Вы находитесь на странице: 1из 20

Trane Commercial Systems

Trane : A Trusted HVAC Partner

ENERGY EFFICIENCY SUMMIT


Hyderabad 31st Oct , 2014

Small Capacity Water Cooled Screw Chiller

Caters to Hospitality industry &


Hot water utility
60 ~ 250 TR Range
Single / Twin Compressor
Hot Water Option upto 60 C
High reliability & Redundancy

Advanced controls

RTWD/S

RTWD : Twin Compressor Machine


RTWS : Single Compressor Machine

LARGE Capacity Water Cooled Screw Chiller


Hospitality, Commercial & Industrial
Applications

VFD option

140 400 TR Range

Single Compressor machine

High Reliability & Efficiency

COP Upto 6.45

ASME Certified Heat Exchangers

Advanced CH530 LLID Controls

RTHD

evaporator

High Performance & Efficiency


Proven Design Components
Optimized Operating Costs : Patented Falling Film
evaporator technology
Uses significantly less refrigerant than a similar-sized
chiller with flooded evaporator design
Offers better heat transfer and more overall energy
efficiency.
Patent by Trane

High reliability : Compressors

RTWD

Direct Drive - 3000 rpm @ 50 Hz


Only 3 moving parts
R134a optimized
Step-less Control unloading/loading scheme

EVAPORATOR DESIGN for EFFICIENCY

Tranes Patented Falling Film Evaporator design not only


Increases efficiency by Increasing Heat Transfer Area but also
reduces Refrigerant Charge by almost 35% compared to units of
similar capacity. Also, the cost of Refrigerant replacement/top
up is very high for units requiring Higher charge of Refrigerant

Building energy consumption


Chiller solution
For decades Trane has used slide valve
capacity control to:
Adapt chiller capacity to building needs
Reduce power input at part load
Technology providing best in class
efficiency

CPM-CMS001-E4_0613
2013 Trane - All rights reserved

New solution: Adaptive Frequency Drive


Reduce compressor speed
Adjust compressor speed to building needs
Keep unmatched full load efficiency and
reach best in class part load efficiency

RTHD with AFD

New RTHD AFD: top class efficiences


New Trane controller with TD7 interface
New Adaptive Frequency Drive allowing +17% on SEER( Seasonal
Energy Efficiency)
Still the highest EER of the market
Unbeatable Total Cost of Ownership
and Trane legendary reliability!

New RTAF: the new market standard!

New RTAE: Industry Leader !

The highest ESEER & the lowest sound levels

Industry Leading Part and

CPM-CMS001-E4_0613
2013 Trane - All rights reserved

both at no compromise
Optional Adaptive Frequency Drive
Integrated pumps with Variable Primary Flow
Partial and Total Heat Recovery
Unbeatable Total Cost of Ownership
and Trane legendary reliability!

Full -Load Energy


Permanent Magnet motors
screw compressors (both
circuits)
condenser fans (all)
Variable Speed
screw compressors (both circuits)
condenser fans (all)

CPM-CMS001-E4_0613
2013 Trane - All rights reserved

Air-Cooled Chillers
RTAF 85-200 TR

The best bundled in one. Our best.

Range introduction

EC
fans
EC
fans

Standard
Efficiency
SE

High
Efficiency
HE

eXtra
Efficiency
XE

High
Seasonal
Efficiency
HSE

090

090

090

090

105

105

105

105

125

125

125

125

500 kW

145

145

145

145

550 kW

155

155

155

155

600 kW

175

175

175

175

650 kW

190

190

190

190

205

205

205

205

300 kW
350 kW
400 kW
450 kW

700 kW
CPM-CMS001-E4_0613
2013 Trane - All rights reserved

750 kW

AFD = Adaptive Frequency Drive by Trane

Acoustics
Standard Noise SN
Low Noise LN
eXtra Low Noise XLN

no compromise on efficiencies
Main options
Hydraulic kit with dual pumps
Variable Primary Flow (VPF)
Partial & Total Heat Recovery
Modbus, BACnet, Lon

Top class efficiences reduced electricity bill!

CPM-CMS001-E4_0613
2013 Trane - All rights reserved

Standard Efficiency : SE
EER > 3,00 (B class)
ESEER = 3,90
Entry offering
High Efficiency : HE
EER > 3,15 (A class)
ESEER = 3,9
Value for money
High Efficiency : XE (EC fans)
EER > 3,25 (A class)
ESEER > 4,15
Highest savings
High Seasonal Efficiency : HSE
Adaptive Frequency Drive, inverter technology
ESEER up to 4,5
*ESEER = (EER@100% load x 0,03) + (EER@75% load x 0,33) + (EER@50% load x 0,41) + (EER@25% load x 0,23)

SMART to ease your life!


Intuitive & user friendly
Touchscreen
Color
Screen dimensions: 7 Inches
Main processor in the control panel

Operational effectiveness
Data trending
Clear alarm log
TIS enable for remote monitoring

CPM-CMS001-E4_0613
2013 Trane - All rights reserved

Settings

Data trends & graphs

Reports

Alarms

CPM-CMS001-E4_0613
2013 Trane - All rights reserved

TRANE STEALTH Chiller

with AdaptiSpeed Technology

Superior Part Load Efficiency


PM Motor

100%

AdaptiSpeed delivers optimal


performance at all conditions
AFD3 Adaptive Frequency
Drive
Variable speed on all
compressors
Variable speed on all
condenser fans
Permanent magnet motors
Standard on compressors
and condenser fan motors

AdaptiSpeed Technology
CPM-CMS001-E4_0613
2013 Trane - All rights reserved

Its the design and integration of

Rotor Profile has been Optimized


Specific Speed
Permanent Magnet Motor
AFD3 Adaptive Frequency Drive

Motor Efficiency (%)

Chiller Design
90%

80%

2% to 30%
Efficiency
Improvement

Induction
Motor

70%

60%

0%

10%

20%

30%

40%

50%

60%

70%

Speed (%)

80%

90% 100%

STEALTH Chiller
Industry-Leading Part and Full-Load Energy Efficiency
Multiple Sound Reduction Options
the quietest offering the lowest published levels
Variable Speed
screw compressors (both circuits)
condenser fans (all)

AdaptiView Display 7 color


Permanent Magnet motors

CPM-CMS001-E4_0613
2013 Trane - All rights reserved

screw compressors (both


circuits)
condenser fans (all)

150 300 tons


HFC-134a

Full Load Efficiency

150 300 Ton Stealth (RTAE)


Full Load Efficiency is anticipated to be within this
box

ASHRAE 90.1 2010 minimum

RTAC Extra High Efficiency


Introduced in 2012

RTAC High Efficiency

CPM-CMS001-E4_0613
2013 Trane - All rights reserved

RTAC Standard Efficiency

Over 20% more Efficient than ASHRAE 90.1 2010 at Full Load

Part Load Efficiency

150 300 Ton Stealth (RTAE)


Part Load Efficiency is within this box

ASHRAE 90.1 2010


minimum

CPM-CMS001-E4_0613
2013 Trane - All rights reserved

RTAC Standard, High and Extra Efficiency

Over 40% more Efficient than ASHRAE 90.1 2010 at Part Load

RTHD Water-Cooled Chillers with


Adaptive Frequency Drive

CPM-CMS001-E4_0613
2013 Trane - All rights reserved

High Efficiency Chillers for High


Performance Buildings

RTHD High Seasonal Efficiency


25%

Increased Part Load Efficiency (ESEER)


+25% vs market average at fixed speed
+17% vs Trane extra efficiency models

50%

75%

100%

With AFD
Savings
area

Without AFD
Part load operation

Decreased Inrush Current


Starting current lower than with standard Star-Delta starter
Superior Capacity Adjustment vs Load
RTHD fixed speed: 20% min.
RTHD HSE: 15% load min.
RTHD HSE can be provided with a built-in Harmonic Filter
Reduction % of Total Harmonic Distortion (THiD) transmitted
to the electrical network
Compliance with local standards and recommendations
Prevents from component breakdown by harmonic pollution
THiD < 5% (norm limits THiD < 30%)
IP 23, integrated in chiller panel

225%

25%

Inrush current with


Star-Delta Starter

Inrush current with AFD

Building energy consumption


Chiller operation

Chillers are selected at


most unfavourable
conditions.
99% of the time, chillers
operate at part load.
Improving part load
efficiency is key to reduce
building energy
consumption.

RTHD with AFD

Monthly typical load in comfort application


Selection conditions

Maximum temperature
Average temperature

Thanks