Job No

Project

NEW GATHERING CENTRE GC-31

14050474
Dept

Calculations for

WIND LOAD ON WALL ONLY FOR FLAT


ROOF STRUCTURE

SC

Date

11/11/2014

Sheet No

Checked by

VS

Date

11/11/2014

XXXXX

Variable

Description

XXXXX

Doc No

Civil

Calculated by

Formula

Value

Referance

Unit

Wind Prssure
Basic wind speed

Velocity pressure

qz

45.0

Topographic factor
Wind directionality factor

Kzt

1.0

Cl. 6.5.7 of ASCE7-05

Kd

0.85

Table 6-4

III

Table 1-1

1.15

Table 6-1

Occupancy category
Importance factor

Exposure
Velocity pressure exposure coefficient

Kz

Height of Structure

m/s

0.613*Kz*Kzt*Kd*V2*I

2.01*(Z/Zg)(2/

Section 5.0of KOC-G-007


Cl. 6.5.10 of ASCE7-05

Cl. 6.5.6.3 of ASCE7-05

Table 6-3
Varies

Zg

274.32

9.50

Z/Zg

Kz

qz (Kn/m2)

2.9

0.011

0.772

0.937

7.30

0.027

0.937

1.137

11.70

0.043

1.035

1.256

13.70

0.050

1.070

1.299

0.00

0.000

0.000

0.000

0.000

0.000

0.000

0.000

0.000

0.000

0.000

0.000

0.000

0.000

0.000

h/Zg

Kh

qh (Kn/m2)

13.70

0.050

1.070

1.299

Table 6-2
Table 6-2

Wind Pressure Coefficient Calculation:


Length of building (Larger dimension)

72.50

Width of building (Shorter dimension)

19.00

Height of building

13.70

Mean height of roof from ground

13.70

Gust Factor

0.85

Cl 6.5.8 of ASCE7-05

Job No

Project

NEW GATHERING CENTRE GC-31

14050474
Dept

Calculations for

WIND LOAD ON WALL ONLY FOR FLAT


ROOF STRUCTURE

Civil
SC

Date

11/11/2014

Sheet No

Checked by

VS

Date

11/11/2014

XXXXX

Variable

Description

XXXXX

Doc No

Calculated by

Formula

Value

Unit

Referance

External Pressure coefficient for wind blowing normal to larger dimension


L/B ratio

( where L = 19m & B = 72.5m )

Wall external pressure coefficient Cp

0.263

Cp

Windward wall

0.8

Leeward wall

-0.5

-0.7

Side wall
L =19m
-0.7

Wall pressure coefficient as per Figure 6-6 (ASCE 7-05)

Wind Dir.

Surface

L/B

Cp

use with

Windward

All values

0.8

qz

0-1

-0.5

Leeward
wall
0.8

qh

-0.5

B =72.5m

Side wall

All values

3.816

-0.7

qh

-0.7
External Pressure coefficient for wind blowing parallel to larger dimension
L/B ratio

( where L = 72.5m & B = 19m )

Wall external pressure coefficient

Cp

Windward wall

0.8

Leeward wall

-0.21

Side wall

-0.7

Coefficient diagram
B =19m
Wall pressure coefficient as per Figure 6-6 (ASCE 7-05)
-0.21

Surface

L/B

Cp

use with

Windward

All values

0.8

qz
qh

Leeward
wall
-0.7

-0.7

Side wall

-0.3

>=4

-0.2

All values

-0.7

qh

L =72.5m

0.8
Wind Dir.
Internal pressure coefficient
G*Cpi

(+)

0.18

(-)

-0.18

Fig 6-5 for Encosed building

Pressure

Suction

(+)0.18

(-)0.18

Job No

Project

NEW GATHERING CENTRE GC-31


Calculations for

WIND LOAD ON WALL ONLY FOR FLAT


ROOF STRUCTURE
Description

Design Wind Pressure calculation:

14050474
Dept

XXXXX

Doc No

Civil

Calculated by

SC

Date

11/11/2014

Sheet No

Checked by

VS

Date

11/11/2014

XXXXX

Variable

p=

Formula

q*G*Cp - qi*G*Cpi

Value

Unit

(For conservative considered qi = qh )

Referance

Eq 6-17 of ASCE7-05

(negative is for away from building and positive is for towards the building)
Contributing width for column along larger dimension

9.00

Contributing width for column along shorter dimension

6.00

Unit load on structure

U = p*W

in Kn/m
Uniform
Pressure

1) For Pressure(i.e. positive internal pressure) and wind blowing normal to Larger dimension
Windward wall (q=qz & qi=qh) at

Uniform load on structure in Kn/m

2.90

0.937*0.85*(0.8)-1.299*(0.18) =

0.41

Kn/m2

9*(0.41) =

3.69

7.30

1.137*0.85*(0.8)-1.299*(0.18) =

0.54

Kn/m2

9*(0.54) =

4.86

11.70 m

1.256*0.85*(0.8)-1.299*(0.18) =

0.63

Kn/m2

9*(0.63) =

5.67

13.70 m

1.299*0.85*(0.8)-1.299*(0.18) =

0.65

Kn/m2

9*(0.65) =

5.85

Leeward wall (q=qi=qh)

1.299*0.85*(-0.5)-1.299*(0.18) =

-0.79

Kn/m2

9*(-0.79) =

-7.11

Side wall (q=qi=qh)

1.299*0.85*(-0.7)-1.299*(0.18) =

-1.01

Kn/m2

6*(-1.01) =

-6.06

2) For Pressure(i.e. positive internal pressure) and wind blowing parallel to larger dimension
Windward wall (q=qz & qi=qh) at

2.90

0.937*0.85*(0.8)-1.299*(0.18) =

0.41

Kn/m2

6*(0.41) =

2.46

7.30

1.137*0.85*(0.8)-1.299*(0.18) =

0.54

Kn/m2

6*(0.54) =

3.24

11.70 m

1.256*0.85*(0.8)-1.299*(0.18) =

0.63

Kn/m2

6*(0.63) =

3.78

13.70 m

1.299*0.85*(0.8)-1.299*(0.18) =

0.65

Kn/m2

6*(0.65) =

3.9

1.299*0.85*(-0.21)-1.299*(0.18) =

-0.47

Kn/m2

6*(-0.47) =

-2.82

1.299*0.85*(-0.7)-1.299*(0.18) =

-1.01

Kn/m2

9*(-1.01) =

-6.06

Leeward wall (q=qi=qh)


Side wall (q=qi=qh)

3) For Suction (i.e. negative internal pressure) and wind blowing normal to larger dimension
Windward wall (q=qz & qi=qh) at

2.90

0.937*0.85*(0.8)-1.299*(-0.18) =

0.88

Kn/m2

9*(0.88) =

7.92

7.30

1.137*0.85*(0.8)-1.299*(-0.18) =

1.01

Kn/m2

9*(1.01) =

9.09

11.70 m

1.256*0.85*(0.8)-1.299*(-0.18) =

1.09

Kn/m2

9*(1.09) =

9.81

13.70 m

1.299*0.85*(0.8)-1.299*(-0.18) =

1.12

Kn/m2

9*(1.12) =

10.08

Leeward wall (q=qi=qh)

1.299*0.85*(-0.5)-1.299*(-0.18) =

-0.32

Kn/m2

9*(-0.32) =

-2.88

Side wall (q=qi=qh)

1.299*0.85*(-0.7)-1.299*(-0.18) =

-0.54

Kn/m2

6*(-0.54) =

-3.24

4) For Suction (i.e. negative internal pressure) and wind blowing parallel to larger dimension
Windward wall (q=qz & qi=qh) at

Leeward wall (q=qi=qh)


Side wall (q=qi=qh)

2.90

0.937*0.85*(0.8)-1.299*(-0.18) =

0.88

Kn/m2

6*(0.88) =

5.28

7.30

1.137*0.85*(0.8)-1.299*(-0.18) =

1.01

Kn/m2

6*(1.01) =

6.06

11.70 m

1.256*0.85*(0.8)-1.299*(-0.18) =

1.09

Kn/m2

6*(1.09) =

6.54

13.70 m

1.299*0.85*(0.8)-1.299*(-0.18) =

1.12

Kn/m2

6*(1.12) =

6.72

1.299*0.85*(-0.21)-1.299*(-0.18) =

0.01

Kn/m2

6*(0.01) =

0.06

1.299*0.85*(-0.7)-1.299*(-0.18) =

-0.54

Kn/m2

9*(-0.54) =

-3.24

Job No

Project

MOLEETA FPF AND OBC PROJECT

236207 IN01

Calculations for

Dept

Tank Foundation for T-8309 A/B

Calculated by

Fire Water Storage Tank.

Checked by

Civil

Doc No

PDOC-236207-CA-CIV-001-A

SB

Date

10/18/2007

Sheet No

MAT

Date

10/18/2007

1 of 7

SCOPE
This calculation presents the design of the foundation for the Fire Water Storage Tank T-8309 A/B . It includes dimension of the ringwall, analysis of stability to the
overturning for earthquake and wind.

REFERANCES, CODES and STANDARDS


The following documents were taken into account for the elaboration of this calculation .
ACI 301 :Specifications for Structural Concrete for Building
ACI 302 : Recommended Practice for Structural Concrete Floor and Slab Construction
ACI 318 : Building Code Requirements for Structural Concrete
ANSI/ASCE 7-95 : Minimum Design Loads for Buildings and Other Structures.
API Standard 650 - Welded Steel Tanks for Oil Storage Recommendations for Design and Construction of Foundations for Aboveground Oil Storage Tanks.
Appendix B.Seismic Design of Storage Tanks. Appendix E
General Specifications of Melut Basin Oil Development Project.
PDOC-SP-CIV-003 Sitework Design
PDOC-SP-CIV-013 Structural Design
PDOC-SP-CIV-014 Design of Specific Structures.

REFERENCES
PDOC-236207-DS-MEC-013 Rev. A - Data Sheet Fire Water Storage Tanks T-8309 A/B (Data Sheet attached).
Geotechnical Investigation for Moleeta FPF Project.

NOTE
These Design Calculations of Tank Foundation will be updated as per the data from Tank Vendor.
The width of Ring wall (b) calculation is based on following :
a) 200mm edge distance from Anchor bolt centre to outer face of Ring wall and
b) 150mm edge distance from internal diameter of shell to inner diameter of Ring wall
The height of Ring wall (h) calculation is based on following :
a) 200mm edge distance from Anchor bolt centre to outer face of Ring wall and
b) 150mm edge distance from internal diameter of shell to inner diameter of Ring wall