Академический Документы
Профессиональный Документы
Культура Документы
BUILDING PERMIT
Anytown, MA
The undersigned hereby applies to the Inspectional Services Commissioner for permit to erect the following building
or structure:
Certified street and number
Within
fire zone
Ward
Name of owner
Address
Address
Post-code
Type of construction
Dimensions of building or structure:
Main stairs
Front
Right side
Left side
Rear
Back stairs
Fire escapes
Concrete balconies
Other
Foundation material
Floor material
Wall material
Wall thickness
Roof construction
Soil
Party walls
Floors
Any others
Occupancy
Number of persons accommodated
Designed live load
Number of employees in building
Proposed occupancy
Cubic volume
Estimated cost
Date
The facts set forth above in this application and accompanying plans are a true statement made under penalty of perjury.
Telephone
(Signature of owner or authorized agent)
Address
(Name of contractor)
Address
License number
2005 National Fire Protection Association
Address
Class
BUILDING INFORMATION
Building address
Owner's representative or management company
Address
Telephone
Pager
Cell phone
Contact person
Number of stories above grade
Occupancy type
CONTRACTOR INFORMATION
Contact person (project manager, job foreman)
Name of company
Address
Company telephone
Pager
Cell phone
License number
Type
Pager
Cell phone
Name
Title
Date
(p. 1 of 3)
JOB INFORMATION
Is this a new sprinkler system installation?
Is this an alteration to an existing system?
Is this maintenance of an existing system?
Is this installation of new sprinkler equipment?
Will existing sprinkler system be physically removed
from area under construction?
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
N/A
N/A
N/A
N/A
N/A
IMPAIRMENT INFORMATION
Will (Check one.)
Building sprinkler system be shut off?
Building sprinkler system be drained?
Construction area be zoned out?
Will (Check one.)
Fire alarm be shut off?
Sprinkler alarm be disabled by zone?
Sprinkler alarm be disabled by building?
Will any means of egress or other fire protection feature be affected by this work or by any other work being performed by
you or any other contractor? (Consult with building management before answering this question.) Yes No N/A
Floor location
Job location
Job description
2005 National Fire Protection Association
(p. 2 of 3)
These fire safety requirements are in addition to and not in lieu of the requirements of NFPA 1, Uniform Fire Code.
Applicant signature
Print name
Impairment Coordinator signature
Print name
Date
Official Use Only
Approved by
Issued by
Date issued
Date of expiration
Permit number
(p. 3 of 3)
BASIS OF DESIGN
Project Name
Contract Number
BUILDING
Intended use
Construction type(s)
Building height
RESOURCES FOR FIRE FIGHTING (List when available during construction stages.)
SPECIAL CONSIDERATIONS
(p. 1 of 2)
Required
(Y/N)
Area
Protected
New, Addition,
or Modifcation
Plan Review
Installation
Acceptance
Fire alarm
Water-based sprinkler systems
Standpipe and hose systems
Water spray fixed systems
Foam water systems
Water mist systems
Wet chemical systems
Dry chemical systems
Inert gas systems
Low expansion foam systems
Private fire service mains
Private hydrants
Water tanks
Stationary pumps for fire
protection
Smoke-control systems
Emergency power systems
Other
Other
(p. 2 of 2)
Sales Rep:
Const. PM:
Job Name:
Heads Hrs/Head
P.M.
Const. Type:
Estimated:
Actual:
Hours to Go:
Variance:
New
Remodel
Address:
City/State:
Completed
No
Yes
Task
Design & PM review of documents
Pre-design meeting w/ sales rep.
Product brochure
Pre-install foreman meeting
O&M manuals
Comments
Quan.
Description
Req. No.
Date req.
X
X
X
X
X
% Matl in 2 weeks:
Floor or
Area
Start
Date
Head Count
Est.
Act.
Field
Check
Stock
List
Test
Cert.
Hyd.
Tag
0%
Job %
Ordered
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
Notes/Comments:
PROJECT SCHEDULE
Project Name
Contract Number
Date
Building System
D = Design
2005 National Fire Protection Association
A = Approval
F = Fabrication
I = Installation
PREINSTALLATION CHECKLIST
Project Name
Contract Number
Material/Equipment:
No shipping damage
Shipping damage (Describe.)
Signed:
Name
Title
Date
Company
COMMISSIONING TEAM
(The following is a list of organizations/individuals involved in the commissioning process for this project.)
Owner representative
Registered design professional
CONSTRUCTION MANAGER
Project manager
Superintendent
Commissioning manager
Coordination drawing manager
(Print name.)
(Print name.)
(Print name(s).)
Yes
No
N/A
Yes
No
N/A
Interface between system activation and building automatic systems is successful. List systems:
Numbered test blanks, if used, were removed and each is accounted for.
NFPA 25 was reviewed with owners rep. and copy given to:
Training class was scheduled.
Date
Time
Location
TRAINING PLAN
Project Name
Contract Number
Equipment/system
Training objective
Date
Time
Training location
Department
Telephone
Date
The undersigned hereby applies for a permit of occupancy in accordance with 780 CMR 120, sixth edition:
1. Location of building
Street Address
Unit Number
2. Applicant
3. Owner
Address
4. Occupant
5. Use group
Occupancy
6. Construction type
Occupant load
Plumbing/gas
Fire
Electrical
Health
Public works
I hereby certify that the work specified by the above named building permit has been completed and is ready for
occupancy.
Building Inspector
Inspection Director
Date
Installer
Supplier
Service organization
Location of record (as-built) drawings
Location of operation and maintenance manuals
Location of test reports
A contract for test and inspection in accordance with NFPA standard(s)
Contract number(s)
Effective date
System Software
(a) Operating system (executive) software revision level(s)
(b) Site-specific software revision date
(c) Revision completed by
(Name)
Representative name/phone
Expiration date
(Firm)
(p. 1 of 4)
Means of transmission of signals from the protected premises to the central station
McCulloh
Multiplex
One-way radio
Two-way radio
Others
Local energy
Shunt
Parallel telephone
10
11
Date
Organization
10
11
Date
Organization
Style
Class
(p. 2 of 4)
Coded
Addressable
Partial
Nonrequired
Addressable
Addressable
seconds to
seconds.
6. SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUITS (use blanks to indicate quantity of devices)
GUARDS TOUR
(a)
Coded stations
(b)
Noncoded stations
(c)
Compulsory guards tour system comprised of
transmitter stations and intermediate stations
Note: Combination devices are recorded under 5(b), Manual, and 6(a), Guards Tour.
SPRINKLER SYSTEM
Check if provided
(a)
Valve supervisory switches
(b)
Building temperature points
(c)
Site water temperature points
(d)
Site water supply level points
(p. 3 of 4)
7. ANNUNCIATOR(S)
Number
Type
Location
Multiple
Quantity and the class of notification appliance circuits connected to system (see NFPA 72, Table 6.7):
Quantity
Style
Class
Bells
With Visible
Speakers
With Visible
Horns
With Visible
Chimes
With Visible
Other:
With Visible
Visible appliances without audible
Nominal voltage
Type
Location
Current rating
Current rating
10. COMMENTS
Frequency of routine tests and inspections, if other than in accordance with the referenced NFPA standard(s)
System deviations from the referenced NFPA standard(s)
(title)
(date)
(title)
(date)
(title)
(date)
Upon completion of the system(s) satisfactory test(s) witnessed (if required by the authority having jurisdiction)
(signed) representative of the authority having jurisdiction
(title)
(date)
(p. 4 of 4)
Name
Name
Address
Address
Representative
Owner contact
License No.
Telephone
Telephone
MONITORING ENTITY
APPROVING AGENCY
Contact
Contact
Telephone
Telephone
SERVICE
Weekly
Monthly
Quarterly
Semiannually
Annually
Other (specify)
Model No.
Circuit styles
Number of circuits
Software revised
Last date system had any service performed
Last date that any software or configuration was revised
Circuit Style
Manual fire alarm boxes
Ion detectors
Photo detectors
Duct detectors
Heat detectors
Waterflow switches
Supervisory switches
Other (specify)
enabled
(p. 1 of 4)
Circuit Style
Bells
Horns
Chimes
Strobes
Speakers
Other (specify)
Circuit Style
Building temperature
Site water temperature
Site water level
Fire pump power
Fire pump running
Fire pump auto position
Fire pump or pump controller trouble
Fire pump running
Generator in auto position
Generator or controller trouble
Switch transfer
Generator engine running
Other
Amps
Amps
(p. 2 of 4)
No
Who
Time
Visual
Functional
Comments
Visual
Functional
Comments
SECONDARY POWER
Type
Battery condition
Load voltage
Discharge test
Charger test
Specific gravity
Transient Suppressors
Remote Annunciators
Notification Applicances
Audible
Visible
Speakers
Voice clarity
Device
Type
Visual
Check
Functional
Test
Factory
Setting
Measured
Setting
Pass
Fail
Comments
(p. 3 of 4)
INTERFACE EQUIPMENT
(Specify)
(Specify)
(Specify)
Visual
Functional
Comments
Visual
Device
Operation
Simulated
Operation
Comments
Yes
No
Time
Comments
Yes
No
Who
Time
Time
Date
Time
Signature
Name of owner or representative
Date
Time
Signature
(p. 4 of 4)
Name of owner
Name of occupant
Device legend
Date
Floor plan drawings are drawn to an indicated scale and include the following information:
Point of compass
Graphic scale
Room descriptions
Riser locations
Number of risers
Type and number of fire alarm system components/devices on each circuit, on each floor or level
Control panel wiring diagrams are provided for all control equipment, power supplies, battery chargers,
and annunciators and include the following information:
Locations
All indicators and manual controls, including full text of all labels
All field connections to supervising station signaling equipment, releasing equipment, and fire safety
control interfaces
Typical wiring diagrams are provided for all initiating devices, notification appliances, remote alarm
light emitting diodes (LEDs), remote test stations, and end-of-line and power supervisory devices.
Reviewed by
Date
Name of owner
Name of occupant
Date
PLANS
Working plans are drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and
show those items from the following list that pertain to the design of the system:
Full-height cross section or schematic diagram, including structural member information (if required for
clarity), ceiling construction, and method of protection for nonmetallic piping
Location of partitions
Location of fire walls
Occupancy class of each area or room
Location and size of concealed spaces, closets, attics, and bathrooms
Any small enclosures in which no sprinklers are to be installed
Make, type, model, and nominal K-factor of sprinklers, including sprinkler identification number
Temperature rating and location of high-temperature sprinklers
Total area protected by each system on each floor
Number of sprinklers on each riser, per floor
Total number of sprinklers on each dry pipe, preaction, combined dry pipepreaction, or deluge system
Approximate capacity in gallons of each dry pipe system
Pipe type and schedule of wall thickness
Nominal pipe size and cutting lengths of pipe (or center-to-center dimensions)
Where typical branch lines prevail, necessary information is shown to complete plan review:
Types and locations of valves, valve indicators, regulators, meters, and valve pits
2005 National Fire Protection Association
(p. 1 of 3)
Location and elevation of static and residual test gauge with relation to riser reference point
Flow location
Static pressure, psi (bar)
Residual pressure, psi (bar)
Flow, gpm (L/min)
Date and time of test
Other sources of water supply, with pressure or elevation
Date
Location
Name of owner
Name of occupant
Building number or other identification
Description of hazard
Name and address of contractor or designer
Name of approving agency
(p. 2 of 3)
DETAILED WORKSHEETS
Detailed worksheets or computer printout sheets contain the following information:
Sheet number
Sprinkler description and discharge constant, K
Hydraulic reference points
Flow, gpm (L/min)
Pipe size
Pipe lengths, center-to-center of fittings
Equivalent pipe lengths for fittings and devices
Friction loss of pipe, psi/ft (bar/m)
Total friction loss between reference points
In-rack sprinkler demand balanced to ceiling demand
Elevation head between reference points, psi (bar)
Required pressure at each reference point, psi (bar)
Velocity pressure and normal pressure if included in calculations
Notes to indicate starting points or reference to other sheets or to clarify data shown
Diagram to accompany gridded system calculations to indicate flow quantities and directions for lines with
sprinklers operating in the remote area
Combined K-factor calculations for sprinklers on drops, armovers, or sprigs where calculations do not begin
at the sprinkler
GRAPH SHEET
Graphic representation of complete hydraulic calculation is plotted on semiexponential graph paper
(Q1.85) and includes the following:
Water supply curve
Sprinkler system demand
Hose demand (where applicable)
In-rack sprinkler demand (where applicable)
Reviewed by
Date
(p. 3 of 3)
Inspector
System
GENERAL
System designation
Building
Location of sprinkler valve
Type of sprinkler system Wet Dry Deluge Preaction
Make and model of sprinkler valve
Is building fully sprinklered? Yes No
Is entire sprinkler system in service? Yes No
Has sprinkler system been modified since last inspection? Yes No
VALVES
How are valves supervised? Seated Locked
Are valves identified with signs? Yes No
Tamper switch
WATER SUPPLY
When was last water supply test made?
Are reservoirs, tanks, or pressure tanks in good condition?
Yes
No
PUMPS
What type of fire pump does system have? Diesel
When was pump last inspected?
Is pump in good condition? Yes No
Electric
Gasoline
Yes
No
WET SYSTEMS
Is building adequately heated? Yes No
Is system hydraulically calculated? Yes No
If yes, is hydraulic information sign provided at valve?
Yes
DRY SYSTEMS
Is dry pipe valve in heated room? Yes No
Does heated room have low-temperature alarm? Yes
Notes
No
No
None
Yes
Yes
Yes
Yes
No
No
No
No
Airport terminal
Aircraft engine test facility
Power plant
Water-cooling tower
Yes
Yes
Yes
Yes
No
No
No
No
If the answer to any of the above is yes, the appropriate NFPA standard should be referenced for sprinkler density/area criteria.
Indicate whether any of the following special materials are intended to be present:
Flammable or combustible liquids
Yes
No
Compressed or liquefied gas cylinders
Aerosol products
Yes
No
Liquid or solid oxidizers
Nitrate film
Yes
No
Organic peroxide formulations
Pyroxylin plastic
Yes
No
Idle pallets
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
If the answer to any of the above is yes, describe type, location, arrangement, and intended maximum quantities.
Indicate whether the protection is intended for one of the following specialized occupancies or areas:
Spray area or mixing room
Solvent extraction
Laboratory using chemicals
Oxygenfuel gas system for welding
or cutting
Acetylene cylinder charging
Production or use of compressed or
liquefied gases
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
If the answer to any of the above is yes, describe type, location, arrangement, and intended maximum quantities.
No
If the answer is yes, describe product, intended storage arrangement, and height.
Will there be any storage of plastic, rubber, or similar products over 5 ft (1.5 m) high except as described above? Yes
If the answer is yes, describe product, intended storage arrangement, and height.
I certify that I have knowledge of the intended use of the property and that the above information is correct.
Signature of owners representative or agent
Name of owners representative or agent completing certificate (print)
Relationship and firm of agent (print)
2002 National Fire Protection Association
Date
No
Property name
Property address
Accepted by approving authorities (names)
Address
Plans
Instructions
Location of
System
Yes
No
Yes
No
Yes
No
Yes
Yes
Yes
No
No
No
Model
Make
Orifice
Size
Temperature
rating
Quantity
Sprinklers
Pipe and
Fittings
Type of pipe
Type of fittings
Alarm
Valve or
Flow
Indicator
Alarm Device
Type
Make
Model
Minutes
Q. O. D.
Dry Valve
Make
Dry Pipe
Operating
Test
Model
Seconds
Make
Serial no.
Time to Trip
Through Test
Connection1,2
Water
Pressure
Air
Pressure
Trip Point
Air Pressure
Minutes Seconds
psi
psi
psi
Model
Time Water
Reached
Test Outlet1,2
Minutes
Seconds
Serial no.
Alarm
Operated Properly
Yes
No
Without
Q.O.D.
With
Q.O.D.
If no, explain
(p. 1 of 3)
Operation
Pneumatic
Piping supervised
Deluge and
Preaction
Valves
Electric
Yes
Yes
Manual
Model
Make and
model
Location
and floor
Setting
No
Remote
Both
If no, explain.
Yes
Test
Description
No
Make
Pressure
Reducing
Valve Test
Hydraulics
No
Yes
Minutes
No
Seconds
Residual pressure
(flowing)
Static pressure
Inlet (psi)
Maximum time to
operate release
Outlet (psi)
Inlet (psi)
Flow rate
Outlet (psi)
Flow (gpm)
Hydrostatic: Hydrostatic tests shall be made at not less than 200 psi (13.6 bar) for 2 hours or 50 psi (3.4 bar)
above static pressure in excess of 150 psi (10.2 bar) for 2 hours. Differential dry-pipe valve clappers shall be left
open during the test to prevent damage. All aboveground piping leakage shall be stopped.
Pneumatic: Establish 40 psi (2.7 bar) air pressure and measure drop, which shall not exceed 1Z\x psi (0.1 bar)
in 24 hours. Test pressure tanks at normal water level and air pressure and measure air pressure drop, which shall
not exceed 1Z\x psi (0.1 bar) in 24 hours.
All piping hydrostatically tested at
Dry piping pneumatically tested
Equipment operates properly
psi (
hours
bar) for
Yes
Yes
No
No
Do you certify as the sprinkler contractor that additives and corrosive chemicals, sodium silicate or derivatives
of sodium silicate, brine, or other corrosive chemicals were not used for testing systems or stopping leaks?
Yes
Tests
Drain
test
No
bar)
Underground mains and lead-in connections to system risers flushed before connection made to
sprinkler piping
Verified by copy of the Contractors Material and Test
Other
Yes
No
Certificate for Underground Piping
Flushed by installer of underground sprinkler piping
Yes
No
If powder-driven fasteners are used in concrete,
has representative sample testing been
satisfactorily completed?
Blank Testing
Gaskets
Number used
Welding piping
Yes
Locations
Yes
No
bar)
Explain
If no, explain
Number removed
No
If yes . . .
Welding
Cutouts
(Discs)
Yes
No
Yes
No
Do you certify that the welding was carried out in compliance with a
documented quality control procedure to ensure that all discs are retrieved,
that openings in piping are smooth, that slag and other welding residue
are removed, and that the internal diameters of piping are not penetrated?
Yes
No
Yes
No
(p. 2 of 3)
Hydraulic Data
Nameplate
Remarks
If no, explain.
Nameplate provided
Yes
No
Title
Date
Title
Date
(p. 3 of 3)
Inspector
System
GENERAL
System designation
Building
Location of control valve
Type of system Class I Class II Class III
Length of hose provided None 50 ft (15 m) 75 ft (23 m) 100 ft (30 m)
Type of hose Rubber lined Unlined
(If unlined hose is presently installed, it may remain in use. However, when it requires replacement, only lined hose
should be used in accordance with NFPA 14, Standard for the Installation of Standpipe and Hose Systems.)
Are shutoff nozzles provided? Yes No
(If no, nozzles should be replaced with shutoff type in accordance with NFPA 14.)
Are pressure-regulating devices provided?
Yes
No
VALVES
How are valves supervised? Sealed Locked
Are valves identified with signs? Yes No
Tamper switch
WATER SUPPLY
When was last water supply test made?
Are reservoirs, tanks, or pressure tanks in good condition?
Yes
No
PUMPS
What type of fire pump does system have? Diesel
Is pump in good condition? Yes No
When was pump last tested?
Yes
Notes
No
Electric
Gasoline
None
Date
Property address
Accepted by approving authorities (names)
Address
Plans
Type of
System
Water Supply
Data Used for
Design and As
Shown on Plans
Water Supply
Source Capacity,
Gallons
If Public
Waterworks
System:
Have Copies
of the Following
Been Left on
the Premises?
Supplies
Building(s)
Valve
Supervision
Pipe and
Fittings
Backflow
Preventor
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Automatic-dry
Automatic-wet
Semitautomatic-dry
Manual-dry
Manual-wet
Combination standpipe/sprinkler
Other (if yes, explain)
Model
Electric
Diesel
Rated, gpm
Public waterworks system
Other (explain)
Rated, psi
Storage tank
Shutoff, psi
Gravity tank
Open reservoir
Other (explain)
Static, psi
Residual, psi
NFPA 25
Hydraulic data/calculations
Yes
Tamperproof switch
No
Other
If other, explain.
Type of pipe
Type of fittings
Double check assembly
Reduced-pressure device
Size
(p. 1 of 3)
Size
Make
Min
Min
No
Yes
Electric activation
Yes
Pneumatic activation
Yes
Sec
Water pressure
Sec
Air pressure
psi
If no, explain.
Min
Model
Sec
Yes
No
If no, explain.
Yes
No
If no, explain.
PRESSURE-REGULATING DEVICE
Nonflowing (psi)
Location & Floor
Model
Inlet
Yes
Outlet
No
Flowing (psi)
Inlet
Outlet
gpm
If no, explain.
(p. 2 of 3)
Test
Description
Hydrostatic: Hydrostatic tests shall be made at not less than 200 psi (13.6 bar) for 2 hours or 50 psi (3.4 bar) above static
pressure in excess of 150 psi (10.2 bar) for 2 hours. Differential dry pipe valve clappers shall be left open during test to
prevent damage. All aboveground piping leakage shall be stopped.
Pneumatic: Establish 40 psi (2.7 bar) air pressure and measure drop, which shall not exceed 1Z\x psi (0.1 bar) in 24 hours.
Test pressure tanks at normal water level and air pressure and measure air pressure drop, which shall not exceed
1Z\x psi (0.1 bar) in 24 hours.
All piping hydrostatically tested at
Dry piping pneumatically tested?
Equipment operates properly?
Tests
psi (
Yes
Yes
hr
bar) for
No
No
Do you certify as the standpipe contractor that additives and corrosive chemicals,
sodium silicate, or derivatives of sodium silicate, brine, or other corrosive chemicals
were not used for testing systems or stopping leaks?
Yes
Drain
test
psi (
bar)
No
psi (
bar)
Underground mains and lead-in connections to system risers flushed before connection made to standpipe piping.
Blank Testing
Yes
No
Yes
No
Number used
Welded piping
Other
Explain:
Locations
Yes
Number removed
No
If yes . . .
Welding
Cutouts
(Discs)
Hydraulic
Data
Nameplate
Do you certify as the standpipe contractor that welding procedures comply with the requirements
of at least AWS D10.9, Level AR-3?
Yes
No
Do you certify that the welding was performed by welders qualified in compliance with the
requirements of at least AWS D10.9, Level AR-3?
Yes
No
Do you certify that welding was carried out in compliance with a documented quality control
procedure to ensure that all discs are retrieved, that openings in piping are smooth, that slag and
other welding residue are removed, and that the internal diameters of piping are not penetrated?
Yes
No
Do you certify that you have a control feature to ensure that all cutouts (discs) are retrieved?
Yes
No
Nameplate provided?
Yes
No
If no, explain.
Name of contractor
Address
State license number (if applicable)
Property owner
Title
Date
Sprinkler/standpipe contractor
Title
Date
Approving authorities
Title
Date
Additional
Explanation
and Notes
(p. 3 of 3)
Inspector
System
GENERAL
System designation
Building
Location of control valve
Has system been modified since last inspection?
Yes
No
VALVES
How are valves supervised?
Sealed
Locked
Yes
Tamper switch
No
WATER SUPPLY
When was last water supply test made?
Are reservoirs, tanks, or pressure tanks in good condition?
Yes
No
PUMPS
What type of fire pump does system have?
Diesel
Yes
No
Yes
No
OPERATING INSTRUCTIONS
Are operating instructions posted?
Yes
Notes
No
Electric
Gasoline
None
Inspector
System
GENERAL
System designation
Building
Location of main control valve
Has system been modified since last inspection?
Yes
No
VALVES
How are valves supervised?
Sealed
Locked
Yes
Tamper switch
No
WATER SUPPLY
Is water supply filtered?
Yes
No
Yes
PUMPS
When was pump last inspected?
Is pump in good condition?
Yes
No
OPERATING INSTRUCTIONS
Are operating instructions posted?
Yes
Notes
No
No
Inspector
System
GENERAL
System designation
Building
Location of control valve
Make and model of valve
Has system been modified since last inspection?
Yes
No
VALVES
How are valves supervised?
Sealed
Locked
Yes
Tamper switch
No
WATER SUPPLY
When was last water supply test made?
Are reservoirs, tanks, or pressure tanks in good condition?
Yes
No
PUMPS
What type of fire pump does system have?
Diesel
Yes
No
Yes
No
OPERATING INSTRUCTIONS
Are operating instructions posted?
Yes
Notes
No
Electric
Gasoline
None
Inspector
System
GENERAL
System designation
Building
Location of control valve
Make and model of valve
Has system been modified since last inspection?
Yes
No
Sealed
Locked
Yes
Tamper switch
No
WATER SUPPLY
When was last water supply test made?
Are reservoirs, tanks, or pressure tanks in good condition?
Yes
No
PUMPS
What type of fire pump does system have?
Diesel
Yes
No
Yes
No
OPERATING INSTRUCTIONS
Are operating instructions posted?
Yes
Notes
No
Electric
Gasoline
None
Inspector
System
150
N1.85
140
130
120
110
100
Pressure (psi)
90
80
70
60
50
40
30
20
10
12 3 4 5
10
Notes
11
12
13
14
Flow (gpm)
15
16
17
18
19
20
Date
Test made by
Time
Representative of
Witness
Purpose of test
A1
A2
A3
A4
Size nozzle
Pitot reading
Discharge coefficient
Total gpm
gpm
Static B
psi
Residual B
gpm or @
psi
psi residual
gpm
Remarks
Location map: Show line sizes and distance to next cross-connected line. Show valves and hydrant branch size. Indicate
north. Show flowing hydrants and label as A1, A2, A3, A4. Show location of static and residual and label as B.
Indicate B: Hydrant
Sprinkler
Other (identify)
Inspector
System
120
(827)
110
(758)
100
(689)
90
(621)
80
(552)
70
(483)
60
(414)
50
(345)
40
(276)
30
(207)
20
(138)
10
(69)
0
400
100 200 300
(378.5) (757) (1136) (1514)
500
(1893)
Q1.85
Notes
600
(2271)
700
(2650)
800
(3028)
900
(3407)
1000
(3785)
Inspector
System
CO2 system manufacturer
Detector manufacturer
Control panel manufacturer
Date system installed
Room or area designation
Volume protected
Above ceiling
System concentration
50%
65%
75%
Other
lb (kg)
lb (kg)
lb (kg)
psi (bar)
Detection system
Single zone
Two zones (cross-zoned)
Two detectors on any zone
Other
Notes
for
minutes
Inspector
System
System designation
System manufacturer
Date system installed
Service contractor
Type of extinguishing agent
Potassium bicarbonate
Ammonium phosphate
Sodium bicarbonate
Other
Dry chemical cylinder
Normal pressure
psi (bar)
psi (bar)
Normal weight
lb (kg)
lb (kg)
Equipment protected
Deep-fat fryer(s)
Upright broiler(s)
Grill(s)
Griddle(s)
Charbroiler(s)
Range top(s)
Other
Expellant gas cartridge provided?
Yes
No
lb (kg)
Yes
psi (bar)
No
Gas
Electric
Notes
Yes
No
Inspector
System
Y = Satisfactory
N = Unsatisfactory (explain)
Note: Pressures and weights are satisfactory if equal to or greater than minimums in Form 9B
Acceptance?
Dry chemical cylinder pressure
psi (bar)
Notes
If N, Explanation
Inspector
System
Date of acceptance test
Manual release
Fusible link
Satisfactory
Satisfactory
Satisfactory
Unsatisfactory
Unsatisfactory
Yes
No
Unsatisfactory
Satisfactory
Yes
No
Unsatisfactory
Yes
No
Satisfactory
Unsatisfactory
Continues to run
Stops
Satisfactory
Unsatisfactory
Yes
No
Yes
No
Yes
No
Check valves
Yes
No
Yes
No
Directional valves
Yes
No
Valve assemblies
Yes
No
Manifolds
Yes
No
Notes
Inspector
System
System designation
System manufacturer
Date system installed
Service contractor
Type of extinguishing agent
Potassium carbonate
Potassium acetate
psi (bar)
psi (bar)
Normal weight
lb (kg)
lb (kg)
Equipment protected
Deep-fat fryer(s)
Upright broiler(s)
Grill(s)
Griddle(s)
Charbroiler(s)
Range top(s)
Other
Expellant gas cartridge provided?
Yes
No
lb (kg)
Yes
psi (bar)
No
Gas
Electric
Notes
Yes
No
Inspector
System
Y = Satisfactory
N = Unsatisfactory (explain)
Note: Pressures and weights are satisfactory if equal to or greater than minimums in Form 9E
Acceptance?
Wet chemical cylinder pressure, psi (bar)
(if stored-pressure type)
Expellant gas cartridge (if expellant gas type):
Pressure of nitrogen, psi (bar)
Weight of carbon dioxide, lb (kg)
Components are undamaged:
Detectors or fusible links
Expellant gas cylinder(s)
Wet chemical containers
Releasing devices
Piping
Nozzles
Alarms
Auxiliary equipment
Damaged components replaced or hydrostatically tested
System piping tested for obstructions
System piping not obstructed
Fusible link installed
Notes
If N, Explanation
Inspector
System
Date of acceptance test
Manual release
Fusible link
Satisfactory
Satisfactory
Satisfactory
Unsatisfactory
Unsatisfactory
Yes
No
Unsatisfactory
Satisfactory
Yes
No
Unsatisfactory
Satisfactory
Unsatisfactory
Continues to run
Stops
Satisfactory
Unsatisfactory
Yes
No
Inspector
System
Clean agent system manufacturer
Detector manufacturer
Control panel manufacturer
Date system installed
Room or area designation
Type of extinguishing agent
Volume protected
Above ceiling
System concentration
50%
65%
75%
Other
lb (kg)
lb (kg)
lb (kg)
psi (bar)
Detection system
Single zone
Two zones (cross-zoned)
Two detectors on any zone
Other
Notes
Inspector
System
Y = Satisfactory
N = Unsatisfactory (explain)
Acceptance?
Clean agent containers free from physical damage
Container pressure
psi (bar)
(Pressure loss greater than 5% requires container refill
or replacement.)
Container weight
lb (kg)
(Weight loss greater than 5% requires container refill
or replacement.)
Container pressure and weight recorded on tag attached
to container
Control heads operational (Remove heads from containers.)
Conduct acceptance test of system.
Notes
If N, Explanation
Location
HP
RPM
CFM
Location
Type
Location
Location
Location
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
FST*
FST
FST
FST
FST
FST
N/A
N/A
N/A
N/A
N/A
N/A
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
FST
FST
FST
FST
FST
FST
N/A
N/A
N/A
N/A
N/A
N/A
Yes
Yes
No
No
FST
FST
N/A
N/A
Yes
Yes
No
No
FST
FST
N/A
N/A
Yes
No
FST
N/A
Comments
(p. 1 of 2)
Stair
Door
Door Latch
Release
Force
Door Set
in Motion
Force
Door Swing
to Full Open
Force
Pressure
Difference
with All
Doors Closed
Pressure
Difference
with One
Door Open
Pressure
Difference
with Two
Doors Open
Pressure
Difference
with Three
Doors Open
Comments
(p. 2 of 2)
Inspector
System
Y = Satisfactory
Equipment
Fans (list each)
Other Equipment
N = Unsatisfactory (explain)
Equipment
Operates
Properly?
Inspector
System
Y = Satisfactory
N = Unsatisfactory (explain)
Record
Information
Ensure that system is in normal mode.
Measure and record:
Wind speed
Wind direction
Outside temperature
Test system normal power.
Test system emergency power.
Confirm that for each input there is a designated output.
Demonstrate complete smoke-control system sequence:
Normal mode
Automatic smoke control from first alarm
Manual override of normal and automatic modes
Return to normal
Confirm that fire alarm inputs produce correct outputs.
Establish consistent method for recording pressure
differences.
Confirm that introduction of untempered air will not
damage equipment.
Confirm that weather conditions (freezing temperatures)
will not damage equipment.
Notes
Notes
Inspector
System
Record
Information
Notes
Pressure
Difference
Notes
Verify proper operation of each zoned smoke-control system in response to each required means of actuation. List each.
Record
Information
Notes
Inspector
System
Y = Satisfactory
N = Unsatisfactory (explain)
Acceptance?
Inspector
System
Y = Satisfactory
N = Unsatisfactory (explain)
Acceptance?
Notes
If N, Explanation
Inspector
System
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
Check door for physical damage and to see that vision panel (if provided) is secure.
Check that closer works.
Check that latch works.
Check that hinges are secure.
Check that coordinator (if provided) works.
Check tin-clad or Kalamein doors for dry rot.
Check cables and/or chains on sliding doors to ensure that they are in good condition and operate properly.
Check cables, chains, rollers, fusible links, and other moving parts for paint or other contaminants that may alter
operation. Replace fusible links that have been painted.
Lubricate hinges on swinging doors and rollers on sliding doors.
Check that labeled fire doors have not been modified improperly.
Clear surrounding area of obstructions that may interfere with door operation.
Check that sliding doors close freely and completely.
Y = Satisfactory
Notes
10
11
12