Fan theory
22-23
Page 3
Description
The fan has two impellers on a single shaft and inspection
covers in the backplate and end faces. The end faces,
with their bearing supports, are bolted onto the sides of
the fan casing. To provide good sealing, there is a rubber
gasket between the contact surfaces of the casing and
end faces.
There are special seals where the shaft passes through
the end faces and the partition plate.
The impeller is of a welded construction and, in sizes
010 - 016, has straight, radial blades. In sizes 020 - 040,
the blades are backward-curved. Both impeller types
have inlet shrouds.
Spherical roller bearings are used. The plummer block is
steel and designed to facilitate continuous lubrication.
The inlet and outlet connectors are circular.
Materials and surface treatments: Steel coated with a primer.
Alternatively, stainless steel SS 23 33 or acid-proof steel
SS 23 43 with the shaft in SS 23 24.
Lubricator
This screws simply into the top of the plummer block.
Lubrication interval and dose are both adjustable. The
lubricator is recommended for high speed fans (these
normally have short lubrication intervals) and, in particular, for fans in continuous operation.
Belt drive, belt guard
Belt drive HDCZ-01 can generally be selected for all fan
sizes (see pages 15 - 16). In other cases, the min. diameter
of the pulley on the fan shaft must be taken into consideration (see page 7). Belt guards are ventilated and have
openable covers to facilitate easy inspection of belt condition.
Motor
Refer to pages 19 - 21.
Sizes
010, 012, 016, 020, 025, 031 and 040.
Base frame
The base frame is a primed steel construction and is suitable for all discharge directions. Other surface coatings
and stainless steels are also available. Please contact us
with all your enquiries.
The base frame is delivered with a separately ordered fan
and motor (see the specifications on page 4).
Flexible connecting ducts
Suitable for both inlet and outlet, these are made of a
neoprene-coated, woven polyester with a spiral steel
insert.
Flexible connecting ducts are fitted using ring clamps; two
of these are supplied with each duct.
Protective screen
Suitable for the inlets and outlets of, respectively, free
inlet and free outlet fans. Screens have a galvanized steel
frame; the grille itself is also galvanized and is of a crenellated design.
Instructions
All necessary instructions are supplied at delivery.
Packaging
Fans are delivered on wooden battens; inlets and outlets
are covered.
Page 4
Centrifugal fan
Sizes 010, 012, 016, 020, 025, 031, 040
HDCB-aaa-bb-c-d
HDCZ-01-bbb-c-dd
HDCZ-11-b-cc-1
Design
1
2
3
4
HDCZ-13-bbb
HDCZ-14-bbb
HDCZ-15
0
Table 1
Fan
size
010
012
0
30
270
300
330
11
14
16
19
23
016
020
025
0
22.5
270
292.5
315
337.5
11
13
16
18
21
24
031
040
Angle Code
V
bb
0
18
36
270
288
306
324
342
11
12
15
16
17
20
22
25
Discharge direction
270
90
Page 5
The charts are for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
Gas flow, m3/h
1000
2000
20 000
012
ma
x=
59
0
0
00
4
5
35
00
300
0
250
0
m
rp
55
00
20 000
40
00
3000
2000
1
m
rp
50
45
0
1000
55
10 000
00
60
00
010
m
ax
30 000
25 000
50
00
45
00
40
00
350
0
10 000
300
0
250
0
10
0,2
0,3
2500
3000
3500
0,4
0,5
450
0
10
500
0
550
0
ma
x
=6
00
400
0
0r
pm
40
50
00
ma
x=
59
00
4000
5000
6000
016
m
ax
55
00
rp
m
300
0
250
0
200
0
3000
4000
10 000
5000
020
ma
x=
44
0
40
7000
6000
00
m
rp
35
00
2000
m
rp
20 000
40
00
1000
0
00
=5
45
00
20 000
30 000
The
be oper
sha chose ating
ded n to poin
are the t mu
a.
left st n
of t ot
he
3000
450
0
20
2000
10 000
30
30 000
1000
3500
10
0,5
2500
3000
4000
20
10
00
0,6
NO
TE:
0,1
Power demand, kW
Power demand, kW
00
35
00
3
30
00
250
0
200
0
10
Power demand, kW
10
0.5
2000
2500
20
35 0
30
40
00
40
10
2000
m
ax
45
00
50
00
rp
m
2500
10
3 0 00
20
3 500
30
4 0 00
40
n
50
60
00
1.5
Power demand, kW
00
ma
50
60
x =4
4 00 r p
Page 6
The charts are for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
Gas flow, m3/h
ma
x
150
0
00
10 000
10
1 5 00
3 0 00
50
3
3500
n
ma
040
x=
26
00
24
00
22
00
20
00
18
00
16
00
140
0
4
1200
1400
10
25
2 4 00
2 600
80
2 8 00
3000
30 000
010-016
20 000
10 000
35
30
25
20
15
10
t = 5C
10
60
2 200
12 0
0
00
30 000
10
2
020-040
160 0
1 8 00
2 0 00
100
2 2 00
2400
n
ma
200
J(= 1/4 GD2) = 0,21 kgm2
x =26
00 rpm
t = approximate
gas temperature ride due
to compression
and fan losses
Power demand, kW
The
be oper
sha chose ating
ded n to poin
are the t mu
a.
left st n
of t ot
he
10 000
ma
160 0
1800
20 0 0
Temperature
increase
charts
m
rp
20 000
30 000
40
40
120
20 000
24
00
100
kgm2
NO
TE:
30 000
= 0,21
800 r p
90 J(= 1/4
GD2)
x =3
220
0
200
0
20
Power demand, kW
Power demand, kW
2 0 00
28
00
26
00
180
0
160
0
00
3 2
Gas flow, m3/s
2 5 00
NO
TE:
200
0
250
0
30
00
20 000
031
ma
x=
rp
30
00
20 000
00
31
The
be oper
sha chose ating
ded n to poin
are the t mu
a.
left st n
of t ot
he
025
10000
m
rp
10 000
35
00
30 000
The
be oper
sha chose ating
ded n to poin
are the t mu
a.
left st n
of t ot
he
00
38
20 000
10 000
NO
TE:
30 000
20 000
10 000
30
25
20
15
10
t = 5C
0
0
Page 7
A1
A2
F
A
G
d dia.
C
H
J
m1
K
L
Y dia.
n n
M
N holes P dia.
R
CL inlet
Centre hole on size 020 only
Dimensions
Size
A1
A2
686
773
916
010
012
016
777 658
919 766
1090 895
020
025
031
040
1308
1580
1940
2365
1056
1259
1548
1870
Size
m1
Wgt., kg
010
012
016
35 38
10 118 80
40 43
12 121 80
50 53,5 14 143 100
100
140
200
020
025
031
040
50
60
70
75
53,5
64
74,5
79,5
14
18
20
20
142
142
138
178
100
120 95
120 130
120 150
345 586
415 686
510 838
615 1005
367
428
512
618
M N P
6 360 151 46 4 18
6 410 174 51 4 18
6 405 167 56 4 18
525 6 455
630 6 530
760 10 725
920 10 850
188
221
315
381
66
66
88
88
6
8
8
8
305
375
465
18 595
18 737
26 916
26 1143
123
145
175
207
315
395
494
624
Y*
Y dia.
* External dimensions
280
420
800
1150
where Dmin
P1
n
k1
=
=
=
=
Size
k1
Max. witdth of belt pulley
1)
010
012
016
020
025
031
040
36
100
18
100
12
160
11
7,5
5,5
4
160 160 160
160
1) Consult Flkt Woods AB if the calculation shows that a wider belt pulley is
required or if an asymmetrical pulley is used.
Base frame
Code suffix cc
Motor size as per IEC
132 160 180 200 225 250
280S
280M
315S
315M
355S
010
012
016
01
02
03
03
05
04
06
06
07
020
025
031
040
08
10
08
10
09
09
09
11
11
11
12 13 14 15
20 21
2)
2)
16 17 18
22 23 24
19
25 26
27
Page 8
F
D
GxH
GxH
5th mounting on
the drive side
M
N
C
CL of inlet
S dia.
K holes L dia.
Code
suffix cc
01, 02
03, 04
05, 06, 07
1172
1430
1515
520
585
685
08
09
10
1630
1630
1735
30
31
31
860
860
952
11
1219
2023
1735
952
1920 1166
2160 1430
24, 25
26, 27
2160 1430
2160 1430
1 722 181
1 1052 204
2 572 200
4
4
6
15
15
15
149
180
220
110
110
110
128
128
128
82
82
82
30
35
35
2 565
2 675
2 562
221
221
266
6
6
6
15
22
22
280
280
342
110
144
144
128 82
172 110
172 110
38
35
45
2 670
2 755
2 775
266
365
431
6
6
6
22
22
22
342
422
519
144
144
182
44
47
2 865
2 865
431
431
6
6
22
22
519
519
182
182
S
11
11
11
Wgt. *
Number of
Max.
mountings motor wgt. **
55
75
95
4
4
5
125
225
380
11
13,5
13,5
117
123
137
5
5
5
300
500
300
172 110
172 110
212 152
13,5
13,5
13,5
142
240
320
5
5
5
550
650
700
212 152
212 152
13,5
13,5
320
365
5
5
900
1100
010
012
016
020
Size
025
031
040
Motor
size as
per IEC
200
225
250
280
280
315
280
315
355
Page 9
Description
The fan has two impellers on a single shaft and inspection covers in the backplate and end faces. These covers
give access to the impeller and all compartments of the
casing. The end faces, with their bearing supports, are
bolted onto the sides of the fan casing. To provide good
sealing, there is a rubber gasket between the contact surfaces of the casing and end faces.
There are special seals where the shaft passes through
the end faces and the partition plate.
The impeller is of a welded construction and has straight
radial blades and an inlet shroud.
The base frame is integrated with the fan in a single unit.
This has slide rails for mounting the motor.
Anti-vibration mountings are included as standard. Motor
and belt drive are ordered separately.
Spherical roller bearings are used. The plummer block is
steel and designed to facilitate continuous lubrication.
The inlet and outlet connectors are circular. As an optional
extra, they can be supplied with flanges. There are 4
drain holes (1 for each compartment) with tubes leading
out through the base frame.
Materials: Fan with base frame in acid-proof SS 23 43
and shaft in SS 23 24.
Sizes
020, 025, 031 and 040.
Instructions
All necessary instructions are supplied at delivery.
Packaging
Fans are delivered on wooden battens; inlets and outlets
are covered.
Page 10
HDCS-aaa-bb-cc-d-3
Discharge direction
11 = 0
21 = 315
IEC motor sizes
14 = 200L
17 = 250M
20 = 315S
15 = 225S
18 = 280S
21 = 315M
16 = 225M
19 = 280M
22 = 315L
23 = 355S
Design
1 = Without connecting flanges at the inlet and outlet
2 = With connecting flanges at the inlet and outlet
Belt drive inc. belt guard
HDCZ-01-bbb-c-dd
HDCZ-12-bbb
HDCZ-13-bbb
HDCZ-15
Counterflange
HDCZ-17-bbb-3
Discharge
direction 11
Discharge
direction 21
Page 11
The charts are for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
Air flow, m3/h
15000
3000
4000
5000
6000
7000
41
00
HDCS
ma
x=
44
20
8000
30000
25000
380
0
35
20000
00
320
0
290
0
10000
5000
10000
HDCS
020
rp
m
5000
15000
NOT
mos E! The
left s t not be operatin
g
ide o chos
en point
f the
shad to the
ed a
rea
20000
2000
25000
1000
NOT
most E! The o
left s not be c perating
ide o
h
p
f the osen to t oint
shad
h
ed ar e
ea
0
30000
ma
x=
38
60
025
rp
35
00
320
0
29
00
260
0
230
0
10000
5000
10
10
Air flow, m /s
3
2300
3200
50
Power demand, kW
3500
3800
4100
100
J 1(= 1/4
GD2)
= 2.2
kgm2
2900
100
Total tryckkning, Pa
20000
15000
10000
1
NOT
most E! The o
left s not be c perating
ide o
h
f the osen to point
th
shad
ed a e
rea
25000
24
15000
HDCS
ma
x=
32
00
30
00
0
30000
rp
031
25000
m
2
20000
270
0
15000
3
00
210
0
10000
180
0
10
10000
2100
2400
J(= 1/4 GD2) = 10.7 kgm2 n
max 3200 rpm
3000
2700
ma
x=
26
50
r
HDCS
040
pm
24
00
220
0
200
0
3
5000
10
Air flow, m /s
1800
20000
1
50
Power demand, kW
Power demand, kW
3200
100
150
3500
160
0
10000
1600
100
50
180
0
5000
5000
Total tryckkning, Pa
0
30000
2600
50
NO
mo TE! Th
left st not b e oper
side e ch atin
of th ose g poi
nt
e sh n to
ade the
d ar
ea
Power demand, kW
2900
1800
150
2000
200
250
2200
J(= 1/4 GD2) = 21 kgm2
2400
t = approximate
gas temperature rise due
to compression
and fan losses
30 000
Page 12
020-040
20 000
10 000
35
30
25
20
15
10
t = 5C
Throttling curve
Notes
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................................
Page 13
A2
V
Y dia.
H1
L
X1
X2
X3
X4
Z1
m1
j
Z2
Z5
d dia.
Z3
Z4
Size
A2
H1
X1
X2
X3
X4
020
200 - 280
1056
783
345
586
367
535
37
315
222
361
1409
98
240
025
200 - 280
1254
950
415
686
428
638
37
395
255
407
1543
115
258
031
280 - 315
1477
1180
510
838
512
775
36
494
290
494
1577
124
263
040
280 - 355
1742
1445
615
1005
618
875
47
624
328
585
1730
127
266
Size
Y*
Z1
Z2
Z3
Z4
Z5
m1
wgt.**
020
250
600
126
599
710
710
50
53,5
14
142
100
630
600
025
315
772
155
747
925
925
60
64
18
142
120
750
600
031
400
768
164
905
730
780
70
74,5
20
138
120
1025
900
040
500
1110
215
1150
75
79,5
20
178
120
1460
1400
*External dimensions
Z4
280M
1555
595
315S
1170
980
315M
1170
980
355S
710
1440
Size
020
025
Size
031
040
Motor
size as
per IEC
280
315
280
315
355
Page 14
Discharge direction 21
E2
A2
U
F2
V
m
G2
B2
Y dia.
B3
H1
L
X1
X4
X2
X3
Z6
m1
Z3
j
k
d dia.
Z2
Z5
Z4
Size
A2
B2
B3
E2
F2
G2
H1
X1
X2
X3
X4
020
200 - 280
1056
310
410
798
410
375
535
315
222
361
1409
98
240
025
200 - 280
1254
378
485
965
485
414
638
395
255
407
1543
115
258
031
280 - 315
1477
474
593
1195
593
526
775
494
290
494
1577
124
263
040
280 - 355
1742
587
711
1457
711
630
875
624
328
585
1730
127
266
Size
Y*
Z2
Z3
Z4
Z5
Z6
m1
Wgt.**
020
250
126
599
710
710
665
50
53,5
14
142
100
630
600
025
315
155
747
925
925
843
60
64
18
142
120
750
600
031
400
164
905
730
780
851
70
74,5
20
138
120
1025
900
040
500
215
1150
1206
75
79,5
20
178
120
1460
1400
*External dimensions
Z4
280M
1555
595
315S
1170
980
315M
1170
980
355S
710
1440
Size
020
025
Size
031
040
Motor
size as
per IEC
280
315
280
315
355
Page 15
HDCZ-01-bbb-c-dd
Belt drive sizes 090 - 459, see the tables below
Design
1 = fitted to the ordered fan.
9 = supplied ready for assembly.
Fan sizes 01 - 07, see the table below.
Check -dd against the belt drive, see the belt drive tables.
Fan size
1. Motor pulley.
2. Fan pulley.
3. Motor bushing.
4. Fan bushing.
5. V-belt.
6. Belt guard.
dd
HDCB/HDCS
01
02
03
04
05
06
07
010
012
016
020
025
031
040
Fan
speed
Code
suffix
Motor
Suitable for:
Fan
speed
Code
suffix
Motor
Suitable for:
Fan
speed
Code
suffix
Motor
Suitable for:
r/m
bbb
dd =
r/m
bbb
dd =
r/m
bbb
dd =
5710
090
01
6190
110
01
6170
140
01
5370
091
01
5860
111
01
5840
141
01
5040
092
01
5510
142
01, 02
4760
4440
01
5560
112
093
APAL-200750-c-0
01
5230
113
094
2 poles
01
4970
114
4210
095
4720
096
Size 132S
as per IEC
01
3970
01
4450
3770
097
01
3570
098
01
01
5230
143
01, 02
4950
144
APAL-201500-c-0
01, 02
115
APAL-201100-c-0
01, 02
01, 02
4690
145
2 poles
01, 02
116
2 poles
01, 02
4450
146
117
01, 02
4210
147
4000
118
Size 160M
as per IEC
Size 160M
as per IEC
02
4220
01, 02
3970
148
02
3770
119
02
3740
149
02
3550
120
02
3540
150
02
3350
121
02
3130
122
02
02
Fan
speed
Code
suffix
r/m
bbb
dd =
5910
230
02
5580
231
02
5300
232
02
5010
233
02
02, 03
Motor
Suitable for:
Suitable for:
Fan
speed
Code
suffix
dd =
r/m
bbb
dd =
4720
234
170
01
5860
200
02
4410
235
171
01, 02
5560
201
02
4140
236
5540
172
01, 02
5230
202
02
3890
237
5230
173
4970
203
3680
238
2 poles
03, 04
02
4720
204
APAL-202200-c-0
02
174
APAL-201850-c-0
01, 02
4960
02, 03
3480
239
03, 04
4670
175
2 poles
02
4450
205
2 poles
02, 03
3310
240
Size 200L
as per IEC
4420
176
4220
206
3110
241
04, 05
177
02, 03
3980
207
Size 180M
as per IEC
03
4170
Size 160L
as per IEC
02
03
2955
242
04, 05
3890
178
03
3770
208
03
2810
243
05
3650
179
03
3560
209
03
2640
244
05
3470
180
03
3350
210
03
2510
245
05
3260
181
03
3130
211
03
2370
246
05
Fan
speed
Code
suffix
r/m
bbb
6170
5840
Motor
Motor
Suitable for:
02, 03, 04
APAL-203000-c-0
03, 04
03, 04
03, 04, 05
Code
suffix
Motor
Suitable for:
Fan
speed
Code
suffix
Motor
Page 16
Suitable for:
FlktFan
speed
Code
suffix
Motor
Suitable for:
r/m
bbb
dd =
r/m
bbb
dd =
r/m
bbb
5900
270
02
5020
300
03
4750
330
dd =
03
5600
271
02
4740
301
03
4440
331
03, 04
5290
272
02
4480
302
03, 04
5010
273
03
4140
303
4720
274
03
3900
4410
275
03, 04
3690
4210
276
03, 04
3930
277
APAL-2
03700-c-0
3670
278
2 poles
3500
279
3300
280
Size 200L
as per IEC
3120
4160
332
04
3940
333
304
APAL-204500-c-0
04
3700
334
APAL-205500-c-0
305
2 poles
04, 05
3490
335
2 poles
04, 05
3490
306
04, 05
3320
336
3290
307
04, 05
3130
337
Size 250M
as per IEC
04, 05
03, 04
Size 225M
as per IEC
04
3120
308
04, 05
2970
338
05
04, 05
2960
309
05
2820
339
05
04, 05
2810
310
05
2660
340
05
281
04, 05
2660
311
05
2520
341
05
2950
282
04, 05
2510
312
05
2800
283
05
2640
284
05
2500
285
05
2360
286
05
04
04, 05
04, 05
05
Fan
speed
Code
suffix
r/m
Suitable for:
Fan
speed
Code
suffix
bbb
dd =
r/m
bbb
dd =
Fan
speed
Code
suffix
4450
360
04
4130
390
04
r/m
bbb
dd =
4140
361
04
3920
391
04, 05
3160
420
06
3910
362
04, 05
3700
392
04, 05
2980
421
06
3710
363
04, 05
3510
393
05
2800
422
3520
364
04, 05
3330
394
3320
365
APAL-207500-c-0
05
3140
3150
366
2 poles
05, 06
2975
2980
367
368
Size 280 S
as per IEC
05, 06
2820
05, 06
2680
369
2520
Motor
Motor
Suitable for:
425
4 poles
06, 07
2230
426
427
Size 315 S
as per IEC
07
2110
1980
1890
1770
428
429
430
2650
423
395
05, 06
2490
424
396
2 poles
05, 06
2360
2820
397
398
Size 280M
as per IEC
06
2670
06
06
2520
399
06, 07
370
06
2380
400
06, 07
2380
371
06
2250
401
2250
372
06
2110
402
1990
Code
suffix
r/m
bbb
dd =
3130
450
06
2970
451
2790
452
2630
453
2490
2350
2250
456
2100
457
07
1980
458
07
1890
459
07
Motor
Suitable for:
06
APAL-413200-c-0
06, 07
06
454
4 poles
06, 07
455
Size 315M
as per IEC
07
07
07
403
1880
404
4 poles
07
1780
405
406
Size 280M
as per IEC
07
1670
07
07
06
06, 07
05
06, 07
Suitable for:
APAL-411000-c-0
APAL-209000-c-0
APAL-409000-c-0
Motor
06, 07
07
07
07
07
Page 17
A dia.
C dia.
C dia.
B holes 5 dia.
+ 10
130 - 10
Size
bbb
010
012
016
125
160
200
3
3
3
020
025
031
040
250
315
400
500
3
4
4
4
Lubricator HDCZ-15
ia.
ia.
Ed
D dia.
n x G dia.
010
50 - 70
150
125
130
012
50 - 70
150
016
50 - 70
150
160
165
200
205
020
50 - 70
150
250
255
255
292
330
12
37,5
025
031
80 - 100
200
315
320
320
366
405
12
80 - 100
200
400
405
405
448
490
12
040
80 - 100
200
500
505
505
551
600
12
o/s duct
C
i/s flex. duct
42,5
42,5
12
47,5
12
Page 18
Sound data
Total sound power level Lwtoto, dB, to connecting duct,
when the fan operates on the throttling curve, which gives
rise to the lowest sound power.
110
100
LWtoto,dB
000
30
=
ise
000
re r
20
ssu
l pr
a
Tot
10
10
L = Throttling curve
20 x 103
Pa
-5
K2,dB
K1,dB
120
0.2
Correction K2
for different sound paths
Correction K1
for different throttling
curves and sound paths
000
00
50
00
30
90
1.5
L
2.5
-10
-15
-20
10 000
20 000
30 000
Total pressure rise, Pa
80
0.05
0.1
0.2
Air flow, m3/s
0.5
Lwtot = Lwtoto + K1 + K2
Lw = Lwtot + Kok
1200-3000
3000-6000
-7
-9
-6
-9
-7
-6
-8
-6
-13
-10
-17
-14
-23
-20
1200-3000
3000-6000
-4
-7
-6
-7
-9
-7
-13
-7
-13
-11
-17
-16
-21
-21
Note!
Sound data
Sound levels are stated as sound power levels (ref. 10 - 12 W). The sound power level for each octave band shows the sound levels
produced by the fan irrespective of the acoustic properties of its surroundings. This sound level is the correct basis for sound level calculations.
Some fan manufacturers still quote sound pressure levels even though these depend on the distance from the fan and the acoustic
properties of the surroundings. Sound pressure levels, sometimes weighted as dB(A) or dB(C) values, are considerably lower than the
corresponding sound power levels, Lwt. For example, at a distance of 3 m, the dB(A) value for a free inlet fan with hemispherical
sound propagation is 17 - 25 dB lower (depending on fan speed and blade type) than the total sound power level.
Electric motors
Page 19
This catalogue section relates to 50 Hz, totally enclosed, foot-mounted, three-phase squirrel cage motors. Motors from size
200 upwards are supplied with thermistor type temperature sensors as standard (see the next page). Quotations for other
sizes with temperature sensors are provided on request.
Casing classes and insulation class, see page 20.
In all cases where fans and fan drives are presented with a specific
motor, this motor is rated for direct on-line starting. If a different motor
is selected, or if star-delta starting is employed, starting times must
be checked by calculation.
Use the following formulae to calculate the starting time for direct online and star-delta starting:
Direct on-line starting t =
Star-delta starting
t=
J x nf2 x 10-3
T
T
46 P MAX + S
TN
TN
J
46 P 1
3
x nf2 x
TMAX
TN
x Pf
Symbols
- Pf
-3
10
T
+ 1x S
4 TN
Pf
- Pf
kW
kW
TS
TN
TMAX
= Ratio of maximum motor torque to normal torque
TN
nf
rpm
No. of poles
Starting method
132
15
45
10
30
= Starting time
160
15
45
15
45
180
15
45
15
45
200
15
45
15
45
Motor
225
15
45
15
45
250
15
45
15
45
280
15
45
18
54
315
18
54
355
20
60
Motor size
Ordering key
Voltage
1 = 220 - 240 V delta/380 - 420 V star
2 = 380 - 420 V delta/660 - 690 V star
5 = 500 V star (sizes 63 - 100)
500 V delta (sizes 112 - 355)
APAL-a-bbbbb-c-0
Electric motors
Page 20
Single-speed motors, 50 Hz
Size designation
ABB
Motors
IEC
Storleksbeteckning
At rated output
Designation
Rated
output
kW
Speed
rpm
Approx
A at
400 V 1)
Is2)
Ts
Tmax
IN
TN
TN
Wgt.
IEC
ABB
Motors
APALM2AA 132 SA
M2AA 132 SB
M2AA 160 MA
2-00550-c-0
2-00750-c-0
2-01100-c-0
5,5
7,5
11
2855
2855
2930
10,5
13,9
20,0
7,8
8,5
6,3
3,2
3,4
1,9
3,4
3,6
2,5
37
42
73
160 M
160 L
180 M
M2AA 160 M
M2AA 160 L
M2AA 180 M
2-01500-c-0
2-01850-c-0
2-02200-c-0
15
18,5
22
2920
2920
2930
26,5
32,0
38,5
6,6
7,3
7,2
2,3
2,6
2,5
2,5
2,7
2,7
84
94
119
200
200
225
250
M2AA
M2AA
M2AA
M2AA
MLA
MLB
SMB
SMA
2-03000-c-0
2-03700-c-0
2-04500-c-0
2-05500-c-0
30
37
45
55
2955
2950
2960
2970
53
64
79
95
7,3
7,3
7,3
7,5
2,4
2,5
2,5
2,0
3,1
3,2
2,8
3,0
175
200
235
285
M2CA 280 SA
M2CA 280 SMA
2-07500-c-0
2-09000-c-0
75
90
2977
2975
131
152
7,4
7,2
2,0
2,1
2,9
2,7
480
545
280 S
280 M
Vid mrkuteffekt
Varvtal
r/min
Strm 1)
vid 400V
ca A
Is2)
Ts
Tmax
IN
TN
TN
Vikt
kg
132 S
132 S
160 M
200
200
225
250
Mrkuteffekt
kW
kg
L
L
M
M
Beteckning
132 M
M2AA 132 M
APAL4-00750-c-0
7,5
1450
14,8
7,9
2,5
3,2
48
160 M
160 L
180 M
M2AA 160 M
M2AA 160 L
M2AA 180 M
4-01100-c-0
4-01500-c-0
4-01850-c-0
11
15
18,5
1460
1455
1470
22,5
28,5
35
6,7
6,8
7,0
2,9
3,0
3,1
2,8
2,8
2,7
75
94
124
180 L
M2AA 180 L
4-02200-c-0
22
1470
41
7,0
2,9
2,8
141
200 L
225 S
225 M
4-03000-c-0
4-03700-c-0
4-04500-c-0
30
37
45
1475
1480
1480
56
68
83
6,7
6,6
6,7
2,6
2,4
2,7
2,8
2,5
2,6
180
215
230
250 M
4-05500-c-0
55
1480
98
7,5
2,3
2,8
275
280 S
280 M
M2CA 280 SA
M2CA 280 SMA
4-07500-c-0
4-09000-c-0
75
90
1483
1484
137
163
6,9
7,6
2,2
2,5
2,8
2,9
445
490
315 S
315 M
315 M
M2CA 315 SA
M2CA 315 SMA
M2CA 315 MB
4-11000-c-0
4-13200-c-0
4-16000-c-0
110
132
160
1487
1486
1486
198
238
282
6,5
6,3
7,0
2,1
2,2
2,4
2,6
2,7
2,7
675
730
850
355 S
355 M
M2CA 355 SA
M2CA 355 MA
4-20000-c-0
4-25000-c-0
200
250
1487
1487
345
430
7,0
7,2
2,1
2,3
2,7
2,8
1220
1350
355 M
M2CA 355 LA
4-31500-c-0
315
1488
545
7,4
2,4
2,8
1550
Voltage codes
1 = 220 - 240 V delta/380 - 420 V star, 50 Hz
2 = 380 - 420 V delta/660 - 680 V star, 50 Hz
5 = 500 V star (sizes 63 - 100)
500 V delta (sizes 112 - 355)
1) Conversion factor where the rated supply is other than 400 V, 50 Hz.
Rated voltage at 50 Hz
and a motor wound for:
2) Is
IN
Conversion factor
220 V
230 V
415 V
1.82
1.74
0.96
500 V
660 V
690 V
0.80
0.61
0.58
Housing class IP 55
Dust-proof, spray-proof design. Sizes 132 - 355 are supplied as standard in a
design complying to IP 55.
Drain holes
Sizes 132 - 355 are supplied with closeable, plastic plugs in the drain holes.
The plugs are in the open position when the motors are delivered.
Insulation class
All motors have class F insulation.
The standard rated outputs of motors from ABB Motors are, in most cases,
based on the temperature increases applying to insulation class B.
This gives the motors a large overload margin.
Temperature sensor
PTC thermistor type 3 x 150 C. Standard for sizes 200 and larger.
Electric motors
Page 21
AC
L1, L2
HD
HD
AC
H
K
B
B'
BB
BC
A
AB
L
B'
BB
A
AB
HD
HD
HC
H
H
E
B
B'
BB
A
AB
B
B'
BB
L
A
AB
Shaft journal
F
GA
DB
D
Size
per
ABB Motors
No. of
poles
A1)
AB
AC
B1)
B'1)
BB
D1)
DB
EA
F1)
GA
H1)
HC
HD
L12)
132 S (A, B)
132 M
2
4
216
216
262
262
261
261
140
1403)
1783)
178
212
212
89
89
38
38
M12
M12
80
80
50
50
10
10
41
41
132
132
295.5
295.5
12
12
4473)
4473)
160
180
4)
4)
5)
5)
254
279
310
340
210
241
2543)
2793)
287.5
316
108
121
42
48
M16
M16
110
110
12
14
45
51.5
160
180
368.5
403,5
15
15
602,5
680
200 ML.
225 SM.
225 SM.
2,4
2
4
318
356
356
380
418
418
386
425
425
2673)
2863)
286
305
311
3113)
365
360
360
133
149
149
55
55
60
M20
M20
M20
110
110
140
16
16
18
59
59
64
200
225
225
496,5
542
542
18
18
18
773
835
865
250 SM.
250 SM.
2
4
406
406
474
474
471
471
3113)
3113)
349
349
409
409
168
168
60
65
M20
M20
140
140
18
18
64
69
250
250
590
590
22
22
872
872
280 SA
280 SA
2
4
457
457
545
545
368
368
450
450
190
190
65
75
M20
M20
140
140
18
20
69
79.5
280
280
558
558
730
730
24
24
1060
990
280 SMA
280 SMA
2
4
457
457
545
545
368
368
419
419
501
501
190
190
65
75
M20
M20
140
140
18
20
69
79.5
280
280
558
558
730
730
24
24
1060
1060
315 SA
508
622
406
535
216
80
M20
170
22
85
315
627
820
28
1125
315 SMA
508
622
406
457
535
216
80
M20
170
22
85
315
627
820
28
1125
315 MB
508
622
457
540
216
80
M20
170
22
85
315
627
820
28
1225
355 SA
610
714
500
584
254
100
M24
210
28
106
355
715
920
28
1380
355 MA
610
714
560
644
254
100
M24
210
28
106
355
715
920
28
1440
355 MB
610
714
560
644
254
100
M24
210
28
106
355
715
920
28
1440
355 LA
610
714
630
714
254
100
M24
210
28
106
355
715
920
28
1520
1) Tolerances
A, B
D = 38-48
D = 55-100
F
H = 132-250
H = 280-355
ISO js14
ISO k6
ISO m6
ISO h9
+0 -0.5
+0 -1.0
2)
3)
4)
5)
Page 22
= fan speed
rpm
kW
pa = absolute pressure
Pe = actual power demand
Pa
kW
= absolute temperature
= gas density
= fan efficiency
Pa
Pa
m /s (m /h)
3
K
m/s
kg/m
Principle of operation
Flow through a fan is characterised by an increase in total gas
pressure as energy is imparted to the gas as it crosses the
impeller. The velocity increase at the fan inlet translates into a
definite rise in dynamic pressure, partnered by an equal magnitude
decrease in static pressure. The increase in total pressure
occurs only at the fan impeller; in the scroll casing, the dynamic
pressure is converted into static pressure. The gas flow and the
outlet area determine the dynamic pressure of the gas at the
outlet. The total pressure delivered at the fan outlet thus always
includes a certain component of dynamic pressure. Because of
the relatively large outlet areas, the dynamic pressures for
HDCB/HDCS fans are relatively low.
Fan data
The fan chart
Fan data is usually shown in the form of a chart. In this chart, the
total pressure rise generated by the fan is plotted as a function of
the gas flow at a number of fixed fan speeds. The corresponding
power characteristics are usually shown in the same chart.
This also includes auxiliary curves (throttling curves) numbered
from 1 to 10. These represent different system characteristics,
for which the required pressure rise is proportional to the square of the gas flow.
Throttling curve number is derived as follows:
10
pd/Dpt
2.5 x
4 outlet area
p
h= P
Pe
100%
P=
q x Dpt
kW,
1000
r = ro
To
T
pa
pao
q = qo
T
To
pao
pa
ro
or q = qo x r
1.2
Dptchart = r
Dpt
The fan speed and power demand Pe chart can then be read
from the chart. Finally, actual power demand is obtained using
the formula:
r
Pe =
1.2
Pechart
q1 n1
q2 = n2
Dpt1
n1
= n
Dpt2
2
P1 n1
=
P2 n2
1.293 x
0.4 x
1.2
0.99
273
273+40
1,293
0,99
20000
101300-12000
10130
= 0.99 kg/m
= 0.52 m/s
~ 24000 Pa
Select HDCB-012. From the chart, fan speed and power demand Pechart are ~ 5350 rpm and 18.0 kW respectively.
Finally, actual power demand is calculated using the formula: Pe = 0.99 x 18 =14.8 kW
1.2
Taking belt losses (5%) into account, select motor size 18.5 kW and belt drive HDCZ-01-173-c-02.
Page 23
Solutions for all your air climate and air movement needs
Flkt Woods is providing solutions for ventilation and air climate for buildings as
well as fan solutions for Industry and Infrastructure.
Fans
Chilled Beams
Active induction beams for ventilation,
cooling and heating, and passive
convection beams for cooling. For
suspended or flush-mounted ceiling
installation and multi-service config uration. With unique Comfort Control
and Flow Pattern Control features.
Residential ventilation
GB 2010.05-2142
Energy recovery
Flkt Woods AB
Chillers
Air-cooled and water-cooled chillers
with cooling capacity up to 1800kW.
Designed to minimised annual energy
consumption in all types of buildings.
Acoustical products