Академический Документы
Профессиональный Документы
Культура Документы
Water cooled
applications with
Single Screw
Technology and
HFC 410A
-
PROXIMUS
Contents
What is a refrigerant ................................................................... 3
What makes a good refrigerant .................................................. 5
Peculiarity for HFC 410A ............................................................ 8
Water cooled application with HFC 410A Proximus ............... 12
What is a refrigerant ?
Refrigerants are the working fluids in refrigeration, air-conditioning, and heat pumping
systems. They absorb low-temperature heat energy from one source, for example an airconditioned space, and reject it into another, for example outdoor ambient, usually through
evaporation and condensation respectively.
There are many substances classified as refrigerants by ASHRAE Standard 34, but only
few are used for commercial air conditioning.
The most common refrigerants are the fluorinated hydrocarbons, but numerous other
substances also function well as refrigerant, including many inorganic compound and
hydrocarbons.
Following is quick a rundown of the common refrigerant groups that are either in use or
have been used in the past.
Water, R-718
Most refrigeration processes use either an absorption
cycle or a vapor compression cycle. Commercial
absorption cycles typically use water as the refrigerant
with a salt solution such as Lithium Bromide as the
absorbent. Water is non toxic, non-flammable, abundant
and of course it is a natural refrigerant.
Ammonia, R-717
Ammonia (NH3) is a natural refrigerant and considered to
be one of the most efficient. It is one of the only original
refrigerants still in use today. It is used in vapor
compression
processes,
typically
with
positive
displacement compressors.
Ammonia is mostly used in industrial applications,
although there are many large commercial air
conditioning installations that utilize it as well.
Hydrocarbons
Propane (R-290) and isobutane (R-600a), among other
hydrocarbons, can be used as refrigerants in the vapor
compression process. In Northern Europe, about 35% of
refrigerators are based on hydrocarbons. They can have
low toxicity and good efficiency but they are highly
flammable.
Hydrochlorofluorocarbons (HCFCs)
Hydrochlorofluorocarbons (HCFCs) have been around
almost as long as CFCs. HCFC-22 is the most widely
used refrigerant in the world.
They are used in vapor compression processes will all
types of compressors.
These refrigerants are phased out, as required by the
Montreal Protocol, in many countries. Others countries
(extra EU) also have a phase-out schedule but on an
extended timeline.
Hydrofluorocarbons (HFCs)
Hydrofluorocarbons (HFCs) are relatively new
refrigerants whose prominence arose with the phase out
of CFCs. HFCs have no ozone depletion potential
(ODP=0).
They are used in vapour compression processes with all
types of compressors. The common HFCs are efficient
and classified as A1 (lower toxicity no flame
propagation) in the ASHRAE Standard 34.
Chemical Name
718
717
290
600
22
134a
407C
410A
Water
Ammonia
Propane
Butane
Chlorodifluoromethane
1,1,1,2-tetrafluoromethane
32/125/134a (23%/25%/52)
32/125 (50%/50%)
Chemical
Formula
Safety
Group
ODP
GWP
H2O
NH3
CH3CH2CH3
CH3CH2CH2CH3
CHClF2
CF3CH2F
A1
B2
A3
0
0
0
<1
0
0
A1
A1
A1
A1
0.055
0
0
0
1500
1300
1530
1730
Three key properties of the refrigerant also affect the overall heat transfer capability of the
system. These are viscosity (), specific heat (Cp) and thermal conductivity (k).
The factors are used to calculate Prandtl numbers (Pr= cp/k) which are used in the
design of the heat exchangers. The goal is to work with substances that can carry a lot of
energy (high specific heats) and can transfer the energy easily (high thermal conductivity).
It is also desirable to have low viscosity to enhance turbulence and reduce the work
required to move the fluid .
With these important consideration
taken in consideration, lets see a
quick comparison between HFC
134a,
that
is,
from
a
thermodynamic point of view, one
of the most efficient refrigerant
available on the market, and an
other refrigerant, HFC 410A that at
this time is known only in efficient
split system application.
Fig 2 shows an ideal refrigerant
cycle reported on ( T,s ) diagram for
a water cooled application with
R410A. The cycle parameters are
showed in the following table:
R - 410A
Evaporating Condition
Condensing Condition
Superheat
Subcooling
DP evaporator
DP condenser
Suction piping lenght
Discharge piping lenght
compressor
Fig. 2
3
40
5
5
0,0
0,0
0
0
1
C
C
C
C
bar
bar
m
m
As you can appreciate by the values reported in table, the cycle shown is an ideal
refrigerant cycle (no Entropy increase).
Comparing the same cycles, with the same parameters, for HFC 134a, HFC 407C and
HFC 410A we can found:
HFC 401A, in an ideal refrigerant cycle for a water cooled application, has a COP
almost same of HFC 134a that is the best on the market from a thermodynamic
efficiency point of view ;
Utilizing the same compressor size, with the same swept volume capacity, we can
improve the chiller cooling capacity by more than 200 percent.
This is one of the great advantage of R410A: the extremely high refrigerant effect per
swept volume which can be up to 150% compared to R407C or up to 200% compared to
R134a.
In this way smaller plant and components may be used, allowing more compact units with
smaller footprint be developed in comparison to HFC 134a.
50% 50%
NO
0,2 K
GLIDE
Glide temperature
No glide means much easier refrigerant re-charging in case of refrigerant loss, and no
need to take any particular attention during refrigerant charge.
As very well know, on a chiller working with a refrigerant blend presenting a strong
temperature glide a leakage results in a change of components proportions in the mixture,
because the relative losses of its most volatile components will be disproportionately high.
If a simple standard refilling is adopted, there is no guarantee that the new refrigerant
mixture has the same proportions as it had before the leakage.
For this reason to guarantee the unit performance, it is preferable to remove the remaining
charge, to make the vacuum in the circuit and re-charge it with new refrigerant (necessarily
in liquid state).
Of course only skilled personnel can perform this service activity.
R-407C and R-410A are both zeotrope, however the glide for R-407C is 5 K while the glide
for R-410A is only 0,2 K.
Also the high glide for HFC 407C means that it can be practically used only in DX system
while HFC 410A can be also used in flooded system, without problems.
8
Another strength point of HFC 410A is that heat transfer properties [thermal
conductivity (k)] and transport properties [viscosity ()] are very good for this
refrigerant.
These properties arent the refrigerants
thermodynamic characteristics but are
very important to realize an efficient
system, an efficient chiller from a real
point of view.
All refrigerants, whether in vapor or liquid
form, suffer pressure drop as they flow
through the refrigeration circuit: both in the
piping and in the components themselves
(i.e. a compressor passageway). As the
pressure changes, the temperature of the
refrigerant changes as well, with a
proportion which depends on the
refrigerant; there temperature variations
adversely affect system performance.
Consider the pressure drops in the suction
and discharge lines: starting from the actual pressure (and temperature) in the evaporator
and in the condenser, the pressure drops (and hence temperature changes) will have to
be added to the total lift that the compressor provides. The type of refrigerant used impacts
on the temperature change relative to the pressure change.
A quickly comparison between HFC134a liquid viscosity and HFC410A liquid viscosity can
show that the viscosity for HFC410A is about 40% less than HFC134a viscosity,
consequently the pressure drops described above and their effect on chiller efficiency is
reduced.
This advantage is especially very important for Dry-eXpansion evaporators, where the
refrigerant flows as a mixture liquid-vapour (saturated) and the refrigerant pressure drops
can reach considerable values.
Another important physical parameter to consider for an efficient system is the heat
transfer coefficient in both the evaporator and condenser. Higher is this parameter, higher
is the potential for increased efficiency.
0,09
0,017
0,089
0,0165
0,088
0,016
+ 3,6%
0,086
0,085
0,084
0,081
0,015
0,0145
0,014
0,083
0,082
+ 17,9%
0,0155
[W/(mK)]
[W/(mK)]
0,087
R-134a
R-410A
0,08
0,0135
0,013
R-134a
R-410A
0,0125
As shown in the above figures thermal conductivity for HFC410A, both for saturated
liquid and saturated vapour, is much higher than HFC134a thermal conductivity: for
saturated vapour is 17,9% higher, for saturated liquid is 3,6% higher (at 25 C).
9
Good refrigerant thermal conductivity helps achieve good heat transfer and this allows
close approaches in the heat exchangers. This in turn means smaller lifts for the
compressor and improved efficiency.
Thanks to these good refrigerant characteristics McQuay is able to offer two efficiency line
for PROXIMUS, its water cooled unit equipped with single screw compressor:
XE with a COP up to 5
COP of 5 means fast pay back time for the investment and big savings in the future chiller
operating costs.
6000
5000
4000
kJ / m3
3000
2000
1000
R134a
R410A
Fig. 3
Small footprints and reduced weight obviously facilitate installation and leave more space
for other equipment.
A compact design also helps installation through most standard industrial doorways
without modification, saving introduction time and costs
.
10
LCWT [C]
Tcond [C]
P cond [bar]
35
35
40
38
24,4
23,2
OAT [C]
Tcond [C]
P cond [bar]
35
35
55
65
24,7
28,3
Proximus SE
Proximus XE
McPower SE ST
McPower SE XXN
OAT = Outside Ambient Temperature
As you can appreciate the highest pressure levels (condensing section) are almost the
same. This means that work with HFC 410A in water cooled applications, from a
mechanical point of view, is equivalent to work with HFC 407C in air cooled applications.
Is important take in consideration that also P between suction and discharge compressor
side is almost the same for two refrigerants and it allows the compressor to work with a
volumetric efficiency that is the same, both in the case of R407C and of R410A. This is
because the internal leakage of the compressor, between discharge and suction side, are
equal for both refrigerants.
McQuay has also obtained the full PED (Pressure Equipment Directive) certification for
R410A heat exchangers (both evaporator and condenser); PED certification, established
by the European Community in May 2002, is one of the most restrictive standards on
pressure equipment and requires high safety margins on pressure calculations and tests.
All McQuay heat exchangers are PED approved, another warranty for safety, reliability and
efficient chiller operation.
11
EER
Fig. 4
12
This is possible of course when spring, river, lake water is available to cool the condenser
or when the cooling tower fan control is implemented to supplies the chillers condenser
with the coolest water.
Take in consideration that during all the year the Outside Ambient Temperature (OAT) is
well below 20C for the 65% of the time (this is true in the South-Europe, in the North the
percentage can increases). With this temperature is possible supply to unit an ECWT
below 30 C with a relevant EER increases. (see Fig. 4)
In a chiller supplied with Thermostatic Expansion Valve (TEXV) is not possible to reach
these energetic benefits because the system is obligated to operate with higher
condensation pressure to ensure correct working condition to the lamination device.
McQuay International is the first manufacturer in European HVAC Market to offer a water
cooled chiller working with HFC 410A: an ecological, efficient, safe, easy to manage
refrigerant.
Thanks this HFC is possible to make, and so to offer, a unit with the best compromise
among: efficiency, compactness, reliability and price.
Proximus is the best choice both to make a new HVAC system and to replace an old
existing refrigerator.
13
We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding.
14