PROCESS BUILDING

ACCESSIBILITY REVIEW

REVIEWER
MICHAEL PERCIALI

Dwg No.

Subject Areas to Comply

Accessibility requirements per UFAS or ADAAG

Compliance / Disposition / Action

A-A2-J0001

Process Bldg 1st Floor


Accessible path of travel to the Entry door from the accessible parking
Facility Support - Area 04

C-CX-J0001

Site Plot Plan

At least one accessible route within the boundary of the site A 5'0" walkway with curb cuts is shown on the drawings.
shall be provided from accessible parking to the accessible Construction details for signage, surface, curb ramp,
detectable warnings, etc are needed on the drawings.
building entrance they serve. (ADAAG-4.3)
Accessible parking spaces need to be closest possible to the
Main Entry in the Process building.

A-A2-J1st Floor Facility Support


Accessible Entrance, Exits, Corridor to the place of work and Services
0005&0006 Area
Change in level greater than 1/2" shall be accomplished by Curb ramp is needed at Covered Entry R100. Door hardware
means of ramp that complies with 4.7 (ADAAG-4.5)
must comply with ADAAG 4.13.8 to 4.13.12
Accessible means of egress shall be provided in the same Exits D101, D167b, and West Exit door from corridor R105
number as required for exits by local building / life safety must be accessible. Curb ramps are needed, door hardware
must comply with ADAAG 4.13.8 to 4.13.12
regulations (ADAAG-4.1.3-9)
If emergency warning systems are provided, they shall include
Audible and visual alarms must be provided along emergency
both audible alarms and visual alarms complying with 4.28.
egress path and comply with 4.28.2 and 4.28.3
(ADAAG 4.1.3-14)

Accessible Rest Rooms


Toilet Facilities: if are provided, shall comply with ADAAG-4.22
and shall be located on the accessible route. (ADAAG-4.1.311)

Accessible Offices, Lockers, Health, Control Room, Clean clothes.

8/21/2005

1 of 2

ADAReview.xls

PROCESS BUILDING
ACCESSIBILITY REVIEW

REVIEWER
MICHAEL PERCIALI

Dwg No.

Subject Areas to Comply

A-A2-J0001

Process Building 1st Floor


Accessible path of travel to the Entry door from the accessible parking
Cold Chemicals - Area 03
At least one accessible route within the boundary of the site
None provided. If accessibility is required, must comply with
Site Plot Plan
shall be provided from accessible parking to the accessible
ADAAG-4.3 and 4.6
building entrance they serve. (ADAAG-4.3)

C-CX-J0001

Accessibility requirements per UFAS or ADAAG

Compliance / Disposition / Action

Accessible Entrance, Exits, Corridor to the place of work and Services


A-A2-J0005

1st Floor Cold Chemicals At least 50% of all public entrances must be accessible (4.1.3- None provided. If accessibility to the lab is required, Entrance
a)
must comply with ADAAG-4.13
Area
Accessible means of egress shall be provided in the same
None provided. If accessibility to the lab is required, Exits must
number as required for exits by local building / life safety
comply with ADAAG 4.13.8 to 4.13.12.
regulations (ADAAG-4.1.3-9)
If emergency warning systems are provided, they shall include None provided. Audible and visual alarms must be provided
both audible alarms and visual alarms complying with 4.28. along emergency egress path and comply with 4.28.2 and
4.28.3
(ADAAG 4.1.3-14)
Accessible Rest Rooms
Toilet Facilities: if are provided, shall comply with ADAAG-4.22
None provided. If accessibility to the lab is required, Rest
and shall be located on the accessible route. (ADAAG-4.1.3Rooms must comply with ADAAG-4.22.
11)

Accessible Workplaces in the Lab

8/21/2005

2 of 2