Вы находитесь на странице: 1из 12

SIZING GROUNDING TRANSFORMERS AND RESISTORS

1.0
2.0
3.0
4.0
5.0
6.0
7.0

TABLE OF CONTENTS
PURPOSE & SCOPE..........................................................................................................................
DEFINITIONS....................................................................................................................................
APPLICABILITY................................................................................................................................
RESPONSIBILITIES..........................................................................................................................
PROCEDURE / REQUIREMENTS...................................................................................................
REFERENCES..................................................................................................................................
ATTACHMENTS..............................................................................................................................

1.0 PURPOSE & SCOPE


This procedure outlines the method to be followed for preparation of the Generator
Neutral Grounding and Transformer Neutral Grounding and Resistor Sizing and is
intended to assure uniformity of all such systems.
This procedure depicts grounding schemes as well as sizing of grounding equipment
for the following electrical systems and equipment:
Main Generator,
Main Transformer,
Unit Auxiliary Transformer, Startup Transformer,
Low-Voltage Load Center Transformer,
Diesel Generator (if provided),
AC and DC UPS systems

2.0 DEFINITIONS
Generator Neutral GroundingThe purposes of generator neutral grounding through
an impedance are to limit the damage at the point of fault, limit transient overvoltages and provide a sensitive means of detection for insulation deterioration.
There are two acceptable methods of grounding unit connected generators; resistor
grounding and resonant (reactor) grounding.Resistance GroundingA resistance
grounded system uses a resistor in the neutral-to-ground circuit to limit the maximum
value of short circuit current during a line to ground fault limiting the current and
reducing the extent of damage to equipment caused by the heating and mechanical
stresses generated by the short circuit currentsLow Resistance GroundingIn a low
resistance grounded system the value of resistance is usually selected so that the
ground fault current is large enough to trip protective devices selectively, yet low
enough to limit damage to equipmentHigh Resistance GroundingIn a high resistance
grounded system the value of resistance is selected so that it is of sufficient value to
limit fault currents to very low values, usually equal to the total charging current of
the systemResonant (Reactor) GroundingThis grounding scheme is similar to
resistance grounding except the resistor is replaced with a reactor equivalent to the
system charging current to form a tuned (resonant) circuit.
3.0 APPLICABILITY
This procedure is applicable to all projects.
4.0 RESPONSIBILITIES
4.1 Lead Electrical Engineer
The Lead Electrical Engineer is responsible for sizing the grounding transformers and
resistors.
5.0 PROCEDURE / REQUIREMENTS
5.1 Equipment Grounding Requirements
5.1.1
Main Generator
Main generator shall always be high resistance grounded.
5.1.2
Main Transformer
Main transformer for the generating plant shall always be solidly grounded at the high
side. Low side connected to the generator is always delta connected. No special
equipment is required for high side grounding.
5.1.3
Unit Auxiliary Transformer
Unit auxiliary transformer connected to the generator leads shall always have the high
side delta connected. Low side of this transformer is generally wye connected and
shall be low resistance grounded allowing a maximum of 1000A ground fault current.
Grounding resistor directly connected to the neutral shall have a minimum of 10-sec
rating. Low resistance grounding shall always be used unless specifically required by
the client.
Cases, where low side of this transformer is also delta connected, due to phasing,
grounding bank of T-type or zig-zag type with a resistor allowing a 1000A maximum
ground fault shall be used. Rating of the grounding equipment shall of a minimum of
10 sec.
When the contract requires a different method, a calculation similar to Attachment 7.2
shall be performed.
5.1.4
Startup Transformer

Startup transformer, when used, may have either delta or wye connection for high or
low side winding. For high side, wye connection, neutral shall be solidly grounded.
For low side wye connection, neutral shall be low resistance grounded. For low side
delta, grounding bank of T-type or zig-zag transformers with a resistor allowing a
1000A maximum ground fault current. Rating of this equipment shall of a minimum
of 10 sec.
5.1.5
Load Center Transformer
Transformer feeding low voltage load center shall be delta/wye-solidly grounded,
neutral, unless specifically required by the client to be different.
5.1.6
Diesel Generators
Diesel generators, when provided shall be low resistance grounded at the medium
voltage and solidly grounded at low voltage distribution. Low resistance grounding
shall allow a maximum of 1000A ground fault current. Grounding resistor directly
connected to the neutral shall have a minimum of 10 sec rating.
5.2 Generator Neutral Grounding Calculation Method
Attachment 7.1 provides a recent project calculation for sizing the generator and
transformer grounding transformer.
The following consideration must be analyzed when recommending and selecting a
method of Generator Grounding.
1) The damage at the point of fault is greatly reduced when the unit is resonant
grounded as compared to resistor grounded.
2) Surges on the high voltage system will not appear between generator neutral and
ground because of the wye-delta transformation of the main transformer.
3) Transient overvoltages on the unfaulted phases are limited by resonant
grounding. Arcing or current surges are reduced by resonant grounding. This
precludes the possibility of transient overvoltages due to arcing grounds.
4) The appearance of zero sequence voltage on the transmission system for a line to
ground fault impresses a transient voltage on the generator system. This voltage
is a function of the capacitive coupling reactance in the unit step-up transformer
and the zero sequence impedance of the generator system. The transient voltage
on the generator system (phase to ground EO) will be higher in magnitude with
resonant grounding than with resistor grounding. This voltage must be controlled
within acceptable limits by the proper selection of the coil constant of the reactor.
5) Resonant grounding provides increased sensitivity for detection of insulation
deterioration at any location in the generator system and neutral connected
apparatus.
6) When resistance grounding is used, there is a dead zone where faults cannot be
detected. This dead zone is a circle at the system neutral concentric with all zero
sequence fault voltages. By using the resonant grounding, this dead zone can be
offset by introducing a voltage to displace the system neutral.
This procedure summarizes the required data and the calculations that must be
performed to specify the distribution transformer, reactor or resistor ratings.
5.3 Required Data
5.3.1
GENERATOR:
phase

MVA, three

Eg
Cg
E30g
Eog

5.3.2

= Phase to phase voltage


V
= Single phase to ground capacitance
mmf
= Zero sequence normal third harmonic voltage
V
= Zero sequence normal fundamental frequency voltage
V

=
=
=
=

MAIN TRANSFORMERS:
phase

MVA, three

Nm
= Number of transformers
Cm
=
phase to ground capacitance (gen. side)
mmf
Ct
= High to low side winding per phase capacitance
mmf
EHO = High side zero sequence voltage for a fault on the high side
of the transformer
V

5.3.3

UNIT STATION SERVICE TRANSFORMER:

Nu

Cu

= Single phase to ground capacitance (gen. side)


mmf

5.3.4
Cb

5.3.5

Number of unit station service transformers

=
Single
=
=
=

MVA, three phase


=
=

ISOLATED PHASE BUS:


= Total single phase to ground capacitance
mmf

SURGE CAPACITORS:

Cs
mmf

Single phase to ground capacitance (gen. side)

Em
V

Maximum acceptable voltage the system equipment can take without damage =

5.4 Calculations For Resonant Grounding


Eg
= 3

Ege

= Generator phase to neutral voltage


V

= Total system capacitance = 3. (Cg+NmCm+NuCu+Cb+Cs)


mmf

1
= Total system capacitive reactance = C

Xc

1012
or 2 f C

ohms

Ege

1
Xc

Ic

= System capacitive fault current =


amps

XL

= Effective inductive reactance for resonant ground = Xc


ohms

ELP = Distribution transformer primary voltage Ege


V available

ELS = Distribution transformer secondary voltage


120/240 V

TR
KVA

-3
Continuous distribution transformer rating = Ic Ege 10

If no delay is intended for the unit trip, this rating can be reduced by
the factors from the following table:
TIME
1 Minute
5 Minutes
30 Minutes
1 Hour
2 Hours
Xct

FACTOR
0.212
0.357
0.55
0.625
0.714

Capacitive coupling reactance between high and low side of

1012
2 f C t
the main transformer =

ohms
LS

= Assumed total losses for the reactor


5%

Effective zero sequence resistance in the generator


neutral for this loss =

3 XL

100
LS

ohms
K.Eog =

Neutral voltage displacement due to generator's

100
Eog
fundamental zero sequence voltage = LS

V
ER

Neutral displacement due to fault on the high side

EHO R
R j X ct
of the main transformer =

Phase to ground voltage for a ground fault on the high


of the main transformer = Ege + KEog + ER

V
E

=
V

If E calculated above is more than the maximum acceptable voltage


(E M) increase the reactor losses (LS) to a higher value and
recalculate R, KEog and ER
XLS

Reactance in the secondary of the distribution transformer

XL

E LS 2
E LP 2

ohms
RLS

Resistance in the secondary of the distribution transformer

X LS

LS
100

ohms
KL

Coil constant = 100


LS

Ic
Is

= Secondary current =
amps

ELP
ELS

E ge
Vs

= Secondary voltage =
V

E LS
E LP

XLSKVA = Reactors KVA =


KVA
rF
= Fault resistance
ohms

Is . Vs .10-3

=
=

E ge
IFO

= Zero sequence fault current =


amps

IF

= Fault current = 3 . IFO


amps

Eao

R 3 rF

=
=

Percentage neutral voltage displacement (Relay Sensitivity)


=

I FO R 100
Ege

amps
wF

= Energy into the fault = IF2 . rF


watts

Changing the value of fault resistance from zero upward in reasonable


steps, calculate and plot wF and Eao against resistance.

5.4.1

180 Hz, No Fault Or Normal Conditions

Using the above distribution transformer with percentage reactance (X) equal to impedance
(Z)
=%

Xe
ohms

3 Z 10 2 ELP
TR 103
= Primary reactance =

XL3 =
ohms

Third harmonic reactance in the generator neutral 3 XL

=
=

(Including distribution transformer reactance)

E30 g
j 3 X L 3 3 RL j X c
= Third harmonic zero sequence current =

I30p
amps

I 30 p
I30s
=
amps

Reactor current =

ELP
ELS

V30s

Third harmonic normal voltage across the reactor

= I30s
V

3 (RL + jXL3 = jXe)

5.5 Calculations For Resistor Grounding


Eg
3

Ege

= Generator phase to neutral voltage =


V

= Total system capacitance = 3(Cg + NmCm + NuCu + Cb + Cs)


mmf

Xc

1
1012

wc 2 f c
= Total system capacitive resistance =

ohms

E ge

1
Xc

Ic

= System capacitive fault current =


amps

Ireq

= Assuming neutral current (Minimum 5 amps) = Ic


amps

Req

= Equivalent resistance in the generator neutral =


ohms

Ep

= Distribution transformer primary voltage Ege


Vavailable

TR

E ge
I req

Continuous distribution transformer rating


= Ireq . Ege . 10-3

=
=

KVA
If no delay is intended for the unit trip, this rating can be reduced by
the factors given under resonant grounding.
Es = Distribution transformer secondary voltage
120/240 V

Req
Rs = Grounding resistor in the secondary =
ohms

Vs = Maximum secondary voltage =


V

I req
Is

= Secondary current =
amps

RsKVA =
KV
rF

Es

Es
E ge
Ep

Ep
Es

Grounding resistors KVA = Is . Vs . 10-3

Fault resistance
ohms

3 rF 3

E ge
Req j X x

j Xc

IFO

= Zero sequence fault current =


amps

IF

= Fault current = 3 . IFO


amps

WF

= Energy into the fault = IF2 . rF


watts

eq

I FO 3

R j X
R j X 100
eq

eq

Eao

= Percentage neutral voltage displacement =


%

E ge

Changing the value of fault resistance from zero upward in reasonable


steps,
calculate and plot WF and Eao against fault resistance.
%

5.5.1

180 Hz, No Fault, or Normal Condition:

Using the above distribution transformer with percentage reactance (X) equal to impedance
(Z)

3 Z 10 2 E p
Xe

= Primary reactance =
ohms

TR 103

E30 g

I30p

= Third harmonic zero sequence current =


amps

I 30 p
I30s

= Ground resistor currents =


amps

V30s

= Ground resistor normal voltage =


V

3 Req j X e j X c

Ep
Es

I 30 s 3 Rs

5.6 Required Calculation Inputs


The following is a summary of the required inputs to the calculation to satisfy this
procedure:
1) Contract grounding requirements of medium-voltage and low-voltage auxiliary
system.
2) Unit auxiliary, startup and load center transformer connections.
3) Capacitance to ground for:
Generator
Surge arrester (if applied between generator and transformer)
Generator step-up and unit auxiliary transformers
Isolated Phase Bus Duct
5.7 Required Calculation Outputs
The following is a summary of the required outputs to the calculation provided by this
procedure:
1) Generator Neutral Grounding Calculation and Equipment Rating.
2) Medium-Voltage Neutral Grounding Equipment Rating.

6.0 REFERENCES
6.1
EPRI Power Plant Electrical Reference Series, Volume 8, Station Protection.
7.0 ATTACHMENTS
7.1
Sample Project Calculation- Generator and Transformer Grounding Equipment
Ratings (pdf)
7.2
Sample Project Calculation- Neutral Grounding Transformer and Resistor Sizing
Calculation4 kV Auxiliary distribution System (zip)

Вам также может понравиться