Академический Документы
Профессиональный Документы
Культура Документы
Min
12.3
15.7
17.5
13.2
10.7
12.0
Dec-13
Aug-14
Sept-14
Oct-14
Nov-14
Dec-14
CofA Limit
OPERATIONAL
PARAMETERS
Dec-13
Aug-14
Sept-14
Oct-14
Nov-14
Dec-14
CofA Limit
CHEMICAL
ADDITION
Dec-13
Aug-14
Sept-14
Oct-14
Nov-14
Dec-14
Raw Water
(m3)
Max
Average
25.5
16.9
37.6
28.8
36.9
23.3
47.2
23.1
40.0
17.8
28.2
18.6
93
Max Filter
Turbidity
(NTU)
0.53
0.49
0.10
0.45
0.70
0.40
>1.0 for 15 mins.
< 0.30 for 95%
Sodium Hypochlorite
Average Usage
(L)
0.7
1.5
1.1
1.1
0.9
0.9
Min
11.9
15.4
17.3
13.2
10.7
12.0
Treated Water
(m3)
Max
Average
25.0
16.4
37.0
28.5
36.9
23.1
47.2
23.1
40.2
17.8
28.4
18.7
Static
Level
(m)
19.00
19.60
19.08
21.00
19.60
18.35
0.05
Raw Water #1
(m3)
Min
Max
Average
2
6
3.40
1
5
3.30
2
5
3.75
2
4
3.00
2
9
4.40
1
4
2.33
696
STATIC
WATER
LEVELS
Dec-13
Aug-14
Sept-14
Oct-14
Nov-14
Dec-14
Min
7.70
11.60
11.60
8.90
5.39
6.00
OPERATIONAL
PARAMETERS
Dec-13
Aug-14
Sept-14
Oct-14
Nov-14
Dec-14
CofA Limit
CHEMICAL
ADDITION
Dec-13
Aug-14
Sept-14
Oct-14
Nov-14
Dec-14
Well #1
(m)
Max
7.85
15.60
16.30
8.96
7.50
7.60
Average
7.78
13.60
13.95
8.93
6.45
6.80
Sodium
Hypochlorite
Average Usage
(L)
3.37
2.88
2.56
3.39
3.01
2.28
Raw Water #2
(m3)
Min
Max
Average
48
306
184.13
79
228
130.74
58
192
126.32
59
232
143.87
69
351
141.60
49
197
127.58
696
Min
9.30
14.10
14.10
11.45
7.91
8.55
Min
93
53
67
77
63
66
Treated Water
(m3)
Max Average
194
135.03
133
90.13
118
86.79
127
99.42
243
96.80
120
87.62
Well #12
(m)
Max
Average
11.00
10.15
18.00
16.05
18.85
16.48
11.48
11.47
10.20
9.06
10.15
9.35
Polyaluminum
Chloride
Average Usage
(L)
7.1
4.6
4.8
6.3
6.4
5.2
0.05
Potassium
Permanganate
Average Usage
(L)
5.7
4.8
6.3
6.2
6.0
4.8
Min
423
174
483
602
385
544
Dec-13
Aug-14
Sept-14
Oct-14
Nov-14
Dec-14
CofA Limit
OPERATIONAL
PARAMETERS
Dec-13
Aug-14
Sept-14
Oct-14
Nov-14
Dec-14
CofA Limit
CHEMICAL
ADDITION
Dec-13
Aug-14
Sept-14
Oct-14
Nov-14
Dec-14
Raw Water
(m3)
Max
1041
1310
1208
1158
1524
1458
2600
Average
718.74
779.55
858.00
835.23
865.40
946.03
Sodium Hypochlorite
Average Usage
(L)
22.08
26.10
26.26
23.66
25.52
26.26
Min
431
414
433
606
26
569
Treated Water
(m3)
Max
Average
1152
726.10
1384
793.10
1332
867.20
1224
842.10
1642
870.33
1480
931.55
Min
1.19
1.59
0.01
1.64
3.70
2.35
Bulk Water
(m3)
Max
20.45
34.63
14.99
29.92
19.72
28.19
Min
1.38
1.13
1.29
1.20
1.19
1.41
0.40
0.05
Average
7.09
12.89
6.89
10.29
10.35
11.69
Min
42
48
54
51
41
45
Water Meter
(m3)
Max
Average
85
61.81
172
106.32
112
76.57
108
77.35
90
67.43
94
67.23
Facility Summaries
Pottawatomi
Static water levels have been fairly stable throughout the past 5 months with a slight drop in
December.
Chemical usage is flow paced so increases and decreases as flows increase or decrease.
Shallow Lake
Static water levels have dropped significantly the past 3 months.
Filter turbidity of 2.00NTU each month is a direct result of running generators or power bumps
Chemical usage is flow paced so increases and decreases as flows increase or decrease.
Oxenden
Flows are decreasing due to season change. Residents are leaving cottages for the winter
East Linton
Plant flows have been fairly stable, no noticeable increases or decreases observed.
Chemical usage is flow paced so increases and decreases as flows increase or decrease.
As of 1 April, 2007 Veolia Water Canada has completed the installation and set-up of a computerized
maintenance monitoring program (Job Plus).
Pottawatomi
Shallow Lake
Oxenden
East Linton
No water main / service connection repairs during the month of December, 2014
The annual MOE inspection for East Linton WTP was completed on 8 December, 2014. No draft or final
copy of the inspection report has been received.
No adverse water quality incident (AWQI) reports during the month of December, 2014
The monthly safety inspections for the Georgian Bluffs facilities are completed by the local Safety
Coordinator, Robert Robinson.
System
Item Identified
Action Needed
Shallow Lake
Fire pump electrical conduit needs repair
Contact local electrician to repair conduit
East Linton
Sodium Hypochlorite drum storage
Require a location to store these drums
- Eye wash required
- Proper containment
- Secure location
Front door requires repair
Township to contact contractor to repair door