I N S T R U M E N T S
TYPE 4860
GENERAL
A D VA N TA G E S
S TA N D A R D
V O LTA G E D I V I D E R
ARRANGEMENT
High voltage divider unit
The high voltage divider unit comprises
a capacitive high voltage divider (compressed gas standard capacitor C1 and
air capacitor C2) and an electronic device in series, constituting a variable electronic divider (see system diagram).
Capacitive voltage divider C1/C2 divides
the primary voltage Uprim to voltage
U1, which the electronic device matches
to the required secondary voltage Usec.
Voltage instrument transformers of less
than 1 kV primary voltage can be
connected directly to the electronic
system via the adaptor box supplied
with the divider.
Electronic device
The main components of this system are
an input amplifier and a guard-potential
control (up to 1010 V), an electronic
divider and a power amplifier with the
output stage. The instrument is protected against setting errors, overvoltages
and short-circuits. Message errors are
indicated in the dot matrix.
T E C H N I C A L S P E C I F I C AT I O N
Electronic system
type 4861 (4862)
General data
Power supply
230/115 V,
Input
50/60 Hz
1010 V
Power requirement
approx. 100 VA
Input resistance
> 10 G
Input capacitance
< 0.1 pF
temperature
Measurement signal
20...+70 C
Dimensions
frequency
45...65 Hz
(W x H x D)
16 2/3 Hz on request
10 nF
Weight
34 kg (74.8 lb)
Error limits
Output
Max. output voltage Usec
250 V
5 VA
Test frequency
0.4 A
At reference
50 or 60 Hz 1%
10 nF
System parameters
Rated primary voltage PV
At rated operating
conditions F = 100 ppm 0.2 min
Reference and rated operating conditions according to IEC 359, class I.
Input ranges:
Direct input
0.010...1.010 kV
With capacitive
divider
adjustment factors
Important!
Max. measurement voltage = max.
permissible rated voltage of compressed gas capacitor.
5 ... 250 V
x1, x1/3, x1/3
1:1...1:10 4
110 -6
Additional errors
With extended operating range
5...20% U/UR
50 ppm; 0.1 min
1...5% U/UR
B A S I C T E S T S E T- U P
type 4861
electronic device
Uprim
uN
vN
mains ground
U/UR
C1 + C2
C1
= 1 :
PV
SV
CR
200%
Uprim
U1
Excitation
UR
Uprim
PV
Usec
SV
Uprim
Usec
U1
100%
to instrument
transformer
test set
U1
series
3330/
C2
Usec
0
0
50%
100%
UR (PV, SV)
U
UR
U/UR
Dimensions
(L x W x H)
Weight
1000 V
1900...10,000 pF
E L E C T R O N I C S TA N D A R D V O LTA G E D I V I D E R
S E R I E S 4 8 0 0 S TA N D A R D S Y S T E M S
Standard system
Measurement range
(Primary HV)
Compressed gas
standard capacitor C1
Air capacitor C2
C divider ratio CR
Type
[Series/pF/kV]
Type
[Serie/pF]
CR = 1: (C1 + C2)/C1
3370NK/100/100 D
3330/9900
1:100
without
without
1:1
2 200 kV
3370NK/100/200 D
3330/9900
3330/10000 +
1:200
1 100 kV
3370NK/100/200 D
3330/9900
1:100
without
without
1:1
3 300 kV
3370NK/50/300
3330/4950
3330/10000 +
1:300
1 100 kV
3370/50/300 D
3330/4950
1:100
without
without
1:1
3370NK/50/400 D
3330/9950
3330/10000 +
1:400
without
without
1:1
3370NK/50/400 D
3330/9950
3370NK/50/400 D
3330/10000 +
1:400
3330/4950
1:100
without
without
1:1
3370NK/50/600 D
3330/9950
3330/10000 (2x) +
1:600
without
without
1:1
6 600 kV
3370NK/50/600 D
3330/9950
3330/10000 (2x) +
1:600
1 100 kV
3370NK/50/600 D
3330/4950
1:100
without
without
1:1
3370NK/50/800 D
3330/9950
3330/10000 (3x) +
1:800
without
without
1:1
8 800 kV
3370NK/50/800 D
3330/9950
3330/10000 (3x) +
1:800
1 100 kV
3370NK/50/800 D
3330/4950
1:100
without
without
1:1
Type
4861/100
1 100 kV
10 1010 V
4861/200
10 1010 V
4861/300
10 1010 V
4861/400a
4 400 kV
10 1010 V
4861/400b
4 400 kV
100 kV
10 1010 V
4861/600a
6 600 kV
10 1010 V
4861/600b
10 1010 V
4861/800a
8 800 kV
10 1010 V
4861/800b
10 1010 V
O R D E R S P E C I F I C AT I O N
Options
Electronic device
Type 4861
Compressed gas standard
capacitor
series 3370*
Air capacitors
series 3330
Adaptor box for direct
connection,
no. 014235-00
Measuring cable, 10 m
no. 014107-00
Measuring cable, 1.5 m no. 013685-00
Measuring cable, 0.5 m no. 014108-00
Ground cable,
16 mm2, 10 m
no. 016351-00
Power cable
Triax/coax adapter
no. 008140-72
for compressed gas standard capacitor
(for C/tan measurement)
RS 232C interface
type 4861/2
Power voltage
(please specify with order)
type 4861/1
type 5993
type 5991
type 5992
Important!
Adaption and comissioning of the standard voltage divider by TETTEX Instruments
is essential to ensure its required accuracy.
230 or 115 V,
50/60 Hz
TYPE 4860
Standard supply
E191.90
Subject to change
without notice 03.00
Haefely Test AG
Tettex & Haefely EMC Division
Bernstrasse 90, P.O. Box
CH-8953 Dietikon - Zurich
Switzerland
www.tettex.com
Phone: +41.1.744 74 74
Fax.:
+41.1.744 74 84
e-mail: sales@tettex.com