Вы находитесь на странице: 1из 3

POWERED BY CUMMINS ENGINE

www.univpower.com
Model

Prime Power

Standby Power

UC48E

48KW/60KVA

52KW/65KVA

Power Output at Different Voltage


Voltage
(V)

Frequency
(Hz)

Phases

PF(cos)

Standby
Current
(A)

Prime Current
(A)

Standby
Power
(KW/KVA)

Prime Power
(KW/KVA)

230/400

50

0.8

93.9

86.6

52/65

48/60

Dimension(mm)

Weight (kg)

Open Type: UC48E


750
1400
1920
1920
750

750

Soundproof Type: UC48E


1050
1600
2440
2440
1050

1290

Appearance Pictures

Standard Configurations
Open type

Soundproof Type

Cummins Diesel Engine made by DCEC China, Model 4BTA3.9G2. With radiator, fans driven by belt, with safety guard, With DC Base Fuel tank is equipped, With lifting ear
24V charge alternator.
Stamford Alternator Model: 224E, single bearing alternator;
Brushless, Self-exciting, IP23 Protection,Insulation class H

Special design air flow channel to reduce sound level,


professional consideration anti-rain drop proof

Muti-functional control panel is equipped

Outside Emergency Stop Button

24V starter maintenance free battery and connecting cable


together with switch

24V starter maintenance free battery and connecting cable


together with switch

Power output MCCB is equipped.

Outside Fuel Inlet, Outside Power Output Distribute Panel

Accessory: A suit of ripple flex exhaust pipe; exhaust siphon,


muffler; and a set of spare parts & Tools.

Fulfill 70 Db @ 7 meter high performance soundproof


canopy, Weatherproof & soundproof. The surface is under
antisepsis & antirust.

Specification can be changed without notice


Page 1

www.univpower.com
Optional Parts
Engine:

Water Jacket Heater / Water Separator

Alternator:

Permanent Magnet GeneratorPMG/ Anti Condensation Heater


Control System: Auto Control Panel / ATS / Battery Charge
Others:

Spare Parts / Tools / Daily Fuel Tank


Standard Control System

Automatic start control type panel is fit for backpack


structure and standing structure, and applied for whole
genset assembling. This control panel is a panel which
holds an intelligence gauge as its core control module
combined with engine operation assembling. It has
many functions as genset running parameter detecting
& running protection. With this intelligence gauge, some
parameters are adjustable such as start running,
preheating, and auto startup. It is the basic configuration
for unmanned guarding auto startup genset with its easy
operation, fully function & reliable protection. The MCCB
can be added to the standing structure panel according
to special requirements, in order to meet the power output.

Alternator Data
In compliance with GB755, BS5000, VDE0530, NEMAMG1-22, IED34-1, CSA22.2 and AS1359 standards
Manufacturer / Type:
Number of Phase:

STAMFORD/ 224E
3

Connecting Method:

3 Phase and 4 Wires, Y type connecting

Number of Bearing:

Power Factor:
Protection Grade:
Altitude Requirement:
Exciter Type:
Insulation Class/Temperature Rise:
Telephone Influence Factor (TIF):
THF:

0.8
IP23
1000m
Brushless, Self-exciting
H/H
50
2%

Steady State Voltage Regulation:

1%

Alternator Capacity:

60KVA

Alternator Efficiencies:

91.20%

Specification can be changed without notice

Page 2

www.univpower.com
Engine Data
Manufacturer / Model:
Air Intake System:
Fuel System:
No. of Cylinder:
Displacement:
BoreStroke:
Compression Ratio:
Rated RPM:
Max. Standby Power at Rated RPM:
Governor Type:

Cummins(DCEC) /4BTA3.9-G2
4 Cycle, Turbocharger
Direct Injection Fuel System
4 - In Line
3.9L
102120mm
16.5
1500rpm
55KW
High-precision Electric Speed Governor

Steady State Frequency Regulation:

0.5%

RPM of Piston:

6.0m/s
Exhaust System

Exhaust Flow:

4.05m3/min

Exhaust Temperature:

380

Max Back Pressure:

10kPa
Air Intake System

Max Intake Restriction:


Burning Capacity:
Intake Flow:

5kPa
1.97m3/min
m3/min
Fuel System(Fuel Consumption)

100% Standby Power Load:

8.1L/h

100% Prime Power Load:

12.5L/h

75% Prime Power Load:

10.4L/h

50% Prime Power Load:

7.8L/h

Total Fuel Flow:

L/h
Lubricating Oil System

Total Oil Capacity:

10.9L

Oil Pan Capacity:

9.5L

Oil Pressure at Rated RPM:

207~345kpa
Cooling System

Total Coolant Capacity:


The Highest Temperature:
Coolant Flow:

20L
104
132L/min
Electrical System

System Voltage(Starter Voltage):


Rated Current for Charge Alternator:

DC 24V
40A

Specification can be changed without notice