Вы находитесь на странице: 1из 3

Muhammad Huzaifa

Omer Qasim [omer.qasim@ajec-consulting.com]


Saturday, July 05, 2014 10:14 AM
'Muhammad Huzaifa'
FW: Al-Khurma SS - Lighting System Design Calculation-comments

From:
Sent:
To:
Subject:

Regards
Omer Qasim |Electrical Design Engineer
AlJazirahEngineers&Consultants|EML:omer.qasim@ajecconsulting.com
P:(+966)138584415Ext302|URL:www.ajecconsulting.com

From: S Ravichandran [mailto:sravichandran@starpowergen.in]


Sent: Saturday, July 05, 2014 9:29 AM
To: omer.qasim@ajec-consulting.com
Cc: rowther@starpowergen.in; soundararajan; anuja; ahmed Danish; Aleem Khan; Mohammed Altaf; bhuhari; ifthikar
Subject: Al-Khurma SS - Lighting System Design Calculation-comments

DearMr.Omer,

Pleasefindourcomments/clarificationsandobservationspertainingtoLightingDesigncalculationforAlKhurmah
Substation.

General
PleasechangethesubstationnameasAlKhurmah110/33/13.8kVinallthepages.
Page3of7and4of7.pleasechange13.8kVswitchgearinsteadof13.3kVswitchgear.
PLEASENOTETHATNOFITTINGSARHAVINGANYFIXINGDIMENSIONSVIZ.,XANDYCOORDINATES.THISWILL
RESULTDIFFICULTYTODEVELOPTHELAYOUTANDVERIFICATIONOFLAYOUTSINLINEWITHTHE
CALCULATION.PLEASEINCLUDETHEFIXINGCOORDINATESFOREACHFIXTURE.
PleasecheckandconfirmthatthetotallightingloadDBwise/roomwiseismatchingwiththeLightingDB
systemSLD.

PleaseincludeatableinIndoorandoutdoorDesignbasisgivinginformationasperthetablebelow

Sl.No

Room
Mounting Luxlevelrequired
(min)asperTES.P
Description Height
119.25,Rev01
(m)
1

Luxlevel
achieved
asper
calculation

Typeof
No.of
Luminarire/Lamp Fittings

IndoorLightingAnnexureI
In110kVGISroom,Mountingheightofall(Fl.Fitting&HighBay)luminaireisnotmentioned.Pleaseprovidethe
same.
InGISroomHPS(Highpressuresodiumvapourlamp)isused.Sodiumvapourhaspoorcolourrendering
comparedtometalhalidelamp.HoweverpleaseclarifytheyellowlightoutputisallowedinGISroomandalso
confirmSaud/NationalGridSAwillapprovewithHPSinGISroom.
Incontrolroomandcommunicationroom,pleasecalculatethelightingcalculationwiththepanelsasarrangedin
theLayout.
Inofficeroomthequantitycalculatedin1no,whereasquantitymentionedis2nos.pleasecheck.
Pleasecoordinatefixingoftheluminairesw.r.tthecabletrays,slabopenings,andotherservicesasrequired.
OutdoorLightingAnnexure3
ForsubstationyardareaLightlossfactorisconsideredas0.8,Howeverintheoutdoorlightingdesignbasisitis
mentionedas0.62(asperspec.).Pleasecheckandrevisethecalculation.

PleasefurnishALMOWYAH&ALQAMESSLightingdesignstakingcareoftheabove.

Regards
RAVI

From: Omer Qasim [mailto:omer.qasim@ajec-consulting.com]


Sent: Thursday, July 03, 2014 11:59 AM
To: 'S Ravichandran'
Cc: 'ifthikar'; 'bhuhari'; 'Mohammed Altaf'; 'soundararajan'; 'Aleem Khan'; 'ahmed Danish'; 'a.j.Naveen'; 'anuja'
Subject: Al-Khurma SS - Lighting System Design Calculation

Dear Mr. Ravichandran


Attached Lighting System Design Calculation for Al-Khurma SS.
Regards
Omer Qasim |Electrical Design Engineer
2

AlJazirahEngineers&Consultants|EML:omer.qasim@ajecconsulting.com
P:(+966)138584415Ext302|URL:www.ajecconsulting.com

Вам также может понравиться