from accidental contact with the resistor.
To ensure that the input fuses protect the resistor cable, use resistor cables with the
same rating as used for the power input to the drive.
The maximum length of the resistor cable(s) is 10 m (33 ft). See section Power
connection diagrams on page 25 for the resistor cable connection points.
Mandatory circuit protection
The following setup is essential for safety it interrupts the main supply in fault
situations involving chopper shorts:
Equip the drive with a main contactor.
Wire the contactor so that it opens if the resistor thermal switch opens (an
overheated resistor opens the contactor).
Below is a simple wiring diagram example.
L1 L2 L3

1
Off

Fuses

13

14

3
On
4

ACS550
U1 V1 W1
Q

Thermal switch (standard in


ABB resistors)

K1

Parameter set-up
To enable dynamic braking, switch off the drives overvoltage control [Set parameter
2005 = 0 (DISABLE)].

Technical data

ACS550-01/U1 Users Manual

299

Control connections
Control connection specifications
Control connection specifications
Analog inputs and
outputs
Digital inputs

Relays
(digital outputs)

Cable specifications

See section Control terminals table on page 28.


Digital input impedance 1.5 kohm. Maximum voltage for digital inputs is
30 V.

Max. contact voltage: 30 V DC, 250 V AC


Max. contact current / power: 6 A, 30 V DC; 1500 VA, 250 V AC
Max. continuous current: 2 A rms (cos = 1), 1 A rms (cos = 0.4)
Minimum load: 500 mW (12 V, 10 mA)
Contact material: Silver-nickel (AgN)
Isolation between relay digital outputs, test voltage: 2.5 kV rms, 1 minute

See section Control terminals table on page 28.

Control cables
General recommendations
Use multi-core cables with a braided copper wire shield, temperature rated at 60 C
(140 F) or above:

Double shielded
Example: JAMAK by Draka NK Cables

Single shielded
Example: NOMAK by Draka NK Cables

For digital and analog I/O cables, twist the shield together into a bundle (pig-tail) not
longer than five times its width and connect it to terminal X1-1 at the drive end.
Leave the other end of the cable shield unconnected.
For connecting the shield wires of the RS485 cable, see the instructions (and notes)
in section Mechanical and electrical installation EFB on page 204.
Route control cables to minimize radiation to the cable:
Route as far away as possible from the input power and motor cables (at least
20 cm [8 in]).
Where control cables must cross power cables, make sure they are at an angle
as near 90 as possible.
Stay at least 20 cm (8 in) from the sides of the drive.
Use care in mixing signal types on the same cable:
Do not mix relay-controlled signals using more than 30 V and other control
signals in the same cable.
Run relay-controlled signals as twisted pairs (especially if voltage > 48 V). Relaycontrolled signals using less than 48 V can be run in the same cables as digital
input signals.

Technical data

300

ACS550-01/U1 Users Manual

Note: Never mix 24 V DC and 115/230 V AC signals in the same cable.


Analog cables
Recommendations for analog signal runs:
Use double shielded, twisted pair cable.
Use one individually shielded pair for each signal.
Do not use a common return for different analog signals.
Digital cables
Recommendation for digital signal runs: A double shielded cable is the best
alternative, but single-shielded, twisted, multi-pair cable is also usable.
Control panel cable
If the control panel is connected to the drive with a cable, use only Category 5 Patch
ethernet cable. The maximum length that is tested to meet EMC specifications is 3 m
(9.8 ft). Longer cables are susceptible to electromagnetic noise and must be usertested to verify that EMC requirements are met. Where long runs are required
(especially for runs longer than about 12 m [40 ft]), use a RS232/RS485 converter at
each end and run RS485 cable.
Drives control connection terminals
The following table provides specifications for the drives control terminals
Frame size

All
1

Control
Maximum wire size

Tightening torque

mm2

AWG

Nm

lbft

1.5

16

0.4

0.3

Values given for solid wires.


For stranded wires, the maximum size is 1 mm2.

Efficiency
Approximately 98% at nominal power level.

Technical data

ACS550-01/U1 Users Manual

301

Losses, cooling data and noise


Cooling specifications
Method

Internal fan, flow direction from bottom to top.

Free space above and below the ACS550 drive: 200 mm (8 in).
Requirement Free space is not required on the drives sides ACS550 drives can be mounted
side-by-side.

Air flow, 208240 V drives


The following table lists the requirements for the cooling air flow data for 208240 V
drives at full load in all ambient conditions listed in Ambient conditions on page 307.
Drive

Heat dissipation
W

Air flow
m3/h

BTU/hr

Noise

ft3/min

dB

ACS550-x1-

Frame size

-04A6-2

R1

55

189

44

26

52

-06A6-2

R1

73

249

44

26

52

-07A5-2

R1

81

276

44

26

52

-012A-2

R1

118

404

44

26

52

-017A-2

R1

161

551

44

26

52

-024A-2

R2

227

776

88

52

66

-031A-2

R2

285

973

88

52

66

-046A-2

R3

420

1434

134

79

67

-059A-2

R3

536

1829

134

79

67

-075A-2

R4

671

2290

280

165

75

-088A-2

R4

786

2685

280

165

75

-114A-2

R4

1014

3463

280

165

75

-143A-2

R6

1268

4431

405

238

77

-178A-2

R6

1575

5379

405

238

77

-221A-2

R6

1952

6666

405

238

77

-248A-2

R6

2189

7474

405

238

77
00467918.xls C

Air flow, 380480 V drives


The following table lists the requirements for the cooling air flow data for 380480 V
drives at full load in all ambient conditions listed in Ambient conditions on page 307.
Drive

Heat dissipation
W

Air flow
m3/h

BTU/hr

Noise

ft3/min

dB

ACS550-x1-

Frame size

-03A3-4

R1

40

137

44

26

52

-04A1-4

R1

52

178

44

26

52

-05A4-4

R1

73

249

44

26

52

-06A9-4

R1

97

331

44

26

52

-08A8-4

R1

127

434

44

26

52

-012A-4

R1

172

587

44

26

52

Technical data

302

ACS550-01/U1 Users Manual

Drive

Heat dissipation
W

Air flow
m3/h

Noise

ft3/min

ACS550-x1-

Frame size

-015A-4

R2

232

792

88

52

66

-023A-4

R2

337

1151

88

52

66

-031A-4

R3

457

1561

134

79

67

-038A-4

R3

562

1919

134

79

67

-045A-4

R3

667

2278

134

79

67

-059A-4

R4

907

3098

280

165

75

-072A-4

R4

1120

3825

280

165

75

-078A-4

R4

1295

4423

250

147

75

-087A-4

R4

1440

4918

280

165

75

-097A-4

R4

1440

4918

280

165

75

-125A-4

R5

1940

6625

350

205

75

-157A-4

R6

2310

7889

405

238

77

-180A-4

R6

2810

9597

405

238

77

-195A-4

R6

3050

10416

405

238

77

-246A-4

R6

3260

11134

405

238

77

-290A-4

R6

3850

13125

405

238

77

BTU/hr

dB

00467918.xls C

Air flow, 500600 V drives


The following table lists the requirements for the cooling air flow data for 500600 V
drives at full load in all ambient conditions listed in Ambient conditions on page 307.
Drive

Technical data

Heat dissipation
W

Air flow
m3/h

BTU/hr

Noise

ft3/min

dB

ACS550-U1-

Frame size

-02A7-6

R2

52

178

88

52

66

-03A9-6

R2

73

249

88

52

66

-06A1-6

R2

127

434

88

52

66

-09A0-6

R2

172

587

88

52

66

-011A-6

R2

232

792

88

52

66

-017A-6

R2

337

1151

88

52

66

-022A-6

R3

457

1561

134

79

67

-027A-6

R3

562

1919

134

79

67

-032A-6

R4

667

2278

280

165

75

-041A-6

R4

907

3098

280

165

75

-052A-6

R4

1117

3815

280

165

75

-062A-6

R4

1357

4634

280

165

75

-077A-6

R6

2310

7889

405

238

77

-099A-6

R6

2310

7889

405

238

77

-125A-6

R6

2310

7889

405

238

77

ACS550-01/U1 Users Manual

303

Drive

Heat dissipation

ACS550-U1-

Frame size

-144A-6

R6

Air flow
m3/h

BTU/hr

W
2310

7889

Noise

ft3/min

405

238

dB
77
00467918.xls C

Dimensions and weights


The dimensions and mass for the ACS550 depend on the frame size and enclosure
type. If unsure of the frame size, first, find the Type designation on the drive labels
(see sections The labels contain information on the Type designation (page 17),
Ratings and frame size (page 17), Serial number (page 17), degree of protection
(see also Degrees of protection on page 306) and valid markings (see also Markings
on page 309). on page 17 and Drive labels on page 16). Then look up that type
designation in the rating tables (see chapter Technical data, page 277), to determine
the frame size.
Mounting dimensions
W1
W2
See detail A

H1

See detail B

Detail A

Detail B

X0032

IP21 / UL type 1 and IP54 / UL type 12 Dimensions for each frame size
Ref.
1

R1
mm

R2
in

mm

R3
in

mm

R4
in

mm

R5
in

mm

R6
in

mm

in

W1

98.0

3.9

98.0

3.9

160

6.3

160

6.3

238

9.4

263

10.4

W21

--

--

--

--

98.0

3.9

98.0

3.9

--

--

--

--

H11

318

12.5

418

16.4

473

18.6

578

22.8

588

23.2

675

26.6

5.5

0.2

5.5

0.2

6.5

0.25

6.5

0.25

6.5

0.25

9.0

0.35

10.0

0.4

10.0

0.4

13.0

0.5

13.0

0.5

14.0

0.55

18.0

0.71

5.5

0.2

5.5

0.2

8.0

0.3

8.0

0.3

8.5

0.3

8.5

0.3

5.5

0.2

5.5

0.2

6.5

0.25

6.5

0.25

6.5

0.25

9.0

0.35

Center to center dimension.

Technical data

304

ACS550-01/U1 Users Manual

Outside dimensions
Drives with IP21 / UL type 1 enclosures
Types ACS550-x1-221A-2,
ACS550-x1-246A-4, ACS550-x1-248A-2,
and ACS550-01-290A-4, frame size R6
D

W
W

H2

H2

H3

H3

H3

X0031

IP21 / UL type 1 dimensions for each frame size


Ref.

R1
mm

R2
in

mm

R3
in

mm

R4
in

mm

R5
in

mm

R6
in

mm

in

125

4.9

125

4.9

203

8.0

203

8.0

265

10.4

302

11.9

330

13.0

430

16.9

490

19.3

596

23.5

602

23.7

700

27.6

H2

315

12.4

415

16.3

478

18.8

583

23.0

578

22.8

698

27.5

H3

369

14.5

469

18.5

583

23.0

689

27.1

736

29.0

8881

35.01

212

8.3

222

8.7

231

9.1

262

10.3

286

11.3

400

15.8

00467918.xls C

1. ACS550-x1-221A-2, ACS550-x1-246A-4, ACS550-x1-248A-2 and ACS550-x1-290A-4: 981 mm /


38.6 in.

Technical data

ACS550-01/U1 Users Manual

305

Drives with IP54 / UL type 12 enclosures


Type ACS550-01-290A-4, IP54
(UL type 12 not available), frame size R6
W2

W2

H3

H3

D
W

IP54 / UL type 12 Dimensions for each frame size


Ref.

R1

R2

R3

R4

R62

R5

mm

in

mm

in

mm

in

mm

in

mm

in

mm

in

213

8.4

213

8.4

257

10.1

257

10.1

369

14.5

410

16.1

W2

222

8.8

222

8.8

267

10.5

267

10.5

369

14.5

410

16.1
36.41
16.7

H3

461

18.2

561

22.1

629

24.8

760

29.9

775

30.5

9241

234

9.2

245

9.7

254

10.0

284

11.2

309

12.2

423

00467918.xls C

1. ACS550-01-290A-4: 1119 mm / 44.1 in.


2. UL type 12 not available for ACS550-01-290A-4.

Technical data

306

ACS550-01/U1 Users Manual

Weight
The following table lists typical maximum weights for each frame size. Variations
within each frame size (due to components associated with voltage/current ratings
and options) are minor.
Weight
Enclosure

R1
kg

R2
lb

kg

R3
lb

kg

R4
lb

kg

R5
lb

kg

R6
lb

kg

lb

1521

IP21 / UL type 1

6.5

14.3

9.0

19.8

16

35

24

53

34

75

69

IP54 / UL type 12

8.0

17.6

11.0

24.3

17.0

37.5

26.0

57.3

42.0

93.0

86.02 1902
00467918.xls C

1. ACS550-x1-221A-2, IP21 / UL type 1:70 kg / 154 lb


ACS550-x1-246A-4, IP21 / UL type 1: 70 kg / 154 lb,
ACS550-x1-248A-2, IP21 / UL type 1,80 kg / 176 lb.
ACS550-01-290A-4, IP21 / UL type 1: 80 kg / 176 lb.
2. ACS550-x1-246A-4, IP54 / UL type 12: 80 kg / 176 lb
ACS550-01-290A-4, IP54: 90 kg / 198 lb (UL type 12 not available).

Degrees of protection
Available enclosures:
IP21 / UL type 1 enclosure. The site must be free of airborne dust, corrosive
gases or liquids, and conductive contaminants such as condensation, carbon
dust and metallic particles.
IP54 / UL type 12 enclosure. This enclosure provides protection from airborne
dust and light sprays or splashing water from all directions.
Note: UL type 12 enclosure is not available for type ACS550-01-290A-4.
Compared to the IP21 / UL type 1 enclosure, the IP54 / UL type 12 enclosure has:
the same internal plastic shell as the IP21 enclosure
a different outer plastic cover
an additional internal fan to improve cooling
larger dimensions
the same rating (does not require a derating).

Technical data

ACS550-01/U1 Users Manual

307

Ambient conditions
The following table lists the ACS550 environmental requirements.
Ambient environment requirements
Storage and transportation in the
protective package

Installation site

Altitude

01000 m (03 300 ft)


10002000 m (3 3006 600 ft) if
PN and I2N derated 1% every 100 m
above 1000 m (300 ft above 3 300 ft)

Ambient
temperature

Min. -15 C (5 F) no frost allowed


Max. (fsw = 1 or 4) 40 C (104 F);
50 C (122 F) if
PN and I2N derated to 90%
Max. (fsw = 8) 40 C (104 F) if
PN and I2N derated to 80%
Max. (fsw = 12) 30 C (86 F) if
PN and I2N derated to 65% (to 50%
for 600 V, R4 frame sizes, that is for
ACS550-U1-032A-6 ACS550-U1062A-6)

Relative
humidity

Contamination
levels
(IEC 60721-3-3)

-4070 C (-40158 F)

595%, no condensation allowed


No conductive dust allowed.
The ACS550 should be installed in
clean air according to enclosure
classification.
Cooling air must be clean, free from
corrosive materials and free from
electrically conductive dust.
Chemical gases: Class 3C2
Solid particles: Class 3S2

Storage
No conductive dust allowed.
Chemical gases: Class 1C2
Solid particles: Class 1S2
Transportation
No conductive dust allowed.
Chemical gases: Class 2C2
Solid particles: Class 2S2

The following table lists the standard stress testing that the ACS550 passes.
Stress tests
Without shipping package
Sinusoidal
vibration

Shock

Free fall

Inside shipping package

Mechanical conditions: In accordance


with IEC 60721-3-3, Class 3M4
29 Hz 3.0 mm (0.12 in)
9200 Hz 10 m/s2 (33 ft/s2)

In accordance with ISTA 1A and 1B


specifications.

Not allowed

In accordance with IEC 68-2-29:


max. 100 m/s2 (330 ft/s2), 11ms

Not allowed

76 cm (30 in), frame size R1


61cm (24 in), frame size R2
46 cm (18 in), frame size R3
31 cm (12 in), frame size R4
25 cm (10 in), frame size R5
15 cm (6 in), frame size R6

Technical data

308

ACS550-01/U1 Users Manual

Materials
Material specifications

Technical data

Drive enclosure

PC/ABS 2.5 mm, color NCS 1502-Y or NCS 7000-N


Hot-dip zinc coated steel sheet 1.52 mm, thickness of coating 20
micrometers. If the surface is painted, the total thickness of the coating (zinc
and paint) is 80100 micrometers.
Cast aluminium AlSi
Extruded aluminium AlSi

Package

Corrugated board, expanded polystyrene, plywood, raw wood (heat dried).


Package wrap consists of one or more of the following: PE-LD plastic wrap, PP
or steel bands.

Disposal

The drive contains raw materials that should be recycled to preserve energy
and natural resources. The package materials are environmentally compatible
and recyclable. All metal parts can be recycled. The plastic parts can either be
recycled or burned under controlled circumstances, according to local
regulations. Most recyclable parts are marked with recycling marks.
If recycling is not feasible, all parts excluding electrolytic capacitors and printed
circuit boards can be landfilled. The DC capacitors contain electrolyte and, if the
drive is not provided with the RoHS marking, the printed circuit boards contain
lead, both of which are classified as hazardous waste within the EU. They must
be removed and handled according to local regulations.
For further information on environmental aspects and more detailed recycling
instructions, contact your local ABB representative.

ACS550-01/U1 Users Manual

309

Applicable standards
Drive compliance with the following standards is identified by the standard marks
on the type designation label. The following standards are applicable to the drive:
Mark

Applicable standards
EN 50178:1997

Electronic equipment for use in power installations

IEC/EN 60204-1:2005

Safety of machinery. Electrical equipment of machines.


Part 1: General requirements. Provisions for compliance: The
final assembler of the machine is responsible for installing:
an emergency-stop device
a supply disconnecting device.

IEC/EN 60529:1989 +
A1:1999 + A2:2013

Degrees of protection provided by enclosures (IP code)

IEC 60664-1:2002

Insulation coordination for equipment within low-voltage


systems. Part 1: Principles, requirements and tests

IEC/EN 61800-5-1:2007

Adjustable speed electrical power drive systems.


Part 5-1: Safety requirements. Electrical, thermal and energy

IEC/EN 61800-3:2004
+A1:2012

Adjustable speed electrical power drive systems.


Part 3: EMC requirements and specific test methods

IEC/EN 61000-3-12:2011

Electromagnetic compatibility (EMC).


Part 3-12: Limits - Limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current > 16 A and = 75 A per phase

IEC/EN 61800-3:2004
+A1:2012

Adjustable speed electrical power drive systems.


Part 3: EMC requirements and specific test methods

UL 508C

UL Standard for Safety, Power Conversion Equipment, third


edition

C22.2 No. 14

CSA Standard for Industrial Control Equipment (for ACS550-U1


drives only)

Markings
CE marking
A CE mark is attached to the drive to verify that the drive follows the provisions of the
European Low Voltage, EMC and RoHS Directives
Note: The 600 V ACS550-U1 drives are not CE approved.
Compliance with the European Low Voltage Directive
The compliance with the European Low Voltage Directive has been verified
according to standards IEC/EN 60204-1:2005 and EN 50178:1997.
Compliance with the European EMC Directive
The Directive defines the requirements for immunity and emissions of electrical
equipment used within the European Union. The EMC product standard IEC/EN
61800-3:2004 +A1:2012 covers requirements stated for drives.

Technical data

310

ACS550-01/U1 Users Manual

Compliance with IEC/EN 61800-3:2004 +A1:2012


See page 311.
C-Tick marking
The drive carries C-Tick marking.
C-Tick marking is required in Australia and New Zealand. A C-Tick mark is attached
to the drive to verify compliance with the relevant standard (IEC 61800-3:2004)
Adjustable speed electrical power drive systems Part 3: EMC product standard
including specific test methods), mandated by the Trans-Tasman Electromagnetic
Compatibility Scheme.
The Trans-Tasman Electromagnetic Compatibility Scheme (EMCS) was introduced
by the Australian Communication Authority (ACA) and the Radio Spectrum
Management Group (RSM) of the New Zealand Ministry of Economic Development
(NZMED) in November 2001. The aim of the scheme is to protect the radio
frequency spectrum by introducing technical limits for emission from electrical/
electronic products.
Compliance with IEC/EN 61800-3:004
See page 311.
UL/CSA markings
An UL mark is attached to ACS550 drives to verify that the drive follows the
provisions of UL 508C.
A CSA mark is attached to ACS550-U1 type drives to verify that the drive follows the
provisions of C22.2 NO. 14.
The ACS550 is suitable for use in a circuit capable of delivering not more than
100 kA RMS symmetrical amperes, 600 V maximum. The ampere rating is based on
tests done according to UL 508.
Branch circuit protection must be provided in accordance with local codes.
The ACS550 has an electronic motor protection feature that complies with the
requirements of UL 508C and, for ACS550-U1, C22.2 No. 14. When this feature is
selected and properly adjusted, additional overload protection is not required unless
more than one motor is connected to the drive or unless additional protection is
required by applicable safety regulations. See parameters 3005 (MOT THERM PROT)
and 3006 (MOT THERM RATE).
The drives are to be used in a controlled environment. See section Ambient
conditions on page 307 for specific limits.
Note: For open type enclosures, i.e. drives without the conduit box and/or cover for
IP21 / UL type 1 drives, or without the conduit plate and/or hood for IP54 /
UL type 12 drives, the drive must be mounted inside an enclosure in accordance
with National Electric Code and local electrical codes.
Brake choppers, when applied with appropriately sized brake resistors, will allow the
drive to dissipate regenerative energy (normally associated with quickly decelerating
a motor). Frame sizes R1 and R2 have a built-in brake chopper as standard

Technical data

Marking with the Single mark of product circulation on the market of the Customs Union member
states

ACS550-01/U1 Users Manual

311

equipment. For frame sizes R3R6, contact your local ABB representative for
appropriate parts. See section Brake components on page 295.
EAC marking
The drive has EAC certification. EAC marking is required in Russia, Belarus and
Kazakhstan.

IEC/EN 61800-3:2004 Definitions


EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic
equipment to operate without problems within an electromagnetic environment.
Likewise, the equipment must not disturb or interfere with any other product or
system within its locality.
First environment includes establishments connected to a low-voltage network which
supplies buildings used for domestic purposes.
Second environment includes establishments connected to a network not directly
supplying domestic premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be
installed and commissioned only by a professional when used in the first
environment.
Note: A professional is a person or organization having necessary skills in installing
and/or commissioning power drive systems, including their EMC aspects.
Category C2 has the same EMC emission limits as the earlier class first environment
restricted distribution. EMC standard IEC/EN 61800-3 does not any more restrict the
distribution of the drive, but the using, installation and commissioning are defined.
Drive of category C3: drive of rated voltage less than 1000 V, intended for use in the
second environment and not intended for use in the first environment.
Category C3 has the same EMC emission limits as the earlier class second
environment unrestricted distribution.

Compliance with the IEC/EN 61800-3:2004 +A1:2012


The immunity performance of the drive complies with the demands of IEC/
EN 61800-3, category C2 (see page 311 for IEC/EN 61800-3 definitions). The
emission limits of IEC/EN 61800-3 comply with the provisions described below.
First environment (drives of category C2)
1. The internal EMC filter is connected.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. The motor cable length does not exceed the allowed maximum length specified in
section Motor cable length for 400 V drives on page 290 for the frame size and
switching frequency in use.

Technical data

312

ACS550-01/U1 Users Manual

WARNING! In a domestic environment, this product may cause radio inference, in


which case supplementary mitigation measures may be required.
Second environment (drives of category C3)
1. The internal EMC filter is connected.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. The motor cable length does not exceed the allowed maximum length specified in
section Motor cable length for 400 V drives on page 290 for the frame size and
switching frequency in use.
WARNING! A drive of category C3 is not intended to be used on a low-voltage public
network which supplies domestic premises. Radio frequency interference is
expected if the drive is used on such a network.
Note: It is not allowed to install a drive with the internal EMC filter connected on IT
(ungrounded) systems. The supply network becomes connected to ground potential
through the EMC filter capacitors, which may cause danger or damage the drive.
Note: It is not allowed to install a drive with the internal EMC filter connected to a
corner grounded TN system as this would damage the drive.

Technical data

ACS550-01/U1 Users Manual

313

Index
Numerics
0xxxx register
EFB function codes . . . . . . . . . . . . . . . . . . . 218
EFB mapping . . . . . . . . . . . . . . . . . . . . . . . 216
1xxxx register
EFB function codes . . . . . . . . . . . . . . . . . . . 219
EFB mapping . . . . . . . . . . . . . . . . . . . . . . . 218
2-wire sensor/transmitter, connection example . . 86
3-wire macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
3-wire sensor/transmitter, connection example . . 86
3xxxx register
EFB function codes . . . . . . . . . . . . . . . . . . . 219
EFB mapping . . . . . . . . . . . . . . . . . . . . . . . 219
4xxxx register
EFB function codes . . . . . . . . . . . . . . . . . . . 222
EFB mapping . . . . . . . . . . . . . . . . . . . . . . . 219

A
ABB
document library . . . . . . . . . . . . . . . . . . . . . 325
feedback on ABB manuals . . . . . . . . . . . . . 325
product and service inquiries . . . . . . . . . . . 325
product training . . . . . . . . . . . . . . . . . . . . . . 325
standard (default) macro . . . . . . . . . . . . . . . . 78
acceleration
/deceleration, parameter group . . . . . . . . . . 139
at aux. stop (PFC), parameter. . . . . . . . . . . 200
compensation, parameter . . . . . . . . . . . . . . 142
ramp select, parameter . . . . . . . . . . . . . . . . 139
ramp shape, parameter. . . . . . . . . . . . . . . . 139
ramp time (PFC), parameter . . . . . . . . . . . . 200
ramp zero select, parameter . . . . . . . . . . . . 140
time, parameter . . . . . . . . . . . . . . . . . . . . . . 139
activate (external PID), parameter. . . . . . . . . . . 178
actual input (PID), parameters. . . . . . . . . . . . . . 174
actual max. (PID), parameters. . . . . . . . . . . . . . 174
actual min. (PID), parameters . . . . . . . . . . . . . . 174
actual values
mapping, FBA, generic profile. . . . . . . . . . . 257
scaling, EFB comm . . . . . . . . . . . . . . . . . . . 211
scaling, FBA comm . . . . . . . . . . . . . . . . . . . 244
scaling, FBA, ABB drives profile . . . . . . . . . 255
scaling, FBA, generic profile . . . . . . . . . . . . 257
alarm
codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
codes (Basic Control Panel) . . . . . . . . . . . . 269
display enable, parameter. . . . . . . . . . . . . . 132
listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
words, data parameters . . . . . . . . . . . . . . . 113
alternate macro . . . . . . . . . . . . . . . . . . . . . . . . . . 80
altitude
derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
environment limit . . . . . . . . . . . . . . . . . . . . . 307
shipping limit . . . . . . . . . . . . . . . . . . . . . . . . 307
ambient conditions. . . . . . . . . . . . . . . . . . . . . . . 307

Index

ambient temperature
derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
environment limit . . . . . . . . . . . . . . . . . . . . . 307
shipping limit. . . . . . . . . . . . . . . . . . . . . . . . . 307
amplitude logging
see load analyzer
analog cable, requirements. . . . . . . . . . . . . . . . . 300
analog I/O
connections . . . . . . . . . . . . . . . . . . . . . . . . . . 28
specifications . . . . . . . . . . . . . . . . . . . . . . . . . 28
analog input
parameter group . . . . . . . . . . . . . . . . . . . . . . 123
data parameter . . . . . . . . . . . . . . . . . . . . . . . 109
fault limit, parameters . . . . . . . . . . . . . . . . . . 150
filter, parameters . . . . . . . . . . . . . . . . . . . . . 123
less than min. auto. reset, parameter . . . . . . 152
less than min., fault parameter . . . . . . . . . . . 148
loss, fault codes . . . . . . . . . . . . . . . . . . . . . . 261
maximum, parameters . . . . . . . . . . . . . . . . . 123
minimum, parameters. . . . . . . . . . . . . . . . . . 123
analog output
parameter group . . . . . . . . . . . . . . . . . . . . . . 127
content max., parameters. . . . . . . . . . . . . . . 127
content min., parameters . . . . . . . . . . . . . . . 127
current max., parameters . . . . . . . . . . . . . . . 127
current min., parameters . . . . . . . . . . . . . . . 127
data content, parameters . . . . . . . . . . . . . . . 127
data parameters . . . . . . . . . . . . . . . . . . . . . . 109
filter, parameters . . . . . . . . . . . . . . . . . . . . . 127
obtain 0...10 V . . . . . . . . . . . . . . . . . . . . . . . . 87
analyzer, load
see load analyzer
angle
mechanical, data parameter . . . . . . . . . . . . . 110
application block output, data parameter . . . . . . 108
application macro, parameter . . . . . . . . . . . . . . . 106
application macros
see macros
arrow (Assistant Control Panel) . . . . . . . . . . . . . . 49
assistant (Assistant Control Panel)
start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Assistant Control Panel
see control panel (Assistant)
assistants mode (Assistant Control Panel) . . . . . . 57
autochange
interval, parameter . . . . . . . . . . . . . . . . . . . . 193
level, parameter . . . . . . . . . . . . . . . . . . . . . . 194
overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
starting order counter . . . . . . . . . . . . . . . . . . 194
automatic reset
see reset, automatic
auxiliary motor
see motor, auxiliary

314

ACS550-01/U1 Users Manual

B
backing up parameters
Assistant Control Panel . . . . . . . . . . . . . . . . 64
Basic Control Panel . . . . . . . . . . . . . . . . . . . 75
Basic Control Panel
see control panel (Basic)
battery (Assistant Control Panel). . . . . . . . . . . . 275
baud rate (RS-232), parameter . . . . . . . . . . . . . 183
braking
components . . . . . . . . . . . . . . . . . . . . . . . . 295
protection from overheated resistor . . . . . . 298
resistor heat dissipation . . . . . . . . . . . . . . . 298
selecting brake choppers/resistors . . . . . . . 295
wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298
break point frequency, fault parameter . . . . . . . 149
buffer overruns (count), parameter . . . . . . . . . . 183

C
cable requirements
control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
grounding . . . . . . . . . . . . . . . . . . . . . . . . . . 285
input power . . . . . . . . . . . . . . . . . . . . . . . . . 284
motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
capacitor
reforming. . . . . . . . . . . . . . . . . . . . . . . . . . . 275
replacement . . . . . . . . . . . . . . . . . . . . . . . . 275
category (IEC/EN 61800-3 definition)
C2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
C3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
CB
see control board
CE marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
changed parameters (Assistant Control Panel). . 60
chopper
see braking
clock
see time and date setting (Assistant Control
Panel)
CO2 conversion factor
see energy saving
communication
see EFB (embedded fieldbus)
see EFB, drive parameters
see FBA (fieldbus adapter)
see FBA, drive parameters
compatibility. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
conduit kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
config file
CPI firmware revision, parameter . . . . . . . . 182
fault code . . . . . . . . . . . . . . . . . . . . . . . . . . 263
id revision, parameter . . . . . . . . . . . . . . . . . 182
revision, parameter . . . . . . . . . . . . . . . . . . . 182
connections
control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
EFB comm . . . . . . . . . . . . . . . . . . . . . . . . . 204
FBA module . . . . . . . . . . . . . . . . . . . . . . . . 240
X1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
constant speed
see speed, constant
construction code . . . . . . . . . . . . . . . . . . . . . . . . 17

Index

contamination levels
environment limit . . . . . . . . . . . . . . . . . . . . . 307
shipping limit . . . . . . . . . . . . . . . . . . . . . . . . 307
contrast, control panel (Assistant) . . . . . . . . . . . . 54
control
connection specifications . . . . . . . . . . . . . . . 299
location, data parameter . . . . . . . . . . . . . . . 108
terminal specifications . . . . . . . . . . . . . . . . . 300
through I/O interface . . . . . . . . . . . . . . . . . . . 44
control board
overtemperature, fault code . . . . . . . . . . . . . 264
overtemperature, fault parameter. . . . . . . . . 151
temperature, data parameter . . . . . . . . . . . . 110
control cable
connections . . . . . . . . . . . . . . . . . . . . . . . . . . 28
requirements . . . . . . . . . . . . . . . . . . . . . . . . 299
control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
cable requirements. . . . . . . . . . . . . . . . . . . . 300
comm error, fault parameter. . . . . . . . . . . . . 148
display bar-graph . . . . . . . . . . . . . . . . . 156, 157
display decimal point (form), parameters . . . 156
display max., parameters . . . . . . . . . . . . . . . 157
display min., parameters . . . . . . . . . . . . . . . 157
display process variables, parameter group 156
display selection, parameters. . . . . . . . . . . . 156
display units, parameters . . . . . . . . . . . . . . . 157
maintenance. . . . . . . . . . . . . . . . . . . . . . . . . 275
manual compatibility. . . . . . . . . . . . . . . . . . . . 47
parameter lock, parameter . . . . . . . . . . . . . . 129
pass code, parameter . . . . . . . . . . . . . . . . . 129
reference control, parameter . . . . . . . . . . . . 117
signal max., parameters . . . . . . . . . . . . . . . . 156
signal min., parameters . . . . . . . . . . . . . . . . 156
control panel (Assistant) . . . . . . . . . . . . . . . . . . . . 48
arrow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
assistants mode . . . . . . . . . . . . . . . . . . . . . . . 57
battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
changed parameters mode . . . . . . . . . . . . . . 60
direction of rotation. . . . . . . . . . . . . . . . . . 49, 53
display contrast . . . . . . . . . . . . . . . . . . . . . . . 54
fault logger mode . . . . . . . . . . . . . . . . . . . . . . 61
fault mode . . . . . . . . . . . . . . . . . . . 49, 259, 260
help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
how to do common tasks . . . . . . . . . . . . . . . . 50
I/O settings mode . . . . . . . . . . . . . . . . . . . . . . 67
main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
output mode . . . . . . . . . . . . . . . . . . . . . . . . . . 53
overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
parameter backup mode . . . . . . . . . . . . . . . . 64
parameters mode . . . . . . . . . . . . . . . . . . . . . . 55
soft keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
start/stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
status line (LOC/REM, arrow) . . . . . . . . . . . . 49
time and date mode . . . . . . . . . . . . . . . . . . . . 62

ACS550-01/U1 Users Manual

315

control panel (Basic) . . . . . . . . . . . . . . . . . . . . . . 68


alarm codes. . . . . . . . . . . . . . . . . . . . . . . . . 269
copy mode. . . . . . . . . . . . . . . . . . . . . . . . . . . 75
direction of rotation . . . . . . . . . . . . . . . . . 68, 70
fault mode . . . . . . . . . . . . . . . . . . . 69, 259, 260
how to do common tasks . . . . . . . . . . . . . . . 69
main menu . . . . . . . . . . . . . . . . . . . . . . . . . . 69
operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
output mode . . . . . . . . . . . . . . . . . . . . . . . . . 71
overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
parameter mode . . . . . . . . . . . . . . . . . . . . . . 73
reference mode . . . . . . . . . . . . . . . . . . . . . . . 72
start/stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
control word
ABB drives, FBA, description . . . . . . . . . . . 248
EFB, description . . . . . . . . . . . . . . . . . . . . . 224
FBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
FBA generic profile . . . . . . . . . . . . . . . . . . . 256
cooling
air flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
fan maintenance triggers. . . . . . . . . . . . . . . 147
heat dissipation . . . . . . . . . . . . . . . . . . . . . . 301
space requirement . . . . . . . . . . . . . . . . . . . 301
copy mode (Basic Control Panel) . . . . . . . . . . . . 75
corner grounded TN system . . . . . . . . . . . . . . . 285
warning about filters . . . . . . . . . . . . . . . . . . . . 6
warning about screws at EM1, EM3 . . . . . . . 25
warning about screws at F1, F2 . . . . . . . . . . 26
correction source (PID), parameter . . . . . . . . . . 179
cover
remove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
replace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
cover, top, see hood
CRC errors (count), parameter . . . . . . . . . . . . . 183
crimp-on ring lugs . . . . . . . . . . . . . . . . . . . . . . . 287
critical speeds (avoiding)
parameter group . . . . . . . . . . . . . . . . . . . . . 144
high, parameters . . . . . . . . . . . . . . . . . . . . . 144
low, parameters. . . . . . . . . . . . . . . . . . . . . . 144
select, parameter . . . . . . . . . . . . . . . . . . . . 144
C-Tick marking . . . . . . . . . . . . . . . . . . . . . . . . . 310
current
at fault, history parameter . . . . . . . . . . . . . . 114
data parameter . . . . . . . . . . . . . . . . . . . . . . 108
max. limit, parameter. . . . . . . . . . . . . . . . . . 133
measurement, fault code. . . . . . . . . . . . . . . 262
rating code . . . . . . . . . . . . . . . . . . . . . . . . . . 17

D
date
see time and date setting (Assistant Control
Panel)
DC
brake time, parameter . . . . . . . . . . . . . . . . .
bus voltage, data parameter . . . . . . . . . . . .
current ref., parameter . . . . . . . . . . . . . . . .
magnetizing time, parameter. . . . . . . . . . . .
overvoltage, fault code . . . . . . . . . . . . . . . .
undervoltage, fault code . . . . . . . . . . . . . . .
voltage stabilizer, parameter . . . . . . . . . . . .

137
108
137
136
261
261
146

deceleration
parameter group . . . . . . . . . . . . . . . . . . . . . . 139
at aux. start (PFC), parameter . . . . . . . . . . . 200
emergency time, parameter . . . . . . . . . . . . . 140
ramp select, parameter . . . . . . . . . . . . . . . . 139
ramp shape, parameter . . . . . . . . . . . . . . . . 139
ramp time (PFC), parameter . . . . . . . . . . . . 200
ramp zero select, parameter . . . . . . . . . . . . 140
time, parameter . . . . . . . . . . . . . . . . . . . . . . 139
default values
listing for macros . . . . . . . . . . . . . . . . . . . . . . 89
listing for parameters . . . . . . . . . . . . . . . . . . . 91
derating
adjustment example . . . . . . . . . . . . . . . . . . . 280
altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
single phase supply . . . . . . . . . . . . . . . . . . . 280
switching frequency . . . . . . . . . . . . . . . . . . . 280
temperature . . . . . . . . . . . . . . . . . . . . . . . . . 280
derivation time (PID), parameter. . . . . . . . . . . . . 171
derivation time, parameter . . . . . . . . . . . . . . . . . 141
device overtemperature, fault code. . . . . . . . . . . 261
diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
EFB comm . . . . . . . . . . . . . . . . . . . . . . . . . . 212
FBA comm . . . . . . . . . . . . . . . . . . . . . . . . . . 245
digital cable requirements . . . . . . . . . . . . . . . . . . 300
digital input
at fault, history parameters . . . . . . . . . . . . . . 114
connections . . . . . . . . . . . . . . . . . . . . . . . . . . 28
specifications . . . . . . . . . . . . . . . . . . . . . . . . . 29
status, data parameter . . . . . . . . . . . . . . . . . 109
digital output
connections . . . . . . . . . . . . . . . . . . . . . . . . . . 28
specifications . . . . . . . . . . . . . . . . . . . . . . . . 299
dimensions
drive, mounting . . . . . . . . . . . . . . . . . . . . . . . 303
drive, outside . . . . . . . . . . . . . . . . . . . . . . . . 304
DIP switches . . . . . . . . . . . . . . . . . . . . . . . . . . 25, 28
direction control, parameter . . . . . . . . . . . . . . . . 116
direction of rotation
Assistant Control Panel . . . . . . . . . . . . . . 49, 53
Basic Control Panel . . . . . . . . . . . . . . . . . 68, 70
display format (PID), parameter . . . . . . . . . . . . . 171
disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
document library . . . . . . . . . . . . . . . . . . . . . . . . . 325
download parameter sets
application . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
full set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
user sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
drive
EFB comm installation . . . . . . . . . . . . . . . . . 204
FBA module installation . . . . . . . . . . . . . . . . 240
id, fault code . . . . . . . . . . . . . . . . . . . . . . . . . 263
mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
mounting dimensions . . . . . . . . . . . . . . . . . . 303
outside dimensions. . . . . . . . . . . . . . . . . . . . 304
rating, parameter . . . . . . . . . . . . . . . . . . . . . 155
temperature, data parameter . . . . . . . . . . . . 108
weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
drive on time, data parameters . . . . . . . . . . . . . . 110

E
EAC marking. . . . . . . . . . . . . . . . . . . . . . . . . . . . 311

Index

316

earth fault
detection level . . . . . . . . . . . . . . . . . . . . . . . 151
fault code . . . . . . . . . . . . . . . . . . . . . . . . . . 262
parameter . . . . . . . . . . . . . . . . . . . . . . . . . . 150
earthing
see ground
EFB (embedded fieldbus) . . . . . . . . . . . . . . . . . 203
actual value scaling . . . . . . . . . . . . . . . . . . 211
actual values . . . . . . . . . . . . . . . . . . . . . . . . 211
analog output control, activate . . . . . . . . . . 209
comm fault response . . . . . . . . . . . . . . . . . 210
configuration . . . . . . . . . . . . . . . . . . . . . . . . 206
configure for loss of communication . . . . . . 213
control interface . . . . . . . . . . . . . . . . . . . . . 203
control word . . . . . . . . . . . . . . . . . . . . . . . . 224
diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . 212
drive control of functions, activate. . . . . . . . 207
exception codes . . . . . . . . . . . . . . . . . . . . . 223
fault code 28 . . . . . . . . . . . . . . . . . . . . . . . . 214
fault code 31 . . . . . . . . . . . . . . . . . . . . . . . . 214
fault code 32 . . . . . . . . . . . . . . . . . . . . . . . . 214
fault code 33 . . . . . . . . . . . . . . . . . . . . . . . . 214
fault tracing parameters . . . . . . . . . . . . . . . 212
fault, duplicate stations . . . . . . . . . . . . . . . . 213
fault, intermittent off-line . . . . . . . . . . . . . . . 214
fault, no master station on line . . . . . . . . . . 213
fault, swapped wires . . . . . . . . . . . . . . . . . . 213
feedback from drive . . . . . . . . . . . . . . . . . . 211
input reference sel., activate . . . . . . . . . . . . 208
installation . . . . . . . . . . . . . . . . . . . . . . . . . . 204
misc. drive control, activate. . . . . . . . . . . . . 208
modbus actual values . . . . . . . . . . . . . . . . . 223
PID control setpoint source, activate . . . . . 210
planning . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
reference scaling, ABB drives profile . . . . . 233
reference scaling, DCU profile . . . . . . . . . . 233
relay output control, activate . . . . . . . . . . . . 209
set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
start/stop/direction control, activate . . . . . . 207
state diagram . . . . . . . . . . . . . . . . . . . . . . . 232
status word . . . . . . . . . . . . . . . . . . . . . . . . . 227
termination . . . . . . . . . . . . . . . . . . . . . . . . . 205
EFB, drive parameters . . . . . . . . . . . . . . . . . . . 184
protocol, parameter group . . . . . . . . . . . . . 184
baud rate, parameter . . . . . . . . . . . . . . . . . 184
command words, data parameters . . . . . . . 112
config file, fault code . . . . . . . . . . . . . . . . . . 263
control profile, parameter . . . . . . . . . . . . . . 184
CRC errors (count), parameter . . . . . . . . . . 184
fault codes . . . . . . . . . . . . . . . . . . . . . . . . . 263
fault function, parameter . . . . . . . . . . . . . . . 150
fault time, parameter . . . . . . . . . . . . . . . . . . 150
ok messages (count), parameter . . . . . . . . 184
parameters . . . . . . . . . . . . . . . . . . . . . 184, 185
parity, parameter. . . . . . . . . . . . . . . . . . . . . 184
protocol id, parameter . . . . . . . . . . . . . . . . . 184
protocol select, parameter . . . . . . . . . . . . . 201
relay output word, data parameter . . . . . . . 109
station id, parameter . . . . . . . . . . . . . . . . . . 184
status words, data parameters . . . . . . . . . . 112
status, parameter . . . . . . . . . . . . . . . . . . . . 184
UART errors (count), parameter . . . . . . . . . 184
values, data parameter . . . . . . . . . . . . . . . . 109

Index

ACS550-01/U1 Users Manual

efficiency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
ELV (Extra Low Voltage) . . . . . . . . . . . . . . . . . . . 29
EM1 and EM3 screws
location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
on corner grounded TN system . . . . . . . . . . . 27
on IT systems . . . . . . . . . . . . . . . . . . . . . . . . . 27
on symmetrically grounded TN systems . . . . 27
warning. . . . . . . . . . . . . . . . . . . . . . 25, 285, 286
embedded fieldbus
see EFB
see EFB, drive parameters
EMC
CE marking . . . . . . . . . . . . . . . . . . . . . . . . . 309
C-Tick marking . . . . . . . . . . . . . . . . . . . . . . . 310
motor cable requirements . . . . . . . . . . . . . . 293
EMC filter, external . . . . . . . . . . . . . . . . . . . . . . . 286
EMC filter, internal . . . . . . . . 27, 285, 286, 311, 312
emergency
deceleration time, parameter . . . . . . . . . . . . 140
stop devices . . . . . . . . . . . . . . . . . . . . . . . . . 283
stop select, parameter . . . . . . . . . . . . . . . . . 137
enclosure
protection class code . . . . . . . . . . . . . . . . . . . 17
types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
encoder
parameter group. . . . . . . . . . . . . . . . . . . . . . 181
enable, parameter . . . . . . . . . . . . . . . . . . . . 181
error, fault code . . . . . . . . . . . . . . . . . . . . . . 263
fault, parameter . . . . . . . . . . . . . . . . . . . . . . 181
number of pulses, parameter . . . . . . . . . . . . 181
position reset enable, parameter . . . . . . . . . 181
zero pulse detected, data parameter . . . . . . 110
zero pulse enable, parameter . . . . . . . . . . . 181
energy saving
parameter group. . . . . . . . . . . . . . . . . . . . . . 180
CO2 conversion factor, parameter . . . . . . . . 180
energy price, parameter . . . . . . . . . . . . . . . . 180
energy reset, parameter . . . . . . . . . . . . . . . . 180
pump power, parameter . . . . . . . . . . . . . . . . 180
saved amount 1, data parameter . . . . . . . . . 111
saved amount 2, data parameter . . . . . . . . . 111
saved CO2, data parameter. . . . . . . . . . . . . 111
saved kWh, data parameter . . . . . . . . . . . . . 111
saved MWh, data parameter . . . . . . . . . . . . 111
error value inversion (PID), parameter . . . . . . . . 171
exception codes, EFB modbus . . . . . . . . . . . . . . 223
external comm module, parameter group
see FBA, drive parameters
external commands selection, parameter. . . . . . 115
external control selection, parameter . . . . . . . . . 117
external fault
automatic reset, parameter . . . . . . . . . . . . . 152
fault codes . . . . . . . . . . . . . . . . . . . . . . . . . . 262
parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 148
external reference, data parameter . . . . . . . . . . 108

ACS550-01/U1 Users Manual

F
F1 and F2 screws
location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
on corner grounded TN system. . . . . . . . . . . 27
on IT systems . . . . . . . . . . . . . . . . . . . . . . . . 27
on symmetrically grounded TN systems . . . . 27
warning . . . . . . . . . . . . . . . . . . . . . 26, 285, 286
fan
control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
maintenance . . . . . . . . . . . . . . . . . . . . 272, 274
fault
functions, parameter group . . . . . . . . . . . . . 148
history, parameter group . . . . . . . . . . . . . . . 114
codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
comm failure (EFB) . . . . . . . . . . . . . . . . . . . 210
current at, history parameter . . . . . . . . . . . . 114
digital input status at, history parameter . . . 114
FBA comm . . . . . . . . . . . . . . . . . . . . . . . . . 244
frequency at, history parameter . . . . . . . . . 114
history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
last, history parameter. . . . . . . . . . . . . . . . . 114
listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
logging (Assistant Control Panel) . . . . . . . . . 61
mode (Assistant Control Panel) . . 49, 259, 260
mode (Basic Control Panel) . . . . . 69, 259, 260
previous, history parameter. . . . . . . . . . . . . 114
reset . . . . . . . . . . . . . . . . . . . . . . . . . . 132, 265
reset select, parameter . . . . . . . . . . . . . . . . 129
speed at, history parameter . . . . . . . . . . . . 114
status at, history parameter. . . . . . . . . . . . . 114
time of, history parameters . . . . . . . . . . . . . 114
torque at, history parameter . . . . . . . . . . . . 114
voltage at, history parameter. . . . . . . . . . . . 114
words, data parameters . . . . . . . . . . . . . . . 113
fault display
alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
fault names . . . . . . . . . . . . . . . . . . . . . . . . . 260
FB actual signals, parameter group. . . . . . . . . . 112
FBA
protocol listing . . . . . . . . . . . . . . . . . . . . . . . 237
FBA (fieldbus adapter). . . . . . . . . . . . . . . . . . . . 237
actual values . . . . . . . . . . . . . . . . . . . . . . . . 239
analog output control, activate . . . . . . . . . . 243
comm fault response. . . . . . . . . . . . . . . . . . 244
configuration . . . . . . . . . . . . . . . . . . . . . . . . 241
control word. . . . . . . . . . . . . . . . . . . . . . . . . 238
control word, ABB drives. . . . . . . . . . . . . . . 248
diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . 245
drive feedback. . . . . . . . . . . . . . . . . . . . . . . 244
fieldbus control, activate . . . . . . . . . . . . . . . 241
input reference sel., activate . . . . . . . . . . . . 242
installation . . . . . . . . . . . . . . . . . . . . . . . . . . 240
PID control setpoint source, activate. . . . . . 244
planning. . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
reference . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
relay output control, activate . . . . . . . . . . . . 243
set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
start/stop /direction control, activate . . . . . . 241
state diagram, ABB drives. . . . . . . . . . . . . . 251
status word . . . . . . . . . . . . . . . . . . . . . . . . . 239
status word, ABB drives . . . . . . . . . . . . . . . 249

Index

317

FBA, drive parameters . . . . . . . . . . . . . . . . . . . . 182


ext comm module parameter group . . . . . . . 182
command words, data parameters . . . . . . . . 112
config file CPI firmware revision, parameter. 182
config file id revision, parameter. . . . . . . . . . 182
config file revision, parameter . . . . . . . . . . . 182
fault function, parameter. . . . . . . . . . . . . . . . 150
fault time, parameter . . . . . . . . . . . . . . . . . . 150
fieldbus appl. program revision, parameter . 182
fieldbus CPI firmware revision, parameter . . 182
fieldbus parameter refresh, parameter . . . . . 182
fieldbus parameters . . . . . . . . . . . . . . . . . . . 182
fieldbus status, parameter . . . . . . . . . . . . . . 182
fieldbus type, parameter. . . . . . . . . . . . . . . . 182
protocol select, parameter . . . . . . . . . . . . . . 201
relay output word, data parameter . . . . . . . . 109
status words, data parameters . . . . . . . . . . . 112
values, data parameter. . . . . . . . . . . . . . . . . 109
feedback
multiplier (PID), parameter . . . . . . . . . . . . . . 173
on ABB manuals. . . . . . . . . . . . . . . . . . . . . . 325
select (PID), parameter . . . . . . . . . . . . . . . . 173
field weakening point . . . . . . . . . . . . . . . . . . . . . 289
fieldbus
see EFB (embedded fieldbus)
see EFB, drive parameters
see FBA (fieldbus adapter)
see FBA, drive parameters
fieldbus adapter
see FBA
see FBA, drive parameters
fieldbus, embedded
see EFB
see EFB, drive parameters
firmware
compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . 13
panel, version . . . . . . . . . . . . . . . . . . . . . . 47, 51
version, parameter . . . . . . . . . . . . . . . . . 66, 155
first environment
(C2), compliance with IEC/EN 61800-3 . . . . 311
(C2), motor cable length . . . . . . . . . . . . . . . . 290
definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
flange mounting . . . . . . . . . . . . . . . . . . . . . . . . . . 20
FlashDrop
application macro, parameter . . . . . . . . . . . . 106
connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
parameter view, parameter . . . . . . . . . . . . . 132
floating network
see IT system
flux braking, parameter . . . . . . . . . . . . . . . . . . . . 145
flux optimization, parameter . . . . . . . . . . . . . . . . 145
force trip, fault code . . . . . . . . . . . . . . . . . . . . . . 263
frame errors (count), parameter . . . . . . . . . . . . . 183
frame size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
free fall, stress testing . . . . . . . . . . . . . . . . . . . . . 307
frequency
at fault, history parameter. . . . . . . . . . . . . . . 114
max. limit, parameter . . . . . . . . . . . . . . . . . . 134
min. limit, parameter . . . . . . . . . . . . . . . . . . . 134
motor, resolution. . . . . . . . . . . . . . . . . . . . . . 289
motor, specification . . . . . . . . . . . . . . . . . . . 289
switching, parameter . . . . . . . . . . . . . . . . . . 146

318

ACS550-01/U1 Users Manual

fuses
208240 V drives . . . . . . . . . . . . . . . . . . . 282
380480 V drives . . . . . . . . . . . . . . . . . . . 282
500600 V drives . . . . . . . . . . . . . . . . . . . 283

G
gain (PID), parameter . . . . . . . . . . . . . . . . . . . . 170
generic profile, FBA
actual value mapping . . . . . . . . . . . . . . . . . 257
actual value scaling . . . . . . . . . . . . . . . . . . 257
overview . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
reference scaling . . . . . . . . . . . . . . . . . . . . 256
technical data . . . . . . . . . . . . . . . . . . . . . . . 256
gland kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
ground
cable/wire requirements . . . . . . . . . . . . . . . 285
fault protection . . . . . . . . . . . . . . . . . . . . . . 292

H
hand-auto macro . . . . . . . . . . . . . . . . . . . . . . . . . 82
heat dissipation . . . . . . . . . . . . . . . . . . . . . . . . . 301
hood (IP54 / UL type 12) . . . . . . . . . . . . . . . . 21, 36
how to do common tasks
with Assistant Control Panel . . . . . . . . . . . . . 50
with Basic Control Panel . . . . . . . . . . . . . . . . 69

I
I/O settings (Assistant Control Panel) . . . . . . . . . 67
I/O, control through . . . . . . . . . . . . . . . . . . . . . . . 44
id run
fail, fault code . . . . . . . . . . . . . . . . . . . . . . . 262
parameter . . . . . . . . . . . . . . . . . . . . . . . . . . 107
performing. . . . . . . . . . . . . . . . . . . . . . . . . . . 45
identification magnetization . . . . . . . . . . . . . . . . 107
IEC ratings
see ratings
impedance grounded network
see IT system
incompatible software, fault code . . . . . . . . . . . 264
information on the Internet . . . . . . . . . . . . . . . . 325
information, parameter group . . . . . . . . . . . . . . 155
input power
cable/wire requirements . . . . . . . . . . . . . . . 284
disconnecting device (disconnecting means) 281
specifications . . . . . . . . . . . . . . . . . . . . . . . 281
input power connection
IT system . . . . . . . . . . . . . . . . . . . . . . . . . . 286
lugs for R6 . . . . . . . . . . . . . . . . . . . . . . . . . 287
terminal size . . . . . . . . . . . . . . . . . . . . . . . . 286
torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
installation
check list . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
compatibility . . . . . . . . . . . . . . . . . . . . . . . . . 18
environment . . . . . . . . . . . . . . . . . . . . . . . . . 18
flow chart . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
mounting drive . . . . . . . . . . . . . . . . . . . . . . . 22
preparation . . . . . . . . . . . . . . . . . . . . . . . . . . 16
procedures . . . . . . . . . . . . . . . . . . . . . . . . . . 15
tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
wiring overview . . . . . . . . . . . . . . . . . . . . . . . 23

Index

insulation check . . . . . . . . . . . . . . . . . . . . . . . . . . 30
integration time (PID), parameter . . . . . . . . . . . . 171
integration time, parameter. . . . . . . . . . . . . . . . . 141
interlocks, parameter . . . . . . . . . . . . . . . . . . . . . 195
internal setpoint (PID), parameter . . . . . . . . . . . 173
Internet, information on. . . . . . . . . . . . . . . . . . . . 325
IR compensation
frequency, parameter . . . . . . . . . . . . . . . . . . 145
parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 145
voltage, parameter . . . . . . . . . . . . . . . . . . . . 145
isolation, between AC power source and drive . 281
IT system
connections . . . . . . . . . . . . . . . . . . . . . . . . . 286
warning about filters . . . . . . . . . . . . . . . . . 6, 294
warning about screws at EM1, EM3. . . . . . . . 25
warning about screws at F1, F2 . . . . . . . . . . . 26

J
jogging activation, parameter . . . . . . . . . . . . . . . 116

K
keypad
see control panel
keypad reference select, parameter . . . . . . . . . . 117
kWh
counter, data parameter . . . . . . . . . . . . . . . . 108

L
label
serial number . . . . . . . . . . . . . . . . . . . . . . . . . 16
type designation . . . . . . . . . . . . . . . . . . . . . . . 16
language, parameter . . . . . . . . . . . . . . . . . . . . . 106
LED
on Assistant Control Panel. . . . . . . 48, 259, 260
on drive body . . . . . . . . . . . . . . . . . 25, 259, 260
library, document . . . . . . . . . . . . . . . . . . . . . . . . 325
limits, parameter group . . . . . . . . . . . . . . . . . . . . 133
load analyzer
parameter group. . . . . . . . . . . . . . . . . . . . . . 186
amplitude logger 1, distribution . . . . . . . . . . 187
amplitude logger 2 signal base value, par.. . 186
amplitude logger 2 signal, parameter. . . . . . 186
amplitude logger 2, distribution . . . . . . . . . . 187
loggers reset date . . . . . . . . . . . . . . . . . . . . 187
loggers reset time. . . . . . . . . . . . . . . . . . . . . 187
loggers reset, parameter . . . . . . . . . . . . . . . 186
peak value logger filter time, parameter . . . . 186
peak value logger signal, parameter . . . . . . 186
peak value logger, current at peak value . . . 187
peak value logger, detected peak value. . . . 186
peak value logger, frequency at peak value. 187
peak value logger, peak value date . . . . . . . 186
peak value logger, peak value time . . . . . . . 186
peak value logger, voltage at peak value . . . 187
load curve, see user load curve
load frequency, see user load curve
load torque, see user load curve
loading package version, parameter . . . . . . . . . 155
LOC (local control)
indication on Assistant Control Panel. . . . . . . 49
indication on Basic Control Panel . . . . . . . . . 68

ACS550-01/U1 Users Manual

local control mode lock, parameter . . . . . . . . . . 130


lock
control panel access, IP54 . . . . . . . . . . . . . . 36
drive control at local control panel. . . . . . . . 130
parameters . . . . . . . . . . . . . . . . . . . . . . . . . 129
loggers
see load analyzer
low frequency (PFC), parameters . . . . . . . . . . . 191
lugs
for R6 power cables . . . . . . . . . . . . . . . . . . 287
ring, crimp-on . . . . . . . . . . . . . . . . . . . . . . . 287
terminal, screw-on. . . . . . . . . . . . . . . . . . . . 288

M
macros
3-wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
ABB standard (default) . . . . . . . . . . . . . . . . . 78
alternate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
hand-auto . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
motor potentiometer . . . . . . . . . . . . . . . . . . . 81
PFC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
PID control . . . . . . . . . . . . . . . . . . . . . . . . . . 83
torque control . . . . . . . . . . . . . . . . . . . . . . . . 85
user parameter sets . . . . . . . . . . . . . . . . . . . 88
parameter default values. . . . . . . . . . . . . . . . 89
parameters not changed . . . . . . . . . . . . . . . . 77
magnetization, identification . . . . . . . . . . . . . . . 107
main menu
Assistant Control Panel. . . . . . . . . . . . . . . . . 50
Basic Control Panel. . . . . . . . . . . . . . . . . . . . 69
mains
see input power
maintenance
capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . 275
control panel . . . . . . . . . . . . . . . . . . . . . . . . 275
heat sink . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
internal enclosure fan . . . . . . . . . . . . . . . . . 274
intervals. . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
main fan . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
triggers, parameter group . . . . . . . . . . . . . . 147
manuals
list of ACS550 manuals. . . . . . . . . . . . . . . . . . 2
providing feedback . . . . . . . . . . . . . . . . . . . 325
mapping
actual value, FBA, generic profile . . . . . . . . 257
EFB modbus . . . . . . . . . . . . . . . . . . . . . . . . 216
materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
maximum
frequency, parameter . . . . . . . . . . . . . . . . . 134
torque limit, parameters . . . . . . . . . . . . . . . 135
torque select, parameter . . . . . . . . . . . . . . . 134
mechanical
angle, data parameter . . . . . . . . . . . . . . . . . 110
revolutions, data parameter . . . . . . . . . . . . 110
minimum
frequency, parameter . . . . . . . . . . . . . . . . . 134
torque limit, parameters . . . . . . . . . . . . . . . 134
torque select, parameter . . . . . . . . . . . . . . . 134

Index

319

modbus
EFB addressing, convention . . . . . . . . . . . . 216
EFB coils . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
EFB discrete inputs . . . . . . . . . . . . . . . . . . . 218
EFB holding registers . . . . . . . . . . . . . . . . . . 219
EFB input registers . . . . . . . . . . . . . . . . . . . . 219
EFB mapping details . . . . . . . . . . . . . . . . . . 216
EFB mapping summary . . . . . . . . . . . . . . . . 216
EFB supported features . . . . . . . . . . . . . . . . 215
EFB technical data . . . . . . . . . . . . . . . . . . . . 215
motor
checking insulation . . . . . . . . . . . . . . . . . . . . . 30
compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . 18
id run, parameter . . . . . . . . . . . . . . . . . . . . . 107
load curve break point frequency . . . . . . . . . 149
load curve max., fault parameter . . . . . . . . . 149
load curve zero speed load . . . . . . . . . . . . . 149
maintenance triggers . . . . . . . . . . . . . . . . . . 147
nominal current, parameter . . . . . . . . . . . . . 107
nominal frequency, parameter . . . . . . . . . . . 107
nominal power, parameter . . . . . . . . . . . . . . 107
nominal speed, parameter . . . . . . . . . . . . . . 107
nominal voltage, parameter . . . . . . . . . . . . . 107
phase, fault code . . . . . . . . . . . . . . . . . . . . . 263
requirements . . . . . . . . . . . . . . . . . . . . . . . . . 18
stall, fault code . . . . . . . . . . . . . . . . . . . . . . . 262
thermal protection. . . . . . . . . . . . . . . . . . . . . 291
motor cable
checking insulation . . . . . . . . . . . . . . . . . . . . . 30
length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289
max. length . . . . . . . . . . . . . . . . . . . . . . . . . . 289
requirements . . . . . . . . . . . . . . . . . . . . . . . . 292
requirements, EMC . . . . . . . . . . . . . . . . . . . 293
motor connection
lugs for R6 . . . . . . . . . . . . . . . . . . . . . . . . . . 287
terminal size . . . . . . . . . . . . . . . . . . . . . . . . . 286
torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
motor control
parameter group . . . . . . . . . . . . . . . . . . . . . . 145
control mode, parameter . . . . . . . . . . . . . . . 106
IR compensation, parameters . . . . . . . . . . . 145
motor potentiometer macro. . . . . . . . . . . . . . . . . . 81
motor temperature
measure, parameter group . . . . . . . . . . . . . . 159
alarm limit, parameter. . . . . . . . . . . . . . . . . . 160
data parameter . . . . . . . . . . . . . . . . . . . . . . . 110
fault limit, parameter . . . . . . . . . . . . . . . . . . . 161
overtemperature, fault code . . . . . . . . . . . . . 261
sensor selection, parameter . . . . . . . . . . . . . 160
sensor type, parameter . . . . . . . . . . . . . . . . 160
thermal protection. . . . . . . . . . . . . . . . . . . . . 291
thermal protection, fault parameter . . . . . . . 148
thermal stress, data parameter . . . . . . . . . . 111
thermal time, fault parameter . . . . . . . . . . . . 149
motor, auxiliary
aux start order, parameter . . . . . . . . . . . . . . 200
aux. start delay (PFC), parameter . . . . . . . . 191
aux. stop delay (PFC), parameter . . . . . . . . 191
number of aux., parameter . . . . . . . . . . . . . . 192
motors
several . . . . . . . . . . . . . . . . . . . . . . . . . 279, 289

320

ACS550-01/U1 Users Manual

mounting
dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 303
flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
template . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
multimotor systems . . . . . . . . . . 136, 146, 279, 289
MWh
counter, data parameter . . . . . . . . . . . . . . . 110
power consumption, maintenance trigger . . 147

N
NEMA ratings
see ratings
noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
random sw. freq. parameter . . . . . . . . . . . . 146
NPN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

O
offset (PID), parameter . . . . . . . . . . . . . . . . . . . 178
ok messages (count), parameter. . . . . . . . . . . . 183
operating data, parameter group. . . . . . . . . . . . 108
operation
Assistant Control Panel . . . . . . . . . . . . . . . . 49
Basic Control Panel . . . . . . . . . . . . . . . . . . . 69
OPEX link, fault code . . . . . . . . . . . . . . . . . . . . 262
OPEX power, fault code . . . . . . . . . . . . . . . . . . 262
options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
parameter group . . . . . . . . . . . . . . . . . . . . . 201
code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
output
frequency, data parameter . . . . . . . . . . . . . 108
voltage, data parameter . . . . . . . . . . . . . . . 108
wiring, fault code . . . . . . . . . . . . . . . . . . . . . 263
output mode
Assistant Control Panel . . . . . . . . . . . . . . . . 53
Basic Control Panel . . . . . . . . . . . . . . . . . . . 71
overcurrent
automatic reset, parameter . . . . . . . . . . . . . 152
fault code . . . . . . . . . . . . . . . . . . . . . . . . . . 260
overload curve
see user load curve
overmodulation . . . . . . . . . . . . . . . . . . . . . . . . . 146
overspeed, fault code . . . . . . . . . . . . . . . . . . . . 263
overvoltage
control enable, parameter . . . . . . . . . . . . . . 133

P
panel communication, parameter group . . . . . . 183
panel display variables, parameter group . . . . . 156
panel firmware version . . . . . . . . . . . . . . . . . 47, 51
panel loss, fault code. . . . . . . . . . . . . . . . . . . . . 261

Index

parameter
analog input scale, fault code. . . . . . . . . . . . 264
analog output scale, fault code . . . . . . . . . . 264
change lock . . . . . . . . . . . . . . . . . . . . . . . . . 129
descriptions . . . . . . . . . . . . . . . . . . . . . . . . . 106
external relay output, fault code . . . . . . . . . . 265
fieldbus, fault code . . . . . . . . . . . . . . . . . . . . 265
hz rpm, fault code. . . . . . . . . . . . . . . . . . . . . 264
listing (ranges, resolutions, defaults) . . . . . . . 91
PCU 1 (power control unit), fault code . . . . . 265
PCU 2 (power control unit), fault code . . . . . 265
PFC IO, fault code . . . . . . . . . . . . . . . . . . . . 265
PFC mode, fault code . . . . . . . . . . . . . . . . . 265
PFC ref. neg., fault code . . . . . . . . . . . . . . . 264
save changes . . . . . . . . . . . . . . . . . . . . . . . . 130
table version, parameter . . . . . . . . . . . . . . . 155
user load curve, fault code . . . . . . . . . . . . . . 265
view, parameter . . . . . . . . . . . . . . . . . . . . . . 132
parameter mode
Assistant Control Panel . . . . . . . . . . . . . . . . . 55
Basic Control Panel . . . . . . . . . . . . . . . . . . . . 73
parameter restore
Assistant Control Panel . . . . . . . . . . . . . . . . . 64
Basic Control Panel . . . . . . . . . . . . . . . . . . . . 75
parity
(RS-232), parameter . . . . . . . . . . . . . . . . . . 183
errors (count), parameter . . . . . . . . . . . . . . . 183
PE earth
earth fault, parameter . . . . . . . . . . . . . . . . . . 150
PE earth connection
terminal size . . . . . . . . . . . . . . . . . . . . . . . . . 286
torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
peak value logging
see load analyzer
PELV (Protective Extra Low Voltage) . . . . . . . . . . 29
PFC
control, parameter group . . . . . . . . . . . . . . . 189
acceleration time, parameter . . . . . . . . . . . . 200
aux start order, parameter . . . . . . . . . . . . . . 200
aux. motor start delay, parameter . . . . . . . . 191
aux. motor stop delay, parameter . . . . . . . . 191
deceleration time, parameter . . . . . . . . . . . . 200
enable, parameter . . . . . . . . . . . . . . . . . . . . 199
low frequency, parameters. . . . . . . . . . . . . . 191
macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
number of aux. motors, parameter . . . . . . . . 192
number of motors parameter . . . . . . . . . . . . 200
reference step, parameters . . . . . . . . . . . . . 189
start delay, parameter . . . . . . . . . . . . . . . . . 199
start frequency, parameters . . . . . . . . . . . . . 190

ACS550-01/U1 Users Manual

PID

process sets, parameter groups . . . . . . . . . 169


external / trimming, parameter group . . . . . 178
0% (actual signal), parameter . . . . . . . . . . . 172
100% (actual signal), parameter . . . . . . . . . 172
actual input select, parameters . . . . . . . . . . 174
actual value max., parameters . . . . . . . . . . 174
actual value min., parameters . . . . . . . . . . . 174
adjustment procedure . . . . . . . . . . . . . . . . . 170
comm value 1, data parameter . . . . . . . . . . 111
comm value 2, data parameter . . . . . . . . . . 111
control macro . . . . . . . . . . . . . . . . . . . . . . . . 83
correction source, parameter . . . . . . . . . . . 179
decimal point (actual signal), parameter . . . 171
derivation filter, parameter . . . . . . . . . . . . . 171
derivation time, parameter . . . . . . . . . . . . . 171
deviation, data parameter . . . . . . . . . . . . . . 109
error feedback inversion, parameter . . . . . . 171
external source activate, parameter . . . . . . 178
feedback multiplier, parameter . . . . . . . . . . 173
feedback select, parameter. . . . . . . . . . . . . 173
feedback, data parameter . . . . . . . . . . . . . . 109
gain, parameter . . . . . . . . . . . . . . . . . . . . . . 170
integration time, parameter . . . . . . . . . . . . . 171
internal setpoint, parameter . . . . . . . . . . . . 173
offset, parameter . . . . . . . . . . . . . . . . . . . . . 178
output, data parameter . . . . . . . . . . . . . . . . 109
parameter set select, parameter . . . . . . . . . 176
scaling (0100%), parameters. . . . . . . . . . 172
setpoint maximum, parameter. . . . . . . . . . . 173
setpoint minimum, parameter . . . . . . . . . . . 173
setpoint select, parameter. . . . . . . . . . . . . . 172
setpoint source, EFB comm activate. . . . . . 210
setpoint source, FBA comm, activate . . . . . 244
setpoint, data parameter . . . . . . . . . . . . . . . 109
sleep delay, parameter . . . . . . . . . . . . . . . . 175
sleep level, parameter. . . . . . . . . . . . . . . . . 175
sleep selection, parameter . . . . . . . . . . . . . 174
trim mode, parameter . . . . . . . . . . . . . . . . . 178
trim scale, parameter . . . . . . . . . . . . . . . . . 178
units (actual signal), parameter. . . . . . . . . . 171
wake-up delay, parameter. . . . . . . . . . . . . . 175
wake-up deviation, parameter. . . . . . . . . . . 175
PID controller
advanced set-up . . . . . . . . . . . . . . . . . . . . . 170
basic set-up. . . . . . . . . . . . . . . . . . . . . . . . . 169
planning
EFB comm . . . . . . . . . . . . . . . . . . . . . . . . . 204
FBA comm . . . . . . . . . . . . . . . . . . . . . . . . . 239
PNP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
power
consumption (MWh) maintenance trigger . . 147
data parameter . . . . . . . . . . . . . . . . . . . . . . 108
previous faults, history parameters . . . . . . . . . . 114
process PID sets, parameter groups . . . . . . . . . 169
process variables, data parameter . . . . . . . . . . 110
product
inquiries. . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
training . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
profiles, EFB comm . . . . . . . . . . . . . . . . . . . . . . 216
proportional gain, parameter . . . . . . . . . . . . . . . 141

Index

321

protection
circuit, required w/ chopper . . . . . . . . . . . . . 298
disconnecting device (disconnecting means) 281
enclosure standard . . . . . . . . . . . . . . . . . . . . 309
environmental. . . . . . . . . . . . . . . . . . . . . . . . 306
motor thermal . . . . . . . . . . . . . . . . . . . . . . . . 291
PT100 temperature sensor . . . . . . . . . . . . . . . . . 160
PTC temperature sensor. . . . . . . . . . . . . . . . . . . 160
pump power
see energy saving

R
radiation limits, conducted
EN 61800-3 . . . . . . . . . . . . . . . . . . . . . . . . . 294
ramp pair (accel/decel), parameter . . . . . . . . . . . 139
range listing for parameters . . . . . . . . . . . . . . . . . 91
ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
reference
select, parameter group . . . . . . . . . . . . . . . . 117
corrections for parameter values . . . . . . . . . 118
keypad control, parameter . . . . . . . . . . . . . . 117
maximum, parameters . . . . . . . . . . . . . . . . . 119
minimum, parameters. . . . . . . . . . . . . . . . . . 119
mode (Basic Control Panel) . . . . . . . . . . . . . . 72
select source, parameter . . . . . . . . . . . . . . . 117
step (PFC), parameters . . . . . . . . . . . . . . . . 189
reference scaling
EFB, ABB Drives profile . . . . . . . . . . . . . . . . 233
EFB, DCU profile . . . . . . . . . . . . . . . . . . . . . 233
FBA, ABB drives profile . . . . . . . . . . . . . . . . 252
FBA, generic profile . . . . . . . . . . . . . . . . . . . 256
reference setting
Assistant Control Panel . . . . . . . . . . . . . . . . . 54
Basic Control Panel . . . . . . . . . . . . . . . . . . . . 72
regulator by-pass control, parameter . . . . . . . . . 199
relative humidity
environment limit . . . . . . . . . . . . . . . . . . . . . 307
shipping limit. . . . . . . . . . . . . . . . . . . . . . . . . 307
relay output
parameter group . . . . . . . . . . . . . . . . . . . . . . 124
activation condition parameters . . . . . . . . . . 124
off-delay, parameters . . . . . . . . . . . . . . . . . . 125
on-delay, parameters . . . . . . . . . . . . . . . . . . 125
status, data parameter . . . . . . . . . . . . . . . . . 109
relays, specifications. . . . . . . . . . . . . . . . . . . . . . 299
REM (remote control)
indication on Assistant Control Panel. . . . . . . 49
indication on Basic Control Panel. . . . . . . . . . 68
remove cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
reset, automatic
parameter group . . . . . . . . . . . . . . . . . . . . . . 152
analog input less than min., parameter . . . . 152
delay time, parameter. . . . . . . . . . . . . . . . . . 152
external fault, parameter . . . . . . . . . . . . . . . 152
number of trials, parameter . . . . . . . . . . . . . 152
overcurrent, parameter . . . . . . . . . . . . . . . . . 152
trial time, parameter . . . . . . . . . . . . . . . . . . . 152
undervoltage, parameter . . . . . . . . . . . . . . . 152
resolution listing for parameters . . . . . . . . . . . . . . 91
resonance (avoiding)
select, parameter . . . . . . . . . . . . . . . . . . . . . 144
revolution counter, data parameter . . . . . . . . . . . 110

322

ACS550-01/U1 Users Manual

revolutions, mechanical, data parameter . . . . . 110


ring lugs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
RS-232
baud rate, parameter . . . . . . . . . . . . . . . . . 183
parity, parameter. . . . . . . . . . . . . . . . . . . . . 183
station id, parameter . . . . . . . . . . . . . . . . . . 183
RS-232 counts
buffer overruns, parameter . . . . . . . . . . . . . 183
CRC errors, parameter . . . . . . . . . . . . . . . . 183
frame errors, parameter . . . . . . . . . . . . . . . 183
ok messages, parameter . . . . . . . . . . . . . . 183
parity errors, parameter . . . . . . . . . . . . . . . 183
RS485 comm. . . . . . . . . . . . . . . . . . . . . . . . . . . 204
run enable source select, parameter. . . . . . . . . 129
run time
data parameter . . . . . . . . . . . . . . . . . . 108, 110
maintenance trigger . . . . . . . . . . . . . . . . . . 147

S
safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
save changes parameter. . . . . . . . . . . . . . . . . . 130
saving, energy
see energy saving
scalar:frequency mode . . . . . . . . . . . . . . . . . . . 106
scaling
actual value, FBA, ABB drives profile . . . . . 255
actual value, FBA, generic profile . . . . . . . . 257
actual values, EFB comm . . . . . . . . . . . . . . 211
reference, EFB, ABB drives profile . . . . . . . 233
reference, EFB, DCU profile . . . . . . . . . . . . 233
reference, FBA, ABB drives profile . . . . . . . 252
reference, FBA, generic profile . . . . . . . . . . 256
screw-on terminal lugs . . . . . . . . . . . . . . . . . . . 288
s-curve ramp, parameter . . . . . . . . . . . . . . . . . . 139
second environment
(C3), compliance with IEC/EN 61800-3 . . . 312
(C3), motor cable length . . . . . . . . . . . . . . . 290
definition . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
sensor type, parameter . . . . . . . . . . . . . . . . . . . 160
sensorless vector control mode. . . . . . . . . . . . . 106
serial 1 error (fault code 28) . . . . . . . . . . . . . . . 214
serial 1 error, fault code. . . . . . . . . . . . . . . . . . . 263
serial communication
see EFB (embedded fieldbus)
see EFB, drive parameters
see FBA (fieldbus adapter)
see FBA, drive parameters
serial number. . . . . . . . . . . . . . . . . . . . . . . . . 16, 17
service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
setpoint maximum (PID), parameter . . . . . . . . . 173
setpoint minimum (PID), parameter . . . . . . . . . 173
setpoint select (PID), parameter . . . . . . . . . . . . 172
shock, stress testing . . . . . . . . . . . . . . . . . . . . . 307
short circuit, fault code . . . . . . . . . . . . . . . . . . . 261
single phase supply
connection . . . . . . . . . . . . . . . . . . . . . . . . . . 23
derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
sleep selection (PID), parameter. . . . . . . . . . . . 174
slip compensation ratio, parameter . . . . . . . . . . 146
soft keys (Assistant Control Panel) . . . . . . . . . . . 48

Index

specifications
control connections . . . . . . . . . . . . . . . . . . . 299
input power. . . . . . . . . . . . . . . . . . . . . . . . . . 281
mains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
speed
and direction (signed), data parameter . . . . 108
at fault, history parameter . . . . . . . . . . . . . . 114
data parameter . . . . . . . . . . . . . . . . . . . . . . . 108
max. limit, parameter . . . . . . . . . . . . . . . . . . 133
min. limit, parameter. . . . . . . . . . . . . . . . . . . 133
speed control
parameter group. . . . . . . . . . . . . . . . . . . . . . 141
acceleration compensation, parameter . . . . 142
automatic tuning, parameter . . . . . . . . 141, 142
derivation time, parameter . . . . . . . . . . . . . . 141
integration time, parameter . . . . . . . . . . . . . 141
proportional gain, parameter . . . . . . . . . . . . 141
vector:speed mode. . . . . . . . . . . . . . . . . . . . 106
speed, constant
parameter group. . . . . . . . . . . . . . . . . . . . . . 120
digital input selection parameter . . . . . . . . . 120
parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 121
stall
frequency, fault parameter . . . . . . . . . . . . . . 150
function, fault parameter . . . . . . . . . . . . . . . 150
region . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
time, fault parameter . . . . . . . . . . . . . . . . . . 150
standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
C22.2 No. 14 . . . . . . . . . . . . . . . . . . . . . . . . 309
CE marking . . . . . . . . . . . . . . . . . . . . . . . . . 309
CSA marking . . . . . . . . . . . . . . . . . . . . . . . . 310
C-Tick marking . . . . . . . . . . . . . . . . . . . . . . . 310
EN 50178 . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
IEC 60664-1 . . . . . . . . . . . . . . . . . . . . . . . . . 309
IEC/EN 60204-1 . . . . . . . . . . . . . . . . . . . . . . 309
IEC/EN 60529 . . . . . . . . . . . . . . . . . . . . . . . 309
IEC/EN 61000-3-12 . . . . . . . . . . . . . . . . . . . 309
IEC/EN 61800-3 . . . . . . . . . . . . . . . . . . . . . . 309
IEC/EN 61800-5-1 . . . . . . . . . . . . . . . . . . . . 309
UL 508C . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
UL marking. . . . . . . . . . . . . . . . . . . . . . . . . . 310
start
parameter group. . . . . . . . . . . . . . . . . . . . . . 136
aux. motor (PFC), parameters . . . . . . . . . . . 190
aux. motor delay. . . . . . . . . . . . . . . . . . . . . . 191
control, EFB comm. . . . . . . . . . . . . . . . . . . . 207
control, FBA comm. . . . . . . . . . . . . . . . . . . . 241
DC magnetizing time, parameter . . . . . . . . . 136
delay (PFC), parameter . . . . . . . . . . . . . . . . 199
delay, parameter . . . . . . . . . . . . . . . . . . . . . 138
frequency (PFC), parameters. . . . . . . . . . . . 190
function, parameter . . . . . . . . . . . . . . . . . . . 136
inhibit, parameter . . . . . . . . . . . . . . . . . . . . . 137
select enable source, parameter . . . . . . . . . 131
torque boost current, parameter. . . . . . . . . . 137
start mode
automatic . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
automatic torque boost. . . . . . . . . . . . . . . . . 136
DC magnetizing . . . . . . . . . . . . . . . . . . . . . . 136
flying start. . . . . . . . . . . . . . . . . . . . . . . . . . . 136
start/stop
parameter group. . . . . . . . . . . . . . . . . . . . . . 136
with Assistant Control Panel . . . . . . . . . . . . . 52
with Basic Control Panel . . . . . . . . . . . . . . . . 70

ACS550-01/U1 Users Manual

start/stop/dir, parameter group . . . . . . . . . . . . . 115


starting order counter . . . . . . . . . . . . . . . . . . . . 194
start-up
assistant . . . . . . . . . . . . . . . . . . . . . . . . . 42, 57
data, parameter group. . . . . . . . . . . . . . . . . 106
guided, Assistant Control Panel . . . . . . . . . . 42
limited, Assistant or Basic Control Panel . . . 37
state diagram
comm (EFB) . . . . . . . . . . . . . . . . . . . . . . . . 232
comm, ABB drives. . . . . . . . . . . . . . . . . . . . 251
station id (RS-232), parameter . . . . . . . . . . . . . 183
status at fault, history parameter . . . . . . . . . . . . 114
status word
ABB drives, FBA, description . . . . . . . . . . . 249
EFB comm, definition . . . . . . . . . . . . . . . . . 227
FBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
FBA generic profile . . . . . . . . . . . . . . . . . . . 256
stop
parameter group . . . . . . . . . . . . . . . . . . . . . 136
aux. motor (PFC), parameters . . . . . . . . . . 191
aux. motor delay . . . . . . . . . . . . . . . . . . . . . 191
DC brake time, parameter. . . . . . . . . . . . . . 137
DC current control, parameter. . . . . . . . . . . 136
DC current ref., parameter . . . . . . . . . . . . . 137
emergency devices . . . . . . . . . . . . . . . . . . . 283
emergency select, parameter . . . . . . . . . . . 137
flux braking, parameter . . . . . . . . . . . . . . . . 145
function, parameter . . . . . . . . . . . . . . . . . . . 136
stress tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
supervision
parameter group . . . . . . . . . . . . . . . . . . . . . 153
parameter low limit, parameters . . . . . . . . . 153
parameter selection, parameters . . . . . . . . 153
supply cable
checking insulation . . . . . . . . . . . . . . . . . . . . 30
supply phase, fault code . . . . . . . . . . . . . . . . . . 262
switching frequency . . . . . . . . . . . . . . . . . . . . . . 289
control, parameter . . . . . . . . . . . . . . . . . . . . 146
derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
parameter . . . . . . . . . . . . . . . . . . . . . . . . . . 146
symmetrically grounded network
see corner grounded TN system
symmetrically grounded TN system . . . . . . . . . 285
system controls, parameter group . . . . . . . . . . . 129

T
temperature derating . . . . . . . . . . . . . . . . . . . . . 280
template, mounting . . . . . . . . . . . . . . . . . . . . . . . 20
terminal lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
terminals
control, description . . . . . . . . . . . . . . . . . . . . 28
control, specifications . . . . . . . . . . . . . . . . . 300
location diagram, R1R4 . . . . . . . . . . . . . . . 25
location diagram, R5/R6 . . . . . . . . . . . . . . . . 26
termination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
test date, parameter . . . . . . . . . . . . . . . . . . . . . 155
thermal fail, fault code . . . . . . . . . . . . . . . . . . . . 262
three-wire sensor/transmitter, connection example 86
time and date setting (Assistant Control Panel) . 62

Index

323

timed functions
parameter group . . . . . . . . . . . . . . . . . . . . . . 162
autochange, parameter . . . . . . . . . . . . . . . . 200
booster, parameter . . . . . . . . . . . . . . . . . . . . 164
enable, parameter . . . . . . . . . . . . . . . . . . . . 163
source, parameter . . . . . . . . . . . . . . . . . . . . 164
speed control . . . . . . . . . . . . . . . . . . . . . . . . 122
start time, parameter . . . . . . . . . . . . . . . . . . 163
stop time, parameter . . . . . . . . . . . . . . . . . . 163
timed mode, parameter. . . . . . . . . . . . . . . . . . . . 122
TN-S system . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
top cover, see hood
torque
at fault, history parameter. . . . . . . . . . . . . . . 114
boost current, parameter . . . . . . . . . . . . . . . 137
data parameter . . . . . . . . . . . . . . . . . . . . . . . 108
max. limit select, parameter . . . . . . . . . . . . . 134
max. limit, parameter . . . . . . . . . . . . . . . . . . 135
min. limit select, parameter . . . . . . . . . . . . . 134
min. limit, parameters . . . . . . . . . . . . . . . . . . 134
ramp down, parameter . . . . . . . . . . . . . . . . . 143
ramp up, parameter . . . . . . . . . . . . . . . . . . . 143
torque control
parameter group . . . . . . . . . . . . . . . . . . . . . . 143
macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
ramp down, parameter . . . . . . . . . . . . . . . . . 143
ramp up, parameter . . . . . . . . . . . . . . . . . . . 143
vector:torque mode . . . . . . . . . . . . . . . . . . . 106
training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
trim
mode (PID), parameter. . . . . . . . . . . . . . . . . 178
scale (PID), parameter . . . . . . . . . . . . . . . . . 178
two-wire sensor/transmitter, connection example. 86
type code
see type designation
type designation . . . . . . . . . . . . . . . . . . . . . . . 16, 17

U
U/f ratio, parameter . . . . . . . . . . . . . . . . . . . . . . . 145
UL/CSA markings . . . . . . . . . . . . . . . . . . . . . . . . 310
underload curve
see user load curve
undervoltage
automatic reset, parameter . . . . . . . . . . . . . 152
control enable, parameter . . . . . . . . . . . . . . 133
ungrounded network
see IT system
units (PID), parameter. . . . . . . . . . . . . . . . . . . . . 171
unknown drive type, fault code . . . . . . . . . . . . . . 264
unpacking drive. . . . . . . . . . . . . . . . . . . . . . . . . . . 16
unsymmetrically grounded networks
see corner grounded TN system
user load curve
parameter group . . . . . . . . . . . . . . . . . . . . . . 166
fault code . . . . . . . . . . . . . . . . . . . . . . . . . . . 264
frequency, parameters . . . . . . . . . . . . . 166, 167
function, parameter . . . . . . . . . . . . . . . . . . . 166
mode, parameter . . . . . . . . . . . . . . . . . . . . . 166
time, parameter . . . . . . . . . . . . . . . . . . . . . . 166
torque, parameters . . . . . . . . . . . . . . . . 166, 167

324

ACS550-01/U1 Users Manual

user parameter set . . . . . . . . . . . . . . . . . . . . . . . 88


change control, parameter . . . . . . . . . . . . . 130
download . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

V
vector:
speed mode . . . . . . . . . . . . . . . . . . . . . . . . 106
torque mode . . . . . . . . . . . . . . . . . . . . . . . . 106
version
firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
firmware, parameter . . . . . . . . . . . . . . . 66, 155
loading package, parameter . . . . . . . . . . . . 155
panel firmware . . . . . . . . . . . . . . . . . . . . 47, 51
parameter table, parameter . . . . . . . . . . . . 155
vibration, stress testing . . . . . . . . . . . . . . . . . . . 307
voltage
at fault, history parameter . . . . . . . . . . . . . . 114
rating code . . . . . . . . . . . . . . . . . . . . . . . . . . 17
voltage/frequency ratio, parameter . . . . . . . . . . 145

W
wake-up
delay (PID), parameter . . . . . . . . . . . . . . . . 175
deviation (PID), parameter . . . . . . . . . . . . . 175
warning
automatic start up . . . . . . . . . . . . . . . . . . . . . . 7
dangerous voltages . . . . . . . . . . . . . . . . . . 5, 6
disconnecting device (disconnecting means) . 7
ELV (Extra Low Voltage) . . . . . . . . . . . . . . . 29
EM1, EM3, F1 and F2 screws. . . . . . . . . . . . . 6
filter on corner grounded TN system. . . . . . . . 6
filter on IT system . . . . . . . . . . . . . . . . . . . . . . 6
high temperatures . . . . . . . . . . . . . . . . . . . . . . 5
listing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
not field repairable . . . . . . . . . . . . . . . . . . . 5, 6
parallel control connections . . . . . . . . . . . . . . 6
qualified installer . . . . . . . . . . . . . . . . . . . . . . . 5
weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
wiring
control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
fault, parameter. . . . . . . . . . . . . . . . . . . . . . 151
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
installation steps, IP21/cables . . . . . . . . . . . 30
installation steps, IP21/conduit . . . . . . . . . . . 32
installation steps, IP54/cables . . . . . . . . . . . 33
installation steps, IP54/conduit . . . . . . . . . . . 34
overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
requirements, general . . . . . . . . . . . . . . . . . . 23

XYZ
zero pulse
detected, data parameter . . . . .
enable, parameter. . . . . . . . . . .
zero speed
delay, parameter . . . . . . . . . . . .
load, fault parameter . . . . . . . . .

Index

. . . . . . . . . 110
. . . . . . . . . 181
. . . . . . . . . 138
. . . . . . . . . 149

Further information
Product and service inquiries
Address any inquiries about the product to your local ABB representative, quoting the type
designation and serial number of the unit in question. A listing of ABB sales, support and service
contacts can be found by navigating to www.abb.com/searchchannels.
Product training
For information on ABB product training, navigate to www.abb.com/drives and select Training
courses.
Providing feedback on ABB Drives manuals
Your comments on our manuals are welcome. Go to www.abb.com/drives and select Document
Library Manuals feedback form (LV AC drives).
Document library on the Internet
You can find manuals and other product documents in PDF format on the Internet. Go to
www.abb.com/drives and select Document Library. You can browse the library or enter selection
criteria, for example a document code, in the search field.

Contact us

www.abb.com/drives
www.abb.com/drivespartners

3AFE64804588 (3AUA0000001418) Rev H / EN