Prevention
System for Oil
Filled Transformers
NITROGEN INJECTION
T YPE PNT
BUCHHOLZ RELAY
FIRE DETECTOR
CONTROL
BOX
OPERATING
SIGNALS
FROM
CONTROL
ROOM/
RELAY
PANEL
FIRE
EXTINGUISHING
CUBICLE
TRANSFORMER
N2
NITROGEN
INJECTION
COVERED
OIL PIT
1
1 QUICK
OIL DRAIN VALVE
ASSEMBLY
2 N2 RELEASE
DEVICE
CIVIL WORK
GENERAL
Dedicated system. Proven technology. Over 6000 systems operating worldwide in transformers upto
2500 MVA. Approved by major Electricity boards, Industrial customers, Project consultants, Tariff advisory
committee, Fire Brigade, Oil Industrial Safety Directorate and others. Type PNT is suitable for
transformer rating 2.5 to 315 MVA, three phase. Also single phase 3 X 200 = 600 MVA.
DESCRIPTION
Consists of a fire extinguishing cubicle near the transformer, a control box in the control room, several
fire detectors on the top cover of the transformer, specially designed Transformer Conservator Isolation
Valve between buchholz relay and conservator, signal box placed on transformer. The fire extinguishing
cubicle is connected to the transformer tank by pipes for oil drain and nitrogen injection. Cable
connections are provided from signal box to control box and from control box to fire extinguishing cubicle.
Prevents rupture of the transformer tank and fire due to internal failures. Extinguishes external fire
caused due to transformer tank rupture, fire in bushings, fire in tapchanger or fire from surrounding. Apart
from automatic operation, also operates on remote electrical and local manual controls.
SYSTEM ACTIVATION SIGNALS
For Prevention : Differential relay trip+Rapid pressure rise relay or Buchholz relay or Pressure relief
valve trip+Transformer Isolation
For Extinction : Fire detector operation+Rapid pressure rise relay or Buchholz relay or Pressure relief
valve trip+Transformer Isolation
POWER SUPPLY
For System Operation : 110 / 220 V DC. For lighting and heater for F.E. Cubicle : 230 V AC.
PM FS 1002
OCT 2008
OPERATION
On receipt of required activating signals, a pre-determined
quantity of oil drain commences. Simultaneously Nitrogen is
injected under pressure at a pre-determined flow rate to
create a stirring action thereby bringing the temperature of
top oil surface below ignition point. Fire is extinguished
within 30 seconds maximum. Nitrogen gas occupies the
space created by oil drain and acts as an insulating layer
between the oil in the transformer tank and fire above top
cover. Transformer Conservator Isolation Valve blocks the
passage of oil and isolates
conservator oil thereby
preventing escalation of fire.
ADVANTAGES
Low investment compared to conventional systems.
Very low maintenance and running cost compared to
conventional systems.
NOMENCLATURE
M 50 B 10
1
2
3
4
7
6
5