Академический Документы
Профессиональный Документы
Культура Документы
4, November 1996
205 1
P. B. Brogan
R Yacamini
University of Aberdeen
Department atf Engineering
AB9 2UE - Aberdeen, Scotland
TRANSFORMER INRUSH
ABSTRACT
2.0
Figure 1 shows the transient inrush current for a typical singlephase, 15 MVA, 230ld3kV169kV transformer switched onto the
system to which there were ncl other transformen connected. The
switch was closed at the momcent the voltage passes through zero
going positive and the residual flux in the transformer was zero.
INTRODUCTION
1.0
The transient phenomenon that occurs when a transformer is energised has been with us since the transformer was invented. Much
research has been carried out in order to explain the nature of the
transformer inrush current and to derive its mathematical formulations [l 41. However, one of the aspects of this transient which has
been largely ignored in the relevant literature is the effect of the
inrush current on the other transformers whch are already connected
to the system.
(I
2.1
I n r h Current Decay
The mechanism by which the clecay of the inrush current is accomplished may be illustrated in figure 2. It can be noted that whea the
inrush current flows through the system from the generator, the
voltage impressed on the terminals of the transformer is equal to the
system voltage source (e.m.0 minus the voltage drop across the
system impedance. Examination of the voltage waveshape shows
that the effect of the resistance is to decrease the area (integral) of
the positive voltage wave and to increase the area of the negative
voltage wave, thus making the resultant voltage at the transformer
terminals asymmetrical. As the transformer flux is strictly proportional to the area of the impre:;sed voltage, it is evident that under
this conditions, the positive flux generated in each cycle in the transformer is less than the negative flux generated by an amount equal
to [l]:
2052
3.0
SYMPATHETIC
TRANSFORMERS
Ap = :+T ( R - i)dt
where Ay is the flux change per cycle, R is the total senes resistance i n the clrcuit, 2 is the current through th~sresistance and T
is the penod of a cycle Note that R includes the resistance of the
transformer wnding
Voltage, flux
Bcurrent
-exist
time
INTERACTION
BETWEEN
..____.______....___.___~
system
e.m.f.
The point on the voltage wave at which the transformer is
energised.
2. The residual tlux in the transformer core and its sign with
respect to the first half-cycle of the steady state alternating
I
flux.
3. The saturation or maximum flux density of the ferromagnetic
material of the transformer core.
Figure 3 - Circuit used to investigate sympathetic mteraction
The total impedance of the circuit through which the inrush
4.
current flows.
Figure 4 shows the transient currents which are representative of the
simulations where TZ is energised m parallel wth the unloaded
This is true when just one hansformer is mvolved, i e. when the transformer TI. As can be seen in thls figure, the sympathetic intertransformer is swtched onto a system wthout any other transformer achon phenomenon takes place between the two transformers, with
in service However, m general, there are one or more transformers the peaks of the offset magnetismg current I , (sympathetic magnetalready connected to the system when another one is to be energised
In this case an interaction between the transformers may be pro- ising current) and to the inrush magnehsing current I 2 occumng m
duced, whch changes dramatically the duration and magrvtude of the opposite direction to each other, on alternate half cycles. Note
the inrush current [7] This mteraction, called Sympathetic interac- that the supply current i,, (figure 4c) is the sum of the currents I ,
tion, occurs due to saturation m the transformers already in service
and, therefore, it should be taken into account if an accurate analysis and I?
of transformer m s h transients is demanded Thus, a new item
could be included in the list above as a factor that affects the m s h The sympathetic mteraction may be explamed as follows: Before the
switch S is closed only the magnetising current of the unloaded
current, i e
transformer TI flows through the system. When the transformer TIis
5. The saturatlon level reached by the transformers already con- energised a transient inrush current is drained Gom the generator (e.
m. f.), which flows through the system. Due to the ai. ost entirely
nected to the system
1.
2053
unidifectional characteristic of this inrush current, the voltage drop
across the series resistance R, makes the voltage at the transformer's busbar (point of common coupling) asymmetrical. As the
flux in a transformer is strictly proportional to the area (integral) of
the voltage waveform at the transformer terminals, the flux generated in the transformer TI begins to be asymmetrical by an amount
which may be given by:
Ap,
=I:'T
[(Rs+r,)-i,+Rs-i2]d
where Ap, is the flux change per cycle in the transformer TI and
r, is the winding resistance of TI.
(4)
I
Thereafter, the polarity of the flux change per cycle Aq, inverts,
reducing the flux in the transfainner TI. As a result, the sympathetic
current i, begins to decay, as does the inrush current z, . Under this
condition, the voltage on the taminals of the transformers presents a
waveshape nearly symmetrical and the flux change per cycle in each
transformer will depend basically on the winding resistance of each
transformer, i. e.:
(5)
(r2. i , ) - dt
Ap2=
(AI
i2
13k12k-
At the same time, a flux change per cycle Ap, is produced in the
transformer Tz,which may be given by:
1 lklk-
900
800
(3)
600
(AI
i1
loot
W
O
2Wm
LOOm
bWm
BOOm
12
1L
16
18
'
2054
It is i
nto note that, in this case, the system resistance R,
plays the paradoxid role of keep- both transformers TI and, Tz
saturated (on alternate halfcycles) he currents i, and z2 will be
CoIlcOmttantly C S ~ S ~and eiieet of satumbon in the transfimners.
That is, the voltage drop ILC~OSSthe resistance R, produced by the
cwent i, during one halfkycle reduces the offset flux in TI and, at
the m e time,increases the offsetflux in the transformer Tz. In the
subsequent halfGyce is the current i, that will produce the voltage
drop, which inthe offset flux in the transfwmer TI and, at
the same time,redwesthe offset flux in Tz. This sequence repeats
itself, developing the phemnneMHl of sympathetic interaCtian between the transformers, a c h keeps them saturated for a long peridoftime. Thecurrentszl mdzZ thenwillalsoflowforapm
longed period of time until the transfreach thetr steady-state
magnetisiug conditions.This may take several seconds or perhaps
over minutes, dependmg essentdly on the transformer resistances.
This method of studying the inrush m a t has been used to examine the harmonic content of the inrush current in HVDC mverter
stations and to show how this high level of harmonic current can
cause temporary overvoltages 19, 101. However, the effect of the
sympathetic interaction on the duration and magnitude of the iKush
current has not been taken into account.
Considesring the very simple system shown in figure 3, ifthe transformer TI was not connected the current lr. tbrougb the system
would be the inrush current of the transfixiner T2 itself (figure 1)
The peak values of the harmonic components of this c m t as a
fimction of time is shown in figure 5. However, with TI cmnected to
the system (as shown in the figwe 3) the waveform of the current ins
will be that shown in figure 4c,which is the sum of the magnetising
HARMOMCANALYSIS
4.0
(A)
600
Ih
600
HaF+Aauc
CURnENT
500
500
-Ill Fundomenloll
400
300
\\
40(
i \
30
IOIDcl
2 00
20
I
~
\ \ \
'
I A
r t .
'"1
loo
\I.
Number
of
1
10
15
20
25
30
35
40
clc*s
25
30
35
40
'vcles
2055
It should be noted that this current decays relatively fast, with its
fundamental and harmonic components reaching relatively low
values after 30 cycles. At the 10th cycle, for example, the three
more predominant harmonic components Io, 4 and 13 are approximately 70A, 110A and 80A, respectively, and at the 30th
cycle all these harmonic currents are around 20A (the nominal
current of the transformer is 113A).
In the case with sympathetic interaction the even ordered harmonic compoflents of the supply current i,, decay rather quickly,
whereas the odd harmonics .increase and continue to be present
for a considerable period of time (figure 6). This supply current,
which is the sum of the inrush magnetising current 2, and the
6.0
CONCLUSION
It has also been shown that the supply current is greatly affected by
this interaction due to the sympathetic magnetising currents that rise
in the transformers already connected to the system. The harmonic
analysis of the supply current when sympathetic interaction occurs
Eventually this current will have no DC neither even harmonic has shown that the even ordered harmonics of this current decay
components, as can be seen in figure 6. This figure shows that relatively quickly but the odd ordered harmonics increase and rethese harmonics are neghgible after the 20th cycle. In this case, main for a long period of time. This may change significantly the
the peak values of the harmonic components b, 12 and 13, at the temporary harmonic overvoltages which may occur in systems. The
10th cycle, are respectively 30A, 50A and 170A, showing a dra- duration of these overvoltages depends basically on the saturation
matic reduction of Io and 12 and a significant increase of I3 when level reached by the transformers and the energy dissipation pattern
compared with the case without sympathetic interaction, Note in the system considered.
that the 5th harmonic increases to a value that is substantially
ACKNOWLEDGEMENTS
greater than that in the case without sympathetic interaction.
sympathetic magnetising current i, (figure 4c), becomes increasingly symmetrical as TI goes into saturation.
It should be also noted, by inspection of figure 6, that the h- The authors wish to thank the Companhia Hidro Eletrica do S b
damental component of the supply current presents a hgh value Francisco - CHESF (Brazil) and the ConseIho Nacional de Desenand decays at a relatively very slow rate. This can cause a pro- volvimento Cientifico e Tecnolbgico - CNpq (Brazil) for the study
longed and appreciable transient demand of reactive power, pro- leave and financial support granted to Mr. H. Bronzeado, respecb i n g a sustained voltage drop in the system which may cause tively. The authors would like 10 thank Mr. J. F. de Lima for preparing this paper.
load rejection.
5.0
REFERENCES
BLUME L F., CAMlaLI G., FARNHAlW S. B. and
PETERSON H. A., Transformer Magnetizing Inrush Currents and Its Influence on System Operation, AIEE Trans.,
Vol. 63, pp. 366-375, 1944.
O
S
2056
P. B. Brogan received his Meng (Hons) degree f?om Glasgow University, in June 1993. Since October 1994 he has been a research
student at Aberdeen University.
BIOGRAPHIES
At the beginning of his career, he worked on maintenance of transmission lines and high-voltage equipment. In 1980, he started to
work with Power Quality, being responsible for performing power
system analysis and measurements associated with disturbances
caused by non-linear loads.
In 1993, after nearly 18 years experience of practical power engineering, he went to University of Aberdeen, Scotland (U. K), from
which he received his MSc degree m Power System Engineering. He
is currently working towards his PhD degree. His research interests
include Power Quality, power system transients and modelling of
transformers for transient and harmonic studies.
(E-mail:
doeph%cpul .ufpevm@pd3.npd.ufpe.br, Fax: + 55 81 2274970).