CaseEditor
I1:SimulatorCaseEditor
2014PowerWorld Corporation
Overview
Simulatorseamlesslyintegratestwofunctions
oncecommonlyseparatedinpowerflow
software:
Graphicalpowersystemcaseeditor
PowerFlowpackagewithmanyrelatedanalysis
tools:
ContingencyAnalysis,TimeStepSimulation,Sensitivity
Analysis,LossAnalysis,FaultAnalysis,OPF,PVQV,ATC,
SCOPF
Also,TransientStabilityandDistributedComputing
haverecentlybecomeavailable
I1:SimulatorCaseEditor
2014PowerWorld Corporation
StartingSimulator
Onstartup,click
File ontheribbon
toaccesstheFile
Menu
I1:SimulatorCaseEditor
2014PowerWorld Corporation
10
ModesofOperation
Thegraphicalpowersystemcaseeditorand
thepowerflowpackageareimplementedin
Simulatorstwodistinctmodes:
EditMode
RunMode
I1:SimulatorCaseEditor
2014PowerWorld Corporation
14
EditMode
Tasks
Createnewpowerflowcases
Modifyexistingcases
Abilities
Casescanbemodifiedeithergraphicallyorviatext
displays
I1:SimulatorCaseEditor
2014PowerWorld Corporation
15
RunMode
Standalonepowerflow
Powerflowanalysistoolsandsensitivities
ContingencyAnalysis
TimeStepSimulation
OptimalPowerFlow(OPF)
PVandQVCurveTools(PVQV)
AvailableTransferCapability(ATC)
SecurityConstrainedOPF(SCOPF)
SensitivityAnalysis
LossAnalysis
FaultAnalysis
TransientStability
Geomagnetically InducedCurrent(GIC)
I1:SimulatorCaseEditor
2014PowerWorld Corporation
16
EditMode
Usedtocreateanewcaseormodifyanexisting
case.
UsetheRibbonbuttonstoswitchbetween
modes.
YoucanswitchtoEditModeatjustaboutany
timeduringasimulation.
ThetoolsandtechniquesofEditModewillbe
introducedbycreatinganewpowerflowcase
andbymodifyinganexistingcase.
I1:SimulatorCaseEditor
2014PowerWorld Corporation
17
CreatingaNewCase
ClicktheFileMenu,thenselectNewCase.
ModeisautomaticallyswitchedtoEdit.
Promptedtosaveanyexistingcase.
Displaythenturnstodefaultoneline
backgroundcolor.
Casemaybebuiltbygraphicallyplacingobjects
ontheoneline.
I1:SimulatorCaseEditor
2014PowerWorld Corporation
18
Enteringabus
Clickanywhereontheoneline andselectthe
Drawribbontab.
Inordertoinsertabus,selectNetwork Bus
Selectpointonscreen.
BusOptions dialogisdisplayed
setbusnumberto1
setbusnametoONE
checkSystemSlackBus field
selectOK
I1:SimulatorCaseEditor
2014PowerWorld Corporation
19
BusOptionsDialog
Eachelectricalislandneedsaslackbusfor
powerbalance(pickupslack)
SelectOK to
savechangesAND
closethedialog
I1:SimulatorCaseEditor
Usedtocustomize
oneline
appearance
Usedtocancelbus
2014PowerWorld Corporation insertionorchanges
20
EnteringaGenerator
SelectNetwork Generator fromtheDraw
ribbontab.
Clickondesiredbus.
GeneratorOptions dialogisdisplayed
Enter0 intheMWOutput fieldoftheMWand
VoltageControltab
MakesureAnchored boxischecked
ClickOKtoacceptdefaultvaluesofremainingfields
I1:SimulatorCaseEditor
2014PowerWorld Corporation
21
GeneratorDialog
Terminal
busnumber
andname.
Status
Cost
models
Usedto
customize
display
appearance
Voltage/reactive
powercontrol
fields
I1:SimulatorCaseEditor
2014PowerWorld Corporation
Rotor
shape
22
OnelineDiagram
I1:SimulatorCaseEditor
2014PowerWorld Corporation
23
SavingtheCase
Tosavetheworkdonesofar,selectSaveCase,
fromtheFileMenu.
Beforecaseissaved,validationisruntomake
suretherearenoerrors.
ValidationresultsaredisplayedinMessageLog
display.Toviewthemessagelog,clickonLog
buttonintheToolsribbontab
I1:SimulatorCaseEditor
2014PowerWorld Corporation
24
DefaultSaveCaseFormats
Thepowerflowcaseitselfissavedusingthe
PowerWorldBinaryformat(*.pwb).
TheonelineissavedusingthePowerWorld
Displayformat(*.pwd).
Savingtheonelineinformationinaseparate
fileallowsusing:
Multipleonelineswiththesamecase
Asingleonelinewithdifferentcases
I1:SimulatorCaseEditor
2014PowerWorld Corporation
25
EnteringaSecondBus
AgainselecttheDrawribbontab,Network Bus
ClicktotherightofthebusONE
SetbusnametoTWO
Tomodelaload,selectAttachedDevicestab,click
AddorEditBusLoad,setConstantPowerMW to200
andConstantPowerMvar to100.
SelectNetwork Loadtoenteraloadsymbol
SetOrientation toup
EnsureAnchored boxischecked
I1:SimulatorCaseEditor
2014PowerWorld Corporation
26
UndoOnelineActions
Accidentaleditsononelinediagramcanbeundone
FoundonDraw ribbontab
DoesnotworkwithCaseInformationDisplays
Doesnotaffectchangestopowerflowcase
I1:SimulatorCaseEditor
2014PowerWorld Corporation
31
EnteringaTransmissionLine
Transmissionlinesaredrawnasaseriesofline
segments
Toenteratransmissionlinebetweenbuses1and2
SelecttheDraw ribbontab,Network TransmissionLine.
Clickonbus1.Thisbeginsprocessofinsertingtheline.
Movecursortodesiredlocation,thenleftclicktoentera
segment,doubleclickonterminalbustoend.
Note:Clickinganddraggingmousewhendrawing
transmissionlinesisusuallyNOTrecommended.This
willproduceacurvedlinewithmanysegments.
I1:SimulatorCaseEditor
2014PowerWorld Corporation
34
EnteringaTransmissionLine
Afterdoubleclicking,TransmissionLine/Transformer
Options dialogisdisplayed
I1:SimulatorCaseEditor
2014PowerWorld Corporation
35
TransmissionLineDialog
Terminal
busesare
usuallyset
automatically
Line
parameters
Linestatus
I1:SimulatorCaseEditor
Simulator
allowseight
different
limits
2014PowerWorld Corporation
36
TextFields
Descriptivetextfieldscanbeaddedtotheoneline by
selectingBackground TextfromtheDrawribbon
tab.
EntertextFirstCase towardstopofoneline
Tochangefontandbackgroundcoloroftextfields:
Selectthetextfield
SelecttheFormatbutton
Changethefonttoblue,26pointandthebackgroundto
white.
I1:SimulatorCaseEditor
2014PowerWorld Corporation
40
BusFields
Busfieldsshowinformationaboutbusdevices,
includingloadsandgenerators.
Fieldscanbeenteredautomatically,or
manually.ChooseFieldintheDraw ribbontab.
Canchoosetypeoffield,digitstorightandleft
ofdecimal,andwhetherornotitisanchored.
I1:SimulatorCaseEditor
2014PowerWorld Corporation
41
LineFields
Linefieldsshowinformationabout
transmissionlinesandtransformers.
Forlinefields,flowisalwaysspecifiedatan
endofthetransmissionlineortransformer.
Endisnormallydeterminedautomaticallyby
insertionpoint.
JustlikeTextFields,BusandLinefieldscanbe
formattedusingtheoptionsintheFormatting
ribbongroup.
I1:SimulatorCaseEditor
2014PowerWorld Corporation
42
SolvingtheCase
Tosolvethecase,clickonRunMode.
OnlypermittedtochangetoRunModeifthere
arenoerrors.Notethatasystemslackbus
mustbeset.
Toanimatethesimulation,gototheTools
ribbontabandselectthePlay buttoninthe
PowerFlowToolsribbongroup.
Ifnotvisible,clickonLogtoseeabackstage
viewofthepowerflowsolution.
I1:SimulatorCaseEditor
2014PowerWorld Corporation
43
CaseOptions
Tomodifyanimatedlineflows,selectthe
Onelines ribbontab Oneline Display
Options.IntheDialog:
clickontheAnimatedFlowsPage
checkShowFlowSymbols
checkUseFillColor
clickonActualMWFillColor
selectalightgreencolor
selectOK
I1:SimulatorCaseEditor
2014PowerWorld Corporation
44
InsertingPieCharts
Piechartsareusuallyautomaticallyinserted.
Formanuallyinserting,selecttheDraw ribbon
tab,Pies/Gauges LineFlowPieChart. Then
clickonthelinemidpoint.
Thepiechartsareusedtographicallyindicate
thepercentageloadingofeachline.
I1:SimulatorCaseEditor
2014PowerWorld Corporation
48
AutoFieldInsertion
ClicktheFieldPositionsTab
Typeof
fieldsbeing
modified
Clickon
Positionsto
AddorChange
FieldType
Displayed
I1:SimulatorCaseEditor
2014PowerWorld Corporation
52
Model Explorer
Encapsulates most Case Information
Displays
Provides means of navigating through
almost all of the data in the model
Available from a few places
Case Information Ribbon Tab
Tools Ribbon Tab
Quick Access Toolbar
2008 PowerWorld Corporation
I3-1
Model Explorer
Explore Pane
Recent Tabs
Options Pane
Case Information
Toolbar
Object Types
with no data
grayed-out
Note: The option available on
the Case Information right-click
local menu are now all available
on the Case Information Toolbar
directly above the display
Search Toolbar
I3-2
buses
generators
lines/transformers
loads
areas, zones
and everything else
I3-9
Model Explorer:
Generator Case Information Display
I3-10
I3-11
Auto-Size
Column
Widths
Send
Bus View
Set Field Values
Advanced
Sort
Advanced
Refresh
Filter
Geographic Data
Auxiliary
Headings,
View
File Options
Highlight
Set
Define
Key Fields,
Get
Column
Area/Zone
Expressions, etc.
etc.
Metrics, etc.
Filters
Display/Column
Options
2008 PowerWorld Corporation
I3-16
Logical
Comparator
Conditions
I3-41
Advanced Filtering
Some objects allow the use of filters defined for
related objects
Change Select Filter Type to select/define filters for
related objects
Example: Use bus filter for nominal voltages greater
than 138 kV to filter generators
I3-42
Advanced Filter
Logical Comparison specifies the filter logic.
Comparison applies across ALL conditions
I3-43
Field-To-Field Comparisons
Users have the option to include Field-To-Field
comparisons
I3-44
Copy/Send to Excel
Dialog Occurs only if session
of Excel is already running.
Cell A1 describes
the kind of data
Row 2
describes
which fields
are being
pasted
Select existing or
new workbook
and worksheet for
sending data
I3-57
I7-10
Simulator Options:
Power Flow Solution Page
To customize the power flow solution, go to the
Options ribbon tab and select Simulator Options
Power Flow Solution page
I7-11
Simulator Options:
Power Flow Solution Page
Common Options Tab
MVA Convergence Tolerance
the tolerance for the inner power flow loop
Must be larger than zero
I7-12
Simulator Options:
Power Flow Solution Page
Common Options Tab
Unchecking Enforce Generator MW Limits
means generator MW limits are not enforced
Gen MVAR Limits
Disable Checking means generator MVAR limits
are not enforced
Check immediately means the MVAR limits are
checked and handled first before a solution iteration
is run
I7-13
Simulator Options:
Power Flow Solution Page
Common Options Tab
Disable Switched Shunt Control (affects entire case)
Disable LTC Transformer Control (affects entire
case)
Disable Phase Shifter Control (affects entire case)
Transformer Stepping Methodology
Coordinated Sensitivities looks at all transformers that are
out-of-range and coordinates the movement to bring all
back within regulation range
Self-Sensitivity Only looks at each transformer
individually and determines the sensitivity of its regulated
value with respect to changing its own tap or phase only
2008 PowerWorld Corporation
I7-14
Simulator Options:
Power Flow Solution Page
Common Options Tab
Prevent Controller Oscillations
keeps controlled devices from continually switching
between two control states for the entire case
I7-15
Simulator Options:
Power Flow Solution Page
Advanced Options Tab
I7-16
Simulator Options:
Power Flow Solution Page
Advanced Options Tab
Dynamically add/remove slack buses as topology is
changes (Allow Multiple Islands)
If a single island is split into two islands (by opening lines),
then a new slack bus is chosen (generator with the largest MW
limit is chosen)
I7-17
Simulator Options:
Power Flow Solution Page
Advanced Options Tab
Disable Power Flow Optimal Multiplier
The optimal multiplier is a mathematically calculated step size
for Newtons Method that prevents the mismatch equations
from increasing between iterations.
I7-18
Simulator Options:
Power Flow Solution Page
Advanced Options Tab
Disable Treating Continuous SSs as PV Buses
Continuous switched shunts are normally treated as buses with
fixed power and voltage inside the inner power flow loop.
I7-19
Simulator Options:
Power Flow Solution Page
Advanced Options Tab
Disable Angle Rotation Processing
Voltage angles are rotated so that the angle range in an island is
equally spaced around zero degrees if any angles fall outside +/- 160
degrees
I7-20
Simulator Options:
Power Flow Solution Page
General Tab
I7-26
Simulator Options:
Power Flow Solution Page
General Tab
Assumed MVA Per Unit Base
MVA base used for the entire case
Default is 100 MVA
I7-27
Simulator Options:
Power Flow Solution Page
Storage Tab
I7-28
Islands - Defined
Often times power system consists of a single
interconnected system operating in synchronism
However sometimes multiple systems exist that are
either unconnected, or connected only through DC
transmission lines.
Such systems operate asynchronous with one another
and are called Islands.
Each island must have a slack bus. Check Allow
Multiple Islands.
I7-29
I7-30
Simulator
has automatically
chosen
bus 2 as the
slack.
Open tie-lines
2008 PowerWorld Corporation
I7-31
It is not uncommon to
have multiple islands.
Often cases in the
Eastern United States
have Five Islands
I7-32
Simulator Options:
Environment Page
Can have
Blackout
appear if
case does not
converge
Memory limit
for Oneline
Undo feature
I7-34
Simulator Options:
Oneline Page
Display
only; no
simulation
Solution
method
when
animating
Name of default oneline
file to open for ALL cases
Shows hints
when cursor
over element
Non-US
style XFR
symbols
Name of main oneline file
for CURRENT case
I7-35
Simulator Options:
File Manage Page
Special options
tab for EPC
and RAW files
Automatically
save over
current PWB.
0 means do
not Autosave
Enables previously saved PWB files to be automatically
archived each time the file is saved with the same name
2008 PowerWorld Corporation
I7-36
Contingency Analysis
Power systems are operated so that overloads do
not occur either in real-time or under any
statistically likely contingency.
This is often called maintaining system security
I10-1
specification
make-up
power also
allowed
I10-2
I10-3
I10-4
I10-5
Auto-Insertion of
Contingencies Dialog
Choose
types to
include
Select to include
only elements in
chosen areas
Apply Advanced
Filters for branches,
generators, or buses
I10-6
A Description of the
selected contingency
appears in the Contingency
Definition Section
Click X to
hide the
Definition
Section
Click to save the contingencies to file
2008 PowerWorld Corporation
I10-7
List of
contingency
elements
I10-8
Choose
element
type
Choose
action
type
Choose the
Element
Choose the
action
parameters
Add a comment
which will be
saved with
Auxiliary Files
I10-9
Options Tab:
Modeling
I10-14
Options Tab:
Modeling
Calculation Method
Full Power Flow
Linearized Lossless DC
similar to the DC Power Flow, but this is linearized around
present operating point
I10-15
Options Tab:
Modeling
Retry Solution using the Robust Solution Process
after a contingency failure
Attempts to solve the power flow in a series of steps
that involves turning on controls one type of control at
a time
I10-16
Options Tab:
Modeling Make-up Power
Describe which areas make up for a change
in the MW generation or load in the system.
Normally done use some sort of
participation from the areas or generation
in the case
Typically power systems control schemes like
AGC (or Economic Dispatch), do not respond
quickly enough to remove an overload after a
contingency. AGC acts on the 15 minute to 1
hour time frame (not tens of seconds)
2008 PowerWorld Corporation
I10-17
Options Tab:
Modeling Make-up Power
Area Participation Factors specified below
Each area is weighted according to the factors
specified. The total weight for the area is then spread
across all the area generation according to generator
participation factors.
The power flow is then solved using Island-Based AGC
I10-18
Options Tab:
Modeling
Define Contingency Solution Options
Allows you to specify different power flow solution
options for solving the post-contingency power flow.
This gives 3 levels of power flow solution options
1.
2.
3.
I10-19
Set As Reference
Sets whatever the present power system state is as the reference
state for Contingency Analysis
Restore Reference
Restores the system to the reference state
I10-20
I10-21
Fault Analysis
Analysis of power system parameters
resulting from a ground or line to line fault
somewhere in the system
Simulator contains a tool for analyzing
faults in an automatic fashion
Can perform single and three phase faults
I13-1
Fault Analysis
Fault types include:
I13-2
I13-3
I13-4
Current through
the fault
Devices
listed here
depend on
bus or inline fault
I13-5
I13-6
Transmission Lines
Zero sequence impedance
Zero sequence line shunt admittance
I13-7
Loads
Negative and zero sequence load, as an admittance
Set on a bus-basis, with admittance given is total
admittance for all loads at that bus
I13-8
I13-9
Mutual
impedance
records
I13-10