ACCESSIBILITY REVIEW
REVIEWER
MICHAEL PERCIALI
Dwg No.
A-A2-J0001
C-CX-J0001
At least one accessible route within the boundary of the site A 5'0" walkway with curb cuts is shown on the drawings.
shall be provided from accessible parking to the accessible Construction details for signage, surface, curb ramp,
detectable warnings, etc are needed on the drawings.
building entrance they serve. (ADAAG-4.3)
Accessible parking spaces need to be closest possible to the
Main Entry in the Process building.
8/21/2005
1 of 2
ADAReview.xls
PROCESS BUILDING
ACCESSIBILITY REVIEW
REVIEWER
MICHAEL PERCIALI
Dwg No.
A-A2-J0001
C-CX-J0001
1st Floor Cold Chemicals At least 50% of all public entrances must be accessible (4.1.3- None provided. If accessibility to the lab is required, Entrance
a)
must comply with ADAAG-4.13
Area
Accessible means of egress shall be provided in the same
None provided. If accessibility to the lab is required, Exits must
number as required for exits by local building / life safety
comply with ADAAG 4.13.8 to 4.13.12.
regulations (ADAAG-4.1.3-9)
If emergency warning systems are provided, they shall include None provided. Audible and visual alarms must be provided
both audible alarms and visual alarms complying with 4.28. along emergency egress path and comply with 4.28.2 and
4.28.3
(ADAAG 4.1.3-14)
Accessible Rest Rooms
Toilet Facilities: if are provided, shall comply with ADAAG-4.22
None provided. If accessibility to the lab is required, Rest
and shall be located on the accessible route. (ADAAG-4.1.3Rooms must comply with ADAAG-4.22.
11)
8/21/2005
2 of 2
ADAReview.xls