EGGER CONSTRUCTION
Wood based panels for use
in timber construction
www.egger.com
03
04
1. Plaster boards
2. Insulated service cavity
1
4. Cellulose insulation
5. EGGER DHF 15 mm
6. Vertical lathing
7. Weatherboarding
1. Plaster boards
benefits on a view
3. Cellulose insulation
4. EGGER DFF 30 mm
5. Horizontal lathing
6. Larch wood planking
benefits on a view
easy handling
improved noise control
05
note
4
5
8. Resilient channel
5
4
benefits on a view
At a centre-to-centre span greater
than 62.5 cm (i.e. reconstruction of
old buildings) for a fire resistance of
30 minutes EUROSTRAND
OSB 4 TOP, 30 mm, T&G2, size
3000 1250 mm is recommended.
06
9
8
5. Counter lathing
6. Cross joists
6
1
7. Roofing tiles
2
3
benefits on a view
8
7
1
6
5
4
5. Sarking membrane
1.60 m
6. Counter lathing
7. Cross joists
8. Roofing tiles
2
3
07
08
SPECIAL APPLICATIONS
1
3
6
8
09
10
note
In the context of the permission was regulated:
Design values for fasteners like screws, staples, and nails.
That enables to design the distribution of loads directly into
the EUROSTRAND OSB 4 TOP panels.
Structural glueing of the unsanded panels at edge and surface
with approved PU glue from the Purbond HB product range
(type HB 110, 440, 530)
sErviCE Class
According to ENV 1995-1-1 (EC5) EUROSTRAND OSB 3 E0,
OSB 4 TOP can be used in service class 1 (dry conditions) and 2
(humid conditions), and EUROSTRAND OSB/2 in service class 1.
tonguE and groovE profilE
The asymmetrical, conical tongue and groove profile of the
board and cladding panel guarantees exact and rapid construction
of floors, roofs and walls and the required stress transfer on
braced (diaphragm action) board connections. In addition, it
also improves the windproofness of the construction.
Our plant in Wismar, Germany has been certified in accordance
with ISO 9001 since 2001.
11
Test standard
Unit
EUROSTRAND OSB 3 E0
ISO 12572
300/200
200/200
Thermal conductivity R
EN 13986
W/mK
0.13
0.13
DIN 4102-1
B2
B2
EN 13986
(9mm) D-s2, d0
D-s2, d0
Burning rate 0, , t
EN 1995-1-2
mm/min
0.9
0.9
EN 318
%/%
0.03
0.03
Density
EN 323
kg/m3
600
600
Thickness swelling 24 h
EN 317
15
8-10 mm 12 / >10-40 mm 10
EN 12524
J/kgK
1700
1700
Formaldehyde emission
EN 120
mg/100g atro
<2.0 (E1<0.03ppm)
Thickness [mm]
t nom
Bending
Tension
fm
Compression
Panel shear
Planar shear
fc
fv
fr
ft
0 )
90 )
90
90
810
18.0
9.0
9.9
7.2
15.9
12.9
6.8
1.0
>10<18
16.4
8.2
9.4
7.0
15.4
12.7
6.8
1.0
1825
14.8
7.4
9.0
6.8
14.8
12.4
6.8
1.0
Thickness [mm]
t nom
Bending
Tension
Compression
Panel shear
Planar shear
Em
Et
Ec
Gv
Gr
90
90
90
810
4930
1980
3800
3000
3800
3000
1080
50
>10<18
4930
1980
3800
3000
3800
3000
1080
50
1825
4930
1980
3800
3000
3800
3000
1080
50
Compression
Panel shear
Planar shear
fc
fv
fr
1) 0major axis
2) 90minor axis
Thickness [mm]
t nom
12
Bending
Tension
fm
ft
90
90
90
810
25
15
12
10
19
16
9.0
1.6
>10<18
25
15
12
10
19
16
9.0
1.6
1825
25
15
12
10
19
16
9.0
1.6
>2530
25
15
12
10
17
15
8.0
1.6
>3040
25
15
10
10
15
14
6.0
1.6
Thickness [mm]
t nom
Tension
Compression
Panel shear
Planar shear
Em
Et
Ec
Gv
Gr
0 )
90 )
90
90
810
7000
3000
4300
3200
4300
3200
1500
160
>10<18
7000
3000
4300
3200
4300
3200
1500
160
1825
7000
3000
4300
3200
4300
3200
1500
160
>2530
7000
3000
4300
3200
4300
3200
1300
140
>3040
6000
3000
4000
3200
4000
3200
1200
140
1) 0major axis
2) 90minor axis
Water drainage
Service class
According to ENV 1995-1-1 (EC5) EGGER DHF can be applied in service classes 1
(dry conditions) and 2 (humid conditions). When used as part-bearing bracing,
constructive measures must be taken to ensure that the material moisture content
of 15% is not exceeded.
Diffusion resistance /S d
Standard
Unit
EGGER DHF
EN 323
kg/m
ISO 12572
-/m
Sd
13mm
11
0.143m
15mm
11
0.165m
Thermal conductivity R
Z-9.1-454
W/mK
0.10
EN 318
%/%
0.04
DIN 4102-1
B2 normal flammability
EN 13986
D-s2, d0
EN 120
mg/100g atro
0.8 (E1<0.03ppm)
EN 12524
J/kgK
1700
Reaction to fire
(Euroclass)
Formaldehyde emission
Specific thermal capacity
13
Thickness [mm]
Bending
Tension
Compression
Panel shear
Planar shear
t nom
fm
ft
fc
fv
fr
1220
19
11.7
9.6
3.4
1.1
Bending
Tension
Compression
Panel shear
Planar shear
t nom
Em
Et
Ec
Gv
Gr
1220
3000
2100
2000
600
100
Thickness [mm]
Thickness [mm]
t nom
fh
1220
18.0
Calculated values for the modification factor kmod and the deformation coefficient kdef,
in accordance with DIN 1052:2004-08, type MBH.LA2 table F1 and F2
k mod
k def
Load duration
class
SC1
SC2
medium
0.6
0.45
short
0.8
0.6
instantaneous
1.1
0.8
SC1
SC2
3.0
4.0
EGGER DFF
VAPOUR PERMEABLE, MOISTURE REGULATING WOOD FIBREBOARDS
DFF was specially designed by EGGER for use as a vapour
permeable light exterior cladding for roof and wall construction.
When used as a sub-roof board all of its advantages become
obvious. Here the board can be used as a second water-bearing
layer. Its useful insulating properties help protect against
summer heat input in the construction and improves the noise
control of the structure. EGGER DFF boards have been tested for
use as impact sound insulation boards under floating
EUROSTRAND OSB boards. Further application examples can
be found in this brochure on page 4/5.
Standard
Unit
Density
EN 1602
kg/m
Value
250270
EN 12086
-/m
3/0.09
EN 12667
W/mk
0.051
EN 12667
W/mk
0.061
Thermal resistance R
EN 12667
mK/W
0.49
EN 12524
J/kgK
1700
DIN 4102-1
B2 normal flammability
EN 13501-1
C-s2, d0
Formaldehyde emission
EN 120
mg/100g atro
The properties and characteristics of EGGER DFF fulfill the requirements of EN 13171:2001.
Thermal insulation products for buildings Factory-made wood-fibre [WF] products and
therefore it bears the CE marking.
14
PROCESSING RECOMMENDATIONS
The following instructions also apply to EUROSTRAND OSB,
EGGER DHF and EGGER DFF. These are essential for correct
use of the boards.
max. 80 cm
15
MoisturE protECtion
EUROSTRAND OSB is characterised by low thickness swelling
and a high degree of dimensional stability (see technical data:
dimensional changes under influence of moisture). When used
as a supporting and bracing element, appropriate measures
should be taken against weathering. According to EN/TS 12872
wood and wood-based materials with the following equilibrium
moistures (see table) are fit for use if installation is carried out
correctly and no impermissible condensation can form.
application
Service class 1, 30 % to 65 %
Dry conditions
4 % to 11 %
Installed dry,
no moisture during usage.
11 % to 17 %
Service class 2, 65 % to 85 %
Humid conditions
disposal
In its delivery condition, wood waste can be used as a material
or for the production of energy. In this case it is classified according
to Appendix III of the Waste Wood Ordinance to (EWC Codes)
030105, 150103 or 170201. According to the waste code, it will be
decided by local waste laws what form the disposal will take.
benefits on a view
reduced edge distances for fasteners
EUROSTRAND OSB 4 TOP edge distance > 4 dn
Optimized timber cross sections
> 5 dn
7 dn
150
7 dn
fastEning
EUROSTRAND OSB can be attached with all fasteners suitable
for chipboard, such as screws, staples and nails. The length of
the nail/screw should be 2.5 board thickness and at least
50 mm. With staples, a minimum wire gauge of 1.53 mm should
be used. Corrosion resistant fasteners, e.g. made from galvanised
or stainless steel, are to be used. Due to the high withdrawal
strength, only flat-head nails with gutter groove, screw nails or
annularly threaded nails should be used (see also DIN 1052-2).
The crosswise orientation of the strands in the EUROSTRAND
OSB creates a secure base for the fastener, even in the outermost board edge. The thick core-layer structure ensures a high
withdrawal strength around the edges.
dn Nail diameter
150
Installation
300
300
17
18
CLADDING/STRUCTURAL SHEATHING
WITH WOOD-BASED PANELS
Installation instructions
Detailed recommendations and basic rules for installation of wood-based materials
for roofs, walls and ceilings can be found in EN/TS 12872.
Edge distances/expansion joint floor/roof, ceiling
The installed wood-based panels must have an extra space of 15mm to the surrounding
construction components. This extra space enables tension free work to be carried out
on the panels as well as ventilation in the case of flooring. Skirtings must be fitted so
that the floor has adequate ventilation. Glued plastic skirtings are not suitable.
Trusses, etc. in the space should be sufficiently exposed. In areas with edge lengths
>10m, expansion joints that are permanently elastic should be arranged.
Wall
In the case of walls with edge lengths >10m expansion joints approx. 1015mm
wide should also be added.
Floor installation
The installation of the wood-based panels is carried out by joining them together
and therefore requires hardly any cutting in the case of floating installation. Cross
joints must not be formed. Panels must be offset by at least 40cm. Tongue and groove
panels can be fitted in the adjacent wall area by simply putting them in at an angle
in the groove. Free floating panel joints parallel to the supports are not permissible
according to Eurocode 5 Timber construction. Overhanging panels must be cut back
to the size of the decking. The frame of the subconstruction should match that of
the available panel sizes in order to minimise cutting. On old floorboards, first check
the old screws, and tighten them if necessary. Cut free any boards that are rubbing
against each other. Be aware of functional adjacent construction.
Board thickness
In the case of floating installations with EUROSTRAND OSB use a board thickness
of 18mm. In the case of high concentrated and individual loads use a board
thickness of at least 25mm.
Subconstruction FOR CERAMIC FLOOR COVERING
The EUROSTRAND OSB boards must have a board thickness of at least 25mm for
floors and 18mm in the case of walls and they must have high bending strength.
The tongue and groove flooring boards must be glued under one another and pushed
into place with force. They are screwed into the substructure (see also fastening
section). Deflection must not exceed e/600. When installing ceramic floors include
permanently elastic expansion joints every 34m.
19
note
If the pitch of the roof is less then 8
further measures should be taken
to ensure rain and water tightness
of the roof covering (i.e. taping the
EGGER DHF/DFF panel joints).
undErlay ClassifiCation
As interlocked underlay (boards with circumferential tongue and groove profile), the
boards are assigned to Class 3 according to the ZVDH guidelines. EGGER DHF and
EGGER DFF can be installed without an additional nail sealing strip under the counterbatten and without taping the tongue and groove joint, even in case of elevated
requirements and with a roof pitch up to 8 less than the regulation pitch. Compliance
with the minimum roof pitch of 16 is mandatory. Openings (for chimneys etc.) and
joints (covings, groins, dormers etc.) must be taped using suitable adhesive tape.
Increased requirements in addition to shortfall of standard roof pitch:
Use of attic, especially as living space
Special construction features, e.g. dormer windows, ridges, complicated roof shapes
Climatic factors, e.g. mountains or coasts
Local requirements, e.g. from building control
additional gluing
A taped underlay must be implemented when the roof pitch is less than the regulation
pitch of 16 by a maximum of 8. All board joints are taped using suitable adhesive
tape. The minimum roof pitch is 10.
transiEnt WEathEring
After installing EGGER DHF and DFF the roof covering/facade should be fitted
immediately. Between March and November the boards can be exposed to natural
weathering for 2 months as a temporary roof. In the winter months, structural
measures must be employed to ensure that the external covering layer of EGGER DHF
cannot freeze, since this would seriously impair the diffusion ability of the external
panelling cladding and potentially lead to moisture damage. In the winter months it
should only be exposed to natural weathering for a maximum of 2 weeks. If EGGER
DHF is used for load-bearing purposes then the moisture protection regulations of the
approval Z-9.1-454 apply and DIN 68800-2, i.e. the fitted boards have to be protected
from natural weathering.
EGGER DHF/DFF
used as rigid underlay
note
During the winter months, icing of
the outer layer of the EGGER DHF
board must be excluded by means
of suitable construction measures,
since this would severely impair the
diffusion characteristics of exterior
sheathing, which may result in
moisture damage.
uninsulatEd CoCk-loft
The roof area of an uninsulated cock-loft and an unconverted attic must also be
ventilated even by using a vapour permeable sub-roofing material. The recommended
ventilation cross-section, derived from the regulations for the ventilation of flat roofs
is 200 cm per running meter at the ridge and the eaves.
DIMENSIONING
note
Wooden structures are designed according to the appropriate National and European
standards. In the medium-term, Eurocode 5 has been introduced as an EU-wide
regulation for the design of wooden constructions. Characteristic values for the
structural design of EUROSTRAND OSB in accordance with Eurocode 5 can be
taken from DIN EN 12369-1 or from the building authorities.
The following assessment tables were created using the regulations for EUROSTRAND
OSB 4 TOP in accordance with approval Z-9.1-566 as well as the rules for the assessment
of wooden constructions in accordance with Eurocode 5.
timber stud
distance a r (cm) *
62.5
83.5
100.0
125.0
h = 2.50 m
h = 2.65 m
h = 2.80 m
10 mm
12 mm
15 mm
10 mm
12 mm
15 mm
10 mm
12 mm
15 mm
1- a r
1.89
2.17
2.71
1.79
2.05
2.57
1.71
1.95
2.44
2- a r
3.18
3.78
4.73
3.08
3.65
4.56
2.95
3.48
4.35
1- a r
3.25
3.77
4.71
3.09
3.58
4.48
2.95
3.41
4.26
3- a r
5.87
7.04
8.80
5.91
6.94
8.67
5.65
6.78
8.47
1- a r
4.34
5.10
6.38
4.24
4.96
6.17
4.05
4.71
5.89
2- a r
6.49
7.79
9.73
6.45
7.64
9.55
6.16
7.39
9.24
1- a r
6.36
7.56
9.45
6.24
7.26
9.11
5.90
6.96
8.70
2- a r
8.80
10.56
13.20
8.86
10.40
13.01
8.47
10.16
12.70
assuMptions
The longitudinal edge of the board runs parallel to the wall studs. There are no
horizontal joints in the area. The nailing is carried out using staples with 1.8 mm wire
gauges with a length of 55 mm and a clearance of 50 mm; N1 = 280 N permissible.
21
2.0/1.0
3.0/3.0
gk
gk
ar (cm)
0.5
1.0
1.5
0.5
1.0
1.5
41.7
12
12
15
15
15
15
50.0
15
15
15
15
18
18
60.0
18
18
18
18
22
22
62.5
18
18
22
22
22
22
70.0
22
22
22
22
22
25
80.0
22
25
25
25
25
25
83.3
25
25
25
25
2*22
2*22
90.0
25
2*22
2*22
2*22
2*22
2*22
100.0
2*22
2*22
2*22
120.0
2*25
2*25
2*25
2.0/1.0
3.0/3.0
gk
gk
ar (cm)
0.5
1.0
1.5
0.5
1.0
1.5
50.0
12
15
15
15
15
15
60.0
15
18
18
18
18
18
62.5
18
18
18
18
18
18
70.0
18
18
22
22
22
22
80.0
22
22
22
22
25
25
83.3
22
22
25
22
25
25
90.0
22
25
25
25
25
30
100.0
25
30
30
30
30
30
120.0
30
40
40
40
40
40
22
2.0/1.0
3.0/3.0
gk
gk
ar (cm)
0.5
1.0
1.5
0.5
1.0
1.5
50.0
12
12
12
15
15
15
60.0
15
15
15
15
18
18
62.5
15
15
15
18
18
18
70.0
18
18
18
18
18
22
80.0
22
22
22
22
22
22
83.3
22
25
25
25
25
25
90.0
22
25
25
25
25
25
100.0
25
25
25
2*22
2*22
2*22
120.0
2*22
2*22
2*22
2*25
2*25
2*25
Pre-dimensioning of 2 single girders, loaded on both sides with EUROSTRAND OSB 4 TOP
2.0/1.0
3.0/3.0
gk
gk
ar (cm)
0.5
1.0
1.5
0.5
1.0
1.5
50.0
12
12
12
12
15
15
60.0
12
15
15
15
15
15
62.5
15
15
15
15
18
18
70.0
15
15
18
18
18
22
80.0
18
18
18
22
22
22
83.3
18
18
22
22
22
22
90.0
18
22
22
22
25
25
100.0
22
22
25
25
25
30
120.0
25
30
30
30
30
30
23
24
note
EggEr dhf
prE-diMEnsioning of Wall panEls
The following design tables are based on one-sided external panelling of the
supporting structure using EGGER DHF. The calculated values for humid conditions
(service class 2) are used. The calculations were carried out in accordance with the
regulations set out in DIN 1052-1:1988-04, 11.4.2, on the testing of tensile force on
the board.
assuMptions
The longitudinal edge of the board runs parallel to the wall studs. There are no
horizontal joints in the area.
The nailing is carried out using clips with 1.53 mm wire gauges with a length of
55 mm and a clearance of 50 mm; N1 = 250 N permissible.
Sheathing thickness d=13mm/15mm (0.51 / 0.59)
f v (kn/a r ) permissible
Wall panels in the height h under horizontal stress
h = 2.50 m
timber stud
distances a r (cm)
h = 2.65 m
h = 2.80 m
13 mm
15 mm
13 mm
15 mm
13 mm
15 mm
62.5*
2- a r
1.46
1.69
1.41
1.63
1.36
1.57
83.5**
3- a r
2.44
2.81
2.43
2.81
1.42
2.79
25
26
stock PROGRAM EUROSTRAND OSB AND EGGER DHF AND DFF/P LANT WISMAR
Board thickness d (mm)
Product/
lengthwidth (mm)
10
11
12
13
15
18
20
22
25
50002500
50001250
30
35
40
29602500
*
30001250
28001250
26501250
**
25001250
T&G 4 unsanded
2500675
25001250
T&G 4 sanded
2500675
T&G 2 unsanded
30001250
3000675
**
6250675
EUROSTRAND OSB 3 E0 EN 300
Straight edge unsanded
*
50002500
50001250
28001250
25001250
**
20702770
*
*
**
*
T&G 4 unsanded
2500675
25001250
T&G 4 sanded
2500675
T&G 2 unsanded
24401205
EUROSTRAND OSB/2 EN 300
Straight edge unsanded
24401220
EGGER DHF underlay boards acc. to Z-9.1-454 /E N 622-5 MDF.RWH
T&G 4 unsanded
25001250
2500675
T&G 2 unsanded
28001250
30001250
EGGER DFF insulating boards acc. to EN 13171
T&G 4 unsanded
2500675
* on request (by load)
** Delivery by request, production as individual customer order 250m (8,829 cubic feet)
EggEr holzwerkstoe
Wismar gmbh & Co. kg
Am Haffeld 1
23970 Wismar
Germany
T +49 3841 301-21260
F +49 3841 301-61260
holzbau@egger.de
www.egger.com
EN_879274_10/10